Menu overview ................................................................................ 18
INTRODUCTION
This operation manual concerns condensorless water-cooled water
chillers of the Daikin EWLP-KB series. These units are provided for
indoor installation and used for cooling applications. The EWLP units
can be combined with Daikin fan coil units or air handling units for air
conditioning purposes. They can also be used for supplying water for
process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local Daikin dealer.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Before starting".
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter "Operation" on page 6 before changing
the parameters.
The English text is the original instruction. Other languages are
translations of the original instructions.
This appliance is not intended for use by persons, including children,
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person
responsible for their safety.
Children should be supervised to ensure that they do not play with
the appliance.
Typebrased plate heat exchanger
Min. water volume
Water flow range
Condenser
(l)
62.1103134155
(l/min)
17~6929~11538~15345~179
refer to engeneering specifications as published by the supplier of your
remote condenser
Compressor EWLP040055065
Model2x
Speed
(rpm)
JT212DA-YE
2x
JT300DA-YE
2900
2x
JT335DA-YE
Oil typeFVC68D
Oil charge volume
(l)
2x 2.72x 2.72x 2.7
Refrigerant typeR407C
Evaporator
Typebrased plate heat exchanger
Min. water volume
Water flow range
Condenser
(l)
(l/min)
205268311
57~22977~30789~359
refer to engeneering specifications as published by the supplier of your
remote condenser
Electrical specifications
Model EWLP012020026030
(2)
Power supply
• Phase
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM)
(Hz)
(%)
(V)
3x 163x 203x 253x 32
3N~
50
400
±10
Compressor
• Phase
•Frequency
•Voltage
• Nominal running current (A)
(Hz)
(V)
7.411.614.716.8
3~
50
400
Control
• Phase
•Frequency
•Voltage
• Recommended fuses (aM)
Model EWLP040055065
(Hz)
(V)
1~
50
230
factory installed
Power supply
• Phase
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM)
(Hz)
(%)
(V)
3x 403x 503x 50
3N~
50
400
±10
Compressor
• Phase
•Frequency
•Voltage
• Nominal running current (A)
(Hz)
(V)
11.614.716.8
3~
50
400
Control
• Phase
•Frequency
•Voltage
• Recommended fuses (aM)
(Hz)
(V)
1~
50
230
factory installed
(1) Refer to the engineering data book for the complete list of specifications.
EWLP012~065KBW1N
Condenserless water-cooled water chillers
4PW61666-1 – 07.2010
(2) Refer to the engineering data book for the complete list of specifications.
Operation manual
2
DESCRIPTION
The EWLP condenserless water-cooled water chillers are available in 7 standard sizes.
EWLP040~065KBW1N
17
2
13141516
EWLP012~030KBW1N
2
3
14
9
11
7
8
1212
Figure: Main components
1Compressor
2Evaporator
3Accumulator
4Switchbox
5Chilled water in
6Chilled water out
7Discharge stop valve
8Liquid stop valve
9Evaporator entering water temperature sensor
10Freeze up sensor
11Digital display controller
12Power supply intake
13Ball valve (field installed)
14Water filter (field installed)
15Air purge valve (field installed)
16T-joint for air purge (field installed)
17Flow switch (with T-joint) (field installed)
18Main switch
500
500
500
3
1
1
3
4
500
5
11
10
500
500
500
500
759
8661818
10
Required space around the unit for service
Operation manual
3
Condenserless water-cooled water chillers
EWLP012~065KBW1N
4PW61666-1 – 07.2010
Function of the main components
EWLP012~030KBW1N
EWLP040~065KBW1N
64
13
5
12
14
R3T
R4T
R3T
R4T
S4LP
S5LP
S4LP
1
M1C
LP
HP
37
M2C
LP
HP
M1C
LP
HP
S1HP
Q1D
2
89
S2HP
Q2D
S1HP
Q1D
10111513
Figure: Functional diagram
1Compressor9Liquid stop valve
2Filter10Discharge stop valve
3Expansion valve11Accumulator
4Evaporator12Flow switch (delivered with the unit, installed in the field)
5Evaporator water outlet13Ball valve (delivered with the unit, installed in the field)
6Evaporator water inlet14Water filter (delivered with the unit, installed in the field)
7Sight glass15Air purge valve (delivered with the unit, installed in the field)
8Liquid solenoid valveField piping
As the refrigerant circulates through the unit, changes in its state or
Safety devices
condition occur. These changes are caused by the following main
components:
■Compressor
The compressor (M*C) acts as a pump and circulates the
refrigerant in the refrigeration circuit. It compresses the
refrigerant vapour coming from the evaporator to a pressure at
which it can easily be liquified in the condenser.
