Carrier 68RV15103A, 68RV15102A, 68RV14123A, 68RV11302A, 68RV14102A User Manual

...
2P
1
2
BLK
BLU
Transport Air Conditioning
Transport Air Conditioning
R
R
BRN
WHT
GRN/YEL
WHT
F
EVAP.
RED
WHT
YEL
2
1
C
RED
R
BLU
S
BLU
PTC
SERVICE MANUAL
for
Rooftop Air Conditioning Systems
T--298 Rev G
MODEL AirV
SERVICE MANUAL
For
AirV
AIR CONDITIONING AND
HEATING EQUIPMENT
MODELS
68RV11112A
68RV11122A
68RV11302A 68RV14102A 68RV14103A
68RV14113A 68RV14123A 68RV15102A 68RV15103A
SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses. Keep hands clear of the evaporator blower and condenser fan.
No work should be performed on the unit until all circuit breakers and start--stop switches are turned off, and power supply is disconnected.
Always work in pairs. Never work alone. In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill assembly or the upper unit cover assembly before turning the power off, and disconnecting the power supply. Before disconnecting, discharge capacitors by shorting across the capacitors terminals. (See Paragraph
3.6.8) When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick,
accurate reassembly. Be sure power is turned off before working on motors, controllers, or electrical control switches. Tag any circuit
breakers and power supply to prevent accidental energizing of circuits. Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires.
Problems with the system should be diagnosed and any necessary repairs must be performed by qualified service personnel.
In case of electrical fire, open circuit switch and extinguish with CO Use dry nitrogen to pressurize the system for leak checking. Be careful not to exceed 150 psig test pressure in
the hermetic compressor. Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury .
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
Disconnect power to the AirV unit before checking the capacitor.
(never use water).
2
10/09
Safety-- i
T-298
SPECIFIC WARNING AND CAUTION STATEMENTS
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These recommended precautions must be understood and applied during operation and maintenance of the equipment covered herein.
SPECIFIC WARNINGS AND CAUTIONS
WARNING
Be sure to observe warnings listed in the safety summary in the front of this manual before performing maintenance on the AirV system
WARNING
Beforeworking on theunit be sureto first disconnect all electric power to the unit to avoidthe possibility of electrical shock and personal injury. Before disconnecting, discharge capaci- tors by shorting across the capacitors terminals (Refer to paragraph 3.6.8)
WARNING
Shield coils with cardboard to protect hands against injury from sharp metal edges when re­moving compressor and other components.
WARNING
Oil vapor in piping stubs can ignite from torch flame and cause serious injury . Exercise ex­treme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
WARNING
Disconnect power to the AirV unit before checking the capacitor.
WARNING
Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock.
WARNING
Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
CAUTION
In order for the AirV systems to operate efficiently, a dedicated 115 V olt 20 Amp power con­nection is required.
T--298
Safety-- ii
10/09
CAUTION
Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sec­tions.
CAUTION
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury.
CAUTION
The changefrom Fahrenheit to Celsius will be permanent. It cannotbe changed back to Fahr­enheit.
CAUTION
When re--assembling, ensure the battery springs are correctly placed in the battery spring holders.
CAUTION
Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes.
10/09
Safety--iii
T-298
TABLE OF CONTENTS
PARAGRAPH NUMBER Page
SPECIFIC WARNING AND CAUTION STATEMENTS ii...........................................
SPECIFIC WARNINGS AND CAUTIONS ii......................................................
DESCRIPTION 1--1...............................................................................
1.1 INTRODUCTION 1--1.....................................................................
1.2 SERIAL NUMBER IDENTIFICATION 1--1....................................................
1.3 DESIGN CHANGE DESCRIPTIONS 1--1....................................................
1.4 SYSTEM (UNIT) INSTALLED DIMENSIONS 1--9.............................................
1.5 SERIAL NUMBER LOCATIONS 1--14........................................................
1.6 AirV SYSTEM COMPONENT SPECIFICATIONS 1--15.........................................
1.6.1 Refrigerant Charge 1--15................................................................
1.6.2 Compressor -- 115 Volts, 60 Cycles, 1 Phase 1--15.........................................
1.6.3 Compressor -- 220 Volts, 50 Cycles, 1 Phase 1--15.........................................
1.6.4 Thermostat Range (All Free Blow Units) 1--15..............................................
1.6.5 Return Air Sensor (Thermistor) 1--15......................................................
1.6.6 Heat Pump Sensors (Thermistors) 1--15...................................................
1.7 START--UP 1--15..........................................................................
1.8 Dry Mode Function 1--15....................................................................
1.9 REFRIGERANT CYCLE--STANDARD SYSTEM 1--15..........................................
1.10 REFRIGERANT CYCLE -- HEAT PUMP 1--16.................................................
1.10.1 Cooling 1--16..........................................................................
1.10.2 Heating 1--17..........................................................................
1.11 FREQUENTLY ASKED QUESTIONS AND ANSWERS 1--17....................................
TROUBLESHOOTING 2--1.........................................................................
