Daikin EWWQ014KBW1N, EWWQ025KBW1N, EWWQ033KBW1N, EWWQ049KBW1N, EWWQ064KBW1N Operation manuals

OPERATION MANUAL
Packaged water-cooled water chillers
EWWQ014KBW1N EWWQ025KBW1N EWWQ033KBW1N EWWQ049KBW1N EWWQ064KBW1N
Operation manual
Packaged water-cooled water chillers
Bedienungsanleitung
Kompakte wassergekühlte Kaltwassererzeuger
Manuel d'utilisation
Gebruiksaanwijzing
Watergekoelde ijswaterkoelgroepen
Manual de funcionamiento
Enfriadores de agua empaquetados
Manuale d'uso
Refrigeratori d'acqua monoblocco con raffreddamento ad acqua
∂Б¯ВИЪ›‰ИФ ПВИЩФ˘ЪБ›·˜
™˘БОЪФЩ‹М·Щ· ˘‰Ъfi„˘ОЩˆУ „˘ОЩТУ УВЪФ‡
Manual de operação
Refrigeradores de água arrefecidos a água
Инструкция по эксплуатации
Моноблочные чиллеры с водяным охлаждением
English
Deutsch
Français
Nederlands
Español
Italiano
EППЛУИО¿
Portugues
русский
EWWQ014KBW1N EWWQ064KBW1N EWWQ025KBW1N EWWQ033KBW1N EWWQ049KBW1N
Packaged water-cooled water chillers

Operation manual

CONTENTS Page
Introduction ....................................................................................... 1
Technical specifications............................................................................. 1
Electrical specifications ............................................................................. 2
Description........................................................................................ 2
Function of the main components.............................................................. 3
Safety devices............................................................................................3
Internal wiring - Parts table........................................................................4
Before operation................................................................................ 5
Checks before initial start-up..................................................................... 5
Water supply.............................................................................................. 5
General recommendations ........................................................................ 5
Operation .......................................................................................... 5
Digital controller.........................................................................................5
Working with the units................................................................................ 6
Advanced features of the digital controller................................................. 9
BMS connection modbus................................................................ 12
General description of Modbus................................................................ 12
Implemented error code........................................................................... 13
Defining the BMS setting......................................................................... 13
Variables database .................................................................................. 13
Troubleshooting............................................................................... 14
Maintenance.................................................................................... 15
Important information regarding the refrigerant used .............................. 15
Maintenance activities ............................................................................. 15
Disposal requirements.............................................................................15
Menu overview................................................................................ 16
(mm)
(kg)
(mm)
(kg)
(rpm)
(kg)
(l/min)
(l/min)
(1)
600x600x600
120 170 175
600x600x1200
310 340
JT140L-P8Y1
(l)
1.5 3.0 3.0
1.2 2.1 3.1
(l)
62 103 155
31~75 53~123 76~186
24~95 39~157 59~237
JT236DJ-Y1 JT315DJ-Y1
2900
Technical specifications
General EWWQ 014 025 033
Dimensions HxWxD Machine weight Connections
•water inlet G 1
•water outlet G 1
General EWWQ 049 064
Dimensions HxWxD Machine weight Connections
•water inlet G 1-1/2
•water outlet G 1-1/2
Compressor 014 025 033
Model Speed Oil type FVC68D Oil charge volume Refrigerant type R410A Refrigerant charge
Evaporator 014 025 033
Type brased plate heat exchanger Min. water volume Water flow range
Condenser 014 025 033
Type brased plate heat exchanger Water flow range
READ THIS MANU AL ATTENTIVELY BEFORE ST ARTING UP THE UNIT. DO NOT THROW THIS MANUAL AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE. Read the chapter "Operation" on page 5 before changing the parameters.
The English text is the original instruction. Other languages are translations of the original instructions.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

INTRODUCTION

This operation manual concerns packaged water-cooled water chillers of the Daikin EWWQ-KB series. These units are provided for indoor installation and used for cooling and/or heating applications. The units can be combined with Daikin fan coil units or air handling units for air conditioning purposes. They can also be used for supplying water for process cooling.
This manual has been prepared to ensure adequate operation and maintenance of the unit. It will tell you how to use the unit properly and will provide help if problems occur. The unit is equipped with safety devices, but they will not necessarily prevent all problems caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local Daikin Dealer.
Compressor 049 064
Model 2x Speed Oil type FVC68D Oil charge volume Refrigerant type R410A Refrigerant charge
Evaporator 049 064
Type brased plate heat exchanger Min. water volume Water flow range
Condenser 049 064
Type brased plate heat exchanger Water flow range
(rpm)
(l)
(kg)
(l)
(l/min)
(l/min)
JT236DJ-Y1
2x 3.0 2x 3.0
4.6 5.6
205 311
101~247 152~373
79~314 118~474
2900
2x
JT315DJ-Y1
Before starting up the unit for the first time, make sure that it has been properly installed. It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in "Before starting".
Operation manual
1
(1) Refer to the engineering data book for the complete list of specifications.
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Electrical specifications
(1)
General EWWQ 014 025 033
Power supply
• Phase 3N~
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM) 16 gG 25 gG 25 gG
Compressor
• Phase 3~
•Frequency
•Voltage
• Nominal running current (A)6.5 10.5 15.0
Control
• Phase 1~
•Frequency
•Voltage
• Recommended fuses (aM) factory installed
(Hz)
(%)
(Hz)
(Hz)
(V)
(V)
(V)
50 400 ±10
50 400
50 230
General EWWQ 049 064
Power supply
• Phase 3N~
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM) 40 gG 50 gG
Compressor
• Phase 3~
•Frequency
•Voltage
• Nominal running current (A) 10.5 15.0
Control
• Phase 1~
•Frequency
•Voltage
• Recommended fuses (aM) factory installed
(Hz)
(V)
(%)
(Hz)
(V)
(Hz)
(V)
50 400 ±10
50 400
50 230

DESCRIPTION

The EWWQ packaged water-cooled water chillers are available in 5 standard sizes with nominal cooling capacities ranging from 13 to 64 kW.
EWWQ049~064KB
18
2
14 15 16 17
3
EWWQ014~033KB
2 3
500 500
1
4
9
12
Figure - Main components
1 Compressor 2 Evaporator 3 Condenser 4 Switchbox 5 Chilled water in 6 Chilled water out 7 Condenser water out 8 Condenser water in 9 Evaporator entering water temperature sensor
10 Freeze up sensor
(1) Refer to the engineering data book for the complete list of specifications.
75
8611 13
500
1
1
500 500
4
11 Condenser entering water temperature sensor 12 Digital display controller 13 Power supply intake 14 Ball valve (field installed) 15 Water filter (field installed) 16 Air purge valve (field installed) 17 T-joint for air purge (field installed) 18 Flow switch (with T-joint) (field installed) 19 Main switch
Required space around the unit for service
10
500
75129
8611 141919 10
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
2

Function of the main components

EWWQ014~033KB
EWWQ049~064KB
65
7
119
9
10
R3T
8
R4T
R3T
R4T
S4LP
S5LP
S4LP
12
M1C
LP
Q1D
HP
4
3
M2C
LP
Q2D
HP
M1C
LP
Q1D
HP
S1HP
S2HP
S1HP
11
R5T
R5T
9
7
910
6
Figure - Functional diagram
1 Compressor 7 Water outlet 2 Condenser 8 Flow switch (delivered with the unit, installed in the field) 3 Filter 9 Ball valve (delivered with the unit, installed in the field) 4 Expansion valve 10 Water filter (delivered with the unit, installed in the field) 5 Evaporator 11 Air purge valve (delivered with the unit, installed in the field) 6 Water inlet Field piping
As the refrigerant circulates through the unit, changes in its state or condition occur. These changes are caused by the following main components:
Compressor The compressor (M*C) acts as a pump and circulates the refrigerant in the refrigeration circuit. It compresses the refrigerant vapour coming from the evaporator to a pressure at which it can easily be liquefied in the condenser.
Condenser The function of the condenser is to change the state of the refrigerant from gaseous to liquid. The heat gained by the gas in the evaporator is discharged through the condenser and the vapour condenses to liquid.
Filter The filter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the tubes.
Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve. The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator.
Evaporator The main function of the evaporator is to take heat from the water that flows through it. This is done by turning the liquid refrigerant, coming from the condenser, into gaseous refrigerant.
Water in/outlet connections The water inlet and outlet connection allow an easy connection of the unit to the water circuit of the air handling unit or industrial equipment.

Safety devices

The unit is equipped with General safety devices: shut down all circuits and stop the whole unit.
I/O PCB (A2P) (input/output) The I/O PCB (A2P) contains a reverse phase protector. The reverse phase protector detects if the 3 phases of the power supply are connected correctly. If a phase is not connected or if 2 phases are inverted, the unit can not start up.
Overcurrent relay The overcurrent relay (K*S) is located in the switch box of the unit and protects the compressor motor in case of overload, phase failure or too low voltage . The relay is factory-set and may not be adjusted. When activated, the overcurrent relay has to be reset in the switch box and the controller needs to be reset manually.
High-pressure switch The high-pressure switch (S*HP) is installed on the discharge pipe of the unit and measures the condenser pressure (pressure at the outlet of the compressor). When the pressure is too high, the pressure switch is activated and the circuit stops. When activated, it resets automatically, but the controller needs to be reset manually.
Low pressure switch The low-pressure switch (S*LP) is installed on the suction pipe of the unit and measures the evaporator pressure (pressure at the intlet of the compressor). When the pressure is too low, the pressure switch is activated and the circuit stops. When activated, it resets automatically, but the controller needs to be reset manually.
Operation manual
3
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Discharge thermal protector The discharge thermal protector (Q*D) is activated when the temperature of the refrigerant leaving the compressor becomes too high. When the temperature retur ns to normal, the protector resets automatically, but the controller needs to be reset manually.
Freeze up sensor The outlet water temperature sensor (R4T) measures the temperature of the water at the water heat exchanger outlet. The protection device shuts down the circuit when the temperature of the chilled water becomes too low in order to prevent freezing of the water during operation. When the outlet water temperature returns to normal, the protector resets automatically, but the controller needs to be reset manually.
Fuse for control circuit (F1U) The fuse for control circuit protects cables of control circuit and controller components in case of short circuit.
Fuse for control circuit (F4) The fuse for the control circuit protects cables of the control circuit in case of a short circuit.
Fuse for digital controller (F3U) The fuse protects cables of digital controller and digital controller in case of short circuit.
Flow switch (delivered with the unit, installed in the field) The flow switch measures the flow in the water circuit. In case the flow does not reach the minimum allowed water flow, the unit will be shut down.
Ball valve (delivered with the unit, installed in the field) A ball valve is installed in front of and behind the water filter to allow filter cleaning without having to drain the water circuit.
Water filter (delivered with the unit, installed in the field) The filter installed in front of the unit removes dirt from the water to prevent damage to the unit or blockage of the evaporator or condenser. The water filter should be cleaned on a regular base.
Air purge valve (delivered with the unit, installed in the field) Remaining air in the chiller water system will be automatically removed via the air purge valve.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The abbreviations used are listed below:
A1P........................PCB: controller PCB
A2P........................PCB: I/O PCB (input/output)
A3P..............** ...... PCB: Address card for BMS
A5P,A6P.......** ......PCB: Softstarter for circuit 1, circuit 2
A7P..............** ...... PCB: Remote user interface
A71P......................PCB: power supply card
A72P......................PCB: remote user interface
F1,F2,F3.......# ...... Main fuses for the unit
F4 .................* ...... Fuse I/O PCB
F5 ...............## ...... Surge proof fuse
F6 .................# ...... Fuse for pumpcontactor
F1U........................Fuse I/O PCB
F3U........................Fuse for controller PCB
H3P............... * ......Indication lamp alarm
H4P............... * ......Indication lamp operation compressor 1
H5P............... * ......Indication lamp operation compressor 2
H6P............... * ......Indication lamp general operation
K1M,K2M...............Compressor contactor circuit 1, circuit 2
K4S,K5S................ Overcurrent relay circuit 1, circuit 2
K6S...............* ...... Overcurrent relay pump
K1P...............* ...... Pumpcontactor
M1C,M2C...............Compressor motor circuit 1, circuit 2
PE..........................Main earth terminal
Q1D,Q2D...............Discharge thermal protector circuit 1, circuit 2
R3T........................Evaporator inlet water temperature sensor
R4T........................Evaporator outlet water temperature sensor
R5T........................Condenser inlet temperature sensor
S1HP,S2HP............High pressure switch circuit 1, circuit 2
S4LP,S5LP............. Low pressure switch circuit 1, circuit 2
S7S...............* ...... Switch for remote cooling/heating selection or
dual setpoint
(2)
S9S...............* ...... Switch for remote start/stop or dual setpoint
S10L...................... Flow switch
S12M..................... Main isolator switch
TR1........................Transfo 230 V ➞ 24 V for supply of controller
PCB
TR2........................Transfo 230 V ➞ 24 V for supply of I/O PCB
(A2P)
Y3R........................ Reversing valve
X1~3,X1~82A........ Connectors
Not included with standard unit
Not possible as option Possible as option
Obligatory # ##
Not obligatory * **
(1)
(1)
(1)
(2)
(2)
(2)
(2) (2)
(2)
(2)
(2)
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
(1) optional (2) field supply
Operation manual
4

BEFORE OPERATION

OPERATION

Checks before initial start-up

Make sure that the circuit breaker on the power supply panel of the unit is switched off.
After the installation of the unit, check the following before switching on the circuit breaker:
1 Field wiring
Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual, according to the wiring diagrams and according to European and national regulations.
2 Fuses or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified in the installation manual. Make sure that neither a fuse nor a protection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
5 Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
6 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
8 Oil leak
Check the compressor on oil leakage. If there is an oil leak, call your local dealer.
9 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage on the identification label of the unit.
The EWWQ units are equipped with a digital controller offering a user-friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart from the first section, which gives a brief description of the controller itself, each section or subsection deals with a specific task you can perform with the unit.

