Daikin EKHVH008BB6V3, EKHVX008BB6V3, EKHVH008BB6WN, EKHVX008BB6WN, EKHVH008BB9WN Operation manuals

...
OPERATION MANUAL
Daikin Altherma indoor unit
EKHVH008BB6V3 EKHVX008BB6V3
EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN
EKHVH008BB6V3 EKHVX008BB6V3 EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN
Daikin Altherma indoor unit
Operation manual
CONTENTS Page
1. Definitions.................................................................................. 1
1.1. Meaning of warnings and symbols................................................. 1
1.2. Meaning of used ter ms .................................................................. 1
3. Introduction................................................................................ 2
3.1. This manual ................................................................................... 2
3.2. General information........................................................................ 2
Heating/cooling units and heating only units.................................. 2
4. Operating the unit ...................................................................... 3
4.1. Introduction .................................................................................... 3
4.2. Operating the digital controller ....................................................... 3
Features and functions................................................................... 3
4.3. Name and function of buttons and icons ........................................ 4
4.4. Setting up the controller ................................................................. 5
Setting the clock............................................................................. 5
Setting the schedule timer ............................................................. 5
4.5. Description of the operation modes ............................................... 5
Space heating operation (h).......................................................... 5
Space cooling operation (c).......................................................... 6
Domestic water heating operation (w).......................................... 6
Quiet mode operation (s) ............................................................ 6
4.6. Controller operations ...................................................................... 6
Manual operation ........................................................................... 6
Schedule timer operation ............................................................... 7
4.7. Programming and consulting the schedule timer ........................... 8
Getting started ............................................................................... 8
Programming.................................................................................. 9
Consulting programmed actions .................................................. 10
Tips and tricks.............................................................................. 11
5. Field settings ........................................................................... 12
5.1. Procedure .................................................................................... 12
Detailed description ..................................................................... 13
Field settings table ....................................................................... 17
6. Maintenance ............................................................................ 19
6.1. Impor tant information regarding the refrigerant used .................. 19
6.2. Maintenance activities .................................................................. 19
6.3. Standstill ...................................................................................... 19
7. Troubleshooting ....................................................................... 19
8. Disposal requirements............................................................. 19
READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
The English text is the original instruction. Other languages are translations of the original instructions.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
WARNING
Before operating the unit, make sure the installation has been carried out correctly by a professional Daikin dealer.
If you feel unsure about operation, contact your Daikin dealer for advice and information.

1. DEFINITIONS

1.1. Meaning of warnings and symbols

Warnings in this manual are classified according to their severity and probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or property-damage accidents only.
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Electric current.
Danger of burning and scalding.

1.2. Meaning of used terms

Installation manual:
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required service to the unit.
Applicable legislation:
All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain.
Operation manual
1
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
Accessories:
Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation.
Optional equipment:
Equipment which can optionally be combined to the products as per the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in this manual, but which are not supplied by Daikin.

2. GENERAL SAFETY PRECAUTIONS

The precautions listed here are divided into the following four types. They all cover very important topics, so be sure to follow them carefully.

3. INTRODUCTION

3.1. This manual

This manual describes how to start up and switch off the unit, set parameters and configure the schedule timer by means of the controller, maintain the unit and solve operational problems.

3.2. General information

Thank you for purchasing this indoor unit.
The unit is the indoor part of the air to water ERHQ or ERLQ heat pumps. These units are designed for floor standing indoor installation. The units can be combined with Daikin fan coil units, floor heating applications, low temperature radiators, Daikin domestic water heating applications and solar kit for domestic hot water applications.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switchbox service panel or before making any connections or touching electrical parts.
Do not touch any switch with wet fingers. Touching a switch with wet fingers can cause electrical shock. Before touching electrical parts, turn off all applicable power supply.
To avoid electric shock, be sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, be sure that those voltages are 50 V DC or less.
When service panels are removed, live parts can easily be touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
Do not touch the refrigerant piping, water piping or internal parts during and immediately after operation. The piping and internal parts may be hot or cold depending on the working condition of the unit.
Your hand may suffer burns or frostbite if you touch the piping or internal parts. To avoid injury, give the piping and internal parts time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
WARNING
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
CAUTION
Do not rinse the unit. This may cause electric shocks or fire.

