Daikin CVXM20A2V1B, FVXM25A2V1B, FVXM35A2V1B, FVXM50A2V1B Installation manuals

Installation manual
Split system air conditioners
CVXM20A2V1B FVXM25A2V1B FVXM35A2V1B FVXM50A2V1B
Installation manual
Split system air conditioners
English

Table of Contents

Table of Contents

1 About the documentation 2

1.1 About this document.................................................................. 2

2 Specific installer safety instructions 2

3 About the box 3
3.1 Indoor unit ................................................................................. 3
3.1.1 To remove the accessories from the indoor unit......... 3
4 About the unit 4
4.1 About the wireless LAN ............................................................. 4
4.1.1 Precautions when using the wireless LAN.................. 4
4.1.2 Basic parameters ........................................................ 4
4.1.3 Setting the wireless LAN............................................. 4
5 Unit installation 4
5.1 Preparing the installation site .................................................... 4
5.1.1 Installation site requirements of the indoor unit .......... 4
5.2 Opening the indoor unit ............................................................. 4
5.2.1 To remove the front panel........................................... 4
5.2.2 To remove the front grille ............................................ 5
5.2.3 To open the terminal block and remove the electrical
wiring box cover .......................................................... 5
5.3 Mounting the indoor unit............................................................ 5
5.3.1 To install the indoor unit.............................................. 5
5.3.2 To drill a wall hole ....................................................... 8
5.3.3 To remove the slit portions.......................................... 8
5.3.4 To provide drainage.................................................... 8
6 Piping installation 9
6.1 Preparing refrigerant piping....................................................... 9
6.1.1 Refrigerant piping requirements.................................. 9
6.1.2 Refrigerant piping insulation ....................................... 9
6.2 Connecting the refrigerant piping .............................................. 10
6.2.1 To connect the refrigerant piping to the indoor unit .... 10
7 Electrical installation 10
7.1 Specifications of standard wiring components .......................... 10
7.2 To connect the electrical wiring to the indoor unit ..................... 10
7.3 To connect optional accessories (wired user interface, central
user interface, wireless adapter, etc.) ....................................... 11
8 Finishing the indoor unit installation 11
8.1 To finish the indoor unit installation ........................................... 11
8.2 To close the indoor unit ............................................................. 11
8.2.1 To close the electrical wiring box and close the
terminal block.............................................................. 11
8.2.2 To re-install the front grille .......................................... 11
8.2.3 To re-install the front panel ......................................... 11
9 Commissioning 12
9.1 To perform a test run................................................................. 12
9.1.1 To perform a test run using the user interface............ 12
1 About the documentation

1.1 About this document

INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
Target audience
Authorised installers
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you MUST read before installing
▪ Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
Installer reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
10 Disposal 12
11 Technical data 12
11.1 Wiring diagram .......................................................................... 12
11.1.1 Unified wiring diagram legend..................................... 12
2
2 Specific installer safety
instructions
Always observe the following safety instructions and regulations.
Unit installation (see "5Unit installation"[44])
WARNING
CVXM-A and FVXM-A Floor Standing range is allowed to be combined only with systems with total refrigerant amount <1.842 kg. Therefore in case of combination with outdoor units 3MXM40N8 or 3MXM52N8, the total liquid refrigerant piping length of the installation MUST be ≤30m.
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10

3 About the box

edb ca f
j k lih
g
m
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
Piping installation (see "6Piping installation"[49])
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ Use the flare nut fixed to the unit.
▪ To prevent gas leakage, apply refrigeration oil only to
the inside of the flare. Use refrigeration oil for R32.
▪ Do NOT reuse joints.
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ NEVER install a drier to this R32 unit to guarantee its
lifetime. The drying material may dissolve and damage the system.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
3 About the box

3.1 Indoor unit

Electrical installation (see "7Electrical installation"[410])
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

3.1.1 To remove the accessories from the indoor unit

1 Remove the accessories located at the bottom of the package.
Spare SSID sticker is located on the unit.
a Installation manual b Operation manual c General safety precautions d Mounting plate (attached to the unit) e Titanium apatite deodorising filter
f Drain hose g Insulation piece h User interface
i User interface holder
j Dry battery AAA.LR03 (alkaline) for user interface k Spare SSID sticker (attached to the unit)
l Screws for fixing drain hose
m White head screws "To re-install the front grille"[411]
Spare SSID sticker. Do NOT throw away the spare sticker. Keep
it in a safe place in case it is needed in the future (e.g. in case the front grille is replaced, attach it to the new front grille).
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
3

4 About the unit

60
(65)
≤27°
(mm)
≥467
≥50 ≥50
A B
(105)
60
4 About the unit
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Following symbols may occur on the indoor unit:
Symbol Explanation
Measure the voltage at the terminals of main circuit capacitors or electrical components before servicing.

