Daikin EWWQ380B-SS, EWWQC20B-SS, EWWQ420B-XS, EWWQC21B-XS Operation manuals

Installation, Operation and Maintenance Manual
D–EIMWC00504-14EN
Water-cooled screw chillers
EWWQ380B-SS~EWWQC20B-SS EWWQ420B-XS~EWWQC21B-XS
50Hz – Refrigerant: R-410A
Original Instructions
Contents
General information………………………………………………………………………………………………………………….4
Warnings for the operator ................................................................................................................................................. 4
Assistance ........................................................................................................................................................................ 4
Spare parts ....................................................................................................................................................................... 4
Receiving the machine ..................................................................................................................................................... 4
Checks ............................................................................................................................................................................. 5
Purpose of this manual ..................................................................................................................................................... 5
Important information on the refrigerant used ................................................................................................................... 5
NOMENCLATURE ........................................................................................................................................................... 7
Operating limits ............................................................................................................................................................... 17
Storing ............................................................................................................................................................................ 17
Operation ........................................................................................................................................................................ 17
Mechanical Installation ................................................................................................................................................... 18
Shipping ......................................................................................................................................................................... 19
Responsibility ................................................................................................................................................................. 19
Safety ............................................................................................................................................................................. 19
Moving and lifting ........................................................................................................................................................... 19
Positioning and assembly ............................................................................................................................................... 20
Minimum space requirements ........................................................................................................................................ 21
Ventilation ....................................................................................................................................................................... 21
Sound protection ............................................................................................................................................................ 21
Water piping ................................................................................................................................................................... 21
Water treatment .............................................................................................................................................................. 23
Evaporator and exchangers anti-freeze protection ......................................................................................................... 23
Installing the flow switch ................................................................................................................................................. 23
Electrical Installation ...................................................................................................................................................... 37
General specifications .................................................................................................................................................... 37
Electrical components .................................................................................................................................................... 40
Electrical wiring .............................................................................................................................................................. 40
Electrical heaters ............................................................................................................................................................ 40
Water pump control ........................................................................................................................................................ 40
Unit On/Off remote control – Electrical wiring ................................................................................................................. 40
Double Setpoint – Electrical wiring ................................................................................................................................. 40
External water Setpoint reset – Electrical wiring (Optional) ............................................................................................ 40
Unit limitation – Electrical wiring (Optional) .................................................................................................................... 41
Operation ......................................................................................................................................................................... 42
Operator’s responsibilities .............................................................................................................................................. 42
Description of the machine ............................................................................................................................................. 42
Description of the refrigeration cycle .............................................................................................................................. 42
Description of the refrigeration cycle with partial heat recovery...................................................................................... 47
Controlling the partial recovery circuit and installation recommendations ...................................................................... 47
Compression process ..................................................................................................................................................... 48
Pre-startup checks .......................................................................................................................................................... 52
General........................................................................................................................................................................... 52
Units with external water pump ...................................................................................................................................... 53
Electrical power supply ................................................................................................................................................... 53
Unbalance in power supply voltage ................................................................................................................................ 53
Electrical heaters power supply ...................................................................................................................................... 53
Emergency Stop ............................................................................................................................................................. 53
Startup procedure ........................................................................................................................................................... 54
Turning on the machine .................................................................................................................................................. 54
Seasonal shutdown ........................................................................................................................................................ 55
Starting up after seasonal shutdown .............................................................................................................................. 55
System maintenance....................................................................................................................................................... 56
General........................................................................................................................................................................... 56
Compressor maintenance .............................................................................................................................................. 56
Lubrication ...................................................................................................................................................................... 56
Replacement of filter dryer ............................................................................................................................................. 58
Procedure to replace the filter dryer cartridge ................................................................................................................ 59
Replacement of filter dryer ............................................................................................................................................. 59
Procedure to replace the filter dryer cartridge ................................................................................................................ 59
Rplacement of the oil filter .............................................................................................................................................. 60
Fr3200 compressor ............................................................................................................................................. 60
FR4 compressor ................................................................................................................................................. 61
Fr4200 compressor ............................................................................................................................................. 61