Heating/cooling units and heating only units

The unit range consists of two main versions: a heating/cooling (EKHVX) version and a heating only (EKHVH) version.
Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of the outdoor unit. The backup heater models are available for a heating capacity of 6 and 9 kW, and – depending on the heating capacity – for three different power supply specifications.
Backup heater
Indoor unit model Backup heater capacity
EKHV*008BB6V3 6 kW 1x 230 V
EKHV*008BB6WN 6 kW 3x 400 V
EKHV*008BB9WN 9 kW 3x 400 V
Domestic hot water tank (option)
An optional EKHTS* domestic hot water tank can be connected to the indoor unit. The EKHTS* domestic hot water tank is available in two different water capacities: 200 and 260 litre.
Refer to the domestic hot water tank installation manual for further details.
Solar kit for domestic hot water tank (option)
For information concerning the EKSOLHT solar kit, refer to the installation manual of that kit.
Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the indoor unit and allows:
remote alarm output,
heating/cooling ON/OFF output,
bivalent operation (permission signal for the auxiliary boiler).
Refer to the operation manual of the indoor unit and to the installation manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Remote thermostat kit (option)
An optional room thermostat EKRTW or EKRTR can be connected to the indoor unit. Refer to the installation manual of the room thermostat for more information.
Connection to a benefit kWh rate power supply
This equipment allows for connection to benefit kWh rate power supply delivery systems. Refer to "Connection to a benefit kWh rate
power supply" in the installation manual for more details.
nominal voltage
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
Operation manual
2

4. OPERATING THE UNIT

4.1. Introduction

The heat pump system is designed to provide you a comfortable indoor climate for many years at low energy consumption.
To get the most comfort with the lowest energy consumption out of your system, it is very important to observe the items listed below.
Defining possible schedule timer actions for each day and filling out the form at the very end of this manual can help you minimize the energy consumption. Ask your installer for support if required.
Make sure the heat pump system works at the lowest possible hot water temperature required to heat your house.
To optimize this, make sure the weather dependent set point is used and configured to match the installation environment. Refer to "Field settings" on page 12.
It is advised to install the room thermostat connected to the indoor unit. This will prevent excessive space heating and will stop the outdoor unit and the indoor circulation pump when the room temperature is above the thermostat set point.
Next recommendations only apply to installations with an optional domestic hot water tank.
Make sure the domestic hot water is only heated up to the
domestic hot water temperature you require. Start with a low domestic hot water temperature set point (e.g. 45°C), and only increase if you feel that the domestic hot water supply temperature is not sufficient.
If the domestic hot water is not used for two weeks or more, a
quantity of hydrogen gas which is highly flammable may accumulate in the domestic hot water tank. To dissipate this gas safely, it is recommended that a hot tap be turned on for several minutes at a sink, basin, or bath, but not at a dishwasher, clothes washer or other appliance. During this procedure there must be no smoking, open flame or any electrical appliance operating nearby. If hydrogen is discharged through the tap, it will probably make a sound as of air escaping.

4.2. Operating the digital controller

Operating the EKHV* unit comes down to operating the digital controller.
CAUTION
Never let the digital controller get wet. This may cause an electric shock or fire.
Never press the buttons of the digital controller with a hard, pointed object. This may damage the digital controller.
Never inspect or service the digital controller yourself, ask a qualified service person to do this.