■Filter
The filter installed behind the condenser removes small particles
from the refrigerant to prevent blockage of the tubes.
■Expansion valve
The liquid refrigerant coming from the condenser enters the
evaporator via an expansion valve. The expansion valve brings
the liquid refrigerant to a pressure at which it can easily be
evaporated in the evaporator.
■Evaporator
The main function of the evaporator is to take heat from the
water that flows through it. This is done by turning the liquid
refrigerant, coming from the condenser, into gaseous
refrigerant.
■Water in/outlet connections
The unit is equipped with General safety devices: shut down all
circuits and stop the whole unit.
■I/O PCB (A2P) (input/output)
The I/O PCB (A2P) contains a reverse phase protector.
The reverse phase protector detects if the 3 phases of the power
supply are connected correctly. If a phase is not connected or if
2 phases are inverted, the unit can not start up.
■Overcurrent relay
The overcurrent relay (K*S) is located in the switch box of the
unit and protects the compressor motor in case of overload,
phase failure or too low voltage. The relay is factory-set and may
not be adjusted. When activated, the overcurrent relay has to be
reset in the switch box and the controller needs to be reset
manually.
■High-pressure switch
The high-pressure switch (S*HP) is installed on the discharge
pipe of the unit and measures the condenser pressure (pressure
at the outlet of the compressor). When the pressure is too high,
the pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
The water inlet and outlet connection allow an easy connection
of the unit to the water circuit of the air handling unit or industrial
equipment.
EWLP012~065KBW1N
Condenserless water-cooled water chillers
4PW61666-1 – 07.2010
Operation manual
4
■Low pressure switch
The low-pressure switch (S*LP) is installed on the suction pipe
of the unit and measures the evaporator pressure (pressure at
the intlet of the compressor). When the pressure is too low, the
pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
■Discharge thermal protector
The discharge thermal protector (Q*D) is activated when the
temperature of the refrigerant leaving the compressor becomes
too high. When the temperature returns to normal, the protector
resets automatically, but the controller needs to be reset
manually.
■Freeze up sensor
The outlet water temperature sensor (R4T) measures the
temperature of the water at the water heat exchanger outlet. The
protection device shuts down the circuit when the temperature of
the chilled water becomes too low in order to prevent freezing of
the water during operation.
When the outlet water temperature returns to normal, the
protector resets automatically, but the controller needs to be
reset manually.
■Fuse for control circuit (F1U)
The fuse for control circuit protects cables of control circuit and
controller components in case of short circuit.
■Fuse for control circuit (F4)
The fuse for control circuit protects cables of control circuit in
case of short circuit.
■Fuse for digital controller (F3U)
The fuse protects cables of digital controller and digital controller
in case of short circuit.
■Flow switch (delivered with the unit, installed in the field)
The flow switch measures the flow in the water circuit. In case
the flow does not reach the minimum allowed water flow, the unit
will be shut down.
■Ball valve (delivered with the unit, installed in the field)
A ball valve is installed in front of and behind the water filter to
allow filter cleaning without having to drain the water circuit.
■Water filter (delivered with the unit, installed in the field)
The filter installed in front of the unit removes dirt from the water
to prevent damage to the unit or blockage of the evaporator or
condenser. The water filter should be cleaned on a regular base.
■Air purge valve (delivered with the unit, installed in the field)
Remaining air in the chiller water system will be automatically
removed via the air purge valve.
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below: