Daikin ERHQ011-014-016BA, ERLQ011-014-016CA, EHVZ16S18CB Installer reference guide

Page 1
+
Installer reference guide
Daikin Altherma – Low temperature split
ERHQ011-014-016BA ERLQ011-014-016CA EHVZ16S18CB
Installer reference guide
Daikin Altherma – Low temperature split
English
Page 2

Table of Contents

Table of Contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the installer.......................................................................... 4
1.2.1 General ....................................................................... 4
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 4
1.2.4 Brine............................................................................ 5
1.2.5 Water .......................................................................... 5
1.2.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
2.2 Installer reference guide at a glance ......................................... 6
3 About the box 7
3.1 Overview: About the box ........................................................... 7
3.2 Outdoor unit............................................................................... 7
3.2.1 To unpack the outdoor unit ......................................... 7
3.2.2 To handle the outdoor unit.......................................... 7
3.2.3 To remove the accessories from the outdoor unit....... 7
3.3 Indoor unit ................................................................................. 8
3.3.1 To unpack the indoor unit ........................................... 8
3.3.2 To remove the accessories from the indoor unit......... 8
4 About the units and options 8
4.1 Overview: About the units and options...................................... 8
4.2 Identification .............................................................................. 9
4.2.1 Identification label: Outdoor unit ................................. 9
4.2.2 Identification label: Indoor unit .................................... 9
4.3 Combining units and options ..................................................... 9
4.3.1 Possible options for the outdoor unit........................... 9
4.3.2 Possible options for the indoor unit............................. 9
4.3.3 Possible combinations of indoor unit and outdoor
unit .............................................................................. 10
5 Application guidelines 11
5.1 Overview: Application guidelines............................................... 11
5.2 Setting up the space heating system ........................................ 11
5.2.1 Multiple rooms – TwoLWT zones............................... 11
5.3 Setting up the domestic hot water tank ..................................... 12
5.3.1 System layout – Integrated DHW tank........................ 12
5.3.2 Selecting the volume and desired temperature for
the DHW tank.............................................................. 12
5.3.3 Setup and configuration – DHW tank.......................... 13
5.3.4 DHW pump for instant hot water................................. 13
5.3.5 DHW pump for disinfection ......................................... 13
5.4 Setting up the energy metering ................................................. 13
5.4.1 Produced heat............................................................. 13
5.4.2 Consumed energy....................................................... 13
5.4.3 Normal kWh rate power supply................................... 14
5.4.4 Preferential kWh rate power supply............................ 14
5.5 Setting up the power consumption control ................................ 14
5.5.1 Permanent power limitation ........................................ 14
5.5.2 Power limitation activated by digital inputs ................. 15
5.5.3 Power limitation process ............................................. 15
5.6 Setting up an external temperature sensor ............................... 15
6 Preparation 16
6.1 Overview: Preparation............................................................... 16
6.2 Preparing installation site .......................................................... 16
6.2.1 Installation site requirements of the outdoor unit ........ 16
6.2.2 Additional installation site requirements of the
outdoor unit in cold climates ....................................... 17
6.2.3 Installation site requirements of the indoor unit .......... 17
6.3 Preparing refrigerant piping....................................................... 18
6.3.1 Refrigerant piping requirements.................................. 18
6.3.2 Refrigerant piping insulation ........................................ 18
6.4 Preparing water piping ............................................................... 18
6.4.1 Water circuit requirements ........................................... 18
6.4.2 Formula to calculate the expansion vessel pre-
pressure ....................................................................... 19
6.4.3 To check the water volume and flow rate .................... 19
6.4.4 Changing the pre-pressure of the expansion vessel.... 20
6.4.5 To check the water volume: Examples ........................ 21
6.5 Preparing electrical wiring .......................................................... 21
6.5.1 About preparing electrical wiring.................................. 21
6.5.2 About preferential kWh rate power supply ................... 21
6.5.3 Overview of electrical connections except external
actuators ...................................................................... 22
6.5.4 Overview of electrical connections for external and
internal actuators ......................................................... 22
7 Installation 23
7.1 Overview: Installation ................................................................. 23
7.2 Opening the units ....................................................................... 23
7.2.1 About opening the units ............................................... 23
7.2.2 To open the outdoor unit.............................................. 23
7.2.3 To open the indoor unit ................................................ 23
7.2.4 To open the switch box cover of the indoor unit .......... 23
7.3 Mounting the outdoor unit........................................................... 23
7.3.1 About mounting the outdoor unit.................................. 23
7.3.2 Precautions when mounting the outdoor unit............... 24
7.3.3 To provide the installation structure ............................. 24
7.3.4 To install the outdoor unit............................................. 24
7.3.5 To provide drainage ..................................................... 24
7.3.6 To prevent the outdoor unit from falling over ............... 25
7.4 Mounting the indoor unit............................................................. 25
7.4.1 About mounting the indoor unit.................................... 25
7.4.2 Precautions when mounting the indoor unit................. 25
7.4.3 To install the indoor unit............................................... 25
7.5 Connecting the refrigerant piping ............................................... 25
7.5.1 About connecting the refrigerant piping ....................... 25
7.5.2 Precautions when connecting the refrigerant piping.... 26
7.5.3 Guidelines when connecting the refrigerant piping...... 26
7.5.4 Pipe bending guidelines............................................... 26
7.5.5 To flare the pipe end .................................................... 26
7.5.6 To braze the pipe end .................................................. 27
7.5.7 Using the stop valve and service port .......................... 27
7.5.8 To connect the refrigerant piping to the outdoor unit ... 28
7.5.9 To connect the refrigerant piping to the indoor unit ..... 29
7.5.10 To determine if oil traps are required ........................... 29
7.6 Checking the refrigerant piping .................................................. 29
7.6.1 About checking the refrigerant piping .......................... 29
7.6.2 Precautions when checking the refrigerant piping ....... 29
7.6.3 Checking refrigerant piping: Setup............................... 29
7.6.4 To check for leaks........................................................ 29
7.6.5 To perform vacuum drying ........................................... 30
7.7 Charging refrigerant ................................................................... 30
7.7.1 About charging refrigerant ........................................... 30
7.7.2 Precautions when charging refrigerant ........................ 30
7.7.3 To determine the additional refrigerant amount........... 30
7.7.4 To determine the complete recharge amount.............. 30
7.7.5 To charge additional refrigerant ................................... 31
7.7.6 To fix the fluorinated greenhouse gases label ............. 31
7.8 Connecting the water piping....................................................... 31
7.8.1 About connecting the water piping............................... 31
7.8.2 Precautions when connecting the water piping............ 31
7.8.3 To connect the water piping......................................... 31
7.8.4 To connect the recirculation piping .............................. 32
7.8.5 To connect the pressure relief valve to the drain......... 32
7.8.6 To fill the water circuit .................................................. 32
7.8.7 To fill the domestic hot water tank ............................... 33
7.8.8 To insulate the water piping ......................................... 33
7.9 Connecting the electrical wiring.................................................. 33
7.9.1 About connecting the electrical wiring.......................... 33
7.9.2 About electrical compliance ......................................... 33
Installer reference guide
2
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 3

1 General safety precautions

7.9.3 Precautions when connecting the electrical wiring ..... 34
7.9.4 Guidelines when connecting the electrical wiring ....... 34
7.9.5 Specifications of standard wiring components............ 34
7.9.6 To connect the electrical wiring on the outdoor unit.... 34
7.9.7 To reposition the air thermistor on the outdoor unit .... 35
7.9.8 To connect the electrical wiring on the indoor unit...... 36
7.9.9 To connect the main power supply ............................. 37
7.9.10 To connect the backup heater power supply .............. 37
7.9.11 To connect the user interface ..................................... 38
7.9.12 To connect the shut-off valve ...................................... 39
7.9.13 To connect the electrical meters ................................. 39
7.9.14 To connect the domestic hot water pump ................... 39
7.9.15 To connect the alarm output ....................................... 39
7.9.16 To connect the power consumption digital inputs ....... 40
7.9.17 To connect the safety thermostat (normal closed
contact) ....................................................................... 40
7.10 Finishing the outdoor unit installation ........................................ 40
7.10.1 To finish the outdoor unit installation .......................... 40
7.10.2 To close the outdoor unit ............................................ 41
7.11 Finishing the indoor unit installation .......................................... 41
7.11.1 To fix the user interface cover to the indoor unit ......... 41
7.11.2 To close the indoor unit............................................... 41
8 Configuration 41
8.1 Overview: Configuration ............................................................ 41
8.1.1 To connect the PC cable to the switch box................. 41
8.1.2 To access the most used commands ......................... 42
8.1.3 To copy the system settings from the first to the
second user interface.................................................. 42
8.1.4 To copy the language set from the first to the second
user interface .............................................................. 43
8.1.5 Quick wizard: Set the system layout after first power
ON............................................................................... 43
8.2 Basic configuration .................................................................... 43
8.2.1 Quick wizard: Language / time and date..................... 43
8.2.2 Quick wizard: Standard............................................... 44
8.2.3 Quick wizard: Options ................................................. 45
8.2.4 Quick wizard: Capacities (energy metering) ............... 47
8.2.5 Space heating control ................................................. 48
8.2.6 Domestic hot water control ......................................... 50
8.2.7 Contact/helpdesk number........................................... 50
8.3 Advanced configuration/optimization......................................... 50
8.3.1 Space heating operation: advanced ........................... 50
8.3.2 Domestic hot water control: advanced........................ 53
8.3.3 Heat source settings ................................................... 56
8.3.4 System settings........................................................... 57
8.4 Menu structure: Overview user settings .................................... 61
8.5 Menu structure: Overview installer settings............................... 62
9 Commissioning 63
9.1 Overview: Commissioning......................................................... 63
9.2 Precautions when commissioning ............................................. 63
9.3 Checklist before commissioning................................................ 63
9.4 Checklist during commissioning ................................................ 63
9.4.1 To check the minimum flow rate ................................. 64
9.4.2 Air purge function........................................................ 64
9.4.3 To perform a test run .................................................. 65
9.4.4 To perform an actuator test run .................................. 65
9.4.5 Underfloor heating screed dryout................................ 66
10 Hand-over to the user 67
11 Maintenance and service 67
11.1 Overview: Maintenance and service ......................................... 67
11.2 Maintenance safety precautions................................................ 67
11.2.1 Opening the indoor unit............................................... 67
11.3 Checklist for yearly maintenance of the outdoor unit ................ 67
11.4 Checklist for yearly maintenance of the indoor unit................... 67
11.4.1 To drain the domestic hot water tank .......................... 68
12 Troubleshooting 69
12.1 Overview: Troubleshooting......................................................... 69
12.2 Precautions when troubleshooting ............................................. 69
12.3 Solving problems based on symptoms....................................... 69
12.3.1 Symptom: The unit is NOT heating as expected ......... 69
12.3.2 Symptom: The compressor does NOT start (space
heating or domestic water heating).............................. 69
12.3.3 Symptom: The pump is making noise (cavitation) ....... 70
12.3.4 Symptom: The pressure relief valve opens.................. 70
12.3.5 Symptom: The water pressure relief valve leaks ......... 70
12.3.6 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ............................................ 70
12.3.7 Symptom: The pressure at the tapping point is
temporarily unusually high ........................................... 71
12.3.8 Symptom: Decoration panels are pushed away due
to a swollen tank .......................................................... 71
12.3.9 Symptom: Tank disinfection function is NOT
completed correctly (AH-error)..................................... 71
12.4 Solving problems based on error codes ..................................... 71
12.4.1 Error codes: Overview ................................................. 71
13 Disposal 73
13.1 Overview: Disposal..................................................................... 73
13.2 About pump down ...................................................................... 73
13.3 To pump down............................................................................ 73
14 Technical data 74
14.1 Piping diagram: Outdoor unit...................................................... 74
14.2 Piping diagram: Indoor unit ........................................................ 75
14.3 Wiring diagram: Outdoor unit ..................................................... 76
14.4 Wiring diagram: Indoor unit ........................................................ 77
14.5 ESP curve: Indoor unit ............................................................... 79
15 Glossary 81
16 Field settings table 82
1 General safety precautions

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be performed by an authorized installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
3
Page 4
1 General safety precautions
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.

1.2 For the installer

1.2.1 General

If you are not sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

1.2.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

1.2.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
Installer reference guide
4
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 5
1 General safety precautions
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
Charge with the cylinder upright.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.

1.2.4 Brine

If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.2.5 Water

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.

1.2.6 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
A siphon tube is NOT present Charge with the cylinder upside
down.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring.
Installer reference guide
5
Page 6

2 About the documentation

WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation

2.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
Installer reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
http://www.daikineurope.com/support-and-manuals/product­information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).

2.2 Installer reference guide at a glance

Chapter Description
General safety precautions
About the documentation What documentation exists for the
About the box How to unpack the units and remove
About the units and options
Application guidelines Various installation setups of the system
Preparation What to do and know before going
Installation What to do and know to install the
Configuration What to do and know to configure the
Safety instructions that you must read before installing
installer
their accessories
▪ How to identify the units
▪ Possible combinations of units and
options
on‑site
system
system after it is installed
Installer reference guide
6
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 7

3 About the box

21
102~114 kg
2
1
a
c
b
d
e
f
g
Chapter Description
Commissioning What to do and know to commission the
system after it is configured
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
kept for future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.
3 About the box

3.1 Overview: About the box

This chapter describes what you have to do after the boxes with the outdoor and indoor unit are delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.

3.2 Outdoor unit

3.2.1 To unpack the outdoor unit

3.2.2 To handle the outdoor unit

Carry the unit slowly as shown:
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.

3.2.3 To remove the accessories from the outdoor unit

a Outdoor unit installation manual b Cable tie c Fluorinated greenhouse gases label d Multilingual fluorinated greenhouse gases label e Screw (only for ERLQ)
f Thermistor fixing plate (spare) (only for ERLQ)
g Thermistor fixture (only for ERLQ)
Installer reference guide
7
Page 8

4 About the units and options

a~e+i
h
f+g
5
4
1
2
3
4
a b c d
f
g h ie

3.3 Indoor unit

3.3.1 To unpack the indoor unit

3.3.2 To remove the accessories from the indoor unit

1 Remove the screws at the top of the unit.
2 Remove the top panel.
3 Remove the screws at the front of the unit.
4 Push on the button on the bottom of the front plate.
5 Remove the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower part. Watch your fingers, there are sharp edges on the lower part of the front plate.
6 Remove the accessories.
a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut-off valve
f Shut-off valve with drain/fill point g Shut-off valve h User interface cover
i 2 screws for fixing the user interface.
7 Reinstall the top panel and the front plate.
4 About the units and options

4.1 Overview: About the units and options

This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the indoor unit
▪ Combining outdoor and indoor units
▪ Combining the outdoor unit with options
▪ Combining the indoor unit with options
Installer reference guide
8
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 9
4 About the units and options

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Outdoor unit

Location
Model identification
▪ ERLQ: Contains components (insulation, bottom plate heater,…)
to prevent freeze-up in areas with low ambient temperature and high humidity.
▪ ERHQ: Does NOT contain these components.
Example: ERLQ011CAW1
Code Explanation
ER European split outdoor pair heat pump
L H=Low water temperature – ambient zone:
0⁠~⁠−⁠10°C
L=Low water temperature – ambient zone:
−⁠10⁠~⁠−⁠20°C
Q Refrigerant R410A
011 Capacity class
CA Model series
W1 Power supply

4.2.2 Identification label: Indoor unit

Location
Code Description
S Integrated tank material: Stainless steel
18 Integrated tank volume
CB Model series
3V Backup heater model

4.3 Combining units and options

4.3.1 Possible options for the outdoor unit

Demand PCB (KRP58M51) (only for ERLQ)
▪ Limits the maximum current. However, this also decreases the
heating/cooling capacity of the system.
▪ Only the "Setting of demand running" function of the demand PCB
is applicable.
▪ For installation instructions, see the installation manual of the
demand PCB.
Snow cover (EK016SNC) (only for ERLQ)
▪ Prevents the outdoor unit from being snowed up.
▪ Recommended in areas with low ambient temperatures or heavy
snowfall.
▪ For installation instructions, see the installation manual of the
snow cover.
Drain plug kit (EKDK04) (only for ERHQ)
▪ Gathers the condensate from the outdoor unit and guides it away
through 1 plug in the bottom plate.
▪ For ERLQ: Drain plug kit is not applicable.
▪ For ERHQ: Drain plug kit is option.
▪ Cannot be combined with bottom plate heater.
▪ For installation instructions, see the installation manual of the
drain plug kit.
Bottom plate heater (EKBPHTH16A) (only for ERHQ in combination with C* indoor unit)
▪ Prevents freeze-up of the bottom plate.
▪ Recommended in areas with low ambient temperature and high
humidity.
▪ For ERLQ: Bottom plate heater is standard (factory-mounted).
▪ For ERHQ: Bottom plate heater is option.
▪ Cannot be combined with drain plug kit.
▪ If you install EKBPHTH16A, you also have to install the digital I/O
PCB (EKRP1HB).
▪ For installation instructions, see the installation manual of the
bottom plate heater and addendum book for optional equipment.
Model identification
Example: EHVZ04S18CB3V
Code Description
E European model
HV Floor-standing indoor unit with integrated tank
Z Dual-zone model
04 Capacity class
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04

4.3.2 Possible options for the indoor unit

User interface (EKRUCBL*)
The user interface and a possible additional user interface are available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
Installer reference guide
9
Page 10
4 About the units and options
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.
For installation instructions, see "7.9.11 To connect the user
interface"on page38.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation manual of the simplified user interface.
Room thermostat (EKRTWA, EKRTR1, RTRNETA)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1 and RTRNETA). Thermostat RTRNETA can only be used in heating-only systems.
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating On/OFF output
▪ Changeover to external heat source
▪ Only for EHVZ16S18 model: Control signal for bottom plate heater
kit EKBPHTH16A.
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the
user interface is configured with room thermostat functionality.
▪ You can only connect either the remote indoor sensor
or the remote outdoor sensor.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to upload different language files to the user interface and indoor parameters to the indoor unit. For the available language files, contact your local dealer.
The software and corresponding operating instructions are available on http://www.daikineurope.com/support-and-manuals/software-
downloads/.
For installation instructions, see the installation manual of the PC cable and "8Configuration"on page41.
Heat pump convector (FWXV)
For providing space heating, it is possible to use heat pump convectors (FWXV).
For installation instructions, refer to the installation manual of the heat pump convectors, and the addendum book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter.

4.3.3 Possible combinations of indoor unit and outdoor unit

Outdoor unit Indoor unit
EHVZ16
ERHQ011+ERLQ011 O
ERHQ014+ERLQ014 O
ERHQ016+ERLQ016 O
Installer reference guide
10
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 11

5 Application guidelines

j
k
j
HPC1
FHL1 FHL2 FHL3
HPC2 HPC3
B
A
C
E
D
M
a b c
g hf
d e
i
i
hh
h
5 Application guidelines

5.1 Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the Daikin heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant
for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
▪ For more information about the configuration settings to
optimize heatpump operation, see "8Configuration"on
page41.
This chapter contains application guidelines for:
▪ Setting up the space heating system
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption
▪ Setting up an external temperature sensor

5.2 Setting up the space heating system

The Daikin heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
▪ How many rooms are heated by the Daikin heatpump system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating requirements are clear, Daikin recommends to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set auto emergency [A.6.C] to 1.
5.2.1 Multiple rooms – TwoLWT zones
This unit is designed to deliver water at 2 different temperatures. A typical installation consists of underfloor heating at a lower temperature and radiators at a higher water temperature.
In this document:
▪ Main zone = Zone with the lowest design temperature
▪ Additional zone = Zone with the highest design temperature
Typical example:
Living room (main zone) Underfloor heating: 35°C
Room (zone) Heat emitters: Design
temperature
Room (zone) Heat emitters: Design
temperature
Bed rooms (additional zone) Heat pump convectors: 45°C
Setup
A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone E Room 3
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Motorised 3-way valve (mixing the main zone)
f Additional pump g Main pump h Shut-off valve
i Collector (field supply)
j Remote controller of the heat pump convectors (field
supply)
k User interface (field supply)
HPC1...3 Heat pump convectors (field supply)
FHL1...3 Floor heating loops (field supply)
▪ For the main zone: the room temperature is controlled by the user
interface, which is used as room thermostat.
▪ For the additional zone:
▪ The external thermostat is directly connected to the indoor unit.
▪ The desired room temperature is set via the external thermostat
and the thermostatic valves of the radiators in each room.
▪ The heating demand signal from the external thermostat is
connected to the digital input on the indoor unit (X2M/1a and X2M/4). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
Note:
▪ Main room = user interface
used as room thermostat functionality
▪ Other rooms = external room
thermostat functionality
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
11
Page 12
5 Application guidelines
M
M
a b c d ge h ii
i
j
j
fki
HPC1
UI
FHL1 FHL2 FHL3
HPC2 HPC3
Setting Value
Number of water temperature zones:
1 (2 LWT zones): Main + additional
▪ #: [A.2.1.8]
▪ Code: [7-02]
In case of heatpump convectors:
External room thermostat for the additional zone:
▪ #: [A.2.2.5]
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition.
▪ Code: [C-06]
Shut-off valve output Set to follow the thermo demand
of the main zone.
Benefits
Comfort. The smart room thermostat functionality can decrease
or increase the desired leaving water temperature based on the actual room temperature (modulation).
Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of the different heat emitters.
▪ Underfloor heating has the best performance with Altherma LT.

5.3 Setting up the domestic hot water tank

5.3.1 System layout – Integrated DHW tank

5.3.2 Selecting the volume and desired temperature for the DHW tank

People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the desired temperature for the DHW tank.
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the desired DHW tank temperature.
▪ The heatpump itself can produce domestic hot water of maximum
55°C (50°C if outdoor temperature is low). The electrical resistance integrated in the heat pump can increase this temperature. However, this consumes more energy. Daikin recommends to set the desired DHW tank temperature below 55°C to avoid using the backup heater.
▪ The higher the outdoor temperature, the better the performance of
the heatpump.
▪ If energy prices are the same during the day and the night,
Daikin recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, Daikin recommends
to heat up the DHW tank during the night.
▪ When the heatpump produces domestic hot water, it cannot heat
up a space. When you need domestic hot water and space heating at the same, Daikin recommends to produce the domestic hot water during the night when there is lower space heating demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using the typical water volumes:
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Motorised 3‑wave valve (switch between space heating
and domestic hot water)
f Motorised 3‑way valve (mixing the main zone) g Main pump h Additional pump
i Shut-off valve j Collector (field supply)
k Domestic hot water tank
FHL1...3 Floor heating loops (field supply)
UI User interface (field supply)
HPC1...3 Heat pump convectors (field supply)
Installer reference guide
12
Question Typical water volume
How many showers are needed per day?
How many baths are needed per
1shower = 10min×10l/min = 100l
1bath = 150l
day?
How much water is needed at the
1sink = 2min×5l/min = 10l
kitchen sink per day?
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 13
5 Application guidelines
c f
a b
g
h
i
c a b
d f
e g
h
i
Determining the volume and desired temperature for the DHW tank
Formula Example
V1=V2+V2×(T2−40)/(40−T1) If:
▪ V2=180l
▪ T2=54°C
▪ T1=15°C
Then V1=280l
V1DHW consumption (equivalent hot water volume at 40°C) V2Required DHW tank volume if only heated once T2DHW tank temperature T1Cold water temperature

5.3.3 Setup and configuration – DHW tank

▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heatpump
▪ Electrical backup heater
▪ For more information about optimizing the energy consumption for
producing domestic hot water, see "8Configuration"on page41.

5.3.4 DHW pump for instant hot water

Setup
a Indoor unit
b DHW tank
c DHW pump (field supply)
f Shower (field supply)
g Cold water h Domestic hot water OUT
i Recirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For more information about connecting the recirculation
connection: see "7Installation"on page23.
Configuration
▪ For more information, see "8Configuration"on page41.
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference guide.

5.3.5 DHW pump for disinfection

Setup
i Recirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ The temperature of the DHW tank can be set to maximum 60°C. If
applicable legislation requires higher temperature for disinfection, you can connect a DHW pump and heater element as shown above.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.
▪ To ensure a complete disinfection, you have to open the tapping
point.
WARNING
When opening the tapping point, the water temperature can be up to 55°C.
Configuration
The indoor unit can control DHW pump operation. For more information, see "8Configuration"on page41.

5.4 Setting up the energy metering

▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space heating
▪ For domestic hot water production
▪ You can read out the energy data:
▪ Per month
▪ Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy cannot be guaranteed.

5.4.1 Produced heat

INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪ The produced heat is calculated internally based on:
▪ The leaving and entering water temperature
▪ The flow rate
▪ Setup and configuration: No additional equipment needed.

5.4.2 Consumed energy

You can use the following methods to determine the consumed energy:
▪ Calculating
▪ Measuring
a Indoor unit
b DHW tank
c DHW pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
f Shower (field supply)
g Cold water h Domestic hot water OUT
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater) and measuring the consumed energy (example: for outdoor unit). If you do so, the energy data will be invalid.
Calculating the consumed energy
▪ Only applicable for EHVZ04+08.
Installer reference guide
13
Page 14
5 Application guidelines
b
5
8
0
1
5
0
0
0
c c
fed
A B
a
b
5
8
0
1
5
0
0
0
gfe
A B
c d
a

P
i
t
DI
a
b
▪ The consumed energy is calculated internally based on:
▪ The actual power input of the outdoor unit
▪ The set capacity of the backup heater
▪ The voltage
▪ Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via the user interface for the backup heater (step1).
Measuring the consumed energy
▪ Applicable for all models.
▪ Preferred method because of higher accuracy.
▪ Requires external power meters.
▪ Setup and configuration: When using electrical power meters, set
the number of pulses/kWh for each power meter via the user interface. Consumed energy data for EHVZ16 model will only be available if this setting is configured.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters.

