Daikin EWAD TZ-B user guide manual

Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
1/84
Air cooled:
EWAD TZ EWAD TZ-B
Water cooled:
EWWD VZ
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN
OPERATION MANUAL
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 2/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
TABLE OF CONTENTS
1 SAFETY CONSIDERATIONS ...................................................................................................................... 7
1.1 General ................................................................................................................................................. 7
1.2 Avoid electrocution ................................................................................................................................ 7
1.3 Safety Devices ...................................................................................................................................... 7
1.3.1 General safety devices ................................................................................................................................. 7
1.3.2 Circuit safety devices .................................................................................................................................... 8
1.3.3 Component safety devices ........................................................................................................................... 8
1.4 Available sensors .................................................................................................................................. 9
1.4.1 Pressure transducers .................................................................................................................................... 9
1.4.2 Temperature sensors .................................................................................................................................... 9
1.4.3 Thermistors ................................................................................................................................ ................... 9
1.4.4 Leak detectors ................................................................ .............................................................................. 9
1.5 Available Controls ............................................................................................................................... 10
1.5.1 Evaporator pumps ...................................................................................................................................... 10
1.5.2 Condenser pumps (W/C units only) ............................................................................................................ 10
1.5.3 Compressors .............................................................................................................................................. 10
1.5.4 Expansion Valve ......................................................................................................................................... 10
1.5.5 Switchbox Pressurization fan for HFO units (W/C only) .............................................................................. 10
1.6 Customer Terminal Block Connections .............................................................................................. 10
1.6.1 Evaporator Flow Switch .............................................................................................................................. 11
1.6.2 Condenser Flow Switch (W/C units only) .................................................................................................... 11
1.6.3 Double setpoint ........................................................................................................................................... 11
1.6.4 Current limit (optional) ................................................................................................................................ 11
1.6.5 External Fault.............................................................................................................................................. 11
1.6.6 Rapid Restart (optional) .............................................................................................................................. 11
1.6.7 Remote On-Off ........................................................................................................................................... 11
1.6.8 General Alarm............................................................................................................................................. 11
1.6.9 Compressor Status ..................................................................................................................................... 11
1.6.10 Circuit Alarm (optional) ............................................................................................................................... 11
1.6.11 Evaporator Pump Start ............................................................................................................................... 12
1.6.12 Condenser Pump Start (W/C units only) ..................................................................................................... 12
1.6.13 Demand limit ............................................................................................................................................... 12
1.6.14 Setpoint override ......................................................................................................................................... 12
1.6.15 Pump VFD Signal (A/C units only) .............................................................................................................. 12
2 GENERAL DESCRIPTION ........................................................................................................................ 13
2.1 Basic Information ................................................................................................................................ 13
2.2 Abbreviations used ............................................................................................................................. 13
2.3 Controller Operating Limits ................................................................................................................. 13
2.4 Controller Architecture ........................................................................................................................ 14
2.5 Communication Modules .................................................................................................................... 14
3 USING THE CONTROLLER ...................................................................................................................... 15
3.1 General Recommendation .................................................................................................................. 15
3.2 Navigating ........................................................................................................................................... 15
3.3 Passwords .......................................................................................................................................... 16
3.4 Editing ................................................................................................................................................. 16
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
3/84
3.5 Basic Control System Diagnostic ........................................................................................................ 17
3.6 Controller maintenance ....................................................................................................................... 18
3.7 Optional Remote User Interface ......................................................................................................... 18
3.8 Embedded Web Interface ................................................................................................................... 19
4 MENU STRUCTURE .................................................................................................................................. 21
4.1 Main Menu .......................................................................................................................................... 21
4.2 View/Set Unit ...................................................................................................................................... 21
4.2.1 Thermostat Ctrl ........................................................................................................................................... 21
4.2.2 Network Ctrl ................................................................................................................................................ 22
4.2.3 Compressor Vfd Setup (A/C Units only) ..................................................................................................... 22
4.2.4 Pumps ........................................................................................................................................................ 22
4.2.5 Condenser (W/C units only) ........................................................................................................................ 23
4.2.6 Press Fan (W/C units only) ......................................................................................................................... 23
4.2.7 Master/Slave ................................................................ ............................................................................... 23
4.2.7.1 Data .................................................................................................................................................... 24
4.2.7.2 Options ............................................................................................................................................... 24
4.2.7.3 Thermostat Ctrl .................................................................................................................................. 25
4.2.7.4 Timers ................................................................................................................................................ 25
4.2.7.5 Standby Chiller ................................................................................................................................... 25
4.2.8 Rapid Restart ................................ ................................ .............................................................................. 25
4.2.9 Date/Time ................................................................................................................................................... 25
4.2.10 Scheduler ................................................................................................................................................... 26
4.2.11 Power Conservation ................................................................................................................................... 26
4.2.12 Controller IP setup ...................................................................................................................................... 27
4.2.13 Daikin on Site.............................................................................................................................................. 27
4.2.14 Menu Password .......................................................................................................................................... 27
4.3 View/Set Circuit ................................................................................................................................... 28
4.3.1 Data ............................................................................................................................................................ 28
4.3.2 Compressor ................................................................................................................................................ 29
4.3.3 Condenser (A/C only) ................................................................................................................................. 29
4.3.4 EXV ............................................................................................................................................................ 30
4.3.5 Economizer (A/C only) ................................................................................................................................ 30
4.3.6 Settings (A/C units only) ............................................................................................................................. 30
4.3.7 Variable VR................................................................................................................................................. 30
4.4 Active Setpoint .................................................................................................................................... 30
4.5 Evaporator LWT .................................................................................................................................. 31
4.6 Condenser LWT (W/C Units only) ...................................................................................................... 31
4.7 Unit Capacity ....................................................................................................................................... 31
4.8 Unit Mode ............................................................................................................................................ 31
4.9 Unit Enable (A/C Units only) ............................................................................................................... 32
4.10 Timers ................................................................................................................................................. 32
4.11 Alarms ................................................................................................................................................. 32
4.12 Commission Unit ................................................................................................................................. 32
4.12.1 Alarm Limits ................................................................................................................................................ 32
4.12.2 Calibrate Sensors ....................................................................................................................................... 33
4.12.2.1 Unit Calibrate Sensors ....................................................................................................................... 33
4.12.2.2 Circuit Calibrate Sensors .................................................................................................................... 33
4.12.3 Manual Control ........................................................................................................................................... 34
4.12.3.1 Unit ..................................................................................................................................................... 34
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 4/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
4.12.3.2 Circuit #1 (Circuit #2 if present) .......................................................................................................... 35
4.12.4 Scheduled Maintenance ............................................................................................................................. 36
4.13 About this Chiller ................................................................................................................................. 36
5 WORKING WITH THIS UNIT ..................................................................................................................... 37
5.1 Unit Setup ........................................................................................................................................... 37
5.1.1 Control Source ............................................................................................................................................ 37
5.1.2 Available Mode Setting ............................................................................................................................... 37
5.1.3 Temperature Settings ................................................................................................................................. 38
5.1.3.1 LWT Setpoint Setting ......................................................................................................................... 38
5.1.3.2 Thermostat Control Settings ............................................................................................................... 39
5.1.4 Alarm Settings ............................................................................................................................................ 40
5.1.4.1 Pumps ................................................................................................................................................ 40
5.1.5 Power Conservation ................................................................................................................................... 40
5.1.5.1 Demand Limit ..................................................................................................................................... 40
5.1.5.2 Current Limit (Optional) ...................................................................................................................... 41
5.1.5.3 Setpoint Reset .................................................................................................................................... 41
5.1.5.4 Setpoint Reset by OAT Reset (A/C units only) ................................................................................... 41
5.1.5.5 Setpoint Reset by External 4-20 mA Signal ....................................................................................... 42
5.1.5.6 Setpoint Reset by Evaporator Return Temperature ........................................................................... 42
