Heating devices that have not been set
up and installed correctly can impair
the function of the heating device and/
or cause serious or fatal injuries to the
user.
▪ Work on the device (such as set-up,
servicing, connection and initial startup) must only be carried out by persons who are authorised who are
authorised and who have successfully completed qualifying technicalor vocational training and who
have taken part in advanced training
sessions recognised by the relevant
responsible authorities for the specific activity. These include, in particular, certified heating engineers,
qualified electricians and HVAC
specialists, who, because of their
professional training and their expert knowledge, have experience in
the professional installation and
maintenance of heating systems,
gas installations and hot water tanks.
WARNING
Disregarding the following safety instructions may result in serious physical injury or death.
▪ This device must only be used by
children aged 8 and above and by
persons with restricted physical,
sensory or mental capabilities or with
a lack of experience and knowledge,
if they are under supervision or if
they have been instructed in the safe
use of the equipment and understand the dangers arising therefrom.
Children must not play with the
device. Cleaning and user mainten-
ance must not be carried out by
children without supervision.
▪ Make up the power supply in accord-
ance with IEC 60335-1, via a separator device which exhibits contact
separation in all poles with a contact
opening distance that provide full
disconnection in accordance with
overvoltage category III.
▪ All the electrical work must only be
carried out by electrically qualified
experts and with consideration of the
local and national regulations, and
the instructions in this manual.
Check that a suitable electrical circuit is being used.
Inadequate capacity of the power circuit or improperly executed connections can cause electrocution or fire.
▪ The customer must install a pressure
relief device with rated over-pressure
less than 0.6MPa (6bar) for connecting a hot water storage tank.
The connected drain line must have
a continuous gradient and a free outlet in a frost-free environment
(seeChap. 4.4).
▪ Water may drip out of the drain line
of the pressure relief device. The
drain opening must be left free to atmosphere.
▪ The pressure relief device must be
operated regularly in order to remove scale deposits and to make
sure it is not blocked.
▪ All work on oil-carrying parts must
only be carried out by heating oil-related qualified experts and with consideration of local and national regulations, and the instructions in this
manual.
▪ Improperly performed work on oil or
flue gas-carrying lines can endanger
life and health and hinder the operation of the heating device.
Installation and operating instructions
4
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
1 General safety precautions
1.1.1Observing the instructions
▪ The original documentation is written in German. All other lan-
guages are translations.
▪ Please read this manual carefully and thoroughly before proceed-
ing with the installation or modification of the heating system.
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system, and all activities described in this
manual and the applicable documents for the installer must be
carried out by an approved installer.
This manual provides all the necessary information for installation,
start-up and maintenance, as well as basic information on operation
and settings. Please see the attached documents for a detailed description of operation and control.
All heating parameters needed for smooth operation are already
factory-set. Please refer to other relevant documents for information
on setting the control.
Relevant documents
▪ A2 F :
▪ Operating manual for the operator
▪ RoCon BF: Operating instructions.
▪ When additional components are connected; the associated in-
stallation and operating instructions.
The guides are included in the scope of supply for the individual
devices.
1.1.2Meaning of warnings and symbols
Warnings in this manual are classified according into their severity
and probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or
death
WARNING
Indicates a potentially dangerous situation
Disregarding this warning may result in serious physical injury or death.
CAUTION
Indicates a situation which may cause possible damage
Disregarding this warning can cause damage to property
and the environment, and result in minor injuries.
This symbol identifies user tips and particularly useful information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols:
Electric current
Danger of explosion
Risk of burning or scalding
Risk of poisoning
Validity
Some information in this manual has limited validity. The validity is
highlighted by a symbol.
Observe specified tightening torque (see )
Handling instructions
1 Handling instructions are shown as a list. Actions for which the
sequential order must be maintained are numbered.
è
Results of actions are identified with an arrow.
1.2Safety instructions for installation
and operation
1.2.1General
WARNING
Heating devices that have not been set up and installed
correctly can impair the function of the heating device and/
or cause serious or fatal injuries to the user.
▪ Work on the A2 F (such as set-up, servicing, connection
and initial start-up) must only be carried out by persons
who are authorised and who have successfully completed qualifying technical or vocational training and
who have taken part in advanced training sessions recognised by the relevant responsible authorities for the
specific activity. These include, in particular, certified
heating engineers, qualified electricians and HVAC
specialists, who, because of their professional training and their expert knowledge, have experience in the
professional installation and maintenance of heating systems, gas installations and hot water tanks.
▪ Switch off the main switch and secure it against uninten-
ded switching on when carrying out any work on the A2
F.
▪ Do not leave any tools or other objects inside the device
after finishing installation or maintenance work.
Avoiding danger
A2 F conforms to the state-of-the-art and meets all recognised technical requirements. However, improper use may result in serious
physical injuries or death, as well as property damage. To prevent
such risks, only install and operate the devices:
▪ as stipulated and in perfect condition,
▪ with an awareness of safety and the hazards involved.
This assumes knowledge and use of the contents of this manual, of
the relevant accident prevention regulations as well as the recognised safety-related and occupational health rules.
Before working on the heating system
▪ Only authorised and trained heating technicians may work on the
heating system (such as installation, connection and initial startup).
▪ Switch off the main switch and secure it against unintended
switching on when carrying out any work on the heating system.
▪ Seals must not be damaged or removed.
▪ Make sure that the safety valves comply with the requirements of
EN12828 when connecting on the heating side, and with the re-
quirements of EN12897 when connecting on the domestic water
side.
1.2.2Intended use
The A2 F may only be used for the heating of hot water heating systems. It must only be installed, connected and operated according to
the information in this manual.
The A2 F may only be operated with the integrated circulation pump
and in conjunction with a controller approved by the manufacturer.
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
5
1 General safety precautions
Any other use outside the intended use is considered as improper
and will result in a loss of warranty. The operator alone shall bear responsibility for any resulting damage.
The A2 F is suitable for operation with light heating oil.
Intended use also includes compliance with the maintenance and
service conditions. Replacement parts must at least satisfy the technical requirements defined by the manufacturer. This is the case,
forexample, with original spare parts.
1.2.3Device installation room
▪ Operate A2 F only if sufficient combustion air supply is ensured. If
the A2 F is operated as an ambient air-independent device with a
concentric air/flue gas system (LAS) dimensioned according to the
manufacturer's standard, this is automatically ensured and there
are no further conditions for the installation room. Only this
method of operation is permissible for installation in residential
rooms.