5.4.3 Normal kWh rate power supply

General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.
Power meter type
In case of… Use a… power meter
▪ Single-phase outdoor unit
▪ Backup heater supplied from a
single-phase grid
Three-phase outdoor unit Three-phase
Example
Single-phase power meter Three-phase power meter
Single-phase
Exception
▪ You can use a second power meter if:
▪ The power range of one meter is insufficient.
▪ The electrical meter cannot easily be installed in the electrical
cabinet.
▪ 230 V and 400 V three-phase grids are combined (very
uncommon), because of technical limitations of power meters.
▪ Connection and setup:
▪ Connect the second power meter to X5M/9 and X5M/10.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which power consumption. You only need to set the number of pulses of each power meter.
▪ See "5.4.4 Preferential kWh rate power supply"on page 14 for
an example with two power meters.

5.4.4 Preferential kWh rate power supply

General rule
▪ Power meter1: Measures the outdoor unit.
▪ Power meter 2: Measures the rest (i.e. indoor unit and backup
heater).
Setup
▪ Connect power meter1 to X5M/7 and X5M/8.
▪ Connect power meter2 to X5M/9 and X5M/10.
Power meter types
▪ Power meter1: Single- or three-phase power meter according to
the power supply of the outdoor unit.
▪ Power meter2: Use a single-phase power meter.

5.5 Setting up the power consumption control

▪ The power consumption control:
▪ Is only applicable for EHVZ04+08.
▪ Allows you to limit the power consumption of the entire system
(sum of outdoor unit, indoor unit and backup heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (inA)
▪ Maximum power input (inkW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
A Outdoor unit
B Indoor unit
a Electrical cabinet (L1/N)
b Power meter (L1/N)
c Fuse (L1/N)
d Outdoor unit (L1/N)
e Indoor unit (L1/N)
f Backup heater (L1/N)
Installer reference guide
14
A Outdoor unit
B Indoor unit
a Electrical cabinet (L1/L2/L3/N)
b Power meter (L1/L2/L3/N)
c Fuse (L1/L2/L3/N)
d Fuse (L1/N)
e Outdoor unit (L1/L2/L3/N)
f Indoor unit (L1/L2/L3/N)
g Backup heater (L1/N)

5.5.1 Permanent power limitation

Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 15
5 Application guidelines
a
b
A B
C
1
2
3
4
5
A8P
P
i
t
DI4
DI3
DI1
a
b
P
h
C
e
a
b
c
A B
PiPower input
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings in [A.6.3.1] via the
user interface (for the description of all settings, see
"8Configuration"on page41):
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
NOTICE
Mind the following guidelines when selecting the desired power limitation level:
▪ Set a minimum power consumption of ±3.6 kW to
guarantee defrost operation. Otherwise, if defrosting is interrupted several times, the heat exchanger will freeze up.
▪ Set a minimum power consumption of ±3 kW to
guarantee space heating and DHW production by allowing the backup heater step1.

5.5.2 Power limitation activated by digital inputs

Power limitation is also useful in combination with an energy management system.
The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation of a certain power limitation level. Example: To limit the maximum power of the entire house (lighting, domestic appliances, space heating…).
b Actual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
▪ Maximum four digital inputs are used to activate the
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specifications of the digital inputs, and for where to
connect them, refer to the wiring diagram.
Configuration
Set the power consumption control settings in [A.6.3.1] via the user interface (for the description of all settings, see "8Configuration"on
page41):
▪ Select activation by digital inputs.
▪ Select the type of limitation (power in kW or current in A).
▪ Set the desired power limitation level corresponding to each digital
input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority is fixed: DI4 priority>…>DI1.

5.5.3 Power limitation process

The outdoor unit has better efficiency than the electrical heater. Therefore, the electrical heater is limited and turned OFF first. The system limits power consumption in the following order:
1 Turns OFF the backup heater.
2 Limits the outdoor unit.
3 Turns OFF the outdoor unit.
Example
If the configuration is as follows: Power limitation level does NOT allow operation of backup heater (step1).
Then power consumption is limited as follows:
A Outdoor unit B Indoor unit C Energy management system
a Power limitation activation (4 digital inputs)
b Backup heater
PiPower input
t Time
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
DI Digital inputs (power limitation levels)
a Power limitation active
PhProduced heat CeConsumed energy
A Outdoor unit B Backup heater
a Limited outdoor unit operation b Full outdoor unit operation c Backup heater step1 turned ON

5.6 Setting up an external temperature sensor

You can connect one external temperature sensor. It can measure the indoor or outdoor ambient temperature. Daikin recommends to use an external temperature sensor in the following cases:
Installer reference guide
15
Page 16

6 Preparation

b
c
a
Indoor ambient temperature
▪ In room thermostat control, the user interface is used as room
thermostat and it measures the indoor ambient temperature. Therefore, the user interface must be installed on a location:
▪ Where the average temperature in the room can be detected
▪ That is NOT exposed to direct sunlight
▪ That is NOT near a heat source
▪ That is NOT affected by outside air or air draught because of,
for example, door opening/closing
▪ If this is NOT possible, Daikin recommends to connect a remote
indoor sensor (option KRCS01-1).
▪ Setup: For installation instructions, see the installation manual of
the remote indoor sensor.
▪ Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
▪ In the outdoor unit, the outdoor ambient temperature is measured.
Therefore, the outdoor unit must be installed on a location:
▪ At the north side of the house or at the side of the house where
the most heat emitters are located
▪ That is NOT exposed to direct sunlight
▪ If this is NOT possible, Daikin recommends to connect a remote
outdoor sensor (option EKRSCA1).
▪ Setup: For installation instructions, see the installation manual of
the remote outdoor sensor.
▪ Configuration: Select outdoor sensor [A.2.2.B].
▪ During suspend (see "8 Configuration"on page 41), the outdoor
unit is turned down to reduce the standby energy losses. As a result, the outdoor ambient temperature is NOT read out.
▪ If the desired leaving water temperature is weather dependent, the
full time outdoor temperature measurement is important. This is another reason to install the optional outdoor ambient temperature sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged or instantaneous) is used in the weather-dependent control curves. To protect the outdoor unit, the internal sensor of the outdoor unit is always used.
6 Preparation

6.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring
NOTICE
This unit is designed for operation on 2 temperature zones:
▪ underfloor heating in the main zone (water
temperature 35°C), this is the zone with the lowest water temperature,
▪ radiators in the additional zone (water temperature
45°C), this is the zone with the highest water
temperature.

6.2.1 Installation site requirements of the outdoor unit

INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Service space requirements. See the "Technical data"
chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
▪ Select a place where rain can be avoided as much as possible.
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble. Note: If the sound is measured under actual installation conditions, the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea winds. This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.

6.2 Preparing installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.
Installer reference guide
16
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 17
6 Preparation
a
b
c
d
c
d
a
b
c
b
a
b
c
c
d
>500
>10>10
(mm)
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a Sea wind
b Building
c Outdoor unit
d Windbreaker
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind.
INFORMATION
You can use the optional snow cover (EK016SNC).
a Snow cover or shed b Pedestal (minimum height=150mm) c Prevailing wind direction d Air outlet

6.2.3 Installation site requirements of the indoor unit

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
▪ Mind the measurement guidelines:
Maximum refrigerant piping length between indoor unit and outdoor unit
Minimum refrigerant piping length between indoor
ERHQ: 75m
ERLQ: 50m
(95m)
(70m)
(a)
(a)
3m
unit and outdoor unit
Maximum height difference between indoor unit and
30m
outdoor unit
(a) Parenthesised figure represents the equivalent length.
▪ Mind the following spacing installation guidelines:
a Baffle plate
b Prevailing wind direction
c Air outlet
The outdoor unit is designed for outdoor installation only, and for ambient temperatures ranging 10~43°C in cooling mode and – 25~25°C in heating mode.

6.2.2 Additional installation site requirements of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
Installer reference guide
17
Page 18
6 Preparation
t
Ø
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full of water into account. Make sure, in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~35°C.

6.3 Preparing refrigerant piping

6.3.1 Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Piping material: Phosphoric acid deoxidised seamless copper.
Piping diameter:
Liquid piping Ø9.5mm (3/8")
Gas piping Ø15.9mm (5/8")
Piping temper grade and thickness:
Outer diameter
(Ø)
9.5mm (3/8") Annealed (O) ≥0.8mm
15.9mm (5/8") Annealed (O) ≥1.0mm
(a) Depending on the applicable legislation and the unit's
Temper grade Thickness (t)
maximum working pressure (see "PS High" on the unit name plate), larger piping thickness might be required.

6.3.2 Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Ambient
temperature
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
Humidity Minimum thickness
(a)
Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.
Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get damaged.
Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
Closed circuit. Use the indoor unit ONLY in a closed water
system. Using the system in an open water system will lead to excessive corrosion.
Glycol. For safety reasons, it is NOT allowed to add any kind of
glycol to the water circuit.
Piping length. It is recommended to avoid long runs of piping
between the domestic hot water tank and the hot water end point (shower, bath,…) and to avoid dead ends.
Piping diameter. Select the water piping diameter in relation to
the required water flow and the available external static pressure of the pump. See "14 Technical data"on page74 for the external static pressure curves of the indoor unit.
Water flow. You can find the minimum required water flow for
indoor unit operation in the following table. In all cases, this flow needs to be guaranteed. When the flow is lower, the indoor unit will stop operation and display error 7H.
Minimum required flow rate during defrost/backup heater operation
04+08 models 12l/min
16 model 15l/min
Field supply components – Water. Only use materials that are
compatible with water used in the system and with the materials used in the indoor unit.
Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the water pressure and water temperature.
Water pressure. The maximum water pressure is 4 bar. Provide
adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Water temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following temperatures:

6.4 Preparing water piping

6.4.1 Water circuit requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
NOTICE
In case of plastic pipes, make sure they are fully oxygen diffusion tight according to DIN 4726. The diffusion of oxygen into the piping can lead to excessive corrosion.
Installer reference guide
18
INFORMATION
The following illustration is an example and might NOT match your system layout.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 19
89°C
75°C
M
M
a b c d ge h ii
i
j
j
fki
HPC1
FHL1 FHL2 FHL3
HPC2 HPC3
a Outdoor unit
c d
a b
b Indoor unit
c Heat exchanger
d Backup heater
e Motorised 3‑way valve (switch between space heating and
domestic hot water)
f Motorised 3‑way valve (mixing the main zone) g Main pump h Additional pump
i Shut-off valve j Collector (field supply)
k Domestic hot water tank
HPC1...3 Heat pump convector (field supply)
FHL1...3 Floor heating loop (field supply)
Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
Drainage – Pressure relief valve. Provide a proper drain for the
pressure relief valve to avoid water dripping out of the unit. See
"7.8.5 To connect the pressure relief valve to the drain" on page32.
Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. An automatic air purge is provided in the indoor unit. Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible.
Zn-coated parts. Never use Zn-coated parts in the water circuit.
Because the unit's internal water circuit uses copper piping, excessive corrosion may occur.
Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Valve – Change‑over time. When using a 2-way valve or a 3-way
valve in the water circuit, the maximum change-over time of the valve must be 60seconds.
Filter. It is strongly recommended to install an additional filter on
both heating water circuits. Especially to remove metallic particles from foul heating piping, it is recommended to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.
Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water.
Domestic hot water tank – After installation. Immediately after
installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
6 Preparation
Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the equipment MUST be flushed with fresh water before usage.
Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "8.3.2Domestic hot
water control: advanced"on page53.
Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing valves.
Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic installation measures.
Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.
a Recirculation connection b Hot water connection c Shower d Recirculation pump

6.4.2 Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)

6.4.3 To check the water volume and flow rate

The indoor unit has an expansion vessel of 10litre with a factory set pre-pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Check that the total water volume in the installation is minimum 10 litre for EHVZ04+08 and 20litre for EHVZ16, the internal water volume of the indoor unit NOT included. Do NOT split up the minimum water volume over the 2 temperature zones.
It is sufficient to foresee the minimum water volume on the main zone. In case of underfloor heating, this is easily done by 1 floor heating loop that never will be closed by a (remotely) controlled valve.
It is NOT required to foresee the minimum water volume on the additional zone.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required.
NOTICE
When circulation in each space heating/cooling loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
19
Page 20
6 Preparation
T1
M1
T1
M1
T2M2T3
M3
M
FHL1
FHL2
FHL3
M2 M3
T2 T3
HPC1 HPC2 HPC3
a b c
g hf
d e
i
i
hh
h
j
j
0.3
0.5
1
1.5
2
2.5
100500
20
150 200 250 300 350 400 450
a
b
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Motorised 3‑way valve (mixing the main zone)
f Additional pump g Main pump h Shut-off valve
i Collector (field supply) j By-pass valve (field supply)
FHL1...3 Floor heating loop (field supply)
HPC1...3 Heat pump convector (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3 and
HPC1...3 (field supply)
Maximum water volume
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
Installation
height
difference
(a)
≤280l >280l
>7m Do the following:
▪ Increase the pre-
pressure according to the required installation height difference. The pre­pressure should
Water volume
The expansion vessel of the indoor unit is too small for the installation. In this case, it is recommended to install an extra vessel outside the unit.
increase by 0.1 bar for each metre above 7 m.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0m.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup heater operation) in the installation is guaranteed in all conditions on each zone separately.
NOTICE
When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating/operation).
a Pre-pressure (bar) b Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre­pressure
Installation
height
difference
(a)
≤280l >280l
≤7m No pre-pressure
adjustment is required.
Water volume
Do the following:
▪ Decrease the pre-
pressure according to the required installation height difference. The pre-pressure should decrease by 0.1 bar for each metre below 7 m.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
Minimum required flow rate during defrost/backup heater operation
04+08 models 12l/min
16 model 15l/min
See the recommended procedure as described in "9.4 Checklist
during commissioning"on page63.

6.4.4 Changing the pre-pressure of the expansion vessel

NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
When changing the default pre-pressure of the expansion vessel (1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the Schrader valve of the expansion vessel.
Installer reference guide
20
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 21
180 l
a
a Schrader valve

6.4.5 To check the water volume: Examples

Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350l.
Actions:
▪ Because the total water volume (350l) is more than the default
water volume (280l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 410 l.
(See the graph in the chapter above).
▪ Because 350 l is lower than 410 l, the expansion vessel is
appropriate for the installation.
6 Preparation
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable legislation.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.

6.5.2 About preferential kWh rate power supply

6.5 Preparing electrical wiring

6.5.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
INFORMATION
Also read "7.9.5 Specifications of standard wiring
components"on page34.
NOTICE
For applications with preferential kWh rate power supply:
The interruption of the outdoor unit power supply may not be more than 2 hours to guarantee optimised startup conditions for the compressor.
Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available, if any.
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the outdoor unit compressor will not operate.
Whether the power supply is interrupted or not, the wiring to the unit is different.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
21
Page 22
6 Preparation
1
5
8
0
1
5
0
0
0
2
a
3
1
4
5
8
0 1
5
0
0
0
2
b
3
5 3
a
b
14
5
8
0
1
5
0
0
0
5
8
0
1
5
0
0
0
2
M
a
16
21
22 19
15
20
24
23
12
6
13
17 18

6.5.3 Overview of electrical connections except external actuators

Normal power
supply
a Normal power supply b Preferential kWh rate power supply 1 Power supply for outdoor unit 2 Power supply and interconnection cable to indoor unit 3 Power supply for backup heater 4 Preferential kWh rate power supply (voltage free contact) 5 Normal kWh rate power supply (to power the indoor unit
PCB in the event of power supply interruption of the preferential kWh rate power supply)
Preferential kWh rate power supply
Power supply is NOT interrupted
Power supply is
interrupted
During preferential During preferential kWh rate power supply activation, power supply is NOT interrupted. The outdoor unit is turned off by the control.
Remark: The electricity company must always allow the power consumption of the indoor unit.
kWh rate power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
indoor unit must be
powered by a
separate normal
power supply.

6.5.4 Overview of electrical connections for external and internal actuators

The following illustration shows the required field wiring.
INFORMATION
The following illustration is an example and might NOT match your system layout.
Item Description Wires Maximum
running
current
3 Power supply for
See table below. —
backup heater
4 Preferential kWh rate
2
(d)
power supply (voltage free contact)
5 Normal kWh rate power
2 6.3A
supply
User interface
6 User interface 2
(e)
Optional equipment
11 Power supply for
2
(b)
bottom plate heater
12 Room thermostat 2 or 3 100mA
13 Outdoor ambient
2
(b)
temperature sensor
14 Indoor ambient
2
(b)
temperature sensor
15 Heat pump convector 2 100mA
Field supplied components
16 Shut-off valve 2 100mA
17 Electricity meter 2 (per meter)
18 Domestic hot water
2
(b)
(b)
pump
19 Alarm output 2
20 Changeover to external
2
(b)
(b)
heat source control
21 Space heating
2
(b)
operation control
22 Power consumption
digital inputs
23 Safety thermostat for
2 (per input signal)
2
(b)
(b)
the main zone
24 Safety thermostat for
2
(d)
the additional zone
(a) Refer to name plate on outdoor unit. (b) Minimum cable section 0.75mm². (c) Cable section 2.5mm². (d) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum applicable load of 15VDC, 10mA.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual user interface connection.
NOTICE
More technical specifications of the different connections are indicated on the inside of the indoor unit.
(b)
(b)
(b)
a Indoor unit
Item Description Wires Maximum
Outdoor unit and indoor unit power supply
1 Power supply for
2 Power supply and
outdoor unit
interconnection cable to indoor unit
Installer reference guide
22
2+GND or 3+GND
3
running
current
(a)
(c)
NOTICE
A safety thermostat (normal closed contact) MUST be installed for the main zone. See "7.9.17 To connect the
safety thermostat (normal closed contact)"on page40.
Backup heater
type
Power supply Required number of
conductors
*3V 1× 230V 2+GND
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 23

7 Installation

3
45°~90°
(4)
2
1
2
3
4
5
1
2
7 Installation

7.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
1 Mounting the outdoor unit.
2 Mounting the indoor unit.
3 Connecting the refrigerant piping.
4 Checking the refrigerant piping.
5 Charging refrigerant.
6 Connecting the water piping.
7 Connecting the electrical wiring.
8 Finishing the outdoor installation.
9 Finishing the indoor installation.
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.

7.2 Opening the units

7.2.3 To open the indoor unit

1 Loosen and remove the screws at the bottom of the unit.
2 Push on the button at the bottom of the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower part. Watch your fingers, there are sharp edges on the lower part of the front plate.
3 Slide the front panel of the unit downwards and remove it.
CAUTION
The front panel is heavy. Be careful NOT to jam your fingers when opening or closing the unit.
4 Loosen and remove the 4 screws that fix the top panel.
5 Remove the top panel from the unit.

7.2.1 About opening the units

At certain times, you have to open the unit. Example:
▪ When connecting the refrigerant piping
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.

7.2.2 To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING

7.2.4 To open the switch box cover of the indoor unit

ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04

7.3 Mounting the outdoor unit

7.3.1 About mounting the outdoor unit

When
You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping.
Installer reference guide
23
Page 24
7 Installation
(mm)
>150
620
350
(345-355)
4× M12
a
20
a
4× M12
≥150 mm
58
16
16
71
11710270
45 376 191
a b
c
d (4×)
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the outdoor unit.
3 Providing drainage.
4 Preventing the unit from falling over.
5 Protecting the unit against snow and wind by installing a snow
cover and baffle plates. See "Preparing installation site" in
"6Preparation"on page16.

7.3.2 Precautions when mounting the outdoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.3.3 To provide the installation structure

Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing.
Prepare 4 sets of anchor bolts, nuts and washers (field supply) as follows:

7.3.4 To install the outdoor unit

7.3.5 To provide drainage

▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is a proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water surrounding the unit.
▪ Avoid drain water flowing over the footpath, so that it does not
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping (see the following illustration).
Installer reference guide
24
a Make sure not to cover the drain holes of the bottom plate
of the unit.
INFORMATION
The recommended height of the upper protruding part of the bolts is 20mm.
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is stripped off, the nuts rust easily.
INFORMATION
You can use the optional drain plug kit (EKDK04) (only for ERHQ).
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface, raise the unit to provide a free space of more than 150mm under the outdoor unit.
Drain holes
Model Bottom view (mm)
ERHQ_V3
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 25
7 Installation
45
43 378
10 60
58 16
71 16
191
117102
a b
c
d (4×)
35
36
61 99
1671
60 159154182
a b
c
d (4×)
135 kg
≤1°
Model Bottom view (mm)
ERHQ_W1
ERLQ
a Discharge side
b Drain holes
c Knockout hole (piping intake - downwards route)
d Anchor points

7.3.6 To prevent the outdoor unit from falling over

In case the unit is installed in places where strong wind can tilt the unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.

7.4.3 To install the indoor unit

1 Lift the indoor unit from the pallet and place it on the floor.
2 Slide the indoor unit into position.
3 Adjust the height of the leveling feet to compensate for floor
irregularities. The maximum allowed deviation is 1°.
NOTICE
Do NOT tilt the unit backwards:

7.4 Mounting the indoor unit

7.4.1 About mounting the indoor unit

When
You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1 Installing the indoor unit.

7.4.2 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
▪ Preparation

7.5 Connecting the refrigerant piping

7.5.1 About connecting the refrigerant piping

Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the outdoor unit
▪ Connecting the refrigerant piping to the indoor unit
▪ Installing oil traps
▪ Insulating the refrigerant piping
Installer reference guide
25
Page 26
7 Installation
a b
c
d
R=0.4~0.8
45°
±2
90°
±2
A
a b
A
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Brazing
▪ Using the stop valves

7.5.2 Precautions when connecting the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R410A unit to guarantee
its lifetime. The drying material may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
▪ Avoid anything but the designated refrigerant to get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R410A when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
▪ Install the piping so that the flare is NOT subjected to
mechanical stress
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use caution when passing copper tubes through walls
(see figure below).
Unit Installation period Protection method
Outdoor unit >1month Pinch the pipe
<1month Pinch or tape the pipe
Indoor unit Regardless of the
period
INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging.

7.5.3 Guidelines when connecting the refrigerant piping

Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before tightening firmly.
▪ Always use 2 wrenches together when loosening a flare nut.
▪ Always use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking and leaks.
a Torque wrench b Spanner c Piping union d Flare nut
Piping size
(mm)
Tightening
torque (N•m)
Flare
dimensions (A)
Flare shape
(mm)
(mm)
Ø9.5 33~39 12.8~13.2
Ø15.9 63~75 19.3~19.7

7.5.4 Pipe bending guidelines

Use a pipe bender for bending. All pipe bends should be as gentle as possible (bending radius should be 30~40mm or larger).

7.5.5 To flare the pipe end

CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the
chips do not enter the pipe.
a Cut exactly at right angles. b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut
on the pipe.
4 Flare the pipe. Set exactly at the position as shown in the
following illustration.
Installer reference guide
26
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 27
7 Installation
a b
c
a b c d e
f
f
c d
a
b
a
b
Flare tool for
R410A (clutch
type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
5 Check that the flaring is properly made.
a Flare’s inner surface must be flawless.
b The pipe end must be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.

7.5.6 To braze the pipe end

The indoor unit and outdoor unit have flare connections. Connect both ends without brazing. If brazing should be needed, take the following into account:
▪ When brazing, blow through with nitrogen to prevent creation of
large quantities of oxidised film on the inside of the piping. This film adversely affects valves and compressors in the refrigerating system and prevents proper operation.
▪ Set the nitrogen pressure to 20kPa (0.2bar) (just enough so it
can be felt on the skin) with a pressure-reducing valve.
▪ Do NOT apply excessive force to the valve stem. Doing so may
break the valve body.
▪ Always make sure to secure the stop valve with a spanner, then
loosen or tighten the flare nut with a torque wrench. Do NOT place the spanner on the stem cap, as this could cause a refrigerant leak.
a Spanner b Torque wrench
▪ When it is expected that the operating pressure will be low (e.g.
when cooling will be performed while the outside air temperature is low), sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
To open/close the stop valve
1 Remove the valve cover.
2 Insert a hexagon wrench (liquid side: 4mm, gas side: 6mm)
into the valve stem and turn the valve stem:
a Refrigerant piping
b Part to be brazed
c Taping
d Manual valve
e Pressure-reducing valve
f Nitrogen
▪ Do NOT use anti-oxidants when brazing pipe joints.
Residue can clog pipes and break equipment.
▪ Do NOT use flux when brazing copper-to-copper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP), which does not require flux. Flux has an extremely harmful influence on refrigerant piping systems. For instance, if chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will deteriorate the refrigerant oil.

7.5.7 Using the stop valve and service port

To handle the stop valve
Take the following guidelines into account:
▪ The stop valves are factory closed.
▪ The following illustration shows each part required in handling the
valve.
Counterclockwise to open. Clockwise to close.
3 When the valve stem cannot be turned any further, stop turning.
The valve is now opened/closed.
To handle the stem cap
▪ The stem cap is sealed where indicated with the arrow. Do NOT
damage it.
▪ After handling the stop valve, tighten the stem cap, and check for
refrigerant leaks.
Item Tightening torque (N∙m)
Stem cap, liquid side 13.5~16.5
Stem cap, gas side 22.5~27.5
a Service port and service port cap
b Valve stem
c Field piping connection
d Stem cap
▪ Keep both stop valves open during operation.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
To handle the service cap
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, tighten the service port cap, and
check for refrigerant leaks.
Item Tightening torque (N∙m)
Service port cap 11.5~13.9
Installer reference guide
27
Page 28
7 Installation
c
a
b d
a
b
c
d
cc
ba
4× Ø6 mm
a
b
d
c
e
b a
g
g
h h
f
a
b
c
a

7.5.8 To connect the refrigerant piping to the outdoor unit

1 Do the following:
▪ Remove the service cover (a) with screw (b). ▪ Remove the piping intake plate (c) with screw (d).
2 Choose a piping route (a, b, c or d).
3 If you have chosen the downwards piping route:
▪ Drill (a, 4×) and remove the knockout hole (b). ▪ Cut out the slits (c) with a metal saw.
6 If the outdoor unit is installed above the indoor unit, cover the
stop valves (h, see above) with sealing material to prevent condensed water on the stop valves from moving to the indoor unit.
NOTICE
Any exposed piping might cause condensation.
7 Reattach the service cover and the piping intake plate.
8 Seal all gaps (example: a) to prevent snow and small animals
from entering the system.
4 Do the following:
▪ Connect the liquid pipe (a) to the liquid stop valve. ▪ Connect the gas pipe (b) to the gas stop valve.
5 Do the following:
▪ Insulate the liquid piping (a) and the gas piping (b). ▪ Make sure the piping and piping insulation do NOT touch the
compressor (c), the compressor terminal cover (d), and the compressor bolts (e). If the liquid pipe insulation might touch the compressor terminal cover, adjust the height of the insulation (f=no insulation around the compressor terminal cover (d)).
▪ Seal the insulation ends (sealant etc.) (g).
Installer reference guide
28
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend you
remove the burrs and paint the edges and areas around the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent damage.
a Knockout hole b Burr c Sealant etc.
NOTICE
Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying. Running the system with the stop valves closed may break the compressor.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 29
7 Installation
b a
a
b
10 m
R410A
a
b d e
f
c

7.5.9 To connect the refrigerant piping to the indoor unit

1 Connect the liquid stop valve from the outdoor unit to the
refrigerant liquid connection of the indoor unit.
a Refrigerant liquid connection
b Refrigerant gas connection
2 Connect the gas stop valve from the outdoor unit to the
refrigerant gas connection of the indoor unit.
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape.