Digital controller

User interface
The digital controller consists of a numeric display, four labelled keys which you can press and LEDs providing extra user information.
Figure - Digital controller
Figure - Remote user interface (optional kit)

Water supply

Fill the water piping, taking into account the minimum water volume required by the unit. Refer to the chapter "Water charge, flow and quality" in the installation manual.
Make sure that the water is of the quality as mentioned in the installation manual.
Purge the air at the high points of the system and check the operation of the circulation pump and the flow switch.

General recommendations

Before switching on the unit, read following recommendations: 1 When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.
2 The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
Operation manual
5
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Keys provided on the controller:
The function carried out when the user presses one or a combination of these keys depends on the status of the controller and the unit at that specific moment.
Keys digital
controller
AT
BU
A + BS
CC
DD
C + DR
Keys remote
interface
Main display Sensor readout menu Parameter selection menu Parameter setting menu
Press once:
Press for 5 seconds:
To be able to access DIRECT parameters
Press for 5 seconds: A + B OR Press once:
S
To be able to access USER parameters (after entering USER password)
Press for 5 seconds: Switch unit on/off in heating mode Press once: Direct access to readout menu sensor (b01/b02/b03)
Press for 5 seconds: Switch unit on/off in cooling mode Press once: Direct access to readout menu sensor (b01/b02/b03)
Press for 5 seconds: Manually alarm reset in the event of alarm
Select previous sensor
Return
Press once:
parameter
Press once:
Select next sensor
parameter
Press once:
Return
Press once:
Select parameter group or
parameter
Press once:
Select previous parameter
group or parameter
Press once:
Select next parameter group
or parameter
Press once:
Cancel and return
Press once:
Confirm and return
Press once:
Increase value
Press once:
Decrease value
LEDs provided on the controller and remote interface:
Function during main display (not inside menu)
Remote
Leds digital controller
P
Led (green) Z Inlet water temperature.
Led (amber)
F
G Led (amber) G
H
Led (red) Y
L Led (amber) L
M Led (amber) M
& Led (amber) &
é Led (amber) é
interface
F
Main display
Indicates that heating mode is active.
Indicates that cooling mode is active.
Indicates that the alarm is active.
Indicates the status of the pump
LED, indicates that at least one compressor is active.
LED is on, indicates that compressor 1 is active. LED is flashing, indicates compressor 1 startup request.
LED is on, indicates that compressor 2 is active. LED is flashing, indicates compressor 2 startup request.
When selecting a parameter group or parameter, different LEDs related to the parameter group or parameter are displayed.
Example: The LEDs F and G are displayed when accessing a parameter group or when accessing parameters directly.
Direct and user parameters
The digital controller provides direct and user parameters. The direct parameters are important for the everyday usage of the unit, e.g. to adjust the temperature setpoint or to consult actual operational information. The user parameters on the contrary provide advanced features such as adjusting time delays.
Each parameter is defined by a code and a value. For example: the parameter used to select local or remote on/off control has code h07 and value 1 or 0.
For an overview of the parameters, refer to "Overview of the direct and user parameters" on page 9.

Working with the units

This chapter deals with the everyday usage of the units. Here, you will learn how to perform routine tasks, such as:
"Switching the unit on" on page 7 and "Switching the unit off" on
page 7,
"Adjusting the cooling temperature setpoint" on page 7 and
"Adjusting the heating temperature setpoint" on page 7,
"Consulting actual operational information" on page 8,
"Resetting alarms" on page 8,
"Resetting warnings" on page 8.
NOTE
Temperature readout tolerance: ±1°C. Legibility of the numeric display may decrease in direct
sunlight.
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
6
Switching the unit on
How to consult and modify the direct parameters
To switch the unit on in cooling mode, proceed as follows:
1 Press the D key for approximately 5 seconds, the G LED will
be displayed.
To switch the unit on in heating mode, proceed as follows:
1 Press the C key for approximately 5 seconds, the F LED will
be displayed.
In both cases an initialization cycle is started, the L LED, the M LED, the & LED and the é LED will light up depending on the programmed thermostat function.
In case the & LED or the é LED is flashing, it indicates that there is a compressor 1 or 2 startup request. The compressor will start after the timer has reached zero.
NOTE
If remote on/off control is enabled, refer to "Selecting local or remote on/off control" on page 11.
2 When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to go through the following checklist.
Abnormal noise and vibrations
Make sure the unit does not produce any abnormal noises or vibrations: check the fixations and piping. If the compressor makes any abnormal noises, this may also be caused by an overcharge of refrigerant.
Working pressure
It is important to check the high and low pressure of the refrigerant circuit to ensure the proper operation of the unit and to guarantee that the rated output will be obtained.
The pressures measured will vary between a maximum and minimum value, depending on the water and outdoor temperatures (at the moment of measurement).
3 If the unit does not start after a few minutes, consult the actual
operational information available in the list of direct parameters. Also refer to the chapter "Troubleshooting" on page 14.
NOTE
In case of remote on/off control (h07=1), it is recom­mended to install an on/off switch near the unit in series with the remote switch. The unit can then be switched off from either place.
The selection of cooling mode or heating mode can only be carried out at startup. Selecting an opposite mode without switching the unit off is impossible.
For an overview of the menu structure, refer to "Menu overview" on page 16.
1 Press B for 5 seconds in the main display.
The -/- parameter group is displayed.
2 Press the C or D key to select the required parameter
group.
3 Press the B key to enter the selected parameter group. 4 Press the C or D key to select the required parameter. 5 Press the B key to consult the selected parameter. 6 Press the C or D key to raise, respectively lower the
setting of the selected parameter. (Only valid for read/write parameters.)
7 Press the B key to confirm the modified setting.
OR Press the A key to cancel the modified setting.
8 Press the A key to return to the parameter group. 9 Press 2 times the A key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display without saving any modified parameter.
How to consult the "sensor readout menu" parameters
For an overview of the menu structure, refer to "Menu overview" on page 16.
The b01/b02/b03 parameters are part of the "sensor readout menu".
1 Press the C or D key in the main display.
The b01 parameter is displayed. In case no buttons are pressed, the value of the b01 sensor will be displayed until C or D is pressed again to select another parameter (b02 or b03).
2 Press the A key to return to the main display. If during the procedure no buttons are pressed for 30 seconds, the
displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display.
Adjusting the cooling temperature setpoint
Switching the unit off
To switch the unit off and cooling mode is active, proceed as follows:
1 Press the D key for approximately 5 seconds, the G LED will
be extinguished.
To switch the unit off and heating mode is active, proceed as follows:
1 Press the C key for approximately 5 seconds, the F LED will
be extinguished.
NOTE
If remote on/off control is enabled, refer to "Selecting local or remote on/off control" on page 11.
Operation manual
7
1 Modify the r1 cooling setpoint parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 7.
NOTE
When dual setpoint is enabled (refer to "Selecting dual setpoint control" on page 11).
Adjusting the heating temperature setpoint
1 Modify the r3 heating setpoint parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 7.
NOTE
When dual setpoint is enabled (refer to "Selecting dual setpoint control" on page 11).
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Consulting actual operational information
The actual operational information that can be consulted in the list of direct parameters consists of:
b01:Evaporator inlet water temperature,
b02:Evaporator outlet water temperature,
b03: When cooling mode is active: inlet water temperature of
the condenser. When heating mode is active: inlet water temperature of the evaporator.
c10:Total running hours of the compressor 1,
c11:Total running hours of the compressor 2,
c15:Total running hours of the pump.
NOTE
The parameters b01, b02 and b03 can also be consulted by the "sensor readout menu". Refer to "How to consult the "sensor readout menu" parameters" on page 7.
To reset the timers of parameters c10, c11 and c15 refer to "Resetting warnings" on page 8.
These are direct parameters, refer to "How to consult and modify the direct parameters" on page 7.
Resetting alarms
When an alarm is detected, the following happens:
the alarm relay is energized,
the H LED is displayed
the display starts flashing, alternately showing the alarm code
and the inlet water temperature.
The following alarm codes may appear on the screen:
a1:indicates an anti-freeze alarm.
e1:indicates that the NTC probe used to measure the
e2:indicates that the NTC probe used to measure the
e3:indicates that the fuse for the evaporator heatertape (F4)
ehs:indicates that the supply voltage is exceedingly high. In
el1:indicates that there is a power supply error (example:
el2:indicates that there is a power supply error (example:
els:indicates that the supply voltage is exceedingly low. In this
epb:indicates that the EEPROM on the controller PCB inside
epr:indicates that the EEPROM on the controller PCB inside
fl:indicates that there was no sufficient water flow either
hp1:indicates that a high pressure switch, the discharge
evaporator inlet water temperature is defective.
evaporator outlet water temperature is defective.
is blown or that there is a rev erse phase error or that there is a problem with the I/O PCB (A2P).
In case the unit is equipped with freeze protection, it is highly recommended to install the remote indicator lamp alarm (H3P) (see wiring diagram supplied with the unit). By doing so, breakdown of the fuse for the evaporator heatertape (F4) will be detected sooner and freezing of the circuit will be avoided during cold weather.
this case contact a licensed electrician.
noise). In this case contact a licensed electrician.
noise). In this case contact a licensed electrician.
case contact a licensed electrician.
the unit is defective.
the unit is defective.
during the period of 15 seconds after the pump was started or for 5 seconds while the compressor is active or that the overcurrent protection of the pump is activated.
thermal protection or the overcurrent protection of the compressor motor is activated or that the NTC probe used to measure the ambient temperature is defective.
fl + hp1
:indicates that there is most likely an RPP error or that the
F4 fuse is blown.
lp1:indicates that the low pressure switch is activated.
ter:indicates that there is a remote user interface
communication error.
:
communication failure between the digital controller of the unit and the remote user interface. Confirm the correct selection of parameter code h23. This should be default setting 0 and confirm the correction installation according to the installation manual of the remote user interface EKRUMCA.
NOTE
If the alarm codes fl and h1 are flashing alternately, the alarm is most probably caused by the reverse phase protector or by the fuse for evaporator heater­tape (F4) that was blown.
To reset an alarm, proceed as follows:
1 Find the cause of shutdown and correct.
Refer to the chapter "Troubleshooting" on page 14.
2 If the alarm codes a1, fl, hp1 or lp1 appear on the display,
reset the alarm manually by pressing the E combination keys C and D simultaneously for approximately 5 seconds.
In all other cases the alarm is reset automatically. Once the alarm is reset, the error code and the H LED no longer
appears on the display. The controller continues its normal operation, displaying the inlet water temperature.
Resetting warnings
During normal operation, the display of the controller may start flashing, alternately showing the inlet water temperature and the following warning code:
hc1:indicates that the compressor 1 requires maintenance: the total running hours of the compressor 1 (direct parameter c10) has exceeded the setting of the timer threshold for maintenance warning (user parameter c14).
hc2:indicates that the compressor 2 requires maintenance: the total running hours of the compressor 2 (direct parameter c11) has exceeded the setting of the timer threshold for maintenance warning (user parameter c14).
To reset the maintenance warning hc1 or hc2, proceed as follows:
1 Consult c10 running hours of compressor 1 or c11 running
hours of compressor 2. These are direct parameters, refer to "How to consult and modify the direct parameters" on page 7.
2 When c10 or c11 parameter value is displayed, press the
C and D key simultaneously for 5 seconds. The value of the timer becomes 0 and the warning is reset.
NOTE
Do not forget to carry out the required maintenance activities after resetting the timers.
Besides resetting timer c10 and c11, it is also possible to reset timer c15 (running hours of pump) in the same way.
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
8

