8.2.2To re-install the front grille .......................................... 11
8.2.3To re-install the front panel ......................................... 11
9 Commissioning12
9.1To perform a test run................................................................. 12
9.1.1To perform a test run using the user interface............ 12
1About the documentation
1.1About this document
INFORMATION
Make sure that the user has the printed documentation and
ask him/her to keep it for future reference.
Target audience
Authorised installers
INFORMATION
This appliance is intended to be used by expert or trained
users in shops, in light industry, and on farms, or for
commercial and household use by lay persons.
WARNING
Make sure installation, servicing, maintenance, repair and
applied materials follow the instructions from Daikin and, in
addition, comply with applicable legislation and are
performed by qualified persons only. In Europe and areas
where IEC standards apply, EN/IEC 60335-2-40 is the
applicable standard.
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪ General safety precautions:
▪ Safety instructions that you MUST read before installing
▪ Format: Paper (in the box of the indoor unit)
▪ Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
▪ Installer reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Always observe the following safety instructions and regulations.
Unit installation (see "5Unit installation"[44])
WARNING
CVXM-A and FVXM-A Floor Standing range is allowed to
be combined only with systems with total refrigerant
amount <1.842 kg. Therefore in case of combination with
outdoor units 3MXM40N8 or 3MXM52N8, the total liquid
refrigerant piping length of the installation MUST be ≤30m.
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
3 About the box
1×2×1×1×1×1×
2×1×2×1×
edbcaf
1×2×2×
jklih
g
m
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
CAUTION
For walls containing a metal frame or a metal board, use a
wall embedded pipe and wall cover in the feed-through
hole to prevent possible heat, electrical shock, or fire.
Piping installation (see "6Piping installation"[49])
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ Use the flare nut fixed to the unit.
▪ To prevent gas leakage, apply refrigeration oil only to
the inside of the flare. Use refrigeration oil for R32.
▪ Do NOT reuse joints.
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ NEVER install a drier to this R32 unit to guarantee its
lifetime. The drying material may dissolve and damage
the system.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
3About the box
3.1Indoor unit
Electrical installation (see "7Electrical installation"[410])
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
3.1.1To remove the accessories from the
indoor unit
1 Remove the accessories located at the bottom of the package.
Spare SSID sticker is located on the unit.
a Installation manual
b Operation manual
c General safety precautions
d Mounting plate (attached to the unit)
e Titanium apatite deodorising filter
f Drain hose
g Insulation piece
h User interface
i User interface holder
j Dry battery AAA.LR03 (alkaline) for user interface
k Spare SSID sticker (attached to the unit)
l Screws for fixing drain hose
m White head screws "To re-install the front grille"[411]
▪ Spare SSID sticker. Do NOT throw away the spare sticker. Keep
it in a safe place in case it is needed in the future (e.g. in case the
front grille is replaced, attach it to the new front grille).
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
Installation manual
3
4 About the unit
≤60
(65)
≤27°
(mm)
≥467
≥50≥50
AB
(105)
≤60
4About the unit
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Following symbols may occur on the indoor unit:
SymbolExplanation
Measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
4.1About the wireless LAN
For detailed specifications, installation instructions, setting methods,
FAQ, declaration of conformity and the latest version of this manual,
visit http://www.onlinecontroller.daikineurope.com.
INFORMATION
▪ Daikin Industries Czech Republic s.r.o. declares that
the radio equipment type inside of this unit is in
compliance with Directive 2014/53/EU.
▪ This unit is considered as combined equipment
according to the definition of Directive 2014/53/EU.
4.1.1Precautions when using the wireless LAN
Do NOT use near:
▪ Medical equipment. E.g. persons using cardiac pacemakers or
defibrillators. This product may cause electromagnetic
interference.
▪ Auto-control equipment. E.g. automatic doors or fire alarm
equipment. This product may cause faulty behaviour of the
equipment.
▪ Microwave oven. It may affect wireless LAN communications.
2 Search for Daikin Residential Controller.
3 Follow the directions on the screen to install.
5Unit installation
5.1Preparing the installation site
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
5.1.1Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70dBA.