5.1.5.7 Soft Load ............................................................................................................................................ 42
5.1.6 Date/Time ................................................................................................................................................... 43
5.1.6.1 Date,Time and UTC Settings ............................................................................................................. 43
5.1.6.2 Quiet Mode Scheduling (A/C units only) ............................................................................................. 43
5.1.7 Scheduler ................................................................................................................................................... 43
5.2 Unit/Circuit Start-up ............................................................................................................................. 43
5.2.1 Unit Status .................................................................................................................................................. 43
5.2.2 Prepare the unit to start .............................................................................................................................. 44
5.2.2.1 Unit Switch Enable (A/C units only) .................................................................................................... 44
5.2.2.2 Unit Switch Enable (W/C units only) ................................................................................................... 44
5.2.2.3 Keypad Enable ................................................................................................................................... 45
5.2.2.1 BMS Enable ....................................................................................................................................... 45
5.2.3 Unit Start sequence .................................................................................................................................... 45
5.2.4 Circuit Status .............................................................................................................................................. 45
5.2.5 Circuits start sequence ............................................................................................................................... 46
5.2.6 High Water Temperature Limit (A/C units only) .......................................................................................... 47
5.2.7 Low Evaporating Pressure .......................................................................................................................... 47
5.2.8 High Condensing Pressure ......................................................................................................................... 48
5.2.9 High Vfd Current ......................................................................................................................................... 48
5.2.10 High Discharge Temperature ...................................................................................................................... 48
5.3 Condensation Control (A/C units only) ............................................................................................... 49
5.3.1 Fan Settings (A/C units only) ...................................................................................................................... 49
5.3.1.1 Fan VFD Settings ............................................................................................................................... 49
5.4 Condensation Control (W/C units only) .............................................................................................. 50
5.5 EXV Control ........................................................................................................................................ 51
5.6 Economizer Control (A/C units only) ................................................................................................... 51
5.7 Liquid Injection Control ....................................................................................................................... 52
5.8 Variable Volume Ratio Control ........................................................................................................... 52
6 ALARMS AND TROUBLESHOOTING ...................................................................................................... 53
6.1 Unit Alerts ........................................................................................................................................... 54
6.1.1 Bad Current Limit Input ............................................................................................................................... 54
6.1.2 Bad Demand Limit Input ............................................................................................................................. 54
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
5/84
6.1.3 Bad Leaving Water Temperature Reset Input............................................................................................. 54
6.1.4 Condenser Pump #1 Failure (W/C units only)............................................................................................. 55
6.1.5 Condenser Pump #2 Failure (W/C units only)............................................................................................. 55
6.1.6 Energy Meter Communication Fail .............................................................................................................. 55
6.1.7 Evaporator Pump #1 Failure ....................................................................................................................... 56
6.1.8 Evaporator Pump #2 Failure ....................................................................................................................... 56
6.1.9 External Event ............................................................................................................................................ 56
6.1.10 Fan Alarm Module Communication Fail (A/C units only) ............................................................................ 57
6.1.11 Heat Recovery Entering Water Temperature sensor fault (A/C units only) ................................................. 57
6.1.12 Heat Recovery Leaving Water Temperature sensor fault (A/C units only) .................................................. 57
6.1.13 Heat Recovery Water Temperatures inverted (A/C units only) ................................................................... 58
6.1.14 Rapid Recovery Module Communication Fail ............................................................................................. 58
6.1.15 Switch Box Temperature sensor fault (A/C units only) ................................................................................ 58
6.2 Unit Pumpdown Stop Alarms .............................................................................................................. 59
6.2.1 Condenser Entering Water Temperature (EWT) sensor fault ..................................................................... 59
6.2.2 Condenser Leaving Water Temperature (LWT) sensor fault ...................................................................... 59
6.2.3 Evaporator Entering Water Temperature (EWT) sensor fault ..................................................................... 59
6.2.4 Evaporator Water Temperatures inverted ................................................................................................... 60
6.2.5 Outside Air Temperature (OAT) Lockout (A/C units only) ........................................................................... 60
6.2.6 Outside Air Temperature sensor fault alarm (A/C units only) ...................................................................... 60
6.3 Unit Rapid Stop Alarms....................................................................................................................... 61
6.3.1 Condenser Water Freeze alarm (W/C units only) ....................................................................................... 61
6.3.2 Condenser Water Flow Loss alarm (W/C units only) .................................................................................. 61
6.3.3 Emergency Stop ......................................................................................................................................... 61
6.3.4 Evaporator Flow Loss alarm ...................................................................................................................... 62
6.3.5 Evaporator Leaving Water Temperature (LWT) sensor fault ...................................................................... 62
6.3.6 Evaporator Water Freeze alarm .................................................................................................................. 62
6.3.7 External alarm............................................................................................................................................. 63
6.3.8 Gas Leakage Alarm (W/C units only) .......................................................................................................... 63
6.3.9 Heat Recovery Water Freeze Protect alarm (A/C units only) ...................................................................... 63
6.3.10 OptionCtrlrCommFail (A/C units only) ......................................................................................................... 64
6.3.11 Power Fault (only for A/C units with the UPS option) .................................................................................. 64
6.3.12 PVM alarm (A/C units only)......................................................................................................................... 64
6.4 Circuit Alerts ........................................................................................................................................ 65
6.4.1 Economizer Pressure Sensor fault (A/C units only) .................................................................................... 65
6.4.2 Economizer Temperature Sensor fault (A/C units only) .............................................................................. 65
6.4.3 Failed Pumpdown ....................................................................................................................................... 66
6.4.4 Fan Fault (A/C units only) ........................................................................................................................... 66
6.4.5 Gas Leakage Sensor fault (A/C units only) ................................................................................................. 66
6.4.6 CxCmp1 MaintCode01 (A/C units only) ...................................................................................................... 67
6.4.7 CxCmp1 MaintCode02 (A/C units only) ...................................................................................................... 67
6.4.8 Power Loss (A/C units only)........................................................................................................................ 67
6.5 Circuit Pumpdown Stop Alarms .......................................................................................................... 68
6.5.1 Discharge Temperature Sensor fault .......................................................................................................... 68
6.5.2 Gas Leakage fault (A/C units only) ............................................................................................................. 68
6.5.3 High Compressor Vfd Temperature fault (A/C units only) ........................................................................... 69
6.5.4 Liquid Temperature Sensor fault (W/C units only) ...................................................................................... 69
6.5.5 Low Compressor Vfd Temperature fault (A/C units only) ............................................................................ 69
6.5.6 Low Oil Level fault (W/C units only) ............................................................................................................ 70
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 6/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
6.5.7 Low Discharge Superheat fault ................................................................................................................... 70
6.5.8 Oil Pressure Sensor fault ............................................................................................................................ 70
6.5.9 Suction Temperature Sensor fault .............................................................................................................. 71
6.6 Circuit Rapid Stop Alarms ................................................................................................................... 71
6.6.1 Compressor Extension Communication Error (W/C units only) .................................................................. 71
6.6.2 EXV Driver Extension Communication Error (W/C units only) .................................................................... 71
6.6.3 Compressor VFD Fault ............................................................................................................................... 72
6.6.4 Compressor VFD OverTemp (A/C units only) ............................................................................................. 72
6.6.5 Condensing Pressure sensor fault .............................................................................................................. 72
6.6.6 Economizer EXV Driver Error (A/C unit only).............................................................................................. 73
6.6.7 Economizer EXV Motor Not Connected (A/C unit only) .............................................................................. 73
6.6.8 Evaporating Pressure sensor fault .............................................................................................................. 73
6.6.9 EXV Driver Error (A/C units only) ................................................................................................................ 74
6.6.10 EXV Motor Not Connected (TZ B units only) .............................................................................................. 74
6.6.11 Fail Start Low Pressure .............................................................................................................................. 74
6.6.12 Fan VFD Over Current (A/C units only) ...................................................................................................... 75
6.6.13 High Discharge Temperature Alarm ........................................................................................................... 75
6.6.14 High Motor Current Alarm ........................................................................................................................... 75
6.6.15 High Motor Temperature Alarm .................................................................................................................. 76
6.6.16 High Oil Pressure Differential Alarm ........................................................................................................... 76
6.6.17 High Pressure alarm ................................................................................................................................... 76
6.6.18 Low Pressure alarm .................................................................................................................................... 77
6.6.19 Low Pressure Ratio Alarm .......................................................................................................................... 78
6.6.20 Maximum Number of Restart Alarm (A/C units only) .................................................................................. 78
6.6.21 Mechanical High Pressure Alarm ................................................................................................................ 79
6.6.22 Mechanical Low Pressure Alarm (W/C units only) ...................................................................................... 79
6.6.23 No Pressure At Start Alarm ........................................................................................................................ 80
6.6.24 No Pressure Change At Start Alarm ........................................................................................................... 80
6.6.25 Overvoltage Alarm ...................................................................................................................................... 80
6.6.26 Undervoltage Alarm .................................................................................................................................... 81
6.6.27 VFD Communication Failure ....................................................................................................................... 81
7 OPTIONS .................................................................................................................................................... 82
7.1 Total Heat Recovery (Optional – A/C units only) ................................................................................ 82
7.2 Energy Meter including Current Limit (Optional) ................................................................................ 82
7.3 Rapid Restart (Optional) ..................................................................................................................... 83
7.4 Inverter Pump Kit (Optional) ............................................................................................................... 83
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
7/84
RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched off, certain circuits may still be energized, since they may be connected to a separate power source.
RISK OF BURNS: Electrical currents cause components to get hot either temporarily or permanently. Handle power cable, electrical cables and conduits, terminal box covers and motor frames with great care.
