Daikin EKHBH008BB3V3, EKHBH008BB6V3, EKHBH008BB6WN, EKHBH008BB6T1, EKHBH008BB9WN Installation manuals

...
INSTALLATION MANUAL
Indoor unit for air to water heat pump system
EKHBH008BB3V3 EKHBH008BB6V3 EKHBH008BB6WN EKHBH008BB6T1 EKHBH008BB9WN EKHBH008BB9T1
EKHBX008BB3V3 EKHBX008BB6V3 EKHBX008BB6WN
EKHBH008BB
EKHBX008BB6T1
EKHBX008BB
35
8
01
SP
1
12 3 45
2x2x1x 1x 1x
2
1
3
895
922
2
4
260
T T
830
1" MB
2 3
B B
469
4
30°
90°
361
48
4
1
96
39
4 5
3
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
deklaruje na własną wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
m
o
x
r
18
20
19
17
CE - IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE - DEKLARACJA-ZGODNOŚCI
CE - DECLARAŢIE-DE-CONFORMITATE
19 Direktive z vsemi spremembami.
10 Direktiver, med senere ændringer.
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
декларира на своя отговорност, че оборудването, за което се отнася тази декларация:
b
21
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu donanımının aşağıdaki gibi olduğunu beyan eder:
t
v
k
w
23
24
25
22
instrukcjami:
conformitate cu instrucţiunile noastre
инструкции:
16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
s našim návodom:
22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
01 Directives, as amended.
20 Direktiivid koos muudatustega.
21 Директиви, с техните изменения.
22 Direktyvose su papildymais.
23 Direktīvās un to papildinājumos.
24 Smernice, v platnom znení.
25 Değiştirilmiş halleriyle Yönetmelikler.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
irányelv(ek) és módosításaik rendelkezéseit.
14 v platném znění.
15 Smjernice, kako je izmijenjeno.
16
17 z późniejszymi poprawkami.
11 Direktiv, med företagna ändringar.
12 Direktiver, med foretatte endringer.
13
02 Direktiven, gemäß Änderung.
03 Directives, telles que modifiées.
04 Richtlijnen, zoals geamendeerd.
18 Directivelor, cu amendamentele respective.
05 Directivas, según lo enmendado.
06 Direttive, come da modifica.
07 √‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
08 Directivas, conforme alteração em.
09 Директив со всеми поправками.
Cертификата <C>.
положително от <B> съгласно
22 Pastaba * kaip nustatyta <A> ir kaip teigiamai nuspręsta <B>
21 Забележка * както е изложено в <A> и оценено
a(z) <C> tanúsítvány szerint.
<B> i Świadectwem <C>.
pagal Sertifikatą <C>.
vērtējumam saskaņā ar sertifikātu <C>.
23 Piezīmes * kā norādīts <A> un atbilstoši <B> pozitīvajam
de <B> în conformitate cu Certificatul <C>.
<A> DAIKIN.TCF.025D10/10-2010
<B> KEMA (NB0344)
<C> 2082543.0551-QUA/EMC
súlade s osvedčením <C>.
<A>‘da belirtildiği gibi ve <C> Sertifikasına
göre <B> tarafından olumlu olarak
değerlendirildiği gibi.
*
Not
24 Poznámka * ako bolo uvedené v <A> a pozitívne zistené <B> v
25
skladu s certifikatom <C>.
kiidetud <B> järgi vastavalt sertifikaadile <C>.
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLÁŠENÍ-O-SHODĚ
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
erklærer som eneansvarlig, at udstyret, som er omfattet af denne erklæring:
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon, innebærer at:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
u
q
s
n
j
c
y
09
10
11
12
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - DECLARAÇÃO-DE-CONFORMIDADE
СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ¢H§ø™H ™YMMOPºø™H™
13
14
la declaración:
referencia
h
15
16
acordo com as nossas instruções:
инструкциям:
instrukser:
förutsättning att användning sker i överensstämmelse med våra instruktioner:
disse brukes i henhold til våre instrukser:
08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) nor mativo(s), desde que estes sejam utilizados de
09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
mukaisesti:
12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC *
19 ob upoštevanju določb:
20 vastavalt nõuetele:
21 следвайки клаузите на:
22 laikantis nuostatų, pateikiamų:
23 ievērojot prasības, kas noteiktas:
24 održiavajúc ustanovenia:
25 bunun koşullarına uygun olarak:
16 Megjegyzés * a(z) <A> alapján, a(z) <B> igazolta a megfelelést,
Certifikatet <C>.
11 Information * enligt <A> och godkänts av <B> enligt
da <B> secondo il Certificato <C>.
06 Nota * delineato nel <A> e giudicato positivamente
19 Opomba * kot je določeno v <A> in odobreno s strani <B> v
17 Uwaga * zgodnie z dokumentacją <A>, pozytywną opinią
18 Notă * aşa cum este stabilit în <A> şi apreciat pozitiv
hyväksynyt Sertifikaatin <C> mukaisesti.
souladu s osvědčením <C>.
bedømmelse av <B> ifølge Sertifikat <C>.
13 Huom * jotka on esitetty asiakirjassa <A> ja jotka <B> on
14 Poznámka * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v
12 Merk * som det fremkommer i <A> og gjennom positiv
положительным решением <B> согласно
·fi ÙÔ <B> Û‡Ìʈӷ Ì ÙÔ ¶ИЫЩФФИЛЩИОfi <C>.
positivo de <B> de acordo com o Certificado <C>.
07 ™ËÌ›ˆÛË * fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ <A> Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
08 Nota * tal como estabelecido em <A> e com o parecer
09 Примечание * как указано в <A> и в соответствии с
20 Märkus * nagu on näidatud dokumendis <A> ja heaks
strane <B> prema Certifikatu <C>.
15 Napomena * kako je izloženo u <A> i pozitivno ocijenjeno od
Свидетельству <C>.
henhold til Certifikat <C>.
10 Bemærk * som anført i <A> og positivt vurderet af <B> i
Jean-Pierre Beuselinck
General Manager
Ostend, 1st of December 2010
declares under its sole responsibility that the equipment to which this declaration relates:
erklärt auf seine alleinige Verantwortung, dass die Ausrüstung für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que l’équipement visé par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
declara bajo su única responsabilidad que el equipo al que hace
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
a
d
f
l
e
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
01
02
i
05
04
06
03
10 under iagttagelse af bestemmelserne i:
11 enligt villkoren i:
12 gitt i henhold til bestemmelsene i:
13 noudattaen määräyksiä:
14 za dodržení ustanovení předpisu:
15 prema odredbama:
16 követi a(z):
17 zgodnie z postanowieniami Dyrektyw:
18 în urma prevederilor:
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Ф ВНФПИЫМfi˜ ЫЩФУ ФФ›Ф ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
p
g
07
08
EKHBH008BB3V3*, EKHBH008BB6V3*, EKHBH008BB6WN*, EKHBH008BB6T1*, EKHBH008BB9WN*, EKHBH008BB9T1*,
EKHBX008BB3V3*, EKHBX008BB6V3*, EKHBX008BB6WN*, EKHBX008BB6T1*, EKHBX008BB9WN*,
* = , , 1, 2, 3, ..., 9, A, B, C, ..., Z
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
daß sie gemäß unseren Anweisungen eingesetzt werden:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspr icht/entsprechen, unter der Voraussetzung,
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) nor mativo(s), siempre que sean utilizados de acuerdo con
nuestras instrucciones:
nostre istruzioni:
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
07 В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
01 following the provisions of:
02 gemäß den Vorschriften der:
03 conformément aux stipulations des:
04 overeenkomstig de bepalingen van:
EN60335-2-40,
05 siguiendo las disposiciones de:
06 secondo le prescrizioni per:
07 Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
08 de acordo com o previsto em:
09 в соответствии с положениями:
according to the Certificate <C>.
beurteilt gemäß Zertifikat <C>.
<B> conformément au Certificat <C>.
<B> overeenkomstig Certificaat <C>.
positivamente por <B> de acuerdo con el
Certificado <C>.
01 Note * as set out in <A> and judged positively by <B>
02 Hinweis * wie in der <A> aufgeführt und von <B> positiv
03 Remarque * tel que défini dans <A> et évalué positivement par
04 Bemerk * zoals vermeld in <A> en positief beoordeeld door
05 Nota * como se establece en <A> y es valorado
3PW57792-1
EKHBH008BB*** EKHBX008BB***
Indoor unit for air to water heat pump system
Installation manual
CONTENTS Page
1. Definitions.................................................................................. 2
1.1. Meaning of warnings and symbols................................................. 2
1.2. Meaning of used terms .................................................................. 2
2. General safety precautions........................................................ 2
3. Introduction................................................................................ 3
3.1. General information........................................................................ 3
3.2. Scope of this manual ..................................................................... 4
3.3. Model identification ........................................................................ 4
3.4. Typical application examples.......................................................... 5
Application 1 .................................................................................. 5
Application 2 .................................................................................. 5
Application 3 .................................................................................. 6
Application 4 .................................................................................. 7
Application 5 .................................................................................. 7
