Daikin CXTQ36TASBLUA, CXTQ24TASBLUA, CXTQ48TASBLUA, CXTQ60TASBLUA Installation Manual

MODELS
Cased Coil Unit
CXTQ24TASBLUA CXTQ36TASBLUA CXTQ48TASBLUA CXTQ60TASBLUA
INSTALLATION MANUAL
SYSTEM Inverter Air Conditioners
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST, SERVICE OR REPAIR (HEREINAFTER EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT
MPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR
I
OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
. THE
MANUFACTURER WILL NOT BE RESPONSIBLE
.
, “
. IN
ADDITION, IN
SERVICE
. IF
,
”)
THE
YOU SERVICE
.
Read these instructions carefully before installation. Keep this manual in a handy place
English
for future reference. This manual should be left with the equipment owner.
Lire soigneusement ces instructions avant l’installation.
Français
Conserver ce manuel à portée de main pour référence ultérieure. Ce manuel doit être donné au propriétaire de l’équipement.
Español
Lea cuidadosamente estas instrucciones antes de instalar. Guarde este manual en un lugar a mano para leer en caso de tener alguna duda. Este manual debe permanecer con el propietario del equipo.
IOD-4028A 11/2017
English
1
Installation manualVRV SYSTEM Inverter Air Conditioners
CONTENTS
1. SAFETY INSTRUCTIONS ...................................................2
2. BEFORE INST ALLA TION ...................................................4
3. SELECTING INST ALLATION SITE.....................................5
4. INST ALLA TION LOCA TION................................................5
5. REFRIGERANT PIPING WORK .........................................8
6. DRAIN PIPING WORK.......................................................10
7. DUCT WORK ....................................................................11
8. ELECTRICAL WIRING WORK .........................................11
9. FIELD SETTING ................................................................17
10. ACCESSORIES.................................................................21
11. TEST RUN .........................................................................22
1. SAFETY INSTRUCTIONS
Read these “SAFETY INSTRUCTIONS for Installation” care­fully before installing an air conditioner or heat pump. After completing the installation, make sure that the unit operates properly during the start-up operation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference. Always use a licensed installer or contractor to install this product. Improper installation can result in water or refriger­ant leakage, electrical shock, fire, or explosion.
Refrigerant gas is heavier than air and replaces oxygen. A massive leak can lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death. For a refrigerant leak, contact your licensed professional contractor.
Do not ground units to water pipes, gas pipes, telephone wires or lightning rods since incomplete grounding can cause a severe shock hazard, resulting in severe injury or death. Additionally, grounding to gas pipes could cause a gas leak resulting in a potential explosion caus­ing severe injury or death.
If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas may produce toxic gas if it comes in contact with fire. Exposure to this gas could cause severe injury or death.
After completing the installation work, ensure the re­frigerant gas does not leak anywhere in the system.
Due to the risk of explosions that can cause serious injury or death, do not install the unit in an area where flammable materials are present.
Safely dispose of all packing and transportation materi­als in accordance with federal/state/local laws or ordi­nances. Plastic packing materials used for transporta­tion may cause injuries or death by suffocation.
Nails and other metal or wood parts used for packing may cause wounds or other injuries.
All phases of the field-installation, including, but not lim­ited to, electrical, piping, safety, etc., must be in accor­dance with manufacturer’s instructions and must com­ply with national, state, provincial and local codes.
Only a licensed professional contractor should install this equipment and must be done in accordance with this installation manual. Improper installation could lead to leaks and electric shock or fire.
When installing the unit in a small room, ensure the re­frigerant concentration does not exceed allowable safety limits. Excessive accidental refrigerant leaks in a closed ambient space can lead to oxygen deficiency.
Do not use any device that is not design-certified by Daikin for use with this unit. Serious property damage, personal injury, reduced unit performance and/or haz­ardous conditions may result from the use of such non­approved devices.
Install the air conditioner or heat pump on a foundation strong enough that it can withstand the weight of the unit. A foundation of insufficient strength may result in the unit falling and causing injuries.
When installing, take into account strong winds, ty­phoons or earthquakes. Improper installation may re­sult in the unit falling and injuries.