2.1 NO POWER TO UNIT 2--1.................................................................
2.2 DUCTED UNIT WILL NOT OPERATE 2--1...................................................
2.3 DUCTED UNIT WILL NOT COOL 2--1.......................................................
2.4 COMPRESSOR POWER SUPPLY OPEN 2--1...............................................
2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY 2--1....................
2.6 CYCLES ON COMPRESSOR OVERLOAD 2--2..............................................
2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE 2--2..............................
2.8 CONDENSER AIR NOT ADEQUATE 2--2....................................................
2.9 INSUFFICIENT COOLING 2--2.............................................................
2.10 COMPRESSOR FLOODING 2--2...........................................................
2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY) 2--2.....................
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY) 2--2.............................
2.13 WATER LEAKAGE 2--2....................................................................
2.14 INADEQUATE HEAT (FREE--BLOW HEAT ONLY) 2--3........................................
2.15 INADEQUATE HEAT (HEAT--PUMP) 2--3....................................................
10/09
i
T--298
TABLE OF CONTENTS -- Continued:
SERVICE AND MAINTENANCE 3--1................................................................
3.1 PREVENTATIVE MAINTENANCE 3--1......................................................
3.2 OPERATING INSTRUCTIONS 3--1.........................................................
3.3 SERVICE -- GENERAL 3--1................................................................
3.4 CEILING UNIT -- FREE BLOW SYSTEMS 3--1...............................................
3.4.1 Filter Removal 3--1....................................................................
3.4.2 Ceiling Grill Removal 3--2..............................................................
3.4.3 Ceiling Panel Removal 3--2.............................................................
3.4.4 Master Control Switch 3--2.............................................................
3.4.5 Air Sweep Switch Removal 3--2.........................................................
3.4.6 Indoor Thermostat Removal 3--3........................................................
3.4.7 Air Sweep Removal 3--3...............................................................
3.4.8 Heat Strip Assembly Removal 3--3......................................................
3.5 CEILING UNIT -- DUCTED SYSTEMS 3--4...................................................
3.5.1 Filter Removal 3--4....................................................................
3.5.2 Ceiling Grill Removal 3--4..............................................................
3.5.3 Control Box Assembly Removal 3--4.....................................................
3.5.4 Main PCB Board Removal 3--5..........................................................
3.5.5 PCB Display Removal 3--5.............................................................
3.5.6 Fuse Removal 3--5....................................................................
3.5.7 Dip Switch Functions 3--6..............................................................
3.5.8 Return Air Thermistor 3--6..............................................................
3.5.9 Heat Pump Thermistors 3--7............................................................
3.6 SERVICE -- UPPER UNIT -- STANDARD, HC & HP 3--8.......................................
3.6.1 Exterior Cover Removal 3--8............................................................
3.6.2 Compressor Replacement 3--8..........................................................
3.6.3 Control Box Assembly Removal 3--8.....................................................
3.6.4 Upper Scroll Assembly Removal 3--8....................................................
3.6.5 Motor Assembly and Condenser Fan Removal 3--9........................................
3.6.6 Evaporator Blower Wheel Adjustment or Removal 3--10.....................................
3.6.7 Air Handling System Removal 3--10......................................................
3.6.8 Capacitor Troubleshooting 3--10..........................................................
3.6.9 Capacitor Testing and Replacement 3--11.................................................
3.6.10 Positive Temperature Coefficient Thermistor (PTC) (Start Thermistor) Troubleshooting 3--11.....
3.6.11 Line Voltage -- 10% 3-- 11................................................................
3.7 SERVICE -- UPPER UNIT -- LOW PROFILE 3--12.............................................
3.7.1 Exterior Cover Removal 3--12............................................................
3.7.2 Upper Scroll Assembly Removal 3--12....................................................
3.7.3 Condenser Fan Assembly Removal 3--13..................................................
3.7.4 Condenser Motor Removal 3--14.........................................................