Application 6 .................................................................................. 9
4. Accessories ............................................................................. 10
4.1. Accessories supplied with the indoor unit .................................... 10
5. Overview of the indoor unit...................................................... 10
5.1. Opening the indoor unit................................................................ 10
5.2. Main components......................................................................... 11
5.3. Switch box main components ...................................................... 12
5.4. Functional diagram....................................................................... 12
6. Installation of the indoor unit.................................................... 13
6.1. Selecting an installation location.................................................. 13
6.2. Dimensions and service space .................................................... 13
6.3. Inspecting, handling and unpacking the unit................................ 14
6.4. Mounting the indoor unit .............................................................. 14
6.5. Installation of the EKHBDP drain pan kit (only for
EKHBX models) ........................................................................... 15
6.6. Refrigerant pipework.................................................................... 15
6.7. Water pipework ............................................................................ 15
Checking the water circuit............................................................ 15
6.8. General precautions concerning water circuit.............................. 15
Checking the water volume and expansion vessel
pre-pressure................................................................................. 16
Setting the pre-pressure of the expansion vessel........................ 17
Connecting the water circuit......................................................... 17
6.9. Charging water............................................................................. 17
6.10. Piping insulation........................................................................... 18
7. Electrical wiring work............................................................... 18
7.1. Precautions on electrical wiring work........................................... 18
7.2. Internal wiring - Parts table .......................................................... 18
7.3. System overview of field wiring.................................................... 19
Field wiring guidelines.................................................................. 19
Connection of the indoor unit power supply and
communication cable ................................................................... 20
Connection of the backup heater power supply........................... 20
Connection of the thermostat cable ............................................. 21
Connection of the valve control cables......................................... 21
Connection of the bottom plate heater......................................... 21
Connection to a benefit kWh rate power supply........................... 22
7.4. Relocation of the digital controller................................................ 23
Wiring specifications .................................................................... 23
Mounting ...................................................................................... 23
8. Start-up and configuration ....................................................... 23
8.1. DIP switch settings overview........................................................ 23
8.2. Room thermostat installation configuration.................................. 24
8.3. Pump operation configuration ...................................................... 24
8.4. Domestic hot water tank installation configuration....................... 25
8.5. Initial start-up at low outdoor ambient temperatures.................... 25
8.6. Pre-operation checks ................................................................... 25
Checks before initial start-up........................................................ 25
8.7. Powering up the indoor unit ......................................................... 26
8.8. Setting the pump speed ............................................................... 26
8.9. Field settings................................................................................ 26
Procedure .................................................................................... 26
Detailed description ..................................................................... 27
8.10. Field settings table....................................................................... 39
9. Test run and final check ...........................................................43
9.1. Final check................................................................................... 43
9.2. Test run operation (manual) ......................................................... 43
Procedure .................................................................................... 43
9.3. Underfloor heating screed dry-out program ................................. 43
Disclaimer .................................................................................... 43
Field settings................................................................................ 43
Getting started ............................................................................. 44
10. Maintenance and service.........................................................45
10.1. Maintenance activities.................................................................. 45
Cautions before obtaining maintenance and service ................... 45
Opening the unit........................................................................... 45
Maintenance and service ............................................................. 45
11. Troubleshooting........................................................................ 46
11.1. General guidelines....................................................................... 46
11.2. General symptoms....................................................................... 46
11.3. Error codes .................................................................................. 48
12. Technical specifications ...........................................................50
12.1. General ........................................................................................ 50
12.2. Electrical specifications................................................................ 50
Appendix ........................................................................................ 51
3. Introduction .............................................................................. 51
3.1. General information...................................................................... 51
3.4. Typical application examples........................................................ 52
Application 2 ................................................................................ 52
5. Overview of the indoor unit ...................................................... 53
5.2. Main components......................................................................... 53
6. Installation of the indoor unit....................................................53
6.8. General precautions concerning water circuit.............................. 53
Checking the water volume and expansion vessel pre-pressure . 53
7. Electrical wiring work ...............................................................53
7.3. System overview of field wiring.................................................... 53
Connection to a benefit kWh rate power supply........................... 53
8. Start-up and configuration .......................................................53
8.5. Re-start at low outdoor ambient temperatures............................. 53
8.9. Field settings................................................................................ 53
8.10. Field settings table....................................................................... 56
11. Troubleshooting........................................................................ 58
11.2. General symptoms....................................................................... 58
The original instructions are written in English. All other languages are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL AND HOW TO CONFIGURE THE UNIT PROPERLY. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT TEMPERATURES RANGING 4°C~35°C.
Installation manual
1
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011

1. DEFINITIONS

1.1. Meaning of warnings and symbols

Warnings in this manual are classified according to their severity and probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or property-damage accidents only.
INFORMATION
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Optional equipment:
Equipment which can optionally be combined to the products as per the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in this manual, but which are not supplied by Daikin.