4.1 About the wireless LAN

For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit http://www.onlinecontroller.daikineurope.com.
INFORMATION
▪ Daikin Industries Czech Republic s.r.o. declares that
the radio equipment type inside of this unit is in compliance with Directive 2014/53/EU.
▪ This unit is considered as combined equipment
according to the definition of Directive 2014/53/EU.

4.1.1 Precautions when using the wireless LAN

Do NOT use near:
Medical equipment. E.g. persons using cardiac pacemakers or
defibrillators. This product may cause electromagnetic interference.
Auto-control equipment. E.g. automatic doors or fire alarm
equipment. This product may cause faulty behaviour of the equipment.
Microwave oven. It may affect wireless LAN communications.
2 Search for Daikin Residential Controller.
3 Follow the directions on the screen to install.

5 Unit installation

5.1 Preparing the installation site

WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

5.1.1 Installation site requirements of the indoor unit

INFORMATION
The sound pressure level is less than 70dBA.
WARNING
CVXM-A and FVXM-A Floor Standing range is allowed to be combined only with systems with total refrigerant amount <1.842 kg. Therefore in case of combination with outdoor units 3MXM40N8 or 3MXM52N8, the total liquid refrigerant piping length of the installation MUST be ≤30m.
Spacing. Mind the following requirements:

4.1.2 Basic parameters

What Value
Frequency range 2400MHz~2483.5MHz
Radio protocol IEEE 802.11b/g/n
Radio frequency channel 13ch
Output power 13dBm
Effective radiated power 15dBm (11b) / 14dBm (11g) /
14dBm (11n)
Power supply DC 14 V / 100 mA

4.1.3 Setting the wireless LAN

The customer is responsible for providing:
▪ Smartphone or tablet with minimum supported version of Android
or iOS, specified on http://www.onlinecontroller.daikineurope.com
▪ Internet line and communicating device, such as modem, router,
etc.
▪ Wireless LAN access point.
▪ Installed free Daikin Residential Controller application.
To install the Daikin Residential Controller application
1 Open:
▪ Google Play for appliances using Android. ▪ App Store for appliances using iOS.
A Front view B Side view
▪ Do not install the unit more than 60mm above the floor.
Wall insulation. When conditions in the wall exceed 30°C and a
relative humidity of 80%, or when fresh air is inducted into the wall, then additional insulation is required (minimum 10 mm thickness, polyethylene foam).
Wall or floor strength. Check whether the wall or the floor is
strong enough to support the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit.

5.2 Opening the indoor unit

5.2.1 To remove the front panel

1 Slide both sliders in the direction of the arrows until they click.
4
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
2 Open the front panel and remove the string.
b
a
c
b
c
b
a
1
2
3
b
a
c
c
b
a
b
A B C
3 Remove the front panel.

5.2.2 To remove the front grille

1 Remove the front panel. See "To remove the front panel"[44].
2 Remove the 4 screws, remove the grille from 4 tabs on the top
and remove the front grille while pulling it toward you.
5 Unit installation
a Screw b Sensor securing plate c Metal plate cover
To remove the electrical wiring box cover
1 Open the terminal block.
2 Remove 1 screw from the electrical wiring box.
3 Unhook the 2 tabs on the electrical wiring box cover and
remove it.
a Front grille b Tabs

5.2.3 To open the terminal block and remove the electrical wiring box cover

To open the terminal block
1 Remove the front grille.
2 Remove 1 lower screw.
3 Lift the sensor securing plate.
4 Move the metal plate cover down and then towards you to
remove it.
a Screw b Wiring box cover c Tabs