Advanced features of the digital controller

This chapter gives an overview of the direct parameters and user parameters provided by the controller. In the following chapter, you will learn how you can set up and configure the unit using these parameters.
Overview of the direct and user parameters
The list of direct parameters is accessible by pressing the B key for approximately 5 seconds. Refer also to "How to consult and modify the direct parameters" on page 7.
Parameter
group
-/- /23
Parameter
code
Description
Measurement unit
0=°C 1=°F
Default
value
Min Max Units
Read/
Write
User/
Direct
Modbus Address
001 R/WU5 D
-a- No user or direct parameters accessible b01 Evaporator inlet water temperature 0.1°C R D 102 A b02 Evaporator outlet water temperature 0.1°C R D 103 A
-b­b03
When cooling mode is active: inlet water temperature of the condenser. When heating mode is active: inlet
0.1°C R D 104 A
water temperature of the evaporator. Time delay between pump startup and
compressor startup Time threshold between the unit
shutdown and the pump shutdown
15 0 999 1 sec R/W U 238 I
00150 1 min R/W U 239 I
-c-
c07
c08 c10 Total running hours of compressor 1 x100 hours R D 122 A
c11 Total running hours of compressor 2 x100 hours R D 123 A
c14
Maintenance threshold for maintenance warning (c10 and c11)
00100 x100 hours R/W U 241 I
c15 Total running hours of pump x100 hours R D 126 A
-d- No user or direct parameters accessible
-f- No user or direct parameters accessible
To activate remote cool/heat control
h06
0=not active 1=active
001 R/WU14 D
(only in case p09=9) To activate remote on/off control
h07
-h-
0=not active 1=active
(only in case p34=23)
001 R/WU15 D
To lock the controller keyboard
h09
0=lock
101 R/WU16 D
1=unlock
h10 Serial address for BMS connection 1 1 200 R/W U 256 I
To select address card connection
h23
0=remote user interface connection
001 R/WU11 D
1=MODBUS connection Changeable digital input selection
S7S
p09
0=no function 9=remote cool/heat (only active in
combination with h06)
9027 R/W U 277 I
13=remote dual setpoint
-p-
DO NOT SELECT OTHER VALUES
Changeable digital input selection S9S
p34
0=no function 13=remote dual setpoint 23=remote on/off (only active in
23 0 27 R/W U 329 I
combination with h07)
DO NOT SELECT OTHER VALUES
r01
Cooling setpoint
12.0
(b)
25.0 0.1°C R/W D 41 A
8.0
r02 Cooling difference 3.0 0.3 19.9 0.1°C R/W D 42 A
-r-
r03 Heating setpoint 30.0 15.0 50.0 0.1°C R/W D 43 A r04 Heating difference 3.0 0.3 19.9 0.1°C R/W D 44 A
r21
r22
Cooling setpoint 2 Heating setpoint 2
(c) (c)
12.0
30.0 15.0 50.0 0.1°C R/W D 56 A
(b)
25.0 0.1°C R/W D 55 A
8.0
-t- No user or direct parameters accessible
f-r h99 Software release version R D 208 I
(a) D=digital, A=analog, I=integer. (b) –2.0 and –7.0 only applicable for units with glycol applications. (c) Used in case dual setpoint is enabled in p09 or p34 and dual setpoint digital input is closed.
Parameter
(a)
type
Operation manual
9
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
How to consult and modify the user parameters
inlet water
temperature of
evaporator
ON
OFF
compressor
inlet water
temperature of
evaporator
ON
OFF
ON
compressor
OFF
inlet water
temperature of
condenser
ON
OFF
compressor
inlet water
temperature of
condenser
ON
OFF
ON
compressor
OFF
Defining the cooling temperature differential
NOTE
When user parameters are consulted, the direct parameters are displayed as well.
For an overview of the menu structure, refer "Menu overview" on page 16.
1 In case of digital controller, press the A and B keys for
approximately 5 seconds until O is displayed. In case of remote user interface, push S once.
2 Enter the correct password by using the C and D keys.
The password's value is 22.
3 Press the B key to confir m the password and to enter the
menu, s-p is displayed.
4 Press the B key to consult the parameter settings (=s-p).
(l-p means consulting the parameter level, but this function is not used). The -/- parameter group is displayed.
5 Press the C or D key to select the required parameter
group.
6 Press the B key to enter the selected parameter group. 7 Press the C or D key to select the required parameter. 8 Press the B key to consult the selected parameter. 9 Press the C or D key to increase, respectively decrease
the setting. (Only valid for read/write parameters.)
10 Press the B key to confirm the modified setting.
OR Press the A key to cancel the modified setting.
11 Press the A key to return to the parameter group. 12 Press 2 times the A key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display without saving any modified parameter.
Modify the r02 cooling differential parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 7.
for 1 compressor
°C
12 15
r02
r01/
r21
for 2 compressors
°C
12 13.5 15
r02
r01/
r21
Defining the heating temperature differential
Modify the r04 heating differential parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 7.
for 1 compressor
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
°C
27 30
r04
r03/
r22
for 2 compressors
°C
27 28.5 30
r04
r03/
r22
Operation manual
10
Tasks carried out using user parameters
Defining the measurement unit
Depending on the setting of user parameter /23 (measurement unit), all temperature values are displayed in °C (=0) or in °F (=1).
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
Defining the time delay between pump and compressor startup
User parameter c07 allows you to define the time delay between the pump startup and the compressor startup.
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
Defining the time delay between unit and pump shutdown
User parameter c08 allows you to define the time delay between the unit shutdown and the pump shutdown, more specifically the period during which the pump will still be active after the unit has been shut down.
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
Selecting local or remote on/off control
User parameter h07 in combination with the remote on/off switch (installed by the customer) allows the user to switch the unit on without using the D or C key on the controller.
When user parameter h07 is set to 0 (=not active), the unit can only be switched on by means of the D and C key o n t h e controller.
When user parameter h07 is set to 1 (=active), the unit can be switched on or off as follows:
When remote on/off switch is opened, then the unit is
switched off and it is not possible to switch the unit on/off while pressing the D or C key on the controller (5 sec).
When remote on/off switch is closed, then the unit is switched
on and it is possible to switch the unit on/off while pressing the D or C key on the controller (5 sec).
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
NOTE
This is only in case p34 (changeable digital input selection S9S) has value 23 (default value).
In case dual setpoint function is selected for this function (p34=13) then the remote on/off control is not activated.
Defining the timer threshold for maintenance warning
User parameter c14 allows you to define a timer threshold (running hours of the compressor) after which the controller will generate a maintenance warning or request.
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
Selecting local or remote cool/heat control
User parameter h06 in combination with the remote cool/heat selection switch (installed by the customer) allows the user to select cooling or heating mode without using the D or C key on the controller.
When user parameter h06 is set to 0 (=not active), cooling or heating mode is determined by means of the controller.
When user parameter h06 is set to 1 (=active), cooling or heating mode is determined by means of the remote switch.
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
NOTE
This is only in case p09 (changeable digital input selection S7S) has value 9 (default value).
In case dual setpoint function is selected for this function (p09=13) then the remote cool/heat control is not activated. Meaning the D or C keys on the controller are still active.
Selecting dual setpoint control
User parameters p09 (changeable digital selection S7S) and p34 (changeable digital selection S9S) can be used to assign the dual setpoint control to S7S or S9S.
There are 3 different controls available for 2 different change digital inputs (S7S and S9S):
p09: changeable digital input selection S7S
0=no function
9=remote cool/heat
13=remote dual setpoint
p34: changeable digital input selection S9S
0=no function
13=remote dual setpoint
23=remote on/off
When dual setpoint switch is open, the first setpoint is activated (r01 cooling setpoint or r03 heating setpoint, depending on cooling or heating operation).
When dual setpoint switch is closed, the second setpoint is activated (r21 cooling setpoint 2 or r22 heating setpoint 2, depending on cooling or heating operation).
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.
Operation manual
11
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Locking the controller keyboard
General information about the Modbus protocol
Once user parameter h09 is set to 0, the following advanced features can no longer be carried out by means of the controller:
modifying direct and user parameters (parameters can be displayed but not modified),
resetting the timers.
switching the unit on/off in cooling or heating
When user parameter h09 is set to 1, the above-described advanced features can be carried out using the controller.
To modify user parameter h09 value from 1 to 0, the standard user parameter modification procedure can be used with the standard password "22". Refer to "How to consult and modify the user parameters" on page 10.
To modify user parameter h09 value from 0 to 1, the user parameter modification procedure can be used with dedicated password "11". Refer to "How to consult and modify the user parameters" on page 10.

BMS CONNECTION MODBUS

By installing the optional kit address card EKAC10C, you will be able to communicate with your chiller through a Building Management System or supervisory system via the Modbus protocol.

General description of Modbus

The address card communicates using the Modbus protocol.
Different parts of the communication network
The communication network consists of two major players:
The Building Management System (BMS) or supervisory
system.
The chiller or multiple chillers.
The BMS or other supervisory system is able to communicate
with the chillers through the address card. The management of the communication occurs in accordance with a master-slave structure in polling, where the supervising BMS is the master and the address cards are the slaves.
The chiller unit can be identified by the supervisor through the assignment of an address within the Modbus network. The address of the chiller unit can be programmed during the configuration of the BMS settings.
The variables database of every chiller with installed address card is the point of reference for the supplier of the supervisory system in Modbus to assign a suitable meaning to the variables. The variables can be read and/or written by the supervisory system. Whether the variables are read-only or read/write depends on the connected chiller and/or the application program being used.
- If the supervisory system assigns a value to a variable with
read-only status, the command will not be executed at all.
-Variables requested by the supervisory system that are not
available in a chiller with an address card are sent from the address card to the supervisory system with zero value. The supervisory system will have to manage these properly.
-In case the supervisory system tries to write a value of a
parameter that is out of range, the writing will be ignored.
The Modicon Modbus protocol implemented in the address card complies with the content of the following document:
Modicon Modbus Protocol
Reference Guide
June 1996, PI-MBUS-300 Rev. J
The Modbus protocol implemented is of the RTU (Remote Terminal Unit) type based on character tranmission times. The configuration uses the multi-drop feature of RS485. The address sent within the Modbus packet addresses the chiller unit.
Implemented RS485 communication settings for the Modbus protocol
The RS485 communication settings are implemented as follows:
Baud-rate: 9600
Stop bit: 2
Parity: none
Implemented commands for the Modbus protocol
The implemented commands in the program are as listed:
Modbus command Meaning Notes
01 read coil status Read digital
02 read input
status
03 read holding
registers
04 read input
registers
05 force single coil Write individual
06 preset single
register
15 force multiple
coils
16 preset multiple
registers
variable(s)
Read digital variable(s)
Read analogue variable(s)
Read analogue variable(s)
digital variable(s) Write individual
analogue variable(s) Write series of
digital variables
Write series of analogue variables
Note that:
Due to the variety of chillers with installed address cards, no distinction is made between input variables (with read-only status) and output variables (with read/write status) so that the knowledge of the database and its management depends on the part present on the supervisory system.
Due to the general nature of the system, the address card answers in the same way to various Modbus commands.
obtains current status (ON/ OFF) of a group of logic coils or discrete input
obtains current status (ON/ OFF) of a group of logic coils or discrete input
obtains current binary value in one or more holding registers
obtains current binary value in one or more holding registers
forces single coil to ON or OFF status
places a specific binary value into a holding register
forces a series of consecutive logic coils to be defined to ON or OFF status
places specific binary values into a series of consecutive holding registers
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
12
Data representation of the Modbus protocol
Digital All digital data is coded by a single bit:
"0" for OFF
"1" for ON.
All digital variables are assigned to bits of consecutive registers, each one having:
the lower-address variable assigned to the less significant bit
the higher-address variable assigned to the most significant
bit.
Analogue and integer data An analogue and integer value is represented by a 16-bit W ORD register in binary notation. For each register, the first byte contains the high order bits and the second byte contains the low order bits.
The analogue variables are represented in tenths:
for example, the value 10.0 is transmitted as 0064h=100d for example, the value –10.0 is transmitted as FF9Ch=–100d
The integer variables are transferred using the effective
value: for example, the value 100 is transmitted as 0064h=100d
The address card operates on registers where one register must be considered at 16-bit.
In case the BMS or supervisory system tries to wr ite a value of a parameter that is out of range, the writing will be ignored.

Implemented error code

Code Modbus interpretation Condition
1 Illegal function Message is not supported or the
number of variables required is greater than the allowed limit (length 20)
Defining the BMS setting
Activating the Modbus protocol
The Modbus protocol is activated by setting the h23 par ameter to 1. This is a user parameter, ref er to "Ho w to consult and modify the user
parameters" on page 10.
Defining the unit's serial address
To define each unit's unique serial address required for communication with the supervisionary system, set parameter h10.
This is a user parameter, ref er to "Ho w to consult and modify the user parameters" on page 10.