2. GENERAL SAFETY PRECAUTIONS

The precautions here, all cover very important topics, so be sure to follow them carefully.
All activities described in this manual shall be carried out by an installer and in accordance with the applicable legislation.
Be sure to wear adequate personal protection equipment (protection gloves, safety glasses, …) when performing installation, maintenance or service to the unit.
If not sure of installation procedures or operation of the unit, always contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories and optional equipment made by Daikin which are specially designed for use with the products as of subject in this manual and have them installed by an installer.
Electric current.
Danger of burning and scalding.

1.2. Meaning of used terms

Installation manual:
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required service to the unit.
Applicable legislation:
All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switch box service panel or before making any connections or touching electrical parts.
Do not touch any switch with wet fingers. Touching a switch with wet fingers can cause electrical shock. Before touching electrical parts, turn off all applicable power supply.
To avoid electric shock, be sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, be sure that those voltages are 50 V DC or less.
When service panels are removed, live parts can easily be touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
Do not touch the refrigerant piping, water piping or internal parts during and immediately after operation. The piping and internal parts may be hot or cold depending on the working condition of the unit.
Your hand may suffer burns or frostbite if you touch the piping or internal parts. To avoid injury, give the piping and internal parts time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
Installation manual
2
WARNING
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
CAUTION
Do not rinse the unit. This may cause electric shocks or fire.

3. INTRODUCTION

3.1. General information

Thank you for purchasing this indoor unit.
The unit is the indoor part of the air to water ERHQ or ERLQ heat pumps. This unit is designed for wall mounted indoor installation. See
"6.1. Selecting an installation location" on page 13. The unit can be
combined with Daikin fan coil units, floor heating applications, low temperature radiators, Daikin domestic water heating applications and Daikin solar kit for domestic hot water applications.
For installations with restricted power supply, the indoor unit can be configured to limit the power consumption.
There are 2 possibilities to limit the power consumption:
allow simultaneous operation of outdoor unit and backup heater only or outdoor unit and booster heater only by priority setting [4-01] (see "[4] Backup/booster heater operation and space
heating off temperature" on page 28),
allow operation of backup heater only, booster heater only or outdoor unit only (see "Appendix" on page 51) by [d-02] (see
"[d] Restricted power supply condition mode/Local shift value weather dependent" on page 55).
INFORMATION
All information and settings in the manual are applicable for all applications, except the chapters with following footnote indication: "When the unit is configured for restricted power supply condition mode, see "Appendix" on page 51".
Heating/cooling units and heating only units
(1)
The unit range consists of two main versions: a heating/cooling (EKHBX) version and a heating only (EKHBH) version.
Both versions are delivered with an integrated backup heater for additional heating capacity during low outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of the outdoor unit. The backup heater models are available for a heating capacity of 3, 6 and 9 kW, and – depending on the heating capacity – for three different power supply specifications.
Backup heater
Indoor unit model Backup heater capacity
EKHB*008BB3V3 3 kW 1x 230 V EKHB*008BB6V3 6 kW 1x 230 V EKHB*008BB6WN 6 kW 3x 400 V EKHB*008BB9WN 9 kW 3x 400 V EKHB*008BB6T1 6 kW 3x 230 V EKHB*008BB9T1 9 kW 3x 230 V
P
H
43
1 Heat pump capacity 2 Required heating capacity (site dependent) 3 Additional heating capacity provided by the backup heater 4 Equilibriumtemperature (can be set through the user
interface, refer to "8.9. Field settings" on page 26) Ambient (outdoor) temperature
T
A
Heating capacity
P
H
Domestic hot water tank (option)
(2)
nominal voltage
1
2
T
A
An optional domestic hot water tank can be connected to the indoor unit. The domestic hot water tank is available in 2 types:
tank with built-in electrical booster heater (EKHW*) in 3 different sizes: 150, 200 and 300 litre,
tank without electrical booster heater (EKHTS) in 2 different sizes: 200 and 260 litre.
Refer to the domestic hot water tank installation manual for further details.
NOTICE
Restricted power supply condition mode can only be used for a tank with built-in electrical booster heater (EKHW*).
Installation manual
3
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
(2) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Drain pan kit (option)
For heating/cooling versions (EKHBX), it is necessary to install the EKHBDP drain pan kit.
For more information concerning the drain pan kit, refer to
"6.5. Installation of the EKHBDP drain pan kit (only for EKHBX models)" on page 15.
Solar kit for domestic hot water tank (option)
For information concerning the EKSOLHW solar kit, refer to the installation manual of that kit.
INFORMATION
Use the EKSOLHW solar kit only in combination with the EKHW* domestic hot water tank.
Connection between EKSOLHW and EKHTS domestic hot water tank is NOT possible.
Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the indoor unit and allows:
remote alarm output,
heating/cooling ON/OFF output,
bivalent operation (permission signal for the auxiliary boiler) or
additional external backup heater permission signal.
Refer to the operation manual of the indoor unit and to the installation manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Room thermostat kit (option)
An optional room thermostat EKRTW, EKRTWA, or EKRTR can be connected to the indoor unit. Refer to the installation manual of the room thermostat for more information.
Bottom plate heater (option)
Connectable heaters
EKBPHT08 EKBPHT08BA
EKHBH/X008BB Possible Possible
(a) Recommended.
(a)
Possible combinations
EKHBH/X_BB
ERHQ_BA Possible ERLQ_BA Possible
(a) If a bottom plate heater is required, see "Bottom plate heater (option)" on page 4.
Connection to a benefit kWh rate power supply
(a)
(1)
This equipment allows for connection to benefit kWh rate power supply delivery systems. Full control of the unit will remain possible even in case the benefit kWh rate power supply is of the type that power supply is interrupted. Refer to "Connection to a benefit kWh
rate power supply" on page 22 for more details.