Make sure that a separate power supply circuit is pro­vided for this unit and that all electrical work is carried out by qualified personnel according to local, state, and national regulations. An insufficient power supply ca­pacity or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secured, that specified wires are used and that no external forces act on the terminal connections or wires. Improper connections or instal­lation may result in fire.
When wiring, position the wires so that the control panel and cover can be securely fastened. Improper position­ing of the control panel and cover may result in electric shocks, fire or the terminals overheating.
If the control panel cover is not installed properly, dust or water may enter the control panel causing fire or elec­tric shock.
Before touching electrical parts, turn off the unit.
2 English
This equipment can be installed with a Ground-Fault Cir­cuit Breaker (GFCI). Although this is a recognized mea­sure for additional protection, with the grounding sys­tem in North America, a dedicated GFCI is not required.
When installing or relocating the system, keep the refriger­ant circuit free from substances (such as air) other than the specified refrigerant (R-410A). Any presence of air or other foreign substance in the refrigerant circuit can cause an ab­normal pressure rise or rupture, resulting in injury.
Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur.
Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluo­rescent lamps (inverter or rapid start types). Install the indoor unit far away from fluorescent lamps as much as possible.
Indoor units are for indoor installation only. Outdoor units can be installed either outdoors or indoors. This unit is for indoor use.
Do not install the air conditioner or heat pump in the following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced (for example, in a kitchen).
Plastic parts may deteriorate and fall off or result
in water leakage.
Do not touch the switch with wet fingers. Touching switch with wet fingers can cause electric shock.
To prevent injury, children should never play on or around the unit.
Do not touch the refrigerant pipes during and immedi­ately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal tem­perature or, if you must touch them, be sure to wear proper gloves.
Install drain piping to proper drainage. Improper drain piping may result in water leakage and property dam­age.
Insulate piping to prevent condensation.
Be careful when transporting the product.
Do not use a charging cylinder. Using a charging cylin­der may cause the refrigerant to deteriorate.
Refrigerant R-410A in the system must be kept clean, dry and tight.
(a) Clean and Dry — Foreign materials (including min-
eral oils such as SUNISO oil or moisture) should be prevented from getting into the system.
(b) Tight — R-410A does not contain any chlorine, does
not destroy the ozone layer, and does not reduce the earth’s protection again harmful ultraviolet ra­diation. R-410A can contribute to the greenhouse effect if it is released. Therefore take proper mea­sures to check for the tightness of the refrigerant piping installation. Read the Refrigerant Piping (section 5) and follow the procedures.
• Since R-410A is a blend, the required additional refrig­erant must be charged in its liquid state. If the refriger­ant is charged in a state of gas, its composition can change and the system will not work properly.
The indoor unit is for R-410A. See the catalog for indoor models that can be connected. Normal operation is not possible when connected to other units.
(b) Where corrosive gas, such as sulfurous acid gas,
is produced. Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and cause the unit to mal­function.
(d) Where flammable gas may leak, where there is car-
bon fiber or ignitable dust suspension in the air, or where volatile flammables such as thinner or gaso­line are handled. Operating the unit in such condi­tions can cause a fire.
Take adequate measures to prevent the outside unit from being used as a shelter by small animals. Small animals making contact with electrical parts can cause malfunc­tions, smoke, or fire. Instruct the customer to keep the area around the unit clean.
Install the power supply and control wires for the indoor and outdoor units at least 3.5 feet away from televisions or radios to prevent image interference or noise. Depend­ing on the radio waves, a distance of 3.5 feet may not be sufficient to eliminate the noise.
When dismantling the unit, treatment of the refrigerant, oil and additional parts must be done in accordance with the relevant local, state and national regulations.
Do not use the following tools that have been previously used with conventional refrigerants: gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge or refrigerant re­covery equipment.
If the conventional refrigerant and refrigerator oil are mixed in R-410A, the refrigerant may deteriorate.
This air conditioner or heat pump is an appliance that should not be accessible to the general public.
As design pressure is 450 psi, the wall thickness of field­installed pipes should be selected in accordance with the relevant local, state and national regulations.
English
3
2. BEFORE INST ALLATION
Installation must be performed by a licensed professional
contractor. Improper installation could lead to leaks and elec­tric shock or fire.
Do not use any device that is not design-certified by Daikin for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous condi­tions may result from the use of such non-approved devices.
Read and understand this manual before installing the in­door unit.