7.5.10 To determine if oil traps are required

If oil flows back into the outdoor unit's compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas piping can prevent this.
If Then
The indoor unit is installed higher than the outdoor unit
Install an oil trap every 10m (height difference).
Typical workflow
Checking the refrigerant piping typically consists of the following stages:
1 Checking for leaks in the refrigerant piping.
2 Performing vacuum drying to remove all moisture, air or
nitrogen from the refrigerant piping.
If there is a possibility of moisture being present in the refrigerant piping (for example, water may have entered the piping), first carry out the vacuum drying procedure below until all moisture has been removed.

7.6.2 Precautions when checking the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
NOTICE
Use a 2-stage vacuum pump with a non-return valve that can evacuate to a gauge pressure of −⁠100.7 kPa (−⁠1.007 bar)(5 Torr absolute). Make sure the pump oil does not flow oppositely into the system while the pump is not working.
NOTICE
Use this vacuum pump for R410A exclusively. Using the same pump for other refrigerants may damage the pump and the unit.

7.6.3 Checking refrigerant piping: Setup

The outdoor unit is installed higher than the indoor unit

7.6 Checking the refrigerant piping

7.6.1 About checking the refrigerant piping

The outdoor unit's internal refrigerant piping has been factory tested for leaks. You only have to check the outdoor unit's external refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor unit and the indoor unit.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
a Rising gas piping with oil trap
b Liquid piping
Oil traps are NOT required.
a Pressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump
f Stop valve

7.6.4 To check for leaks

NOTICE
Do NOT exceed the unit's maximum working pressure (see "PS High" on the unit name plate).
NOTICE
Make sure to use a recommended bubble test solution from your wholesaler. Do not use soap water, which may cause cracking of flare nuts (soap water may contain salt, which absorbs moisture that will freeze when the piping gets cold), and/or lead to corrosion of flared joints (soap water may contain ammonia which causes a corrosive effect between the brass flare nut and the copper flare).
Installer reference guide
29
Page 30
7 Installation
1 Charge the system with nitrogen gas up to a gauge pressure of
at least 200 kPa (2 bar). It is recommended to pressurize to 3000kPa (30bar) in order to detect small leaks.
2 Check for leaks by applying the bubble test solution to all
connections.
3 Discharge all nitrogen gas.

7.6.5 To perform vacuum drying

1 Vacuum the system until the pressure on the manifold indicates
−0.1MPa (−1bar).
2 Leave as is for 4-5minutes and check the pressure:
If the pressure… Then…
Does not change There is no moisture in the
system. This procedure is finished.
Increases There is moisture in the
system. Go to the next step.
3 Evacuate for at least 2 hours to a pressure on the manifold of
−0.1MPa (−1bar).
4 After turning OFF the pump, check the pressure for at least
1hour.
5 If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1hour, do the following:
▪ Check for leaks again. ▪ Perform vacuum drying again.
NOTICE
Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying. Running the system with the stop valves closed may break the compressor.
INFORMATION
After opening the stop valve, it is possible that the pressure in the refrigerant piping does NOT increase. This might be caused by e.g. the closed state of the expansion valve in the outdoor unit circuit, but does NOT present any problem for correct operation of the unit.
Typical workflow – Charging additional refrigerant typically consists of the following stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's external refrigerant piping is checked (leak
test, vacuum drying).
3 Vacuum drying on the outdoor unit's internal refrigerant piping is
performed.
NOTICE
Before completely recharging, perform vacuum drying on the outdoor unit's internal refrigerant piping as well. To do so, use the internal service port of the outdoor unit (between the heat exchanger and the 4‑way valve). Do NOT use the service ports of the stop valves, because vacuum drying cannot be performed properly from these ports.
Typical workflow – Completely recharging refrigerant typically consists of the following stages:
1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.

7.7.2 Precautions when charging refrigerant

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.7 Charging refrigerant

7.7.1 About charging refrigerant

The outdoor unit is factory charged with refrigerant, but in some cases the following might be necessary:
What When
Charging additional refrigerant When the total liquid piping
length is more than specified (see later).
Completely recharging refrigerant Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's
external refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.
Installer reference guide
30

7.7.3 To determine the additional refrigerant amount

If the total liquid
piping length is…
≤10m Do NOT add additional refrigerant.
>10m R=(total length (m) of liquid
piping⁠–⁠10m)×0.054
R=Additional charge (kg)(rounded in units of 0.1kg)
INFORMATION
Piping length is the one way length of liquid piping.
Then…

7.7.4 To determine the complete recharge amount

INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory refrigerant charge (see unit name plate) + the determined additional amount.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 31
7 Installation
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
GWP × kg
1000
= =
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d e
fac e d b

7.7.5 To charge additional refrigerant

WARNING
▪ Only use R410A as refrigerant. Other substances may
cause explosions and accidents.
▪ R410A contains fluorinated greenhouse gases. Its
global warming potential (GWP) value is 2087.5. Do NOT vent these gases into the atmosphere.
▪ When charging refrigerant, always use protective
gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the
gas stop valve and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
If pump down is needed in case of dismantling or relocating the system, see "13.3To pump down"on page73 for more details.

7.7.6 To fix the fluorinated greenhouse gases label

1 Fill in the label as follows:
Typical workflow
Connecting the water piping typically consists of the following stages:
1 Connecting the water piping to the indoor unit.
2 Connecting the recirculation piping.
3 Connecting the pressure relief valve to the drain.
4 Filling the water circuit.
5 Filling the domestic hot water tank.
6 Insulating the water piping.

7.8.2 Precautions when connecting the water piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.8.3 To connect the water piping

NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
To facilitate service and maintenance, 4 shut-off valves are provided. Mount these valves on the space heating water inlets and space heating water outlets. Mind their position. The orientation of the integrated drain and fill valves is important for servicing.
a If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO2-equivalent
f GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the total refrigerant charge in the system (expressed as tonnes CO2-equivalent) is used to determine the maintenance intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.

7.8 Connecting the water piping

7.8.1 About connecting the water piping

Before connecting the water piping
Make sure the outdoor and indoor unit are mounted.
NOTICE
This unit is designed for operation on 2 temperature zones:
▪ underfloor heating in the main zone (water
temperature 35°C), this is the zone with the lowest water temperature,
▪ radiators in the additional zone (water temperature
45°C), this is the zone with the highest water
temperature.
1 Install the shut-off valves on the space heating water pipes.
a Space heating additional zone water out b Space heating additional zone water in c Domestic hot water out d Domestic cold water in (cold water supply) e Space heating main zone water out
f Space heating main zone water in
NOTICE
It is recommended to install shut-off valves to domestic cold water in and domestic hot water out connections. These shut-off valves are field supplied.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
31
Page 32
7 Installation
b
a
c
a
ab
NOTICE
To avoid damage to the surroundings in case of water leakage, it is recommended to close the cold water inlet shut‑off valves during periods of absence.
2 Screw the indoor unit nuts on the shut-off valves.
3 Connect the domestic hot water in and out pipes to the indoor
unit.
NOTICE
Install air purge valves at all local high points.
NOTICE
▪ A drain device and pressure relief device should be
installed on the cold water inlet connection of the domestic hot water cylinder.
▪ To avoid back siphonage, it is recommended to install a
non-return valve on the water inlet of the domestic hot water tank in accordance with the applicable legislation.
▪ It is recommended to install a pressure reducing valve
on the cold water inlet in accordance with the applicable legislation.
▪ An expansion vessel should be installed on the cold
water inlet in accordance with the applicable legislation.
▪ It is recommended to install the pressure relief valve on
a higher position than the top of the domestic hot water tank. Heating of the domestic hot water tank causes water to expand and without pressure relief valve the water pressure inside the tank can rise above the tank design pressure. Also the field installation (piping, tapping points, etc.) connected to the tank is subjected to this high pressure. To prevent this, a pressure relieve valve needs to be installed. The overpressure prevention depends on the correct operation of the field installed pressure relief valve. If this is NOT working correctly, overpressure will deform the tank and water leakage may occur. To confirm good operation, regular maintenance is required.
6 Connect the recirculation piping to the recirculation connection
(b) and route the piping through the hole at the backside of the unit (a).
a Piping intake hole b Recirculation connection c Cut-out location
7 Reattach the top insulation, expansion vessel, and casing.

7.8.5 To connect the pressure relief valve to the drain

The blow out of the pressure relief valve is coming out of the backside of the unit.

7.8.4 To connect the recirculation piping

Prerequisite: Only required if you need recirculation in your system.
1 Loosen and remove the 4 screws that fix the top panel.
2 Remove the top panel from the unit.
a Pressure relief blow-out
The blow out should be connected to an appropriate drain according to the applicable legislation. It is recommended to use a tundish.

7.8.6 To fill the water circuit

1 Connect the water supply hose to the fill valve.
3 Disconnect and remove the expansion vessel of the top
insulation.
4 Remove the top insulation.
5 Cut out part (c) on the left or right side from the top insulation.
Tank capacity Cut out position
180l Left OR right
Installer reference guide
32
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 33
7 Installation
INFORMATION
Please fill with water through connection a OR b. Both circuits (main and additional) will be filled.
2 Open the fill valve.
3 Make sure that the automatic air purge valve is open (at least 2
turns).
4 Fill the circuit with water until the manometer indicates a
pressure of ±2.0bar.
5 Purge as much air as possible from the water circuit.
6 Close the fill valve.
7 Disconnect the water supply hose from the fill valve.
NOTICE
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure shall remain above 1bar to avoid air entering the circuit.

7.8.7 To fill the domestic hot water tank

1 Open every hot water tap in turn to purge air from the system
pipe work.
2 Open the cold water supply valve.
3 Close all water taps after all air is purged.
4 Check for water leaks.
5 Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.

7.8.8 To insulate the water piping

The piping in the complete water circuit MUST be insulated to prevent condensation during defrost operation and reduction of the heating capacity.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.

7.9 Connecting the electrical wiring

7.9.1 About connecting the electrical wiring

Before connecting the electrical wiring
Make sure:
▪ The refrigerant piping is connected and checked
▪ The water piping is connected
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the
electrical specifications of the heat pump.
2 Connecting the electrical wiring to the outdoor unit.
3 Repositioning the air thermistor on the outdoor unit.
4 Connecting the electrical wiring to the indoor unit.
5 Connecting the main power supply.
6 Connecting the backup heater power supply.
7 Connecting the user interface.
8 Connecting the shut–off valves.
9 Connecting the electrical meters.
10 Connecting the domestic hot water pump.
11 Connecting the alarm output.
12 Connecting the changeover to an external heat source.
13 Connecting the power consumption digital inputs.
14 Connecting the safety thermostat.

7.9.2 About electrical compliance

ERHQ_V3
Equipment complying with EN/IEC 61000‑3‑12 (European/ International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase.).
ERLQ_V3
Equipment complying with:
EN/IEC 61000‑3‑11 provided that the system impedance Z
less than or equal to Z
at the interface point between the user's
max
supply and the public system.
▪ EN/IEC 61000‑3‑11 = European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤75A.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a system impedance Z
less than or equal to Z
sys
max
EN/IEC 61000‑3‑12 provided that the short-circuit power Ssc is
greater than or equal to the minimum Ssc value at the interface point between the user's supply and the public system.
▪ EN/IEC 61000‑3‑12 = European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to the minimum Ssc value.
is
sys
.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Model Z
max
Minimum S
sc
value
ERLQ011CAV3
0.22Ω 525kVA
ERLQ014CAV3
ERLQ016CAV3
ERLQ_W1
Equipment complying with EN/IEC 61000‑3‑12 (European/ International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase.).
Installer reference guide
33
Page 34
7 Installation
b a
cb
c
aa
A
AA´
c b ba c
a
B
B
a b
c
b
a
d
V3 1~ 50 Hz 230 V
W1
3N~ 50 Hz
400 V
L1 L3L2
L1 L3L2
Only for indoor units
See "7.9.10 To connect the backup heater power supply" on
page37.

7.9.3 Precautions when connecting the electrical wiring

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.

7.9.4 Guidelines when connecting the electrical wiring

Keep the following in mind:
▪ If stranded conductor wires are being used, install a round crimp-
style terminal on the tip. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.
a Stranded conductor wire
b Round crimp-style terminal
▪ Use the following methods for installing wires:

7.9.5 Specifications of standard wiring components

Component V3 W1
ERHQ ERLQ ERHQ ERLQ
Power supply cable
(a)
MCA
31.9A 34.2A 13.5A 16.3A
Voltage 230V 400V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with applicable
legislation
Interconnection cable Minimum cable section of 2.5mm²
and applicable for 230V
Recommended field fuse 32A 40A 20A
Earth leakage circuit breaker Must comply with applicable
legislation
(a) MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with indoor units for exact values).

7.9.6 To connect the electrical wiring on the outdoor unit

NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "7.2.2 To open the outdoor
unit"on page23.
2 Strip insulation (20mm) from the wires.
Wire type Installation method
Single core wire
Stranded conductor wire with round crimp-style terminal
Tightening torques
M4 (X1M) 1.2~1.8
M5 (X1M) 2.0~3.0
M5 (earth) 3.0~4.0
34
Installer reference guide
a Curled single core wire
b Screw
c Flat washer
a Terminal
b Screw
c Flat washer
Item Tightening torque (N•m)
a Strip wire end to this point b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cable and power supply as follows:
a Interconnection cable b Power supply cable c Earth leakage circuit breaker d Fuse
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 35
7 Installation
d
b
a
V3 W1
e
h f
d
g
e
h f
g
c
c
a
b
a
b
a
b
2
3
1
a b c d e
A B
1
3
2
4
5
a Switch box
b Stop valve attachment plate
c Earth
d Cable tie
e Interconnection cable
f Power supply cable
Only if bottom plate heater is installed (option for ERHQ):
g Bottom plate heater cable h Power supply cable of the bottom plate heater (from the
indoor unit)
INFORMATION
ERLQ units control the bottom plate heater internally (field wiring NOT required).
4 Fix the cables (power supply, interconnection cable and power
supply of the bottom plate heater (if applicable)) with a cable tie to the stop valve attachment plate.
5 Route the wiring through the frame and connect it to it.
Connecting to the frame
When cables are routed from the unit, a protection sleeve for the conduits (PG insertions) can be inserted at the knockout hole.
When you do not use a wire conduit, protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires.
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
6 Reattach the service cover. See "7.10.2To close the outdoor
unit"on page41.
7 Connect an earth leakage circuit breaker and fuse to the power
supply line.

7.9.7 To reposition the air thermistor on the outdoor unit

This task is only required for ERLQ.
Required accessories:
Thermistor fixture.
Use the one from the accessory bag.
Thermistor fixing plate.
Reuse the one attached to the unit. If necessary, you can use the spare one from the accessory bag.
Routing through the frame
Choose one of the 3 possibilities:
a Power supply, earth wiring, and bottom plate heater wire (if applicable)
b Interconnection cable
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
35
Page 36
7 Installation
7
6
7
8
9
10
11
a b+c
a
b+c
3 Routing of the wiring inside the unit should be as follows:

7.9.8 To connect the electrical wiring on the indoor unit

1 To open the indoor unit, see "7.2.3To open the indoor unit"on
page23 and "7.2.4To open the switch box cover of the indoor unit"on page23.
2 Wiring should enter the unit from the top:
Routing Possible cables (depending on unit type and installed options)
a
Low voltage
b
High voltage power supply
▪ Preferential power supply contact
▪ User interface
▪ Power consumption digital inputs (field supply)
▪ Outdoor ambient temperature sensor (option)
▪ Indoor ambient temperature sensor (option)
▪ Electrical meters (field supply)
▪ Safety thermostat for the main zone (field supply)
▪ Safety thermostat for the additional zone (field supply)
▪ Interconnection cable
▪ Normal kWh rate power supply
▪ Preferential kWh rate power supply
▪ Power supply for backup heater
▪ Power supply for bottom plate heater (option)
4 Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in contact with the piping and sharp edges.
INFORMATION
To access the domestic hot water temperature sensor, the switch box can be tilted. The switch box should NOT be removed from the unit.
Installer reference guide
36
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 37
Routing Possible cables (depending on unit type and installed options)
X2M
X5M
A5P
X1M
K3M
K2M
1 2 3
1 2 3
X6YB
X6YA
X6Y
3031
X1A
X6YA
X19A
a
X2M
X5M
A5P
X1M
K3M
K2M
1 2 3
1 2 3
X6YB
X6Y
X1A
L N
L N
30 31
S1S
3 4
X19A
abc
c
High voltage control signal
▪ Heat pump convector (option)
▪ Room thermostat (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source control
▪ Space heating operation control
7 Installation
CAUTION
Do NOT push or place redundant cable length in the unit.

7.9.9 To connect the main power supply

1 Connect the main power supply.
In case of normal kWh rate power supply
Legend: see illustration below.
INFORMATION
In case of preferential kWh rate power supply, connect X6Y to X6YB. The necessity of separate normal kWh rate power supply to indoor unit (b) X2M30/31 depends on the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals (X5M/3+4) as the safety thermostat for the additional zone. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone.

7.9.10 To connect the backup heater power supply

CAUTION
To guarantee the unit is completely earthed, always connect the backup heater power supply and the earth cable.
Make sure that the power supply is in accordance with the backup heater capacity, as listed in the table below.
In case of preferential kWh rate power supply
Connect X6Y to X6YB.
a Interconnection cable (=main power supply)
b Normal kWh rate power supply
c Preferential power supply contact
2 Fix the cable with cable ties to the cable tie mountings.
Backup
heater type
Backup
heater
capacity
Power
supply
Maximum
running
current
Z
(Ω)
max
*3V 3kW 1~230V 13A
1 Connect the backup heater power supply. A double‑pole fuse is
used for F1B.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
37
Page 38
7 Installation
X2M
F1B
X1M
L NL N
X5M
A5P
A2P A2P
a b
1 2
Backup heater type Connections to backup heater power
supply
3kW 1~ 230V (*3V)
2 Fix the cable with cable ties to the cable tie mountings.

7.9.11 To connect the user interface

▪ If you use 1 user interface, you can install it at the indoor unit (for
control close to the indoor unit), or in the room (when used as room thermostat).
▪ If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface in the room (used as room thermostat).
# At the indoor unit In the room
1 Connect the user interface cable to the indoor unit.
Fix the cable with cable ties to the cable tie mountings.
a Main user interface
(a)
b Optional user interface
2 Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the wallplate.
The PCB is mounted in the faceplate of the user interface. Be careful NOT to damage it.
INFORMATION
The user interface can only be used as room thermostat of the main zone.
The procedure differs slightly depending on where you install the user interface.
3 Use the 2 screws in the accessory
bag to fix the wallplate of the user interface to the sheet metal of the
Fix the wallplate of the user interface to the wall.
unit.
Be careful NOT to distort the shape of the backside of the user interface by overtightening the mounting screws.
4 Connect as shown in 4A. Connect as shown
in 4A, 4B, 4C or 4D.
5 Reinstall the faceplate onto the wallplate.
Be careful NOT to pinch the wiring when attaching the frontplate to the unit.
(a) The main user interface is required for operation, but has to
be ordered separately (mandatory option).
Installer reference guide
38
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 39
7 Installation
b
a
PCB
a
PCB
b
a
b
PCB
b
a
PCB
b
b
X2M
X1M
K3M
K2M
X2M
X1M
K3M
K2M
5 6 7
M2S
5 6 7
M2S
NO NC
X5M
A5P
78910
S2S S3S
X2M
X1M
K3M
K2M
3534
1~
M
M2P
X2M
X5M
A5P
X1M
A4P
K3M
K2M
29
X1M
YC Y1 Y2 Y3 Y4
a
4A From the rear
4C From the top
a Notch this part for the wiring to pass through with nippers
b Secure the wiring to the front part of the casing using the
4B From the left
4D From the top centre
2 Fix the cable with cable ties to the cable tie mountings.

7.9.14 To connect the domestic hot water pump

1 Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.
etc.
wiring retainer and clamp.

7.9.12 To connect the shut-off valve

1 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normal closed) valve and a NO (normal open) valve.
2 Fix the cable with cable ties to the cable tie mountings.

7.9.15 To connect the alarm output

1 Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.
2 Fix the cable with cable ties to the cable tie mountings.

7.9.13 To connect the electrical meters

INFORMATION
In case of an electrical meter with transistor output, check the polarity. The positive polarity MUST be connected to X5M/7 and X5M/9; the negative polarity to X5M/8 and X5M/10.
1 Connect the electrical meters cable to the appropriate terminals
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
as shown in the illustration below.
a Installation of EKRP1HB is required.
2 Fix the cable with cable ties to the cable tie mountings.
Installer reference guide
39
Page 40
7 Installation
X5M
A5P
A8P
1 2 3 4 5
X801M
S6S
S7S
S8S
S9S
a
X5M
A5P
1211
3 4
X5M
f
b
a
e
d
c

7.9.16 To connect the power consumption digital inputs

1 Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
a Installation of EKRP1AHTA is required.
2 Fix the cable with cable ties to the cable tie mountings.

7.9.17 To connect the safety thermostat (normal closed contact)

Main zone
1 Connect the safety thermostat (normal closed) cable to the
appropriate terminals as shown in the illustration below.
4 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat for the additional zone according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, it is recommended that …
▪ … the safety thermostat is automatically resettable.
▪ … the safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ … there is a minimum distance of 2 m between the
safety thermostat and the 3‑way valve.
INFORMATION
After it is installed, do NOT forget to configure the safety thermostat for the additional zone. Without configuration, the indoor unit will ignore the safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals (X5M/3+4) as the safety thermostat for the additional zone. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone.

7.10 Finishing the outdoor unit installation

7.10.1 To finish the outdoor unit installation

2 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
Installation of a safety thermostat (field supply) is required for the main zone, otherwise the unit will NOT operate.
NOTICE
A safety thermostat MUST be installed on the main zone to avoid too high water temperatures in this zone. The safety thermostat is typically a thermostatically controlled valve with a normal closed contact. When the water temperature in the main zone is too high, the contact will open and the user interface will show a 8H‑02 error. ONLY the main pump will stop.
Additional zone
3 Connect the safety thermostat (normal closed) cable to the
appropriate terminals as shown in the illustration below.
1 Insulate and fix the refrigerant piping and interconnection cable
as follows:
a Gas pipe b Gas pipe insulation c Interconnection cable d Liquid pipe e Liquid pipe insulation
f Finishing tape
2 Install the service cover.
Installer reference guide
40
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 41

8 Configuration

1
3
2
4
A1P
X10A

7.10.2 To close the outdoor unit

NOTICE
When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 4.1N•m.

7.11 Finishing the indoor unit installation

7.11.1 To fix the user interface cover to the indoor unit

1 Make sure that the front panel is removed from the indoor unit.
See "7.2.3To open the indoor unit"on page23.
2 Plug the user interface cover into the hinges.
8 Configuration

8.1 Overview: Configuration

This chapter describes what you have to do and know to configure the system after it is installed.
Why
If you do NOT configure the system correctly, it might NOT work as expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system using two different methods.
Method Description
Configuring via the user interface
Configuring via the PC configurator
INFORMATION
When the installer settings are changed, the user interface will request to confirm. When confirmed, the screen will shortly turn OFF and "busy" will be displayed for several seconds.
Accessing settings – Legend for tables
You can access the installer settings using two different methods. However, NOT all settings are accessible via both methods. If so, the corresponding table columns in this chapter are set to N/A (not applicable).
First time – Quick wizard. When you turn ON the user interface for the first time (via the indoor unit), a quick wizard starts to help you configure the system.
Afterwards. If necessary, you can make changes to the configuration afterwards.
You can prepare the configuration off-site on PC and afterwards upload the configuration to the system with the PC configurator.
See also: "8.1.1To connect the PC cable to
the switch box"on page41.
3 Mount the front panel to the indoor unit.

7.11.2 To close the indoor unit

1 Close the switch box cover.
2 Reinstall the top plate.
3 Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1N•m.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Method Column in tables
Accessing settings via the breadcrumb in the menu structure.
Accessing settings via the code in the overview settings.
See also:
"To access the installer settings"on page42
"8.5Menu structure: Overview installer settings"on page62
#
Code

8.1.1 To connect the PC cable to the switch box

Prerequisite: The EKPCCAB kit is required.
1 Connect the cable with USB connection to your PC.
2 Connect the plug of the cable to X10A on A1P of the switch box
of the indoor unit.
Installer reference guide
41
Page 42
8 Configuration
2
345
H JS T
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
15
Overview settings
Confirm Adjust Scroll
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
15
Overview settings
Confirm
Adjust
Scroll
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
20
Overview settings
Confirm
Adjust
Scroll
Installer settings
The system will restart.
Confirm Adjust
Cancel
OK
15:10
Tue
U5:Auto address
Push 4 sec. to continue
3 Pay special attention to the position of the plug!
3 Go to the corresponding second part of the setting by using the
and button.
NOTICE
Another cable is already connected to X10A. To connect the PC cable to X10A, therefore temporarily disconnect this other cable. Do NOT forget to reconnect it afterwards.