3.2. Scope of this manual

This manual does NOT include the selection procedure and the water system design procedure. Only some precautions and tips and tricks about the design of the water circuit are given in a separate chapter of this manual.
Once the selection is done and the water system is designed, this manual describes the procedures for handling, installing and connecting the EKHBH/X units. This manual has been prepared to ensure adequate maintenance of the unit, and it will provide help if problems occur.
INFORMATION
Refer to the installation manual of the outdoor unit for items not described in this manual.
The operation of the indoor unit is described in the indoor unit operation manual.
3.3. Model identification
Indoor unit
EK HB X 008 BB 3 V3
Backup heater nominal voltage: V3 = 1P, 230 V
WN = 3P, 400 V T1 = 3P, 230 V
Backup heater capacity (kW)
Series
Indication of heating/cooling capacity (kW)
X = heating and cooling, H = heating only
Hydro box
European kit
(a) For exact values, refer to "12. Technical specifications" on page 50.
Drain pan kit (optional)
EK HB DP 150
Drain pan
Hydro box
European kit
(a)
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
Installation manual
4

3.4. Typical application examples

The application examples given below are for illustration purposes only.

Application 1

Space heating only application with the room thermostat connected to the indoor unit.
T
6745321

Application 2

(1)
Space heating only application without room thermostat connected to the indoor unit. The temperature in each room is controlled by a valve on each water circuit. Domestic hot water is provided through the domestic hot water tank which is connected to the indoor unit.
645321
7 8
M
M1T1M2T2M3
9
T3
6
FHL1
FHL2
FHL3
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Collector (field supply)
FHL1...3 Floor heating loop
T Room thermostat (optional)
Pump operation and space heating
When the room thermostat (T) is connected to the indoor unit, the pump (5) will operate when there is a heating request from the room thermostat, and the outdoor unit will start operating to achieve the target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the outdoor unit and pump will stop operating.
NOTICE
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat cable" on
page 21) and to configure the DIP switch toggle switches
correctly (see "8.2. Room thermostat installation
configuration" on page 24).
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Collector (field supply)
9 By-pass valve (field supply) 10 Domestic hot water tank (optional) 11 Booster heater 12 Heat exchanger coil
FHL1...3 Floor heating loop
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control the floor heating loop
(field supply)
11 12
(2)
(3)
FHL1
FHL2
FHL3
10
Pump operation
With no thermostat connected to the indoor unit (2), the pump (5) can be configured to operate either as long as the indoor unit is on, or until the required water temperature is reached.
INFORMATION
Details on pump configuration can be found under
"8.3. Pump operation configuration" on page 24.
Installation manual
5
Space heating
The outdoor unit (1) will operate to achieve the target leaving water temperature as set on the user interface.
NOTICE
When circulation in each space heating loop (FHL1...3) is controlled by remotely controlled valves (M1...3), it is important to provide a by-pass valve (9) to avoid the flow switch safety device from being activated.
The by-pass valve should be selected as such that at all time the minimum water flow as mentioned under
"6.7. Water pipework" on page 15 is guaranteed.
It is recommended to select a pressure difference controlled by-pass valve.
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
(2) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(3) Only applicable for tank with built-in electrical booster heater (EKHW*).
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Domestic water heating
When domestic water heating mode is enabled (either manually by the user, or automatically through a schedule timer) the target domestic hot water temperature will be achieved by a combination of the heat exchanger coil and the electrical booster heater
(2)
heater
.
(1)
or backup
When the domestic hot water temperature is below the user configured set point, the 3-way valve will be activated to heat the domestic hot water by means of the heat pump. In case of large domestic hot water demand or a high domestic hot water temperature setting, the booster heater (11)
(3)
or backup heater (4)
can provide auxiliary heating.
INFORMATION
Only for EKHW*:
At low outdoor temperatures when space heating demand is higher, the indoor unit can be configured to have the domestic hot water heated by the booster heater exclusively. This assures that the full capacity of the heat pump is available for space heating.
Details on domestic hot water tank configuration for low outdoor temperatures can be found under
"8.9. Field settings" on page 26, field settings [5-02]
to [5-04].
Only for EKHTS:
At low outdoor temperatures when space heating demand is higher, the indoor unit can be configured to have the domestic hot water heated the heat pump and backup heater at the same time. This assures that the interruption of space heating is limited to a minimum.
Details on domestic hot water tank configuration for low outdoor temperatures can be found under
"8.9. Field settings" on page 26, field settings [5-02]
to [5-04].
NOTICE
Be sure that the correct field settings are active or selected according to the applicable tank type. See field settings in
"[4] Backup/booster heater operation and space heating off temperature" on page 28 for more details.

Application 3

Space heating and cooling application with the room thermostat set for heating/cooling connected to the indoor unit. Heating is provided
through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
Domestic hot water is provided through the domestic hot water tank which is connected to the indoor unit.
9
(4)
T
645321
7
M
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Motorised 2-way valve (field supply)
9 Collector (field supply) 10 Domestic hot water tank (optional) 11 Booster heater 12 Heat exchanger coil
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T Room thermostat (optional)
(5)
(6)
Pump operation and space heating and cooling
According to the season, the customer will select heating or cooling on the room thermostat (T). This selection is not possible by operating the user interface.
When space heating/cooling is requested by the room thermostat (T), the pump will start operating and the indoor unit (2) will switch to "heating mode"/"cooling mode". The outdoor unit (1) will start operating to achieve the target leaving hot/cold water temperature.
In case of cooling mode, the 2-way valve (8) will close as to prevent cold water running through the floor heating loops (FHL).
8
M
11 12
FCU1
FHL1
10
FCU2
FHL2
FCU3
FHL3
(1) Only applicable for tank with built-in electrical booster heater (EKHW*). (2) Only applicable for tank without electrical booster heater (EKHTS). (3) Only applicable for tank with built-in electrical booster heater (EKHW*). (4) Only applicable for tank without electrical booster heater (EKHTS).
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
(5) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(6) Only applicable for tank with built-in electrical booster heater (EKHW*).
Installation manual
6
NOTICE
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat
cable" on page 21) and to configure the DIP switch
toggle switches correctly (see "8.2. Room thermostat
installation configuration" on page 24).
Wiring of the 2-way valve (8) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the room thermostat and cannot be done by the user interface on the indoor unit.
Domestic water heating
(1)
Domestic water heating is as described under "Application 2" on
page 5.