▪ Make sure that there is an outside air opening of at least 150cm
for ambient-air dependent or partial ambient-air independent operation.
▪ Do not operate the A2 F in ambient-air dependent operation in
rooms with aggressive vapours (e.g. hair spray, perchloroethylene, carbon tetrachloride), strong dust formation (e.g. workshop)
or high humidity (e.g. laundries).
▪ Avoid operating conditions that can cause heavy soiling of the
burner. Do not operate the device if temporary heavy dust deposits occur in the area of the air extraction system.
▪ Always ensure the minimum distances to walls and other objects
(see Chap. 4.4.1).
1.2.4Electrical installation
▪ Electrical installations may only be carried out by electrical techni-
cians and in compliance with valid electrical guidelines as well as
the specifications of the responsible energy supply company.
▪ Compare the mains voltage (230V, 50Hz) indicated on the name-
plate with the supply voltage before connecting to the mains.
▪ Before beginning work on live parts, disconnect them from the
power supply (switch off main switch, remove fuse) and secure
against unintentional restart.
▪ Device covers and service panels must be replaced as soon as
the work is completed.
Using filling water and top-up water which does not meet the stated
quality requirements can cause a considerably reduced service life
of the device. The responsibility for this lies solely with the operator.
1.2.6Heating system and sanitary connection
▪ Create a heating system according to the safety requirements of
EN12828.
▪ The sanitary connection for filling the system from the drinking wa-
ter supply network and for connection of a hot water tank must
meet the requirements of EN12897. The requirements of the following must also be observed:
▪ EN1717 – Protection against pollution of potable water installa-
tions and general requirements of devices to prevent pollution
by backflow
▪ EN61770 – Electric appliances connected to the water mains –
Avoidance of backsiphonage and failure of hose-sets
2
▪ EN806 – Specifications for installations inside buildings con-
veying water for human consumption
▪ and, in addition, the country-specific legislation.
1.2.7Fuel
The A2 F is intended exclusively for the use of approved heating oils
(see Chap. 12).
1.2.8Operation
▪ Do not operate the A2 F if the boiler cladding is open.
▪ Only operate the A2 F if all requirements according to the check-
list in Chap. 5.2 are satisfied.
1.2.5Requirements for the heating water
Avoid damage caused by deposits and corrosion: Comply with the
applicable engineering regulations on prevention of corrosion
products and deposits (VDI 2035, BDH/ZVSHK technical information
"Scale formation").
Measures for desalination, softening or hardness stabilisation are
necessary if the filling and top-up water have a high total hardness
(>3mmol/l - total of the calcium and magnesium concentrations, calculated as calcium carbonate).
Minimum requirements regarding the quality of filling and supplementary water:
▪ Water hardness (calcium and magnesium, calculated as calcium
Measures for desalination, softening or hardness stabilisation or
other suitable conditioning measures are necessary to maintain the
required water quality if the filling and top-up water have a high total
hardness or other properties divergent from the minimum requirements.
Installation and operating instructions
6
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
2Handover to operator and
warranty
2.1Instruct the owner
▪ Before you hand over the heating system, explain to the owner
how he/she can operate and check the heating system.
▪ Hand over the technical documentation (at least the operating in-
structions and operating manual) to the operator and advise him
that these documents must be made available at all times and be
stored in the immediate vicinity of the device.
▪ Document the handover by filling out the installation and instruc-
tion forms together with the owner and sign them.
2.2Warranty conditions
The legal guarantee conditions fundamentally apply. Our more extensive warranty conditions can be found in the Internet. Ask your
suppliers if necessary.
There is only an entitlement to warranty services when it can be certified that the annual maintenance work according to chap. 9has
been regularly completed.
2 Handover to operator and warranty
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
7
3 Product description
3Product description
3.1Design and components
Fig.3-1Design and components - view from above
Fig.3-2Design and components - front and rear view
(1)
Fig.3-3Design and components - view without cladding
(1)
(1)
(1)
For legend, see Tab. 3-1
Installation and operating instructions
8
Fig.3-4Design and components - view of lower part
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
(1)
3 Product description
Fig.3-5Design and components with standard equipment -
schematic drawing (hydraulic system)
Fig.3-6Design and components with valve kit - schematic draw-
ing (hydraulic system)
(1)
(1)
Fig.3-7Design and components with Smart start kit - schematic
drawing (hydraulic system)
(1)
ItemDesignationItemDesignation
AView from front21Heating circulation
pump
BRear view22Condensate siphon
1Heating flow23Supply air connection
2Heating return flow24oil filter
3Storage tank – char-
25MAG connection
ging flow (optional)
4Storage tank – char-
26Recirculation tube
ging return flow (optional)
5Oil connection27KFE cock
6flue gas connection28Flue gas temperature
3-way valve (distribution valve, hot water/
heating)
12Optional flue gas con-
3UVB13-way mixer valve
nection
13Condensate drainFLSFlowSensor
14Feed-through for ex-
ternal diaphragm expansion vessel
MAGDiaphragm expansion
vessel (accessory/
provided by the customer)
(1)
For legend, see Tab. 3-1
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
9
3 Product description
ItemDesignationItemDesignation
15Blow-off line from
safety valve
16Cable penetrationSTBKSafety temperature
17Burnertv1Inflow temperature
18Boiler control panelt
19Boiler main body with
heat and sound insulation
20Type plate with manu-
facturer's number
Tab.3-1Legend for Fig. 3-1 to Fig. 3-7
DSPressure sensor
limiter
sensor
v2
t
R
Internal mixer sensor
Return flow temperat-
ure sensor
3.2Brief description
The A2 F is a completely pre-assembled oil condensing unit.
Operating mode
The A2 F is constructed so it can be operated independent of the
ambient air (concentric flue gas/air supply pipes). All flue gas carrying parts are surrounded by combustion air. The burner suctions the
combustion air directly in through an installation shaft or a doublewalled flue gas pipe. This operating mode is recommended by us
and has many advantages:
▪ The heating room does not need any ventilation opening into the
open air and therefore does not cool down.
▪ Lower energy consumption.
▪ Additional energy recovery in the flue gas pipe through preheating
the combustion air.