Variables database

The BMS or supervisory system and the chiller unit communicate through a fixed set of variables, also called address numbers. Hereafter, you will find the infor mation you need about the digital, integer and analogue variables that the BMS or supervisory system can read from or write to the address card of the chiller.
For addresses of all the direct and user parameters refer to "Overview of the direct and user parameters" on page 9.
Overview of all variables which are not direct or user parameters
Description
Circuit alarm
General alarm
NTC Probe alarm
Input of flowswitch
alarm
Input of
changeable digital
S7S input
Input of high
pressure or
discharge protector
or overcurrent
alarm
Input of low
pressure switch
alarm
Input of
changeable digital
S9S input
Output of
compressor 1
Output of
compressor 2
Output of pump
Output of reversing
valve
Output of alarm
On or off
Cooling or heating
(a) D=digital.
1=A1, HP1, or LP1 alarm codes active
0=no alarm code active
1=FL alarm code
0=no alarm code active
1=E1, E2, or E3 alarm
codes
0=no alarm code active
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=cooling
0=heating
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read/
write
Read/
write
Modbus address
Parameter
type
41 D
45 D
46 D
53 D
54 D
55 D
56 D
57 D
59 D
60 D
61 D
62 D
63 D
64 D
65 D
(a)
Operation manual
13
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU

TROUBLESHOOTING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will save you time and money.
When carrying out an inspection on the supply panel or on the switch box of the unit, always make sure that the circuit breaker of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circum­stances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer.
Symptom 1: The unit does not start, but the L LED lights up
POSSIBLE CAUSES CORRECTIVE ACTION The temperature setting is not correct. Power supply failure. Check the voltage on the supply
Blown fuse or interrupted protection device.
Loose connections. Inspect connections of the field
Shorted or broken wires. Test circuits using a tester and repair
Symptom 2: The unit does not start, but the
POSSIBLE CAUSES CORRECTIVE ACTION The flowstart timer is still running. The unit will start after approx. 15
The anti-recycling timer is still active. The circuit can only start up after
The guard timer is still active. The circuit can only start up after
Symptom 3: The unit does not start and the
POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety de vices is
activated:
•Reverse phase protector
•Overcurrent relay (K*S)
•Discharge thermal protector (Q*D)
•Evaporating temperature thermostat (S*T)
•Flow switch (S10L)
•High pressure switch (S*HP)
The unit is in anti-freeze alarm. Check on the controller and refer to
The remote ON/OFF input is enabled and the remote switch is off.
The keyboard is locked. The user parameter h09 is set to 0.
Check the controller setpoint.
panel. Inspect fuses and protection devices.
Replace by fuses of the same size and type (refer to chapter "Electrical specifications" on page 2).
wiring and the internal wiring of the unit. Tighten all loose connections.
if necessary.
L LED is flashing
seconds. Make sure that water is flowing through the evaporator.
approximately 6 minutes.
approximately 1 minute.
L LED does not light up
Check on the controller and refer to symptom "4. One of the following safety devices is activated". Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 8.
symptom "4. One of the following safety devices is activated". Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 8
Put the remote switch on or disable the remote ON/OFF input.
Unlock the controller keyboard.
Symptom 4: One of the following safety devices is activated
Symptom 4.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
Voltage too low. Measure the supply voltage. Overload of motor. Reset. If the failure persists, call your
RESET Push the red button on the over-
Symptom 4.2: Low pressure switch or anti-freeze alarm
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger too low.
Shortage of refrigerant. Check for leaks and refill refrigerant,
Unit is working out of its operation range.
Inlet temperature to the water heat exchanger is too low.
Flow switch is not working or no water flow.
RESET After pressure rise, the low pressure
Symptom 4.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow through the condenser is too low.
RESET After pressure decrease, the high
Symptom 4.4: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Two phases of the power supply are connected in the wrong phase position.
One phase is not connected properly.
RESET After inverting two phases or fixing
Symptom 4.5: Discharge thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Unit is working outside the operation range.
RESET After temperature decrease, the
Symptom 4.6: Flow switch is activated
POSSIBLE CAUSES CORRECTIVE ACTION
No water flow. Check the water pump.
RESET After finding the cause, the flow
Symptom 5: Unit stops soon after operation
POSSIBLE CAUSES CORRECTIVE ACTION
One of the safety devices is activated.
Voltage is too low. Test the voltage in the supply panel
measure the supply voltage.
local dealer.
current relay inside the switch box. The controller still needs to be reset.
Increase the water flow.
if necessary. Check the operation conditions of
the unit. Increase the inlet water temperature.
Check the flow switch and the water pump.
switch resets automatically, but the controller still needs to be reset.
Increase the water flow and/or check the strainer for clogging.
pressure switch resets automatically , but the controller still needs to be reset.
Invert two phases of the power supply (by licensed electrician).
Check the connection of all phases.
the power supply cables properly, the protector is reset automatically, but the unit still needs to be reset.
Check the operation condition of the unit.
thermal protector resets automatically but the controller still needs to be reset.
switch is reset automatically, but the controller still needs to be reset.
Check safety devices (refer to symptom "4. One of the following safety devices is activated").
and, if necessary, in the electrical compartment of the unit (voltage drop due to supply cables is too high).
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
14
Symptom 6: Unit runs continuously and the water temperature remains higher than the temperature set on the controller
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting on the controller is too low, respectively too high.
The heat production, respectively cold production in the water circuit is too high.
Water flow is too high. Recalculate the water flow.
Symptom 7: Excessive noises and vibrations of the unit
POSSIBLE CAUSES CORRECTIVE ACTION
Unit has not been fixed properly. Fix the unit as described in the
Check and adjust the temperature setting.
The cooling, respectively heating capacity of the unit is too low. Call your local dealer.
installation manual.

MAINTENANCE

In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
If the unit is used for air conditioning application, the described checks should be executed at least once a year. In case the unit is used for other applications, the checks should be executed every 4 months.
Compressor
• Check on oil leaks. If there is an oil leak, call your local dealer.
• Check for abnormal noises and vibrations. If the compressor is damaged, call your local dealer.
Water supply
• Check if the water connection is still well fixed.
• Check the water quality (refer to the installation manual of the unit for specifications of the water quality).
Water filters
• Check if the mesh width is 1 mm maximum.

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Do never clean the unit with water under pressure.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Refrigerant type: R410A
(1)
value: 2090
GWP
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.

Maintenance activities

The wiring and power supply must be checked by a licensed electrician.
Field wiring and power supply
• Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage marked on the identifi­cation label of the unit.
• Check the connections and make sure they are properly fixed.
• Check the proper operation of the circuit breaker and the earth leak detector provided on the local supply panel.
Internal wiring of the unit Visually check the switch box on loose connections (terminals and components). Make sure that the electrical components are not damaged or loose.
Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened.
Refrigerant circuit
• Check for leaks inside the unit. In case a leak is detected, call
your local dealer.
• Check the working pressure of the unit. Refer to paragraph
"Switching the unit on" on page 7.
Operation manual
15
Packaged water-cooled water chillers
EWWQ014~064KBW1N
D-EOMHP00908-17EU

MENU OVERVIEW

Sensor readout menu
(b01/b02/b03)
2"
DC
2"
C
C
C
C
C
C
D
D
D
D
D
D
B
A
C
C
D
D
C D
C
DC D
B
B
CD
confirm
A
=
cancel
=
C
D
C/
D
A
A+B
Main display
(a) l-p function is not used.
DC
2"
Select and read parameter
5"
/
S
A
Enter
password
5"
B
B
C
Select
parameter
setting
values s-p
or levels
l-p
D
(a)
B
A
C
C
C
C
C
parameter
Select
group
D
D
D
D
D
Select
parameter
Read and
modify
parameter
EWWQ014~064KBW1N
Packaged water-cooled water chillers
D-EOMHP00908-17EU
Operation manual
16
EWWQ014KBW1N EWWQ064KBW1N EWWQ025KBW1N EWWQ033KBW1N EWWQ049KBW1N
Kompakte wassergekühlte Kaltwassererzeuger

Bedienungsanleitung

INHALTSVERZEICHNIS Seite
Einleitung .......................................................................................... 1
Technische Daten ...................................................................................... 1
Technische Daten zur Elektrik................................................................... 2
Beschreibung.................................................................................... 2
Funktion der Hauptkomponenten .............................................................. 3
Schutzvorrichtungen..................................................................................3
Innenverkabelung – Teileübersicht ............................................................4
Vor der Inbetriebnahme..................................................................... 5
Kontrollen vor der erstmaligen Inbetriebnahme......................................... 5
Wasserzufuhr............................................................................................. 5
Allgemeine Empfehlungen......................................................................... 5
Betrieb............................................................................................... 5
Digitalregler................................................................................................ 5
Arbeiten mit den Einheiten......................................................................... 7
Erweiterte Funktionen des Digitalreglers.................................................10
Modbus für BMS-Verbindung .......................................................... 13
Allgemeine Beschreibung des Modbus-Protokolls...................................13
Implementierter Fehlercode..................................................................... 14
Festlegen der Einstellung des Gebäudeverwaltungssystems ................. 14
Variablendatenbank................................................................................. 14
Fehlerbeseitigung............................................................................ 15
Wartung........................................................................................... 16
Wichtige Informationen hinsichtlich des verwendeten Kältemittels ......... 16
Wartungsarbeiten .................................................................................... 16
Vorschriften zur Entsorgung.................................................................... 16
Menüüberblick................................................................................. 17
LESEN SIE SICH DIESE ANLEITUNG SORGFÄLTIG DURCH, BEVOR SIE DIE EINHEIT IN BETRIEB NEHMEN. WERFEN SIE SIE NICHT WEG. BEWAHREN SIE SIE AUF, SO DASS SIE AUCH SPÄTER NOCH DARIN NACHSCHLAGEN KÖNNEN. Lesen sie sich unbedingt das Kapitel "Betrieb" auf Seite 5 durch, bevor sie diese Parameter ändern.
Bei der englischen Fassung der Anleitung handelt es sich um das Original. Bei den Anleitungen in anderen Sprachen handelt es sich um Übersetzungen des Originals.
Das Gerät ist nicht konzipiert, um von folgenden Personengruppen einschließlich Kindern benutzt zu werden: Personen mit eingeschränkten körperlichen, sensorischen oder geistigen Fähigkeiten oder Personen mit mangelhafter Erfahr ung oder Wissen, es sei denn, sie sind von einer Person, die für ihre Sicherheit verantwortlich ist, darin unterwiesen worden, wie das Gerät ordnungsgemäß zu verwenden und zu bedienen ist. Kinder sollten so beaufsichtigt werden, dass gewährleistet ist, dass sie nicht mit dem Gerät spielen.

EINLEITUNG

Diese Bedienungsanleitung bezieht sich auf die kompakten wassergekühlten Kaltwassererzeuger der Reihe Daikin EWWQ-KB. Diese Einheiten sind für die Anwendung in geschlossenen Räumen vorgesehen und werden zum Kühlen und/oder Heizen verwendet. Die Einheiten lassen sich mit Verdampfereinheiten oder Luftbehandlungsgeräten von Daikin zur Klimatisierung kombinieren. Sie können zudem zur Versorgung mit Kühlwasser zur Verfahrenskühlung eingesetzt werden.
Diese Anleitung wurde erarbeitet, um eine ordnungsgemäße Funktion und Wartung der Einheit zu gewährleisten. Sie beschreibt die sachgemäße Bedienung der Einheit und gibt bei etwaigen Problemen Hilfestellung. Die Einheit ist zwar mit Schutzvorrichtungen ausgestattet; diese verhindern jedoch nicht automatisch alle Probleme, die auf unsachgemäße Bedienung oder Wartung zurückzuführen sind.
Wenden Sie sich bei hartnäckigen Störungen an Ihren Daikin­Händler.
Achten Sie vor dem ersten Einschalten der Einheit darauf, dass sie korrekt installiert wurde. Lesen Sie sich hierzu die mit der Einheit ausgelieferte Installationsanleitung und die Empfehlungen unter "Kontrollen vor der Erstinbetrieb­nahme" sorgfältig durch.

Technische Daten

Allgemeines EWWQ 014 025 033
Abmessungen HxBxT Maschinengewicht Anschlüsse
•Wassereinlass G 1
•Wasserauslass G 1
Allgemeines EWWQ 049 064
Abmessungen HxBxT Maschinengewicht Anschlüsse
•Wassereinlass G 1-1/2
•Wasserauslass G 1-1/2
Verdichter 014 025 033
Modell JT140L-P8Y1 Drehzahl Öltyp FVC68D Ölfüllmenge Kältemitteltyp R410A Kältemittelfüllmenge
Verdampfer 014 025 033
Typ messingverlöteter Platten-Wärmetauscher Mindestwassermenge Wasserdurchfluss-
bereich
Verflüssiger 014 025 033
Typ messingverlöteter Platten-Wärmetauscher Wasserdurchfluss-
bereich
Verdichter 049 064
Modell 2x Drehzahl Öltyp FVC68D Ölfüllmenge Kältemitteltyp R410A Kältemittelfüllmenge
Verdampfer 049 064
Typ messingverlöteter Platten-Wärmetauscher Mindestwassermenge Wasserdurchfluss-
bereich
Verflüssiger 049 064
Typ messingverlöteter Platten-Wärmetauscher Wasserdurchfluss-
bereich
(1) Die vollständigen technischen Daten sind dem technischen Datenbuch zu
entnehmen.
(1)
(rpm)
(kg)
(l/min)
(l/min)
(rpm)
(kg)
(l/min)
(l/min)
(mm)
(kg)
120 170 175
(mm)
(kg)
(l)
1,5 3,0 3,0
1,2 2,1 3,1
(l)
62 103 155
31~75 53~123 76~186
24~95 39~157 59~237
JT236DJ-Y1
(l)
(l)
2x 3,0 2x 3,0
101~247 152~373
79~314 118~474
600x600x600
600x600x1200
310 340
JT236DJ-Y1 JT315DJ-Y1
2900
2900
4,6 5,6
205 311
2x
JT315DJ-Y1
Bedienungsanleitung
1
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU

Technische Daten zur Elektrik

(1)
Allgemeines EWWQ 014 025 033
Netzanschluss
• Phase 3N~
•Frequenz
• Spannung
• Spannungstoleranz
• Empfohlene Sicherungen (aM) 16 gG 25 gG 25 gG
Verdichter
• Phase 3~
•Frequenz
• Spannung
• Nennbetriebsstrom(A)6,5 10,5 15,0
Steuerung
• Phase 1~
•Frequenz
• Spannung
• Empfohlene Sicherungen (aM) werkseitig installiert
(Hz)
(%)
(Hz)
(Hz)
(V)
(V)
(V)
50
400
±10
50
400
50
230
Allgemeines EWWQ 049 064
Netzanschluss
• Phase 3N~
•Frequenz
• Spannung
• Spannungstoleranz
• Empfohlene Sicherungen (aM) 40 gG 50 gG
Verdichter
• Phase 3~
•Frequenz
• Spannung
• Nennbetriebsstrom(A) 10,5 15,0
Steuerung
• Phase 1~
•Frequenz
• Spannung
• Empfohlene Sicherungen (aM) werkseitig installiert
(Hz)
(%)
(Hz)
(Hz)
(V)
(V)
(V)
50 400 ±10
50 400
50 230