Refrigerant charge .......................................................................................................................................................... 62
Procedure to replenish refrigerant .................................................................................................................................. 63
Standard Checks ............................................................................................................................................................. 64
Temperature and pressure sensors ............................................................................................................................... 64
Test sheet ........................................................................................................................................................................ 65
D-EIMWC00504-14EN - 2/68
Water side measurements .............................................................................................................................................. 65
Refrigerant side measurements ..................................................................................................................................... 65
Electrical measurements ................................................................................................................................................ 65
Service and limited warranty .......................................................................................................................................... 66
Obligatory routine checks and starting up apparatuses under pressure .................................................................. 67
Important information regarding the refrigerant used ................................................................................................. 67
List of tables
Table 1 – EWWQ380B-SS~EWWQ730B-SS - Technical Data ........................................................................................... 8
Table 2 – EWWQ800B-SS~EWWQC10B-SS - Technical Data .......................................................................................... 9
Table 3 – EWWQC11B-SS~EWWQC15B - Technical Data ............................................................................................. 10
Table 4 – EWWQC16B-SS~EWWQC20B-SS - Technical Data ....................................................................................... 11
Table 5 – EWWQ420B-XS~EWWQ800B-XS - Technical Data ......................................................................................... 12
Table 6 – EWWQ970B-XS~EWWQC13B-XS - Technical Data ........................................................................................ 13
Table 7 – EWWQC14B-XS~EWWQC19B-XS - Technical Data ....................................................................................... 14
Table 8 – EWWQC20B-XS-EWWQC21B-XS - Technical Data ........................................................................................ 15
Table 9 - Sound levels EWWQ B-SS ................................................................................................................................ 16
Table 10 - Sound levels EWWQ B-XS .............................................................................................................................. 16
Table 11 – Acceptable water quality limits ........................................................................................................................ 23
Table 12 – Electrical data EWWQ B-SS Unit .................................................................................................................... 38
Table 13 – Electrical data EWWQ B-XS Unit .................................................................................................................... 39
Table 14 - Typical operating conditions with compressors at 100% .................................................................................. 54
Table 15 – Routine maintenance programme ................................................................................................................... 58
List of Figures
Fig. 1 – Operating limits .................................................................................................................................................... 18
Fig. 2 - Lifting the unit ....................................................................................................................................................... 20
Fig. 3 – Minimum clearance requirements for machine maintenance ............................................................................... 21
Fig. 4 – Water piping connection for heat recovery exchangers ........................................................................................ 22
Fig. 5 - Adjusting the safety flow switch............................................................................................................................. 24
Fig. 6 – Evaporator pressure drop – EWWQ B-SS ........................................................................................................... 25
Fig. 7 – Evaporator pressure drop – EWWQ B-SS ........................................................................................................... 26
Fig. 8 – Evaporator pressure drop - EWWQ B-XS ............................................................................................................ 27
Fig. 9 – Evaporator pressure drop - EWWQ B-XS ............................................................................................................ 28
Fig. 10 – Condenser pressure drop - EWWQ B-SS .......................................................................................................... 29
Fig. 11 – Condenser pressure drop - EWWQ B-SS .......................................................................................................... 30
Fig. 12 – Condenser pressure drop - EWWQ B-XS .......................................................................................................... 31
Fig. 13 – Condenser pressure drop - EWWQ B-XS .......................................................................................................... 32
Fig. 14 – Partial heat recovery pressure drop - EWWQ B-SS ........................................................................................... 33
Fig. 15 – Partial heat recovery pressure drop - EWWQ B-SS ........................................................................................... 34
Fig. 16 – Partial heat recovery pressure drop - EWWQ B-XS ........................................................................................... 35
Fig. 17 – Partial heat recovery pressure drop - EWWQ B-XS ........................................................................................... 36
Fig. 18 – User connection to the interface terminal board ................................................................................................. 41
Fig. 19 - Refrigeration cycle of the EWWQ B-SS / EWWQ B-XS DUAL Fr4 unit .............................................................. 43
Fig. 20 - Refrigeration cycle of the EWWQ B-SS / EWWQ B-XS Mono Fr4 unit ............................................................... 44
Fig. 21 - Refrigeration cycle of the EWWQ B-SS / EWWQ B-XS DUAL 3200 unit ............................................................ 45
Fig. 22 - Refrigeration cycle of the EWWQ B-SS / EWWQ B-XS Mono 3200 unit ............................................................ 46
Fig. 23 - Picture of Fr4100 compressor ............................................................................................................................. 48
Fig. 24 – Picture of Fr3200 compressor ............................................................................................................................ 48
Fig. 25 - Compression process ......................................................................................................................................... 49
Fig. 26 - Refrigeration capacity control mechanism of compressor Fr3200 – Fr4 ............................................................. 50
Fig. 27 - Capacity control mechanism ............................................................................................................................... 51
Fig. 28 - Installation of control devices for Fr4 compressor ............................................................................................... 57
Fig. 29 - Installation of control devices for Fr3200 compressor ......................................................................................... 57
D–EIMWC00504-14EN - 3/68
General information
IMPORTANT
The units described in the present manual represent a valuable investment. Maximum care should be taken to ensure correct installation and appropriate working conditions of the units. Installation and maintenance must be performed by qualified and specifically trained personnel only. Correct maintenance of the unit is indispensable for its safety and reliability. Manufacturer’s service centres are the only having adequate technical skill for maintenance.
CAUTION
This manual provides information about the features and procedures for the complete series. All units are delivered from factory as complete sets which include wiring diagrams and dimensional drawings with
size, weight and features of each model.
WIRING DIAGRAMS AND DIMENSIONAL DRAWINGS MUST BE CONSIDERED ESSENTIAL DOCUMENTS OF THIS MANUAL
In case of any discrepancy between this manual and the two aforesaid documents, please refer to the wiring diagram and dimensional drawings.
WARNING
Before starting the installation of the unit, please read this manual carefully. Starting up the unit is absolutely forbidden if all instructions contained in this manual are not clear.
Warnings for the operator
READ THIS MAINTENANCE AND USE MANUAL BEFORE USING THE UNIT
THE OPERATOR MUST BE TRAINED AND INSTRUCTED ON HOW TO USE THE UNIT
THE OPERATOR MUST STRICTLY FOLLOW ALL INSTRUCTIONS, SAFETY REGULATIONS AND
LIMITATIONS REGARDING THE USE OF THE UNIT.
Key to symbols
Important note: failure to respect the instruction can damage the unit or compromise functioning
Note regarding safety in general or respect of laws and regulations
Note concerning electrical safety
Safe use and maintenance of the unit, as explained in this Maintenance and Use Manual, is fundamental to prevent any accidents occurring to operators during both operation and maintenance as well as during repair work.
Therefore, it is highly recommended that this document be read carefully, complied with and stored safely.
Assistance
Should additional maintenance be required, it is advisable to consult authorised staff before carrying out any repair work.
Spare parts
Spare parts to be used for maintenance of the unit must be original. Therefore, always consult the manufacturer.
Receiving the machine
The machine must be inspected for any possible damage immediately upon reaching its final place of installation. All components described in the delivery note must be carefully inspected and checked; any damage must be reported to the carrier. Before connecting the machine to earth, check that the model and power supply voltage shown on the nameplate are correct. Responsibility for any damage after acceptance of the machine cannot be attributed to the manufacturer.