▪ Contamination from the environment of the burner are not suc-
tioned in. The heating room can thus be used as a workspace,
laundry room, etc. at the same time.
▪ Possible to install in loft areas or attic.
▪ Possible to install in garages.
The heating water is first fed into the boiler body at the lowest position. There, it is heated in counterflow via the adjacent combustion
chamber and several stainless steel heat exchanger tubes that pass
through the boiler body. The heated heating water is fed from the upper connection of the boiler body to the inflow connection of the
boiler housing. The combustion gases flow through the heat exchanger tubes into the boiler body from top to bottom after flame reversal in the combustion chamber. These tubes contain turbulators
that improve heat transfer to the heating water.
The condensate produced is fed into the sewage system via the condensate siphon and then via a plastic pipe. Optionally, it can be
neutralised via the optional condensate box.
Smart Start function
The Smart Start function was developed to avoid frequent switching
of the burner when the requirement for room heating is low.
If the optional Smart Start kit (two steplessly controllable 3-way
valves) is installed in the A2 F, the Smart Start function can be used.
The requirement for room heating is therefore temporarily covered
by the heat stored in the hot water storage tank. The Smart Start
function remains active until the next request for hot water generation is pending.
The Smart Start function is automatically controlled by the RoCon
BF controller.
Safety management
The entire safety management of the A2 F is carried out by the electronic controller. If there is water shortage, oil shortage or undefined
operating conditions, there is a safety shutdown. A corresponding
fault signal provides an engineer with all the necessary information
for troubleshooting.
Electronic controller
An electronic digital controller combined with the burner "intelligent"
firing unit automatically controls all heating and hot water functions
for the direct heating circuit and an optional storage tank charging
circuit.
One or more mixed circuits can be connected and controlled via optionally connected mixer modules RoCon M1.
All settings, displays and functions are carried out by the integrated
RoCon BF controller. The display and the operating elements make
operation easy.
A digital room controller (RoCon U1) is optionally available for
greater comfort. It can be used as a remote control and room thermostat.
The controller can be connected to the Internet via the optional gateway (RoCon G1). This enables remote control of the A2 F by mobile
phones (by app).
Condensing technology
Condensing technology makes optimum use of the energy contained
in the heating oil. The flue gas is cooled down in the boiler – and in
the flue system with ambient air-independent operation in the concentric flue gas system – to the extent that the temperature is below
the dew point. A part of the water vapour generated through combustion of the heating oil thus condenses. The condensation heat is
fed to the heating, as opposed to low-temperature boilers, which enables efficiency rates of over 100% (based on the lower heating
value).
Fuel
The A2 F can be operated with standard or low-sulphur heating oil
(sulphur content <50ppm). It is equipped for the combustion of heating oil with biogenic components. Mixing of bio-heating oil up to
10% (B10) is permitted without further conversion.
INFORMATION
We recommend using EL low sulphur heating oil, in order
to achieve the highest efficiency and to keep the maintenance expenditure low.
Condensate treatment unit
The condensate produced during combustion in an oil condensing
boiler has a pH-value of 1.8 – 3.7 when using heating oil that is not
low in sulphur.
The optional condensate preparation unit fulfils the following functions:
▪ Removal of floating particles in the settling basin
▪ Neutralisation of the condensate in the Hydrolit-MG filter material
When using low-sulphur heating oil, the condensate can usually be
drained off into the sewage network without neutralisation. Please
refer to the regulations of the local water authorities.
Installation and operating instructions
10
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
4 Set-up and installation
A
736
A
606
271
262
1360
134
263140
140
80
0
0
110
293
368
442
516
540
50
124
R
H
≥ 40 cm
≥ 40
cm
≥ 40 cm
≥ 200 cm
CA
FG
RV
(e)
(e)
(d)
(d)
(f)
(a)
1
(a)
4
(a)
3
(b)
5
(c)
6
(a)
2
C
93
C
53
C
53
C
83
C
33
C
33
B
23
B
23P
B
33
B
53
B
53P
4Set-up and installation
WARNING
Devices which have been set-up and installed incorrectly
may not operate properly and can be a health and safety
risk endangering human life.
▪ Only authorised and trained heating technicians may set
up and install the A2 F.
4.1Dimensions and connection
dimensions
4.2Different set-ups
Fig.4-1Installation dimensions
ItemDesignation
R
H
Tab.4-1Legend for Fig. 4-1
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Minimum room height (see Chap. 4.4.1)
INFORMATION
To avoid increased cooling losses, we recommend the installation of SKB gravity brakes (accessory) or the syphoning of the connection line.
Fig.4-2Different set-ups
ItemDesignation
1-6Installation versions (for a description, see Chap. 4.2.1
to Chap. 4.2.3)
CASupply air (combustion air)
FGFlue gas
RVRear ventilation
aInstallation version for ambient air-independent opera-
tion (flue gas/supply air concentric)
bInstallation version for conditional ambient air-independ-
ent operation (flue gas/supply air separate)
cInstallation version for ambient air-dependent mode
dLongitudinally ventilated shaft with a fire-resistance
period of 90minutes (30minutes in low height residen-
tial buildings). Observe country-specific regulations for
The A2 F is designed for ambient air-independent operation. It is
fitted as standard with a concentric flue gas /air supply pipe DN
80/125.
INFORMATION
In some cases, the resonance in the flue gas system can
amplify the noise at the mouth of the flue gas duct. The
noise level can be effectively reduced by using a silencer
(accessory: DN80: E8MSD or DN110:E11MSD).
Installation and operating instructions
11
4 Set-up and installation
INFORMATION
Use of the A2 F in ambient air-independent operation with
a concentric flue gas/air supply line is recommended by us.
If possible, choose this installation version!
In partial ambient air-independent operation (separate flue
gas/air supply lines with a single-walled connecting pipe)
and ambient air-dependent operation the installation room
must have a ventilation opening of at least 150cm2 to the
outside.
As such, the installation room will not be assigned the
heated building envelope under the Energy Conservation
Ordinance (EnEV), which downgrades the energy rating of
the building. This reduces the overall energy efficiency of
the building according to European Directive 2010/31/EU:
EPBD.
The following descriptions of the different set-ups includes
information regarding the possible classification of the
devices based on the type of flue gas routing (equipment
type) in accordance with EN15035 and CEN/TR1749.