3.7.5 Evaporator Motor/Blower Assembly Removal 3--14.........................................
3.7.6 Compressor Replacement 3--15..........................................................
3.7.7 Capacitor Removal 3--15................................................................
3.7.8 Remote Control (Fahrenheit to Celsius) 3--15..............................................
T--298
ii
10/09
TABLE OF CONTENTS -- Continued:
3.8 THERMOSTAT INSTALLATION AND START--UP INSTRUCTIONS (WALL MOUNTED) 3--17.......
3.8.1 Introduction 3--17......................................................................
3.8.2 Installation 3--17.......................................................................
3.8.3 Thermostat Location 3--17...............................................................
3.8.4 Install Thermostat -- 12VDC 3--17........................................................
3.9 LCD DISPLA Y 3--17.......................................................................
3.9.1 Cool Only Thermostat (Part No. 1110--421) 3--17...........................................
3.9.2 Heat/Cool Thermostat (Part No. 1110--420) 3--17...........................................
3.10 SET THERMOSTAT CONFIGURATION 3--17.................................................
3.10.1 Enter Configuration Mode 3--17..........................................................
3.11 CHECK THERMOSTAT OPERATION 3--18...................................................
3.11.1 Fan Operation (Cool Only) 3--18..........................................................
3.11.2 Fan Operation (Heat/Cool) 3--18.........................................................
3.11.3 Cooling Operation (Cool Only) 3--18......................................................
3.11.4 Cooling Operation (Heat/Cool) 3--18......................................................
3.11.5 Heating Operation (Heat/Cool) 3--18......................................................
3.12 CHECK THERMOSTAT OPERATION 3--18...................................................
3.12.1 Temperature Display 3--18...............................................................
3.12.2 Timeguard Timer 3-- 19..................................................................
3.12.3 Cycle Timer 3-- 19......................................................................
3.12.4 Minimum On Timer 3--19................................................................
3.12.5 Error Messages 3--19...................................................................
WIRING SCHEMATICS 4--1........................................................................
4.1 INTRODUCTION 4--1.....................................................................
4.2 WALL MOUNTED THERMOSTATS 4--6.....................................................
4.3 WALL--MOUNTED SENSOR FOR REMOTE CONTROL 4--6...................................
LIST OF FIGURES
Figure 1--1 Model/Serial Number Plate (Typical) 1--1..................................................
Figure 1--2 Roof Unit (Standard) Component Identification 1--5.........................................
Figure 1--3 Ceiling Unit Component Identification (Free--Blow) 1--6......................................
Figure 1--4 Component Identification -- Low Profile -- Upper Unit 1--7....................................
Figure 1--5 Component Listing--Ceiling Unit For Ducted Systems 1--8....................................
Figure 1--6 Unit Dimensions -- Top View -- Upper Unit (Roof) Installed 1--9................................
Figure 1--7 Unit Dimensions -- Standard -- Side View -- Roof + Ceiling 1--10...............................
Figure 1--8 Unit Dimensions -- Low Profile -- Side View -- Roof + Ceiling 1--11.............................
Figure 1--9 Unit Dimensions -- Ceiling Unit -- Bottom View 1--12..........................................
Figure 1--10 Ducted System Air Flow Arrangement 1--13................................................
Figure 1--11 Serial Number Locations (Free--Blow) 1--14................................................
Figure 1--12 Serial Number Locations (Ducted) 1--14...................................................
Figure 1--13 Refrigerant Flow Schematic (Standard System) 1--15.......................................
Figure 1--14 Refrigerant Flow Schematic -- Heat Pump -- (Cool Mode) 1--16...............................
Figure 1--15 Refrigerant Flow Schematic -- Heat Pump -- (Heat Mode) 1-- 17...............................
10/09
iii
T--298
LIST OF FIGURES -- Continued:
Figure 3--1 Filter Removal -- Free Blow 3--1..........................................................
Figure 3--2 Ceiling Grill -- Free Blow 3-- 2.............................................................
Figure 3--3 Ceiling Panel Assembly 3--2.............................................................
Figure 3--4 Ceiling Panel With Heat Option 3--2.......................................................
Figure 3--5 Control Box Assembly -- Free Blow 3--2...................................................
Figure 3--6 Indoor Thermostat 3-- 3..................................................................