D-EIMWC00504-14EN - 4/68
Checks
1
6
2
7
3
8
4
9
5
10
To prevent the possibility of incomplete delivery (missing parts) or transportation damage, please perform the following checks upon receipt of the machine:
a) Before accepting the machine, please verify every single component in the consignment. Check for any damage. b) In the event that the machine has been damaged, do not remove the damaged material. A set of photographs
are helpful in ascertaining responsibility.
c) Immediately report the extent of the damage to the transportation company and request that they inspect the
machine.
d) Immediately report the extent of the damage to the manufacturer representative, so that arrangements can be
made for the required repairs. In no case must the damage be repaired before the machine has been inspected
by the representative of the transportation company.
Purpose of this manual
The purpose of this manual is to allow the installer and the qualified operator to carry out all required operations in order to ensure proper installation and maintenance of the machine, without any risk to people, animals and/or objects. This manual is an important supporting document for qualified personnel but it is not intended to replace such personnel.
All activities must be carried out in compliance with local laws and regulations.
Important information on the refrigerant used
This product contains fluorate gases which have a greenhouse effect and which are covered by the Kyoto protocol. Do not release such gases into the atmosphere. Type of refrigerant: R410A GWP value The quantity of refrigerant used is indicated on the identity plate with the name of the unit. Routine inspections may be necessary pursuant to local and/or European laws, to check on possible refrigerant leakage. For more detailed information, contact your local dealer.
(1)
GWP=Global warming potential
(1)
= 1975
Description of the labels applied to the electrical panel
– Lifting instructions – Unit nameplate data – Non flammable gas symbol – Manufacturer’s logo
– Emergency stop
D–EIMWC00504-14EN - 5/68
Single Compressor unit
– Gas type – Hazardous Voltage warning – Cable tightening warning – Water circuit filling warning
– Electrical hazard symbol
1
– Unit nameplate data
6
2
7
3
8
4
9
5
10
– Lifting instructions – Hazardous Voltage warning – Cable tightening warning
– Water circuit filling warning
Two Compressors Unit
– Non flammable gas symbol – Manufacturer’s logo – Gas type – Electrical hazard symbol
– Emergency stop
D-EIMWC00504-14EN - 6/68
NOMENCLATURE
Machine type
EWA = Air-cooled chiller, cooling only EWY = Air-cooled chiller, heat pump EWL = Remote condenser water chiller ERA = Air-cooled condensing unit EWW = Water cooled packaged water chiller EWC = Air-cooled chiller, cooling only with centrifugal fan EWT = Air-cooled chiller, cooling only with heat recovery
Refrigerant
D: R-134a P: R-407C Q: R-410A
Capacity class in kW (cooling)
Always 3-digit code Idem as previous
Model series
Letter A, B,…: major modification
Inverter
- = Non inverter Z = Inverter
Efficiency Level
S = Standard efficiency X = High efficiency P = Premium efficiency (N.A. for this range)
Sound Level
S = Standard noise L = Low noise (N.A. for this range) R = Reduced noise (N.A. for this range) X = Extra low noise (N.A. for this range) C = Cabinet (N.A. for this range)
Warranty
0 = 1 year of warranty B = 2 years of warranty C = 3 years of warranty … = … years of warranty
Sequential number
000 = Base model 001 = First order this model (1 or more units) 002 = Second order this model (1 or more units) … = … order this model B01 = First order for this model + 1 year warranty B02 = Second order for this model + 1 or more units … = … order for this model
EWW Q 380 B - S S 0 01
D–EIMWC00504-14EN - 7/68
TECHNICAL SPECIFICATIONS
EWWQ B
-
SS
Table 1 – EWWQ380B-SS~EWWQ730B-SS - Technical Data
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 380 464 562 637 727 Capacity control Unit power input (1) Cooling kW 86 104 128 144 168
EER (1) 4,44 4,46 4,40 4,41 4,37 ESEER 5,16 5,21 5,22 5,22 4,95
Casing
Dimensions Unit
Weight
Water heat exchanger
Evaporator
Type Stepless Minimum capacity % 25 25 25 25 25
Colour Ivory White (Munsell code 5Y7.5/1) Material Galvanized and painted steel sheet
Height mm 1849 1849 2001 2001 1848 Width mm 1140 1140 1276 1276 1314
Depth mm 3373 3373 3454 3454 3535 Unit kg 1933 1967 2283 2332 2407 Operating Weight kg 2135 2169 2543 2628 2777 Type Shell & tubes Water volume l 124 118 176 170 274 Nominal water flow
rate Nominal Water pressure drop Insulation material Closed cell foam elastomer
Type Shell & tubes Number of condensers No. 1 1 1 1 1
Cooling l/min 18,2 22,2 26,8 30,4 34,7
Cooling kPa 47 63 43 46 53
380 460 560 640 730
Water volume l 79 92 84 126 97
Water heat exchanger
Condenser
Compressor
Sound level
Refrigerant circuit Piping connections Evaporator water inlet/outlet mm 168.3 168.3 219.1 219.1 219.1
Pipinogconnections Condenser water inlet/outlet in 5” 5” 6” 6” 6” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Nominal water flow rate
Nominal Water pressure drop
Insulation Material Expanded elastomer Type Semi-hermetic single screw compr. Oil charge l 16 16 16 16 16 Quantity 1 1 1 1 1 Sound Power (2) Cooling dBA 100,2 101,2 102,3 102,3 101,5 Sound Pressure (2) Cooling dBA 82,2 83,0 83,9 83,9 83,2 Refrigerant type R410A R410A R410A R410A R410A N. of circuits 1 1 1 1 1
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12°/ 7°C; condenser 30°/ 35°C, unit at full load operation. The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser 30°/ 35°C, full load operation.