Be sure to mount an air filter (part to be procured in the field) in the suction air passage of the connected gas furnace in order to prevent water leaking, etc.
The accessories needed for installation must be kept until the installation work is completed. Do not discard them.
1. Decide upon a line of transport.
2. Leave the unit inside its packaging while moving, until reach-
ing the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
2.2 OPTIONAL ACCESSORIES
This indoor unit requires one of the operation remote controls listed below.
Remote Controller Wired type BRC1E73*, BRC2A71 Wireless type** BRC4C8 2
* If BRC1E73 is not used a KRCS01-2UA sens or must be us ed.
** Wireless ty pe controllers will only allow 2­st age airflow
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DUR­ING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.
Be sure to verify the type of R-410A refrigerant to be used before installing the unit.
(Using an incorrect refrigerant will prevent normal opera­tion of the unit.)
For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
2.1 PRECAUTIONS
Be sure to instruct customers how to properly operate the unit (operating different functions, and adjusting the tempera­ture) by having them carry out operations themselves while looking at the operation manual.
Do not install in locations where the air contains high levels of salt such as that near the ocean and where voltage fluctu­ates greatly (as in factories) or in vehicles or vessels.
4 English
ITEMS TO BE CHECKED AFTER COMPLETION OF WORK
Items to be checked Are the indoor and outdoor
units fixed firmly? Is the refrigerant leak test
finished? Is the unit fully insulated? Condensate may drip.
Does the drainage flow smoothly? Does the power supply voltage corres pond to that shown on the name plate? Are the wiring an d piping correct?
Is the unit safely grounded? Is wiri ng size according to
specifications? Is something blocking the air outlet or inlet of either the indoor or outdoor units?
Is the refrigerant piping length and additional refrigerant char ge documented?
Also review the SAFETY CONSIDERATIONS.
If not properly done, what is likely to occur
Units may drop,vibrate or make nois e
This may result in insufficient cooling.
Condensate may drip.
The unit may malfunction or the components b urn out.
The unit may malfunction or the components b urn out. Incompl ete grounding may result in electric shocks. The unit may malfunction or the components b urn out.
This may result In insufficient cooling.
The total refrigerant charge of the system will not be available for future reference.
Check
ITEMS TO BE CHECKED AT TIME OF DELIVERY
I tem s to be ch ecked Chec k Did you hand the operation manual over to your
customer? Did you explain about operations while showing
the operation manual to your customer? Did you explain to your customer how to maintain
and clean loc al pr ocu rements suc h as the air filter, suction grille, and air outlet grille?
Did you hand manuals of local procur ements (in case equipped) over to your customer?
3. SELECTING INST ALLATION SITE
In cases where the unit is installed in a space where the humidity may exceed 86°F and 80%RH, reinforce the insu­lation on the unit body.
Use glass wool or polyethylene foam as insulation to ensure the thickness is more than 2” and fits inside the installation space opening.
Select an installation site where the following conditions are ful­filled and meets with your customer’s approval.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the supports are strong enough to bear the indoor unit weight.
Where piping between indoor and outdoor units is pos­sible within the allowable limit. (Refer to the installa­tion manual for the outdoor unit.)
If a return-air duct is not installed, carefully select the place and method of product installation so that air flow into the product will not be blocked.
When installing this unit in an area that may become wet (such as crawl spaces), elevate the unit with a sturdy, non-porous material.
Refer to section 4.1 for clearance requirements. Con­sult all appropriate regulatory codes when determin­ing final clearance.
4. INST ALLATION LOCATION
NOTE: These cased coils are designed for indoor installation
only. The CXTQ**T product line may be installed in upflow or downflow orientations as shown in Figures 2 and 3.
The unit may be installed in upflow or downflow orientation as shipped (refer to specific sections for more information).
NOTE: Condensation may form on the product during COOL
operation. It is recommended to install a secondary drain pan
(field supplied). If installed above a finished living space, a secondary drain pan should be installed under the entire unit. The drain pan’s con­densate line should be routed to a location where the user will see the condensate discharge. In many regions, the installation of a secondary drain pan is required by building code. Follow­ing and adhering to these and all applicable local, state, and/or national codes is your responsibility as the installer.
In areas where the ambient operating conditions reach above 80%RH, the manufacturer recommends that additional insula­tion be applied to the outside of the cabinet.