Figure 3--7 Air sweep motor 3--3....................................................................
Figure 3--8 Heat Strip Assembly 3--3................................................................
Figure 3--9 Filter Removal -- Ducted Unit 3--4.........................................................
Figure 3--10 Ceiling Grill -- Ducted 3--4..............................................................
Figure 3--11 Control Box & PCB Cover 3--4..........................................................
Figure 3--12 Control Box Assembly -- Ducted 3--5.....................................................
Figure 3--13 Main/Display PCB’s 3--5...............................................................
Figure 3--14 Dip Switch Function 3-- 6...............................................................
Figure 3--15 Cover Assembly -- Standard 3--8........................................................
Figure 3--16 Control Box 3--8......................................................................
Figure 3--17 Control Box Removal 3--8..............................................................
Figure 3--18 Water Cover Removal 3--8.............................................................
Figure 3--19 Upper Scroll Assembly 3-- 9.............................................................
Figure 3--20 Motor Assembly 3--9...................................................................
Figure 3--21 Spring Clamp Removal 3--9............................................................
Figure 3--22 Motor Clip Removal 3--9...............................................................
Figure 3--23 Condenser Fan Removal 3--10...........................................................
Figure 3--24 Blower Wheel 3--10.....................................................................
Figure 3--25 Condenser With Motor Assembly & Compressor 3--10......................................
Figure 3--26 Set--Up For Discharging a Capacitor 3--11.................................................
Figure 3--27 Cover Assembly -- Low Profile 3--12......................................................
Figure 3--28 Upper Scroll Assembly Locking Tabs (b.) & Screw Locations (c.) 3--12.........................
Figure 3--29 Upper Scroll Assembly Keeper Tab Release 3--12..........................................
Figure 3--30 Upper Scroll & Control Box Cover Removed 3--13..........................................
Figure 3--31 Condenser Fan Assembly& Retaining Ring 3--13...........................................
Figure 3--32 Condenser Fan Motor& Fan Assembly Stop 3--13..........................................
Figure 3--33 Condenser Fan Motor& Fan Assembly Tab 3--13...........................................
Figure 3--34 Condenser Motor Ground 3--14..........................................................
Figure 3--35 Evaporator Motor Locking Tabs 3--14.....................................................
Figure 3--36 Evaporator Motor/Blower Assembly 3--14.................................................
Figure 3--37 Evaporator Blower Wheel 3--15..........................................................
Figure 3--38 Control Box Assembly With Capacitor 3--15................................................
Figure 3--39 Remote Control Components 3--16.......................................................
T--298
iv
10/09
LIST OF FIGURES -- Continued:
Figure 3--40 Remote Control PCB (FR9 Location) 3--16.................................................
Figure 3--41 Wall Thermostat Wiring Diagram -- Cool Only Model 3--19...................................
Figure 3--42 Wall Thermostat Wiring Diagram -- Heat/Cool Model 3--20...................................
Figure 3--43 (Optional) Wall Thermostat Wiring Diagram -- Heat/Cool Model 3--21..........................
Figure 4--1 Upper Unit Schematic -- Standard & HC 4--1...............................................
Figure 4--2 Upper Unit Schematic -- Low Profile 4--1...................................................
Figure 4--3 Ceiling Unit Schematic -- Cooling Only 4--2................................................
Figure 4--4 Ceiling Unit Schematic -- Heat/Cool 4--2...................................................
Figure 4--5 Ceiling Unit, Standard -- Ducted 4--2......................................................
Figure 4--6 Heat Pump -- Upper Unit -- Free Blow 4--3.................................................
Figure 4--7 Heat Pump -- Ceiling Unit -- Free Blow 4--3................................................
Figure 4--8 Heat Pump -- Upper Unit -- Standard -- Ducted 4--4.........................................
Figure 4--9 Heat Pump -- Upper Unit -- Low Profile -- Ducted 4--4........................................
Figure 4--10 Heat Pump -- Ceiling Unit -- Ducted 4--5..................................................
Figure 4--11 Ceiling Unit -- Wall Thermostat -- Cool Only -- Ducted & Free Blow 4--5.......................
Figure 4--12 Ceiling Unit -- Wall Thermostat -- Heat/Cool -- Free Blow 4--6...............................
LIST OF TABLES
Table 1--1 Model Chart 1--2.........................................................................
Table1--2MODELCHART 1--3.....................................................................
Table 1--3 ADDITIONAL SUPPORT MANUALS 1--4...................................................