8.1.2 To access the most used commands

To access the installer settings
1 Set the user permission level to Installer.
2 Go to [A]:
To access the overview settings
1 Set the user permission level to Installer.
2 Go to [A.8]:
To set the user permission level to Installer
1 Set the user permission level to Adv. end user.
2 Go to [6.4]:
3 Press
Result:
4 If you do NOT press any button for more than 1hour or press
again for more than 4seconds, the installer permission level
switches back to End user.
To set the user permission level to Advanced end user
1 Go to the main menu or any of its submenus:
2 Press
Result: The user permission level switches to Adv. end user.
Additional information is displayed and "+" is added to the menu title. The user permission level will stay in Adv. end user until set otherwise.
To set the user permission level to End user
1 Press
Result: The user permission level switches to End user. The user
interface will return to the default home screen.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
1 Go to [A.8]:
2 Go to the corresponding screen of the first part of the setting by
using the
INFORMATION
An additional 0-digit is added to the first part of the setting when you access the codes in the overview settings.
Example: [1‑01]: "1" will result in "01".
Installer reference guide
42
> Installer settings.
> Installer settings > Overview settings.
> Information > User permission level.
for more than 4seconds.
is displayed on the home pages.
for more than 4seconds.
for more than 4 seconds.
> Installer settings > Overview settings.
and button.
Result: The value to be modified is now highlighted.
4 Modify the value by using the
5 Repeat previous steps if you have to modify other settings.
6 Push
7 At installer settings menu, press
Result: The system will restart.
to confirm the modification of the parameter.
and button.
to confirm the settings.

8.1.3 To copy the system settings from the first to the second user interface

.
If a second user interface is connected, the installer must first proceed below instructions for the proper configuration of the 2 user interfaces.
This procedure offers you also the possibility to copy the language set from one user interface to the other one: e.g. from EKRUCBL2 to EKRUCBL1.
1 When power is turned on for the first time, both user interfaces
display:
2 Push for 4seconds on the user interface on which you want
to proceed to the quick wizard. This user interface is now the main user interface.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 43
8 Configuration
Synchronization
Data difference detected. Please select action:
Send data
Confirm
Adjust
Start copy
Are you sure you want to start the copy operation?
Cancel
OK
Confirm Adjust
Language
Select the desired language
Confirm Adjust
1 2013
Jan
Tue
Confirm Adjust Scroll
Date
What is the date today?
00 : 00
What is the current time?
Time
Confirm
Adjust
Scroll
A.2 1
Scroll
Select
System layout
Standard
Options Capacities Confirm layout
Confirm layout Please confirm the system
layout. The system will restart and will be ready for first startup.
OK
Cancel
Confirm
Adjust
INFORMATION
During the quick wizard, the second user interface displays Busy and will NOT be possible to operate.
3 The quick wizard will guide you.
4 For proper operation of the system, the local data on the two
user interfaces must be the same. If this is NOT the case, both user interfaces will display:
5 Select the required action:
▪ Send data: the user interface you are operating contains the
correct data and the data on the other user interface will be overwritten.
▪ Receive data: the user interface you are operating does
NOT contain the correct data and the data on the other user interface will be used to overwrite.
6 The user interface requests confirmation if you are sure to
proceed.
1 At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
2 Set the current date and time.
3 Set the system layout settings: Standard, Options, Capacities.
For more details, see "8.2Basic configuration"on page43.
7 Confirm the selection on the screen by pushing and all data
(languages, schedules etc.) will be synchronised from the selected source user interface to the other one.
INFORMATION
▪ During the copying, both controllers will NOT allow
operation.
▪ The copy operation can take up until 90 minutes.
▪ It is recommended to change installer settings, or the
configuration of the unit, on the main user interface. If not, it can take up to 5 minutes before these changes are visible in the menu structure.
8 Your system is now set to be operated by the 2 user interfaces.

8.1.4 To copy the language set from the first to the second user interface

See "8.1.3To copy the system settings from the first to the second
user interface"on page42.

8.1.5 Quick wizard: Set the system layout after first power ON

After first power ON of the system, you are guided on the user interface to do initial settings:
▪ language,
▪ date,
▪ time,
▪ system layout.
By confirming the system layout, you can proceed with the installation and commissioning of the system.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
4 After configuration, select Confirm layout and press .
5 The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and commissioning of the system.
When the installer settings are changed, the system will request to confirm. When confirmation is complete, the screen will shortly turn OFF and "busy" will be displayed for several seconds.

8.2 Basic configuration

8.2.1 Quick wizard: Language / time and date

# Code Description
[A.1] N/A Language
[1] N/A Time and date
Installer reference guide
43
Page 44
8 Configuration
c
b
a
c
FHL1 FHL2 FHL3
M
HPC1 HPC2 HPC3

8.2.2 Quick wizard: Standard

Backup heater configuration (only for *9W model)
The backup heater in a *9W model is adapted to be connected to most common European electricity grids. Besides hardware configuration, the grid type and the relay setting must be set on the user interface.
# Code Description
[A.2.1.5] [5-0D] BUH type:
▪ 1 (1P,(1/1+2)): 6kW 1~230V (*9W)
▪ 3 (3P,(1/1+2)): 6kW 3~230V (*9W)
▪ 4 (3PN,(1/2)): 6kW 3N~400V (*9W)
▪ 5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)
Relay setting
Relay setting Backup heater operation
If backup heater step 1 is active:
1/1+2 Relay 1 ON Relays 1+2 ON
1/2 Relay 1 ON Relay 2 ON
Space heating settings
The system can heat up a space. Depending on the type of application, the space heating settings must be made accordingly.
# Code Description
[A.2.1.7] [C-07] Unit control method:
▪ 0 (LWT control): Unit operation is
decided based on the leaving water temperature regardless the actual room temperature and/or heating demand of the room. This is applicable for both temperature zones.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat or equivalent (e.g. heat pump convector). This is applicable for both temperature zones.
▪ 2 (RT control): Unit operation for the
main temperature zone is decided based on the ambient temperature of the user interface. The additional temperature zone is controlled by the external thermostat.
If backup heater step 2 is active:
# Code Description
[A.2.1.B] N/A Only if there are 2user interfaces (1
installed in the room, 1 installed at the indoor unit):
▪ a: At unit
▪ b: In room as room thermostat
▪ c: Remote controller of the heat pump
convectors
User interface location:
▪ At unit: the other user interface is
automatically set to In room and if RT control is selected act as room thermostat.
▪ In room (default): the other user
interface is automatically set to At unit and if RT control is selected to act as room thermostat. Controlling the main zone.
Installer reference guide
44
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 45
8 Configuration
M
FHL1 FHL2 FHL3
HPC1 HPC2 HPC3
a
b
a
b c
d
b c
a b
d
e
f
c
g b
c
a
d
e
b
b
c
b c
c
# Code Description
[A.2.1.8] [7-02] The system can supply leaving water to
up to 2 water temperature zones. During configuration, the number of water zones must be set.
Number of LWT zones: This unit is designed for 2 leaving water temperature zones. Do NOT change this setting.
▪ 0 (1 LWT zone): N/A.
▪ 1 (2 LWT zones)(default): 2 leaving
water temperature zones. The zone with the lowest leaving water temperature is called the main leaving water temperature zone. The zone with the highest leaving water temperature is called the additional leaving water temperature zone. In practice, the main leaving water temperature zone consists of underfloor heating and the additional water temperature zone consists of radiators or heat pump convectors.
# Code Description
[A.2.1.9] [F-0D] << continuation
▪ 1 (Sample): The pump is ON when
there is heating demand and the leaving water temperature has NOT reached the desired temperature yet. When thermo OFF condition occurs, the pump runs every 5 minutes to check the water temperature and demand heating if necessary. Remark: Sample is NOT available in external room thermostat control or room thermostat control.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
continued >>
▪ a: Add LWT zone
▪ b: Main LWT zone
# Code Description
[A.2.1.9] [F-0D] When the space heating control is OFF
by the user interface, the pump is always OFF. When the space heating control is On, you can select the desired pump operation mode (only applicable during space heating). This is applicable for both temperature zones.
Pump operation mode:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or OFF condition. Remark: continuous pump operation requires more energy than sample or request pump operation.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Pump operation
continued >>
# Code Description
[A.2.1.9] [F-0D] << continuation
▪ 2 (Request)(default): Pump operation
based on request. Example: Using a room thermostat creates thermo ON/ OFF condition. When there is no such demand, the pump is OFF. Remark: Request is NOT available in leaving water temperature control.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation

8.2.3 Quick wizard: Options

Domestic hot water settings
Following settings must be made accordingly.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
45
Page 46
8 Configuration
c f
b
a
g
c
b
a
d f
e g
# Code Description
[A.2.2.1] [E-05] DHW operation:
Can the system prepare domestic hot water?
▪ 0 (No): NOT installed.
▪ 1 (Yes)(default): Installed. Remark:
The domestic hot water tank is by default installed. Do NOT change this setting.
[A.2.2.A] [D-02] The indoor unit offers the possibility to
connect a field supplied domestic hot water pump (On/OFF type). Depending on the installation and configuration on the user interface, we distinguish its functionality.
DHW pump:
▪ 0 (No)(default): NOT installed.
▪ 1 (Secondary rtrn): Installed for instant
hot water when water is tapped. The end-user sets the operation timing (weekly schedule time) of the domestic hot water pump when it should run. Control of this pump is possible through the indoor unit.
▪ 2 (Disinf. shunt): Installed for
disinfection. It runs when the disinfection function of the domestic hot water tank is running. No further settings are needed.
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water Disinfection
a Indoor unit
b Tank
c Domestic hot water pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
f Shower (field supply)
g Cold water
Thermostats and external sensors
Following combinations are possible to control the unit (not applicable when [C‑07]=0):
When [C‑07]=2 (RT control)
User interface at
indoor unit
(1)
Room thermostat at
main zone
(2)
External room
thermostat at
additional zone
User interface at
indoor unit
External room
thermostat at main
zone
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.
See "5Application guidelines"on page11.
# Code Description
[A.2.2.4] [C-05] Contact type main
In external room thermostat control, the contact type of the optional room thermostat or heat pump convector for the main leaving water temperature zone must be set. See "5Application
guidelines"on page11.
▪ 1 (Thermo ON/OFF): The connected
external room thermostat or heat pump convector sends the heating demand to the indoor unit (X2M/1). Select this value in case of a connection to the heat pump convector (FWXV).
▪ 2 (H/C request)(default): The
connected external room thermostat sends a heating demand and is connected to the digital input (preserved for the main leaving water temperature zone) on the indoor unit (X2M/1). Select this value in case of connection with the wired (EKRTWA) or wireless (EKRTR1) room thermostat.
[A.2.2.5] [C-06] Contact type add.
In external room thermostat control with 2 leaving water temperature zones, the type of the optional room thermostat for the additional leaving water temperature zone must be set. See "5Application
guidelines"on page11.
▪ 1 (Thermo ON/OFF): See Contact
type main. Connected on the indoor unit (X2M/1a).
▪ 2 (H/C request)(default): See Contact
type main. Connected on the indoor unit (X2M/1a).
External room
thermostat at
additional zone
When [C‑07]=1 (Ext RT control)
(1)Not mandatory. (2)When there is no user interface installed at the indoor unit, the user interface in the main zone will function as room thermostat AND user interface.
Installer reference guide
46
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 47
8 Configuration
# Code Description
[A.2.2.B] [C-08] External sensor
When an optional external ambient sensor is connected, the type of the sensor must be set. See "5Application
guidelines"on page11.
▪ 0 (No)(default): NOT installed. The
thermistor in the user interface and in the outdoor unit are used for measurement.
▪ 1 (Outdoor sensor): Installed. The
external outdoor sensor will be used to measure the outdoor ambient temperature. Remark: For some functionality, the temperature sensor in the outdoor unit is still used.
▪ 2 (Room sensor): Installed. The
temperature sensor in the user interface is NOT used anymore. Remark: This value has only meaning in room thermostat control.
Digital I/O PCB
Modification of these settings is only needed when the optional digital I/O PCB is installed. The digital I/O PCB has multiple functionality which need to be configured. See "5 Application
guidelines"on page11.
# Code Description
[A.2.2.6.1] [C-02] Not applicable.
[A.2.2.6.2] [D-07] Not applicable (read only).
[A.2.2.6.3] [C-09] Alarm output
Indicates the logic of the alarm output on the digital I/O PCB during malfunctioning.
▪ 0 (Normally open): The alarm output
will be powered when an alarm occurs. By setting this value, a distinction is made between the detection of an alarm, and the detection of a power failure.
▪ 1 (Normally closed): The alarm output
will NOT be powered when an alarm occurs.
See also table below (Alarm output logic).
[A.2.2.6.4] [F-04] Bottom plate heater
Only applicable for EHVZ16. Indicates if an optional bottom plate heater is installed on the outdoor unit. The power of the bottom plate heater is in this case supplied by the indoor unit.
▪ 0 (No)(default): NOT installed.
▪ 1 (Yes): Installed. Remark: If this
value is set, the output on the digital I/ O PCB cannot be used for space heating output. See "5 Application
guidelines"on page11.
Alarm output logic
[C-09] Alarm No alarm No power
supply to unit
0 (default) Closed output Open output Open output
1 Open output Closed output
Demand PCB
The demand PCB is used to enable the power consumption control by digital inputs. See "5Application guidelines"on page11.
# Code Description
[A.2.2.7] [D-04] Demand PCB
Only applicable for EHVZ04+08. Indicates if the optional demand PCB is installed.
▪ 0 (No)(default)
▪ 1 (Pwr consmp ctrl)
Energy metering
When energy metering is performed by the use of external power meters, configure the settings as described below. Select the pulse frequency output of each power meter in accordance with the power meter specifications. It is possible to connect (up to 2) power meters with different pulse frequencies. When only 1 or no power meter is used, select No to indicate the corresponding pulse input is NOT used.
# Code Description
[A.2.2.8] [D‑08] Optional external kWh meter1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)
[A.2.2.9] [D‑09] Optional external kWh meter2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)

8.2.4 Quick wizard: Capacities (energy metering)

The capacities of all electrical heaters must be set for the energy metering and/or power consumption control feature to work properly. When measuring the resistance value of each heater, you can set the exact heater capacity and this will lead to more accurate energy data.
# Code Description
[A.2.3.2] [6-03] BUH: step 1: The capacity of the first
step of the backup heater at nominal voltage. Nominal value 3kW. Default: 3kW.
Range: 0~10kW (in steps of 0.2kW)
[A.2.3.6] [6-07] Bottom plate heater: Only applies to an
optional bottom plate heater (EKBPHTH16A). The capacity of the optional bottom plate heater at nominal voltage. Default: 0W.
Range: 0~200W (in steps of 10W)
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
47
Page 48
8 Configuration
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]

8.2.5 Space heating control

The basic required settings in order to configure the space heating of your system are described in this chapter. The weather-dependent installer settings define the parameters for the weather-dependent operation of the unit. When weather-dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. Low outdoor temperatures will result in warmer water and vice versa. During weather-dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C.
See the user reference guide and/or operation manual for more details about this function.
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A LWT setpoint mode:
▪ Fixed (default)
The desired leaving water temperature is:
▪ NOT weather-dependent (i.e. does
NOT depend on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep.: The desired leaving
water temperature is:
▪ weather-dependent (i.e. depends
on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
continued >>
# Code Description
[A.3.1.1.1] N/A << continuation
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT weather-dependent (i.e.,
does NOT depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions consists of desired shift actions, either preset or custom.
Remark: This value can only be set in leaving water temperature control.
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent (i.e., does
depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions consists of desired leaving water temperatures either preset or custom.
Remark: This value can only be set in leaving water temperature control.
# Code Description
[7.7.1.1] [1-00]
Set weather-dependent heating:
[1-01]
[1-02]
[1-03]
▪ Tt: Target leaving water temperature
(main)
▪ Ta: Outdoor temperature
continued >>
# Code Description
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
<< continuation
▪ [1-00]: Low outdoor ambient
temperature.–40°C~+5°C (default: – 10°C)
▪ [1-01]: High outdoor ambient
temperature. 10°C~25°C (default: 15°C)
▪ [1-02]: Desired leaving water
temperature when the outdoor temperature equals or drops below the low ambient temperature. [9‑01]°C~[9‑00]°C (default: 35°C). Note: This value should be higher than [1-03] as for low outdoor temperatures warmer water is required.
▪ [1-03]: Desired leaving water
temperature when the outdoor temperature equals or rises above the high ambient temperature. [9‑01]°C~min(45, [9‑00])°C (default: 25°C). Note: This value should be lower than [1-02] as for high outdoor temperatures less warm water is required.
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.
Installer reference guide
48
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 49
8 Configuration
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
# Code Description
[A.3.1.2.1] N/A LWT setpoint mode:
▪ Fixed (default): The desired leaving
water temperature is:
▪ NOT weather-dependent (i.e. does
NOT depend on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep.: The desired leaving
water temperature is:
▪ weather-dependent (i.e. depends
on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT weather-dependent (i.e.,
does NOT depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be set in leaving water temperature control.
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent (i.e., does
depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be set in leaving water temperature control.
# Code Description
[7.7.2.1] [0-00]
Set weather-dependent heating:
[0-01]
[0-02]
[0-03]
▪ Tt: Target leaving water temperature
(additional)
▪ Ta: Outdoor temperature
continued >>
# Code Description
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
<< continuation
▪ [0-03]: Low outdoor ambient
temperature. –40°C~+5°C (default: – 10°C)
▪ [0-02]: High outdoor ambient
temperature. 10°C~25°C (default: 15°C)
▪ [0-01]: Desired leaving water
temperature when the outdoor temperature equals or drops below the low ambient temperature. [9‑05]°C~[9‑06]°C (default: 45°C). Note: This value should be higher than [0-00] as for low outdoor temperatures warmer water is required.
▪ [0-00]: Desired leaving water
temperature when the outdoor temperature equals or rises above the high ambient temperature. [9‑05]°C~min(45, [9‑06])°C (default: 35°C). Note: This value should be lower than [0-01] as for high outdoor temperatures less warm water is required.
Leaving water temperature: Delta T source
When both temperature zones have heating demand, both pumps will operate at full speed. When only 1 temperature zone has heating demand, only 1 pump will operate and the flow will be controlled to realize a temperature difference between the entering and the leaving water of [9‑09] on that zone. Only 1 temperature difference [9‑09] can be selected, this is then applicable for both temperature zones.
# Code Description
[A.3.1.3.1] [9-09] Heating: Required temperature
difference between entering and leaving water. Range: 3°C~10°C (in steps of 1°C; default value: 5°C).
Leaving water temperature: Modulation
Only applicable in case of room thermostat control. When using the room thermostat functionality, the customer needs to set the desired room temperature. The unit will supply hot water to the heat emitters and the room will be heated. Additionally, also the desired leaving water temperature must be configured: when turning on the modulation, the desired leaving water temperature will be calculated automatically by the unit (based on the preset temperatures, if weather-dependent is selected, modulation will be done based on the desired weather-dependent temperatures); when turning off the modulation, you can set the desired leaving water temperature on the user interface. Moreover, with the modulation turned on, the desired leaving water temperature is lowered or raised in function of the desired room temperature and the difference between the actual and the desired room temperature. This results in:
▪ stable room temperatures exactly matching the desired
temperature (higher comfort level)
▪ less On/OFF cycles (lower noise level, higher comfort and higher
efficiency)
▪ water temperatures as low as possible to match the desired
temperature (higher efficiency)
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
49
Page 50
8 Configuration
a
+[8-06]
−[8-06]
b
T
a
T
t
# Code Description
[A.3.1.1.5] [8-05] Modulated LWT:
▪ No (default): disabled.
Note: The desired leaving water temperature needs to be set on the user interface.
▪ Yes: enabled.
Note: The desired leaving water temperature can only be read out on the user interface
N/A [8-06] Leaving water temperature maximum
modulation:
0°C~10°C (default: 3°C)
Requires modulation to be enabled.
This is the value by which the desired leaving water temperature is increased or lowered.
INFORMATION
Only applicable for the main zone.
INFORMATION
When leaving water temperature modulation is enabled, the weather‑dependent curve needs to be set to a higher position than [8-06] plus the minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for the room. To increase efficiency, modulation can lower the leaving water setpoint. By setting the weather‑dependent curve to a higher position, it cannot drop below the minimum setpoint. Refer to the illustration below.

8.2.6 Domestic hot water control

Configuring the desired tank temperature
The domestic hot water can be prepared in 3 different ways. They differ from each other by the way the desired tank temperature is set and how the unit acts upon it.
# Code Description
[A.4.1] [6-0D] Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.): The domestic hot
water tank is heated according to a schedule and between the scheduled heatup cycles, reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated according to a schedule.
See "8.3.2 Domestic hot water control: advanced" on page 53 for more details.
INFORMATION
There is a risk of space heating capacity shortage/comfort problem (in case of frequent domestic hot water operation, frequent and long space heating interruption will happen) when selecting [6‑0D]=0 ([A.4.1] Domestic hot water Type=Reheat only).
Maximum DHWtemperature setpoint
The maximum temperature that users can select for the domestic hot water. You can use this setting to limit the temperatures at the hot water taps.
a Weather-dependent curve
b Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the room.
Leaving water temperature: Emitter type
This setting only applies to the main zone. Only applicable in case of room thermostat control. Depending on the system water volume and the heat emitters type, the heat up of a space can take longer. This setting can compensate for a slow or a quick heating system during the heat up cycle.
Note: The setting of the emitter type will influence the maximum modulation of the desired leaving water temperature.
Therefore it is important to set this correctly.
# Code Description
[A.3.1.1.7] [9-0B] Emitter type:
Set for the main temperature zone.
Reaction time of the system:
▪ Quick Example: Small water volume
and fan coils.
▪ Slow Example: Large water volume,
floor heating loops.
INFORMATION
During disinfection of the domestic hot water tank, the DHWtemperature can exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the applicable legislation.
# Code Description
[A.4.5] [6-0E] Maximum setpoint
The maximum temperature that users can select for the domestic hot water. You can use this setting to limit the temperature at the hot water taps. Range: 40°C~60°C (default: 60°C).
The maximum temperature is NOT applicable during disinfection function. See disinfection function.