ATTENTION: In accordance with the operating conditions the fans can be cleaned periodically. A fan can start at any time, even if the unit has been shut down.
1 SAFETY CONSIDERATIONS
1.1 General
Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the installation are not considered: operating pressures, presence of electrical components and voltages and the installation site (elevated plinths and built-up up structures). Only properly qualified installation engineers and highly qualified installers and technicians, fully trained for the product, are authorized to install and start-up the equipment safely.
During all servicing operations, all instructions and recommendations, which appear in the installation and service instructions for the product, as well as on tags and labels fixed to the equipment and components and accompanying parts supplied separately, must be read, understood and followed.
Apply all standard safety codes and practices. Wear safety glasses and gloves. Use the proper tools to move heavy objects. Move units carefully and set them down gently.
1.2 Avoid electrocution
Only personnel qualified in accordance with IEC (International Electrotechnical Commission) recommendations may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit be shut off before any work is begun. Shut off main power supply at the main circuit breaker or isolator.
IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown that the equipment conforms to all applicable codes with respect to electromagnetic compatibility.
1.3 Safety Devices
Each unit is equipped with safety devices of three different kinds:
1.3.1 General safety devices
Safeties of this level of severity will shut down all the circuits and stop the entire unit. When a general safety device will occur a manual intervention on the unit will be required in order to re-establish the normal operability of the machine. There are exceptions to this general rule in case of alarms linked to temporary abnormal conditions.
Emergency Stop
A push button is placed on a door of the unit electrical panel. The button is highlighted by a red color in yellow background. A manual pressure of the emergency stop button stops all loads from rotating, thus preventing any accident which may occur. An alarm is also generated by the Unit Controller. Releasing the emergency stop button enables the unit, which may be restarted only after the alarm has been cleared on the controller.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 8/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
The emergency stop causes all motors to stop, but does not switch off power to the unit. Do not service or operate on the unit without having switched off the main switch.
Do not operate on a faulty fan before the main switch has been shut off. Overtemperature protection is auto­reset, therefore a fan may restart automatically if temperature conditions allow it.
Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons.
1.3.2 Circuit safety devices
Safety of this level of severity will shut down the circuit they protect. The remaining circuits will keep running.
1.3.3 Component safety devices
Safety of this level of severity will shut down a component against abnormal running condition that could create permanent damages to it. An overview of the protecting devices is listed below:
Overcurrent/Overload Protections
Overcurrent/overload devices protect electrical motors used on compressors, fans and pumps in case of overload or short circuit. In case of inverter-driven motors, overload and overcurrent protection is integrated in the electronic drives. A further protection from short circuit is accomplished by fuses or circuit breakers installed upstream each load or group of loads.
Overtemperature Protections
Compressor and fan electrical motors are also protected from overheating by thermistors immersed into motor windings. Should the winding temperature exceed a fixed threshold, the thermistors will trip and cause the motor to stop. High Temperature Alarm is recorded in the Unit Controller only in case of compressors. Alarm must be reset from the controller.
Phase reversal, under/over voltage, ground fault protections
When one of those alarms occurs the unit is immediately stopped or even inhibited to start. The alarms clear automatically once the problem is fixed. This auto clear logic allows the unit to automatically recover in case of temporary conditions where the supply voltage reaches the upper or lower limit set on the protection device. In the other two cases a manual intervention on the unit will be required in order to solve the problem. In case of a phase reversal alarm two phases requires to be inverted.
In the event of a power supply outage, the unit will restart automatically without the need for an external command. However, any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or unit from restarting.
Flowswitch
The unit must be protected by a flowswitch. The flowswitch will stop the unit when the water flow becomes lower than the minimum allowed flow. When the water flow is restored the flow protection resets automatically. Exception is when the flowswitch opens with at least one compressor running, in this case the alarm shall be cleared manually.
Freezing protection
Antifreeze protection prevents the water to freeze in the evaporator. It is automatically activated when the water temperature (entering or leaving) at the evaporator drops below the antifreeze limit. In freeze condition if the unit is in standby the evaporator pump will be activated to prevent freezing of the evaporator. If the freeze condition will activate when the unit is running all the unit will shut down in alarm while the pump will keep running. Alarm will automatically clear when the freeze condition will clear.
Low pressure protection
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
9/84
If the circuit operates with a suction pressure lower than an adjustable limit for a certain time the circuit safety logic will shut down the circuit and generate an alarm. The alarm requires a manual action on the Unit Controller to be reset. Reset will take effect only if the suction pressure is no longer lower that the safety limit.
High Pressure Protection
If the discharge pressure becomes too high and exceeds a limit which is linked with the operational envelop of the compressor the circuit safety logic will try to prevent the alarm or, if the corrective actions have no effect, it will shut down the circuit before the Mechanical High Pressure switch will open. This alarm required a manual action on the Unit Controller to be reset.
Mechanical High Pressure Switch
Each circuit is equipped with at least one high pressure switch which tries to prevent the relief safety valve to open. When the discharge pressure becomes too high the Mechanical High Pressure switch will open and immediately stop the compressor cutting the power supply to the auxiliary relay. The alarm can be cleared as soon as the discharge pressure becomes normal again. The alarm must be reset on the switch itself and on the Unit Controller. The triggering pressure value cannot be changed.
Relief Safety Valve
If the pressure becomes too high in the refrigerant circuit, the relief valve will open to limit the maximum pressure. If this happens switch off immediately the machine and contact your local service organization.
Inverter fault
Each compressor can be equipped with its own inverter (integrated or external). The inverter can automatically monitor its status and inform the Unit Controller in case of faults or pre-alarm conditions. If this happen the Unit Controller will limit the compressor operation or eventually switch off the circuit in alarm. A manual action on the controller will be needed in order to clear the alarm.
1.4 Available sensors
1.4.1 Pressure transducers
Two types of electronic sensors are used to measure suction, discharge and oil pressure on each circuit. The range of each sensor is clearly indicated on the sensor casing. Discharge and oil pressures are monitored using a sensor of the same range.
1.4.2 Temperature sensors
The evaporator water sensors are installed in the entering and leaving side. An outdoor temperature sensor is mounted inside the chiller. Additionally each circuit installs a suction and discharge temperature sensors to monitor and control the superheated refrigerant temperatures.
On refrigerant-cooled inverters additional sensors immersed into the cooling plate measure the temperature of the drives.
1.4.3 Thermistors
Each compressor is equipped with PTC thermistors which are immersed into motor windings for motor protection. Thermistors trip to a high value in case the motor temperature reaches a hazardous temperature.
1.4.4 Leak detectors
As an option the unit can be equipped with leak detectors to sense the air in the compressor cabin and being able to identify a refrigerant leakage in that volume.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 10/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
Description
Terminals
EWAD
TZ
Terminals
EWAD
TZ B
Terminals
EWWD
VZ
Notes
Evaporator Flow Switch (mandatory)
708, 724
708, 724
708, 724
24 Vdc digital input
Condenser Flow Switch
- - 888, 890
24 Vdc digital input
Double setpoint
703, 728
703,728
703, 728
24 Vdc digital input
Current limit enable
884, 885
885, 891
-
24 Vdc digital input
External Fault
881,884
881, 884
542, 501
24 Vdc digital input
Rapid Restart Enable (optional)
764, 765
-
764, 765
24 Vdc digital input
Back-up chiller (optional)
764, 763
- - 24 Vdc digital input
LOC/BMS selection (optional)
894, 895
881-1, 834
894, 895
24 Vdc digital input
On-Off Remote
540, 541
540, 541
703, 749
230 Vac digital input
Heat/Cool Remote
- - 892, 893
Leak Detector Output
- - 552, 553
General Alarm
525, 526
525, 526
525, 526
NO digital output (24…230 Vac ext supply)
Compressor #1 status
512, 513
512, 513
-
NO digital output (24…230 Vac ext supply)
Compressor #2 status
514, 515
514, 515
-
NO digital output (24…230 Vac ext supply)
Alarm Circuit #1 (optional)
560, 561
892, 896
564, 565
NO digital output (24…230 Vac ext supply)
Alarm Circuit #2 (optional)
560, 562
894, 899
565, 566
NO digital output (24…230 Vac ext supply)
Evaporator Pump #1 start
806, 805
501, 530
527, 528
NO digital output (24 Vdc internal supply)
Evaporator Pump #2 start
806, 807
501, 531
559, 560
NO digital output (24 Vdc internal supply)
Condenser Pump #1 start
- - 550, 551
NO digital output (24 Vdc internal supply)
Condenser Pump #2 start
- - 559, 562
NO digital output (24 Vdc internal supply)
Demand Limit
888, 889
888, 889
887, 889
4-20 mA analog input
Current Limit (optional)
886, 890
887, 886
-
4-20 mA analog input
Setpoint Override
886, 887
890, 886
886, 887
4-20 mA analog input
Pump VFD Signal (optional)
882, 883
- -
1.5 Available Controls
1.5.1 Evaporator pumps
The controller can regulate one or two evaporator pumps and takes care of automatic change-over between pumps. It’s also possible to prioritize the pumps and temporarily disable one of the two. The controller is also able to control the pump speeds if the pumps are equipped with inverters.