WARNING
CVXM-A and FVXM-A Floor Standing range is allowed to
be combined only with systems with total refrigerant
amount <1.842 kg. Therefore in case of combination with
outdoor units 3MXM40N8 or 3MXM52N8, the total liquid
refrigerant piping length of the installation MUST be ≤30m.
To install the Daikin Residential Controller
application
1 Open:
▪ Google Play for appliances using Android.
▪ App Store for appliances using iOS.
A Front view
B Side view
▪ Do not install the unit more than 60mm above the floor.
▪ Wall insulation. When conditions in the wall exceed 30°C and a
relative humidity of 80%, or when fresh air is inducted into the
wall, then additional insulation is required (minimum 10 mm
thickness, polyethylene foam).
▪ Wall or floor strength. Check whether the wall or the floor is
strong enough to support the weight of the unit. If there is a risk,
reinforce the wall or the floor before installing the unit.
5.2Opening the indoor unit
5.2.1To remove the front panel
1 Slide both sliders in the direction of the arrows until they click.
Installation manual
4
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
2 Open the front panel and remove the string.
4×
b
a
c
b
c
b
a
1
2
3
b
a
c
c
b
a
b
ABC
3 Remove the front panel.
5.2.2To remove the front grille
1 Remove the front panel. See "To remove the front panel"[44].
2 Remove the 4 screws, remove the grille from 4 tabs on the top
and remove the front grille while pulling it toward you.
5 Unit installation
a Screw
b Sensor securing plate
c Metal plate cover
To remove the electrical wiring box cover
1 Open the terminal block.
2 Remove 1 screw from the electrical wiring box.
3 Unhook the 2 tabs on the electrical wiring box cover and
remove it.
a Front grille
b Tabs
5.2.3To open the terminal block and remove
the electrical wiring box cover
To open the terminal block
1 Remove the front grille.
2 Remove 1 lower screw.
3 Lift the sensor securing plate.
4 Move the metal plate cover down and then towards you to
remove it.
a Screw
b Wiring box cover
c Tabs
5.3Mounting the indoor unit
5.3.1To install the indoor unit
Installation options
There are 3 possible type of installation for the indoor unit.
A Floor (exposed) installation
B Wall (exposed) installation
C Half concealed installation
a Mounting plate
b Skirting board
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
Installation manual
5
5 Unit installation
(mm)
634.5
750
006
300
200
285
115
159
238
689
a
a
a
a
159
a
a
75
06
75
45
Ø65
Ø65
45
b
c
75
75
54
f
e
AB
C
54
45
d
6×
82
166
06≤
(mm)
634.5
750
006
553
300
200
285
115
238
b
b
b
b
75
06
75
45
Ø65
Ø65
45
d
e
75
75
54
h
g
54
45
f
AB
C
cc
a
5×
Floor-standing installation
5‒1 Indoor unit installation drawing: Floor-standing installation
A Front view
B Side view
C Top view
a Screw hole 6×
b Left-back piping hole location
c Right-back piping hole location
d Left/right piping hole location
e Left-bottom piping hole location
f Right-bottom piping hole location
1 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
2 Open the front panel and remove the front grille (see
"5.2Opening the indoor unit"[44]).
3 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
4 Secure the unit to the wall and floor using 6 screws M4×25L
(field supply).
Wall-mounted installation
5‒2 Indoor unit installation drawing: Wall-mounted installation
A Front view
B Side view
C Top view
a Mounting plate
b Screw hole 4×
c Floor
d Left-back piping hole location
e Right-back piping hole location
f Left/right piping hole location
g Left-bottom piping hole location
h Right-bottom piping hole location
6 Temporarily secure the mounting plate on the wall.
7 Make sure the mounting plate is level.
8 Mark the centres of the drilling points on the wall.
9 Secure the mounting plate on the wall using 5 screws M4×25L
(field supply).
5 When the complete installation is finished, attach the front panel
and the front grille in their original position.
Installation manual
6
10 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
11 Open the front panel and remove the front grille (see
"5.2Opening the indoor unit"[44]).
12 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
13 If necessary for the skirting board, remove the slit portion on the
bottom frame.