Cooling l/min 22,9 27,2 32,9 37,3 42,7
Cooling kPa 58 62 66 63 15
D-EIMWC00504-14EN - 8/68
Table 2 – EWWQ800B-SS~EWWQC10B-SS - Technical Data
EWWQ B
-
SS
TECHNICAL SPECIFICATIONS
800 860 870 960 C10
Capacity (1) Cooling kW 796 862 872 960 1007 Capacity control
Type Stepless
Minimum capacity % 25 25 12,5 12,5 12,5 Unit power input (1) Cooling kW 172 202 190 209 240 EER (1) 4,64 4,26 4,59 4,60 4,19 ESEER 5,64 4,83 5,63 5,59 4,76
Casing
Colour Ivory White (Munsell code 5Y7.5/1)
Material Galvanized and painted steel sheet
Height mm 2158 1848 2158 2158 1848
Dimensions Unit
Width mm 1350 1314 1350 1350 1314 Depth mm 5020 2001 5020 5020 2001
Weight
Unit kg 3921 2427 3949 3988 2457
Operating Weight kg 4422 2795 4463 4496 2812
Type Shell & tubes
Water volume l 344 266 344 325 251
Water heat exchanger
Evaporator
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min 38,0 41,2 41,7 45,9 48,1 Cooling kPa 52 48 62 57 55
Insulation material Closet cell foam elastomer
Type Shell & tubes
Number of condensers No. 2 1 2 2 1
Water heat exchanger
Condenser
Water volume l
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min
Nominal Water pressure drop
kPa
1) 79
2) 79
1) 23,1
2) 23,1
1) 62
2) 62
102
50,9
19
1) 79
2) 92
1) 23,4
2) 27,4
1) 62
2) 65
1) 92
2) 92
1) 27,9
2) 27,9
1) 65
2) 65
104
59,6
25
Insulation Material Expanded elastomer
Type Semi-hermetic single screw compr. Compressor
Oil charge l 32 16 32 32 16
Quantity 2 1 2 2 1 Sound level
Refrigerant circuit
Sound Power (1) Cooling dBA 104,7 102,3 104,7 105,1 103,2
Sound Pressure (1) Cooling dBA 84 84,9 85,2 85,2 85,6
Refrigerant type
R410A R410A R410A R410A R410A
N. of circuits 2 1 2 2 2 Piping connections Evaporator water inlet/outlet mm 219,1 219,1 219,1 219,1 219,1 Piping connections Condenser water inlet/outlet in 5” 5" 5” 5” 5” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation.
The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser
30°/ 35°C, full load operation.
D–EIMWC00504-14EN - 9/68
Table 3 – EWWQC11B-SS~EWWQC15B - Technical Data
TECHNICAL SPECIFICATIONS
EWWQ B-SS
Capacity (1) Cooling kW 1055 1185 1255 1325 1460 Capacity control
Type Stepless
Minimum capacity % 12,5 12,5 12,5 12,5 12,5 Unit power input (1) Cooling kW 232 256 274 290 333 EER (1) 4,55 4,62 4,59 4,56 4,38 ESEER 5,60 5,61 5,62 5,55 5,18
Casing
Colour Ivory White (Munsell code 5Y7.5/1)
Material Galvanized and painted steel sheet
Height mm 2378 2455 2455 2455 2495
Dimensions Unit
Width mm 1350 1350 1350 1350 1350 Depth mm 4894 5070 5070 5070 4892
Weight
Unit kg 4344 4529 4536 4607 4988
Operating Weight kg 4780 5186 5200 5280 5602
Type Shell & tubes
Water volume l 325 538 538 538 505
Water heat exchanger
Evaporator
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min 50,4 56,6 60,0 63,3 69,8 Cooling kPa 67 43 48 53 58
Insulation material Closet cell foam elastomer
Type Shell & tubes
Number of condensers No. 2 2 2 2 2
Water volume l
Water heat exchanger
Condenser
Nominal water flow
rate
Cooling l/min
C11 C12 C13 C14 C15
1) 52
2) 60
1) 27,6
2) 33,6
1)60
2)60
1)35.4
2)35.4
1)60
2)68
1)35.4
2)39.7
1)68
2)68
1)39.7
2)39.7
1)44.0
2)44.0
1)54
2)54
Nominal Water
pressure drop
Nominal Water pressure drop
kPa
1) 65
2) 67
1) 70
2) 70
1) 70
2) 67
1) 67
2) 67
1) 16
2) 16
Insulation Material Expanded elastomer
Type Semi-hermetic single screw compr. Compressor
Oil charge l 32 32 32 32 32
Quantity 2 2 2 2 2 Sound level
Refrigerant circuit
Sound Power (2) Cooling dBA 104,7 105,2 106,5 106,5 105,8
Sound Pressure (2) Cooling dBA 86,0 86,5 86,9 86,9 86,2
Refrigerant type
R410A R410A R410A R410A R410A
N. of circuits 2 2 2 2 2 Piping connections Evaporator water inlet/outlet mm 219,1 273 273 273 273 Piping connections Condenser water inlet/outlet in 6” 6” 6” 6” 5” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation.
The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser
30°/ 35°C, full load operation.