1.5.2 Condenser pumps (W/C units only)
The controller can regulate one or two condenser pumps and takes care of automatic change-over between pumps. It’s also possible to prioritize the pumps and temporarily disable one of the two.
1.5.3 Compressors
The controller can regulate one or two compressors installed on one or two independent refrigerant circuit (one compressor per circuit). All the safeties of each compressor will be managed by the controller. Embedded inverter safeties are handled by the inverter onboard electronic and only notified to the UC.
1.5.4 Expansion Valve
The controller can regulate an electronic expansion valve per each refrigerant circuit. Microtech® III embedded logic will always guarantee the best operation for the refrigerant circuit.
1.5.5 Switchbox Pressurization fan for HFO units (W/C only)
In case of water cooled units which are installed in plant rooms it’s required to pressurize the switchbox to avoid refrigerant accumulation that could lead to dangerous operations of the unit. To avoid this a pressurization fan will maintain a constant air circulation inside the switchbox. This fan will be always running when the internal temperature will exceed 23°C. Any drop in the delta pressure between the inside and the ambient will generate a stop of the unit to re-establish a safe condition for the users.
1.6 Customer Terminal Block Connections
The contacts below are available at the user’s terminal block referred as MC24 or MC230 in the wiring diagram.
The following table summarizes the connections at the user’s terminal block.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
11/84
Operating the unit by-passing the flow switch input or without an appropriate flow switch may damage the evaporator due to freezing. Operation of the flow switch must be checked prior to start up the unit.
1.6.1 Evaporator Flow Switch
Although the flow switch is offered as an optional, it is mandatory to install one and connect it to the digital input terminals in order to enable chiller operation only when a minimum flow is sensed.
1.6.2 Condenser Flow Switch (W/C units only)
Condenser flow switch is offered as an option but it’s not mandatory to connect it to the digital input terminals.
This input can be eventually closed by a jumper even if for a more reliable use it’s suggested to mount it. If not
installed, other protection will activate in order to protect the unit.
1.6.3 Double setpoint
This contact can be used to switch between two different LWT setpoints and, depending on the application, between different modes of operation.
Ice operation must be selected in case of ice storage application. In this case the UC will run the chiller in on/off mode, switching all the chiller off as soon as the setpoint is reached. In this case the unit will run to full capacity and then will switch off applying an ice delay different chiller starts.
1.6.4 Current limit (optional)
This optional feature enables a capacity control of the unit in order to limit the input current. The current limit feature is included in the Energy Meter option. The limiting signal will be compared with a limiting value set on the HMI. By default the current limit setpoint is selected through the HMI; an external 4-20 mA signal can be enabled to allow a remotely changeable setpoint.
1.6.5 External Fault
This contact is available to report to the UC a fault or a warning from an external device. It could be an alarm coming from an external pump to inform the UC of the fault. This input can be configured as a fault (unit stop) or a warning (displayed on the HMI without any action on the chiller).
1.6.6 Rapid Restart (optional)
Purpose of the rapid restart feature is to let the unit restart in the shortest possible time after a power failure, and then recover in the shortest possible time (maintaining the reliability level of the normal operations) the capacity it had before the power failure. The rapid restart is enabled by the enable switch.
1.6.7 Remote On-Off
This unit can be started through a remote enable contact. The Q0 switch must be selected to “Remote”.
1.6.8 General Alarm
In case of a unit alarm, this output is closed thus indicating a fault condition to an externally connected BMS.
1.6.9 Compressor Status
The digital output is closed when the related circuit is in run state.
1.6.10 Circuit Alarm (optional)
This option is included with the “Rapid Restart” option. The related digital contact is closed in case of alarm on
a circuit.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 12/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
1.6.11 Evaporator Pump Start
A 24 Vdc digital output (with internal supply) is enabled when a pump (#1 or #2) is required to start. The output can be used to start an external pump (either at fixed or variable speed). The output requires an external input or relay with less than 20 mA excitation current.
1.6.12 Condenser Pump Start (W/C units only)
A digital output is enabled when a pump (#1 or #2) is required to start. A pump will be required to start when a compressor will be called to start.
1.6.13 Demand limit
This optional function can be used to limit the unit capacity percentage to a changeable limit value. This limitation cannot be directly linked to a corresponding limitation of the unit current (50% demand limit can differ from 50% of the unit FLA).
The demand limit signal can be changed continuously between 4 and 20 mA. The Microtech III will convert this signal into a unit capacity limitation changing between minimum capacity and full capacity with a linear relationship. A signal between 0 and 4mA will correspond to a full unit capacity, in this way if nothing is connected to this input no limitation will be applied. The maximum limitation will never force a unit shutdown.
1.6.14 Setpoint override
This input allows to apply an offset on the Active Setpoint to adjust the operating point of the ELWT. This input can be used to maximize the comfort.
1.6.15 Pump VFD Signal (A/C units only)
The “Pump VFD Signal” terminals are available for pump inverter kit option when factory wired speed reference
is required. These terminals are placed inside the main electrical panel. For more information about this option see 7.4.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
13/84
A/C
Air Cooled
CEWT
Condenser Entering Water Temperature
CLWT
Condenser Leaving Water Temperature
CP
Condensing Pressure
CSRT
Condensing Saturated Refrigerant Temperature
DSH
Discharge Superheat
DT
Discharge Temperature
E/M
Energy Meter Module
EEWT
Evaporator Entering Water Temperature
ELWT
Evaporator Leaving Water Temperature
EP
Evaporating Pressure
ESRT
Evaporating Saturated Refrigerant Temperature
EXV
Electronic Expansion Valve
HMI
Human Machine Interface
MOP
Maximum operating pressure
SSH
Suction SuperHeat
ST
Suction Temperature
UC
Unit controller (Microtech III)
W/C
Water Cooled
2 GENERAL DESCRIPTION
2.1 Basic Information
Microtech® III is a system for controlling single or dual-circuit air/water-cooled liquid chillers. Microtech® III controls compressor start-up necessary to maintain the desired heat exchanger leaving water temperature. In each unit mode it controls the operation of the condensing devices to maintain the proper condensation process in each circuit.
Safety devices are constantly monitored by Microtech® III to ensure their safe operation. Microtech® III also gives access to a Test routine covering all inputs and outputs. All Microtech® III controls can work in accordance with three independent modes:
Local mode: the machine is controlled by commands from the user interface.  Remote mode: the machine is controlled by remote contacts (volt-free contacts).
Network mode: the machine is controlled by commands from a BAS system. In this case, a data communication cable is used to connect the unit to the BAS.
When the Microtech® III system operates autonomously (Local or Remote mode) it retains all of its own control capabilities but does not offer any of the features of the Network mode. In this case monitoring of the unit operational data is still allowed.
2.2 Abbreviations used
In this manual, the refrigeration circuits are called circuit #1 and circuit #2. The compressor in circuit #1 is labelled Cmp1. The other in circuit #2 is labelled Cmp2. The following abbreviations are used:
2.3 Controller Operating Limits
Operation (IEC 721-3-3):
Temperature -40...+70 °C  Restriction LCD -20… +60 °C Restriction Process-Bus -25….+70 °C Humidity < 90 % r.h (no condensation)  Air pressure min. 700 hPa, corresponding to max. 3,000 m above sea level
Transport (IEC 721-3-2):
Temperature -40...+70 °C  Humidity < 95 % r.h (no condensation)
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 14/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
Controller/ Extension Module
Siemens Part Number
Address
Usage EWAD TZ
EWAD TZ B
EWWD-VZ
Main Controller
POL687.70/MCQ
POL687.70/MCQ
POL687.00/MCQ
n/a
Used on all configurations
Extension Module
- - POL965.00/MCQ
2
Used on all configurations
EEXV Module 1
POL94U.00/MCQ
POL98U.00/MCQ
POL94U.00/MCQ
3
Used on all configurations
EEXV Module 2
POL94U.00/MCQ
POL98U.00/MCQ
- 4 Used when configured for 2 circuits
Extension Module
- - POL965.00/MCQ
4
Used when configured for 2 circuits
EEXV Module 2
- - POL94U.00/MCQ
5
Used when configured for 2 circuits
Extension Module
POL965.00/MCQ
- - 5
Used on all configurations
Rapid Restart Module
POL945.00/MCQ
-
POL945.00/MCQ
22
Used with Rapid Restart option
HFO Module
- - POL945.00/MCQ
27
Used with HFO on W/C units
CAUTION: Maintain the correct polarity when connecting the power supply to the boards, otherwise the peripheral bus communication will not operate and the boards may be damaged.