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
a
b
a Bottom frame
≤60
4×
a
5
4
30
f
734~740
170
350
70
200
593~595
170350
de
c
c
a
AB
(mm)
a
a
75
54
Ø60
Ø60
54
75
C
159
238
689
159
bb
06
75
75
54
h
g
634.5
115
285
b
b
b
b
300
6×
b Slit portion
14 Align the unit using the alignment symbol on the
mounting plate: 375mm from the alignment symbol to the each
side (unit width 750mm), 487mm from the alignment symbol to
the bottom of the unit.
15 Hook the unit on the mounting plate and secure the unit to the
wall using 4 screws M4×25L (field supply).
a Alignment symbol
16 When the complete installation is finished, attach the front panel
and the front grille in their original position.
5 Unit installation
Half-concealed installation
5‒3 Indoor unit installation drawing: Half-concealed installation
A Front view
B Side view
C Top view
a Extra filler board
b Screw hole 6×
c Hole
d Left-back piping hole location
e Right-back piping hole location
f Right/left piping hole location
g Left-bottom piping hole location
h Right-bottom piping hole location
17 Make a hole in the wall as illustrated above.
18 Install the extra filler board (field supply) in accordance with the
space between the unit and the wall. Make sure there is no gap
between the unit and the wall.
19 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
20 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
21 Open the front panel, remove the front grille, remove the top
and side casings (see "5.2Opening the indoor unit"[44]).
22 Secure the unit to the extra filler board and to the floor using 6
screws M4×25L (field supply).
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
23 When the complete installation is finished, attach the front panel
and the front grille in their original position.
Installation manual
7
5 Unit installation
Ø65
a
b
c
a
c
d
d
b
5.3.2To drill a wall hole
CAUTION
For walls containing a metal frame or a metal board, use a
wall embedded pipe and wall cover in the feed-through
hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing
material (field supply), in order to prevent water leakage.
1 Bore a 65 mm large feed-through hole in the wall with a
downward slope towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
a Wall embedded pipe
b Putty
c Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do
NOT forget to seal the gap with putty.
5.3.3To remove the slit portions
For side piping (left/right) and bottom piping (left/right) slit portions
must be removed. Remove slit portions according to where the
piping is taken out.
2 Remove an burrs along the cut section using a half round
needle file.
5.3.4To provide drainage
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Use rigid polyvinyl chloride pipe with 20 mm nominal
diameter and 26mm outer diameter.
NOTICE
▪ Install the drain hose with a downward slope.
▪ Traps are NOT permitted.
▪ Do NOT put the end of the hose in water.
▪ Drain hose. Drain hose (accessory) is 220 mm long and with
18mm outer diameter on the connecting side.
▪ Extension hose. Use rigid polyvinyl chloride pipe (field supply)
with 20 mm nominal diameter as extension hose. When
connecting an extension hose, use a polyvinyl adhesive agent for
a Bottom frame
b Slit portion for side piping on the front grille (same on the
other side)
c Slit portion for side piping on the bottom frame (same of
the other side)
d Slit portion for the bottom piping
1 Cut off the slit portion using nippers.
Installation manual
8
glueing.
▪ Condensation. Take measures against condensation. Insulate
the complete drain piping in the building.
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
1 Push the drain hose (accessory) as far as possible over the
drain socket and fix it with 1 screw (accessory).
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
d
1×
c
a
b
a Drain pan
100
a
≥50
220
150
100
(mm)
c
d
b
a
t
Ø
ØiØ
i
t
ØpØ
p
b Drain socket
c Drain hose (accessory)
d Screw (accessory)
2 Check for water leaks (see "To check for water leaks"[49]).
3 Insulate the indoor drain socket and drain hose with ≥10mm
insulation material to prevent condensation.
4 Connect the drain piping to the drain hose. Insert the drain hose
≥50mm, so it will not be pulled out of the drain pipe.
6 Piping installation
6Piping installation
6.1Preparing refrigerant piping
6.1.1Refrigerant piping requirements
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant.