D-EIMWC00504-14EN - 10/68
Table 4 – EWWQC16B-SS~EWWQC20B-SS - Technical Data
EWWQ B
-
SS
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 1584 1748 1888 2050 Capacity control
Type Stepless
Minimum capacity % 12,5 12,5 12,5 12,5 Unit power input (1) Cooling kW 367 401 432 466 EER (1) 4.32 4,36 4,37 4,40 ESEER 5,18 5,06 5,11 5,07
Casing
Colour Ivory White (Munsell code 5Y7.5/1)
Material Galvanized and painted steel sheet
Height mm 2495 2495
Dimensions Unit
Width mm 1350 1350 1350 1350 Depth mm 4892 4892 4865 4865
Weight
Unit kg 4999 5053 5204 5289
Operating Weight kg 5615 5670 5881 5970
Type Shell & tubes
Water volume l 505 495 539 527 Water heat exchanger
Evaporator
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min 75,7 83,5 90,2 98,0 Cooling kPa 67,2 85,9 95,4 119
Insulation material Closed cell foam elastomer
Type Shell & tubes
Number of condensers No. 2 2 2 2
Water volume l
Water heat exchanger
Condenser
Nominal water flow
rate
Cooling l/min
C16 C17 C19 C20
2495
2495
1) 54
2) 57
1) 42,7
2) 50,2
1) 61
2) 61
1) 51
2) 51
1) 61
2) 77
1) 50,8
2) 59,8
1) 77
2) 77
1) 59,8
2) 59,8
Nominal Water
pressure drop
Nominal Water pressure drop
kPa
1) 16
2) 18
1) 16
2) 18
1) 16
2) 14
1) 14
2) 14
Insulation Material Expanded elastomer
Type Semi-hermet. single screw compr. Compressor
Oil charge l 32 32 32 32
Quantity 2 2 2 2 Sound level
Refrigerant circuit
Sound Power (2) Cooling dBA 106,2 106,6 107,1 107,5
Sound Pressure (2) Cooling dBA 86,6 87,0 87,5 87,9
Refrigerant type
R410A R410A R410A R410A
N. of circuits 2 2 2 2 Piping connections Evaporator water inlet/outlet mm 273 273 273 273 Piping connections Condenser water inlet/outlet in 5” 5” 5” 5” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation.
The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser
30°/ 35°C, full load operation.
D–EIMWC00504-14EN - 11/68
Table 5 – EWWQ420B-XS~EWWQ800B-XS - Technical Data
EWWQ B
-
XS
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 422 516 639 725 801 Capacity control Unit power input (1) Cooling kW 84,9 102 126 143 159
EER (1) 4,97 5,03 5,09 5,07 5,05 ESEER 5,86 5,88 5,97 5,95 5,89
Casing
Dimensions Unit
Weight
Water heat exchanger
Evaporator
Water heat exchanger
Condenser
Type Stepless Minimum capacity % 25 25 25 25 25
Colour Ivory White (Munsell code 5Y7.5/1) Material Galvanized and painted steel sheet
Height mm 2001 2001 2001 2001 2003 Width mm 1276 1276 1276 1268 1314
Depth mm 3863 3863 3863 3878 3878 Unit kg 2322 2403 2464 2738 2407 Operating Weight kg 2594 2685 2745 3158 2815 Type Shell & tubes Water volume l 220 213 200 334 325 Nominal water flow
rate Nominal Water pressure drop Insulation material Closet cell foam elastomer
Type Shell and tubes Number of condensers No. 1 1 1 1 1 Water volume l 52 69 81 86 83
Nominal water flow rate
Cooling l/min 20,2 24,6 30,5 34,6 38,3
Cooling kPa 57 70 73 65 58
Cooling l/min 24,2 29,5 36,5 41,4 45,8
420 520 640 730 800
Nominal Water pressure drop
Insulation Material Expanded elastomer Type Semi-hermetic single screw compr.
Compressor
Sound level
Refrigerant circuit Piping connections Evaporator water inlet/outlet mm 168,3 168,3 168,3 219.1 219.1
Piping connections Condenser water inlet/outlet in 8” 8” 8” 6” 6” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Oil charge l 16 16 16 16 16 Quantity 1 1 1 1 1 Sound Power (2) Cooling dBA 100,9 101,7 102,6 102,7 102,0 Sound Pressure (2) Cooling dBA 82,2 83,0 83,9 83,9 83,2 Refrigerant type R410A R410A R410A R410A R410A N. of circuits 1 1 1 1 1
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation. The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser 30°/ 35°C, full load operation.
Nominal Water
pressure drop
kPa 50 40 41 46 60
D-EIMWC00504-14EN - 12/68
Table 6 – EWWQ970B-XS~EWWQC13B-XS - Technical Data
EWWQ B
-
XS
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 973 1037 1118 1158 1270 Capacity control Unit power input (1) Cooling kW 193 205 227 228 252
EER (1) 5,05 5,06 4,91 5,07 5,04 ESEER 5,66 6,18 5,54 6,13 6,13
Casing
Dimensions Unit
Weight
Water heat exchanger
Evaporator
Water heat exchanger
Condenser
Type Stepless Minimum capacity % 25 12,5 25 12,5 12,5
Colour Ivory White (Munsell code 5Y7.5/1) Material Galvanized and painted steel sheet
Height mm 2003 2454 2003 2454 2454 Width mm 1448 1350 1448 1350 1350
Depth mm 3919 5219 3919 5219 5219 Unit kg 2427 4775 2457 4831 4873 Operating Weight kg 3056 5431 3086 5479 5512 Type Shell & tubes Water volume l 538 587 538 575 563 Nominal water flow
rate Nominal Water pressure drop Insulation material Closet cell foam elastomer
Type Shell & tubes Number of condensers No. 1 2 1 2 2
Water volume l 91
Nominal water flow rate
Cooling l/min 46,5 49,6 53,3 55,3 60,7
Cooling kPa 55 55 70 65 56
Cooling l/min 55,7
970 C10 C11 C12 C13
1) 69
2) 70
1) 29,5
2) 29,5
91
64,2
1) 73
2) 76
1) 29,6
2) 36,3
1) 76
2) 76
1) 36,3
2) 36,3
Nominal Water pressure drop
Insulation Material Expanded elastomer Type Semi-hermetic single screw compressor
Compressor
Sound level
Refrigerant circuit Piping connections Evaporator water inlet/outlet mm 273 219,1 273 219,1 219,1
Piping connections Condenser water inlet/outlet in 6” 5” 6” 5” 5” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Oil charge l 16 32 16 32 32 Quantity 1 2 1 2 2 Sound Power (2) Cooling dBA 102,9 105,2 103,8 105,6 106,1 Sound Pressure (2) Cooling dBA 84,0 85,6 84,9 86,0 86,5 Refrigerant type N. of circuits 1 2 1 2 2
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation. The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser 30°/ 35°C, full load operation.