Module
Siemens Part Number
Usage
BacNet/IP
POL908.00/MCQ
Optional
Lon
POL906.00/MCQ
Optional
Modbus
POL902.00/MCQ
Optional
BACnet/MSTP
POL904.00/MCQ
Optional
Air pressure min. 260 hPa, corresponding to max. 10,000 m above sea level.
2.4 Controller Architecture
The overall controller architecture is the following:
One MicroTech III main controller  I/O extensions as needed depending on the configuration of the unit  Communications interface(s) as selected  Peripheral Bus is used to connect I/O extensions to the main controller.
All boards are supplied from a common 24 Vac source. Extension boards can be directly powered by the Unit Controller. All boards can be also supplied by a 24Vdc source.
2.5 Communication Modules
Any of the following modules can be connected directly to the left side of the main controller to allow a BAS or other remote interface to function. Up to three can be connected to the controller at a time. The controller should automatically detect and configure itself for new modules after booting up. Removing modules from the unit will require manually changing the configuration.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
15/84
Alarm status (from any page it links with the page with alarm list, alarm log and alarm snapshot if available)
Back to Main Page
Back to the previous level (it can be the Main Page)
M a i n M e n u 1 /
11
E n t e r P a s s w o r d  U n i t S t a t u s =
O f f : U n i t S W
A c t i v e S e t p t = 7 . 0 °
C
A
B
C
UC
A
3 USING THE CONTROLLER
The control system consists of a unit controller (UC) equipped with a set of extension modules that implement additional features. All boards communicate via an internal peripheral bus with the UC. The Microtech III continuously manages the information received from the various pressure and temperature probes installed on the compressors and communicated to the unit .The UC incorporates a program that controls the unit.
The standard HMI consists of an inbuilt display (A) with 3 buttons (B) and a push’n’roll control (C).
The keypad/display (A) consists of a 5-line by 22 character display. The function of the three buttons (B) is described below:
The push’n’roll command (C) is used to scroll between the different menu pages, settings and data available on the HMI for the active password level. Rotating the wheel allows to navigate between lines on a screen (page) and to increase and decrease changeable values when editing. Pushing the wheel acts as an Enter Button and will jump from a link to the next set of parameters.
3.1 General Recommendation
Before switching on the unit read the following recommendations:
When all the operations and all the settings have been carried out, close all the switchbox panels  The switchbox panels can only be opened by trained personnel  When the UC requires to be accessed frequently the installation of a remote interface is strongly
recommended
Evaporator, compressors and related inverters are protected from freezing by electrical heaters. These
heaters are supplied through unit main supply and temperature controlled by thermostat or by the unit controller. Also the LCD display of the unit controller may be damaged by extremely low temperatures. For this reason, it is strongly recommended to never power off the unit during winter, especially in cold climates.
3.2 Navigating
When power is applied to the control circuit, the controller screen will be active and display the Home screen, which can also be accessed by pressing the Menu Button. The navigating wheel is the only navigating device necessary, although the MENU, ALARM, and BACK buttons can provide shortcuts as explained previously.
An example of the HMI screens is shown in the following picture.
A bell ringing in the top right corner will indicate an active alarm. If the bell doesn’t move it means that the alarm has been acknowledged but not cleared because the alarm condition hasn’t been removed. A LED will also indicate where the alarm is located between the unit or circuits.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 16/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
M a i n M e n u 1 /
E n t e r P a s s w o r d
U n i t S t a t u s = O f f : U n i t S W
A c t i v e S e t p t = 7 . 0 °
C
E n t e r P a s s w o r d 2 /
2
E n t e r P W * * * *
USER
5321
MAINTENANCE
2526
E n t e r P a s s w o r d 2 / 2
E n t e r P W 5 * *
*
The active item is highlighted in contrast, in this example the item highlighted in Main Menu is a link to another
page. By pressing the push’n’roll, the HMI will jump to a different page. In this case the HMI will jump to the
Enter Password page.
3.3 Passwords
The HMI structure is based on access levels that means that each password will disclose all the settings and parameters allowed to that password level. Basic informations about the status including the active alarm list, active setpoint and controlled water temperature can be accessed without the need to enter the password. The user UC handles two level of passwords:
The following information will cover all data and settings accessible with the maintenance password. User password will disclose a subset of the settings explained in chapter 4.
In the Enter Password screen, the line with the password field will be highlighted to indicate that the field on the right can be changed. This represents a setpoint for the controller. Pressing the push’n’roll the individual field will be highlighted to allow an easy introduction of the numeric password. By changing all fields, the 4 digits password will be entered and, if correct, the additional settings available with that password level will be disclosed.
The password will time out after 10 minutes and is cancelled if a new password is entered or the control powers down. Entering an invalid password has the same effect as continuing without a password.
Once a valid password has been entered, the controller allows further changes and access without requiring the user to enter a password until either the password timer expires or a different password is entered. The default value for this password timer is 10 minutes. It is changeable from 3 to 30 minutes via the Timer Settings menu in the Extended Menus.
3.4 Editing
The Editing Mode is entered by pressing the navigation wheel while the cursor is pointing to a line containing an editable field. Once in the edit mode pressing the wheel again causes the editable field to be highlighted. Turning the wheel clockwise while the editable field is highlighted causes the value to be increased. Turning the wheel counter-clockwise while the editable field is highlighted causes the value to be decreased. The faster the wheel is turned, the faster the value is increased or decreased. Pressing the wheel again cause the new value to be saved and the keypad/display to leave the edit mode and return to the navigation mode.
A parameter with an “R” is read only; it is giving a value or description of a condition. An “R/W indicates a read
and/or write opportunity; a value can be read or changed (providing the proper password has been entered). Example 1: Check Status, for example -is the unit being controlled locally or by an external network? We are
looking for the Unit Control Source Since this a unit status parameter, start at Main Menu and select View/Set Unit and press the wheel to jump to the next set of menus. There will be an arrow at the right side of the box,
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
17/84
BSP LED
Mode
Solid Green
Application running
Solid Yellow
Application loaded but not running (*) or BSP Upgrade mode active
Solid Red
Hardware Error (*)
Flashing Green
BSP startup phase. The controller needs time for starting.
Flashing Yellow
Application not loaded (*)
Flashing Yellow/Red
Fail safe mode (in case that the BSP upgrade was interrupted)
Flashing Red
BSP Error (software error*)
Flashing Red/Green
Application/BSP update or inizialization
BSP LED
Mode
BUS LED
Mode
Solid Green
BSP running
Solid Green
Communication running, I/O working
Solid Red
Hardware Error (*)
Solid Red
Communication down (*)
Flashing Red
BSP Error (*)
Solid Yellow
Communication running but parameter from the application wrong or missing, or uncorrect factory calibration
Flashing Red/Green
BSP upgrade mode
BSP LED
Mode
Solid Green
BPS running, communication with controller
Solid Yellow
BSP running, no communication with controller (*)
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Flashing Red/Green
Application/BSP update
indicating that a jump to the next level is required. Press the wheel to execute the jump. You will arrive at the Status/ Settings link. There is an arrow indicating that this line is a link to a further menu. Press the wheel again to jump to the next menu, Unit Status/Settings. Rotate the wheel to scroll down to Control Source and read the result.
Example 2: Change a Set point, the chilled water set point for example. This parameter is designated as Cool LWT Set point 1 and is a unit set parameter. From the Main Menu select View/Set Unit. The arrow indicated that this is link to a further menu. Press the wheel and jump to the next menu View/Set Unit and use the wheel to scroll down to Temperatures. This again has an arrow and is a link to a further menu. Press the wheel and jump to the Temperatures menu, which contains six lines of temperatures set points. Scroll down to Cool LWT 1 and press the wheel to jump to the item change page. Rotate the wheel to adjust the set point to the desired value. When this is done press the wheel again to confirm the new value. With the Back button it will be possible to jump back to the Temperatures menu where the new value will be displayed.
Example 3: Clear an Alarm. The presence of a new alarm is indicated with a Bell ringing on the top right of the display. If the Bell is frozen one or more alarm had been acknowledged but are still active. To view the Alarm menu from the Main Menu scroll down to the Alarms line or simply press the Alarm button on the display. Note the arrow indicating this line is a link. Press the wheel to jump to the next menu Alarms; there are two lines here: Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the wheel to jump to the next screen. When the Active Alarm list is entered scroll to the item AlmClr which is set to off by default. Change this value to on to acknowledge the alarms. If the alarms can be cleared then the alarm counter will display 0 otherwise it will display the number of alarm still active. When the alarms are acknowledged the Bell on the top right of the display will stop to ring if some of the alarms are still active or will disappear if all the alarms are cleared.