8.2.7 Contact/helpdesk number

# Code Description
[6.3.2] N/A Number that users can call in case of
problems.

8.3 Advanced configuration/ optimization

8.3.1 Space heating operation: advanced

Preset leaving water temperature
You can define preset leaving water temperatures:
Installer reference guide
50
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 51
8 Configuration
T
t
T
A
R
L
0°C
T
t
T
A
R
L
0°C
a b
▪ economic (denotes the desired leaving water temperature which
results in the lowest energy consumption)
▪ comfort (denotes the desired leaving water temperature which
results in the highest energy consumption).
Preset values make it easy to use the same value in the schedule or to adjust the desired leaving water temperature according to the room temperature (see modulation). If you later want to change the value, you ONLY have to do it in one place. Depending on whether the desired leaving water temperature is weather dependent or NOT, the desired shift values or the absolute desired leaving water temperature should be specified.
NOTICE
The preset leaving water temperatures are ONLY applicable for the main zone, as the schedule for the additional zone consists of On/OFF actions.
NOTICE
Select preset leaving water temperatures in accordance with the design and selected heat emitters to ensure the balance between desired room and leaving water temperatures.
# Code Description
Preset leaving water temperature for the main leaving water temperature zone in case of NOT weather dependent
[7.4.2.1] [8-09] Comfort (heating)
[9‑01]°C~[9‑00]°C (default: 35°C)
[7.4.2.2] [8-0A] Eco (heating)
[9‑01]°C~[9‑00]°C (default: 33°C)
Preset leaving water temperature (shift value) for the main leaving water temperature zone in case of weather dependent
[7.4.2.5] N/A Comfort (heating)
–10°C~+10°C (default: 0°C)
[7.4.2.6] N/A Eco (heating)
–10°C~+10°C (default: –2°C)
Temperature ranges (leaving water temperatures)
The purpose of this setting is to prevent selecting a wrong (i.e. too hot or too cold) leaving water temperature. Therefore the available desired heating temperature range can be configured.
NOTICE
In case of a floor heating application it is important to limit the maximum leaving water temperature at heating operation according to the specifications of the floor heating installation.
Example: Set the minimum leaving water temperature to 28°C to avoid NOT to be able to heat up the room: leaving water temperatures MUST be sufficiently higher than the room temperatures (in heating).
# Code Description
Leaving water temperature range for the main leaving water temperature zone (= the leaving water temperature zone with the lowest leaving water temperature)
[A.3.1.1.2.2] [9-00] Maximum temp (heating)
37°C~55°C (default: 55°C)
[A.3.1.1.2.1] [9-01] Minimum temp (heating)
15°C~37°C (default: 25°C)
Leaving water temperature range for the additional leaving water temperature zone (= the leaving water temperature zone with the highest leaving water temperature)
[A.3.1.2.2.2] [9-06] Maximum temp (heating)
37°C~55°C (default: 55°C)
[A.3.1.2.2.1] [9-05] Minimum temp (heating)
15°C~37°C (default: 25°C)
Leaving water temperature overshoot temperature
This function defines how much the water temperature may rise above the desired leaving water temperature before the compressor stops. The compressor will startup again when the leaving water temperature drops below the desired leaving water temperature.
# Code Description
N/A [9-04] 1°C~4°C (default: 1°C)
Leaving water temperature compensation around 0°C
In heating operation, the desired leaving water temperature is locally increased around an outdoor temperature of 0°C. This compensation can be selected when using an absolute or a weather dependent desired temperature (see illustration below). Use this setting to compensate for possible heat losses of the building due to the evaporation of melted ice or snow (e.g. in cold region countries).
NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or the capacity (according to the design and selection of the heat emitters). The desired leaving water temperature is the result of several settings (preset values, shift values, weather dependent curves, modulation). As a result, too high or too low leaving water temperatures could occur which lead to overtemperatures or capacity shortage. By limiting the leaving water temperature range to adequate values (depending on the heat emitter), such situations can be avoided.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
a Absolute desired LWT b Weather dependent desired LWT
TAAmbient temperature (°C)
TtDesired leaving water temperature
# Code Description
N/A [D-03] ▪ 0 (disabled) (default)
▪ 1 (enabled) L=2°C,
R=4°C (−2°C<TA<2°C)
▪ 2 (enabled) L=4°C,
R=4°C (−2°C<TA<2°C)
▪ 3 (enabled) L=2°C,
R=8°C (−4°C<TA<4°C)
▪ 4 (enabled) L=4°C,
R=8°C (−4°C<TA<4°C)
Installer reference guide
51
Page 52
8 Configuration
[
9-0C
]
a
b
c
d
Leaving water temperature maximum modulation
ONLY applicable in room thermostat control and when modulation is enabled. The maximum modulation (=variance) on the desired leaving water temperature decided on the difference between the actual and desired room temperature, e.g. 3°C modulation means the desired leaving water temperature can be increased or lowered by 3°C. Increasing the modulation results in better performance (less On/OFF, faster heat up), but note that depending on the heat emitter, there MUST ALWAYS be a balance (refer to the design and selection of the heat emitters) between the desired leaving water temperature and the desired room temperature.
# Code Description
N/A [8-06] 0°C~10°C (default: 3°C)
Temperature ranges (room temperature)
ONLY applicable in room thermostat control. In order to save energy by preventing overheating the room, you can limit the range of the room temperature.
NOTICE
When adjusting the room temperature ranges, all desired room temperatures are also adjusted to guarantee they are between the limits.
# Code Description
Room temp. range
[A.3.2.1.2] [3-06] Maximum temp (heating)
18°C~30°C (default: 30°C)
[A.3.2.1.1] [3-07] Minimum temp (heating)
12°C~18°C (default: 12°C)
Room temperature step
ONLY applicable in room thermostat control and when the temperature is displayed in °C.
# Code Description
[A.3.2.4] N/A Room temp. step
▪ 1°C (default). The desired room
temperature on the user interface is settable per 1°C.
▪ 0.5°C. The desired room temperature
on the user interface is settable per
0.5°C. The actual room temperature is displayed with an accuracy of 0.1°C.
Room temperature hysteresis
ONLY applicable in case of room thermostat control. The hysteresis band around the desired room temperature is settable. It is recommended NOT to change the room temperature hysteresis as it is set for an optimal use of the system.
interface or by the external room sensor. The settings can be used to compensate for situations where the user interface or external room sensor CANNOT be installed on the ideal installation location (see installation manual and/or installer reference guide).
# Code Description
Room temp. offset: Offset on the actual room temperature measured on the user interface sensor.
[A.3.2.2] [2-0A] –5°C~+5°C, step 0.5°C (default: 0°C)
Ext. room sensor offset: ONLY applicable if the external room sensor option is installed and configured (see [C-08])
[A.3.2.3] [2-09] –5°C~+5°C, step 0.5°C (default: 0°C)
Room frost protection
Room frost protection prevents the room from getting too cold. This setting behaves differently depending on the set unit control method ([C‑07]). Perform actions according to the table below:
Unit control method ([C‑07]) Room frost protection
Room thermostat control ([C‑07]=2)
Allow for the room thermostat to take care of room frost protection:
▪ Set [2‑06] to "1"
▪ Set the room antifrost
temperature ([2‑05]).
External room thermostat control ([C‑07]=1)
Allow for the external room thermostat to take care of room frost protection:
▪ Turn ON the leaving water
temperature home page.
Leaving water temperature control ([C‑07]=0)
Room frost protection is NOT guaranteed.
NOTICE
If the system does NOT contain a backup heater, do NOT change the default room antifrost temperature.
INFORMATION
If a U4 error occurs, room frost protection is NOT guaranteed.
Refer to the sections below for detailed information on room frost protection in relation to the applicable unit control method.
[C‑07]=2: room thermostat control
Under room thermostat control, room frost protection is guaranteed, even if the room temperature home page is OFF on the user interface. When room frost protection ([2‑06]) is enabled and the room temperature drops below the room antifrost temperature ([2‑05]), the unit will supply leaving water to the heat emitters to heat up the room again.
a Room temperature
b Actual room temperature
c Desired room temperature
d Time
# Code Description
N/A [9-0C] 1°C~6°C (default: 1°C)
Room temperature offset
ONLY applicable in case of room thermostat control. You can calibrate the (external) room temperature sensor. It is possible to give an offset to the room thermistor value measured by the user
Installer reference guide
52
# Code Description
N/A [2-06] Room frost protection
▪ 0: disabled
▪ 1: enabled (default)
N/A [2-05] Room antifrost temperature
4°C~16°C (default: 12°C)
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 53
8 Configuration
INFORMATION
If a U5 error occurs:
▪ when 1 user interface is connected, room frost
protection is NOT guaranteed,
▪ when 2 user interfaces are connected and the second
user interface used for room temperature control is disconnected (due to miswiring, damage of the cable), then room frost protection is NOT guaranteed.
NOTICE
If Emergency is set to Manual ([A.6.C]=0), and the unit is triggered to start emergency operation, the user interface will ask confirmation before starting. Room frost protection is active even if the user does NOT confirm emergency operation.
[C‑07]=1: external room thermostat control
Under external room thermostat control, room frost protection is guaranteed by the external room thermostat, provided that the leaving water temperature home page is ON on the user interface, and the auto emergency setting ([A.6.C]) is set to "1".
Additionally, limited frost protection by the unit is possible:
In case of… …then the following applies:
Two leaving water temperature zones
[C‑07]=0: leaving water temperature control
Under leaving water temperature control, room frost protection is NOT guaranteed. However, if [2‑06] is set to "1", limited frost protection by the unit is possible:
▪ When the leaving water temperature home page is OFF and the
outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered.
▪ When the leaving water temperature home page is ON, then the
unit will supply leaving water to the heat emitters to heat up the room according to normal logic.
Shut-off valve
The following is only applicable in case of 2 leaving water temperature zones. In case of 1 leaving water temperature zone, connect the shut-off valve to the heating output.
The shut-off valve, which is in the main leaving water temperature zone, output is configurable.
INFORMATION
During defrost operation, the shut-off valve is ALWAYS opened.
▪ When the leaving water
temperature home page is OFF, and the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered.
▪ When the leaving water
temperature home page is ON, the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered.
Thermo On/OFF: the valve closes, depending on [F‑0B] when there is no heating demand from the main zone.
# Code Description
[A.3.1.1.6.1] [F-0B] The shut-off valve:
▪ 0 (No)(default): is NOT influenced by
heating demand.
▪ 1 (Yes): closes when there is NO
heating demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room thermostat request setting (NOT in case of leaving water temperature setting).
Operation range
Depending on the average outdoor temperature, the operation of the unit in space heating is prohibited.
Space heating OFF temp: When the averaged outdoor temperature raises above this value, space heating is turned OFF to avoid overheating.
# Code Description
[A.3.3.1] [4-02] ▪ EHVZ04+08: 14°C~35°C (default:
25°C)
▪ EHVZ16: 14°C~35°C (default: 35°C)

8.3.2 Domestic hot water control: advanced

Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled or scheduled + reheat.
You can define preset tank temperatures:
▪ storage economic
▪ storage comfort
▪ reheat
▪ reheat hysteresis
Preset values make it easy to use the same value in the schedule. If you later want to change the value, you only have to do it in 1 place (see also operation manual and/or user reference guide).
Storage comfort
When programming the schedule, you can make use of the tank temperatures set as preset values. The tank will then heat up until these setpoint temperatures have been reached. Additionally, a storage stop can be programmed. This feature puts a stop to tank heating even if the setpoint has NOT been reached. Only program a storage stop when tank heating is absolutely undesirable.
# Code Description
[7.4.3.1] [6-0A] 30°C~[6‑0E]°C (default: 60°C)
Storage eco
The storage economic temperature denotes the lower desired tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day).
# Code Description
[7.4.3.2] [6-0B] 30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat
The desired reheat tank temperature is used:
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
53
Page 54
8 Configuration
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E] [0-0D]
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U=TBUH OFF
[6-01] [6-00]
TU= 60°C T
HP MAX
= 50°C [6-01] = 2°C [6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
▪ in reheat mode of scheduled + reheat mode: The guaranteed
minimum tank temperature is set by T
–[6‑08], which is either
HP OFF
[6‑0C] or the weather dependent setpoint, minus the reheat hysteresis. If the tank temperature drops below this value, the tank is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature raises above this value, domestic hot water preparation and space heating is executed sequentially.
# Code Description
[7.4.3.3] [6-0C] 30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat hysteresis
Only applicable when domestic hot water preparation is scheduled + reheat.
# Code Description
N/A [6-08] 2°C~20°C (default: 10°C)
Weather dependent
The weather dependent installer settings define the parameters for the weather dependent operation of the unit. When weather dependent operation is active the desired tank temperature is determined automatically depending on the averaged outdoor temperature: low outdoor temperatures will result in higher desired tank temperatures as the cold water tap is colder and vice versa. In case of scheduled or scheduled+reheat domestic hot water preparation, the storage comfort temperature is weather dependent (according to the weather dependent curve), the storage economic and reheat temperature are NOT weather dependent. In case of reheat only domestic hot water preparation, the desired tank temperature is weather dependent (according to the weather dependent curve). During weather dependent operation, the end­user cannot adjust the desired tank temperature on the user interface.
# Code Description
[A.4.6] N/A Weather dependent desired tank
temperature is:
▪ Fixed (default): disabled. All desired
tank temperature are NOT weather dependent.
▪ Weather dep.: enabled. In scheduled
or scheduled+reheat mode, the storage comfort temperature is weather dependent. Storage economic and reheat temperatures are NOT weather dependent. In reheat mode, the desired tank temperature is weather dependent. Note: When the displayed tank temperature is weather dependent, it cannot be adjusted on the user interface.
# Code Description
[A.4.7] [0-0E]
Weather-dependent curve
[0-0D]
[0-0C]
[0-0B]
▪ T
: The desired tank temperature.
DHW
▪ Ta: The (averaged) outdoor ambient
temperature
▪ [0-0E]: low outdoor ambient
temperature: –40°C~5°C (default: – 10°C)
▪ [0-0D]: high outdoor ambient
temperature: 10°C~25°C (default: 15°C)
▪ [0-0C]: desired tank temperature when
the outdoor temperature equals or drops below the low ambient temperature: 45°C~[6‑0E]°C (default: 60°C)
▪ [0-0B]: desired tank temperature when
the outdoor temperature equals or rises above the high ambient temperature: 35°C~[6‑0E]°C (default: 55°C)
Limits on heat pump operation
In domestic hot water operation, following hysteresis values can be set for the heat pump operation:
# Code Description
N/A [6-00] The temperature difference determining
the heat pump ON temperature.
Range: 2°C~20°C (default: 2°C)
N/A [6-01] The temperature difference determining
the heat pump OFF temperature.
Range: 0°C~10°C (default: 2°C)
Example: setpoint (TU)>maximum heat pump temperature–[6‑01] (T
–[6‑01])
HP MAX
Installer reference guide
54
BUH Backup heater
HP Heat pump. If heating up time by the heat pump takes too
T
long, auxiliary heating by the backup heater can take place Backup heater OFF temperature (TU)
BUH OFF
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
−[6-01])
HP MAX
4P401677-1B – 2017.04
Page 55
T
t
[6-00]
HP
5
10
20
30
40
43
45
TU=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
t
1
0
1
0
[8-01] [8-02]
[8-00]
t
T
A
0
[8-01]
[5-03] [4-02]
[8-02]
[8-01]+
[8-04]
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
TUUser set point temperature (as set on the user interface)
t Time
HP OFF
−[6-00])
Example: setpoint (TU)≤maximum heat pump temperature–[6‑01] (T
–[6‑01])
HP MAX
8 Configuration
# Code Description
N/A [8-04] Additional running time for the maximum
running time depending on the outdoor temperature [4‑02].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
Timers for simultaneous request space and domestic hot water operation
N/A [8-00] Do not change. (default: 1)
N/A [8-01] Maximum running time for domestic hot
N/A [8-02] Anti-recycling time.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
HP Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
TUUser set point temperature (as set on the user interface)
t Time
HP MAX
HP OFF
−[6-01])
−[6-00])
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For more information, see the operation range.
# Code Description
water operation. Domestic hot water heating stops even when the target domestic hot water temperature is NOT reached. The actual maximum running time also depends on setting [8‑04].
▪ When system layout = Room
thermostat control: This preset value is only taken into account if there is a request for space heating. If there is NO request for space heating, the tank is heated until the setpoint has been reached.
▪ When system layout ≠ Room
thermostat control: This preset value is always taken into account.
Range: 5~95 minutes (default: 30)
Minimum time between two cycles for domestic hot water. The actual anti­recycling time also depends on setting [8‑04].
Range: 0~10 hours (default: 0.5) (step:
0.5 hour).
Remark: The minimum time is 1/2 hour even when the selected value is 0.
1 Heat pump domestic water heating mode (1=active, 0=not
active)
2 Hot water request for heat pump (1=request, 0=no request)
t Time
[8-04]: Additional running time at [4-02]/[F-01]
TAAmbient (outdoor) temperature
t Time
Anti-recycle time Maximum running time domestic hot water
Disinfection
The disinfection function disinfects the domestic hot water tank by periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to the applicable legislation.
# Code Description
[A.4.4.2] [2‑00] Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1] [2‑01] Disinfection
▪ 0: No
▪ 1: Yes
[A.4.4.3] [2‑02] Start time: 00~23:00, step: 1:00.
[A.4.4.4] [2‑03] Temperature target: 60°C (fixed).
[A.4.4.5] [2‑04] Duration: 40~60 minutes, default: 40
minutes.
Installer reference guide
55
Page 56
8 Configuration
00.00 22.00 24.0001.00 23.00 t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
T
Domestic hot water temperature
DHW
TUUser set point temperature THHigh set point temperature [2-03]
t Time
WARNING
Be aware that the domestic hot water temperature at the hot water tap will be equal to the value selected in field setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to the applicable legislation.
CAUTION
Be sure that the disinfection function start time [A.4.4.3] with defined duration [A.4.4.5] is NOT interrupted by possible domestic hot water demand.
INFORMATION
In case of error code AH and no interruption of the disinfection function occurred due to domestic hot water tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to program the start-up of the disinfection function at least 4 hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage eco 3 hours before the scheduled start-up of the disinfection function to preheat the tank.
INFORMATION
Disinfection function is restarted in case the domestic hot water temperature drops 5°C below the disinfection target temperature within the duration time.

8.3.3 Heat source settings

Backup heater
Backup heater operation mode: defines when backup heater operation is disabled or only allowed during domestic hot water operation. This setting is only overruled when backup heating is required during defrost operation or malfunctioning of the outdoor unit (when [A.6.C] is enabled).
# Code Description
[A.5.1.1] [4‑00] Backup heater operation:
▪ 0: Disabled
▪ 1 (default): Enabled
N/A [5-00] Is backup heater operation allowed
[A.5.1.4] [5‑01] Equilibrium temperature.
INFORMATION
If backup heater operation during space heating needs to be limited but can be allowed for domestic hot water operation, then put [4‑00] on 1, [5‑00] on 1, and [5‑01] on – 15°C.
Auto emergency
When the heat pump fails to operate, the backup heater can serve as an emergency heater and either automatically or non­automatically take over the heat load.
▪ When auto emergency is set to Automatic and a heat pump failure
occurs, the backup heater will automatically take over the heat load.
▪ When auto emergency is set to Manual and a heat pump failure
occurs, the domestic hot water and space heating operations will stop and need to be recovered manually. The user interface will then ask you to confirm whether the backup heater can take over the heat load or not.
When the heat pump fails, house is unattended for longer periods, we recommend to set [A.6.C] Emergency to Automatic.
# Code Description
[A.6.C] N/A Emergency:
above equilibrium temperature during space heating operation?
▪ 1: NOT allowed (default)
▪ 0: Allowed
Outdoor temperature below which operation of the backup heater is allowed.
Range: –15°C~35°C (default: 0°C) (step: 1°C)
will appear on the user interface. If the
▪ 0: Manual (default)
▪ 1: Automatic
INFORMATION
An AH error occurs if you do the following during disinfection:
▪ Set the user permission level to Installer.
▪ Go to the DHWtank temperature home page (Tank).
Installer reference guide
▪ Press
to interrupt the disinfection.
56
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface only.
INFORMATION
If a heat pump failure occurs and [A.6.C] is set to Manual, the room frost protection function, the underfloor heating screed dryout function, and the water pipe antifreeze function will remain active even if the user does NOT confirm emergency operation.
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 57
8 Configuration
T
A
[F-02]
[F-03]
a
b
YC Y1 Y2 Y3 Y4
X1 X2 X3 X4
OFF ON
X2M
SS1
X1M
Bottom plate heater
Applies only to installation with an outdoor unit ERHQ and the option bottom plate heater kit is installed.
▪ [F-02] Bottom plate heater ON temperature: defines the outdoor
temperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build-up in the bottom plate of the outdoor unit at lower outdoor temperatures.
▪ [F-03] Bottom plate heater hysteresis: defines the temperature
difference between bottom plate heater ON temperature and the bottom plate heater OFF temperature.
Bottom plate heater
TAOutdoor temperature
a On
b OFF
CAUTION
The bottom plate heater is controlled via EKRP1HB.
# Code Description
N/A [F-02] Bottom plate heater ON temperature:
3°C~10°C (default: 3°C)
N/A [F-03] Hysteresis: 2°C~5°C (default: 5°C)
INFORMATION
Depending on setting [F-04], contact Y2, located on digital I/O PCB EKRP1HB, controls the optional bottom plate heater. See the illustration below for the schematic location of this contact. For the complete wiring, see the wiring diagram.

8.3.4 System settings

Priorities
# Code Description
N/A [5‑02] Space heating priority.
Defines whether backup heater will assist the heat pump during domestic hot water operation.
Consequence: Shorter tank heating operation time and shorter interruption of the space heating cycle.
This setting MUST always be 1.
[5‑01] Equilibrium temperature and [5‑03] Space heating priority temperature are related to backup heater. So, you must set [5‑03] equal or a few degrees higher than [5‑01].
If the backup heater operation is limited ([4‑00]=0) and the outdoor temperature is lower than setting [5‑03], the domestic hot water will not be heated with the backup heater.
N/A [5‑03] Space heating priority temperature.
Defines the outdoor temperature which below the backup heater will assist during domestic hot water heating.
Auto-restart
When power returns after a power supply failure, the auto restart function reapplies the remote controller settings at the time of the power failure. Therefore, it is recommended to always enable the function.
If the preferential kWh rate power supply is of the type that power supply is interrupted, always enable the auto restart function. Continuous indoor unit control can be guaranteed independent of the preferential kWh rate power supply status, by connecting the indoor unit to a normal kWh rate power supply.
# Code Description
[A.6.1] [3‑00] Is the auto restart function of the unit
allowed?
▪ 0: No
▪ 1 (default): Yes
Preferential kWh rate power supply
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals (X5M/3+4) as the safety thermostat for the additional zone. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
57
Page 58
8 Configuration
1 2 3
# Code Description
[A.2.1.6] [D‑01] Connection to a preferential kWh rate
power supply:
▪ 0 (default): The outdoor unit is
connected to a normal power supply.
▪ 1: The outdoor unit is connected to a
preferential kWh rate power supply. When the preferential kWh rate signal is sent by the electricity company, the contact will open and the unit will go in forced off mode. When the signal is released again, the voltage-free contact will close and the unit will restart operation. Therefore, always enable the auto restart function.
▪ 2: The outdoor unit is connected to a
preferential kWh rate power supply. When the preferential kWh rate signal is sent by the electricity company, the contact will close and the unit will go in forced off mode. When the signal is released again, the voltage-free contact will open and the unit will restart operation. Therefore, always enable the auto restart function.
Remark: 3 is related to safety thermostat.
[A.6.2.1] [D‑00] Which heaters are allowed to operate
during preferential kWh rate power supply?
▪ 0 (default): None
▪ 1: N/A
▪ 2: Backup heater only
▪ 3: N/A
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals (X5M/3+4) as the safety thermostat for the additional zone. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone.
Power saving function
INFORMATION
Only applicable for ERLQ004~008CAV3.
Defines whether the outdoor unit power supply can be interrupted (internally by indoor unit control) during stand-still conditions (no space heating nor domestic hot water demand). The final decision to allow power interruption of the outdoor unit during standstill depends on the ambient temperature, compressor conditions and minimum internal timers.
To enable the power saving function setting, [E‑08] needs to be enabled on the user interface in combination with the removal of the power saving connector at the outdoor unit.
NOTICE
The power saving connector at the outdoor unit shall only be removed when the main power supply to the application is switched OFF.
In case of ERLQ004~008CAV3
See table below.
Setting 2 is only meaningful if the preferential kWh rate power supply is of type1 or indoor unit is connected to a normal kWh rate power supply (via X2M/30-31) and the backup heater is NOT connected to the preferential kWh rate power supply.
Do NOT use 1 or 3.
[D‑00] Backup heater Compressor
0 (default) Forced OFF Forced OFF
2 Allowed
Safety thermostat for the additional zone
The following setting is related to the safety thermostat for the additional zone. For more information about the safety thermostat for the main zone, see "7.9.17To connect the safety thermostat (normal
closed contact)"on page40.
# Code Description
[A.2.1.6] [D‑01] Connection to a safety thermostat
voltage free contact:
▪ 0 (default): No safety thermostat.
▪ 3: Safety thermostat normal closed
contact.
Remark: 1+2 are related to preferential kWh rate power supply.
# Code Description
N/A [E‑08] Power saving function for outdoor unit:
▪ 0: Disabled
▪ 1 (default): Enabled
In case of ERHQ011~016BAV3, ERHQ011~016BAW1, ERLQ011~016CAV3, and ERLQ011~016CAW1
Do NOT change the default setting.
# Code Description
N/A [E-08] Power saving function for outdoor unit:
▪ 0 (default): Disabled
▪ 1: Enabled
Installer reference guide
58
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 59
8 Configuration
Power consumption control
Only applicable for EHVZ04+08. See "5 Application guidelines" on
page11 for detailed information about this functionality.
Pwr consumpt. control
# Code Description
[A.6.3.1] [4-08] Mode:
▪ 0 (No limitation)(default): Disabled.
▪ 1 (Continuous): Enabled: You can
set one power limitation value (in A or kW) to which the system power consumption will be limited for all the time.
▪ 2 (Digital inputs): Enabled: You can
set up to four different power limitation values (in A or kW) to which the system power consumption will be limited when the corresponding digital input asks.
[A.6.3.2] [4-09] Type:
▪ 0 (Current): The limitation values are
set in A.
▪ 1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3] [5-05] Value: Only applicable in case of full
time power limitation mode.
0A~50A, step: 1A (default: 50A)
[A.6.3.4] [5-09] Value: Only applicable in case of full
time power limitation mode.
0kW~20kW, step: 0.5kW (default: 20kW)
Amp. limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on current values.
[A.6.3.5.1] [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
[A.6.3.5.2] [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)
[A.6.3.5.3] [5-07] Limit DI3
0A~50A, step: 1A (default: 50A)
[A.6.3.5.4] [5-08] Limit DI4
0A~50A, step: 1A (default: 50A)
kW limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on power values.
[A.6.3.6.1] [5-09] Limit DI1
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.2] [5-0A] Limit DI2
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.3] [5-0B] Limit DI3
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.4] [5-0C] Limit DI4
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.7] [4-01] Priority: Not applicable.
The outdoor temperature is averaged over the selected time period.
# Code Description
[A.6.4] [1-0A] Outdoor average timer:
▪ 0: No averaging (default)
▪ 1: 12hours
▪ 2: 24hours
▪ 3: 48hours
▪ 4: 72hours
INFORMATION
If the power saving function is activated (see [E‑08]), the average outdoor temperature calculation is only possible in case the external outdoor temperature sensor is used. See
"5.6 Setting up an external temperature sensor" on page15.
Offset temperature external outdoor ambient sensor
Only applicable in case of an external outdoor ambient sensor is installed and configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible to give an offset to the thermistor value. The setting can be used to compensate for situations where the external outdoor ambient sensor cannot be installed on the ideal installation location (see installation).
# Code Description
[A.6.5] [2‑0B] –5°C~5°C, step: 0.5°C (default: 0°C)
Forced defrost
You can manually start a defrost operation.
The decision to execute the manual defrost operation is made by the outdoor unit and depends on ambient and heat exchanger conditions. When the outdoor unit accepted the forced defrost operation, will be displayed on the user interface. If is NOT displayed within 6 minutes after forced defrost operation was enabled, the outdoor unit ignored the forced defrost request.
# Code Description
[A.6.6] N/A Do you want to start a defrost operation?
Pump operation
When the pump operation function is disabled the pump will stop if the outdoor temperature is higher than the value set by [4‑02]. When the pump operation is enabled, the pump operation is possible at all outdoor temperatures.
# Code Description
N/A [F‑00] Pump operation:
▪ 0 (default): Disabled if outdoor
temperature is higher than [4‑02].
▪ 1: Possible at all outdoor
temperatures.
Pump operation during flow abnormality [F‑09] defines whether the pump stops at flow abnormality or allow to continue operation when flow abnormality occurs. This functionality is only valid in specific conditions where it is preferable to keep the pump active when Ta<4°C (pump will be activated for 10 minutes and deactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality.
Average timer
The average timer corrects the influence of ambient temperature variations. The weather-dependent set point calculation is done on the average outdoor temperature.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
59
Page 60
8 Configuration
[9-0D]=0 [9-0D]=5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]=6 [9-0D]=7
[9-0D]=8
a (kPa)
b (l/min)
# Code Description
N/A [F‑09] Pump continue operation when flow
abnormality:
▪ 0 (default): Pump will be deactivated.
▪ 1: Pump will be activated when
Ta<4°C (10 minutes ON – 10 minutes OFF)
Pump speed limitation
Pump speed limitation main zone [9‑0E] and pump speed limitation additional zone [9‑0D] define the maximum pump speed. In normal conditions, the default setting should NOT be modified. The pump speed limitation will be overruled when the flow rate is in the range of the minimum flow (error 7H).
# Code Description
N/A [9‑0E] Pump speed limitation main zone
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation in all conditions. The required delta T control and comfort are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating output, the pump speed limitation is applicable. When there is heating output, the pump speed is only determined by delta T in relation to the required capacity. With this limitation range, delta T is possible and the comfort is guaranteed.
N/A [9‑0D] Pump speed limitation additional zone
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation in all conditions. The required delta T control and comfort are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating output, the pump speed limitation is applicable. When there is heating output, the pump speed is only determined by delta T in relation to the required capacity. With this limitation range, delta T is possible and the comfort is guaranteed.
The maximum values depend on the unit type:
a External static pressure b Water flow rate
Installer reference guide
60
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 61