Application 4

Space heating and cooling application without the room thermostat connected to the indoor unit, but with the heating only room
thermostat (set heating only) controlling the floor heating and the heating/cooling thermostat (set heating/cooling) controlling the fan coil units. Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
9
10
T4
T5
FCU2
FHL2
T6
FCU3
FHL3
T
7
645321
M
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Motorised 2-way valve to shut off the floor heating loops
during cooling operation (field supply)
8 Motorised 2-way valve for activation of the room thermostat
(field supply)
9 Collector (field supply)
10 By-pass valve (field supply)
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T Heating only room thermostat (optional)
T4...6 Individual room thermostat for fan coil heated/cooled room
(optional)
FCU1
8
M
FHL1
Pump operation
With no thermostat connected to the indoor unit (2), the pump (5) can be configured to operate either as long as the indoor unit is on, or until the required water temperature is reached.
INFORMATION
Details on pump configuration can be found under
"8.3. Pump operation configuration" on page 24.
Space heating and cooling
According to the season, the customer will select heating or cooling through the user interface on the indoor unit.
The outdoor unit (1) will operate in heating mode or cooling mode to achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (7) is open. Hot water is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the 2-way valve (7) is closed to prevent cold water running through the floor heating loops (FHL).
NOTICE
When closing several loops in the system by remotely controlled valves, it might be required to install a by­pass valve (10) to avoid the flow switch safety device from being activated. See also "Application 2" on
page 5.
Wiring of the 2-way valve (7) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the user interface on the indoor unit.

Application 5

Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin indoor unit or by an auxiliary boiler connected in the system. The decision whether either the EKHB* indoor unit or the boiler will operate can be achieved by an auxiliary contact or an EKHB* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 8.
The EKHB* indoor unit controlled contact (also called 'permission signal for the auxiliary boiler') is determined by the outdoor temperature (thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 8.
Bivalent operation is only possible for space heating operation, not for the domestic water heating operation. Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the Daikin indoor unit.
The auxiliary boiler must be integrated in the piping work and in the field wiring according to the illustrations below.
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with the applicable legislation.
Daikin can not be put responsible for incorrect or unsafe situations in the boiler system.
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Installation manual
7
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Field wiring configuration B
1
FHL1...3 Floor heating loop
4532
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Non-return valve (field supply)
9 Shut-off valve (field supply) 10 Collector (field supply) 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Domestic hot water tank (optional) 14 Booster heater 15 Heat exchanger coil
Field wiring configuration A
L
Com
H
EKHB*/auto
/ Boiler
A
K1A
N
BTIBoiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of EKHB* unit (field supply) K2A Auxiliary relay for activation of boiler (field supply)
K2A
6 7
12
14
(1)
(2)
EKHB*
8
M
8
9
11
9
10
X2M
123 4
K1A
Com
HC
EKRTR*
Operation
Com Common room thermostat (optional)
K1A Auxiliary relay for activation of boiler unit (field supply)
KCR Permission signal for the auxiliary boiler
EKHB*
X2M
3 4
12
K1A
Com
H
C
EKRTW*
BTIBoiler thermostat input
C Cooling demand room thermostat (optional) H Heating demand room thermostat (optional)
EKRP1HB*
KCR
X1 X2
X
Y
B
TI
K1A
Configuration A
15
FHL1
FHL2
13
FHL3
When the room thermostat requests heating, either the EKHB* unit or the boiler starts operating, depending on the position of the auxiliary contact (A).
Configuration B
When the room thermostat requests heating, either the EKHB* unit or the boiler starts operating, depending on the outdoor temperature (status of "permission signal for the auxiliary boiler"). When the permission is given towards the boiler, the space heating operation by the EKHB* unit will be automatically switched off. For more details see field setting [C-02~C-04].
NOTICE
Configuration A
Make sure that auxiliary contact (A) has sufficient differential or time delay so as to avoid frequent changeover between the EKHB* unit and the boiler. If the auxiliary contact (A) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun.
Configuration B
Make sure that the bivalent hysteresis [C-04] has sufficient differential to avoid frequent changeover between the EKHB* unit and the boiler. As the outdoor temperature is measured via the outdoor unit, air thermistor make sure to install the outdoor unit in the shade, so that it is not influenced by the sun. Frequent switching may cause corrosion of the boiler in an early stage. Contact the manufacturer of the boiler.
During heating operation of the EKHB* unit, the unit
K1A
EKHB*
X2M
123 4
K2A
B
TI
Y
X
will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature set point on the boiler controller above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Daikin indoor unit.
(1) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(2) Only applicable for tank with built-in electrical booster heater (EKHW*).
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
NOTICE
Make sure to configure the DIP switch SS2-3 on the PCB of the EKHB* switch box correctly. Refer to "8.2. Room
thermostat installation configuration" on page 24.
For configuration B: Make sure to configure the field settings [C-02, C-03 and C-04] correctly. Refer to "Bivalent
operation" on page 36.
Installation manual
8
NOTICE
Make sure that return water to the EKHB* heat exchanger never exceeds 55°C.
For this reason, never put the target leaving water temperature set point on the boiler controller above 55°C and install an aquastat
(a)
valve in the return water flow of
the EKHB* unit. Make sure that the non-return valves (field supply) are
correctly installed in the system. Make sure that the room thermostat EKRTR or EKRTW
are not frequently turned ON/OFF. Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the EKHB* unit again.

Application 6

Space heating with room thermostat application through floor heating loops and fan coil units. The floor heating loops and fan coil units require different operating water temperatures.
The floor heating loops require a lower water temperature in heating mode compared to fan coil units. To achive these two set points, a
mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The fan coil units are directly connected to the indoor unit water circuit and the floor heating loops after the mixing station. The control of this mixing station is not done by the indoor unit.
The operation and configuration of the field water circuit is the responsibility of the installer.
Daikin only offers a dual set point control function. By this function two set points can be generated. Depending on the required water temperature (floor heating loops and/or fan coil units are required) first set point or second set point can be activated.
INFORMATION
Manual permission towards the EKHB* unit on the boiler. In case only the EKHB* unit should operate in space
heating mode, disable the bivalent operation via setting [C-02].
In case only the boiler should operate in space heating mode, increase the bivalent ON temperature [C-03] to 25°C.
Domestic water heating
(1)
Domestic water heating is as described under "Application 2" on
page 5.
B
7
T1
A
FCU1
FHL1
8
FCU2
FHL2
FCU3
FHL3
T2
645321
6
9
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Collector zone B (field supply) 8 Collector zone A (field supply) 9 Mixing station (field supply)
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T1 Room thermostat for zone A (optional) T2 Room thermostat for zone B (optional)
INFORMATION
The advantage of the dual set point control is that the heat pump will/can operate at the lowest required leaving water temperature when only floor heating is required. Higher leaving water temperatures are only required in case fan coil units are operating. This results in a better performance of the heat pump.
The hydraulic balance is very important. (Hydrobox ­mixing station - FCU1...3)
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Installation manual
9
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Pump operation and space heating
When the room thermostat for the floor heating loop (T1) and the fan coil units (T2) are connected to the indoor unit, the pump (5) will operate when there is a request for heating from T1 and/or T2. The outdoor unit will start operating to achieve the target leaving water temperature. The target leaving water temperature depends on which room thermostat is requesting heating.
Set point Field setting Thermo status
Zone A First UI ON OFF ON OFF Zone B Second [7-03] OFF ON ON OFF Resulting water temperature UI [7-03] [7-03] — Result pump operation ON ON ON OFF
When the room temperature of both zones is above the thermostat set point, the outdoor unit and pump will stop operating.
NOTICE
Make sure to connect the thermostat wires to the correct terminals (see "5. Overview of the indoor unit"
on page 10).
Make sure to configure the field settings [7-02], [7-03] and [7-04] correctly. Refer to "Dual set point control"
on page 33.
Make sure to configure the DIP switch SS2-3 on the PCB of the EKHBH switch box correctly. Refer to
"8.2. Room thermostat installation configuration" on page 24.
It is the installers responsibility to make sure no unwanted situations can occur (e.g. too high water temperatures towards floor heating loops, etc.)
Be aware that the actual water temperature through the floor heating loops depends on the control and setting of the mixing station.