4.1 CLEARANCES
Refrigerant lines must be routed depending upon the configura­tion of the unit, in order to maintain the required 24” minimum clearance for service.
In installations that may lead to physical damage (i.e. a garage), it is advised to install a protective barrier to prevent such dam­age. Always install units so that a positive slope in condensate line of 1/100 is allowed.
NOTE: Furnace application requires that the installer MUST re­view and strictly follow ALL furnace installation clearance guide­lines. Failure to do so may result in property/equipment dam­age, personal injury or death.
CONSULT ALL APPROPRIATE REGULATORY CODES WHEN DETERMINING FINAL CLEARANCES.
English
5
UPFLOW
Figure 2
DOWN FLOW
Figure 3
6 English
4.2 FILLER PLA TES
Filler plates are supplied on all 17.5, 21 & 24.5 inch chassis to be used for adapting the unit to a furnace one size smaller. If the plenum and furnace openings are the same size, the filler plates must be removed. See Figure 1.
DPICX-B
Insulation Kit
DPICX-C
Insulation Kit
DPICX-D
Insulation Kit CXTQ24TASBLU CXTQ48TASBLU CXTQ60TASBLU CXTQ36TASBLU
INSULATION KIT
Table 1
4.5 SEALING ALONG THE PANEL GAP
IMPORTANT NOTE: To prevent cabinet “sweating”, apply field
provided insulation tape along all joining surfaces between the coil, gas furnace, duct work, and panels. See Figure 4.
Filler plate
Figure 1
4.3 UPFLOW/DOWNFLOW INST ALLATION
No field modifications are mandatory.
Do not use the manifold or flowrator to pull the coil assembly out. Doing so may result in braze joint damage and leaks.
4.4 INSULATION KIT
IMPORTANT NOTE: To prevent coil pan “sweating”, a coil insu-
lation kit (DPICX) is recommended. Insulation kits are available through your local Daikin distributor. The DPICX is not supplied with the cased coil and is recommended to mini­mize pan sweating in applications where operating conditions exceed 80%RH.
See Table 1 for the correct DPICX and follow the instructions provided with the kit for installation.
Figure 4
Apply insulation tape
English
7
5. REFRIGERANT PIPING WORK
s
Observe the requirements listed below for refrigerant tubing sizes.
Model
CXTQ24/36/48/60 3/8" 5/8"
Tubing Size
Liquid Gas
Using a tube cutter, cut off the factory spun end of both the liquid and gas line piping.
5.2 Disconnect Internal Control Wiring
Remove the left panel.
Disconnect the Control Panel wiring from component wiring using the EEV and Thermistor connectors located on the outside of the control panel. See Figure 6.
Completely insulate both the liquid and gas refrigerant piping in order to prevent condensation and possible water damage.
Failing to insulate the pipes may cause leaking or burns. Be sure to use the insulation which can withstand such tempera­tures of 250°F (120°C) or more. Reinforce the insulation on the refrigerant piping according to the installation environment. If environmental conditions may reach 86°F and 80%RH, con­densate may form on the surface of the insulation. To prevent condensate leakage, reinforce the refrigerant piping insulation according to the installation environment.
Follow the points below.
Use a tube cutter and flaring block suitable for the type or refrigerant.
To prevent dust, moisture or other foreign matter from infil­trating the piping, either pinch the end or cover it with tape.
Do not allow anything other than the designated refrigerant (such as air) to get mixed into the refrigerant circuit. If any refrigerant gas leaks while working on the unit, immediately ventilate the room.
5.1 Cut off the spin closure.
This coil is shipped containing gas under 150 P.S.I.G.
Release pressure from the gas piping pressure-release device before initiating piping work
Cap
Sharp object
(2) Push
After the work is finished, Replace cap.
(1) Remove
To prevent component wiring damage, the Control Panel should be removed from the right front panel. Removing the control panel will assist in allowing the wiring to be safely pushed through the panel wire-way. The control panel is detached from the left front panel by removing the four mounting screws located on the four corners of the control panel.
Internal W iring Connector (EEV and Thermister)
Figure 6
Detail
Pressure rele ase device
Gas piping
Liquid piping
Front pane l
Figure 5
8 English
Loading...
+ 16 hidden pages