8.4 Menu structure: Overview user settings

< >
[1]
[2]
[5]
[6]
[7]
[2]
[6.2]
[6.3]
[6.8]
[7.1]
[7.4]
[7.3]
[3]
Set time/date
Date Time Daylight Saving Time Clock type
Holiday
Holiday
Holiday
Holiday
Holiday mode
Holiday mode
Home
Away
From
Until
Until
From
Use day schedule
Operation mode Heating
Quiet mode
Select schedules
Room temperature LWT main LWT additional Tank temperature
Information
Sensor information Energy metering Error handling User permission level Actuators Operation modes
Running hours Version
Energy metering
Consumed elec.
Produced energy
Error information
Error history Contact/helpdesk number
Version
User interface Indoor unit Outdoor unit
User settings
Display Temperature lock
Set schedules Preset values Unit of measurement
Display
Contrast
Backlit LCD time User profile Available home pages
Set schedules
Room temp. LWT main LWT additional DHW temp Quiet mode
DHW pump
Preset values
Room temperature LWT main Tank temperature Quiet level
DHW
Set weather dependent
Warning history
[7.7]
Set weather dependent
Main Additional
[7.7.1]
Main
Set weather-dependent heating
[7.7.2]
Additional
Set weather-dependent heating
8 Configuration
INFORMATION
Depending on the selected installer settings, settings will be visible/invisible.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
61
Page 62
8 Configuration
[A]
[A.2]
[A.2.1]
[A.2.2]
[A.2.2.6]
[A.3]
[A.3.1]
[A.3.1.1]
[A.3.2]
[A.3.3]
[A.4]
[A.4.4]
[A.5]
[A.5.1]
[A.7]
[A.6]
[A.6.3]
[A.6.2]
Installer settings
Language System layout Space operation Domestic hot water (DHW) Heat sources System operation Commissioning Overview settings
System layout
Standard Options Capacities Confirm layout
Space operation
LWT settings Room thermostat Operation range
Domestic hot water
Type Disinfection Maximum setpoint SP mode Weather-dependent curve
Heat sources
Backup heater
System operation
Auto restart Preferential kWh rate Pwr consumpt. control Averaging time Ext amb. sensor offset
Commissioning
Test run UFH screed dryout Air purge Actuator test run
Standard
Unit type Compressor type Indoor software type
BUH type
Backup heater steps
Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location
Options
DHW operation DHW tank type Contact type main Contact type add. Digital I/O PCB Demand PCB External kWh meter External kWh meter DHW pump External sensor
Leaving water
Main Additional Delta T source
Room thermostat
Room temp. range Room temp. offset
Operation range
Space heating OFF temp
Disinfection
Disinfection Operation day Start time Temperature target Duration
Backup heater
Operation mode Enable BUH step 2
Prefer. kWh rate PS
Allowed heaters Forced pump OFF
Pwr consmp ctrl
Mode Type Amp. value kW value Amp. limits for DI
Digital I/O PCB
Ext. backup heat src Solar kit Alarm output Bottom plate heater
Main
LWT setpoint mode
Temperature range Modulated LWT Shut-off valve
Emitter type
[A.3.1.2]
Additional
LWT setpoint mode Temperature range
Ext. room sensor offset
[A.3.1.3]
Delta T source
Heating
Forced defrost
Room temp. step
kW limits for DI Priority
Emergency
Equilibrium temp.
LAN adapter

8.5 Menu structure: Overview installer settings

INFORMATION
Depending on the selected installer settings, settings will be visible/invisible.
Installer reference guide
62
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 63

9 Commissioning

9 Commissioning

9.1 Overview: Commissioning

This chapter describes what you have to do and know to commission the system after it is configured.
Typical workflow
Commissioning typically consists of the following stages:
1 Checking the "Checklist before commissioning".
2 Performing an air purge.
3 Performing a test run for the system.
4 If necessary, performing a test run for one or more actuators.
5 If necessary, performing an underfloor heating screed dryout.

9.2 Precautions when commissioning

INFORMATION
During the first running period of the unit, the required power may be higher than stated on the nameplate of the unit. This phenomenon is caused by the compressor, that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption.
NOTICE
Before starting up the system, the unit MUST be energised for at least 6hours. The crankcase heater needs to heat up the compressor oil to avoid oil shortage and compressor breakdown during startup.
NOTICE
NEVER operate the unit without thermistors and/or pressure sensors/switches. Burning of the compressor might result.
NOTICE
Do NOT operate the unit until the refrigerant piping is complete (when operated this way, the compressor will break).

9.3 Checklist before commissioning

Do NOT operate the system before the following checks are OK:
You read the complete installation instructions, as described in the installer reference guide.
The indoor unit is properly mounted.
The outdoor unit is properly mounted.
The following field wiring has been carried out according to this document and the applicable legislation:
▪ Between the local supply panel and the outdoor unit
▪ Between indoor unit and outdoor unit
▪ Between the local supply panel and the indoor unit
▪ Between the indoor unit and the valves (if applicable)
▪ Between the indoor unit and the room thermostat (if
applicable)
There are NO missing phases or reversed phases.
The system is properly earthed and the earth terminals are tightened.
The fuses or locally installed protection devices are installed according to this document, and have not been bypassed.
The power supply voltage matches the voltage on the identification label of the unit.
There are NO loose connections or damaged electrical components in the switchbox.
There are NO damaged components or squeezed
pipes on the inside of the indoor and outdoor units.
Backup heater circuit breaker F1B on the switchbox is
turned ON.
There are NO refrigerant leaks.
The refrigerant pipes (gas and liquid) are thermally insulated.
The correct pipe size is installed and the pipes are properly insulated.
There is NO water leak inside the indoor unit.
The shut-off valves are properly installed and fully open.
The stop valves (gas and liquid) on the outdoor unit are fully open.
The air purge valve is open (at least 2 turns).
The pressure relief valve purges water when opened.
The minimum water volume is guaranteed in all conditions. See "To check the water volume" in
"6.4Preparing water piping"on page18.
The safety thermostat is connected.
INFORMATION
The software is equipped with an "installer-on-site" mode ([4‑0E]), that disables automatic operation by the unit. At first installation, setting [4‑0E] is by default set to "1", meaning automatic operation is disabled. All protective functions are then disabled. If the user interface home pages are off, the unit will NOT operate automatically. To enable automatic operation and the protective functions, set [4‑0E] to "0".
36 hours after the first power-on, the unit will automatically set [4‑0E] to "0", ending "installer-on-site" mode and enabling the protective functions. If – after first installation – the installer returns to the site, the installer has to set [4‑0E] to "1" manually.

9.4 Checklist during commissioning

The minimum flow rate during backup heater/defrost operation is guaranteed in all conditions. See "To check the water volume and flow rate" in "6.4Preparing water
piping"on page18.
To perform an air purge.
To perform a test run.
To perform an actuator test run.
Underfloor screed dryout function
The underfloor screed dryout function is started (if necessary).
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
63
Page 64
9 Commissioning

9.4.1 To check the minimum flow rate

Recommended procedure for the additional zone
1 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or other valves.
2 Close all space heating loops that can be closed (see previous
step).
3 Start the pump test run operation (see "9.4.4 To perform an
actuator test run"on page65).
4 Go to [6.1.8]: > Information > Sensor information > Flow rate
to check the flow rate. During pump test run operation, the unit can operate below this minimum required flow rate that is needed during defrost/backup heater operation.
Bypass valve foreseen?
Yes No
Modify the bypass valve setting to reach the minimum required flow rate + 2l/min
Recommended procedure for the main zone
5 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or other valves.
6 Close all space heating loops that can be closed (see previous
step).
7 Create a thermo request on the main zone only.
8 Wait 1 minute until the unit is stabilized.
9 If the additional pump is still assisting (the green LED on the
right hand sided pump is ON), increase the flow until the additional pump is NOT assisting anymore (LED is OFF).
10 Go to [6.1.8]: > Information > Sensor information > Flow rate
to check the flow rate.
Bypass valve foreseen?
Yes No
Modify the bypass valve setting to reach the minimum required flow rate + 2l/min
Minimum required flow rate during defrost/backup heater operation
04+08 models 12l/min
16 model 15l/min
In case the actual flow rate is below the minimum flow rate (required during defrost/backup heater operation), modifications at hydraulic configuration are required. Increase the space heating loops that can NOT be closed or install a pressure controlled bypass valve.
In case the actual flow rate is below the minimum flow rate (required during defrost/backup heater operation), modifications at hydraulic configuration are required. Increase the space heating loops that can NOT be closed or install a pressure controlled bypass valve.

9.4.2 Air purge function

When commissioning and installing the unit, it is very important to remove all air in the water circuit. When the air purge function is running, the pumps operate without actual operation of the unit and the removal of air in the water circuit will start.
NOTICE
Before starting the air purge, open the safety valve and check if the circuit is sufficiently filled with water. Only if water escapes the valve after opening it, you can start the air purge procedure.
There are 2 modes for purging air:
▪ Manually: the unit will operate with a custom pump speed and in a
custom position of the 3-way valve (space heating/domestic hot water). The custom position of the 3-way valve is a helpful feature to remove all air from the water circuit in the space heating or the domestic hot water heating mode. The operation speed of the pump (slow or quick) can also be set.
▪ Automatic: the unit automatically changes the pump speed and
the position of the 3-way valve (space heating/domestic hot water) between the space heating or the domestic hot water heating mode.
INFORMATION
For both manual and automatic air purge, 1 temperature zone is purged with each air purge start. To purge the other temperature zone, you have to restart the air purge function. When performing an air purge for the first time, the main temperature zone will be purged.
Typical workflow
Purging the air from the system should consist of:
1 Performing a manual air purge for both zones
2 Performing an automatic air purge for both zones
INFORMATION
Start by performing a manual air purge on both zones. When almost all the air is removed, perform an automatic air purge on both zones. If necessary, repeat performing the automatic air purge until you are sure that all air is removed from the system. During air purge function, pump speed limitation [9‑0D] is NOT applicable.
Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
To perform a manual air purge
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least 5°C higher than the actual water temperature inside the unit.
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page42.
2 Set the air purge mode: go to [A.7.3.1] > Installer settings >
Commissioning > Air purge > Type.
3 Select Manual and press .
4 Go to [A.7.3.4] > Installer settings > Commissioning > Air
purge > Start air purge and press to start the air purge function.
Result: The manual air purge starts and the following screen appears.
Installer reference guide
64
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 65
01:18
Tue
Air purge
l/min Low SHC
0.5
Flow rate Speed Circuit
Stop
Adjust
Scroll
01:18
Tue
Air purge
l/min Low SHC
0.5
Flow rate Speed Circuit
Stop
Adjust
Scroll
5 Use the and buttons to scroll to Speed.
6 Use the and buttons to set the desired pump speed.
Result: Low
Result: High
7 If applicable, set the desired position of the 3-way valve (space
heating/domestic hot water). Use the and buttons to scroll to Circuit.
8 Use the and buttons to set the desired position of the 3-way
valve (space heating/domestic hot water).
Result: SHC
Result: Tank
To perform an automatic air purge
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least 5°C higher than the actual water temperature inside the unit.
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page42.
2 Set the air purge mode: go to [A.7.3.1] > Installer settings >
Commissioning > Air purge > Type.
3 Select Automatic and press .
4 Go to [A.7.3.4] > Installer settings > Commissioning > Air
purge > Start air purge and press to start the air purge function.
Result: Air purging will start and the following screen will be shown.
The automatic air purge function stops automatically after 30minutes, then the installer has to restart the automatic air purge function for the second temperature zone. This function will also stop automatically after 30minutes
To interrupt air purge
1 Press and press to confirm the interruption of the air
purge function. When you restart the air purge function, the other zone will be air purged.

9.4.3 To perform a test run

INFORMATION
The test run only applies to the additional temperature zone.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
9 Commissioning
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page42.
2 Go to [A.7.1]: > Installer settings > Commissioning > Test
run.
3 Select a test and press . Example: Heating.
4 Select OK and press .
Result: The test run starts. It stops automatically when done
(±30min). To stop it manually, press , select OK and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
▪ The user interface used to start the test run displays a
status screen.
▪ The other user interface displays a "busy" screen. You
cannot use the user interface as long as the "busy" screen is shown.
If the installation of the unit has been done correctly, the unit will start up during test operation. During the test mode, the correct operation of the unit can be checked by monitoring leaving water temperature (heating mode) and tank temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information you want to check.

9.4.4 To perform an actuator test run

Purpose of the actuator test run is to confirm the operation of the different actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page42.
2 Make sure the room temperature control, the leaving water
temperature control and the domestic hot water control are turned OFF via the user interface.
3 Go to [A.7.4]: > Installer settings > Commissioning >
Actuator test run.
4 Select an actuator and press . Example: Pump.
5 Select OK and press .
Result: The actuator test run starts. It automatically stops when
finished. To stop it manually, press , select OK and press .
Possible actuator test runs
▪ Backup heater (step 1) test
▪ Pump test (only the pump of the additional temperature zone)
INFORMATION
Make sure that all air is purged before executing the test run. Also avoid disturbances in the water circuit during the test run.
▪ 2-way valve test
▪ 3-way valve test (3-way valve for switching between space
heating and tank heating)
▪ Bottom plate heater test
▪ Bivalent signal test
▪ Alarm output test
Installer reference guide
65
Page 66
9 Commissioning
t
T
A1
25°C (1) 35°C (2)
24h (1) 36h (2)
▪ Heating signal test
▪ Quick heat-up test
▪ Circulation pump test

9.4.5 Underfloor heating screed dryout

This function is used for drying out the screed of an underfloor heating system very slowly during the construction of a house. It allows the installer to program and execute this program.
Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
This function can be executed without finishing the outdoor installation. In this case, the backup heater will perform the screed dryout and supply the leaving water without heat pump operation.
When no outdoor unit is installed yet, then connect the main power supply cable to the indoor unit via X2M/30 and X2M/31. See
"7.9.9To connect the main power supply"on page37.
INFORMATION
NOTICE
The installer is responsible for:
NOTICE
To perform an underfloor heating screed dryout, room frost protection needs to be disabled ([2‑06]=0). By default, it is enabled ([2‑06]=1). However, due to the "installer-on-site" mode (see "Checklist before commissioning"), room frost protection will be automatically disabled for 36 hours after the first power-on.
If the screed dryout still needs to be performed after the first 36 hours of power-on, manually disable room frost protection by setting [2‑06] to "0", and KEEP it disabled until the screed dryout has finished. Ignoring this notice will result in cracking of the screed.
NOTICE
For the underfloor heating screed dryout to be able to start, make sure the following settings are met:
The installer can program up to 20 steps. For each step he needs to enter:
▪ If Emergency is set to Manual ([A.6.C]=0), and the unit
is triggered to start emergency operation, the user interface will ask confirmation before starting. The underfloor heating screed dryout function is active even if the user does NOT confirm emergency operation.
▪ During underfloor heating screed dryout, pump speed
limitation [9‑0D] is NOT applicable.
▪ contacting the screed manufacturer for the initial
heating instructions to avoid cracking the screed,
▪ programming the underfloor heating screed dryout
schedule according to the above instruction of the screed manufacturer,
▪ checking the proper functioning of the setup on a
regular basis,
▪ selecting the correct program complying with the type
of the used screed of the floor.
▪ [4‑00]=1
▪ [C‑02]=0
▪ [D‑01]=0
▪ [4‑08]=0
▪ [4‑01]≠1
1 the duration in hours, up to 72hours,
2 the desired leaving water temperature.
Example:
T Desired leaving water temperature (15~55°C)
t Duration (1~72h) (1) Action step 1 (2) Action step 2
To program an underfloor heating screed dryout schedule
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page42.
2 Go to [A.7.2]:
screed dryout > Set dryout schedule.
3 Use the
▪ Use ▪ Use
If a time is selected, you can set the duration between 1 and 72hours. If a temperature is selected, you can set the desired leaving water temperature between 15°C and 55°C.
4 To add a new step, select "–h" or "–" on an empty line and
press
5 To delete a step, set the duration to "–" by pressing
6 Press
.
to save the schedule.
It is important that there is no empty step in the program. The schedule will stop when a blank step is programmed OR when 20 consecutive steps have been executed.
> Installer settings > Commissioning > UFH
, , , and to program the schedule.
and to scroll through the schedule. and to adjust the selection.
.
To perform an underfloor heating screed dryout
INFORMATION
Preferential kWh rate power supply cannot be used in combination with underfloor heating screed dryout.
Prerequisite: Make sure there is ONLY 1 user interface connected to your system to perform an underfloor heating screed dryout.
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Go to [A.7.2]:
screed dryout.
2 Set a dryout program.
3 Select Start dryout and press
4 Select OK and press
Result: The underfloor heating screed dryout starts and following
screen will be shown. It stops automatically when done. To stop it manually, press
> Installer settings > Commissioning > UFH
.
.
, select OK and press .
Installer reference guide
66
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 67
15:10
1 14d 12h 25°C
Tue
Screed dryout
Current step
Remaining Desired LWT
Stop
To readout the status of an underfloor heating screed dryout
1 Press .
2 The current step of the program, the total remaining time, and
the current desired leaving water temperature will be displayed.
To interrupt an underfloor heating screed dryout
When the program is stopped by an error, an operation switch off, or a power failure, the U3 error will be displayed on the user interface. To resolve the error codes, see "12.4 Solving problems based on
error codes" on page 71. To reset the U3 error, your User
permission level needs to be Installer.
1 Go to the underfloor heating screed dryout screen.
2 Press .
3 Press to interrupt the program.
4 Select OK and press .
Result: The underfloor heating screed dryout program is stopped.
When the program is stopped due to an error, an operation switch­off, or a power failure, you can read out the underfloor heating screed dryout status.
5 Go to [A.7.2]: > Installer settings > Commissioning > UFH
screed dryout > Dryout status > Stopped at and followed by the last executed step.
6 Modify and restart the execution of the program.
10 Hand-over to the user
Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
▪ Fill in the installer setting table (in the operation manual) with the
actual settings.
▪ Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can find the complete documentation on the url as earlier described in this manual.
▪ Explain the user how to properly operate the system and what to
do in case of problems.
▪ Show the user what to do in relation to maintaining the unit.
▪ Explain the user about energy saving tips as described in the
operation manual.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
INFORMATION
There is limited access to the menu structure. Only the following menus can be accessed:
▪ Information.
▪ Installer settings > Commissioning > UFH screed
dryout.

10 Hand-over to the user

11 Maintenance and service

NOTICE
Maintenance must be done by an authorised installer or
service agent.
We recommend to do maintenance at least once a year.
However, applicable legislation might require shorter
maintenance intervals.
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO2-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

11.1 Overview: Maintenance and service

This chapter contains information about:
▪ The yearly maintenance of the outdoor unit
▪ The yearly maintenance of the indoor unit

11.2 Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE:Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB.

11.2.1 Opening the indoor unit

CAUTION
The front panel is heavy. Be careful NOT to jam your fingers when opening or closing the unit.
You just need to remove the front panel of the unit to gain access to most parts which need maintenance. In rare cases, you may also need to remove the switch box.

11.3 Checklist for yearly maintenance of the outdoor unit

Check the following at least once a year:
▪ Outdoor unit heat exchanger.
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt, leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat exchanger can lead to too low pressure or too high pressure leading to worse performance.

11.4 Checklist for yearly maintenance of the indoor unit

Check the following at least once a year:
▪ Water pressure
▪ Water filters
Installer reference guide
67
Page 68
11 Maintenance and service
1 3
2
5
4
2
×
▪ Water pressure relief valve
▪ Relief valve hose
▪ Pressure relief valve of the domestic hot water tank
▪ Switch box
▪ Descaling
▪ Chemical disinfection
▪ Anode
Water pressure
Check whether the water pressure is above 1bar. If it is lower, add water.
Water filters
Clean the water filters.
NOTICE
Handle the water filters with care. Do NOT use excessive force when you reinsert the water filters so as NOT to damage the water filters mesh.
Water pressure relief valve
Open the valve and check if it operates correctly. The water may be very hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does NOT contain dirt
anymore
▪ flush the system and install an additional water filter (a
magnetic cyclone filter is preferable).
To make sure this water originates from the tank, check after a tank heat up cycle.
It is recommended to do this maintenance more frequently.
Pressure relief valve hose
Check whether the pressure relief valve hose is positioned appropriately to drain the water. See "7.8.5To connect the pressure
relief valve to the drain"on page32.
Relief valve of the domestic hot water tank (field supply)
Open the valve and check the correct operation. Water may be very hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does not contain dirt
anymore
▪ flush and clean the complete tank, including the piping between
the relief valve and cold water inlet.
To make sure this water originates from the tank, check after a tank heat up cycle.
It is recommended to do this maintenance more frequently.
Switch box
▪ Carry out a thorough visual inspection of the switchbox and look
for obvious defects such as loose connections or defective wiring.
▪ Using an ohmmeter, check if contactors K1M, K2M and K3M
operate correctly. All contacts of these contactors must be in open position when the power is turned OFF.
WARNING
If the internal wiring is damaged, it has to be replaced by the manufacturer, its service agent or similarly qualified persons.
Descaling
Depending on water quality and set temperature, scale can deposit on the heat exchanger inside the domestic hot water tank and can restrict heat transfer. For this reason, descaling of the heat exchanger may be required at certain intervals.
Chemical disinfection
If the applicable legislation requires a chemical disinfection in specific situations, involving the domestic hot water tank, please be aware that the domestic hot water tank is a stainless steel cylinder containing an aluminium anode. We recommend to use a non­chloride based disinfectant approved for use with water intended for human consumption.
NOTICE
When using means for descaling or chemical disinfection, it must be ensured that the water quality remains compliant with EU directive 98/83EC.
Anode
No maintenance or replacement required.

11.4.1 To drain the domestic hot water tank

Prerequisite: Switch OFF the power supply.
Prerequisite: Turn OFF the cold water supply.
1 Open the front panel.
2 Remove the 2 screws, unhook and put the switch box aside.
3 The drain hose is located at the right side of the unit. Cut the tie
wraps or tape and bring the flexible drain hose forward.
Installer reference guide
68
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 69
a
a Drain hose
INFORMATION
To drain the tank, all the hot water tapping points need to be opened to allow air to enter the system.
4 Open the drain valve.
12 Troubleshooting

12.1 Overview: Troubleshooting

This chapter describes what you have to do in case of problems.
It contains information about:
▪ Solving problems based on symptoms
▪ Solving problems based on error codes
Before troubleshooting
Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.

12.2 Precautions when troubleshooting

WARNING
▪ When carrying out an inspection on the switch box of
the unit, always make sure that the unit is disconnected from the mains. Turn off the respective circuit breaker.
▪ When a safety device was activated, stop the unit and
find out why the safety device was activated before resetting it. NEVER bridge safety devices or change their values to a value other than the factory default setting. If you are unable to find the cause of the problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazard due to the inadvertent resetting of the thermal cut-out: this appliance must NOT be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF BURNING

12 Troubleshooting

12.3 Solving problems based on symptoms

12.3.1 Symptom: The unit is NOT heating as expected

Possible causes Corrective action
The temperature setting is NOT correct
The water flow is too low Check and make sure that:
The water volume in the installation is too low

12.3.2 Symptom: The compressor does NOT start (space heating or domestic water heating)

Possible causes Corrective action
The unit must start up out of its operation range (the water temperature is too low)
Check the temperature setting on the remote controller. Refer to the operation manual.
▪ All shut-off valves of the water
circuit are completely open.
▪ The water filters are clean.
Clean if necessary.
▪ There is no air in the system.
Purge air if necessary. You can purge air manually (see
"To perform a manual air purge"on page64) or use the
automatic air purge function (see "To perform an automatic
air purge"on page65).
▪ The water pressure is >1 bar.
▪ The expansion vessel is NOT
broken.
▪ The resistance in the water
circuit is NOT too high for the pump (see the ESP curve in the "Technical data" chapter).
If the problem persists after you have conducted all of the above checks, contact your dealer. In some cases, it is normal that the unit decides to use a low water flow.
Make sure that the water volume in the installation is above the minimum required value (see
"6.4.3To check the water volume and flow rate"on page19).
If the water temperature is too low, the unit uses the backup heater to reach the minimum water temperature first (15°C).
Check and make sure that:
▪ The power supply to the
backup heater is correctly wired.
▪ The backup heater thermal
protector is NOT activated.
▪ The backup heater contactor is
NOT broken.
If the problem persists after you have conducted all of the above checks, contact your dealer.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
69
Page 70
12 Troubleshooting
Possible causes Corrective action
The preferential kWh rate power supply settings and electrical connections do NOT match
The preferential kWh rate signal was sent by the electricity company
This should match with the connections as explained in
"6.5Preparing electrical wiring"on page21 and "7.9.9To connect the main power supply"on page37.
Wait for the power to return (2 hours max.).

12.3.3 Symptom: The pump is making noise (cavitation)

Possible causes Corrective action
There is air in the system Purge air manually on both
zones (see "To perform a manual
air purge"on page64) or use the
automatic air purge function on both zones (see "To perform an
automatic air purge"on page65).
The water pressure at the pump inlet is too low
Check and make sure that:
▪ The water pressure is >1bar.
▪ The manometer is not broken.
▪ The expansion vessel is NOT
broken.
▪ The pre-pressure setting of the
expansion vessel is correct (see "6.4.4 Changing the pre-
pressure of the expansion vessel"on page20).