Chap. 4.2.4 and Chap. 4.5 must also be observed in this
regard.
The described SETs are accompanied by separate assembly instructions.
The SETs mentioned below are recommendations for the
appropriate combination of the required individual components for the typical installation variants.
4.2.1Room-air independent operation
INFORMATION
When devices are installed in residential rooms only one of
the installation versions 1 to 4 is permissible.
Installation version 1
The A2 F is connected to the chimney or an installation shaft with
the concentric SetK LAS connection line.
▪ The combustible air supply from the outside runs through the
chimney or through an installation shaft.
▪ The flue gas discharge to the outside runs through the same shaft
as the air supply.
▪ Minimum vertical distance between flue gas exit and roof ridge:
40cm.
▪ Device type C
Installation version 2
The A2 F is placed directly below the roof. Connection with SETL.
▪ The combustible air supply and flue gas discharge run through a
concentric dual pipe.
▪ The combustible air supply from the outside runs through the
outer ring-shaped gap of the dual pipe, and the flue gas discharge
to the outside runs through the inner tube.
▪ Minimum vertical distance between flue gas exit and roof surface:
40cm.
▪ Minimum height of the flue gas pipe: 2m.
▪ Device type C
Installation version 3
The A2 F is not placed directly below the roof. The dual pipe for the
combustible air supply and flue gas duct runs through the roof truss.
▪ The combustible air supply and the flue gas discharge run through
a concentric dual pipe (as in Installation version 2).
▪ In the area of the roof truss, the dual pipe for the combustible air
supply and the flue gas duct must be laid through a protective pipe
with sufficient fire resistance or be structurally separated from the
roof truss.
93x
33x
▪ Device type C
33x
Installation version 4
The A2 F is connected with the SETK LAS connection line to the
SETG outer wall system.
▪ The combustible air supply from the outside runs through the ring-
shaped gap in the dual pipe, through the outer wall (suction from
below).
▪ The flue gas discharge to the outside runs through a concentric
pipe, through the outer wall and then up to at least 40cm over the
roof surface. In the external area, the outer air gap serves as heat
insulation for the flue gas pipe.
▪ Device type C
53x
If the wall feed through is at a height of less than one
meter above the ground, we recommend routing the combustion air through a separate air supply pipe (mounting
height: approx. 2m). W8ZR or W11ZR
Installation version 5
If, for constructional or legal/regulatory reasons, the shaft used for
the flue gas routing is not suited for also routing the combustion air
at the same time, the combustion air must be routed through a separate line.
If the flue gas connection line to the shaft is double-walled and is
surrounded by the combustion air, there are no additional ventilation
requirements on the installation room.
▪ Combustion air supply is routed from the outside via the ad-
equately sealed supply line which is connected directly to the concentric exterior pipe of the connection line. The supply line should
be sized so that the suction resistance at nominal output isless than 50Pa.
▪ The connection line between the A2 F and the installation shaft is
completely concentric and surrounded by combustion air.
▪ Device type C
, C
53x
83x
INFORMATION
The A2 F is suitable for installation and operation within
garages. Requirements:
▪ Ambient air-independent operation,
▪ A durable operating manual placed in a very visible
place near the device,
▪ The construction must include a protective device
against mechanical damage (vehicle!) for the entire system (e.g. bracket or deflector).
▪ Permanently frost-protected.
Installation variant 7 (not shown)
If permitted by local regulations, the A2 F can be connected to
SETW2 to the horizontal flue gas outlet.
▪ The combustible air supply and flue gas discharge run through a
concentric dual pipe.
▪ The combustible air supply runs from the outside through the
outer ring-shaped gap of the dual pipe (supply air inlet via the intake grille of the wall feed through) and the flue gas discharge to
the outside runs through the inner tube.
▪ Minimum height of the flue gas pipe: 2m
▪ Observe local regulations regarding minimum distances of win-
dows or other building openings.
▪ Device type C
13x
4.2.2Partial ambient air-independent mode
Alternative to installation variant 5
The A2 F is operated with separately routed supply air/flue gas lines
(2-pipe system).
Installation and operating instructions
12
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
4 Set-up and installation
▪ The combustion air supply from the outside runs through an ad-
equately sealed air supply line through the external wall. The supply line should be sized so that the suction resistance at nominal
output is less than 50Pa.
▪ Flue gas discharge to the outside runs through the chimney or an
installation shaft. If the connection line between the A2 F and the
installation shaft is single-walled or not completely surrounded by
combustion air, a ventilation opening to the outside of at least
150cm2 is required.
Appropriate measures must be taken to ensure that the burner
cannot be operated if the ventilation opening is closed.
▪ The installation shaft where the flue gas line runs must be rear
ventilated. There must be a rear ventilation opening of at least
150cm2 in the lower area.
The cross-section of this installation shaft must be sized so that
between the external wall of the flue gas line and the internal
face of the installation shaft the following minimum distance
must be maintained:
▪ with a rectangular shaft cross-section: 2cm
▪ with a round shaft cross-section: 3cm.
The rear ventilation opening must not be located in rooms where a
negative pressure is generated (e.g. by controlled apartment ventilation, a tumble-drier etc.).
▪ Device type C
, C
53x
83x
4.2.3Ambient air-dependent mode
Installation version 6
The A2 F can also be connected dependent on the ambient air.
Thereby, only the inner flue gas pipe (plastic pipe Ø 80mm) of the
concentric air-flue gas pipe is connected to the flue gas line. The
device sucks the combustible air from the installation room through
the ring-shaped gap of the jacket pipe.
The same conditions apply to the flue gas routing into the open air,
shaft dimensioning and rear ventilation as in Chap. 4.2.2. A ventila-tion opening into the open air of at least 150cm2 is mandatory.
▪ Device type B23, B
, B33, B53, B
23P
53P
INFORMATION
In some cases, the resonance in the flue gas system can
amplify the noise at the mouth of the flue gas duct. The
noise level can be effectively reduced by using a silencer
(DN80: E8MSD or DN110: E11MSD).
4.2.4Additional information on device type in
accordance with CEN/TR1749
INFORMATION
We basically recommend installing the A2 F regardless of
the room air (device type C) and with concentric air/flue
gas guides (see Chap. 4.2.1). Other permissible applications of the air intake and flue gas discharge are not described in detail in these instructions.