BESCHREIBUNG

Die kompakten luftgekühlten Kaltwassersätze der EWWQ-Baureihe sind in 5 Standardgrößen mit Nennkühlleistungen von 13 bis 64 kW erhältlich.
EWWQ049~064KB
18
2
14 15 16 17
3
EWWQ014~033KB
2 3
500 500
1
4
9
12
75
8611 13
Abbildung – Hauptkomponenten
1 Verdichter 2 Verdampfer 3 Verflüssiger 4 Schaltkasten 5 Kaltwasser ein 6 Kaltwasser aus 7 Verflüssiger-Wasser aus 8 Verflüssiger-Wasser ein 9 Wassertemperaturfühler am Verdampfereingang
10 Frostschutzsensor
(1) Die vollständigen technischen Daten sind dem technischen Datenbuch zu entnehmen.
500
1
1
500 500
4
11 Wassertemperaturfühler an Verflüssigerreingang 12 Steuerung mit digitaler Anzeige 13 Netzanschluss 14 Kugelventil (bauseitig) 15 Wasserfilter (bauseitig) 16 Entlüftungsventil (bauseitig) 17 T-Anschluss für Luftaustritt (bauseitig) 18 Strömungsschalter (mit T-Anschluss) (bauseitig) 19 Hauptschalter
Für Wartung erforderlicher Abstand um die Einheit
10
500
75129
8611 141919 10
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
Bedienungsanleitung
2

Funktion der Hauptkomponenten

EWWQ014~033KB
EWWQ049~064KB
65
7
119
9
10
R3T
8
R4T
R3T
R4T
S4LP
S5LP
S4LP
12
M1C
LP
Q1D
HP
4
3
M2C
LP
Q2D
HP
M1C
LP
Q1D
HP
S1HP
S2HP
S1HP
11
R5T
R5T
9
7
910
6
Abbildung – Funktionsplan
1 Verdichter 7 Wasserauslass 2 Verflüssiger 8 Strömungsschalter (im Lieferumfang der Einheit, am Montageort installiert) 3 Filter 9 Kugelventil (im Lieferumfang der Einheit, am Montageort installiert) 4 Expansionsventil 10 Wasserfilter (im Lieferumfang der Einheit, am Montageort installiert) 5 Verdampfer 11 Entlüftungsventil (im Lieferumfang der Einheit, am Montageort installiert) 6 Wassereinlass Bauseitige Rohrleitung
Beim Durchlauf durch die Einheit ändert sich die Beschaffenheit des Kältemittels. Diese Änderungen werden durch die folgenden Hauptkomponenten verursacht:
Verdichter Der Verdichter (M*C) arbeitet wie eine Pumpe und lässt das
Anschlüsse für Wassereinlass und Wasserauslass Die Anschlüsse für Wassereinlass und Wasserauslass ermöglichen einen einfachen Anschluss der Einheit an den Wasserkreislauf des Luftbehandlungsgeräts oder an industrielle Anlagen.
Kältemittel im Kältemittelkreislauf zirkulieren. Er verdichtet den Kältemitteldampf aus dem Verdampfer, und zwar mit einem Druck, mit dem er am leichtesten im Verflüssiger verflüssigt werden kann.
Verflüssiger Der Verflüssiger wandelt den Zustand des Kältemittels vom gasförmigen in einen flüssigen Zustand um. Die durch das Gas im Verdampfer aufgenommene Wärme wird durch den Verflüssiger abgeleitet, so dass der Dampf kondensiert.
Filter Der hinter dem Verflüssiger installierte Filter filtert kleine Partikel aus dem Kältemittel heraus, so dass ein Verstopfen der Rohre verhindert wird.
Expansionsventil Das flüssige Kältemittel, das aus dem Verflüssiger kommt, gelangt über ein Expansionsventil in den Verdampfer. Das Expansionsventil bringt das flüssige Kältemittel auf einen Druck, bei dem es im Verdampfer leicht verdampft werden kann.
Verdampfer Die wichtigste Funktion des Verdampfers ist es, die Wärme aus dem Wasser, das durch ihn fließt, abzuziehen. Dies geschieht

Schutzvorrichtungen

Die Einheit ist mit allgemeinen Schutzvorrichtungen ausgestattet: Diese Vorrichtungen schalten sämtliche Schaltkreise sowie die gesamte Einheit ab.
E/A-Leiterplatte (A2P) (Eingang/Ausgang) Die E/A-Leiterplatte (A2P) ist mit einem Phasenumkehrschutz ausgestattet. Dieser Phasenumkehrschutz erkennt, wenn die 3 Phasen der Stromversorgung richtig angeschlossen wurden. Wenn eine Phase nicht angeschlossen oder wenn 2 Phasen vertauscht wurden, kann die Einheit nicht eingeschaltet werden.
Überstromrelais Das Überstromrelais (K*S) befindet sich im Schaltkasten der Einheit und schützt den Verdichtermotor bei Überlastung, Phasenausfall oder bei zu niedriger Spannung. Das Relais wurde werksseitig eingestellt und darf nicht verstellt werden. Ist es aktiviert, muss die Rücksetzung über den Schaltkasten erfolgen. Anschließend muss der Regler manuell zurückgesetzt werden.
durch Umwandlung des flüssigen Kältemittels aus dem Verflüssiger in gasförmiges Kältemittel.
Bedienungsanleitung
3
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Hochdruckschalter Der Hochdruckschalter (S*HP) ist an der Gasleitung der Einheit eingebaut und misst den Verflüssigerdruck (Druck am Austritt des Verdichters). Steigt der Druck zu sehr an, wird der Druckschalter aktiviert, und der Schaltkreis wird unterbrochen. Nach Aktivierung wird der Schalter automatisch zurückgesetzt. Der Regler muss jedoch noch manuell zurückgesetzt werden.
Niederdruckschalter Der Niederdruckschalter (S*LP) ist am Saugrohr der Einheit installiert und misst den Verdampferdruck (Druck am Verdichter­eingang). Ist der Druck zu niedrig, wird der Druckschalter ausgelöst und der Stromkreis unterbrochen. Nach Aktivierung wird der Schalter automatisch zurückgesetzt. Der Regler muss jedoch noch manuell zurückgesetzt werden.
Austrittsthermoschutz Der Austrittsthermoschutz (Q*D) spricht bei einem übermäßigen Anstieg der Kältemitteltemperatur bei Austritt aus dem Verdichter an. Hat die Temperatur wieder den normalen Wert erreicht, setzt sich der Thermoschutz automatisch zurück. Der Regler muß jedoch manuell zurückgesetzt werden.
Frostschutzsensor Der Fühler für die Wassertemperatur bei Austritt (R4T) misst die Temperatur des Wassers am Ausgang des Wasserwärme­tauschers. Die Schutzvorrichtung unterbricht den Schaltkreis, wenn die Temperatur des gekühlten Wassers zu stark absinkt, um ein Einfrieren des Wassers während des Betriebs zu verhindern. Hat die Wassertemperatur bei Austritt wieder den normalen Wert erreicht, wird die Schutzvorrichtung automatisch zurückgesetzt. Der Regler muss anschließend noch manuell zurückgesetzt werden.
Sicherung für Regelkreis (F1U) Die Sicherung für den Regelkreis schützt die Kabel des Regelkreises und der Reglerkomponenten bei Kurzschlüssen.
Sicherung für Regelkreis (F4) Die Sicherung für den Regelkreis schützt die Kabel des Regelkreises bei einem Kurzschluss.
Sicherung für Digitalregler (F3U) Diese Sicherung schützt die Kabel des Digitalreglers sowie den Regler selbst bei Kurzschlüssen.
Strömungsschalter (im Lieferumfang der Einheit, am Montageort installiert) Der Strömungsschalter misst den Wasserfluss im Kreislauf. Wenn der Wasserfluss den erforderlichen Wert nicht erreicht, wird die Einheit abgeschaltet.
Kugelventil (im Lieferumfang der Einheit, am Montageort installiert) Vor und hinter dem Wasserfilter ist ein Kugelventil angebracht, so dass ein Reinigen des Filters möglich ist, ohne den Wasserkreislauf entleeren zu müssen.
Wasserfilter (im Lieferumfang der Einheit, am Montageort installiert) Der im vorderen Teil der Pumpe installierte Filter entfernt Schmutzpartikel aus dem Wasser, um eine Beschädigung der Einheit oder eine Verstopfung des Verdampfers oder Verflüssigers zu verhindern. Das Wasserfilter muss in regelmäßigen Abständen gereinigt werden.
Entlüftungsventil (im Lieferumfang der Einheit, am Montageort installiert) Die im Wassersystem des Kaltwassererzeugers verbliebene Luft wird über dieses Ventil automatisch evakuiert.
Innenverkabelung – Teileübersicht
Siehe den der Einheit beiliegenden Innenverdrahtungsplan. Die verwendeten Abkürzungen sind nachfolgend aufgeführt:
A1P........................PCB: Leiterplatte des Reglers
A2P........................PCB: E/A-Leiterplatte (Eingang/Ausgang)
A3P..............** ...... PCB: Adresskarte für BMS
A5P,A6P.......** ......PCB: Softstarter für Kreislauf 1, Kreislauf 2
A7P..............** ...... PCB: Fernbedienung
A71P......................PCB: Stromversorgungskarte
A72P......................PCB: Fernbedienung
F1,F2,F3.......# ...... Hauptsicherungen für die Einheit
F4 .................* ...... Sicherung E/A PCB
F5 ...............## ...... Träge Sicherung
F6 .................# ...... Sicherung für Pumpenschütz
F1U........................Sicherung E/A PCB
F3U........................Sicherung für Regler PCB
H3P............... * ......Anzeigelampe Alarm
H4P............... * ......Anzeigelampe Betrieb Verdichter 1
H5P............... * ......Anzeigelampe Betrieb Verdichter 2
H6P............... * ......Anzeigelampe, allgemeiner Betrieb
K1M,K2M...............Verdichterschütz Kreislauf 1, Kreislauf 2
K4S,K5S................ Überstromrelais Kreislauf 1, Kreislauf 2
K6S...............* ...... Überstromrelais Pumpe
K1P...............* ...... Pumpenstecker
M1C,M2C...............Verdichtermotor Kreislauf 1, Kreislauf 2
PE..........................Haupterdungsklemme
Q1D,Q2D...............Austrittsthermoschutz Kreislauf 1, Kreislauf 2
R3T........................Wassertemperaturfühler Verdampf ereingang
R4T........................Wassertemperaturfühler Verdampf erausgang
R5T........................T emperaturfühler Verflüssigereingang
S1HP,S2HP............Hochdruckschalter Kreislauf 1, Kreislauf 2
S4LP,S5LP............. Niederdruckschalter Kreislauf 1, Kreislauf 2
S7S...............* ...... Schalter für Fernwahl Kühlung/Heizung oder
dualen Sollwert
S9S...............* ...... Schalter für Fern-Start/Stopp oder dualen
Sollwert
(2)
(2)
S10L...................... Strömungsschalter
S12M..................... Haupttrennschalter
TR1........................Trafo 230 V 24 V zur Stromversorgung der
Leiterplatte des Reglers
TR2........................Trafo 230 V ➞ 24 V zur Stromversorgung der
E/A-Leiterplatte (A2P)
Y3R........................ Umkehrventil
X1~3,X1~82A........ Anschlüsse
Nicht in der Standardausführung
Nicht als Option lieferbar Als Option lieferbar
Verbindlich # ##
Nicht verbindlich * **
(1)
(1)
(1)
(2)
(2)
(2)
(2) (2)
(2)
(2)
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
(1) sonderzubehör (2) bauseitig
Bedienungsanleitung
4

VOR DER INBETRIEBNAHME

Kontrollen vor der erstmaligen Inbetriebnahme

Überprüfen Sie, ob der Hauptschalter der Einheit auf der Verteilertafel ausgeschaltet ist.
Überprüfen Sie nach der Installation der Einheit und vor dem Einschalten des Hauptschalters folgende Punkte:
1 Bauseitige Verkabelung
Überprüfen Sie, ob die bauseitige Verdrahtung gemäß den in der Installationsanleitung enthaltenen Anleitungen, den Elektroschaltplänen und den europäischen und nationalen Vorschriften durchgeführt wurde.
2 Sicherungen oder Schutzvorrichtungen
Überprüfen Sie, ob Größe und Ausführung der Sicherungen oder der bauseitig installierten Schutzvorrichtungen der Installationsanleitung entsprechen. Achten Sie außerdem darauf, dass keine Sicherung und keine Schutzvorrichtung überbrückt wurde.
3 Erdung
Achten Sie darauf, dass die Erdungsleitungen ordnungsgemäß angeschlossen und die Erdungsklemmen festgezogen sind.
4 Innenverkabelung
Überprüfen Sie den Schaltkasten auf lose Verbindungen oder beschädigte elektrische Bauteile.
5 Verankerung
Überprüfen Sie, ob die Einheit ordnungsgemäß verankert wurde, um bei Inbetriebnahme ungewöhnliche Betriebs­geräusche und Vibrationen zu vermeiden.
6 Beschädigte Ausrüstung
Überprüfen Sie die Einheit innen auf beschädigte Teile oder zusammengedrückte Rohrleitungen.
7 Austritt von Kältemittel
Überprüfen Sie das Innere der Einheit auf austretendes Kältemittel. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
8 Austritt von Öl
Überprüfen Sie den Verdichter auf austretendes Öl. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
9 Anschlussspannung
Überprüfen Sie die Netzspannung auf der Verteilertafel. Die Spannung muss mit der auf dem Typenschild der Einheit angegebenen Spannung übereinstimmen.