12.3.4 Symptom: The pressure relief valve opens

Possible causes Corrective action
The expansion vessel is broken Replace the expansion vessel.
The water volume in the installation is too high
The water circuit head is too high The water circuit head is the
Make sure that the water volume in the installation is below the maximum allowed value (see
"6.4.3To check the water volume and flow rate"on page19 and "6.4.4Changing the pre-pressure of the expansion vessel"on page20).
difference in height between the indoor unit and the highest point of the water circuit. If the indoor unit is located at the highest point of the installation, the installation height is considered 0m. The maximum water circuit head is 10m.
Check the installation requirements.

12.3.5 Symptom: The water pressure relief valve leaks

Possible causes Corrective action
Dirt is blocking the water pressure relief valve outlet
Check whether the pressure relief valve works correctly by turning the red knob on the valve counterclockwise:
▪ If you do NOT hear a clacking
sound, contact your dealer.
▪ If the water keeps running out
of the unit, close both the water inlet and outlet shut-off valves first and then contact your dealer.

12.3.6 Symptom: The space is NOT sufficiently heated at low outdoor temperatures

Possible causes Corrective action
The backup heater operation is not activated
The backup heater equilibrium temperature has not been configured correctly
There is air in the system. Purge air manually or
Check and make sure that:
▪ The backup heater operation
mode is enabled. Go to:
▪ [A.5.1.1] > Installer settings
> Heat sources > Backup heater > Operation mode [4‑00]
▪ The backup heater overcurrent
fuse has not been turned off. If it has, check the fuse and turn it back on.
▪ The thermal protector of the
backup heater has not been activated. If it has, check the following, and then press the reset button in the switch box:
▪ The water pressure
▪ Whether there is air in the
system
▪ The air purge operation
Increase the "equilibrium temperature" to activate the backup heater operation at a higher outdoor temperature. Go to:
▪ [A.5.1.4] > Installer settings >
Heat sources > Backup heater > Equilibrium temp. OR
▪ [A.8] > Installer settings >
Overview settings [5‑01]
automatically. See the air purge function in the "Commissioning" chapter.
Installer reference guide
70
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 71
12 Troubleshooting
Possible causes Corrective action
Too much heat pump capacity is used for heating domestic hot water
Check and make sure that the "space heating priority" settings have been configured appropriately:
▪ Make sure that the "space
heating priority status" has been enabled. Go to [A.8] > Installer settings > Overview settings [5‑02]
▪ Increase the "space heating
priority temperature" to activate backup heater operation at a higher outdoor temperature. Go to [A.8] > Installer settings > Overview settings [5‑03]

12.3.7 Symptom: The pressure at the tapping point is temporarily unusually high

Possible causes Corrective action
Failing or blocked pressure relief valve.
▪ Flush and clean the complete
tank including the piping between pressure relief valve and the cold water inlet.
▪ Replace the pressure relief
valve.

12.3.8 Symptom: Decoration panels are pushed away due to a swollen tank

Possible causes Corrective action
Failing or blocked pressure relief valve.
Contact your local dealer.

12.3.9 Symptom: Tank disinfection function is NOT completed correctly (AH-error)

Possible causes Corrective action
The disinfection function was interrupted by domestic hot water tapping
Large domestic hot water tapping happened recently before the programmed start-up of the disinfection function
Program the start-up of the disinfection function when the coming 4hours NO domestic hot water tapping is expected.
When the Domestic hot water > Type > Reheat or Reheat + sched. is selected, it is recommended to program the start-up the disinfection function at least 4hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
When the Domestic hot water > Type > Scheduled only is selected, it is recommended to program a Storage eco 3hours before the scheduled start-up of the disinfection function to preheat the tank.
Possible causes Corrective action
The disinfection operation was stopped manually: with the user interface displaying the DHW home page and its user permission level set to Installer, the button was pressed during disinfection operation.
Do NOT press the button while the disinfection function is active.

12.4 Solving problems based on error codes

When a problem happens, an error code appears on the user interface. It is important to understand the problem and to take countermeasure before resetting the error code. This should be done by a licensed installer or by your local dealer.
This chapter gives you an overview of all error codes and the content of the error code as it appears on the user interface.
For a more detailed troubleshooting guideline for each error, please see the service manual.

12.4.1 Error codes: Overview

Error codes of the indoor unit
Error code Detailed error
code
7H 01 Water flow problem.
7H 04 Water flow problem during
7H 05 Water flow problem during
7H 06 Water flow problem during
80 00 Returning water temperature
81 01 Mixed water thermistor
81 00 Leaving water temperature
89 01 Heat exchanger frozen.
Description
Auto restart.
domestic hot water production.
Manual reset.
Check the domestic hot water circuit.
heating/sampling.
Manual reset.
Check the space heating circuit.
defrost.
Manual reset.
Check the plate heat exchanger.
sensor problem.
Please contact your dealer.
abnormality.
Auto reset.
sensor problem.
Please contact your dealer.
1
(1)
On the home screen of your user inter interface, the following information will be displayed:
Bi-zone kit abnormality
detection
Refer to bi-zone kit manual
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
71
Page 72
12 Troubleshooting
Error code Detailed error
Description
code
89 02 Heat exchanger frozen.
89 03 Heat exchanger frozen.
8F 00 Abnormal increase outlet
water temperature (DHW).
8H 00 Abnormal increase outlet
water temperature.
8H 01 Overheating mixed water circuit.
Auto reset.
1
8H 02 Overheating mixed water circuit
(thermostat).
Auto reset.
1
8H 03 Overheating water circuit
(thermostat).
A1 00 Zero cross detection problem.
Power reset required.
Please contact your dealer.
A1 01 EEPROM reading error.
Error code Detailed error
Description
code
H1 00 External temperature
sensor problem.
Please contact your dealer.
HC 00 Tank temperature sensor
problem.
Please contact your dealer.
U3 00 Under floor heating screed
dryout function not completed
correctly.
U4 00 Indoor/outdoor unit
communication problem.
U5 00 User interface
communication problem.
U8 01 Connection with adapter lost
Please contact your dealer.
UA 00 Indoor unit, outdoor unit
matching problem.
Power reset required.
UA 16 Extension/hydro
communication problem.
AA 01 Backup heater overheated.
Power reset required.
Please contact your dealer.
AH 00 Tank disinfection function not
completed correctly.
AJ 03 Too long DHW heat-up time
required.
C0 00 Flow sensor malfunction.
Manual reset.
C4 00 Heat exchanger temperature
sensor problem.
Please contact your dealer.
CJ 02 Room temperature sensor
problem.
Please contact your dealer.
EC 00 Abnormal increase tank
temperature.
UA 17 Tank type problem
UA 21 Extension/hydro
mismatch problem.
INFORMATION
In case of error code AH and no interruption of the disinfection function occurred due to domestic hot water tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to program the start-up of the disinfection function at least 4 hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage eco 3 hours before the scheduled start-up of the disinfection function to preheat the tank.
(1)
On the home screen of your user inter interface, the following information will be displayed:
Bi-zone kit abnormality
detection
Refer to bi-zone kit manual
Installer reference guide
72
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 73

13 Disposal

NOTICE
When the minimum water flow is lower than described in the table below, the unit will temporarily stop operation and the user interface will display error 7H‑01. After some time, this error will reset automatically and the unit will resume operation.
Minimum required flow during heat pump operation
04 models 6l/min
08 models 6l/min
16 models 10l/min
Minimum required flow during defrost operation
04+08 models 12l/min
16 models 15l/min
Minimum required flow during backup heater operation
All models 12l/min
If the 7H-01 error persists, the unit will stop operation and the user interface will display an error code that needs to be reset manually. Depending on the problem, this error code is different:
Error code Detailed error
code
7H 04 The water flow problems mainly
7H 05 The water flow problems mainly
7H 06 The water flow problems mainly
INFORMATION
Error AJ-03 is reset automatically from the moment there is a normal tank heat-up.
INFORMATION
If the unit detects flow when the pump is not running, an external device might be causing flow, or there might be something wrong with the flow measuring devices (flow sensor).
▪ If the flow sensor detects flow when the pump is not
running, the unit will stop operation and the user interface will display error C0‑00. For the unit to resume operation, this error needs to be reset manually.
Description
occurred during domestic hot water operation. Check the domestic hot water circuit.
occurred during space heating operation. Check the space heating circuit.
occurred during defrost operation. Check the space heating circuit.
Additionally, this error code might be an indication of frost damage to the plate heat exchanger. In that case, contact your local dealer.
13 Disposal
NOTICE
Do not try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, oil and other parts must comply with applicable legislation. Units must be treated at a specialised treatment facility for reuse, recycling and recovery.

13.1 Overview: Disposal

Typical workflow
Disposing of the system typically consists of the following stages:
1 Pumping down the system.
2 Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.

13.2 About pump down

The unit is equipped with an automatic pump down function, with which you can collect all refrigerant from the system into the outdoor unit.
NOTICE
The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by turning it OFF. NEVER short-circuit the low pressure switch during pump down operation.
Before pumping down
NOTICE
Before you pump down, make sure the water temperature (example: by performing a heating operation) and water volume (example: by opening all heat emitters) are sufficiently high. Pump down is done in cooling mode.

13.3 To pump down

DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
1 Turn ON the main power supply switch.
2 Make sure the liquid stop valve and the gas stop valve are
open.
3 Press the pump down button (BS4) for at least 8 seconds. BS4
is located on the PCB in the outdoor unit (see wiring diagram).
Result: The compressor and outdoor unit fan start automatically.
4 Once operation stops (after 3~5 minutes), close the liquid stop
valve and the gas stop valve.
Result: The pump down operation is finished. The user interface may display " " and the indoor pump may continue operating. This is NOT a malfunction. Even if you press the ON button on the user interface, the unit will NOT start. To restart the unit, turn OFF the main power supply switch and turn it ON again.
5 Turn OFF the main power supply switch.
NOTICE
Make sure to reopen both stop valves before restarting the unit.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
73
Page 74

14 Technical data

R2T
R4T
R6T
R1T
e
d
g
f
a
c
c
b
e
Y1E
Y1S
M1F-M2F
M1C
E1HC
S1NPH
S1PH
R5T
R3T
3TW57765-1A
R2T
R3T
R6T
e
d
g
f
h
a
c
c
b
e
Y1E
Y3S
Y1S
M1F-M2F
M1C
E1HC
S1NPH
S1PH
R1T
R4T
R5T
3TW57915-1A
R2T
R3T
R6T
e
d
g
f
a
c
c
b
e
Y1E
Y3S
Y3E
Y1S
M1F-M2F
M1C
E1HC
S1NPH
S1PH
h
R1T
R4T
R5T
3TW60335-1A
e
14 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required).

14.1 Piping diagram: Outdoor unit

ERHQ_V3
a Field piping (liquid: Ø9.5 flare connection) b Field piping (gas: Ø15.9 flare connection) c Stop valve (with service port 5/16") d Accumulator e Filter
f Heat exchanger
g Internal service port 5/16"
E1HC Crankcase heater
M1C Motor (compressor)
M1F‑M2F Motor (upper and lower fan)
R1T Thermistor (air) R2T Thermistor (discharge) R3T Thermistor (suction) R4T Thermistor (heat exchanger) R5T Thermistor (heat exchanger middle) R6T Thermistor (liquid)
S1NPH Pressure sensor
S1PH High pressure switch
Y1E Electronic expansion valve Y1S Solenoid valve (4‑way valve)
Heating Cooling
ERHQ_W1
a Field piping (liquid: Ø9.5 flare connection) b Field piping (gas: Ø15.9 flare connection) c Stop valve (with service port 5/16") d Accumulator e Filter
f Heat exchanger g Internal service port 5/16" h Capillary tube
E1HC Crankcase heater
M1C Motor (compressor)
M1F‑M2F Motor (upper and lower fan)
R1T Thermistor (air) R2T Thermistor (discharge) R3T Thermistor (suction) R4T Thermistor (heat exchanger) R5T Thermistor (heat exchanger middle) R6T Thermistor (liquid)
S1NPH Pressure sensor
S1PH High pressure switch
Y1E Electronic expansion valve Y1S Solenoid valve (4‑way valve) Y3S Solenoid valve (injection)
Heating Cooling
ERLQ
a Field piping (liquid: Ø9.5 flare connection) b Field piping (gas: Ø15.9 flare connection) c Stop valve (with service port 5/16") d Accumulator e Filter
f Heat exchanger g Internal service port 5/16" h Capillary tube
E1HC Crankcase heater
M1C Motor (compressor)
Installer reference guide
74
M1F‑M2F Motor (upper and lower fan)
R1T Thermistor (air) R2T Thermistor (discharge) R3T Thermistor (suction) R4T Thermistor (heat exchanger) R5T Thermistor (heat exchanger middle) R6T Thermistor (liquid)
S1NPH Pressure sensor
S1PH High pressure switch
Y1E Electronic expansion valve (main) Y3E Electronic expansion valve (injection) Y1S Solenoid valve (4‑way valve) Y3S Solenoid valve (hot gas pass)
Heating Cooling
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 75

14.2 Piping diagram: Indoor unit

Field installed
M
M
3D096028-1A
R1T
R4T
R3T
R2T
R5T
R7T
A
A
1
7
7
26
12
14
18
9
21
2
5
6
4
3
13
27
16
19
20
17
10
28
22
23
8
8
29
15
11
24
28
Refrigerant inlet
Refrigerant outlet
Refrigerant side
Water side
Field installed
14 Technical data
1 Space heating – water OUT (additional/direct zone) 2 Space heating – water IN (additional/direct zone) 3 Space heating – water OUT (main/mixed zone) 4 Space heating – water IN (main/mixed zone) 5 Domestic hot water: hot water out 6 Domestic hot water: cold water in 7 Shut-off valve with drain/fill valve 8 Shut-off valve
9 Flow sensor 10 3-way valve (space heating/domestic hot water) 11 3-way valve (mixing valve for the main/mixed zone) 12 Water filter (additional/direct zone) 13 Water filter (main/mixed zone) 14 Pump (additional/direct zone) 15 Pump (main/mixed zone) 16 Backup heater 17 Safety valve 18 Plate heat exchanger 19 R1T – Outlet water heat exchanger thermistor 20 R2T – Outlet water backup heater thermistor 21 R3T – Thermistor (heat exchanger, liquid pipe) 22 R4T – Inlet water thermistor 23 R5T – Tank thermistor 24 R7T – Water outlet thermistor (main/mixed zone) 26 Expansion vessel 27 Air purge 28 Check valve 29 Capillary tube
Screw connection Flare connection
Quick coupling
Brazed connection
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
75
Page 76
14 Technical data

14.3 Wiring diagram: Outdoor unit

The wiring diagram is delivered with the unit, located at the inside of the service cover.
Notes:
1 This wiring diagram applies only to the outdoor unit.
2 Symbols (see below).
3 Symbols (see below).
4 Refer to the option manual for connecting wiring to X6A and
X77A.
5 Refer to the wiring diagram sticker (on the back of the service
cover) for how to use the BS1~BS4 and DS1 switches.
6 When operating, do not short-circuit protective device S1PH.
7 Colours (see below).
8 Refer to the service manual for instructions on how to set the
selector switches (DS1). The factory setting of all switches is OFF.
9 Symbols (see below).
Symbols:
L Live
N Neutral
Field wiring
Terminal strip
Connector
Connector
Connection
Protective earth (screw)
Noiseless earth
Terminal
Option
Wiring dependent on model
Colours:
BLK Black
BLU Blue
BRN Brown
GRN Green
ORG Orange
RED Red
WHT White
YLW Yellow
Legend:
A1P~A4P Printed circuit board
BS1~BS4 Push button switch
C1~C4 Capacitor
DS1 DIP switch
E1H Bottom plate heater
E1HC Crankcase heater
F1U~F8U
(ERHQ_V3 + ERLQ_V3)
▪ F1U, F3U, F4U: Fuse (T 6.3 A /
250V)
▪ F6U: Fuse (T 5.0A / 250V)
▪ F7U, F8U: Fuse (F 1.0A / 250V)
F1U~F9U
(ERHQ_W1 + ERLQ_W1)
H1P~H7P (A2P)
(ERHQ_V3 + ERLQ_V3)
H1P~H7P (A1P)
(ERHQ_W1 + ERLQ_W1)
HAP (A1P)
(ERHQ_V3 + ERLQ_V3)
HAP (A1P, A2P)
(ERHQ_W1 + ERLQ_W1)
K1M, K2M
(ERHQ_W1 + ERLQ_W1)
K1R~K4R Magnetic relay
K10R, K11R
(ERHQ_V3 + ERLQ_V3)
L1R~L4R Reactor
M1C Motor (compressor)
M1F Motor (upper fan)
M2F Motor (lower fan)
PS Switching power supply
Q1DI Earth leakage circuit breaker (field
R1~R4 Resistor
R1T Thermistor (air)
R2T Thermistor (discharge)
R3T Thermistor (suction)
R4T Thermistor (heat exchanger)
R5T Thermistor (heat exchanger middle)
R6T Thermistor (liquid)
R7T
(ERHQ_W1 + ERLQ_W1)
R10T
(ERHQ_V3 + ERLQ_V3)
RC
(ERHQ_V3 + ERLQ_V3)
S1NPH Pressure sensor
S1PH High pressure switch
TC
(ERHQ_V3 + ERLQ_V3)
V1R
(ERHQ_V3 + ERLQ_V3)
V1R, V2R
(ERHQ_W1 + ERLQ_W1)
V2R, V3R
(ERHQ_V3 + ERLQ_V3)
V3R
(ERHQ_W1 + ERLQ_W1)
▪ F1U, F2U: Fuse (31.5A / 500V)
▪ F3U~F6U: Fuse (T 6.3A / 250V)
▪ F7U: Fuse (T 5.0A / 250V)
▪ F8U, F9U: Fuse (F 1.0A / 250V)
Light‑emitting diode (service monitor orange)
H2P:
▪ Prepare, test: Flickering
▪ Malfunction detection: Light up
Light‑emitting diode (service monitor orange)
Light‑emitting diode (service monitor green)
Light‑emitting diode (service monitor green)
Magnetic contactor
Magnetic relay
supply)
Thermistor (fin)
Thermistor (fin)
Signal receiver circuit
Signal transmission circuit
Power module
Power module
Diode module
Diode module
Installer reference guide
76
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 77
14 Technical data
15
**
/12.2
1
V1T
(ERHQ_V3 + ERLQ_V3)
X1M Terminal strip (power supply)
X1Y Connector (option for ERHQ: bottom
X6A Connector (option)
X77A
(ERHQ_W1 + ERLQ_W1)
Y1E Expansion valve (main)
Insulated gate bipolar transistor (IGBT)
plate heater)
Connector (option)
Y3E
(ERLQ)
Y1S Solenoid valve (4‑way valve)
Y3S
(ERHQ_W1)
Y3S
(ERLQ)
Z1C~Z9C Noise filter
Z1F~Z4F Noise filter
Expansion valve (injection)
Solenoid valve (injection)
Solenoid valve (hot gas pass)

14.4 Wiring diagram: Indoor unit

See the internal wiring diagram supplied with the unit (on the inside of the indoor unit switch box cover). The abbreviations used are listed below.
Notes to go through before starting the unit
English Translation
Notes to go through before starting the unit
X1M Main terminal
X2M Field wiring terminal for AC
X5M Field wiring terminal for DC
User installed options User installed options
Domestic hot water tank Domestic hot water tank
Remote user interface Remote user interface
Ext. indoor thermistor External indoor thermistor
Ext outdoor thermistor External outdoor thermistor
Digital I/O PCB Digital I/O PCB
Demand PCB Demand PCB
Bottom plate heater Bottom plate heater
Main LWT Main leaving water temperature
On/OFF thermostat (wired) On/OFF thermostat (wired)
On/OFF thermostat (wireless) On/OFF thermostat (wireless)
Ext. thermistor External thermistor
Heat pump convector Heat pump convector
Safety thermostat Safety thermostat
Add LWT Additional leaving water
On/OFF thermostat (wired) On/OFF thermostat (wired)
On/OFF thermostat (wireless) On/OFF thermostat (wireless)
Ext. thermistor External thermistor
Heat pump convector Heat pump convector
Position in switch box
English Translation
Position in switch box Position in switch box
Notes to go through before starting the unit
Earth wiring
Wire number 15
Field supply
Connection ** continues on page 12 column 2
Several wiring possibilities
Option
Not mounted in switch box
Wiring depending on model
PCB
temperature
Legend
A1P Main PCB
A2P User interface PCB
A3P * On/OFF thermostat (PC=power circuit)
A3P * Heat pump convector
A4P * Digital I/O PCB
A4P * Receiver PCB (Wireless On/OFF
thermostat)
A5P Bizone PCB
A6P Current loop PCB
A7P Anode driver PCB
A8P * Demand PCB
B1L Flow sensor
DS1 (A5P) DIP switch
DS1 (A8P) DIP switch
E1A Electrical anode
E3H Backup heater element (3kW)
F1B Overcurrent fuse backup heater
F1T Thermal fuse backup heater
F1U (A4P) * Fuse 5A 250V for digital I/O PCB
F2U (A4P) * Fuse 5A 250V for digital I/O PCB
F1U (A5P) Fuse T 2A 250V for PCB
F2U (A5P) Fuse T 2A 250V for PCB
FU1 (A1P) Fuse T 6.3A 250V for PCB
K1M Contactor backup heater
K2M Relay 3-way valve bypass
K3M Relay 3-way valve flow
K*R (A1P, A4P) Relay on PCB
M1P Additional zone pump
M2P # Domestic hot water pump
M3P Main zone pump
M1S Mixing 3-way valve
M2S # 2-way valve for cooling mode
M3S 3-way valve for space heating/domestic hot
water
PC (A4P) Power circuit
PHC1 (A4P) * Optocoupler input circuit
Q*DI # Earth leakage circuit breaker
Q1L Thermal protector backup heater
Q3L # Safety thermostat
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
77
Page 78
14 Technical data
R1H (A3P) * Humidity sensor
R1T (A1P) Outlet water heat exchanger thermistor
R1T (A2P) Ambient sensor user interface
R1T (A3P) * Ambient sensor On/OFF thermostat
R2T (A1P) Outlet backup heater thermistor
R2T (A3P) * External sensor (floor or ambient)
R3T Refrigerant liquid side thermistor
R4T Inlet water thermistor
R5T Domestic hot water thermistor
R6T * External indoor or outdoor ambient
thermistor
R7T Mixed leaving water thermistor
S1S # Preferential kWh rate power supply contact
S2S # Electrical meter pulse input 1
S3S # Electrical meter pulse input 2
S4S # Safety thermostat
S6S~S9S # Digital power limitation inputs
SS1 (A4P) * Selector switch
TR1 Power supply transformer
CN1-2, X*A
X*H, X*Y
X*M Terminal strip
Translation of text on wiring diagram
English Translation
3 wire type SPST 3 wire type SPST
Add. LWT zone Additional leaving water
Alarm output Alarm output
Anode Anode
Continuous Continuous current
Demand PCB Demand PCB
DHW pump Domestic hot water pump
DHW pump output Domestic hot water pump output
Digital I/O PCB Digital I/O PCB
Electric pulse meter inputs: 12 V DC pulse detection (voltage supplied by PCB)
Ext. ambient sensor option (indoor or outdoor)
Ext. heat source External heat source
For preferential kWh rate power supply
For safety thermostat For safety thermostat
Heat pump convector Heat pump convector
Connector
* = Optional
# = Field supply
temperature zone
Electric pulse meter inputs: 12 V DC pulse detection (voltage supplied by PCB)
External ambient sensor option (indoor or outdoor)
For preferential kWh rate power supply
English Translation
Indoor unit supplied from outdoor Indoor unit supplied from outdoor
Inrush Inrush current
Main LWT zone Main leaving water temperature
zone
Max. load Maximum load
Min. load Minimum load
NC valve Normal closed valve
NO valve Normal open valve
Normal kWh rate power supply Normal kWh rate power supply
Only for *** Only for ***
Only for demand PCB option Only for demand PCB option
Only for digital I/O PCB option Only for digital I/O PCB option
Only for ext. sensor (floor or ambient)
Only for normal power supply (standard)
Only for preferential kWh rate power supply (outdoor)
Only for wired On/OFF thermostat
Only for wireless On/OFF thermostat
Only if no *** Only if no ***
Options: boiler output, alarm output
Options: bottom plate heater OR On/OFF output
Outdoor unit Outdoor unit
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage supplied by PCB)
Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB)
Remote user interface Remote user interface
Safety thermostat Safety thermostat
Safety thermostat contact: 16 V DC detection (voltage supplied by PCB)
Shut-off valve Shut-off valve
Space C/H On/OFF output Space cooling/heating On/OFF
Switch box Switch box
To bottom plate heater To bottom plate heater
Use normal kWh rate power supply for indoor unit
User interface User interface
Only for external sensor (floor or ambient)
Only for normal power supply (standard)
Only for preferential kWh rate power supply (outdoor)
Only for wired On/OFF thermostat
Only for wireless On/OFF thermostat
Options: boiler output, alarm output
Options: bottom plate heater OR On/OFF output
Power limitation digital inputs: 12VDC / 12mA detection (voltage supplied by PCB)
Preferential kWh rate power supply contact: 16VDC detection (voltage supplied by PCB)
Safety thermostat contact: 16VDC detection (voltage supplied by PCB)
output
Use normal kWh rate power supply for indoor unit
Installer reference guide
78
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 79
Electrical connection diagram
X1Y: 1-2
X1M: 1-2-3
X1M: 1-2-3
A4P:Y2 X2M:29
2x0.75
X2M: 30-31
X5M: 3-4
1
1
A4P: Y1
X2M: 29
230 V
A4P: X1-X2
230 V
230 V
230 V
A4P: X1M: H-C-com X2M: L-N
A3P: X1M: 1-3
R2T
230 V
X11M : 5-6
X5M: 1-2
2x0.75
2x0.75
X2M: 34-35
230 V
X5M: 5-6
X5M: 7-8
X5M: 9-10
A8P: X801M: 1-5
A8P: X801M: 2-5
A8P: X801M: 3-5
A8P: X801M: 4-5
230 V
A4P: Y2
X2M: 29
2
2
2
X5M: 11-12
2
2
4D096036A
A3P: X1M: C-com-H
Only for *KRP1HB*
Field supply
communication
External sensor (floor or ambient)
external thermistor (indoor or outdoor)
Only for KRCS01-1 or EKRSCA1
2way valve
Bottom plate heater
Only for *KBPHT* & depending on model
X1M: L1-L2-L3-N-earth or L-N-earth
2 core
3 core
Indoor unit
Notes:
- In case of signal cable: keep minimum distance to power cables > 5 cm
Outdoor unit
Cooling/heating On/OFF output
Electricity meter pulse input 2
Electricity meter pulse input 1
Circulation pump for DHW
M2S (*KHBX units) for cooling mode
Ext. heat source (eg boiler)
alarm indication
2 core
2 core signal
2 core signal
signal
2 core
2 core
2 core
signal
2 core
2 core
Only for *KRTW (wired room thermostat)
External room thermostat / Heat pump convector (main and/or additional zone)
Optional part
Only for *KRTR (wireless room thermostat)
Only for *KRTETS
2 core (3m included)
signal
2 core
2 core
4 core for H only operation
5 core for C/H operation
2 core for H only operation
3 core for C/H operation
Only for (heat pump convector)
signal
2 core
signal
2 core
signal
2 core
signal
2 core
Power limitation demand input 4
Power limitation demand input 3
Power limitation demand input 2
Power limitation demand input 1
Field supply
Standard part
Optional part
A2P: P1-P2 user interface
A2P: P1-P2 user interface
Only for *KRUCBL*
communication
2 core
main: X2M: 1-4 add: X2M: 1a-4
main: X2M: 1-2-3-4
add: X2M: 1a-2a-3-4
main: X2M: 1-2-4
add: X2M: 1a-2a-4
NO valve: X2M: 6-7 NC valve: X2M: 5-7
Cooling/heating
On/OFF output
Changeover to
ext. heat source output
Alarm output
Only for *KRP1AHTA
F1B: L-N + earth
2 core signal
Safety thermostat
Field supply
Field supply
3 core
backup heater power supply (3 kW): 230 V + earth
Safety thermostat
normal kWh rate power supply for indoor unit: 230 V
unit preferential kWh rate power supply: 400 V or 230 V + earth
Only for preferential kWh rate power supply installation
5 or 3 core
2x0.75
2 core
2 core
5 or 3 core
unit power supply: 400 V or 230 V + earth
Only for normal power supply installation
Standard part
Power supply
For more details, please check the unit wiring.
14 Technical data

14.5 ESP curve: Indoor unit

Note: A flow error will occur when the minimum water flow rate is not
reached.
ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
79
Page 80
14 Technical data
80
70
60
50
30
40
20
10
0
0 5 10 15 20 25 30 35 40
45
A
B
C
4D097421-1
EHVZ16S18CB
A External static pressure (kPa) B Water flow rate (l/min) C Operation range
Additional/direct zone Main/mixed zone
Operation area is extended to lower flow rates only in case the unit operates with heat pump only. (Not in startup, no backup heater operation, no defrost operation).
ESP=External static pressure [kPa] in the space heating circuit.
Flow=Water flow through the unit in the space heating circuit.
Notes:
▪ Selecting a flow outside the area of operation can cause damage
or malfunction of the unit. See also the minimum and maximum allowed water flow range in the technical specifications.
▪ Water quality MUST be according to EN directive EC98/83EC.
Installer reference guide
80
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1B – 2017.04
Page 81
15 Glossary
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply
Equipment not made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.