Features and functions

The digital controller is a state of the art controller that offers full control over your installation. It can control a heating/cooling and a heating only installation.
Both installations are available in multiple versions which vary in capacity, electrical supply and installed equipment (with an optional domestic hot water tank without a booster heater).
Descriptions in this manual that apply to a specific installation or that depend on the installed equipment, are marked with an asterisk (*).
Some functions described in this manual may not be available or should not be available. Ask your installer or your local dealer for more information on permission levels.
Basic controller functions
The basic controller functions are:
Turning the unit ON/OFF.
Operation mode change-over:
- space heating (refer to page 5),
- space cooling (refer to page 6) (*),
- domestic water heating (refer to page 6) (*).
Selection of features:
- quiet mode (refer to page 6),
- weather dependent control (refer to page 7).
Temperature set point adjustment (refer to page 6).
(*) The functions 'space cooling' and 'domestic water heating' can only be selected when the corresponding equipment is installed.
The digital controller supports a power cut off of maximum 2 hours. When autorestart is enabled (see "Field settings" on page 12) this allows a power supply shut down of 2 hours without user intervention (e.g. benefit kWh rate power supply).
Clock function
The clock functions are:
24 hour real time clock,
day of the week indicator.
Schedule timer function
The schedule timer function allows the user to schedule the operation of the installation according to a daily or a weekly program.
Operation manual
3
Daikin Altherma indoor unit
4PW64330-1 – 07.2010

4.3. Name and function of buttons and icons

1173
5 6 248
7
9
12 10
23 22
34 29
27 30
28
1. HEATING/COOLING ON/OFF BUTTON y
The ON/OFF button starts or stops the heating or cooling function of the unit.
When the unit is connected with an external room thermostat, this button is not operable and the icon e is shown.
Pressing the ON/OFF button consecutively too many times may cause malfunction of the system (maximum 20 times per hour).
Remark that pushing the y button has no influence on the domestic water heating. Domestic water heating is only switched on or off by means of the
2. OPERATION LED
0
The operation LED is lit during space heating or space cooling operation. The LED blinks if a malfunction occurs. When the LED is OFF, space heating or space cooling are inactive while the other operation modes can still be active.
3. OPERATION MODE ICONS hcws
These icons indicate the current operation mode(s): space heating (h), space cooling (c), domestic water heating (w) or quiet mode (s). Within limits, different modes can be combined, e.g. space heating and domestic water heating. The corresponding mode icons will be displayed simultaneously.
In a heating only installation, the If the domestic hot water tank is not installed, the w icon will
never be displayed.
If the solar option is installed and active, the blinking.
4. EXTERNAL CONTROL ICON
e
This icon indicates that the room thermostat (optional) with higher priority is controlling your installation. This external room thermostat can start and stop the space heating/cooling operation and change the operation mode (heating/cooling).
When the external room thermostat with a higher priority is connected, the schedule timer for space heating and space cooling will not function.
When the benefit kWh power rate signal is sent, the centralised control indication e will flash to indicate that benefit kWh power rate is active.
5. DAY OF THE WEEK INDICATOR 1234567
This indicator shows the current weekday.
When reading or programming the schedule timer, the indicator shows the set day.
6. CLOCK DISPLAY
8
The clock display shows the current time.
When reading or programming the schedule timer, the clock display shows the action time.
2161815
v button.
c icon will never be displayed.
w icon will be
7. SCHEDULE TIMER ICON
p
This icon indicates that the schedule timer is enabled.
8. ACTION ICONS q
These icons indicate the programming actions for each day of the schedule timer.
9. OFF ICON x
This icon indicates that the OFF action is selected when
4
14 21
19 11
20 13
programming the schedule timer.
10. INSPECTION REQUIRED k and l
These icons indicate that inspection is required on the installation. Consult your dealer.
11. SET TEMPERATURE DISPLAY 9