5. OVERVIEW OF THE INDOOR UNIT

5.1. Opening the indoor unit

The front flap on the indoor unit cover gives access to the manometer and user interface.
The indoor unit cover can be removed by removing the 2 bottom screws and unhitching the cover.
INFORMATION
The request signals for space heating can be implemented in two different ways (installer choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the mixing
station
Daikin does not offer any type of mixing station. Dual set point control only provides the possibility to use two set points.
When only zone A request heating, zone B will be fed with water at a temperature equal to the first set point. This can lead to unwanted heating of zone B.
When only zone B request heating, the mixing station will be fed with water at a temperature equal to the second set point. Depending on the control of the mixing station, the floor heating loop can still receive water at a temperature equal to set point of the mixing station.
At this type of application heating/cooling selection always has to be done on the user interface. Refer to
"Dual set point control" on page 33 for more details.

4. ACCESSORIES

4.1. Accessories supplied with the indoor unit

INFORMATION
Make sure to fix the cover with the screws when installing the cover (screws are delivered as accessory).
To gain access to the switch box components – e.g. to connect the field wiring – the switch box service panel can be removed. Thereto, loosen the front screws and unhitch the switch box service panel.
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
See "2. General safety precautions" on page 2.
See figure 1
1 Installation manual 2 Operation manual 3 Shut-off valve 4 Wiring diagram sticker (inside indoor unit cover) 5 Indoor unit cover fixing screw
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
Installation manual
10
3
11

5.2. Main components

20
19 18
17
3
16
14
21
10 13
12
1. Air purge valve
Remaining air in the water circuit will be automatically removed via the air purge valve.
2. Backup heater
(1)
The backup heater consists of an electrical heating element in the backup heater vessel that will provide additional heating capacity to the water circuit if the heating capacity of the outdoor unit is insufficient due to low outdoor temperatures.
3. Temperature sensors
33
Four temperature sensors determine the water and refrigerant temperature at various points in the water circuit.
4. Switch box
The switch box contains the main electronic and electrical parts of the indoor unit.
5. Heat exchanger
3
3
6. Expansion vessel (10 l)
7. User interface
The user interface allows the installer and user to set up, use and maintain the unit.
8. Refrigerant liquid connection
9. Refrigerant gas connection
2
1
10. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water outlet connection allow isolation of the indoor unit water circuit side from the residential water circuit side. This facilitates draining and filter replacement of the indoor unit.
11. Water inlet connection
12. Water outlet connection
13. Drain and fill valves
1
14. Water filter
The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator. The water filter must be cleaned on a regular base. See "10. Maintenance and
service" on page 45.
2
15. Manometer
The manometer allows readout of the water pressure in the water circuit.
3
16. Flow switch
The flow switch checks the flow in the water circuit and protects
4
the heat exchanger against freezing and the pump against damage.
17. Pump
The pump circulates the water in the water circuit.
5
6
18. Backup heater thermal protector
The backup heater is equipped with a thermal protector. The thermal protector is activated when the temperature becomes too high.
19. Backup heater thermal fuse
The backup heater is equipped with a thermal fuse. The thermal
3
fuse is blown when the temperature becomes too high (higher than the backup heater thermal protector temperature).
7
15
3
20. Pressure relief valve
The pressure relief valve prevents excessive water pressure in the water circuit by opening at 3 bar and discharging some water.
21. Pressure relief valve hose
8 9
13 10
11
The actual outlet of the pressure relief valve. Make sure to provide a proper drain.
Installation manual
11
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011

5.3. Switch box main components

14
12
11
10
X9A
X13A
SS2
FU1
9
TR1
K1M K2M
K3M K6M
A1P
F2B F3B F1B
K5M
FU2
1
2 3
1
4 5
5
13
12. X9A socket
The X9A socket receives the thermistor connector (only for installations with domestic hot water tank).
13. Fuse FU2 (in line fuse)
14. Transformer TR1
15. A4P
Digital I/O PCB (only for installations with solar kit or digital I/O PCB kit).
16. X6YA/X6YB/X6Y
(4)
Connectors for connecting to a normal kWh rate power supply. See also "Connection to a benefit kWh rate power supply" on
page 22.
NOTICE
The electrical wiring diagram can be found on the inside of the switch box cover.

5.4. Functional diagram

32 4 8
5 6 7
15
6
A4P
X2M X4M
16
8
6
8
X1M
X3M
7
1. Backup heater contactors K1M, K2M, K5M and K6M.
2. Main PCB
The main PCB (Printed Circuit Board) controls the functioning of the unit.
3. Booster heater contactor K3M (only for installations with
domestic hot water tank)
4. Booster heater circuit breaker F2B (only for installations with
domestic hot water tank)
(1)
(2)
The circuit breaker protects the booster heater in the domestic hot water tank against overload or short circuit.
5. Backup heater circuit breaker F1B, F3B
The circuit breaker protects the backup heater electrical circuit against overload or short circuit.
6. Te r minal blocks
The terminal blocks allow easy connection of field wiring.
7. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable ties to the switch box to ensure strain relief.
8. Te r minal blocks X3M, X4M (only for installations with domestic
hot water tank)
(3)
9. PCB fuse FU1
10. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters. See "8.1. DIP switch settings
overview" on page 23.
11. X13A socket
The X13A socket receives the K3M connector (only for installations with domestic hot water tank).
R1T
t >
H
O
2
R3T
t >
1 Outdoor unit 2 Indoor unit 3 Expansion vessel 4 Manometer 5 Air purge valve 6 Pressure relief valve 7 Backup heater 8 Pump 9 Flow switch
10 Shut-off valve water outlet with drain valve (field
installation)
11 Shut-off valve water inlet with drain valve (field installation) 12 Filter
13 Heat exchanger R1T Outlet water heat exchanger thermistor R2T Outlet water backup heater thermistor R3T Refrigerant liquid side thermistor R4T Inlet water thermistor
R2T
t >
R4T
t >
12131
9
10
11
(1) Only applicable for tank with built-in electrical booster heater (EKHW*). (2) Only applicable for tank with built-in electrical booster heater (EKHW*). (3) Only applicable for tank with built-in electrical booster heater (EKHW*).
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
(4) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Installation manual
12