Allgemeine Empfehlungen

Lesen Sie sich vor dem Einschalten der Einheit die folgenden Empfehlungen durch:
1 Schließen Sie alle Frontblenden der Einheit, nachdem sämtliche
Installationsarbeiten und Einstellungen vorgenommen wurden.
2 Die Bedienungstafel des Schaltkastens darf nur von einem
zugelassenen Elektriker zu Wartungszwecken geöffnet werden.

BETRIEB

Die Geräte der Baureihe EWWQ sind mit einem Digitalregler ausgestattet, der die Inbetriebnahme, die Anwendung und die Wartung des Geräts besonders bedienerfreundlich macht.
Dieser Teil der Anleitung ist funktionsorientiert und modular aufgebaut. Mit Ausnahme des ersten Abschnitts, der einen kurzen Überblick über den Regler selbst vermittelt, behandelt jeder Abschnitt oder Unterabschnitt eine bestimmte Funktion der Einheit.

Digitalregler

Benutzerschnittstelle
Der Digitalregler verfügt über ein numerisches Display, vier beschriftete Tasten und LED-Anzeigen, mit denen zusätzliche Benutzerinformationen abgerufen werden können.
Abbildung – Digitalregler
Abbildung – Fernbedienung (Optionssatz)

Wasserzufuhr

Füllen Sie die Wasserleitungen, und halten Sie sich dabei an die für die Einheit erforderliche Mindestwassermenge. Weitere Informationen finden Sie im Kapitel "Füllmenge, Durchfluss und Qualität des Wassers" in der Installationsanleitung.
Achten Sie darauf, dass das Wasser der in der Installationsanleitung aufgeführten Qualität entspricht.
Entlüften Sie die oben gelegenen Stellen des Systems, und überprüfen Sie den Betrieb der Umwälzpumpe und des Strömungsschalters.
Bedienungsanleitung
5
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Tasten auf dem Regler:
Welche Funktion beim Drücken einer oder einer Kombination dieser Tasten ausgeführt wird, hängt davon ab, in welchem Status sich Regler und Einheit zu diesem Zeitpunkt befinden.
Digitalregler-
Tasten
AT
BU
A + BS
CC
DD
C + DR
Fernbedienungs-
tasten
Hauptanzeige Sensorausgabemenü Parameterauswahlmenü Parametereinstellmenü
5 Sekunden lang drücken: Zugriff auf DIREKTE Parameter
5 Sekunden lang drücken: A + B ODER Einmal drücken:
S
Zugriff auf BENUTZER-Parameter (nach Eingabe des BENUTZER­Kennworts)
5 Sekunden lang drücken: Einheit in Betriebsart "Heizen" ein-/ ausschalten Einmal drücken: Direkter Zugriff auf Sensorausgabemenü (b01/b02/b03)
5 Sekunden lang drücken: Einheit in Betriebsart "Kühlen" ein-/ ausschalten Einmal drücken: Direkter Zugriff auf Sensorausgabemenü (b01/b02/b03)
5 Sekunden lang drücken: Manuelle Alarmzurücksetzung im Alarmfall
Einmal drücken:
Zurückkehren
Einmal drücken:
Vorherigen
Sensorparameter
auswählen
Einmal drücken:
Nächsten
Sensorparameter
auswählen
Einmal drücken:
Zurückkehren
Einmal drücken:
Parametergruppe oder
Parameter auswählen
Einmal drücken:
Vorherige P arameterg ruppe
oder vorherigen Parameter
auswählen
Einmal drücken:
Nächste Parametergruppe
oder nächsten Parameter
auswählen
Einmal drücken:
Abbrechen und
zurückkehren
Einmal drücken:
Bestätigen und
zurückkehren
Einmal drücken:
Wert erhöhen
Einmal drücken:
Wert verringern
LED-Anzeigen auf dem Regler und der Fernbedienung:
Funktion – Hauptanzeige (nicht im Menü)
Digitalregler-LEDs
P
F
(bernsteinfarben)
G
(bernsteinfarben)
H
L
(bernsteinfarben)
M
(bernsteinfarben)
&
(bernsteinfarben)
é
(bernsteinfarben)
LED (grün) Z
LED
LED
LED (rot) Y
LED
LED
LED
LED
Fernbedienung
F
G
L
M
&
é
Hauptanzeige
Wassertemperatur bei Eintritt. Zeigt an, dass der
Heizbetrieb aktiviert ist. Zeigt an, dass der
Kühlbetrieb aktiviert ist. Zeigt an, dass der Alarm
aktiviert ist. Zeigt den Status der Pumpe
an Zeigt an, dass mindestens
ein Verdichter aktiviert ist. LED leuchtet ständig: Zeigt
an, dass Verdichter 1 aktiv ist. LED blinkt: Zeigt eine Startanforderung von Verdichter 1 an.
LED leuchtet ständig: Zeigt an, dass Verdichter 2 aktiv ist. LED blinkt: Zeigt eine Startanforderung von Verdichter 2 an.
Beim Auswählen einer Parametergruppe oder eines Parameters werden verschiedene LEDs in Bezug auf die Parametergruppe oder den Parameter angezeigt.
Beispiel: Die LEDs F und G werden beim Zugriff auf eine Parametergruppe oder beim direkten Zugriff auf Parameter angezeigt.
Direkte Parameter und Benutzerparameter
Der Digitalregler stellt direkte Parameter und Benutzerparameter zur Verfügung. Die direkten Parameter sind für den täglichen Einsatz der Einheit wichtig, beispielsweise zum Einstellen der Temperatur oder zum Abrufen von aktuellen Betriebsinformationen. Die Benutzer­parameter bieten andererseits erweiterte Funktionen wie das Einstellen von Zeitverzögerungen.
Jeder Parameter wird durch einen Code und einen Wert definiert. Der Parameter, mit dem beispielsweise die lokale Regelung oder Fernregelung Ein/Aus ausgewählt wird, hat den Code h07 und den Wert 1 oder 0.
Einen Überblick über die Parameter finden Sie unter "Übersicht über die direkten Parameter und Benutzerparameter" auf Seite 10.
HINWEIS
Temperaturausgabetoleranz: ±1°C. Durch Einstrahlung von direktem Sonnenlicht kann die
Lesbarkeit des numerischen Displays beeinträchtigt werden.
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
Bedienungsanleitung
6