The display shows the current space heating/cooling set
25
temperature of the installation.
12. SETTING $
26
33
32
31
Not used. For installation purposes only.
13. NOT AVAILABLE n
This icon is displayed whenever a non-installed option is addressed or a function is not available.
14. DEFROST/STARTUP MODE ICON d
This icon indicates that the defrost/startup mode is active.
15. COMPRESSOR ICON ç
This icon indicates that the compressor in the outdoor unit of the installation is active.
16. BACKUP HEATER STEP ONE ( OR STEP TWO §
These icons indicate that the backup heater is operating on low capacity (() or on high capacity (§). The backup heater provides extra heating capacity in case of low ambient outdoor temperature (high heating load).
17. BOOSTER HEATER ICON m
Not applicable for these models
18. PUMP ICON é
This icon indicates that the circulation pump is active.
19. OUTDOOR TEMPERATURE DISPLAY u
When this icon is flashing, the outdoor ambient temperature is displayed.
20. WEATHER DEPENDENT SET POINT ICON a
This icon indicates that the controller will adapt the temperature set point automatically, based on the outdoor ambient temperature.
21. TEMPERATURE ICON
b
This icon is displayed when the water outlet temperature of the indoor unit, the outdoor ambient temperature and the domestic hot water tank temperature are shown.
The icon is also displayed when the temperature set point is set in schedule timer programming mode.
22. TEST OPERATION ICON t
This icon indicates that the unit runs in test mode.
23. FIELD SET CODE ;
This code represents the code from the field set list. Refer to the
"Field settings table" on page 17.
24. ERROR CODE
:
This code refers to the error code list and is for service purposes only. Refer to the error code list in the installation manual.
25. SPACE HEATING/COOLING BUTTON =
This button allows manual switching between heating or cooling mode (provided the unit is not a heating only unit).
When the unit is connected with an external room thermostat, this button is not operable and the icon e is shown.
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
Operation manual
4
26. DOMESTIC WATER HEATING BUTTON v
This button enables or disables storage and reheating of the domestic water.
This button is not used when the domestic hot water tank is not installed.
27. WEATHER DEPENDENT SET POINT BUTTON ba
This button enables or disables the weather dependent set point function which is available in space heating operation only.
If the controller is set in permission level 2 or 3 (refer to "Field
settings" on page 12), the weather dependent set point button
will not be operable.
28. INSPECTION/TEST OPERATION BUTTON z
This button is used for installation purposes and changing field settings. Refer to "Field settings" on page 12.
29. PROGRAMMING BUTTON <
This multi-purpose button is used to program the controller. The function of the button depends on the actual status of the controller or on previous actions carried out by the operator.
30. SCHEDULE TIMER BUTTON
The main function of this multi-purpose button is to enable/disable the schedule timer.
The button is also used to program the controller. The function of the button depends on the actual status of the controller or on previous actions carried out by the operator.
If the controller is set in permission level 3 (refer to "Field
settings" on page 12), the schedule timer button will not be
operable.
31. TIME ADJUST BUTTON pi and pj
These multi-purpose buttons are used to adjust the clock, to toggle between temperatures (water outlet temperature of the indoor unit, outdoor ambient temperature and domestic hot water temperature) and in schedule timer programming mode.
32. TEMPERATURE ADJUST BUTTONS bi and bj
These multi-purpose buttons are used to adjust the current set point in normal operation mode or in schedule timer programming mode. In weather dependent set point mode the buttons are used to adjust the shift value. Finally, the buttons are also used to select the weekday while setting the clock.
33. DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS
wbi and wbj
These buttons are used to adjust the current set storage point of the domestic hot water temperature.
The buttons are not used when the domestic hot water tank is not installed.
34. QUIET MODE BUTTON s
This button enables or disables quiet mode.
If the controller is set in permission level 2 or 3 (refer to "Field
settings" on page 12), the quiet mode button will not be
operable.
r/p