Table 2--1 System Self--diagnostics Function (Ducted Remote) 2--4......................................
Table 3--1 Resistance--Temperature Coefficient 3--6....................................................
Table 3--2 Resistance--Temperature Coefficient (IDC -- ODA -- ODC) 3--7.................................
10/09
v
T--298
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
This manual contains service instructions and electrical data for the AirV, Carrier Transport Air Conditioning’s Recreational Vehicle air conditioning unit.
The AirV units are two piece systems, consisting of the Upper Unit and the Ceiling unit. The Upper Unit contains the refrigeration system while the Ceiling Unit contains the controls and vents. The Ceiling Units are available in a free--blow or ducted configuration.
The free-- blow units (see Figure 1--2) deliver air to the vehicle by means of front and rear end vents and one downward vent (air shower). The vents may all be opened or closed to direct air as desired. The front and rear vents are fitted with motorized dampers that oscillates to produce an “air--sweep” effect. These units may be fitted with optional electric heat.
The ducted units (see Figure 1--5 and Figure 1--10) deliver air through ducting built in the vehicle ceiling. These units are fitted with a 12 VDC microprocessor control system, a display panel (PCB display) and a remote controller. These units may be wired to provide thermostatic control of the vehicle furnace.
Carrier’s AirV air conditioning models include cooling only units, heating/cooling units, and heat pump units. The cooling only units are available with free blow or ducted air delivery. Cooling units with heat strips are available for free blow only.
Operation of the AirV units is controlled automatically by the temperature controller (thermostat), which maintains the vehicle’s interior temperature at the desired set point. Free Blow, cool--only units are available with a wall mounted thermostat.
Table 1--1 lists Upper Unit AirV model numbers and descriptions. Table 1--2 lists Ceiling Unit model numbers and descriptions. Table 1--3 lists additional support manuals that are available.
1.2 SERIAL NUMBER IDENTIFICATION
Separate part numbers and serial numbers are provided for the upper and lower unit assemblies The numbers may be found on plates readable from inside the vehicle, See Figure 1--1 1 or Figure 1--12.
The first two numbers of the serial number, see Figure 3--23, is the week the unit was manufactured. For example, 01 would designate the first week of the year and 52 would designate the last week of the year.
The third and fourth numbers designate the year in which the unit was manufactured. For example, 99
would represent the year 1999, 00 the year 2000, and so on.
The letter Y and all the numbers after it designates the unit serial number. Example: Y43210
A serial number of 1303Y12345 designates that the unit was manufactured the 13th week of 2003 and the serial number is Y12345.
Carrier
Air Conditioning
C
Division of Carrier Corporation
USE AMP20
TIME DELAY FUSE OR
CIRCUIT BREAKER
COMPRESSOR
FAN MOTOR
USE CEILING ASSY/ANY
DATE OF Mfg
DESIGN PSIG HIGH 350 LO 150
R--22
MODEL No.
Part No.
VOLTS
CAPACITY
AMPS
SERIAL No.
68RV14102A
99--00468 -- 01
115
ph
1
13,500
3,955
13.5
05/03
1303Y12345
oz
kg
RLA
FLA
99--00469 -- 01
15.9
0.45
12.5
2.58
hz
V
60
Btu/h
W
A
Figure 1--1 Model/Serial Number Plate (Typical)
1.3 DESIGN CHANGE DESCRIPTIONS
The following list provides a description of changes in design and serial number breaks for those changes.
0703Y (Power Assembly) & 1903Y (Control Assembly) New style PCB -- Cool Mode -- Control & Power Assembly (Fans shut off in auto mode).
0803Y (Power Assembly) & 2603Y (Control Assembly) New style PCB -- Heat Pump -- Control & Power Assembly (Fans shut off in auto mode).
4204Y Minimum furnace setpoint lowered from 63°Fto 45°F.
3808Y Changed standard profile blower wheel type from aluminum boss to ring compression type.
