Dacor DHI542, DHI482, DHI421, DHI361 Planning Guide

25 5/8” (65.1 cm)**
15 ¾” (40.0 cm)
Chimney
12 9/16” (31.9 cm)
12 ½”
(31.8 cm)
15 ½”
(39.4 cm)*
28” (71.1 cm) to 36” (91.4 cm)
DHI Hoods
Revised 03/04/08
36”, 42”, 48”, 54”, 60” Wide
Island Hoods
PLANNING
1/2
All tolerances: +1/16”, -0, (+1.6mm, -0) unless otherwise stated
GUIDE
DHIXXX OVERALL DIMENSIONS
GENERAL SPECIFICATIONS
ALL MODELS
Blower
Blower Speeds 4
Exhaust 8-inch
Voltage
Requirements
600 CFM (1200 for units with 2 blowers) with electronic speed control
Lights 12 Vac, 20W halogen
Filters Baffle type, dishwasher safe
Finish 430 stainless steel
120 Vac, 60 Hz (see below for current rating)
Circuit
120 Vac, 15 Amp grounded, dedicated circuit
* 18” 1/4 on models DHI482, DHI542 and DHI602 ** 30” on models DHI482, DHI542 and DHI602
Chemney can accomodate 10” duct work
MODEL SPECIFIC
MODEL Blowers Lights Filters
DHI361 1 4 1 3.75 A
DHI421 1 4 1 3.75 A
DHI482 2 4 2 6.75 A
DHI542 2 6 2 7.10 A
DHI602 2 6 3 7.10 A
Maximum
Current Draw
Web: http://www.Dacor.com Corporate Phone: 800-793-0093
Specifications are subject to change without notice. See installation instructions for additional details.
7.7
DHI Hoods
Revised 03/04/08
Calculating the Maximum Duct Run Length
The maximum straight duct length for the hood is 50 feet. For each elbow and transition added to the duct work, a certain number of feet must be subtracted from the maximum straight length to compensate for wind resistance. To determine the length the duct work cannot exceed, subtract all of the equivalent lengths of the elbows and transitions listed below from 50 feet.
DUCT PIECE SUBTRACT
90° elbow (8” Dia.) 7 feet
45° elbow (8” Dia.) 3 feet
3 1/4” x 10” to 8” round 4 foot
Wall cap with damper 30 feet
Roof cap 30 feet
DUCT WORK EQUIVALENT LENGTHS
Island Hoods
36”, 42”, 48”, 54”, 60” Wide
PLANNING
2/2
GUIDE
Web: http://www.Dacor.com Corporate Phone: 800-793-0093
Specifications are subject to change without notice. See installation instructions for additional details.
7.8