4.4. Setting up the controller

After initial installation, the user can set the clock and day of the week.
The controller is equipped with a schedule timer that enables the user to schedule operations. Setting the clock and day of the week is required to be able to use the schedule timer.

Setting the clock

1 Hold down the pr button for 5 seconds.
The clock read-out and the day of week indicator start flashing.
2 Use the pi and pj buttons to adjust the clock.
Each time the pi or pj button is pressed, the time will increase/decrease by 1 minute. Keeping the pi or pj button pressed will increase/decrease the time by 10 minutes.
3 Use the bi or bj button to adjust the day of the week.
Each time the bi or bj button is pressed the next or previous day is displayed.
4 Press the < button to confirm the current set time and day of the
week.
To leave this procedure without saving, press the pr button. If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.
The clock needs to be set manually. Adjust the setting when switching from summertime to wintertime and vice versa.

Setting the schedule timer

To set the schedule timer, refer to chapter "Programming and
consulting the schedule timer" on page 8.

4.5. Description of the operation modes

Space heating operation (h)

In this mode, heating will be activated as required by the water temperature set point. The set point can be set manually (refer to
"Manual operation" on page 6) or weather dependent (refer to "Selecting weather dependent set point operation (only in heating mode)" on page 7).
Startup (d)
At the start of a heating operation, the pump is not started until a certain refrigerant heat exchanger temperature is reached. This guarantees correct startup of the heat pump. During startup, icon
d is displayed.
Defrost (d)
In space heating operation or heat pump domestic water heating operation, freezing of the outdoor heat exchanger may occur due to low outdoor temperature. If this risk occurs, the system goes into defrost operation. It reverses the cycle and takes heat from the indoor system to prevent freezing of the outdoor system. After a maximum of 8 minutes of defrost operation, the system returns to the previous mode.
Operation manual
5
Daikin Altherma indoor unit
4PW64330-1 – 07.2010

Space cooling operation (c)

4.6. Controller operations

In this mode, cooling will be activated as required by the water temperature set point.
The space cooling temperature set point can only be set manually (refer to "Manual operation" on page 6).
Switching between space heating and space cooling operation can only be done by pressing the = button or by the external room thermostat.
Space cooling operation is not possible if the installation is a "heating only" installation.

Domestic water heating operation (w)

In this mode, the indoor unit will heat up the domestic hot water tank.
There are several modes for heating up the domestic water tank:
1. Storage
• Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the domestic hot water set point is reached. Preferally this is done during nighttime when space heating demand is the lowest (and if applicable, electric tariffs are low).
• Powerful The unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request.
2. Reheat
• Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached. Preferally this is done during the time of day when space heating demand is lowest.
• Continuous The unit will continuously heat up the domestic water tank untill the reheat set point is reached. In this case a balance with the space heating demand is made, which ever demand is higher.
For purpose and configuration refer to "Field settings"
on page 12.
The domestic hot water water temperature set storage point can only be set manually (refer to "Manual
operation" on page 6).
Any domestic water heating operation is impossible when the domestic hot water tank is not installed.
When the w icon is blinking, the domestic hot water is heating up by the solar kit option and not by the indoor unit. Refer to installation manual of the EKSOLHT solar kit.

Quiet mode operation (s)

Quiet mode operation means that the outdoor unit works at reduced capacity so that the sound produced by the outdoor unit drops. This implies that the indoor heating and cooling capacity will also drop. Beware of this when a certain level of heating is required indoors.

Manual operation

In manual operation, the user manually controls the settings of the installation. The last setting remains active until the user changes it or until the schedule timer forces another setting (refer to "Schedule
timer operation" on page 7).
As the controller can be used for a wide variety of installations, it is possible to select a function which is not available on your installation. In that case the message n will appear.
Switching on and setting space heating (h) and space cooling (c)
1 Use the = button to select space heating (h) or space cooling
(c). Icon h or c appears on the display as well as the corresponding
water temperature set point.
2 Use the bi and bj buttons to set the desired water
temperature.
• Temperature range for heating: 25°C to 55°C The temperature for heating can be set as low as 15°C (see
"Field settings" on page 12). However, the temperature for
heating should only be set lower than 25°C during commissioning of the installation. When set lower than 25°C, only the backup heater will operate. In order to avoid overheating, space heating is not operable when the outdoor ambient temperature rises above a certain temperature (as set through field setting [4-02], refer to "Field
settings" on page 12).
• Temperature range for cooling: 5°C to 22°C
The actual operation range depends on the values set on field setting [9].
These values shall be determined based on the application.
In heating mode (h), the water temperature set point can also be weather dependent (icon a is shown).
This means that the controller calculates the water temperature set point based on the outdoor temperature.
In this case, instead of showing the water temperature set point, the controller shows the "shift value" which can be set by the user. This shift value is the temperature difference between the temperature set point calculated by the controller and the real set point. E.g. a positive shift value means that the real temperature set point will be higher than the calculated set point.
3 Switch on the unit by pushing the
The operation LED 0 lights up.
When the unit is connected to an external room thermostat, buttons = and y are not operable and the icon e is shown. In this case, the external room thermostat switches the unit on or off and determines the operation mode (space heating or space cooling).
y button.
Daikin Altherma indoor unit
4PW64330-1 – 07.2010
Operation manual
6
Loading...
+ 15 hidden pages