10/09
1--1
T--298
Table 1--1 Model Chart
UPPER UNIT (ROOF)
MODEL NUMBER PART NUMBER CONFIGURATION VO LTAGE AMPS COLOR
99--00468--00 STANDARD A/C 115/1/60 12.8 WHITE
68RV14102A
99--00468--01 STANDARD A/C 115/1/60 12.8 IVORY 99--00469--20 STANDARD A/C 115/1/60 12.8 BLACK
68RV11302A
99--00468--02 STANDARD A/C 220/1/50 99--00468--03 STANDARD A/C 220/1/50 IVORY
5.3 COOL
6.7 HEAT
WHITE
99--00468--08 HIGH--CAPACITY 1 15/1/60 14.1 WHITE
68RV15102A
99--00468--09 HIGH--CAPACITY 1 15/1/60 14.1 IVORY 99--00468--28 HIGH--CAPACITY 1 15/1/60 14.1 BLACK
HEAT PUMP
68RV11122A
HEAT PUMP
68RV11112A
LOW PROFILE
68RV15103A
LOW PROFILE
68RV14103A
LOW PROFILE
68RV14113A
LOW PROFILE
68RV14123A
99--00468--04
99--00468--05
99--00468--24
99--00468--06
99--00468--07
99--00468--26
99--00468--10
99--00468--32
99--00468--12
99--00468--30
99--00468--13
99--00468--33
99--00468--11
HEAT PUMP
FREE--BLOW
HEAT PUMP
FREE--BLOW
HEAT PUMP
FREE--BLOW
HEAT PUMP
DUCTED
HEAT PUMP
DUCTED
HEAT PUMP
DUCTED
FREE--BLOW
HIGH CAPACITY
FREE--BLOW
HIGH CAPACITY
FREE--BLOW
STANDARD
FREE--BLOW
STANDARD
HEAT PUMP
HIGH CAPACITY
HEAT PUMP
DUCTED
HEAT PUMP
FREE--BLOW
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
14.1 COOL
13.8 HEAT
14.1 COOL
13.8 HEAT
13.4 COOL
13.8 HEAT
13.4 COOL
13.8 HEAT
14.5 COOL
13.8 HEAT
12.7 COOL
10.9 HEAT
12.7 COOL
10.9 HEAT
WHITE
IVORY
BLACK
WHITE
IVORY
BLACK
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
WHITE
T--298
1--2
10/09
TABLE 1--2 MODEL CHART
CEILING UNIT
MODEL NUMBER PART NUMBER VOLTAGE COLOR OPTIONS INTERFACE
68RV0010AA
68RV0010BA
68RV0010KA 99--00469--06 1 15/1/60 (12VDC) White Cool Only Ducted
68RV0030AA
68RV0030BA 99--00469--08 220/1/50 White Heat/Cool Free--Blow 68RV0030KA 99--00469--10 220/1/50 White Cool Only Ducted
68RV0012CA
68RV0011LA 99--00469--13 115/1/60 (12VDC) White Heat Pump Ducted
68RV0010EA 99--00469--17 1 15/1/60 (12VDC) White Heat/Cool
68RV0040MA 99--00469--22 115/1/60 White Cool Only
68RV0010AB (Phased Out)
68RV0010BB (Phased Out)
68RV0010DB 99--00469-- 29 115/1/60 White Cool Only
68RV0010EB 99--00469--31 115/1/60 White Heat/Cool
68RV0012FB 99--00469--33 115/1/60 White Heat Pump
68RV0010KS 99--00469--35 115/1/60 White
68RV0011KS 99--00469--36 1 15/1/60 White
68RV0010MS
(Phased Out)
68RV0011OS (Phased Out)
99--00469--00 1 15/1/60 White Cool Only Free--Blow 99--00469--01 1 15/1/60 Ivory Cool Only Free--Blow 99--00469--02 1 15/1/60 White Heat/Cool Free--Blow 99--00469--03 1 15/1/60 Ivory Heat/Cool Free--Blow
99--00469--04 220/1/50 White Cool Only Free--Blow 99--00469--05 220/1/50 Ivory Cool Only Free--Blow
99--00469--11 115/1/60 White Heat Pump Free--Blow 99--00469--12 1 15/1/60 Ivory Heat Pump Free--Blow
Free--Blow
Wall Thermostat
Ducted
Wall Thermostat
99--00469--23 1 15/1/60 White Cool Only Free--Blow 99--00469--24 1 15/1/60 Ivory Cool Only Free--Blow 99--00469--25 1 15/1/60 White Heat/Cool Free--Blow 99--00469--26 1 15/1/60 Ivory Heat/Cool Free--Blow
Free--Blow
Wall Thermostat
Free--Blow
Wall Thermostat
Free--Blow
Wall Thermostat
99--00469--37 1 15/1/60 White
99--00469--38 1 15/1/60 White
Cool Only
Thick Roof Kit
Heat Pump
Thick Roof Kit
Cool Only
Thick Roof Kit
Heat Pump
Thick Roof Kit
Ducted
Remote
Ducted
Remote
Ducted
W/Wall Sensor
Ducted
W/Wall Sensor
10/09
1--3
T--298
TABLE 1--3 ADDITIONAL SUPPORT MANUALS
MANUAL--FORM NO.