INFORMATION
Additional refrigerant charge is NOT allowed in case of
combination of the outdoor unit 3MXM40N8 or 3MXM52N8
with the indoor units CVXM-A and/or FVXM-A. The total
piping length MUST be ≤30m.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30mg/10m.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
ClassPipe outer diameter (mm)
Liquid pipingGas piping
20~35Ø6.4Ø9.5
50Ø6.4Ø12.7
a Drain hose (accessory)
b Vinyl chloride drain pipe (VP-30) (field supply)
c Reducer (field supply)
d Vinyl chloride drain pipe (VP-20) (field supply)
To check for water leaks
1 Remove the air filters.
2 Gradually pour approximately 1l of water in the drain pan, and
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
6.1.2Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
6.4mm (1/4")8~10mm≥10mm
9.5mm (3/8")12~15mm≥13mm
12.7mm (1/2")14~16mm≥13mm
Insulation inner
diameter (Øi)
Insulation thickness
(t)
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
least 20 mm to prevent condensation on the surface of the
insulation.
Installation manual
9
7 Electrical installation
a
b
c
d
a
b
a
a
e
b
e
c
b
a
d
c
d
b
a
b
c
6.2Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
6.2.1To connect the refrigerant piping to the
indoor unit
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
▪ Pipe length. Keep refrigerant piping as short as possible.
1 Connect refrigerant piping to the unit using flare connections.
2 Insulate the refrigerant piping on the indoor unit as follows:
a Gas pipe
b Gas pipe insulation
c Liquid pipe
d Liquid pipe insulation
NOTICE
Make sure to insulate all refrigerant piping. Any exposed
piping might cause condensation.
3 Close the slit on the refrigerant pipe connection and secure it
with a tape (field supply). Make sure there are no gaps.
4 Wrap the slit and the end of the insulation of the connected
refrigerant piping with insulation piece (accessory). Make sure
there are no gaps.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
7.1Specifications of standard wiring
components
Component
Interconnection cable
(indoor↔outdoor)
4-core cable
1.5mm²~2.5mm²
andapplicable for
220~240V
H05RN-F (60245 IEC 57)
7.2To connect the electrical wiring to
the indoor unit
1 Open the terminal block. See "5.2Opening the indoor unit"[44].
2 Strip the wire ends approximately 15mm.
3 Match wire colours with terminal numbers on indoor and
outdoor unit’s terminal blocks and firmly screw wires to the
corresponding terminals.
4 Connect the earth wires to the corresponding terminals.
a Refrigerant pipe connection
b Refrigerant piping (field supply)
c Slit
d Tape
e Insulation piece (accessory)
a Terminal block
7Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Installation manual
10
5 Pull the wires to make sure that they are securely attached,
then retain the wires with the cable clamp.
6 Make sure that the wires do not come in contact with the metal
parts of the heat exchanger.
7 In case of connecting to an optional adapter, see "7.3 To
connect optional accessories (wired user interface, central user
interface, wireless adapter, etc.)"[411].
b Electrical component block
c Cable clamp
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
8 Finishing the indoor unit installation
a
b
a
b
c
e
f
2×
2×
b
a
cc
7.3To connect optional accessories
(wired user interface, central user
interface, wireless adapter, etc.)
1 Remove the electrical wiring box cover. See "5.2 Opening the
indoor unit"[44].
2 Connect the optional adapter wire to the S21 connector. To
connect the optional adapter wire to the option, refer to the
installation manual of the optional adapter.
3 Lead the wire as shown in the figure below.
a S21connector
B Optional adapter wire
4 Close the electrical wiring box cover. See "8.2 To close the
indoor unit"[411].
2 Attach the front metal cover and fix it with the screw.
3 Close the sensor securing plate.
8.2.2To re-install the front grille
1 Attach the front grille to the original position.
2 Secure the front grille in 4 tabs.
3 Secure with the 2 original screws on the top part and with the 2
white head screws (accessory) on the bottom part.
a Front grille
b 4 tabs
c White head screws (accessory)
8.2.3To re-install the front panel
1 Insert the front panel into the grooves of the unit (3 places) and
attach the string.
8Finishing the indoor unit
8.1To finish the indoor unit
1 After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap the refrigerant pipes and the interconnection
cable with insulation tape. Overlap at least half the width of the
tape with each turn.
2 Pass the pipes through the wall hole and seal the gaps with
putty.
8.2To close the indoor unit
8.2.1To close the electrical wiring box and
1 Hook the electrical wiring box onto the 2 tabs, close it, and fix it
with 1 screw.