6. INSTALLATION OF THE INDOOR UNIT

6.1. Selecting an installation location

WARNING
Be sure to provide for adequate measures in order to prevent that the unit be used as a shelter by small animals.
CAUTION
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean and clear.
The equipment is not intended for use in a potentially explosive atmosphere.
Be sure that sufficient precautions are taken, in accordance with the applicable legislation, in case of refrigerant leakage.
When installing the unit in a small room, take measures in order to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak. Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. Such gases may cause a fire.
The unit is to be wall mounted in an indoor location that meets the following requirements:
The installation location is frost-free.
The space around the unit is adequate for servicing. (See
figure 2).
The space around the unit allows for sufficient air circulation.
There is a provision for condensate drain (only for EKHBX
models with drain pan kit EKHBDP) and pressure relief valve blow-off.
The installation surface is a flat and vertical non-combustible wall, capable of supporting the operation weight of the unit (see
"12. Technical specifications" on page 50).
All piping lengths and distances have been taken into consideration.
Requirement Value
Maximum allowable refrigerant piping length between outdoor unit and indoor unit
Minimum required refrigerant piping length between outdoor unit and indoor unit
Maximum allowable height difference between outdoor unit and indoor unit
Maximum allowable distance between the 3-way valve and the indoor unit (only for installations with domestic hot water tank).
Maximum allowable distance between the domestic hot water tank and the indoor unit (only for installations with domestic hot water tank). The thermistor cable supplied with the domestic hot water tank is 12 m in length.
30 m
3 m
20 m
3 m
10 m
Do not install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Ta ke care that in the event of a water leak, water can not cause any damage to the installation space and surroundings.
Do not place any objects or equipment on top of the unit.
Install the power wire at least 1 meter away from televisions or
radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or water to leak.
Where corrosive gas, such as sulphurous acid gas, is
produced. Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.
Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.
Where the air contains high levels of salt.
Where voltage fluctuates a lot, such as that in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.
INFORMATION
If the installation is equipped with a domestic hot water tank (optional), please refer to the domestic hot water tank installation manual.

6.2. Dimensions and service space

Unit of measurement: mm
Dimensions of the unit, see figure 3.
1 Flexible drain hose 2 Water outlet connection 3 Water inlet connection 4 Refrigerant liquid connection 5 Refrigerant gas connection
FBSP Female British Standard Pipe
MBSP Male British Standard Pipe
Required service space, see figure 2.
During normal operation the hydrobox unit will produce sound which could be observed as noise. The sound origin can be water pump operation and/or contactor activation. Therefore it is advisable to install the hydrobox unit on a firm wall and not in nor close to a sound sensitive environment (e.g. bedroom).
Do not install the unit in places with high humidity (e.g. bathroom).
Installation manual
13
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011

6.3. Inspecting, handling and unpacking the unit

6.4. Mounting the indoor unit

The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet.
At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent.
Check if all indoor unit accessories (see "4. Accessories" on
page 10) are enclosed.
Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during transport.
The indoor unit weighs approximately 46 kg and should be lifted
by two persons using the two lifting bars provided.
CAUTION
Do not grasp the switch box or piping to lift the unit! Tw o lifting bars are provided to lift the unit.
Safely dispose of packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
WARNING
Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation.
CAUTION
The weight of the indoor unit is approximately 46 kg. Two persons are required to mount the unit.
1 Put the installation pattern (see packing) on the wall and mark
the fixation positions (2 on top ( T) and 2 at the bottom (B)). Make sure that the marks (2 by 2) are completely level and the
dimensions of the marks are corresponding according to
figure 4.
When the unit is not installed level, air might get trapped in the water circuit resulting in malfunctioning of the unit. Pay special attention to this when installing an EKHBX model to prevent overflow of the drain pan.
2 Drill 4 holes and install 4 plugs (suitable for M10).
3 Put the screws in top plugs and hang the indoor unit on the top
screws.
4 Put the screws in bottom plugs and fix the screws firmly.
1
2
3
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
1
Installation manual
4
14
6.5. Installation of the EKHBDP drain pan kit (only for
75°C (EKHTS) 65°C (EKHW*)
65°C
EKHBX models)
For heating/cooling models, it is necessary to install the drain pan kit (see "4. Accessories" on page 10).
During cooling operation, water vapour (humidity) in the air might condense to liquid and collect on the cold refrigerant and water pipes. This water is collected in the drain pan, which must be connected to a drain.
For installation instructions, refer to the instruction sheet delivered with the drain pan kit.
CAUTION
Make sure to position the pressure relief valve hose end in the drain pan. Failure to do so might lead to water coming into contact with electrical parts, resulting in electrical shocks or short-circuit of the electrical system.

6.8. General precautions concerning water circuit

Before continuing the installation of the unit, check the following points:
The maximum water pressure is 4 bar.
The maximum water temperature during space heating is 65°C
(safety device setting) and 75°C operation (safety device setting). Make sure that the installed piping and piping accessories (e.g., valve, connections,...) can withstand the temperatures as shown in the figure below.
75°C (EKHTS) 65°C (EKHW*)
(1)
during domestic hot water
65°C
9

6.6. Refrigerant pipework

For all guidelines, instructions and specifications regarding refrigerant pipework between the indoor unit and the outdoor unit, please refer to the outdoor unit installation manual.
The location of the gas pipe and liquid pipe on the indoor unit is shown under "5.2. Main components" on page 11.
Refrigerant piping
specifications
Gas pipe connection 15.9 mm (5/8 inch) 15.9 mm (5/8 inch) Liquid pipe connection 6.4 mm (1/4 inch) 6.4 mm (1/4 inch)
Indoor unit Outdoor unit
CAUTION
When connecting the refrigerant pipes, always use two wrenches/spanners for tightening or loosening nuts! Failure to do so can result in damaged piping connections and leaks.