71LC6A5431A AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide
71LH6A5407A AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide
71LD6A54070 AirV 115 Volts--Ducted (Cool Only) Owner’s Guide
71LH6A5407A AirV 220 Volts--Free Blow (Heat--Cool) Owner’s Guide
71RQ6A5401B AirV 115 Volts--Free Blow (Heat Pump) Owner’s Guide
71LQ6A54010 AirV 115 Volts--Ducted (Heat Pump) Owner’s Guide
71DW6A54070 AirV 115 Volts--Ducted Wired Thermostat Owner’s Guide
71LC6A5431A AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide
71LH6A5407A AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide
71RW6A54310 AirV 1 15 Volts--Free Blow Wired Thermostat Owner’s Guide
71LD6A54070 AirV 115 Volts--Free Blow Wired Thermostat Owner’s Guide
71LQ6A54010 AirV 115 Volts--Free Blow Wired Thermostat Owner’s Guide
71DJ6A54070 AirV 1 15 Volts--Free Blow Wired Thermostat Owner’s Guide
71DK6A54010 AirV 1 15 Volts--Free Blow Wired Thermostat Owner’s Guide
T--298PL AirV Service Parts ALL
62--50455--00 Basic refrigeration Service Training ALL
EQUIPMENT COVERED TYPE OF MANUAL (For) PART NO.
99--00469--00 99--00469--01
99--00469--02 99--00469--03
99--00469--06
99--00469--08 99--00469--09
99--00469--11 99--00469--12
99--00469--13
99--00469--22
99--00469--23 99--00469--24
99--00469--25 99--00469--26
99--00469--29
99--00469--35
99--00469--36
99--00469--37
99--00469--38
T--298
1--4
10/09
1
2
3
4
5
1. Cover
2. Condenser
3. Evaporator
10/09
4. Compressor
5. Base Pan
Figure 1--2 Roof Unit (Standard) Component Identification
1--5
T--298
1
2
3
4
1. Ceiling Panel Assembly
2. Control Box Cover
Figure 1--3 Ceiling Unit Component Identification (Free--Blow)
T--298
3. Control Assembly
4. Ceiling Grill Assembly
1--6
10/09
1
2
3
9
8
5
6
4
7
10
11
1. Cover Assembly
2. Scroll Assembly -- Upper
3. Condenser Fan
4. Condenser Motor
5. Evaporator Motor
6. Evaporator Blower Wheel
Figure 1--4 Component Identification -- Low Profile -- Upper Unit
10/09
7. Condenser Coil
8. Scroll Assembly -- Lower
9. Evaporator Coil
10. Compressor 1 1. Base Pan Assembly
See Figure 1-- 3 for Ceiling Package (Free--
Blow)
1--7
T--298
1
2
3
12
11
10
4
5
6
7
8
1. Telescoping Divider (3 different sizes available)
2. Divider Assembly
3. Frame Panel, Insulation Assembly
4. Control Box Assembly
5. Control Box Cover
6. Suction Packing Assembly
Figure 1--5 Component Listing--Ceiling Unit For Ducted Systems
9
7. Remote Control Assembly
8. Remote Control Bracket Assembly
9. Filter Assemblies (2)
10. PCB Cover 1 1. PCB Main Assembly
12. PCB Display
T--298
1--8
10/09
1.4 SYSTEM (UNIT) INSTALLED DIMENSIONS
Refer to Figure 1--6 thru Figure 1--9 for installation dimensions of Standard & Low Profile Upper Units & Ducted & Free--Blow Ceiling units.
4.3”4.3”
10.3”
14” by 14”
Opening
41.0”
ROOF UNIT -- TOP VIEW -- STANDARD
6.4”
16.7”
22.6”
10/09
3.6”
14” by 14”
Opening
6.4”
24.1”
41.7”
ROOF UNIT -- TOP VIEW -- LOW PROFILE
Figure 1--6 Unit Dimensions -- Top View -- Upper Unit (Roof) Installed
1--9
26.8”
T--298
Loading...
+ 43 hidden pages