Daikin EKWCTRAN1V3 Operation manuals

ANALOGUE THERMOSTAT 230 V
2x
20
EKWCTRAN1V3
1x
The EKWCTRAN1V3 is intended for regulating the room temperature by setting the desired target temperature for the activation of actuators in heating/cooling operation. Every other use is considered not intended; the manufacturer cannot be held liable for unintented use.
¾ The electrical installation must be performed according to the
current national VDE regulations as well as according to the regulations of your local electric power utility company, by an authorised and trained electrician, and in a de-energized state.
¾ Only an authorised electrician may open the device. It may only
be opened in de-energized state. ¾ Only use the device if it is in perfect state. ¾ Ensure that children do not play with this device. Children must
be monitored if necessary.
2x
https://qr.daikin.eu?N=EKWCTRAN1V3

Installation position

± 30 cm
± 150 cm
1 2
Setback temperature
The reduction of 2 K can be activated to L/L1, e. g. by an external timer.
The thermostat can be used in heating and cooling
systems. If you want to block
the cooling function, connect the lower left contacts to each other in de-energized state.
2 K

Dismantling

1. Switch o󰀨 the voltage supply.
2. Remove the wiring.
3. Take o󰀨 the thermostat and dispose of it properly.
Target value regulator
Set the target temperature by rotating the target value regulator
1
3
25
28
-2K
+2K
-1
+1
0
2
15
4
10
Target value calibration
1. Remove the target value
2. Set the target value
by
regulator.
correction: An alignment to the room temperature is possible between
-2 K ... +2 K.
1
2a
3,5 mm
3
*
2b
60 mm
4
CO
µC
Protective cover
*

Installation

Mount the thermostat directly on the wall or on a ush-type box. Make the electric connection as shown in gure 3.
1
2
Optional – Limiting the temperature range
Insert and set the limiters for minimum and maximum temperature.
1

Technical data

Operating voltage: 230 V ±10 %, 50 Hz Fuse 230 V: T2AH Switching elem. 230 V: Relay Switching power 230 V: 2 A resist. load
Rated current w/o valve drives: 230 V: ≤2 mA
Max current draw allowed with connected valve drives: 230 V: 1.8 A Temperature setting range: 10 °C - 28 °C Target value calibration: ±2 K Reduction temperature: 2 K Temperature measurement: 0 - 40 °C Measuring accuracy: ±0.5 K Ambient temperature: 0 - 50 °C Storage temp. range: -25 to +75 °C Admissible amb. humidity: 80%, not condensing Temp. for ball pressure test: Terminals: 100 °C Plastic enclosure: 75 °C CE conformity according to: EN 60730 Protect. class 230 V: II Protection degree: IP 20 Rated impulse voltage: 1500 V Pollution degree: 2 Type action: Type 1 / Type 1.C Weight: 90 g Dimensions (W x H x D): 86 x 86 x 29 mm Antifreeze function: From +6 °C in heating mode, inactive in cooling mode.
Only thermostats with heating/cooling function:
Valve protection function: Once every 14 days for 6 minutes after the last activation
This symbol means that electrical and electronic products may NOT be mixed with unsorted household waste. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.