Nominal Water
pressure drop
kPa 64
R410A R410A R410A R410A R410A
1) 39
2) 39
84
1) 35
2) 48
1) 48
2) 48
D–EIMWC00504-14EN - 13/68
Table 7 – EWWQC14B-XS~EWWQC19B-XS - Technical Data
EWWQ B
-
XS
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 1369 1449 1573 1733 1863 Capacity control
Type Stepless
Minimum capacity % 12,5 12,5 12,5 12,5 12,5 Unit power input (1) Cooling kW 269 286 315 349 382 EER (1) 5,08 5,07 4,99 4,96 4,87 ESEER 6,28 6,23 5,92 6,00 5,73
Casing
Colour Ivory White (Munsell code 5Y7.5/1)
Material Galvanized and painted steel sheet
Height mm 2454 2454 2495 2495 2595
Dimensions Unit
Width mm 1350 1350 1350 1350 1350 Depth mm 5219 5219 4829 4829 4829
Weight
Unit kg 4919 4969 5117 5177 5388
Operating Weight kg 5546 5606 5794 5843 6110
Type Shell & tubes
Water volume l 551 551 495 484 535
Water heat exchanger
Evaporator
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min 65,4 69,2 75,1 82,8 89,0 Cooling kPa 68 76 71 91 93
Insulation material Closet cell foam elastomer
Type Shell & tubes
Number of condensers No. 2 2 2 2 2
Water volume l
Water heat exchanger
Condenser
Nominal water flow
rate
Cooling l/min
C14 C15 C16 C17 C19
1) 75
2) 86
1) 36,7
2) 41,2
1) 86
2) 86
1) 41,2
2) 41,2
1) 91
2) 91
1) 44,9
2) 44,9
1) 91
2) 91
1) 44,6
2) 54,4
1) 91
2)91
1) 53,3
2) 53,3
Nominal Water
pressure drop
Nominal Water pressure drop
kPa
1) 49
2) 46
1) 48
2) 48
1) 43
2) 43
1) 43
2) 62
1) 60
2) 60
Insulation Material Expanded elastomer
Type Semi-hermetic single screw compressor Compressor
Oil charge l 32 32 32 32 32
Quantity 2 2 2 2 2 Sound level
Refrigerant circuit
Sound Power (2) Cooling dBA 106,5 106,5 105,8 106,2 106,6
Sound Pressure (2) Cooling dBA 86,9 86,9 86,2 86,6 87,0
Refrigerant type R410A R410A R410A R410A R410A
N. of circuits 2 2 2 2 2 Piping connections Evaporator water inlet/outlet mm 219,1 273 273 273 273 Pipino connections Condenser water inlet/outlet in 6” 6” 8” 8” 8” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation. The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser 30°/ 35°C, full load operation.
D-EIMWC00504-14EN - 14/68
Table 8 – EWWQC20B-XS-EWWQC21B-XS - Technical Data
EWWQ B
-
XS
TECHNICAL SPECIFICATIONS
Capacity (1) Cooling kW 2020 2152 Capacity control
Type Stepless
Minimum capacity % 12.5 12.5 Unit power input (1) Cooling kW 417 451 EER (1) 4,84 4,77 ESEER 5,78 5,64
Casing
Colour Ivory White (Munsell code 5Y7.5/1)
Material Galvanized and painted steel sheet
Height mm 2495 2495
Dimensions Unit
Width mm 1350 1350 Depth mm 4865 4865
Weight
Unit kg 5408 5414
Operating Weight kg 6118 6124
Type Shell & tubes
Water volume l 527 527
Water heat exchanger
Evaporator
Nominal water flow
rate
Nominal Water
pressure drop
Cooling l/min 96,5 103 Cooling kPa 115 129
Insulation material Closet cell foam elastomer
Type Shell & tubes
Number of condensers No. 2 2
Water volume l
Water heat exchanger
Condenser
Nominal water flow
rate
Cooling l/min
C20 C21
1) 91
2) 91
1) 53,2
2) 62,6
1) 91
2) 91
1) 61,9
2) 61,9
Nominal Water
pressure drop
Nominal Water pressure drop
kPa
1) 52
2) 79
1) 78
2) 78
Insulation Material Expanded elastomer
Type Semi-hermet. single screw compr. Compressor
Oil charge l 32 32
Quantity 2 2 Sound level
Refrigerant circuit
Sound Power (2) Cooling dBA 107,1 107,5
Sound Pressure (2) Cooling dBA 87,5 87,9
Refrigerant type
R410A R410A
N. of circuits 2 2 Piping connections Evaporator water inlet/outlet mm 273 273 Piping connections Condenseer water inlet/outlet in 8” 8” Safety devices High pressure (pressure switch) Safety devices Low pressure (pressure switch) Safety devices Emergency stop Safety devices High discharge temperature on the compressor Safety devices Phase monitor Safety devices Low pressure ratio Safety devices High oil pressure drop Safety devices Low oil pressure
Notes (1) Notes (2)
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12°/ 7°C; condenser 30°/ 35°C unit full load operation.
The values are according to ISO 3744 and are referred to evaporator 12°/ 7°C, condenser
30°/ 35°C, full load operation.
D–EIMWC00504-14EN - 15/68
Sound pressure level at 1 m from the unit in free field (ref.
2 x 10
-
5
)
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
dBA
380
82.2
4
60
83.0
560
83.9
6
40
83.9
7
30
860
C1
0
800
85.2
870
85.2
960
85.6
C1
1
86.0
C1
2
86.5
C1
3
86.9
C1
4
86.9
C1
5
C1
6
C1
7
C19
C20
Sound pressure level at 1 m from the unit in free field (ref.