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
installation
installation
a Interconnection cable
b Gas pipe
c Gas pipe insulation
d Insulation tape
e Liquid pipe
f Liquid pipe insulation
close the terminal block
2 Close the front panel and slide both sliders until they click.
3 Push on the sides of the front panel to make sure the front
panel is securely fixed.
Installation manual
11
9 Commissioning
,
A
INDOOR
OUTDOOR
9Commissioning
NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.
9.1To perform a test run
Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating
mode.
Prerequisite: Test run should be performed in accordance with the
operation manual of the indoor unit to make sure that all functions
and parts are working properly.
1 In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3 minutes after the unit is turned
OFF.
9.1.1To perform a test run using the user
interface
1 Press to switch the system on.
Symbol MeaningSymbol Meaning
Circuit breakerProtective earth
ConnectionProtective earth (screw)
Connector
EarthRelay connector
Field wiringShort-circuit connector
FuseTerminal
Indoor unitTerminal strip
Outdoor unitWire clamp
Residual current
device
Symbol ColourSymbolColour
BLKBlackORGOrange
BLUBluePNKPink
BRNBrownPRP, PPLPurple
GRNGreenREDRed
GRYGreyWHTWhite
YLWYellow
Rectifier
2 Press the middle of and simultaneously.
3 Press twice to choose and confirm selection by pressing
.
Result: on the display indicates that the test run is selected. Test
run operation will stop automatically after about 30 minutes.
4 To stop operation sooner, press the ON/OFF button.
10Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
11Technical data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
11.1Wiring diagram
11.1.1Unified wiring diagram legend
For applied parts and numbering, refer to the wiring diagram on the
unit. Part numbering is by Arabic numbers in ascending order for
each part and is represented in the overview below by "*" in the part
code.
SymbolMeaning
A*PPrinted circuit board
BS*Pushbutton ON/OFF, operation
switch
BZ, H*OBuzzer
C*Capacitor
AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*, NE
D*, V*DDiode
DB*Diode bridge
DS*DIP switch
E*HHeater
FU*, F*U, (for characteristics,
refer to PCB inside your unit)
FG*Connector (frame ground)
H*Harness
H*P, LED*, V*LPilot lamp, light emitting diode
HAPLight emitting diode (service
HIGH VOLTAGEHigh voltage
IESIntelligent eye sensor
IPM*Intelligent power module
K*R, KCR, KFR, KHuR, K*MMagnetic relay
LLive
L*Coil
L*RReactor
M*Stepper motor
M*CCompressor motor
M*FFan motor
M*PDrain pump motor
M*SSwing motor
Connection, connector
Fuse
monitor green)
Installation manual
12
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
SymbolMeaning
MR*, MRCW*, MRM*, MRN*Magnetic relay
NNeutral
n=*, N=*Number of passes through ferrite
core
PAMPulse-amplitude modulation
PCB*Printed circuit board
PM*Power module
PSSwitching power supply
PTC*PTC thermistor
Q*Insulated gate bipolar transistor
(IGBT)
Q*CCircuit breaker
Q*DI, KLMEarth leak circuit breaker
Q*LOverload protector
Q*MThermo switch
Q*RResidual current device
R*Resistor
R*TThermistor
RCReceiver
S*CLimit switch
S*LFloat switch
S*NGRefrigerant leak detector
S*NPHPressure sensor (high)
S*NPLPressure sensor (low)
S*PH, HPS*Pressure switch (high)
S*PLPressure switch (low)
S*TThermostat
S*RHHumidity sensor
S*W, SW*Operation switch
SA*, F1SSurge arrester
SR*, WLUSignal receiver
SS*Selector switch
SHEET METALTerminal strip fixed plate
T*RTransformer
TC, TRCTransmitter
V*, R*VVaristor
V*RDiode bridge, Insulated-gate
bipolar transistor (IGBT) power
module
WRCWireless remote controller
X*Terminal
X*MTerminal strip (block)
Y*EElectronic expansion valve coil
Y*R, Y*SReversing solenoid valve coil
Z*CFerrite core
ZF, Z*FNoise filter
11 Technical data
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
Installation manual
13
Verantwortung für Energie und Umwelt
Copyright 2020 Daikin
3P477070-2L 2020.10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.