Special requirements that exist for such systems based on
EN15035 are listed below.
C13:
▪ Horizontal openings for flue gas outlet and supply air inlet
▪ Openings within a square of 50cmx50cm
C33:
▪ vertical openings for flue gas outlet and supply air inlet
▪ Openings within a square of 50cmx50cm
▪ Spacing of opening levels <50cm
C43:
▪ Connection of more than one device to a common air/flue gas sys-
tem that is part of the building
▪ vertical opening for flue gas outlet and supply air inlet
▪ Openings within a square of 50cmx50cm
▪ Spacing of opening levels <50cm
▪ Suitable calculated dimensioning verification required because va-
cuum prevails in the case of the flue gas inlet into the common air/
flue gas system. The flue gas must be discharged with a natural
draught.
▪ For data on dimensioning, see Chap. 14.1.
▪ Condensate flow from the common air/flue gas system must not
be discharged through the device.
C53:
▪ Vertical opening for flue gas outlet
▪ Opening for supply air inlet into different pressure area possible.
▪ Openings must not be installed on opposite walls of the building.
C63:
▪ Connection to a separately approved and marketed flue gas/sup-
ply air system if allowed by national law.
▪ This allows all other described installation forms to the realised for
device type C if the conditions of the respective installation form
are met.
▪ If the dimensions of the system used differ from those described in
this manual (seeChap. 4.5.1), a suitable arithmetical dimension-
ing verification is required.
▪ For data on dimensioning, see Chap. 14.1.
▪ Properties and possible applications of the pipe system:
▪ Minimum requirements according toChap. 4.5.1 fulfilled
▪ Condensate flow into the device allowed with single assign-
ment, not allowed with multiple assignment.
▪ Maximum combustion air temperature: 60°C
▪ Maximum allowed flue gas recirculation current under wind con-
ditions: 10%
C83:
▪ Connection to one or more devices to a vacuum flue gas system
that is part of the building.
▪ Vertical opening for flue gas outlet
▪ Air intake via associated second
(2)
line.
▪ Opening for supply air inlet into different pressure area possible.
▪ Suitable arithmetical dimensioning verification required because
vacuum prevails in the case of the flue gas inlet into the common
air/flue gas system.
▪ For data on dimensioning, see Chap. 14.1.
▪ Properties and application options of the flue gas system:
▪ Minimum requirements according toChap. 4.5.1 fulfilled (except
for pressure class).
▪ Condensate flow into the device allowed with single assign-
ment, not allowed with multiple assignment.
C93:
▪ as for C33, but
▪ Connection of the supply air pipe to an existing vertical shaft (e.g.
chimney) that is part of the building.
(2)
If the air supply pipe was used beforehand as a flue gas pipe or chimney of an oil or solid fuel furnace, it should be cleaned
prior to use as an air supply pipe.
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
13
4 Set-up and installation
▪ The cross-section of this installation shaft must be sized so that
between the external wall of the flue gas line and the internal
face of the installation shaft the following minimum distance
must be maintained:
▪ with a rectangular shaft cross-section: 2cm
▪ with a round shaft cross-section: 3cm
B23:
▪ Flue gas pipe without flow safeguard - vacuum operation
▪ Properties and application options of the flue gas pipe:
▪ Minimum requirements according toChap. 4.5.1 fulfilled.
▪ Opening for flue gas outlet to the outside
▪ Supply air directly from installation room (seeChap. 4.2.3).
▪ If the dimensions of the flue gas line differ from those described in
this manual, a suitable arithmetical dimensioning verification is required.
▪ For data on dimensioning, see Chap. 14.1.
B
:
23P
▪ as for B23, but underpressure operation
B33:
▪ Connection of more than one device to a common flue gas system
(vacuum flue gas shaft).
▪ Vertical opening for flue gas outlet.
▪ Supply air directly from installation room (seeChap. 4.2.3).
▪ Suitable arithmetical dimensioning verification required because
vacuum prevails in the case of the flue gas inlet into the common
air/flue gas system.
▪ For data on dimensioning, see Chap. 14.1.
▪ Parts under overpressure of the connection pipe must be conduc-
ted as a concentric pipe system.
B53:
▪ as for B33, but connection to associated flue gas pipe including flue
gas opening.
B
:
53P
▪ as for B53, but overpressure operation.
Spacings of brackets and offsets
The distance of the supports of the flue gas line must not be more
than 2m in the vertical area.
In the horizontal area of the connecting lines, the brackets must be
installed so tightly that there is no risk of any gradient in the horizontal area in which condensate could accumulate.
If an offset is required in the vertical part of the flue gas line, the
maximum angle must not exceed 45°. In the case of external installation, the height above the last bracket must not exceed 1.5m.
4.3Transport and delivery
WARNING
Lifting or displacing the A2 F by the panels can damage
the device.
▪ Only carry the A2 F with the cover removed, in pairs us-
ing the recessed grips provided for this purpose in the
rear panel of the device and on the boiler frame.
The A2 F is delivered on a pallet. All industrial trucks, such as lifting
trucks and forklift trucks, are suitable for transporting it.
Scope of delivery
▪ A2 F (preassembled),
▪ Boiler cladding (see Fig. 4-3)
▪ Screws for boiler cladding
▪ Documentation package
▪ Cable tie
▪ oil filter
▪ External temperature sensor
Fig.4-3Scope of delivery standard accessories package
ItemDesignation
ABoiler cladding – side panel
BBoiler cladding – side panel
CBoiler cladding – cover
DBoiler cladding – front panel
ESmall accessories: Screws, 4-pin circuit board con-
nector, strain relief clip (3x)
FCable tie
GExternal temperature sensor
Hoil filter
IDocumentation
Tab.4-3Legend for Fig. 4-3
For A2 F accessories, see price list.
Installation and operating instructions
14
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
4 Set-up and installation
4.4Installing the oil condensing boiler
4.4.1Selecting the installation site
The installation site of the A2 F must meet the minimum requirements below (see alsoChap. 1.2.3).
Installation height
▪ The bottom edge of the condensate connection on the device
must be higher than the drain height of the condensate drain
hose, otherwise condensation can accumulate in the drain. Install
a pedestal if necessary.
▪ Small unevennesses of the installation surface can be com-
pensated using the height-adjustable feet (see Chap. 4.4.2).