2 x 10
-
5
)
63 H
z 125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
dBA
420
520
640
730
800
970
C10
C11
C12
C13
C14
C15
C16
C17
C19
C20
C21
Table 9 - Sound levels EWWQ B-SS
Size
55.1 59.4 71.6 84.1 71.9 72.5 58.5 53.2
55.9 60.2 72.4 84.9 72.7 73.3 59.3 54.0
56.8 61.1 73.3 85.8 73.6 74.2 60.2 54.9
56.8 61.1 73.3 85.8 73.6 74.2 60.2 54.9 56,1 60,4 72,6 85,1 72,9 73,5 59,5 54,2 56,9 61,2 73,4 85,9 73,7 74,3 60,3 55,0 57,8 62,1 74,3 86,8 74,6 75,2 61,2 55,9
58.1 62.4 74.6 87.1 74.9 75.5 61.5 56.2
58.1 62.4 74.6 87.1 74.9 75.5 61.5 56.2
58.5 62.8 75.0 87.5 75.3 75.9 61.9 56.6
58.9 63.2 75.4 87.9 75.7 76.3 62.3 57.0
59.4 63.7 75.9 88.4 76.2 76.8 62.8 57.5
59.8 64.1 76.3 88.8 76.6 77.2 63.2 57.9
59.8 64.1 76.3 88.8 76.6 77.2 63.2 57.9 59,1 63,4 75,6 88,1 75,9 76,5 62,5 57,2 59,5 63,8 76,0 88,5 76,3 76,9 62,9 57,6 59,9 64,2 76,4 88,9 76,7 77,3 63,3 58,0 60,4 64,7 76,9 89,4 77,2 77,8 63,8 58,5 60,8 65,1 77,3 89,8 77,6 78,2 64,2 58,9
Note: The values are according to ISO 3744
Table 10 - Sound levels EWWQ B-XS
83,2 84,0 84,9
86,2 86,6 87,0 87,5 87,9
Size
55.1 59.4 71.6 84.1 71.9 72.5 58.5 53.2
55.9 60.2 72.4 84.9 72.7 73.3 59.3 54.0
56.8 61.1 73.3 85.8 73.6 74.2 60.2 54.9
56.8 61.1 73.3 85.8 73.6 74.2 60.2 54.9 56,1 60,4 72,6 85,1 72,9 73,5 59,5 54,2 56,9 61,2 73,4 85,9 73,7 74,3 60,3 55,0
58.5 62.8 75 87.5 75.3 75.9 61.9 56.6 57,8 62,1 74,3 86,8 74,6 75,2 61,2 55,9
58.9 63.2 75.4 87.9 75.7 76.3 62.3 57.0
59.4 63.7 75.9 88.4 76.2 76.8 62.8 57.5
59.8 64.1 76.3 88.8 76.6 77.2 63.2 57.9
59.8 64.1 76.3 88.8 76.6 77.2 63.2 57.9 59,1 63,4 75,6 88,1 75,9 76,5 62,5 57,2 59,5 63,8 76,0 88,5 76,3 76,9 62,9 57,6 59,9 64,2 76,4 88,9 76,7 77,3 63,3 58,0 60,4 64,7 76,9 89,4 77,2 77,8 63,8 58,5 60,8 65,1 77,3 89,8 77,6 78,2 64,2 58,9
Note: The values are according to ISO 3744
82.2
83.0
83.9
83.9 83,2 84,0
85.6 84,9
86.0
86.5
86.9
86.9 86,2 86,6 87,0 87,5 87,9
D-EIMWC00504-14EN - 16/68
Operating limits
Storing
The units of the series can be stored under the following environmental conditions: Minimum ambient temperature : -20°C Maximum ambient temperature : 41°C Max. R.H. : 95% not condensing
ATTENTION
Storing below the minimum temperature mentioned above may cause damage to components such as the electronic controller and its LCD display.
Storing above the maximum temperature may cause opening of the safety valves on the compressor’s suction line.
WARNING
ATTENTION
Storing in condensing atmosphere may damage the electronic components.
Operation
Operation is allowed within the limits mentioned in the following diagrams.
Operation outside the mentioned limits may damage the unit. In case of doubt contact the manufacturer.
ATTENTION
D–EIMWC00504-14EN - 17/68
Operating limits - EWWQ - AJYNN / EWWQ - AJYNN/A
48,0 47,0 46,0 45,0 44,0 43,0 42,0 41,0 40,0 39,0 38,0 37,0 36,0 35,0 34,0 33,0 32,0 31,0 30,0 29,0 28,0 27,0 26,0 25,0 24,0 23,0 22,0 21,0
Condenser leaving water temperature in °C
20,0
-6,0 -5,0 -4,0 -3,0 -2,0 -1,0 0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0 11,0
Check on rating tables for actual operating limit at full load for SE ST machines with FR4 compressor.
Check on rating tables for actual operating limit at full load for EWWQ B-SS machines with Fr4 compressor
Evaporator leaving water temperature in °C
EWWQ B-SS~EWWQ B-XS
Glycol must be used
Fig. 1 – Operating limit
Mechanical Installation
D-EIMWC00504-14EN - 18/68
Shipping
The stability of the machine during shipping must be ensured. If the machine is shipped with a wooden cross-plank on its base, the cross-plank must be removed only after the final destination has been reached.
Responsibility
The manufacturer declines all responsibility, present and future, for any damage to persons, animals or property caused by negligence of operators failing to follow the installation and maintenance instructions in this manual. All safety equipment must be regularly and periodically checked in accordance with this manual and with local laws and regulations regarding safety and environment protection.
