Condec DLR334 User Manual

DLR334 Series
TWO RELAYS AND
SETPOINTS OPTION
OPERATION/INSTALLATION
MANUAL
PN 74844
.
10/24/01
ADDENDUM 1
TWO RELAYS AND SETPOINTS OPTION
OPERATION/INSTALLATION MANUAL
TABLE OF CONTENTS
SECTION DESCRIPTION PAGE
1 GENERAL INTRODUCTION 1
2 SETPOINTS (TRIP POINTS) DESCRIPTION 1
3 TRIP POINT SPECIFICATIONS 1
4 RELAY WIRING 2
5 LOGIC OUTPUT
2
6 TRIP POINT SETUP 3
7 FRONT PANEL TRIP STATUS INDICATION 4
8 FRONT PANEL TRIP POINT MONITOR AND ENTRY
5
9 SERIAL I/O 6
APPENDIX A EXAMPLES A1
APPENDIX B BOARD INSTALLATION B1
.
ADDENDUM 1
TWO RELAYS AND SETPOINTS OPTION FOR DLR334
1. GENERAL INTRODUCTION
The Analog / Relay / RPM Option board (KKY8924-) can be obtained as a Relay board (KKY8924-1) used with the Two Relays And Setpoint Option. The Option offers two form C relays that are used in conjunction with dual setpoints (trip points) or trip bands. The DLR334 does not support the RPM Option on the KKY8924 board. The option is supported by the DLR334 program KDG-1 version 13 or greater.
2. SETPOINTS (TRIP POINTS) DESCRIPTION
The Setpoint Option is a dual single trip point or a dual band trip performed in the meter's CPU on the processed pressure data. The "Option" provides relay contact closures on the KKY8924­board as well as a visual indication whenever a recorded data value is in or out of a preset trip point or band as set by the configuration. The configurable hysteresis settings are included which can be used to decrease drop-out threshold levels thus minimizing noise effects. Each limit hysteresis can be configured for either ascending or descending hysteresis application.
The trip point type of set point is defined as a single trip point with its associated hysteresis that produces an output when the pressure value is above or below this trip point. The trip is activated at the center of the trip value.
The trip band is defined by two trip points with individual hysteresis and polarity settings selected in the Trip Pt setup that produces an output when the pressure is inside or outside the band.
All settings related to the trip points are configured by the operator in the 1/0 menu under "Trip Pts?" and are stored in the non-volatile memory. When enabled by the setup, the trip points can be modified from the front panel in the "run" mode. The recalled trip points in the “run” mode are expressed in the current selected units. The trip point values are entered in the base mode
units while in the “run” mode.
If a faster response is required for the trip point, set the filter, “FILTR 1” parameter in the “SETUP CONFIG” menu to a lower number.
3. TRIP POINT SPECIFICATIONS:
Number of trip points/ bands: Two Trip point range: 0 to ± 100% of full scale capacity. Data Select: Pressure
1
.
Trip point settability: Set in display (engineering) units with resolution of
the base unit configuration. In “run” mode set in base.
Trip point Hysteresis: Set in display (engineering) units with resolution of
the base unit configuration to a maximum setting of full scale.
Output Relay: Arrangement: Form C contact closure.
MaxSwitchingVoltage: 100VDC,220VAC
Max Current:
AC (resistive load) 120vac: 1 A AC (resistive load) 220vac: 1/2 A DC (resistive load): 1/2 A
Output Logic: Trip 1 on OUT 1 and Trip 2 on OUT 2. A logic
"O" is output "on" (energized).
Output Activation select: If set for "Under" the output relay is "ON"
(energized) when the data is below (under) the Trip point or in the Trip Band, if band type selected. If set for "Over" the output relay is "ON" when the data is at or above (over) the Trip point or out of the Trip Band.
Power-up reset Protection: All relays are held "off' until the CPU re-establishes
proper operating conditions caused by power interruptions.
Indicators: Can be set in configuration for two types of display
indications. If set for "TRIP PTS", the display will indicate the active outputs by "TRIP 1 ", "TRIP 2", or TRIP 1 & 2". If set for "ACCEPT" the alpha display will indicate "LOW', "ACCEPT" and "HIGH" for trip band 1.
Serial 1/0: All Trip point parameters can be recalled or entered
via the Serial Full Duplex.
4. RELAY WIRING:
RELAY CONNECTIONS on OPTION BOARD
RELAY 1 OUT 1 N. C. OUT 1 N.C TB3-1
RELAY 2 OUT 2 N. C. OUT 2 N. C. TB3-4
BOARD
FUNCTION
OUT 1 N.O. OUT 1 N.O. TB3-2 OUT 1 COM OUT 1 COM TB3-3
OUT 2 N.O. OUT 2 N.O. TB3-5
MARKING
2
RELAY BLOCK
POSITION
.