Installation area
▪ The base must be level and smooth and have a sufficient ground
load-bearing capacity of 500kg/m² plus safety factor. Install a
pedestal if necessary.
▪ Observe the installation dimensions (see Chap. 4.1).
Installation room
▪ There are no special conditions for ventilation of the installation
room for ambient air-independent operations (using a concentric
air/flue gas system).
▪ In partial ambient air-independent and ambient-dependent mode,
the installation room must have a ventilation opening of at least
150cm2 to the outside. If the flue gas line is routed to the outside
through an installation shaft, it must be rear-ventilated (seeChap.
4.2.2).
▪ For partial ambient air-independent and for ambient air-dependent
mode, the installation room must be free from aggressive vapours
(e.g. hair spray, perchloroethylene, carbon tetrachloride), heavy
dust formation and high atmospheric humidity (e.g. laundry).
▪ Outdoor installation is not permissible.
▪ Installation in an explosion-risk environment is not permissible.
▪ The electronic controller may never be exposed to the effects of
the weather.
▪ The A2 F must be protected from frost.
INFORMATION: HEATING OIL STORAGE IN THE INSTALLATION ROOM
The construction specifications allow, as a rule, hot oil storage of up to 5000litres (according to the firing ordinance of
the country) if the building is a Building Class 1 construction and the installation room is not a room were people
live or work.
Installation in the attic
If the A2 F is installed in the attic and the oil is stored in the rooms
below it, the oil pump of the burner is generally not sufficient. If the
vacuum on the suction side exceeds the value 0.4bar, the oil must
be supplied to the burner through a separate pump. We strongly recommend using a suction unit.
The minimum height of the flue gas conduit must be 2m in order
to avoid malfunction at start or during operation of the burner.
WARNING
If using a pressure aggregate, oil could escape if there is a
failure. Escaping oil can cause serious damage to the environment.
▪ Install the boiler on a water-proof tray and secure by a
float switch (connection via additional plug strip).
▪ Use only a metallic filter cup (never Plexiglas).
▪ Ambient air-independent operation,
▪ A durable operating manual placed in a very visible place near the
device,
▪ The construction must include a protective device against mech-
anical damage (vehicle!) for the entire system (e.g. bracket or deflector).
▪ Permanently frost-protected.
Surface temperatures, minimum distance
Fig.4-4Minimum distances for installation
ItemDesignation
R
H
aMinimum lateral wall distance: 0.50m
Tab.4-4Minimum distance dimensions
▪ In ambient air-independent mode with rated power, the design
does not allow temperatures >70°C on any component outside
the device panels. Therefore, no minimum distance is specified for
components made with flammable materials.
▪ A minimum distance of 50mm between the flue gas line and flam-
mable components should be maintained in a partial ambient airindependent and ambient air-dependent operation (separate flue
gas/air supply pipes).
▪ Do not store or use easily inflammable and highly combustible
materials in the immediate vicinity of the A2 F (minimum distance
1m).
▪ When installing the device as described in Fig. 4-4, we recom-
mend maintaining the minimum distances from walls and ceilings
in order to perform maintenance and repair work without excessive installation effort.
▪ When installing in a niche, the A2 F can be placed on the left side,
directly against the niche wall, if the area in front of the A2 F is
freely accessible.
Minimum room height: 1.80m
Installation in garages
Provided local regulations do not generally prohibit the installation of
boilers in garages, the A2 F is completely suitable for installation and
operation within garages. Requirements:
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
15
4 Set-up and installation
4.4.2Installing the device
Precondition
▪ The installation site complies with applicable country-specific reg-
ulations and meets the minimum requirements described in Chap.
4.4.1.
Installation
1 Remove the packaging completely (edge protection as well) and
dispose of it in an environment-friendly manner.
2 Installing the A2 F at the installation site. Only lift or move the
device by the recessed grips provided for this purpose.
3 Position the A2 F in such a way that the connection points of the
oil hoses or mounting position of the oil filter, the ducting of the
heating pipes and the flue gas pipe can be operated without restrictions.
4 Check the horizontal position and correct installation height of
the A2 F. Slight unevennesses can be compensated by four
height-adjustable feet.
Height adjustment
Fig.4-5Height-adjustable feet
▪ Adjust the height of the A2 F using the screw with an Allen key
SW 5mm or a 17mm open-ended spanner.
4.5Air/flue gas system (LAS)
4.5.1General instructions for the flue gas
system
DANGER: RISK OF POISONING
There will be a risk of poisoning caused by flue gas escaping within enclosed rooms that are inadequately ventilated.
▪ Install only approved flue gas systems.
▪ Depending on the installation variant, the stipulated
ventilation and rear ventilation must be ensured (see
Chap. 4.2).
Minimum requirements
For the design and measurement of the flue gas system, the respectively valid national fire code ordinance or the country-specific
regulations and EN15287 must be observed.
Basically, for the flue gas system, you can use each flue gas pipe
according to EN14471 with EU label, which meets the following minimum requirements:
▪ Suitable for heating oil.
▪ Suitable for flue gas temperatures of at least 120°C (temperature
class T120 or higher).
▪ Suitable for at least 200Pa overpressure (pressure class P1 or
H1).
▪ Humidity-resistant (condensation resistance class W).
▪ Sufficiently corrosion-resistant (corrosion resistance class 2).
The properties of the flue gas system must be identifiable on the installed system (nameplate in the installation room).
The associated assembly instructions must be observed for installing
the flue gas and supply air holding system components or their
means of attachment.
▪ Each flue gas line must be installed with a suitable test ad-
apter for checking and setting the combustion values. The
LAS construction sets contain one test adapter each (D8PA)
▪ Depending on the local building regulations, inspection compon-
ents must be installed in the required locations.
Type of connections
▪ On the side or at the rear (SETK)
▪ Direct roof feed-through (SETL)
▪ Straight, directly at the rear (SETH), optional connection on the
back of the device
For further details and connection dimensions for the three variants
of the flue gas pipe, see Chap. 4.5.3.
Installation position and piping height
▪ The maximum permitted flue gas counter pressure is 200 Pa. The
pressure loss in the supply line must not exceed 50Pa.
▪ Angle of entry of the flue gas pipe into the chimney or installation
shaft: at least3°.