5.3 Mounting the indoor unit

5.3.1 To install the indoor unit

Installation options
There are 3 possible type of installation for the indoor unit.
A Floor (exposed) installation B Wall (exposed) installation C Half concealed installation
a Mounting plate b Skirting board
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
5
5 Unit installation
(mm)
634.5
750
006
300
200
285
115
159
238
689
a
a
a
a
159
a
a
75
06
75
45
Ø65
Ø65
45
b
c
75
75
54
f
e
A B
C
54
45
d
82
166
06
(mm)
634.5
750
006
553
300
200
285
115
238
b
b
b
b
75
06
75
45
Ø65
Ø65
45
d
e
75
75
54
h
g
54
45
f
A B
C
c c
a
Floor-standing installation
 5‒1 Indoor unit installation drawing: Floor-standing installation
A Front view B Side view C Top view
a Screw hole 6× b Left-back piping hole location c Right-back piping hole location d Left/right piping hole location e Left-bottom piping hole location
f Right-bottom piping hole location
1 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
2 Open the front panel and remove the front grille (see
"5.2Opening the indoor unit"[44]).
3 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
4 Secure the unit to the wall and floor using 6 screws M4×25L
(field supply).
Wall-mounted installation
 5‒2 Indoor unit installation drawing: Wall-mounted installation
A Front view B Side view C Top view
a Mounting plate b Screw hole 4× c Floor d Left-back piping hole location e Right-back piping hole location
f Left/right piping hole location g Left-bottom piping hole location h Right-bottom piping hole location
6 Temporarily secure the mounting plate on the wall.
7 Make sure the mounting plate is level.
8 Mark the centres of the drilling points on the wall.
9 Secure the mounting plate on the wall using 5 screws M4×25L
(field supply).
5 When the complete installation is finished, attach the front panel
and the front grille in their original position.
6
10 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
11 Open the front panel and remove the front grille (see
"5.2Opening the indoor unit"[44]).
12 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
13 If necessary for the skirting board, remove the slit portion on the
bottom frame.
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
a
b
a Bottom frame
≤60
a
5 4
30
f
734~740
170
350
70
200
593~595
170 350
d e
c
c
a
A B
(mm)
a
a
75
54
Ø60
Ø60
54
75
C
159
238
689
159
b b
06
75
75
54
h
g
634.5
115
285
b
b
b
b
300
b Slit portion
14 Align the unit using the alignment symbol on the
mounting plate: 375mm from the alignment symbol to the each side (unit width 750mm), 487mm from the alignment symbol to the bottom of the unit.
15 Hook the unit on the mounting plate and secure the unit to the
wall using 4 screws M4×25L (field supply).
a Alignment symbol
16 When the complete installation is finished, attach the front panel
and the front grille in their original position.
5 Unit installation
Half-concealed installation
 5‒3 Indoor unit installation drawing: Half-concealed installation
A Front view B Side view C Top view
a Extra filler board b Screw hole 6× c Hole d Left-back piping hole location e Right-back piping hole location
f Right/left piping hole location g Left-bottom piping hole location h Right-bottom piping hole location
17 Make a hole in the wall as illustrated above.
18 Install the extra filler board (field supply) in accordance with the
space between the unit and the wall. Make sure there is no gap between the unit and the wall.
19 Drill a wall hole, depending on which side piping is taken out.
See "To drill a wall hole"[48].
20 Remove the slit portions using nippers. See "To remove the slit
portions"[48].
21 Open the front panel, remove the front grille, remove the top
and side casings (see "5.2Opening the indoor unit"[44]).
22 Secure the unit to the extra filler board and to the floor using 6
screws M4×25L (field supply).
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
23 When the complete installation is finished, attach the front panel
and the front grille in their original position.
7
5 Unit installation
Ø65
a
b
c
a
c d
d
b

5.3.2 To drill a wall hole

CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.
1 Bore a 65 mm large feed-through hole in the wall with a
downward slope towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
a Wall embedded pipe b Putty c Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do
NOT forget to seal the gap with putty.

5.3.3 To remove the slit portions

For side piping (left/right) and bottom piping (left/right) slit portions must be removed. Remove slit portions according to where the piping is taken out.
2 Remove an burrs along the cut section using a half round
needle file.

5.3.4 To provide drainage

Make sure condensation water can be evacuated properly. This involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
Pipe length. Keep drain piping as short as possible.
Pipe size. Use rigid polyvinyl chloride pipe with 20 mm nominal
diameter and 26mm outer diameter.
NOTICE
▪ Install the drain hose with a downward slope.
▪ Traps are NOT permitted.
▪ Do NOT put the end of the hose in water.
Drain hose. Drain hose (accessory) is 220 mm long and with
18mm outer diameter on the connecting side.
Extension hose. Use rigid polyvinyl chloride pipe (field supply)
with 20 mm nominal diameter as extension hose. When connecting an extension hose, use a polyvinyl adhesive agent for
a Bottom frame b Slit portion for side piping on the front grille (same on the
other side)
c Slit portion for side piping on the bottom frame (same of
the other side)
d Slit portion for the bottom piping
1 Cut off the slit portion using nippers.
8
glueing.
Condensation. Take measures against condensation. Insulate
the complete drain piping in the building.
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the installation space and surroundings.
1 Push the drain hose (accessory) as far as possible over the
drain socket and fix it with 1 screw (accessory).
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
d
c
a
b
a Drain pan
100
a
≥50
220
150
100
(mm)
c
d
b
a
t
Ø
ØiØ
i
t
ØpØ
p
b Drain socket c Drain hose (accessory) d Screw (accessory)
2 Check for water leaks (see "To check for water leaks"[49]).
3 Insulate the indoor drain socket and drain hose with ≥10mm
insulation material to prevent condensation.
4 Connect the drain piping to the drain hose. Insert the drain hose
≥50mm, so it will not be pulled out of the drain pipe.