Safety
The machine must be firmly secured to the ground. It is essential to observe the following instructions:
- The machine can only be lifted using the lifting points on the base of the machine itself. These are the only points that
can support the entire weight of the unit.
- Do not allow unauthorised and/or unqualified personnel to access the machine.
- It is forbidden to access the electrical components without having opened the machine's general disconnecting switch
and switched off the power supply.
- It is forbidden to access the electrical components without using an insulating platform. Do not access the electrical
components if water and/or moisture are present.
- All operations on the refrigerant circuit and on components under pressure must be carried out by qualified personnel
only.
- Replacement of a compressor or addition of lubricating oil must be carried out by qualified personnel only.
- Sharp edges can cause wounds. Avoid direct contact.
- Avoid introducing solid bodies into the water pipes while the machine is connected to the system.
- A mechanical filter must be installed on the water pipe connected to the heat exchanger inlet.
- The machine is supplied with safety valves, that are installed on both the high and the low pressure sides of the
refrigerant circuit. In case of sudden stop of the unit, follow the instructions on the Control Panel Operating Manual which is part of the on-board documentation delivered to the end user with this manual. It is recommended to perform installation and maintenance with other people. In case of accidental injury or unease, it is necessary to:
- keep calm
- press the alarm button if present in the installation site
- move the injured person in a warm place far from the unit and in rest position
- contact immediately emergency rescue personnel of the building or if the Health Emergency Service
- wait without leaving the injured person alone until the rescue operators come
- give all necessary information to the the rescue operators
WARNING
Before carrying out any operation on the machine, please read this instruction and operating manual carefully. Installation and maintenance must be carried out only by qualified personnel that is familiar with the provisions of law and local regulations and has been trained properly or has experience with this type of equipment.
WARNING
Avoid installing the machine in a place that could be dangerous during maintenance operations, such as (but not only) platforms without parapets or railings or areas not complying with the clearance requirements.
Moving and lifting
Avoid bumping and/or jolting during unloading from the lorry and moving the machine. Do not push or pull the machine from any part other than the base frame. Secure the machine inside the lorry to prevent it from moving and causing damage to the panels and to the base frame. Do not allow any part of the machine to fall during transportation and/or unloading, as this could cause serious damage. All units of the series are supplied with four lifting points. Only these points may be used for lifting the unit, as shown in figure 2.
D–EIMWC00504-14EN - 19/68
Fig. 2 - Lifting the unit
WARNING
Both the lifting ropes and the spacing bar and/or scales must be strong enough to support the machine safely. Please check the unit’s weight on the machine’s nameplate. The weights shown in the "Technical data" tables in the "General Information" chapter refer to standard units. Some specific machines might have accessories that increase their overall weight (heat recovery, etc.)
WARNING
The machine must be lifted with the utmost attention and care. Avoid jolting when lifting and lift the machine very slowly, keeping it perfectly level.
Positioning and assembly
All units are designed for installation indoors. The machine must be installed on a robust and perfectly level foundation; should the machine be installed on balconies or roofs, it might be necessary to use weight distribution beams. For installation on the ground, prepare a strong cement base that is at least 250 mm wider and longer than the machine. Also, this base must be strong enough to support the weight of the machine as stated in the technical specifications. If the machine is installed in places that are easily accessible to people and animals, it is advisable to install protection gratings for the compressor section. To ensure the best possible performance on the installation site, the following precautions and instructions must be followed:
Make sure to provide a strong and solid foundation to reduce noise and vibration as much as possible.
D-EIMWC00504-14EN - 20/68
The water in the system must be particularly clean and all traces of oil or rust must be removed. A mechanical water
filter must be installed on the machine’s inlet piping.
Minimum space requirements
Every side of the machine must be accessible for all post-installation maintenance activities. Figure 3 shows the minimum space necessary.
Fig. 3 – Minimum clearance requirements for machine maintenance
Ventilation
The temperature of the room where the unit is placed should be always maintained between 0°C and 40°C.
Sound protection
When sound levels require special control, great care must be exercised to isolate the machine from its base by appropriately applying anti-vibration elements (supplied as an option). Flexible joints must be installed on the water connections, as well.
Water piping
Piping must be designed with the lowest number of elbows and the lowest number of vertical changes of direction. In this way, installation costs are reduced considerably and system performance is improved. The water system must have:
1. Anti-vibration mountings in order to reduce transmission of vibrations to the underlying structure.
2. Isolating valves to isolate the machine from the water system during service.
3.
Manual or automatic air venting device at the system’s highest point; drain device at the system’s lowest point. Neither the evaporator nor the heat recovery device must be positioned at the system’s highest point.
4. A suitable device that can maintain the water system under pressure (expansion tank, etc.)
5. Water temperature and pressure indicators on the machine to assist the operator during service and maintenance.
6.
A filter or device which can remove foreign particles from the water before it enters the pump (in order to prevent cavitation, please consult the pump manufacturer for the recommended type of filter ). The use of a filter prolongs the life of the pump and helps keep the water system in a better condition.
7.
Another filter must be installed on the machine inlet water pipe, near the evaporator and heat recovery (if installed). The filter prevents solid particles from entering the heat exchanger, as they could damage it or reduce its heat exchanging capacity.
8. The heat recovery device must be emptied of water during the winter season, unless an ethylenic glycol mixture in appropriate percentage is added to the water circuit.
9.
If the machine is intended to replace of another, the entire water system must be emptied and cleaned before the new unit is installed. Regular tests and proper chemical treatment of water are recommended before starting up the new machine.
10.
In the event that glycol is added to the water system as anti-freeze protection, pay attention to the fact that suction pressure will be lower, the machine’s performance will be lower and water pressure drops will be greater. All machine-protection systems, such as anti-freeze, and low-pressure protection will need to be readjusted.
Before insulating water piping, check that there are no leaks.
D–EIMWC00504-14EN - 21/68
Loading...