6.7. Water pipework

Checking the water circuit

The units are equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by an installer and must comply with the applicable legislation.
NOTICE
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
T
645321
7
M
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Motorised 2-way valve (field supply)
9 Collector (field supply) 10 Domestic hot water tank (optional) 11 Booster heater 12 Heat exchanger coil
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T Room thermostat (optional)
(2)
(3)
8
M
11 12
FCU1
FHL1
10
FCU2
FHL2
FCU3
FHL3
Provide adequate safeguards in the water circuit to be sure that the water pressure will never exceed the maximum allowable working pressure (4 bar).
Tw o shut-off valves are delivered with the unit. To facilitate service and maintenance, install one at the water inlet and one at the water outlet of the indoor unit. Mind position of the shut-off valves. Orientation of the integrated drain and fill valves is important for servicing. See figure 3.
Drain taps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance. Tw o drain valves integrated in the shut-off valves are provided to drain the water from the indoor unit water system.
Make sure to provide a proper drain for the pressure relief valve to avoid any water coming into contact with electrical parts.
Installation manual
15
(1) Be sure that the correct field settings are active or selected according to
the applicable tank type. See field settings in "[4] Backup/booster heater
operation and space heating off temperature" on page 28 for more details.
(2) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(3) Only applicable for tank with built-in electrical booster heater (EKHW*).
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Air vents must be provided at all high points of the system. The vents should be located at points which are easily accessible for servicing. An automatic air purge is provided inside the indoor unit. Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible.
Ta ke care that the components installed in the field piping can withstand the water pressure and water temperature.
Always use materials which are compatible with water used in the system and with the materials used on the indoor unit.
If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
Use a good thread sealant for the sealing of the connections.
When using non-brass metallic piping, make sure to insulate
both materials from each other to prevent galvanic corrosion.
Because brass is a soft material, use appropriate tooling for connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
Select piping diameter in relation to required water flow and available external static pressure of the pump.
The minimum required water flow for the indoor unit operation is 12 l/min. When the water flow is lower than this minimum value, flow error 7H will be displayed and the operation of the indoor unit will be stopped.
Never use Zn-coated parts in the water circuit. Excessive corrosion of these parts may occur as copper piping is used in the unit's internal water circuit.
When using a 3-way valve in the water circuit. It is very important to guarantee full separation between domestic hot water and floor heating water circuit.
When using a 3-way valve or a 2-way valve in the water circuit, the maximum change over time of the valve shall be less than 60 seconds.
NOTICE
It is strongly recommended to install an additional filter on the heating water circuit. Especially to remove metallic particles from the field heating piping, it is advised to use a magnetic or cyclone filter which can remove small particles. Small particles can damage the unit and will not be removed by the standard filter of the heat pump unit.
Checking the water volume and expansion vessel pre-pressure
The unit is equipped with an expansion vessel of 10 litre which has a default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the expansion vessel might need to be adjusted and the minimum and maximum water volume must be checked.
1 Check that the total water volume in the installation, excluding
the internal water volume of the indoor unit, is 10 l minimum. Refer to "12. Technical specifications" on page 50 to know the internal water volume of the indoor unit.
INFORMATION
In most applications this minimum water volume will have a satisfying result.
In critical processes or in rooms with a high heat load though, extra water volume might be required.
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that this minimum water volume is kept even if all the valves are closed.
Example
645321
6
1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut-off valve 7 Collector (field supply) 8 By-pass valve (field supply)
FHL1...3 Floor heating loop
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control the floor
heating loop (field supply)
(1)
7
M1T1M2T2M3
FHL1
FHL2
8
T3
FHL3
EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
2 Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
(1) When the unit is configured for restricted power supply condition mode,
see "Appendix" on page 51.
Installation manual
16
3 Using the table and instructions below, determine if the total
water volume in the installation is below the maximum allowed water volume.
Installation height difference
(a)
7 m
>7 m
No pre-pressure adjustment required.
Actions required:
• pre-pressure must be increased, calculate according to "Calculating the
pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the indoor unit. If the indoor unit is located at the highest point of the installation, the installation height is considered 0 m.
280 l >280 l
Water volume
Actions required:
• pre-pressure must be decreased, calculate according to "Calculating the
pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
Expansion vessel of the unit too small for the installation.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l.
Result:
Since 350 l is higher than 280 l, the pre-pressure must be decreased (see table above).
The required pre-pressure is: Pg = (H/10 + 0.3) bar = (0/10 + 0.3) bar = 0.3 bar
The corresponding maximum water volume can be read from the graph: approximately 410 l.
Since the total water volume (350 l) is below the maximum water volume (410 l), the expansion vessel suffices for the installation.

Setting the pre-pressure of the expansion vessel

When it is required to change the default pre-pressure of the expansion vessel (1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure should only be adjusted by an installer.

Connecting the water circuit

Calculating the pre-pressure of the expansion vessel
The pre-pressure (Pg) to be set depends on the maximum installation height difference (H) and is calculated as below:
Pg=(H/10+0.3) bar
Checking the maximum allowed water volume
To determine the maximum allowed water volume in the entire circuit, proceed as follows:
1 Determine for the calculated pre-pressure (Pg) the
corresponding maximum water volume using the graph below.
2 Check that the total water volume in the entire water circuit is
lower than this value.
If this is not the case, the expansion vessel inside the indoor unit is too small for the installation.
2.5
2
1.5
1
pre-pressure [bar]
0.5
0.3
10
pre-pressure = pre-pressure maximum water volume = maximum water volume
100
500
150 200 250 300 350 400 450
maximum water volume [l]
Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l.
In this example, no action or adjustment is required.
Water connections must be made in accordance with the applicable legislation and the outlook diagram delivered with the unit, respecting the water in- and outlet.
NOTICE
Be careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the piping can cause the unit to malfunction.

6.9. Charging water

1 Connect the water supply to a drain and fill valve (see "5.2. Main
components" on page 11).
2 Make sure the automatic air purge valve is open (at least 2
turns).
3 Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge valves. Air present in the water circuit might cause malfunctioning of the backup heater.
4 Check that the backup heater vessel is filled with water by
opening the pressure relief valve. Water must flow out of the valve.
INFORMATION
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required.
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature). However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might dispose some excessive water through the pressure relief valve.
Water quality must be according to EU directive 98/ 83 EC.
Installation manual
17
Indoor unit for air to water heat pump system
EKHBH/X008BB
4PW62570-1A – 01.2011
Loading...
+ 44 hidden pages