▪ Avoid horizontal sections in the connection line or keep them as
short as possible.
▪ Slope for horizontal sections of the flue gas line: at least3°.
Counter-slopes are not permissible at any point in the flue gas
line so that condensate can drain off without restriction.
▪ If the more than 3 deflections >45° are needed for the flue gas
line, the maximum height for the flue gas line reduces by at least
1m per deflection (flue gas calculations may be needed).
▪ If the horizontal connecting piece is extended to more than 2m,
the maximum permitted height of the flue gas duct is reduced by
exactly that length.
▪ Flexible flue gas lines may not be used in horizontal connection
sections.
▪ Straight pipe sections must be fastened at intervals of <2m using
suitable wall brackets. Suitable spacers must be used within vertical shafts.
Flue gas system resistance
A minimum resistance in the flue gas pipe is required for a safe
burner start and stable setting values.
1 Switch on the burner (see Chap. 14.2).
2 Measure the resistance with a differential pressure gauge on the
flue gas measurement section between the flue gas and supply
air measurement openings (differential pressure for all A2 F at
least 0.2mbar).
è
If the differential pressure is not reached at the maximum speed
of the burner blower, a silencer must be installed (E8MSD)
The Tab. 4-5 shows the maximum permissible height of the flue gas
line to ensure that the A2 F can be operated in the nominal output
range.
Installation and operating instructions
16
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
4 Set-up and installation
Installation ver-
sion
(according to im-
age 9)
(3) (4)
1
(5)
2
(5)
3
(5) (4)
4
(3) (4)
5
(3) (4)
6
Max. permissible height of the flue gas line
DN80
A2 F 18HA2 F 24HA2 F 32H
81218
101420
101420
7710
252525
252525
Tab.4-5Maximum height for the flue gas line in m
Any restriction on the output range may require a recalculation of the
maximum permitted height for the flue gas duct. The characteristics
for the flue gas calculation can be obtained from Fig. 4-6 and the
Chap. 14.
Connection
INFORMATION
We recommend use of the associated LAS construction
sets (see Chap. 4.5.3). They satisfy all requirements and
are also fitted with special acid-proof seals.
The associated assembly instructions must be observed
for installing the flue gas and supply air holding system
components or their means of attachment.
1 Connect the A2 F to the flue gas system inside the installation
room (Fig. 4-1).
2 Place the nameplate of the flue gas duct in the installation room.
Fig.4-6Flue gas mass flow in relation to the burner load (all
types)
ItemDesignation
m
AG
Flue gas mass flow
PBurner loading
Tab.4-6Legend for Fig. 4-6
The flue gas mass flow of the system depends on the set burner output of the A2 F.
4.5.2Connecting a flue gas line
INFORMATION
The specialised company carrying out the work must come
to an agreement with the district chimney sweep before beginning the work. Even in regions where it is not legally
specified, we recommend documenting the participation of
the district chimney sweep on a form.
Requirements
▪ The flue gas system fulfils the requirements described inChap.
4.5.1.
▪ The flue gas system fulfils any required other national or regional
safety requirements.
▪ The A2 F is installed correctly.
Fig.4-7Connection dimensions - flue gas pipe
ItemDesignation
ABoiler connection
BFlue gas connection
Tab.4-7Legend for Fig. 4-7
Connection sideConnectionConnection dimen-
sion in mm
A Boiler sideA1 Flue gas DN 80
Collar
A2 Supply air DN 125
Collar
B Flue gas sideB1 Flue gas DN 80Inner diameter = 80.0
B2 Supply air DN 125 Inner diameter =
Tab.4-8
Connection dimensions for the LAS connection of the A2
Inner diameter = 80.4
+0.8
Inner diameter =
-0.5
127.0
+0.3
+0.3
126.0
F
INFORMATION
In some cases, the resonance in the flue gas system can
amplify the noise at the mouth of the flue gas duct. The
noise level can be effectively reduced by using a silencer
(E8MSD or E11MSD).
(3)
Shaft cross-section of DN80: 135mm x 135mm
(4)
A horizontal connecting cable with a length of 2m and an 87° deflection are taken into account
(5)
Concentric flue gas/supply line DN 80/125
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
17
4 Set-up and installation
130
10080
215
014
009
004
013
003
002
015
016
017
040
(PA)
040
(PA)
039052031050
038
052050
α
1335
1835
041
040
(PA)
038
3696
082
(3x)
094
(3x)
081
090
101103
252
W
A
215
088
098
WA
094 W8 WH 40-60 mm
( 155079.0059)
095 W8 WHV14 43-137 mm
( 155079.0087)
096 W8 WHV23 137-231 mm
( 155079.0088)
097 W8 WHV32 231-325 mm
( 155079.0089)
091 W8 WKV15 55 - 147 mm
( 155079.0084)
092 W8 WKV24 147 - 239 mm
( 155079.0085)
093 W8 WKV33 239 - 331 mm
( 155079.0086)
*If neededWHWall bracket
PATest adapterWHVExtension for wall bracket
RRInspection pipeWKVExtension for external wall bracket
SDSlanting roof coverZRSupply air pipe (mounting height for supply air inlet ≥1m
above the ground)
FDFlat roof coveringWAWall distance
MSDSilencer
Tab.4-9Legend for flue gas system construction sets
Additional kits
▪ Flue gas connection to a shaft system (rigid flue gas line SETE or
flexible flue gas line SET-O)
▪ Flue gas connection for external wall line (SET-G)
If necessary, additionally needed concentric LAS pipes for increased
roof or ceiling heights, single wall PP pipes for flue heights of more
than 10m or additional accessory components must be ordered.
The three-digit numbers in assist in finding individual compon-
ents in the price list.
4.6Water connection
The connections of the A2 F are on the top of the device. Optionally,
a valve kit or a Smart Start kit can be installed in the boiler to connect a hot water tank.
Important information
CAUTION
If the A2 F is connected to a heating system with steel
pipes, radiators or non-diffusion-proof floor heating pipes,
slurry and swarf could enter the boiler body and cause
blockages, local overheating or corrosion.
▪ Rinse supply lines before filling the device.
▪ Rinse out the heat distribution network (in the existing
heating system).
▪ Install a dirt filter or sludge separator in the heating re-
turn flow (see Chap. 1.2.6).