3.5 Basic Control System Diagnostic
MicroTech III controller, extension modules and communication modules are equipped with two status LED (BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status of the communication with the controller. The meaning of the two status LED is indicated below.
Main Controller (UC)
(*) Contact Service.
Extension modules
Communication modules
BSP LED (same for all modules)
(*) Contact Service.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 18/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
BUS LED
LON
Bacnet MSTP
Bacnet IP
Modbus
Solid Green
Ready for Communication. (All Parameter loaded, Neuron configured). Doesn't indicate a communication with other devices.
Ready for Communication. The BACnet Server is started. It doesn't indicate an active communication
Ready for Communication. The BACnet Server is started. It doesn't indicate an active communication
All Communication running
Solid Yellow
Startup
Startup
Startup. The LED stays yellow until the module receives a IP Address, therefore a link must be established.
Startup, or one configured channel not communicating to the Master
Solid Red
No Communication to Neuron (internal error, could be solved by downloading a new LON application)
BACnet Server down. Automatically a restart after 3 seconds are initiated.
BACnet Server down. Automatic restart after 3 seconds is initiated.
All configured Communications down. Means no communication to the Master. The timeout can be configured. In case that the timeout is zero the timeout is disabled.
Flashing Yellow
Communication not possible to the Neuron. The Neuron must be configured and set online over the LON Tool.
BUS LED
3.6 Controller maintenance
The controller requires to maintain the installed battery. Every two years it’s required to replace the battery.
Battery model is: BR2032 and it is produced by many different vendors. To replace the battery remove the plastic cover of the controller display using a screw driver as shown in the
following pictures:
Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper battery holder which is highlighted in the following picture, respecting the polarities indicated into the holder itself.
3.7 Optional Remote User Interface
As an option an external Remote HMI can be connected on the UC. The Remote HMI offers the same features as the inbuilt display plus the alarm indication done with a light emitting diode located below the bell button.
The Remote can be ordered with the unit and shipped loose as a field installed option. It can also be ordered any time after chiller shipment and mounted and wired on the job as explained on the following page. The remote panel is powered from the unit and no additional power supply is required.
All viewing and setpoint adjustments available on the unit controller are available on the remote panel. Navigation is identical to the unit controller as described in this manual.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
19/84
MicroTech® III
The initial screen when the remote is turned on shows the units connected to it. Highlight the desired unit and press the wheel to access it. The remote will automatically show the units attached to it, no initial entry is required.
The Remote HMI can be extended up to 700m using the process bus connection available on the UC. With a daisy-chain connection as below, a single HMI can be connected to up to 8 units. Refer to the specific HMI manual for details.
3.8 Embedded Web Interface
The MicroTech III controller has an embedded web interface that can be used to monitor the unit when connected to a local network. It is possible to configure the IP addressing of the MicroTech III as a fixed IP of DHCP depending on the network configuration.
With a common web browser a PC can connect with the unit controller entering the IP address of the controller or the host name, both visible in the “About Chiller” page accessible without entering a password.
When connected, it will be required to enter a user name and a password. Enter the following credential to get access to the web interface:
User Name: ADMIN Password: SBTAdmin!
The Main Menu page will be displayed. The page is a copy of the onboard HMI and follows the same rules in terms of access levels and structure.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 20/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
In addition it allows to trend log a maximum of 5 different quantities. It’s required to click on the value of the quantity to monitor and the following additional screen will become visible:
Depending on the web browser and its version the trend log feature may not be visible. It’s required a web browser supporting HTML 5 like for example:
Microsoft Internet Explorer v.11,  Google Chrome v.37,  Mozilla Firefox v.32.
These software are only an example of the browser supported and the versions indicated have to be intended as minimum versions.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
21/84
Setpoint/Sub-Menu
Default
Range
Description
Enter Password
- Submenu to activate access levels
View/Set Unit
- Submenu for unit data and settings
View/Set Circuit
- Submenu for circuit data and settings
Unit Status=
Off: Unit Sw
Auto Off: Ice Mode Tmr Off: OAT Lockout (A/C units only) Off: All Cir Disabled Off: Unit Alarm Off: Keypad Disable Off: Master Disable Off: BAS Disable Off: Unit Sw Off: Test Mode Off: Schedule Disable Auto: Noise Reduction Auto: Wait For Load Auto: Evap Recirc (A/C units only) Auto: Water Recir (W/C units only) Auto: Wait For Flow Auto: Pumpdn Auto: Max Pulldn Auto: Unit Cap Limit Auto: Current Limit
Status of the Unit
Active Setpoint=
7.0°C,
-
Water temperature active setpoint + link to Setpoint page
MS Ctrl Tmp=
-273.1°C,
-
Master slave controlled temperature + link to Master Slave Data page
Evaporator LWT=
-273.1°C,
-
Evaporator leaving water temperature + link to Temperatures page
Condenser LWT=
-273.1°C,
-
Condenser leaving water temperature + link to Temperatures page (W/C units only)
Unit Capacity=
0.0%,
-
Unit capacity + link to Capacity page
Unit Mode=
Cool,
-
Unit Mode + link to Available modes page
Unit Enable=
Enable,
-
Unit Enable state + link to unit and circuits enable page
Timers
- Submenu for unit timers
Alarms
- Submenu for alarms; same function as Bell Button
Commission Unit
- Submenu for commission unit
About Chiller
- Application Info submenu
Setpoint/Sub-Menu
Default
Range
Description
Thermostat Ctrl
- Submenu for Thermostatic control
Network Ctrl
- Submenu for Network control
Vfd Settings
- Submenu Vfd installation settings (A/C units only)
Pumps
- Submenu for pump settings
Condenser
- Submenu for Condenser tower control (W/C units Only)
Master/Slave
- Submenu for Master Slave data and settings
Rapid Restart
- Submenu for Rapid Restart Option
Date/Time
- Submenu Date, Time and Quiet Night mode schedule
Scheduler
- Submenu for Time Scheduler
Power Conservation
- Submenu Unit Limiting functions
Electrical Data
- Submenu for electrical data
Ctrl IP Setup
- Submenu for controller IP-address setup
Da kin on Site
-
Submenu for connection to Dakin cloud DoS
Menu Password
- Submenu Disable Password for User level
4 MENU STRUCTURE
All settings are divided in different menus. Each menu collects in a single page other sub-menus, settings or data related to a specific function (for example Power Conservation or Setup) or entity (for example Unit or Circuit). In any of the following pages, a grey box will indicate changeable values and the defaults.
4.1 Main Menu
4.2 View/Set Unit
4.2.1 Thermostat Ctrl
This page resumes all the parameters related to the unit thermostatic control.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 22/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
Setpoint/Sub-Menu
Default
Range
Description
TZ/TZ B
VZ
Start Up DT=
2.7°C
2.7°C
0.0…5.0°C
Offset to start thermostat control
Shut Dn DT=
1.0°C
1.5°C
0.0…1.7°C
Offset to standby
Stg Up DT=
0.5°C
0.5°C
0.0…1.7°C
Offset to allow compressor starts
Stg Dn DT=
1.0°C
0.7°C
0.0…1.7°C
Offset to force one compressor off
Stg Up Delay=
5 min
3 min
0…60 min
Compressor start interstage
Stg Dn Delay=
3 min
3 min
3…30 min
Compressor stop interstage
Strt Strt Dly=
20min
15min
15…60 min
Compressor Start to Start delay
Stop Strt Dly=
5min
3min
3…20 min
Compressor Stop to Start delay
Ice Cycle Dly=
12h
12h
1…23h
Ice cycle delay
Lt Ld Stg Dn %=
40%
20%
20…50%
Circuit capacity threshold to stage down one compressor
Hi Ld Stg Up %=
80%
50%
50…100%
Circuit capacity threshold to stage up one compressor
Max Ckts Run=
2
2
1…2
Limit to the number of circuit to be used
C1 Sequence #=
1
1
1…2
Manual sequence of circuit #1
C2 Sequence #=
1
1
1…2
Manual sequence of circuit #2
Next Crkt On=
0
0
-
Shows next circuit to be started up
Next Crkt Off=
0
0
-
Shows next circuit number to be stopped
Setpoint/Sub-Menu
Default
Range
Description TZ / TZ B
VZ
Control Source=
Local
Local
Local, Network
Local Network control selection
Act Ctrl Src=
Local
N/A
Local, Network
Actual control between Local, Network
Netwrk En SP=
Disable
Disable
Enable, Disable
Enable unit command from BMS
Netwrk Mode SP=
Cool
Cool
-
Cool, Ice, Heat (NA), Cool/Heat Recovery
Netwrk Cool SP=
6.7°C
6.7°C
-
Cooling setpoint from BMS
Netwrk Cap Lim=
100%
100%
-
Capacity limitation from BMS
Netwrk HR SP=
45.0°C
N/A
-
Heat recovery setpoint from BMS
Network Heat SP=
N / A
45.0°C
-
Heating setpoint from BMS (W/C Units only)
Netwrk Ice SP=
-4.0°C
-4.0°C
-
Ice setpoint from BMS
Netwrk Current SP=
800A
800A
-
Sepoint for current limitation from BMS
Remote Srv En=
Disable
Disable
Enable, Disable
Remote server enable
Setpoint/Sub-Menu
Default
Range
Description
Baud Rate=
19200
4800, 9600, 19200, 38400
Modbus communication speed
Parity=
None
None, Odd, Even
Parity
Two Stop Bits=
No
No, Yes
Number of stop bits
485 Resistance=
Active
Active, Passive
RS485 Termination resistance
Set Inv1 Fltr=
Hold
Hold, Exec
Command to enable communication filter on the compressor 1
Set Inv2 Fltr=
Hold
Hold, Exec
Command to enable communication filter on the compressor 2
Setpoint/Sub-Menu
Default
Range
Description
TZ / TZB
VZ
Evp Pmp Ctrl=
#1 Only
#1 Only
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Set number of Evaporator pumps operational and which priority.