15 Glossary

ERHQ+ERLQ011~016 + EHVZ16S18CB Daikin Altherma – Low temperature split 4P401677-1B – 2017.04
Installer reference guide
81
Page 82
1/8
Field settings table
[6.8.2] = .... ID66F2
Applicable indoor units
*HVZ04S18CB3V *HVZ08S18CB3V *HVZ16S18CB3V
Notes
(*5) *04/08* (*6) *16*
4P401673-1A - 2017.04
Page 83
2/8
Page 84
3/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1 R/W [3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2 R/W [3-07]~[3-06], step: A.3.2.4
19°C
└─ LWT main
7.4.2.1 [8-09] R/W [9-01]~[9-00], step: 1°C
35°C
7.4.2.2 [8-0A] R/W [9-01]~[9-00], step: 1°C
33°C
7.4.2.5 R/W -10~10°C, step: 1°C
0°C
7.4.2.6 R/W -10~10°C, step: 1°C
-2°C
└─ Tank temperature
7.4.3.1 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
7.4.3.2 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
7.4.3.3 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
└─ Quiet level
7.4.4 R/W
0: Level 1 (*6) 1: Level 2 (*5)
2: Level 3
└─ Electricity price
7.4.5.1 [C-0C] [D-0C]
R/W 0,00~990/kWh
0/kWh
7.4.5.2 [C-0D] [D-0D]
R/W 0,00~990/kWh
0/kWh
7.4.5.3 [C-0E] [D-0E]
R/W 0,00~990/kWh
0/kWh
└─ Fuel price
7.4.6 R/W 0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1 [1-00] Set weather-dependent heating Low ambient temp. for LWT main zone heating
WD curve.
R/W -40~5°C, step: 1°C
-10°C
7.7.1.1 [1-01] Set weather-dependent heating High ambient temp. for LWT main zone heating
WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.1.1 [1-02] Set weather-dependent heating Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
35°C
7.7.1.1 [1-03] Set weather-dependent heating Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
└─ Additional
└────────────────── Set weather-dependent heating
7.7.2.1 [0-00] Set weather-dependent heating Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
7.7.2.1 [0-01] Set weather-dependent heating Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W [9-05]~[9-06]°C, step: 1°C
45°C
7.7.2.1 [0-02] Set weather-dependent heating High ambient temp. for LWT add zone heating
WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.2.1 [0-03] Set weather-dependent heating Low ambient temp. for LWT add zone heating
WD curve.
R/W -40~5°C, step: 1°C
-10°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1 [E-00] R/O 0~5
0: LT s
p
lit
A.2.1.2 [E-01] R/O
0: 8 (*5) 1: 16
(*6)
A.2.1.3 [E-02] R/O
1: T
yp
e 2
A.2.1.4 [E-03] R/O
1: 1 ste
p
A.2.1.5 [5-0D] R/O
1: 1P,
(
1/1+2
)
A.2.1.6 [D-01] R/W
0: No
1: Open tariff 2: Closed tariff 3: Thermostat
A.2.1.7 [C-07] R/W 0: LWT control
1: Ext RT control
2: RT control
A.2.1.8 [7-02] R/W 0: 1 LWT zone
1: 2 LWT zones
A.2.1.9 [F-0D] R/W 0: Continuous
1: Sample
2: Re
q
ues
t
A.2.1.A [E-04] R/O
0: No (*6) 1: Yes
(*5)
A.2.1.B R/W 0: At unit
1: In room
└─ Options
A.2.2.1 [E-05] R/W
0: No
1: Yes
A.2.2.3 [E-07] R/O 0~6
1: T
yp
e 2
A.2.2.4 [C-05] R/W 1: Thermo ON/OFF
2: C/H re
q
ues
t
A.2.2.5 [C-06] R/W 1: Thermo ON/OFF
2: C/H re
q
ues
t
A.2.2.6.1 [C-02] Digital I/O PCB Ext. backup heat src R/W
0~3
0: No
1: Bivalent
A.2.2.6.2 [D-07] Digital I/O PCB Solar kit R/O
0~1
0: No
A.2.2.6.3 [C-09] Digital I/O PCB Alarm output R/W
0: Normally open
1: Normall
y
closed
A.2.2.6.4 [F-04] Digital I/O PCB Bottom plate heater R/W
0: No
1: Yes
A.2.2.7 [D-04] R/W
0: No
1: Pwr consm
p
ctrl
Forced off contact
Contact type add.
Demand PCB
Pump operation mode
Power saving possible
User interface location
DHW operation
DHW tank type
Contact type main
Indoor software type Backup heater steps BUH type
Unit control method
Number of LWT zones
High
Medium
Low
Unit type
Compressor type
Comfort (heating)
Eco (heating)
Storage comfort
Storage eco
Reheat
Field settings table
Installer setting at variance with default value
Comfort (heating)
Eco (heating)
Comfort (heating)
Eco (heating)
(*5) *04/08*_ (*6) *16*
4P401673-1A - 2017.04
Page 85
4/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
A.2.2.8 [D-08] R/W
0: No
1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000
p
ulse/kWh
A.2.2.9 [D-09] R/W
0: No
1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000
p
ulse/kWh
A.2.2.A [D-02] R/W
0~4
0: No
1: Secondary rtrn 2: Disinf. shunt
A.2.2.B [C-08] R/W
0: No
1: Outdoor sensor 2: Room sensor
└─ Capacities
A.2.3.2 [6-03] R/W 0~10 kW, step: 0,2 kW
3 kW
A.2.3.6 [6-07] R/W 0~200 W, step: 10 W
0 W
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1 R/W 0: Fixed
1: Weather dep.
2: Fixed + scheduled 3: WD + scheduled
A.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.1.2.2 [9-00] Temperature range Maximum temp (heating) R/W 37~55, step: 1°C
55°C
A.3.1.1.5 [8-05] R/W
0: No
1: Yes
A.3.1.1.6.1 [F-0B] Shut-off valve Thermo On/OFF R/W
0: No
1: Yes
A.3.1.1.7 [9-0B] R/W 0: Quick
1: Slo
w
└────────────────── Additional
A.3.1.2.1 R/W 0: Fixed
1: Weather dep.
2: Fixed + scheduled 3: WD + scheduled
A.3.1.2.2.1 [9-05] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) R/W 37~55, step: 1°C
55°C
└────────────────── Delta T source
A.3.1.3.1 [9-09] R/W 3~10°C, step: 1°C
5°C
└─ Room thermostat
A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) R/W 12~18°C, step: A.3.2.4
12°C
A.3.2.1.2 [3-06] Room temp. range Maximum temp (heating) R/W 18~30°C, step: A.3.2.4
30°C
A.3.2.2 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.3 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.4 R/W 0: 0,5 °C
1: 1 °C
└─ Operation range
14~35°C, step: 1°C
25°C
(*5)
14~35°C, step: 1°C
35°C
(*6)
└─ Domestic hot water (DHW)
└─ Type
A.4.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
└─ Disinfection
A.4.4.1 [2-01] R/W 0: No
1: Yes
A.4.4.2 [2-00] R/W 0: Each day
1: Monday 2: Tuesday 3: Wednesday 4: Thursday
5: Friday
6: Saturday 7: Sunda
y
A.4.4.3 [2-02] R/W 0~23 hour, step: 1 hour
23
A.4.4.4 [2-03] R/W
60°C
A.4.4.5 [2-04] R/W 40~60 min, step: 5 min
40 min
└─ Maximum setpoint
A.4.5 [6-0E] R/W 40~60°C, step: 1°C
60°C
└─ SP mode
A.4.6 R/W
0: Fixed
1: Weather de
p
.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve Leaving water value for high ambient temp. for
DHW WD curve.
R/W 35~[6-0E]°C, step: 1°C
55°C
A.4.7 [0-0C] Weather-dependent curve Leaving water value for low ambient temp. for
DHW WD curve.
R/W 45~[6-0E]°C, step: 1°C
60°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C
Start time
Temperature target Duration
R/W
Disinfection
Operation day
Heating
Room temp. offset
Ext. room sensor offset
Room temp. step
A.3.3.1 [4-02] Space heating OFF temp
BUH: step 1
Bottom plate heater
LWT setpoint mode
Modulated LWT
Emitter type
LWT setpoint mode
External kWh meter 1
External kWh meter 2
DHW pump
External sensor
4P401673-1A - 2017.04
(*5) *04/08*_
(*6) *16*
Page 86
5/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
└─ Heat sources
└─ Backup heater
A.5.1.1 [4-00] R/W 0~2
0: Disabled
1: Enabled
A.5.1.4 [5-01] R/W -15~35°C, step: 1°C
0°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Preferential kWh rate
A.6.2.1 [D-00] R/W
0~3
0: None
2: BUH onl
y
A.6.2.2 [D-05] R/W 0: Forced off
1: As normal
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous 2: Di
g
ital inputs
A.6.3.2 [4-09] R/W 0: Current
1: Powe
r
A.6.3.3 [5-05] R/W 0~50 A, step: 1 A
50
A
A.6.3.4 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.3 [5-07] Amp. limits for DI Limit DI3 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.4 [5-08] Amp. limits for DI Limit DI4 R/W 0~50 A, step: 1 A
50
A
A.6.3.6.1 [5-09] kW limits for DI Limit DI1 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2 [5-0A] kW limits for DI Limit DI2 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3 [5-0B] kW limits for DI Limit DI3 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4 [5-0C] kW limits for DI Limit DI4 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.7 [4-01] R/W
0~2
0: None
2: BUH
└─ Averaging time
A.6.4 [1-0A] R/W
0: No averaging
1: 12 hours 2: 24 hours 3: 48 hours 4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Boiler efficiency
A.6.A [7-05] R/W
0: Very high
1: High 2: Medium 3: Low 4: Ver
y
low
└─ Emergency
A.6.C R/W
0: Manual
1: Automatic
└─ Overview settings
A.8 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
45°C
A.8 [0-02] R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] R/W -40~5°C, step: 1°C
-10°C
A.8 [0-04] R/W
8
A.8 [0-05] R/W
12
A.8 [0-06] R/W
35
A.8 [0-07] R/W
20
A.8 [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
A.8 [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
A.8 [0-0D] R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-00] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-01] R/W 10~25°C, step: 1°C
15°C
A.8 [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
A.8 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
A.8 [1-04] R/W
1
A.8 [1-05] R/W
1
A.8 [1-06] R/W
20
A.8 [1-07] R/W
35
A.8 [1-08] R/W
22
A.8 [1-09] R/W
18
A.8 [1-0A] R/W
0: No averaging
1: 12 hours 2: 24 hours 3: 48 hours 4: 72 hours
--
--
--
--
-­What is the averaging time for the outdoor temp?
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
--
--
--
-­Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
Type
Amp. value
kW value
Priority
Equilibrium temp.
Allowed heaters
Forced pump OFF
Mode
Operation mode
(*5) *04/08*_ (*6) *16*
4P401673-1A - 2017.04
Page 87
6/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
A.8 [2-00] R/W 0: Each day
1: Monday 2: Tuesday 3: Wednesday 4: Thursday
5: Friday
6: Saturday 7: Sunda
y
A.8 [2-01] R/W 0: No
1: Yes
A.8 [2-02] R/W 0~23 hour, step: 1 hour
23
A.8 [2-03] R/W
60°C
A.8 [2-04] R/W 40~60 min, step: 5 min
40 min
A.8 [2-05] R/W 4~16°C, step: 1°C
12°C
A.8 [2-06] R/W 0: Disabled
1: Enabled
A.8 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
A.8 [3-00] R/W 0: No
1: Yes
A.8 [3-01]
0
A.8 [3-02]
1
A.8 [3-03]
4
A.8 [3-04]
2
A.8 [3-05]
1
A.8 [3-06] R/W 18~30°C, step: A.3.2.4
30°C
A.8 [3-07] R/W 12~18°C, step: A.3.2.4
12°C
A.8 [3-08] R/W
35°C
A.8 [3-09] R/W
15°C
A.8 [4-00] R/W 0: Disabled
1: Enabled
2: Onl
y
DHW
A.8 [4-01] R/W
0~2
0: None
2: BUH 14~35°C, step: 1°C
25°C
(*5)
14~35°C, step: 1°C
35°C
(*6)
A.8 [4-03] R/W
3
A.8 [4-04]
2
A.8 [4-05]
0
A.8 [4-06]
0/1
A.8 [4-07] R/W
1
A.8 [4-08] R/W
0: No limitation
1: Continuous 2: Di
g
ital inputs
A.8 [4-09] R/W 0: Current
1: Powe
r
A.8 [4-0A]
0
A.8 [4-0B] R/W
1
A.8 [4-0D] R/W
3
A.8 [4-0E] Is the installer on site? R/W
0: No
1: Yes
A.8 [5-00] R/W 0: Allowed
1: Not allowe
d
A.8 [5-01] R/W -15~35°C, step: 1°C
0°C
A.8 [5-02] R/W 0: Disabled
1: Enabled
A.8 [5-03] R/W -15~35°C, step: 1°C
0°C
A.8 [5-04] R/W 0~20°C, step: 1°C
10°C
A.8 [5-05] R/W 0~50 A, step: 1 A
50
A
A.8 [5-06] R/W 0~50 A, step: 1 A
50
A
A.8 [5-07] R/W 0~50 A, step: 1 A
50
A
A.8 [5-08] R/W 0~50 A, step: 1 A
50
A
A.8 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0A] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0B] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0C] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0D] R/O 0~5
1: 1P,
(
1/1+2
)
A.8 [5-0E]
1
A.8 [6-00] R/W 2~20°C, step: 1°C
2°C
A.8 [6-01] R/W 0~10°C, step: 1°C
2°C
A.8 [6-02] R/W
0
A.8 [6-03] R/W 0~10 kW, step: 0,2 kW
3 kW
A.8 [6-04] R/W
0
A.8 [6-05]
0
A.8 [6-06]
0
A.8 [6-07] R/W 0~200 W, step: 10 W
0 W
-­What is the capacity of the backup heater step 1?
--
--
-­What is the capacity of the bottom plate heater?
What is the requested limit for DI3?
What is the requested limit for DI4?
What type of backup heater installation is used?
-­The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
What is the requested limit for DI2?
--
Is backup heater operation allowed above equilibrium temperature during space heating operation? What is the equilibrium temperature for the building?
Space heating priority.
Space heating priority temperature.
Set point correction for domestic hot water temperature.
-- (Do not change this value)
-­Which power limitation mode is required on the system?
Which power limitation type is required?
--
--
R/W
--
--
--
--
-­What is the BUH operation mode?
Which electric heater has priority?
A.8 [4-02] Below which outdoor temperature is heating allowed?
--
--
--
-­What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Is auto restart of the unit allowed?
--
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature? How long must the tank temperature be maintained?
Room antifrost temperature
4P401673-1A - 2017.04
(*5) *04/08*_
(*6) *16*
Page 88
7/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
A.8 [6-08] R/W
2~20°C, step: 1°C 10°C
A.8 [6-09]
0
A.8 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
A.8 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
A.8 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
A.8 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
A.8 [6-0E] R/W 40~60°C, step: 1°C
60°C
A.8 [7-00] R/W
0
A.8 [7-01] R/W
2
A.8 [7-02] R/W 0: 1 LWT zone
1: 2 LWT zones
A.8 [7-03]
2,5
A.8 [7-04]
0
A.8 [7-05] R/W
0: Very high
1: High 2: Medium 3: Low 4: Ver
y
low
A.8 [8-00]
1 min
A.8 [8-01] R/W 5~95 min, step: 5 min
30 min
A.8 [8-02] R/W 0~10 hour, step: 0,5 hour
0,5 hour
A.8 [8-03] R/W
50
A.8 [8-04] R/W 0~95 min, step: 5 min
95 min
A.8 [8-05] R/W
0: No
1: Yes
A.8 [8-06] R/W 0~10°C, step: 1°C
3°C
A.8 [8-07] R/W
18
A.8 [8-08] R/W
20
A.8 [8-09] R/W [9-01]~[9-00], step: 1°C
35°C
A.8 [8-0A] R/W [9-01]~[9-00], step: 1°C
33°C
A.8 [8-0B]
13
A.8 [8-0C]
10
A.8 [8-0D]
16
A.8 [9-00] R/W 37~55, step: 1°C
55°C
A.8 [9-01] R/W 15~37°C, step: 1°C
25°C
A.8 [9-02] R/W
22
A.8 [9-03] R/W
5
A.8 [9-04] R/W 1~4°C, step: 1°C
1°C
A.8 [9-05] R/W 15~37°C, step: 1°C
25°C
A.8 [9-06] R/W 37~55, step: 1°C
55°C
A.8 [9-07] R/W
5
A.8 [9-08] R/W
22
A.8 [9-09] R/W 3~10°C, step: 1°C
5°C
A.8 [9-0A] R/W
5
A.8 [9-0B] R/W 0: Quick
1: Slo
w
A.8 [9-0C] R/W 1~6°C, step: 0,5°C
1 °C
A.8 [9-0D] R/W 0~8, step:1
0 : 100% 1~4 : 80~50% 5~8 : 80~50%
6
A.8 [9-0E]
6
A.8 [A-00]
0
A.8 [A-01]
0 (*5) 3
(*6)
A.8 [A-02]
0 (*5) 1
(*6)
A.8 [A-03]
0
A.8 [A-04]
0
A.8 [B-00]
0
A.8 [B-01]
0
A.8 [B-02]
0
A.8 [B-03]
0
A.8 [B-04]
0
A.8 [C-00] R/O 0~1
1: Heat
pump p
riorit
y
A.8 [C-01]
0
A.8 [C-02] R/W
0~3
0: No
1: Bivalent
A.8 [C-03] R/W -25~25°C, step: 1°C
0°C
A.8 [C-04] R/W 2~10°C, step: 1°C
3°C
A.8 [C-05] R/W 1: Thermo ON/OFF
2: C/H re
q
ues
t
A.8 [C-06] R/W 0: -
1: Thermo ON/OFF
2: C/H re
q
ues
t
A.8 [C-07] R/W 0: LWT control
1: Ext RT control
2: RT control
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
--
--
--
-­Domestic heating water priority.
--
--
--
--
--
--
--
What is the desired delta T in heating?
-­What emitter type is connected to the main LWT zone?
Room temperature hysteresis.
Pump speed limitation
--
-­Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
--
--
--
--
-­What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
--
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
--
-­What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
Boiler efficiency
-­Maximum running time for domestic hot water operation.
Anti-recycling time.
-­Additional running time for the maximum running time.
What is the maximum temperature setpoint?
--
-­How many leaving water temperature zones are there?
--
--
What is the hysteresis to be used in reheat mode?
-­What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
(*5) *04/08*_ (*6) *16*
4P401673-1A - 2017.04
Page 89
8/8
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
A.8 [C-08] R/W
0: No
1: Outdoor sensor 2: Room sensor
A.8 [C-09] R/W
0: Normally open
1: Normall
y
closed
A.8 [C-0A]
0
A.8 [C-0C] R/W 0~7
0
A.8 [C-0D] R/W 0~7
0
A.8 [C-0E] R/W 0~7
0
A.8 [D-00] R/W
0~3
0: None
2: BUH onl
y
A.8 [D-01] R/W
0: No
1: Open tariff 2: Closed tariff 3: Thermostat
A.8 [D-02] R/W
0~4
0: No
1: Secondary rtrn 2: Disinf. shunt
A.8 [D-03] R/W
0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C) 2: Enabled, shift 4°C (from -2 to 2°C) 3: Enabled, shift 2°C (from -4 to 4°C) 4: Enabled, shift 4°C
(
from -4 to 4°C
)
A.8 [D-04] R/W
0: No
1: Pwr consm
p
ctrl
A.8 [D-05] R/W 0: Forced off
1: As normal
A.8 [D-07] R/O
0
A.8 [D-08] R/W
0: No
1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000
p
ulse/kWh
A.8 [D-09] R/W
0: No
1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000
p
ulse/kWh
A.8 [D-0A]
0
A.8 [D-0B]
2
A.8 [D-0C] R/W 0~49
0
A.8 [D-0D] R/W 0~49
0
A.8 [D-0E] R/W 0~49
0
A.8 [E-00] R/O
0~5
0: LT s
p
lit
A.8 [E-01] R/O
0: 8 (*5) 1: 16
(*6)
A.8 [E-02] R/O 0~1
1: T
yp
e 2
A.8 [E-03] R/O 0~2
1: 1 ste
p
A.8 [E-04] R/O
0: No (*6) 1: Yes
(*5)
A.8 [E-05] R/W
0: No
1: Yes
A.8 [E-06] R/O 0: No
1: Yes
A.8 [E-07] R/O 0~6
1: T
yp
e 2
A.8 [E-08] R/W
0: Disabled (*6) 1: Enabled
(*5)
A.8 [E-09]
0
A.8 [E-0A]
0
A.8 [E-0B] R/O
0~1
1: Yes
A.8 [E-0C]
0
A.8 [E-0D]
0
A.8 [F-00] R/W
0: Disabled
1: Enabled
A.8 [F-01] R/W
20
A.8 [F-02] R/W 3~10°C, step: 1°C
3°C
A.8 [F-03] R/W 2~5°C, step: 1°C
5°C
A.8 [F-04] R/W
0: No
1: Yes
A.8 [F-05]
0
A.8 [F-06]
0
A.8 [F-09] R/W
0: Disabled
1: Enabled
A.8 [F-0A]
0
A.8 [F-0B] R/W
0: No
1: Yes
A.8 [F-0C] R/W
1
A.8 [F-0D] R/W 0: Continuous
1: Sample
2: Re
q
ues
t
-­Close shut-off valve during thermo OFF?
-­What is the pump operation mode?
Forced off contact type
Bottom plate heater ON temperature.
Bottom plate heater hysteresis.
Is a bottom plate heater connected?
--
-­Pump operation during flow abnormality.
-­Is a bi-zone kit installed?
--
-­Pump operation allowed outside range.
--
Is the power saving function available on the outdoor unit?
Can the system prepare domestic hot water?
Is a DHW tank installed in the system?
What kind of DHW tank is installed?
Power saving function for outdoor unit.
--
What is the medium electricity price (Do not use)
What is the low electricity price (Do not use)
Which type of unit is installed?
Which type of compressor is installed?
What is the indoor unit software type?
What is the number of backup heater steps?
-­Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement?
--
-­What is the high electricity price (Do not use)
Which heaters are permitted if prefer. kWh rate PS is cut?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Which type of external sensor is installed?
What is the required alarm output contact type?
-­High electricity price decimal (Do not use)
Medium electricity price decimal (Do not use)
Low electricity price decimal (Do not use)
4P401673-1A - 2017.04
(*5) *04/08*_
(*6) *16*
Page 90
Page 91
Page 92
4P401677-1B 2017.04
Copyright 2015 Daikin
Loading...