CAUTION
Corrosion may be caused by air entering the heating water
network and by a quality of the heating water that does not
comply with the requirements in accordance with Chap.
1.2.5. Corrosion products (particles) thus created may clog
pumps and valves and cause malfunctions.
▪ Device may not be connected by permeable, flexible
lines.
INFORMATION
In accordance with EN12828 a safety valve that limits the
maximum permissible operating pressure in the heating
system must be installed on or in the immediate vicinity of
the heat generator. There may not be any hydraulic blocking elements between the heat generator and the safety
valve.
Any steam or heating water which may escape must be
drained by a suitable blow-off line with constant gradient in
a frost-protected, safe and observable manner.
A suitable safety valve is integrated in the A2 F as standard (see Fig. 3-4, item29). The blow-off line, which is led
out of the boiler as a transparent hose, must be extended
by the customer and connected to the waste water system.
A suitably-sized diaphragm expansion vessel (available as
an accessory) preset for the heating system must be connected to the A2 F. There may not be any hydraulic blocking elements between the heat generator and the diaphragm expansion vessel.
If the diaphragm expansion vessel is to be connected outside A2 F, the internal connection (Fig. 3-3 and Fig. 3-4,
item 25) must be sealed on site.
4.6.1Connecting hydraulic lines
1 Establish hydraulic connections on the A2 F.
▪ Observe the specified tightening torque.
▪ Connect the water for filling or refilling the heating system as
specified by EN1717/EN61770 to avoid contamination of
drinking water by return flow.
INFORMATION
The A2 F is equipped with a pressure sensor. The system
pressure in monitored electronically and can be displayed
with the device switched on.
Nevertheless, we recommend installing a mechanical pressure gauge between the A2 F and the diaphragm expansion vessel, for example.
▪ Install the pressure gauge so that it is easy to see when
filling.
1 Connect the blow-off line and diaphragm expansion vessel ac-
cording to EN12828.
▪ Any steam or heating water which may escape must be drained
by a suitable blow-off line with constant gradient in a frost-protected, safe and observable manner.
▪ Connect a suitably dimensioned and preset diaphragm expan-
sion vessel for the heating system. There may not be any hydraulic blocking elements between the heat generator and the
safety valve.
▪ Position the diaphragm expansion vessel in an easily access-
ible place (maintenance, parts replacement).
▪ Lay the ducting in such a way that the housing parts of the A2 F
can be inserted easily after installation.
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation and operating instructions
19
4 Set-up and installation
INFORMATION
There must not be any hydraulic blocking elements
between the heat generator and the diaphragm expansion
vessel that can be operated by the system operator. The
location (Fig. 3-3 and Fig. 3-4, item 25) provided for the
connection of an integrated diaphragm expansion vessel
(accessory) is not closed when delivered. If the diaphragm
expansion vessel is connected outside the heat generator,
this point must be sealed on site.
1 Carefully insulate pipework against heat loss and to avoid con-
densation (insulation thickness at least 20mm).
– Water shortage protection: The pressure and temperature
monitoring of the A2 F switches off the oil condensing boiler
safely in the event of a lack of water and locks it. No additional water shortage protection is needed in the construction.
– Avoid damage caused by deposits and corrosion: Ob-
serve the requirements on the heating water (see Chap.
1.2.5).
4.6.2Connect the condensate drain
The condensate resulting from the cooling of the combustion gases
in the boiler and in the flue gas system has a pH-value of 1.8 – 3.7. If
necessary, it must be neutralised in accordance with the guidelines
of the German Wastewater Association (DWA A251) before being
discharged into the public sewage system.
INFORMATION
Depending on the stipulations of the community waster water regulations, the neutralisation can be dispensed with, if
the condensing boiler is operated exclusively with ELlow-sulphur heating oil.
The condensate is conducted via the condensate siphon mounted
on the flue gas elbow under the boiler body and then discharged into
the sewage system.
If the condensate has to be neutralised before discharge into the
sewage system, a condensate box (accessory) can be installed in
the boiler instead of the condensate siphon.
3 The complete outlet must not be lockable and must discharge
the condensation and any medium leaking due to damage (heating water) outwards visibly (e.g. hose to flow drain or transparent
outlet pipe).
4 In order to avoid accumulation in the flue gas connection of the
boiler, make sure that no additional siphon is formed from the
condensate drain line to the connection to the wastewater line.
5 Fill the condensate siphon or condensate box. To do so, pour in
water via the inspection opening of the flue gas pipe.
6 Check the condensate drain section for leakage.
4.7Electrical connection
DANGER: RISK OF ELECTROCUTION
Touching live parts can result in an electric shock and
lead to potentially fatal injuries and burns.
▪ Before beginning work on live parts, disconnect all of
the systems circuits from the power supply (switch off
external main switch, disconnect fuse) and secure
against unintentional restart.
▪ Establishment of the electrical connection and work on
electrical components should only be performed by elec-trical technicians in compliance with valid standards
and guidelines as well as the specifications of the energy supply company and the instructions in this manual.
▪ Never make constructional changes to connectors or
other electrical equipment components.
▪ Device covers and service panels must be replaced
as soon as the work is completed.
All A2 F control and safety devices are connected ready for use and
tested. Modifications on the electrical installation are dangerous and
prohibited. The operator alone shall bear responsibility for any resulting damage.
Mains connection, external temperature sensor and other optional
applications must still be connected to the boiler control panel.
4.7.1Opening the boiler control panel and
establishing electrical connections
1 Check the supply voltage (~230V, 50Hz).
2 Set the mains switch of the A2 F to "Off" (see Fig. 3-2, item 7).
3 Switch off the circuit breaker in the junction box of the domestic
power supply.
4 Remove the front panel of the boiler control panel (Fig. 4-10).
Fig.4-9Connection of the condensate drain line
The condensate box can be mounted under the boiler frame and
connected to the flue gas connection piece of the boiler. The connection to the wastewater network is designed for HT pipe DN 50.
1 Condensation drain line (not included) with free inflow to the
drains connection.
2 Lay the condensate drain sloping down from the boiler, so that
condensation will not accumulate in the flue gas pipe.
INFORMATION
If it is not possible to connect the condensate drain to the
waste water system with a sufficient gradient in the installation room, a condensate lifting pump must be installed on
site.
Installation and operating instructions
20
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.