Cat® C13
DIESEL GENERATOR SETS
CAT® GENERATOR SET PACKAGE
ENGINE SPECIFICATIONS
GENERATOR SET SPECIFICATIONS

COOLING SYSTEM

GENERATORS

EMCP CONTROL PANELS

350 ekW 320 ekW
Standby Prime
400 ekW 365 ekW
Cat generator set packages have been fully prototype tested and certified torsional vibration analysis reports are available. The packages are designed to meet the NFPA 110 requirement for loading, conform to the ISO 8528-5 steady state and fill transient response requirements.

CAT DIESEL ENGINES

.
The four-cycle Cat diesel engine combines consistent performance with excellent fuel economy and transient response that meets or exceeds ISO 8528-5. The engines feature a reliable, rugged, and durable design that has been field proven in thousands of applications worldwide in emergency standby installations.
The cooling system has been designed and tested to ensure proper generator set cooling, and includes the radiator, fan, belts, and all guarding installed as standard. Contact your Cat dealer for specific ambient and altitude capabilities.
Engine Model Cat® C13 ACERT In-line 6, 4-cycle diesel
Bore x Stroke 130mm x 157mm (5.1in x 6.2in)
Displacement 12.5 L (763 in³)
Compression Ratio 16.3:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel Injection System MEUI
Governor Electronic ADEM™ A4
Emission Certifications
Alternator Design Brushless Single Bearing, 4 Pole
Stator 2/3 Pitch
EPA TIER III
The generators used on Cat packages have been designed and tested to work with the Cat engine. The generators are built with robust Class H insulation and provide industry-leading motor starting capability and altitude capabilities.
The EMCP controller features the reliability and durability you have to come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules.
No. of Leads 12
Available Voltage Options 600/480/440/240/220V
Frequency 60Hz
Alternator Voltage 24V
Alternator Insulation & IP Class H; IP23
Standard Temperature Rise
Available Excitation Options Self-Excited, PMG
Voltage Regulation, Steady State +/-
125/130 Deg C
≤1%
1
LEHE1571-02
STANDARD EQUIPMENT
Aftercooler core. Turbocharger
Coolant drain line with valve; terminated
Caterpillar Extended Life Coolant.
Primary fuel filter w/integral water
Engine fuel transfer pump
Brushless, self-excited 2/3 pitch, random
Segregated low voltage wiring pane
Governing system
Safety Shutoff – High Water
Coolant Level Sensor
Narrow Skid
Overfill Prevention Valve
Starting/charging system
24-Volt Electric Starting Motor Charging Alternator
OPTIONAL EQUIPMENT
Single/Dual Element Air Cleaner
EMCP 4.4
Earth (Ground) Fault Relay
3-Pole 100% Rated – Single (Manual &
Neutral Bar
Sound Attenuated (SA). Weather Protective
Industrial grade (10 dBA)
UL2200 Listed
OSHPD
Cat® C13
DIESEL GENERATOR SETS
Generator Set
kg (lb)
WEIGHTS & DIMENSIONS
B
C
Air inlet system
Control panels EMCP4.2 control panel.
on edge of base. Fan and belt guards. Coolant Level Sensor
Cooling system
Exhaust system Exhaust manifold; dry.
Thermostats and housing, full open temperature 92 deg C (198 deg F). Coolant level sight gauge. Jacket water pump, gear driven, centrifugal.
Air inlet system
Control panels
Circuit Breakers
Heavy Duty Air Cleaner
Local Annunciator Remote Annunciators Discrete I/O Module Device Server Volt Free Contact
Motorized). 3-Pole 100% Rated – Dual & Third (Manual). External Paralleling Auxiliary Contacts
Fuel system
Generators and generator attachments
Protection System
Base / Fuel Tank
separator & secondary filter. Fuel cooler. Fuel priming pump. Flexible fuel lines.
wound. IP23 Protection. Insulation Class H and temperature rise Power centre, IP22 bottom cable entry
Cat Electronic Governor (ADEM A4).
Temperature Safety Shutoff – Low Oil Pressure Safety Shutoff – Overspeed
Wide / Standard Sub Tank Base – UL & ULC Listed Integral Tank Base – UL & ULC Listed Spill Containment
Enclosures
Cooling system Stone guards.
Mufflers
Base / Fuel Tank Audio & Visual Fuel Alarm
Fuel System
Generators and generator attachments
Starting/charging system
Certifications
Residential and Critical grade (25 dBA)
Integral 670 Gal Tank Base Sub Tank Bases:660, 1000, 1900, 2200 Gal
Excitation – Self Excitation – Internal / AREP / PMG Oversize Coastal Protection (CIP) Space Heater Control
Standard Battery Set Oversize Battery Set.
CSA 22.2 Certification of Compliance – IBC Seismic Certification of Compliance – IBC Seismic and
Certifications EPA Stationary Emergency Use
General Tool Set.
Standby
Ratings
350 ekW
400 ekW
Dim “A”
mm (in)
3505 (138) 1652 (65) 2069 (82) 3696 (8147)
3505 (138) 1652 (65) 2069 (82) 3823 (8427)
Dim “B”
mm (in)
Dim “C”
mm (in)
Weight
2
LEHE1571-02
Image shown might not reflect ac tual configuration
Cat® C13
INTEGRAL & SUB BASE FUEL TANKS
FEATURES
SUB BASE
base fuel tank mounts below the
INTEGRAL
tank base and engine
UL Listed for United States (UL 142) and Canada
OPTIONS
INTEGRAL & SUB BASE FUEL TANKS
(CAN/ULC S601)
Facilitates compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code
Dual wall
Lockable fuel fill cap, 4” (101.6 mm) NPT
Low fuel level warning standard, customer configurable
warning or shutdown
Primary tank leak detection switch in containment basin
Tank design provides capacity for thermal expansion of
fuel
Fuel supply dip tube is positioned so as not to pick up fuel sediment.
Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of heated return fuel
Pressure washed with an iron phosphate solution
Interior tank surfaces coated with a solvent-based thin-
film rust preventative
Heavy gauge steel gussets with internal lifting rings
Primary and secondary tanks are leak tested at 20.7 kPa
(3 psi) minimum
Compatible with open packages and enclosures
Gloss black polyester alkyd enamel exterior paint
Welded steel containment basin (minimum of 110% of
primary tank capacity)
Direct reading fuel gauge with variable electrical output
Emergency vents on primary and secondary tanks are
sized in accordance with NFPA 30
Rear stub-up access
The sub-
generator set wide base
Integral diesel fuel tank is incorporated into the generator set base frame
Robust base design includes linear vibration isolators between generator.
Audio/visual fuel level alarm panel
5gal (18.9 L) spill containment
5gal (18.9 L) spill containment with fuel fill drop
tube with in 6” (152 mm) from bottom of tank
5gal (18.9 L) spill containment with overfill prevention valve and fuel fill drop tube with in 6” (152 mm) from bottom of tank
ULC Listed 7.5gal (28.4 L) spill containment with vent extensions, vent whistle, and drop tube facilitating compliance with CSA B139-09
ULC Listed 7.5gal (28.4 L) spill containment with overfill prevention valve, vent extensions, vent whistle and drop tube facilitating compliance with CSA B139-09
3