6 Piping installation

6 Piping installation

6.1 Preparing refrigerant piping

6.1.1 Refrigerant piping requirements

NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.
INFORMATION
Additional refrigerant charge is NOT allowed in case of combination of the outdoor unit 3MXM40N8 or 3MXM52N8 with the indoor units CVXM-A and/or FVXM-A. The total piping length MUST be ≤30m.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30mg/10m.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
Class Pipe outer diameter (mm)
Liquid piping Gas piping
20~35 Ø6.4 Ø9.5
50 Ø6.4 Ø12.7
a Drain hose (accessory) b Vinyl chloride drain pipe (VP-30) (field supply) c Reducer (field supply) d Vinyl chloride drain pipe (VP-20) (field supply)
To check for water leaks
1 Remove the air filters.
2 Gradually pour approximately 1l of water in the drain pan, and
check for water leaks.
Refrigerant piping material
Piping material: Phosphoric acid deoxidised seamless copper.
Piping temper grade and thickness:
Outer diameter
Temper grade Thickness (t)
(a)
(Ø)
6.4mm (1/4") Annealed (O) ≥0.8mm
9.5mm (3/8")
12.7mm (1/2")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.

6.1.2 Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
6.4mm (1/4") 8~10mm ≥10mm
9.5mm (3/8") 12~15mm ≥13mm
12.7mm (1/2") 14~16mm ≥13mm
Insulation inner
diameter (Øi)
Insulation thickness
(t)
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
least 20 mm to prevent condensation on the surface of the insulation.
9

7 Electrical installation

a b
c d
a
b
a
a
e
b
e
c
b
a
d
c
d
b
a
b
c

6.2 Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

6.2.1 To connect the refrigerant piping to the indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Pipe length. Keep refrigerant piping as short as possible.
1 Connect refrigerant piping to the unit using flare connections.
2 Insulate the refrigerant piping on the indoor unit as follows:
a Gas pipe b Gas pipe insulation c Liquid pipe d Liquid pipe insulation
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.
3 Close the slit on the refrigerant pipe connection and secure it
with a tape (field supply). Make sure there are no gaps.
4 Wrap the slit and the end of the insulation of the connected
refrigerant piping with insulation piece (accessory). Make sure there are no gaps.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

7.1 Specifications of standard wiring components

Component
Interconnection cable (indoor↔outdoor)
4-core cable
1.5mm²~2.5mm² andapplicable for
220~240V
H05RN-F (60245 IEC 57)

7.2 To connect the electrical wiring to the indoor unit

1 Open the terminal block. See "5.2Opening the indoor unit"[44].
2 Strip the wire ends approximately 15mm.
3 Match wire colours with terminal numbers on indoor and
outdoor unit’s terminal blocks and firmly screw wires to the corresponding terminals.
4 Connect the earth wires to the corresponding terminals.
a Refrigerant pipe connection b Refrigerant piping (field supply) c Slit d Tape e Insulation piece (accessory)
a Terminal block
7 Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
10
5 Pull the wires to make sure that they are securely attached,
then retain the wires with the cable clamp.
6 Make sure that the wires do not come in contact with the metal
parts of the heat exchanger.
7 In case of connecting to an optional adapter, see "7.3 To
connect optional accessories (wired user interface, central user interface, wireless adapter, etc.)"[411].
b Electrical component block c Cable clamp
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10

8 Finishing the indoor unit installation

a
b
a
b c
e f
b
a
c c

7.3 To connect optional accessories (wired user interface, central user interface, wireless adapter, etc.)

1 Remove the electrical wiring box cover. See "5.2 Opening the
indoor unit"[44].
2 Connect the optional adapter wire to the S21 connector. To
connect the optional adapter wire to the option, refer to the installation manual of the optional adapter.
3 Lead the wire as shown in the figure below.
a S21connector
B Optional adapter wire
4 Close the electrical wiring box cover. See "8.2 To close the
indoor unit"[411].
2 Attach the front metal cover and fix it with the screw.
3 Close the sensor securing plate.