Arbeiten mit den Einheiten

Dieses Kapitel behandelt den alltäglichen Betrieb der Einheiten. Es erläutert Ihnen unter anderem die folgenden Routinefunktionen:
"Einschalten der Einheit" auf Seite 7 und "Ausschalten der Einheit" auf Seite 7,
"Ändern der Temperatureinstellung für den Kühlbetrieb" auf Seite 8 und "Ändern der Temperatureinstellung für den Heizbetrieb" auf Seite 8,
"Abrufen der aktuellen Betriebsinformationen" auf Seite 8,
"Rücksetzen bei einer Störung" auf Seite 8,
"Zurücksetzen von Warnmeldungen" auf Seite 9.
Einschalten der Einheit
Um die Einheit im Kühlbetrieb einzuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste D, die LED G
wird angezeigt.
Um die Einheit im Heizbetrieb einzuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste C, die LED F
wird angezeigt.
Dann wird in beiden Fällen ein Initialisierungszyklus gestartet, die LED L, die LED M, die LED & und die LED é leuchten je nach der programmierten Thermostatfunktion.
Wenn die LED & oder die LED é blinkt, liegt eine Startanforderung von Verdichter 1 oder 2 vor. Der Verdichter wird gestartet, wenn der Zeitgeber den Wert 0 erreicht hat.
HINWEIS
2 Wenn die Einheit zum ersten Mal in Betrieb genommen wird,
3 Nimmt die Einheit nach einigen Minuten den Betrieb nicht auf,
Bei Aktivierung der Fernregelung Ein/Aus siehe "Auswählen der lokalen Ein/Aus-Regelung oder Fern­regelung Ein/Aus" auf Seite 12.
oder wenn sie über einen längeren Zeitraum nicht in Betrieb war, sollte die folgende Checkliste durchgegangen werden.
Ungewöhnliche Geräusche und Vibrationen
Achten Sie darauf, dass die Einheit keine ungewöhnlichen Geräusche oder Vibrationen verursacht: Überprüfen Sie Verankerung und die Leitungen. Erzeugt der Verdichter ungewöhnliche Geräusche, kann dies auch daran liegen, dass zu viel Kältemittel eingefüllt wurde.
Betriebsdruck
Hoch- und Niederdruck des Kältemittelkreislaufs müssen überprüft werden, um den ordnungsgemäßen Betrieb der Einheit zu gewährleisten und um sicherzustellen, dass die Nennleistung erzielt wird.
Die gemessenen Druckwerte schwanken zwischen einem Höchst- und einem Mindestwert. Dies ist von Wasser- und Außentemperatur abhängig (zum Zeitpunkt der Messung).
lesen Sie sich die Betriebsinformationen durch, die in der Liste der direkten Parameter aufgeführt sind. Siehe auch Kapitel "Fehlerbeseitigung" auf Seite 15.
Ausschalten der Einheit
Um die Einheit im Kühlbetrieb auszuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste D, die LED G
erlöscht.
Um die Einheit im Heizbetrieb auszuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste C, die LED F
erlöscht.
HINWEIS
Bei Aktivierung der Fernregelung Ein/Aus siehe "Auswählen der lokalen Ein/Aus-Regelung oder Fern­regelung Ein/Aus" auf Seite 12.
Abrufen und Ändern der direkten Parameter
Einen Überblick über die Menüstruktur finden Sie unter "Menüüberblick" auf Seite 17.
1 Drücken Sie 5 Sekunden lang die Taste B in der
Hauptanzeige. Die Parametergruppe -/- wird angezeigt.
2 Drücken Sie die Taste C oder D zum Auswählen der
gewünschten Parametergruppe.
3 Drücken Sie die Taste B zum Eingeben der ausgewählten
Parametergruppe.
4 Drücken Sie die Taste C oder D zum Auswählen des
gewünschten Parameters.
5 Drücken Sie die Taste B zum Abrufen des ausgewählten
Parameters.
6 Drücken Sie zum Erhöhen bzw. Senken des Werts des
ausgewählten Parameters die Taste C oder D. (Nur gültig für Lese-/Schreibparameter.)
7 Drücken Sie die Taste B zum Bestätigen der modifizierten
Einstellung. ODER Drücken Sie die Taste A, um die modifizierte Einstellung nicht zu übernehmen.
8 Drücken Sie die Taste A, um zur Parametergruppe
zurückzukehren.
9 Drücken Sie 2-mal die Taste A, um zur Hauptanzeige
zurückzukehren.
Wenn während einer Maßnahme 30 Sekunden lang keine Taste gedrückt wird, beginnt der angezeigte Parametercode oder Wert zu blinken. Wenn weitere 30 Sekunden lang keine Taste gedrückt wird, wird automatisch wieder die Hauptanzeige eingeblendet, ohne dass modifizierte Parameter gespeichert werden.
HINWEIS
Bei Fernregelung Ein/Aus (h07=1) wird empfohlen, zusätzlich zum Fernregelungsschalter einen Ein-/Aus­Schalter an der Einheit zu installieren. Die Einheit kann dann von jedem beliebigen Platz aus ausgeschaltet werden.
Die Auswahl des Kühl- oder Heizbetriebs kann nur beim Anfahren des Geräts erfolgen. Die Auswahl der jeweils anderen Betriebsart ist ohne Ausschalten des Geräts nicht möglich.
Bedienungsanleitung
7
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Abrufen der Parameter des "Sensorausgabemenüs"
Rücksetzen bei einer Störung
Einen Überblick über die Menüstruktur finden Sie unter "Menüüberblick" auf Seite 17.
Die Parameter b01/b02/b03 sind Teil des "Sensorausgabemenüs".
1 Drücken Sie in der Hauptanzeige die Taste C oder D.
Der Parameter b01 wird angezeigt. Wenn keine Taste gedrückt wird, wird der Wert des Sensors b01 angezeigt, bis C oder D wieder gedrückt wird, um einen anderen Parameter (b02 oder b03) auszuwählen.
2 Drücken Sie die Taste A, um zur Hauptanzeige
zurückzukehren.
Wenn während einer Maßnahme 30 Sekunden lang keine Taste gedrückt wird, beginnt der angezeigte Parametercode oder Wert zu blinken. Wenn weitere 30 Sekunden lang keine Taste gedrückt wird, wird automatisch wieder die Hauptanzeige eingeblendet.
Ändern der Temperatureinstellung für den Kühlbetrieb
1 Ändern Sie den Kühlungssollwertparameter r1. Dies ist ein direkter Parameter, siehe "Abrufen und Ändern der
direkten Parameter" auf Seite 7.
HINWEIS
Wenn dualer Sollwert aktiviert ist (siehe "Auswählen der dualen Einstellung" auf Seite 12).
Ändern der Temperatureinstellung für den Heizbetrieb
1 Ändern Sie den Heizsollwertparameter r3. Dies ist ein direkter Parameter, siehe "Abrufen und Ändern der
direkten Parameter" auf Seite 7.
HINWEIS
Wenn dualer Sollwert aktiviert ist (siehe "Auswählen der dualen Einstellung" auf Seite 12).
Abrufen der aktuellen Betriebsinformationen
Die Liste der direkten Parameter enthält die folgenden Betriebsinformationen:
b01:Wassertemperatur am Verdampfereingang,
b02:Wassertemperatur am Verdampferausgang,
b03: Bei eingeschaltetem Kühlbetrieb: Wassereintritts-
temperatur Verflüssiger. Bei eingeschaltetem Heizbetrieb: Wassereintrittstemperatur des Verdampfers.
c10: Gesamtbetriebsstunden des Verdichters 1,
c11: Gesamtbetriebsstunden des Verdichters 2,
c15: Gesamtbetriebsstunden der Pumpe.
HINWEIS
Dies sind direkte Parameter, siehe "Abr ufen und Ändern der direkten Parameter" auf Seite 7.
Die Parameter b01, b02 und b03 können auch über das "Sensorausgabemenü" abgerufen werden. Siehe "Abrufen der Parameter des "Sensorausgabemenüs"" auf Seite 8.
Informationen zum Zurücksetzen der Zeitgeber der Parameter c10, c11 und c15 finden Sie unter "Zurücksetzen von Warnmeldungen" auf Seite 9.
Bei Feststellung einer Störung geschieht Folgendes:
Das Alarmrelais wird aktiviert.
die LED H wird angezeigt
Das Display beginnt zu blinken und zeigt abwechselnd den
Störungs-Code und die Wassertemperatur bei Eintritt an.
Das Display kann die folgenden Störungscodes anzeigen:
a1:zeigt eine Störung der Frostschutzvorrichtung an.
e1:zeigt an, dass der NTC-Fühler zur Messung der
Verdampferwassertemperatur beim Eintritt defekt ist.
e2:zeigt an, dass der NTC-Fühler zur Messung der Verdampferwassertemperatur beim Austritt defekt ist.
e3:zeigt an, dass die Sicherung der Verdampferheizung (F4) durchgebrannt ist, dass ein Phasenumkehrfehler vorliegt oder dass es ein Problem mit der E/A-Leiterplatte (A2P) gibt.
Wenn die Einheit mit einer Frostschutzvorrichtung ausgestattet ist, ist es empfehlenswert, die Warnlampe für die Ferndiagnose (H3P) zu installieren (siehe den der Einheit beiliegenden Elektroschalt­plan). Dadurch kann ein Durchbrennen der Sicherung der Verdampferheizung (F4) früher erkannt werden. Außerdem kann so ein Einfrieren des Kreislaufs bei kaltem Wetter vermieden werden.
ehs:zeigt an, dass die Versorgungsspannung zu hoch ist. Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
el1:zeigt einen Fehler bei der Stromversorgung an (Beispiel: Rauschen). Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
el2:zeigt einen Fehler bei der Stromversorgung an (Beispiel: Rauschen). Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
els:zeigt an, dass die Versorgungsspannung zu niedrig ist. Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
epb:zeigt an, dass der EEPROM auf der Leiterplatte des Reglers in der Einheit defekt ist.
epr:zeigt an, dass der EEPROM auf der Leiterplatte des Reglers in der Einheit defekt ist.
fl:zeigt an, dass während der 15 Sekunden, nachdem die Pumpe gestartet wurde, oder während der 5 Sekunden bei aktiviertem Verdichter nur ungenügender Wasserdurchfluss vorhanden war oder dass der Überstromschutz der Pumpe aktiviert wurde.
hp1:zeigt an, dass ein Hochdruckschalter, der Austrittsthermo- schutz oder der Überstromschutz des Verdichtermotors aktiviert oder dass der NTC-Fühler zum Messen der Umgebungstemperatur defekt ist.
fl + hp1:
zeigt an, dass höchstwahrscheinlich ein RPP-Fehler vorliegt oder dass die Sicherung F4 durchgebrannt ist.
lp1:zeigt an, dass der Niederdruckschalter aktiviert ist.
ter:zeigt an, dass ein Datenübertragungsfehler bei der
Fernbedienung vorliegt.
:
Datenübertragung zwischen dem Digitalregler der Einheit und der Fernbedienung ist gestört. Prüfen Sie die k orrekte Auswahl des Parametercodes h23. Dies sollte die Standardeinstellung 0 sein, und prüfen Sie, ob die Installation gemäß der Installationsanleitung der Fernbedienung EKRUMCA korrekt ist.
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
HINWEIS
Wenn die Störungs-Codes fl und h1 abwechselnd blinken, wird die Störung wahrscheinlich vom Phasenumkehrschutz oder von der durchgebrannten Sicherung für die Verdampferheizung (F4) verursacht.
Bedienungsanleitung
8
So setzen Sie einen Alarm zurück:
1 Stellen Sie fest, weshalb die Einheit abgeschaltet wurde, und
beheben Sie die Ursache. Siehe Kapitel "Fehlerbeseitigung" auf Seite 15.
2 Wenn der Störungscode a1, fl, hp1 oder lp1 auf dem
Display angezeigt wird, setzen Sie die Störungsmeldung manuell zurück, indem Sie die E-Kombinationstasten C und D gleichzeitig ca. 5 Sekunden lang drücken.
In allen anderen Fällen wird der Alarm automatisch zurückgesetzt.
Nach Rücksetzen des Alarms werden der Störungscode und die LED H nicht mehr auf dem Display angezeigt. Der Regler setzt seinen normalen Betrieb fort und zeigt die Wassertemperatur bei Eintritt an.
Zurücksetzen von Warnmeldungen
Die Anzeige des Reglers kann im Normalbetrieb zu blinken beginnen und abwechselnd die Wassertemperatur bei Eintritt und folgenden Warncode anzeigen:
hc1:zeigt an, dass Verdichter 1 gewartet werden muss: Die Gesamtbetriebsstunden des Verdichters 1 (direkter Parameter c10) haben die Zeitschaltuhrschwelle für die Wartungswarnmeldung überschritten (Benutzerparameter c14).
hc2:zeigt an, dass Verdichter 2 gewartet werden muss: Die Gesamtbetriebsstunden des Verdichters 2 (direkter Parameter c11) haben die Zeitschaltuhrschwelle für die Wartungswarnmeldung überschritten (Benutzerparameter c14).
So setzen Sie die Wartungswarnmeldung hc1 oder hc2 zurück:
1 Rufen Sie c10, Betriebsstunden von Verdichter 1, oder c11,
Betriebsstunden von Verdichter 2, ab. Dies sind direkte Parameter, siehe "Abrufen und Ändern der direkten Parameter" auf Seite 7.
2 Wenn der Parameterwert c10 oder c11 angezeigt wird,
drücken Sie 5 Sekunden lang gleichzeitig die Tasten C und D. Der Wert des Zeitgebers ändert sich auf 0 und der Warnhinweis wird zurückgesetzt.
HINWEIS
Vergessen Sie nicht, nach dem Zurücksetzen der Zeitschaltuhren die erforderlichen Wartungsarbeiten durchzuführen.
Neben den Zeitgebern c10 und c11 kann auch der Zeitgeber c15 (Betriebsstunden der Pumpe) in derselben Weise zurückgesetzt werden.
Bedienungsanleitung
9
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU

Erweiterte Funktionen des Digitalreglers

Dieses Kapitel gibt Ihnen einen Überblick über die direkten Parameter und Benutzerparameter, die der Regler bietet. Im folgenden Kapitel erfahren Sie, wie Sie die Einheit über diese Parameter einrichten und konfigurieren können.
Übersicht über die direkten Parameter und Benutzerparameter
Die Liste der direkten Parameter können Sie aufrufen, indem Sie die Taste B ca. 5 Sekunden lang drücken. Siehe auch "Abrufen und Ändern der direkten Parameter" auf Seite 7.
Parameter-
gruppe
Parameter-
code
-/- /23
Maßeinheit
Beschreibung
0=°C 1=°F
Standard-
wert
Min. Max. Einheiten
Lesen/
Schreiben
Benutzerp. /Direkter P.
Modbus-
Adresse
001 L/S B5 D
-a- Kein Benutzerparameter oder direkter Parameter verfügbar b01 Wassertemperatur am Verdampfereingang 0,1°C L D 102 A b02 Wassertemperatur am Verdampferausgang 0,1°C L D 103 A
-b-
Bei eingeschaltetem Kühlbetrieb: Wassereintrittstemperatur des Verflüssigers.
b03
Bei eingeschaltetem Heizbetrieb:
0,1°C L D 104 A
Wassereintrittstemperatur des Verdampfers. Zeitverzögerung zwischen Pumpenstart
-c-
c07
und Verdichterstart Zeitspanne zwischen dem Abschalten der
c08
Einheit und dem Abschalten der Pumpe Gesamtbetriebsstunden des Verdichters 1 x100
c10
Gesamtbetriebsstunden des Verdichters 2 x100
c11
Grenzwert für Wartungswarnhinweis
c14
(c10 und c11) Gesamtbetriebsstunden der Pumpe x100
c15
15 0 999 1 Sek. L/S B 238 G
00150 1 Min. L/S B 239 G
LD122 A
LD123 A
L/S B 241 G
LD126 A
00100
Stunden
Stunden
x100
Stunden
Stunden
-d- Kein Benutzerparameter oder direkter Parameter verfügbar
-f- Kein Benutzerparameter oder direkter Parameter verfügbar
Zum Aktivieren der Fernregelung "Kühlen/ Heizen"
h06
0=nicht aktiv 1=aktiv
001 L/S B 14 D
(nur wenn p09=9) Zum Aktivieren der Fernregelung Ein/Aus
0=nicht aktiv
h07
1=aktiv
001 L/S B 15 D
(nur, wenn p34=23)
-h-
Zum Sperren oder Freigeben der Reglertastatur
h09
0=sperren
101 L/S B 16 D
1=freigeben Serielle Adresse für Verbindung mit
h10
Gebäudeverwaltungssystem
11200 L/S B 256 G
Zum Auswählen einer Adresskartenverbindung
h23
0=Fernbedienungsverbindung
001 L/S B 11 D
1=MODBUS-Verbindung Variable Auswahl der digitalen Eingabe S7S
0=keine Funktion 9=Fernregelung "Kühlen/Heizen"
p09
(nur aktiv in Kombination mit h06)
9027 L/S B 277 G
13=dualer Sollwert – Fernbedienung KEINE ANDEREN WERTE AUSWÄHLEN
-p-
Änderbare Auswahl der digitalen Eingabe S9S
0=Keine Funktion
p34
13=dualer Sollwert aus der Ferne 23=Fernbedienung Ein/Aus
(nur aktiv in Kombination mit h07)
23 0 27 L/S B 329 G
KEINE ANDEREN WERTE AUSWÄHLEN
r01
Sollwert für Kühlung
12,0
(b)
25,0 0,1°C L/S D 41 A
8,0
r02 Kühlungsunterschied 3,0 0,3 19,9 0,1°C L/S D 42 A
-r-
r03 Sollwert für Heizung 30,0 15,0 50,0 0,1°C L/S D 43 A r04 Unterschied beim Heizen 3,0 0,3 19,9 0,1°C L/S D 44 A
r21
Sollwert 2 für Kühlung
r22
Sollwert 2 für Heizung
(c) (c)
12,0 30,0 15,0 50,0 0,1°C L/S D 56 A
(b)
25,0 0,1°C L/S D 55 A
8,0
-t- Kein Benutzerparameter oder direkter Parameter verfügbar
f-r h99 Softwareversion LD208 G
(a) D=digital, A=analog, G=Ganzzahl. (b) –2,0 und –7,0 nur für Einheiten mit Glykolanwendungen gültig. (c) Wird verwendet, wenn dualer Sollwert in p09 oder p34 aktiviert ist und der Digitaleingang für dualen Sollwert geschlossen ist.
Parameter-
(a)
typ
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
Bedienungsanleitung
10
Abrufen und Ändern der Benutzerparameter
Definieren des Temperaturunterschieds für den Kühlbetrieb
HINWEIS
Beim Abrufen von Benutzerparametern werden auch die direkten Parameter angezeigt.
Einen Überblick über die Menüstruktur finden Sie unter "Menüüberblick" auf Seite 17.
1 Drücken Sie beim Digitalregler die Tasten A und B etwa
5 Sekunden lang, bis O angezeigt wird. Drücken Sie bei der Fernbedienung die Taste S einmal.
2 Geben Sie über die Tasten C und D das korrekte
Kennwort ein. Das Kennwort lautet 22.
3 Drücken Sie die Taste B, um das Kennwort zu bestätigen und
das Menü zu öffnen, s-p wird angezeigt.
4 Drücken Sie die Taste B zum Abrufen der Parameter-
einstellungen (=s-p). (l-p bedeutet Abrufen der Parameterebene, aber diese Funktion wird nicht verwendet). Die Parametergruppe -/- wird angezeigt.
5 Drücken Sie die Taste C oder D zum Auswählen der
gewünschten Parametergruppe.
6 Drücken Sie die Taste B zum Eingeben der ausgewählten
Parametergruppe.
7 Drücken Sie die Taste C oder D zum Auswählen des
gewünschten Parameters.
8 Drücken Sie die Taste B zum Abrufen des ausgewählten
Parameters.
9 Drücken Sie zum Erhöhen bzw. Verringern des
Einstellungswerts die Taste C bzw. D. (Nur gültig für Lese-/Schreibparameter.)
10 Drücken Sie die Taste B zum Bestätigen der modifizierten
Einstellung. ODER Drücken Sie die Taste A, um die modifizierte Einstellung nicht zu übernehmen.
11 Drücken Sie die Taste A, um zur Parametergruppe
zurückzukehren.
12 Drücken Sie 2-mal die Taste A, um zur Hauptanzeige
zurückzukehren.
Wenn während einer Maßnahme 30 Sekunden lang keine Taste gedrückt wird, beginnt der angezeigte Parametercode oder Wert zu blinken. Wenn weitere 30 Sekunden lang keine Taste gedrückt wird, wird automatisch wieder die Hauptanzeige eingeblendet, ohne dass modifizierte Parameter gespeichert werden.
Ändern Sie den Differenzparameter r02 für den Kühlbetrieb. Dies ist ein direkter Parameter, siehe "Abrufen und Ändern der
direkten Parameter" auf Seite 7.
bei 1 Verdichter
Verdichter
EIN
AUS
12 15
r02
r01/
Wassertemperatur
bei Eintritt in den
°C
Verdampfer
r21
bei 2 Verdichtern
Verdichter
EIN
AUS
EIN
AUS
12 13.5 15
r02
r01/
Wassertemperatur
bei Eintritt in den
°C
Verdampfer
r21
Definieren des Temperaturunterschieds für den Heizbetrieb
Ändern Sie den Differenzparameter r04 für den Heizbetrieb. Dies ist ein direkter Parameter, siehe "Abrufen und Ändern der
direkten Parameter" auf Seite 7.
bei 1 Verdichter
Verdichter
EIN
AUS
27 30
r04
r03/
r22
Wassertemperat
ur bei Eintritt
(Verflüssiger)
°C
Bedienungsanleitung
11
Verdichter
EIN
AUS
EIN
AUS
bei 2 Verdichtern
°C
27 28.5 30
r04
Wassertemperatur
r03/
bei Eintritt
(Verflüssiger)
r22
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Funktionen, die über Benutzerparameter durchgeführt werden
Definieren der Maßeinheit
Je nach der Einstellung des Benutzerparameters /23 (Maßeinheit) werden alle Temperaturwerte in °C (=0) oder in °F (=1) angezeigt.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
Definieren der Zeitverzögerung zwischen Inbetriebnahme von Pumpe und Verdichter
Über den Benutzerparameter c07 können Sie die Zeitverzögerung zwischen Inbetriebnahme der Pumpe und Inbetriebnahme des Verdichters definieren.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
Definieren der Zeitverzögerung zwischen Abschalten der Einheit und der Pumpe
Über den Benutzerparameter c08 können Sie die Zeitverzögerung zwischen dem Abschalten der Einheit und dem Abschalten der Pumpe definieren, d. h. den Zeitraum, in dem die Pumpe noch arbeitet, nachdem die Einheit abgeschaltet wurde.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
Definieren der Zeitschaltuhrschwelle für die Wartungswarnmeldung
Auswählen der lokalen Ein/Aus-Regelung oder Fernregelung Ein/Aus
Über den Benutzerparameter h07 in Kombination mit dem Fernregelungsschalter Ein/Aus (durch den Kunden installiert) kann der Benutzer die Einheit einschalten, ohne die Taste D oder C auf dem Regler drücken zu müssen.
Wenn der Benutzerparameter h07 auf 0 (=nicht aktiv) eingestellt ist, lässt sich die Einheit nur über die Tasten D und C auf dem Regler einschalten.
Wenn der Benutzerparameter h07 auf 1 (=aktiv) eingestellt ist, lässt sich die Einheit wie folgt ein- bzw. ausschalten:
Wenn der Fernregelungsschalter Ein/Aus geöffnet ist, ist die
Einheit ausgeschaltet und lässt sich nicht durch Drücken der Taste D oder C auf dem Regler (5 Sek.) ein- oder ausschalten.
Wenn der Fernregelungsschalter Ein/Aus geschlossen ist, ist
die Einheit eingeschaltet und lässt sich durch Drücken der Taste D oder C auf dem Regler (5 Sek.) ein- oder ausschalten.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
HINWEIS
Dies ist nur möglich, wenn p34 (änderbare Auswahl der digitalen Eingabe S9S) den Wert 23 (Standardwert) hat.
Wenn dualer Sollwert für diese Funktion ausgewählt ist (p34=13), ist die Fernregelung Ein/Aus nicht aktiviert.
Über den Benutzerparameter c14 können Sie eine Zeit (Betriebsstunden des Verdichters) definieren, nach der der Regler einen Warnhinweis oder eine Anforderung zur Wartung ausgibt.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
Auswahl zwischen Standortbedienung und Fernbedienung zur Wahlschalter Heizung/Kühlung
Über den Benutzerparameter h06 in Kombination mit dem Fernauswahlschalter "Kühlen/Heizen" (durch den Kunden installiert) kann der Benutzer den Kühlbetrieb oder Heizbetrieb ohne die Taste D oder C auf dem Regler wählen.
Wenn der Benutzerparameter h06 auf 0 (=nicht aktiv) gestellt ist, wird der Kühl- oder Heizbetrieb mit dem Regler festgelegt.
Ist der Benutzerparameter h06 auf 1 (=aktiv) gesetzt, kann mittels Fernbedienungsschalter der Kühl- oder Heiz-Modus eingestellt werden.
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
HINWEIS
Dies ist nur möglich, wenn p09 (variable Auswahl der digitalen Eingabe S7S) den Wert 9 (Standardwert) hat.
Wenn dualer Sollwert für diese Funktion ausgewählt ist (p09=13), ist die Fernregelung "Kühlen/Heizen" nicht aktiviert. Bedeutet, die Taste C oder D am Regler ist nach wie vor aktiv.
Auswählen der dualen Einstellung
Die Benutzerparameter p09 (variable digitale Auswahl S7S) und p34 (variable digitale Auswahl S9S) können verwendet werden, um S7S oder S9S den dualen Sollwert zuzuweisen.
Es sind 3 verschiedene Steuerungen für 2 verschiedene digitale variable Eingaben (S7S und S9S) verfügbar:
p09: variable Auswahl der digitalen Eingabe S7S
0=keine Funktion
9=Kühlen/Heizen über Fernbedienung
13=dualer Sollwert – Fernbedienung
p34: variable Auswahl der digitalen Eingabe S9S
0=keine Funktion
13=dualer Sollwert – Fernbedienung
23=Fernbedienung Ein/Aus
Wenn der Schalter für dualen Sollwert geöffnet ist, ist der erste Sollwert aktiviert (Sollwert für Kühlung r01 oder Sollwert für Heizung r03, je nachdem, ob gekühlt oder geheizt wird).
Wenn der Schalter für dualen Sollwert geschlossen ist, ist der zweite Sollwert aktiviert (Sollwert 2 für Kühlung r21 oder Sollwert 2 für Heizung r22, je nachdem, ob gekühlt oder geheizt wird).
Dies ist ein Benutzerparameter, siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
EWWQ014~064KBW1N
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP00908-17EU
Bedienungsanleitung
12
Sperren der Reglertastatur
Allgemeine Informationen über das Modbus-Protokoll
Wenn der Benutzerparameter h09 auf 0 gesetzt ist, können die folgenden erweiterten Funktionen nicht mehr über den Regler ausgeführt werden:
Verändern der direkten Parameter und Benutzerparameter (die Parameter können zwar angezeigt, aber nicht verändert werden)
Rücksetzen der Zeitschaltuhren
Ein-/Ausschalten der Einheit im Kühl- oder Heizbetrieb
Wenn der Benutzerparameter h09 hingegen auf 1 gesetzt ist, können die oben beschriebenen erweiterten Funktionen über den Regler ausgeführt werden.
Um den Wert des Benutzerparameters h09 von 1 auf 0 zu ändern, kann die Standardänderungsmethode für Benutzerparameter mit dem Standardkennwort "22" verwendet werden. Siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.
Um den Wert des Benutzerparameters h09 von 0 auf 1 zu ändern, kann die Änderungsmethode für Benutzerparameter mit dem speziellen Kennwort "11" verwendet werden. Siehe "Abrufen und Ändern der Benutzerparameter" auf Seite 11.

MODBUS FÜR BMS-VERBINDUNG

Wenn Sie die Optionssatz-Adresskarte EKAC10C installieren, können Sie mit dem Kaltwassererzeuger mithilfe des Modbusses über ein Gebäudeverwaltungssystem (BMS) oder Überwachungs­system kommunizieren.

Allgemeine Beschreibung des Modbus-Protokolls

Die Adresskarte kommuniziert mithilfe des Modbusses.
Verschiedene Teile des Datenübertragungsnetzes
Das Datenübertragungsnetz besteht aus zwei wichtigen Elementen:
Gebäudeverwaltungssystem (Building Management System
– BMS) oder Überwachungssystem.
Ein oder mehrere Kaltwassererzeuger.
Das Gebäudeverwaltungssystem bzw. Überwachungssystem
kann mit den Kaltwassererzeugern über die Adresskarte kommunizieren. Die Datenübertragung wird entsprechend einer Master-Slave­Struktur beim Abfragen verwaltet, wobei das überwachende Gebäudeverwaltungssystem den Master darstellt und die Adresskarten als Slaves funktionieren.
Der Kaltwassererzeuger kann durch den Überwacher durch die Zuweisung einer Adresse innerhalb des Modbus-Netzwerks identifiziert werden. Die Adresse des Kaltwassererzeugers kann bei der Konfiguration der Einstellungen des Gebäude­verwaltungssystems programmiert werden.
Die Variablendatenbank jedes Kaltwassererzeugers mit installierter Adresskarte ist der Referenzpunkt für den Lieferanten des Überwachungssystems im Modbus zum Zuweisen einer geeigneten Bedeutung für die Variablen. Die Variablen können vom Überwachungssystem gelesen und geschrieben werden. Ob die Variablen nur gelesen oder gelesen und geschrieben werden können, hängt vom angeschlossenen Kaltwassererzeuger und vom verwendeten Anwendungs­programm ab.
-Wenn das Überwachungssystem einer Variablen mit
Schreibschutz einen Wert zuweist, wird der Befehl überhaupt nicht ausgeführt.
-Vom Überwachungssystem angeforderte Variablen, die in
einem Kaltwassererzeuger mit einer Adresskarte nicht verfügbar sind, werden von der Adresskarte mit dem Wert 0 zum Überwachungssystem geschickt. Das Überwachungssystem muss diese ordnungsgemäß verwalten.
-Wenn das Überwachungssystem versucht, einen
Parameterwert zu schreiben, der außerhalb des zulässigen Bereichs ist, wird dieser Wert ignoriert.
Das in der Adresskarte implementierte Modicon-Modbus-Protokoll entspricht den Angaben des folgenden Dokuments:
Modicon Modbus Protokoll
Referenz
Juni 1996, PI-MBUS-300 Rev. J
Das implementierte Modbus-Protokoll ist vom Typ RTU (Remote Terminal Unit) auf der Basis von Zeichenübertragungszeiten. Die Konfiguration verwendet die Multidrop-Funktion von RS485. Die im Modbus-Paket gesendete Adresse spricht die Kaltwassererzeuger­einheit an.
Implementierte RS485-Datenübertragungseinstellungen für das Modbus-Protokoll
Die RS485-Datenübertragungseinstellungen werden wie folgt implementiert:
Baudrate: 9600
Stoppbit: 2
Parität: keine
Implementierte Befehle für das Modbus-Protokoll
Folgende Befehle sind im Programm implementiert:
Modbus-Befehl Bedeutung Anmerkungen
01 read coil status Digitale Variable(n)
02 read input
status
03 read holding
registers
04 read input
registers
05 force single coil Einzelne digitale
06 preset single
register
15 force multiple
coils
16 preset multiple
registers
lesen
Digitale Variable(n) lesen
Analoge Variable(n) lesen
Analoge Variable(n) lesen
Variable(n) schreiben
Einzelne analoge Variable(n) schreiben
Eine Reihe von digitalen Variablen schreiben
Eine Reihe analoger Variablen schreiben
Beachten Sie Folgendes:
Wegen der Vielfalt von Kaltwassererzeugern mit installierten Adresskarten wird nicht zwischen Eingabevariablen (mit Schreibschutz-Status) und Ausgabevariablen (mit Lesen/ Schreiben-Status) unterschieden, so dass der Inhalt und die Verwaltung der Datenbank von dem im Überwachungssystem vorhandenen Teil abhängen.
Wegen der allgemeinen Beschaffenheit des Systems antwortet die Adresskarte in derselben Weise auf verschiedene Modbus­Befehle.
ruft den aktuellen Status (EIN/AUS) einer Gruppe logischer Coils oder eine diskrete Eingabe ab
ruft den aktuellen Status (EIN/AUS) einer Gruppe logischer Coils oder eine diskrete Eingabe ab
ruft einen aktuellen binären Wert in einem oder mehreren Halteregistern ab
ruft einen aktuellen binären Wert in einem oder mehreren Halteregistern ab
erzwingt Status EIN oder AUS für Single-Coil
fügt einen speziellen binären Wert in ein Halteregister ein
bewirkt, dass für eine Reihe konsekutiver logischer Coils der Status EIN oder AUS festgelegt wird
fügt spezielle Binärwerte in eine Reihe konsekutiver Halteregister ein
Bedienungsanleitung
13
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ014~064KBW1N
D-EOMHP00908-17EU
Loading...
+ 130 hidden pages