Evap Recirc Tm=
30s
30s
0…300s
Water recirculating timer
Evap Pmp 1 Hrs=
0h
0h Running Hours Evaporator Pump 1 (if present)
Evap Pmp 2 Hrs=
0h
0h Running Hours Evaporator Pump 2 (if present)
Speed 1=
80%
N/A
0-100%
Speed when the input Double Speed Switch is open
Cnd Pump Ctrl=
N/A
#1 Only
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Set number of Condenser pumps operational and which priority.
4.2.2 Network Ctrl
This page resumes all settings related to Network control.
4.2.3 Compressor Vfd Setup (A/C Units only)
This page contains basics Vfd Settings. It will be possible to set the Modbus address of each inverter installed on compressors. This function is supposed to be activated in case of compressor replacement. The page will also contain the Modbus setup parameters like baud rate, parity etc.
4.2.4 Pumps
This page contains the settings to define the operation of the primary/backup pumps, the running hours of each pump and all parameters to configure the behavior of the pump driven with an inverter.
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
23/84
Setpoint/Sub-Menu
Default
Range
Description
TZ / TZB
VZ
Cond Pmp 1 Hrs=
N/A
0h Running Hours Condenser Pump 1 (if present)
Cond Pmp 2 Hrs=
N/A
0h Running Hours Condenser Pump 2 (if present)
Speed 2=
60%
N/A
0-100%
Speed when the input Double Speed Switch is close
Thermo Off Speed=
50%
N/A
0-100%
Speed when there are no compressors running
Plant PD=
-
N/A - Actual Plant Pressure Measurements
Plant PD Sp=
0kPa
N/A
0-1000kPa
Plant Pressure Drop Setpoint
Evap PD=
-
N/A - Actual Evaporator Pressure Drop Measurements
Min Evap PD=
0kPa
N/A
0-1000kPa
Minimum Evaporator Pressure Drop setpoint
Hysteresis
0kPa
N/A
0-1000kPa
Hysteresis value for bypass value
Pump Speed=
-
N/A - Actual Pump Speed
Min Speed=
0%
N/A
0-100%
Minimum Pump Speed
Max Speed=
100%
N/A
0-100%
Maximum Pump Speed
Mode=
Auto
N/A
Auto-Manual
Pump mode
Manual Speed=
0%
N/A
0-100%
Manual Pump Speed
Sns Scale=
200kPa
N/A
0-2000kPa
Plant Pressure Drop Sensor Scale
Bypass
Open
N/A
Open,Close
Bypass valve state
Setpoint/Sub-Menu
Default
Range
Description
Cond LWT
-273.1°C
-
Present value of Condenser Leaving Water Temperature
Cond EWT
-273.1°C
-
Present value of Condenser Entering Water Temperature
Cond Target
25.0 °C
19.0…55.0 °C
Target for Condenser Leaving Water Temperature
Cond Fan Spd
0.0%
0.0…100.0%
Present value of Condenser Fan Speed
Tower Setpt 1
25.0 °C
19.0…55.0 °C
Setpoint for activation of Tower 1
Tower Setpt 1
27.0 °C
26.0…55.0 °C
Setpoint for activation of Tower 2
Tower Setpt 3
29.0 °C
28.0…55.0 °C
Setpoint for activation of Tower 3
Tower Setpt 4
31.0 °C
30.0…55.0 °C
Setpoint for activation of Tower 4
Tower Diff 1
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 2
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 3
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 4
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Min Vfd Sp
10.0%
0.0…49.0 %
Setpoint for minimum percentage of Vfd Speed
Max Vfs Sp
100.0%
55.0…100.0%
Setpoint for maximum percentage of Vfd Speed
PID Prop Gain
10.0
0.0…50.0
Proportional Gain of PID condensation controller
PID Der Time
1s
0...180s
Derivative Time of PID condensation controller
PID Int Time
600s
0…600s
Integral Time of PID condensation controller
Vfd Manual Speed
20.0%
0.0…100.0%
Setpoint for Vfd manual speed
Setpoint/Sub-Menu
Default
Range
Description
Internal Fan
Enable
Disable, Enable
Enable/Disable the pressurization fan internal to the unit switchbox.
Flamablty Lim
23.0 °C
-
Present value of Flammability limit
Setpoint/Sub­Menu
Default
Range
Description
Data  -
Submenu Data. This link is available only on the Master unit
Options
- Submenu Options. This link is available only on the Master unit
Thermostat Ctrl
-
Submenu Thermostat Ctrl. This link is available only on the Master unit
Timers
- Submenu Timers. This link is available only on the Master unit
Standby Chiller
- Submenu Standby Chiller. This link is available only on the Master unit
Disconnect Unit
No
No,Yes
Parameter to disconnect the unit by the Master Slave system. When this parameter is set to Yes the unit follows all local settings.
4.2.5 Condenser (W/C units only)
This page contains basics settings for condensation control described in section 5.4.
4.2.6 Press Fan (W/C units only)
4.2.7 Master/Slave
All data and parameters available in this sub-menus are related to the Master Slave function. Refer to Master Slave manual for more details.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 24/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
Setpoint/Sub-Menu
Default
Range
Description
Next On=
-
-,Master, Slave 1, Slave 2, Slave 4
Display next chiller that will be starts
Next Off=
-
-,Master, Slave 1, Slave 2, Slave 4
Display next chiller that will be stopped
Standby=
-
-,Master, Slave 1, Slave 2, Slave 4
Display the actual standby chiller
Switch Date
-
dd/mm/yyyy
Display the day in which the standby chiller will be cycled
Switch Time
-
hh:mm:ss
Display at which time of the switch day the standby chiller will be cycled
Plant Load=
-
0%...100%
Display the actual plant load
Avg EWT
- - Display the actual average entering water temperature value
Common EWT
- - Display the actual common entering water temperature value
Mst State=
-
Off, On, Alarm, Comm Err
Display the actual state of the Master
Sl1 State=
-
Off, On, Alarm, Comm Err
Display the actual state of the Slave 1
Sl2 State=
-
Off, On, Alarm, Comm Err
Display the actual state of the Slave 2
Sl3 State=
-
Off, On, Alarm, Comm Err
Display the actual state of the Slave 3
Mst Standalone=
-
No, Yes
Display if the standalone mode if active on the Master
Sl1 Standalone
-
No, Yes
Display if the standalone mode if active on the Slave 1
Sl2 Standalone
-
No, Yes
Display if the standalone mode if active on the Slave 2
Sl3 Standalone
-
No, Yes
Display if the standalone mode if active on the Slave 3
Mst Load=
-
0%...100%
Display the actual load of the Master
Sl1 Load=
-
0%...100%
Display the actual load of the Slave 1
Sl2 Load=
-
0%...100%
Display the actual load of the Slave 2
Sl3 Load=
-
0%...100%
Display the actual load of the Slave 3
Mst LWT=
- - Display the Master leaving water temperature
Sl1 LWT=
- - Display the Slave1 leaving water temperature
Sl2 LWT=
- - Display the Slave2 leaving water temperature
Sl3 LWT=
- - Display the Slave3 leaving water temperature
Mst EWT=
- - Display the Master entering water temperature
Sl1 EWT=
- - Display the Slave1 entering water temperature
Sl2 EWT=
- - Display the Slave2 entering water temperature
Sl3 EWT=
- - Display the Slave3 entering water temperature
Mst Hrs=
- - Master running hours
Sl1 Hrs=
- - Slave 1 running hours
Sl2 Hrs=
- - Slave 2 running hours
Sl3 Hrs=
- - Slave 3 running hours
Mst Starts=
- - Master number of starts
Sl1 Starts=
- - Slave 1 number of starts
Sl2 Starts=
- - Slave 2 number of starts
Sl3 Starts=
- - Slave 3 number of starts
Setpoint/Sub-Menu
Default
Range
Description
Master Priority=
1
1…4
Start Up / Shut Down priority of the chiller Master Priority = 1 highest priority Priority = 4 lowest priority
Slave 1 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 1 Priority = 1 highest priority Priority = 4 lowest priority
Slave 2 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 2. Priority = 1 highest priority Priority = 4 lowest priority This menu is visble only if the parameter M/S Num Of Unit has been configured at least with value 3
Slave 3 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 3. Priority = 1 highest priority Priority = 4 lowest priority This menu is visble only if the parameter M/S Num Of Unit has been configured at least with value 4
Master Enable=
Enable
Enable Disable
This parameter allows to enable or disable locally the Master Chiller
Control Mode=
Complete
Partial Complete
Parameter to select the Partial or Complete control mode Partial On/Off control
4.2.7.1 Data
In this menu are collected all main data related to Master Slave function.