8.2.2 To re-install the front grille

1 Attach the front grille to the original position.
2 Secure the front grille in 4 tabs.
3 Secure with the 2 original screws on the top part and with the 2
white head screws (accessory) on the bottom part.
a Front grille b 4 tabs c White head screws (accessory)

8.2.3 To re-install the front panel

1 Insert the front panel into the grooves of the unit (3 places) and
attach the string.
8 Finishing the indoor unit
8.1 To finish the indoor unit
1 After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap the refrigerant pipes and the interconnection cable with insulation tape. Overlap at least half the width of the tape with each turn.
2 Pass the pipes through the wall hole and seal the gaps with
putty.

8.2 To close the indoor unit

8.2.1 To close the electrical wiring box and
1 Hook the electrical wiring box onto the 2 tabs, close it, and fix it
with 1 screw.
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
installation
installation
a Interconnection cable b Gas pipe c Gas pipe insulation d Insulation tape e Liquid pipe
f Liquid pipe insulation
close the terminal block
2 Close the front panel and slide both sliders until they click.
3 Push on the sides of the front panel to make sure the front
panel is securely fixed.
11

9 Commissioning

,
A
INDOOR
OUTDOOR
9 Commissioning
NOTICE
ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.

9.1 To perform a test run

Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating
mode.
Prerequisite: Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properly.
1 In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature. Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3 minutes after the unit is turned
OFF.

9.1.1 To perform a test run using the user interface

1 Press to switch the system on.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Connection Protective earth (screw)
Connector
Earth Relay connector
Field wiring Short-circuit connector
Fuse Terminal
Indoor unit Terminal strip
Outdoor unit Wire clamp
Residual current device
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
YLW Yellow
Rectifier
2 Press the middle of and simultaneously.
3 Press twice to choose and confirm selection by pressing
.
Result: on the display indicates that the test run is selected. Test run operation will stop automatically after about 30 minutes.
4 To stop operation sooner, press the ON/OFF button.

10 Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.

11 Technical data

▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Business Portal (authentication required).

11.1 Wiring diagram

11.1.1 Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*" in the part code.
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation
switch
BZ, H*O Buzzer
C* Capacitor
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*, MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
FU*, F*U, (for characteristics, refer to PCB inside your unit)
FG* Connector (frame ground)
H* Harness
H*P, LED*, V*L Pilot lamp, light emitting diode
HAP Light emitting diode (service
HIGH VOLTAGE High voltage
IES Intelligent eye sensor
IPM* Intelligent power module
K*R, KCR, KFR, KHuR, K*M Magnetic relay
L Live
L* Coil
L*R Reactor
M* Stepper motor
M*C Compressor motor
M*F Fan motor
M*P Drain pump motor
M*S Swing motor
Connection, connector
Fuse
monitor green)
12
CVXM20+FVXM25~50A2V1B
Split system air conditioners
3P477070-2L – 2020.10
Symbol Meaning
MR*, MRCW*, MRM*, MRN* Magnetic relay
N Neutral
n=*, N=* Number of passes through ferrite
core
PAM Pulse-amplitude modulation
PCB* Printed circuit board
PM* Power module
PS Switching power supply
PTC* PTC thermistor
Q* Insulated gate bipolar transistor
(IGBT)
Q*C Circuit breaker
Q*DI, KLM Earth leak circuit breaker
Q*L Overload protector
Q*M Thermo switch
Q*R Residual current device
R* Resistor
R*T Thermistor
RC Receiver
S*C Limit switch
S*L Float switch
S*NG Refrigerant leak detector
S*NPH Pressure sensor (high)
S*NPL Pressure sensor (low)
S*PH, HPS* Pressure switch (high)
S*PL Pressure switch (low)
S*T Thermostat
S*RH Humidity sensor
S*W, SW* Operation switch
SA*, F1S Surge arrester
SR*, WLU Signal receiver
SS* Selector switch
SHEET METAL Terminal strip fixed plate
T*R Transformer
TC, TRC Transmitter
V*, R*V Varistor
V*R Diode bridge, Insulated-gate
bipolar transistor (IGBT) power module
WRC Wireless remote controller
X* Terminal
X*M Terminal strip (block)
Y*E Electronic expansion valve coil
Y*R, Y*S Reversing solenoid valve coil
Z*C Ferrite core
ZF, Z*F Noise filter
11 Technical data
CVXM20+FVXM25~50A2V1B Split system air conditioners 3P477070-2L – 2020.10
13
Verantwortung für Energie und Umwelt
Copyright 2020 Daikin
3P477070-2L 2020.10
Loading...