4.2.7.2 Options
This menu allows to set main parameter of Master Slave function
Air and Water cooled inverter chillers and heat pump
EWAD TZ - EWAD TZ B - EWWD VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual
25/84
Setpoint/Sub-Menu
Default
Range
Description
Complete On/Off + Capacity control
Control Tmp=
Leaving
Entering Leaving
Parameter to define the controlled temperature Entering - Thermoregulations is based on the Average Entering Water Temperature (AEWT) Leaving - Thermoregulation is based on the Common Leaving Water Temperature (CLWT)
Setpoint/Sub-Menu
Default
Range
Description
Stage Up DT=
2.7°C
0.5…5.0°C
Offset respect the active setpoint for the unit startup.
Stage Dn DT =
1.5°C
0.5…5.0°C
Offset respect the active setpoint for the unit shutdown.
Dead Band =
0.2
0.1 - Min(Stage UP DT, Stage Dn DT)
Dead Band respect the active setpoint within which the load/unload command are no longer generated
Threshold=
60%
30...100%
Threshold of load that have to reach all units running before start of a new chiller
Stage Up Time=
5min
0min…20min
Minimum time between the start of two chillers
Stage Dn Time=
5min
0min…20min
Minim time between the stop of two chillers
Min Evap Tmp=
4.0
-18…30°C
Minimum Evaporator leaving water temperature
Setpoint/Sub-Menu
Default
Range
Description
Stage Up Timer=
- - Current delay for new chiller stage up
Stage Dn Timer=
- - Current delay for new chiller stage down
Clear Timers=
Off
Off Reset
This command, visible only with service password, can be used to reset the Stage Up/Dn Timer.
Setpoint/Sub-Menu
Default
Range
Description
Standby Chiller=
No
No, Auto, Master, Slave 1, Slave 2, Slave 3
Standby chiller selection
Cycling Type=
Time
Run Hours, Sequence
Cycling type of standby chiller if previous parameter Standby Chiller is set as Auto
Interval Time=
7 Days
1…365
Define the interval time (expressed in day) for the cycling of standby chiller
Switch Time=
00:00:00
00:00:00…23:59:59
Define the time within the day when will be performed the switch of the standby chiller
Tmp Cmp=
No
No,Yes
Enabling of Temperature Compensation function
Tmp Comp Time=
120 min
0…600
Time constant of Temperature Compensation function
Standby Reset=
Off
Off, Reset
Parameter to reset standby chiller cycling timer
Setpoint/Sub-Menu
Default
Range
Description
Rapid Restart=
Disable
Enable, Disable
Feature enable if Rapid Restart is installed
Pwr Off Time=
60s - Maximum black out time to enable Rapid Restart
4.2.7.3 Thermostat Ctrl
This page resumes all thermostat control parameter of Master Slave.
4.2.7.4 Timers
4.2.7.5 Standby Chiller
This menu allows to configure the standby chiller
4.2.8 Rapid Restart
This page shows if the function Rapid Restart is enabled by external contact and it allows to define the maximum black out time in order to recover quickly the unit load.
4.2.9 Date/Time
This page will allow to adjust the time and date in the UC. This time and date will be used in the alarm log and to enable and disable the Quiet Mode. Additionally it’s also possible to set the starting and ending date for the DayLight Saving time (DLS) if used. Quiet Mode is a feature that is used to reduce the chiller noise. This is done by applying the maximum setpoint reset to the cooling setpoint and increasing the condenser temperature target by an adjustable offset.
Air and Water cooled inverter chillers and heat pump
D-EOMZC00105-17EN Operation Manual 26/84
EWAD TZ - EWAD TZ B -EWWD VZ Air and Water cooled inverter chillers and heat pump
Setpoint/Sub-Menu
Default
Range
Description
TZ / TZ B
VZ
Actual Time=
12:00:00
12:00:00
Present time
Actual Date=
01/01/2014
01/01/2014
Present date
UTC Diff=
-60min
-60min
Difference with UTC
DLS Enable=
Yes
Yes No, Yes
DLS Strt Month=
Mar
Mar DayLight Saving time start month
DLS Strt Week=
2ndWeek
2ndWeek
DayLight Saving time start week
DLS End Month=
Nov
Nov
NA, Jan…Dec
DayLight Saving time end month
DLS End Week=
1stWeek
1stWeek
1
st…5th
week
DayLight Saving time end week
Quiet Mode=
Disable
N/A
Disable, Enable
Activate Quiet Mode
QM Start Hr=
21h
N/A
18…23h
Quiet Mode start hour
QM Start Min=
0min
N/A
0…59min
Quiet Mode start minute
QM End Hr=
6h
N/A
5…9h
Quiet Mode end hour
QM End Min=
0min
N/A
0…59min
Quiet Mode end minute
QM Cond Offset=
5°C
N/A
0.0…14.0°C
Quiet Mode condenser target offset
Setpoint/Sub-Menu
Default
Range
Description
State
Off
Off, On Setpoint 1, On Setpoint 2
Actual state provided by the time scheduler
Monday
- Link to Monday scheduler programming page
Tuesday
- Link to Tuesday scheduler programming page
Wednesday
- Link to Wednesday scheduler programming page
Thursday
- Link to Thursday scheduler programming page
Friday
- Link to Friday scheduler programming page
Saturday
- Link to Saturday scheduler programming page
Sunday
- Link to Sunday scheduler programming page
Setpoint/Sub-Menu
Default
Range
Description
Time 1
*:*
0:00..23:59
Define the starting time of 1st time slot
Value 1
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 1st time slot
Time 2
*:*
0:00..23:59
Define the starting time of 2nd time slot
Value 2
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 2nd time slot
Time 3
*:*
0:00..23:59
Define the starting time of 3rd time slot
Value 3
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 3rd time slot
Time 4
*:*
0:00..23:59
Define the starting time of 4th time slot
Value 4
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 4th time slot
Time 5
*:*
0:00..23:59
Define the starting time of 5th time slot
Value 5
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 5th time slot
Time 6
*:*
0:00..23:59
Define the starting time of 6th time slot
Value 6
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 6th time slot
Setpoint/Sub­Menu
Default
Range
Description
TZ/TZ B
VZ
Unit Capacity=
100.0%
100.0%
Demand Lim En=
Disable
Disable
Disable, Enable
Demand Limit Enable
Demand Limit=
100.0%
100.0%
Demand Limit Mode - Active demand limitation
Unit Current=
0.0A
E/M Only
Current Limit Mode (optional) - Unit current reading
Current Limit=
800A
800A
Current Limit Mode (optional) - Active Current limit
Flex Current Lm=
Disable
Disable
Disable, Enable
Flexible Current Limit Enable
Current Lim Sp=
800A
800A
0…2000A
Current Limit Mode (optional) - Current limit setpoint
Setpoint Reset=
None
None
None, 4-20mA, Return, OAT
Setpoint Reset Type (OAT reset Max Reset=
5.0°C
5.0°C
0.0…10.0°C
Setpoint Reset Mode - Max Reset of water temp. setpoint
On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure that the battery is replaced regularly each 2 years (see section 3.6).
4.2.10 Scheduler
This page allows to program the time scheduler
Table below reports the menu used to program daily time slots. Six time slots can be programmed by the user.
4.2.11 Power Conservation
This page resumes all the settings that allows chiller capacity limitations. Further explanations of the setpoint reset options can be found in the chapter 7.2.
Loading...
+ 58 hidden pages