Carrier 40VMF009A-048A User Manual

40VMF009A-048A
4-Way Cassette Indoor Unit for
Variable Refrigerant Flow (VRF) Systems
Installation and Maintenance Instructions

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
• PROTECTING UNITS FROM DAMAGE
• PREPARING JOBSITE FOR UNIT INSTALLATION
• IDENTIFYING AND PREPARING UNITS
Step 2 — Position the Unit . . . . . . . . . . . . . . . . . . . . 6
Step 3 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . . 7
• INSTALLING HANGER BOLTS
• MOUNTING UNIT
• INSTALLING PANEL
Step 4 — Connect Piping . . . . . . . . . . . . . . . . . . . . . . 8
• CONDENSATE PIPING
• REFRIGERANT PIPING
Step 5 — Complete Electrical Connections. . . . . . 9
Step 6 — Position and Connect Controller . . . . . 11
ACB Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pre-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
System Operation Check . . . . . . . . . . . . . . . . . . . . 15
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INDOOR UNIT ADDRESSING. . . . . . . . . . . . . . 15-17
Wireless Remote Controller (40VM900001) . . . . . 15
Non-Programmable Controller (40VM900002). . . 16
Programmable Controller (40VM900003). . . . . . . 16
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . 17-19
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 19
APPENDIX A — DIP SWITCH SETTINGS . . . . . . . . 20

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) ANSI/NFPA (American National Standards Institute/National Fire Protection Association) 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA (Canadian Standards Association) C22.1.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices,
which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury. Installing, starting up, and servicing equipment can be hazardous due to system pressure, electrical components, and equipment location.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
When installing the equipment in a small space, provide adequate measures to avoid refrigerant concentration exceeding safety limits due to refrigerant leak. In case of refrigerant leak during installation, ventilate the space immediately. Failure to follow this procedure may lead to personal injury.
WARNING
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from
system using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 18-40VMF002-01 Printed in U.S.A. Form 40VMF-2SI Pg 1 1-18 Replaces: 40VMF-1SI
CAUTION
LEGEND
VRF Variable Refrigerant Flow
40 VM F
009
--
3
Equipment Type
40
Indoor Unit
Product Type
VM — VRF
Blank
Voltage (V-Ph-Hz)
3 — 208/2 3 0-1-60
Model Type
F — 4-Way Cassette
Capacity (Btuh)
009
— 9,000
012
— 12,000
015
— 15,000
024
— 24,000
018
— 19,100
030
— 30,000
036
— 36,000
A40-1914
048
— 48,000
LEGEND
VRF — Variable Refrigerant Flow
A
Design Revision
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these procedures may result in damage to equipment. For information about replacement oil type and viscosity, see the Installation, Start-Up, and Service Instructions for the 38VMAH and 38VMAR outdoor units.

GENERAL

The 40VMF 4-way ceiling cassette effectively makes each area served an independently controlled temperature zone. Through thermostatic control of operations, conditions can be varied to suit diverse requirements and activities.
The equipment is initially protected under the manufacturer’s standard warranty; however, the warranty is provided under the condition that the steps outlined in this manual for initial inspection, proper installation, regular periodic maintenance, and everyday operation of the unit be followed in detail. This manual should be fully reviewed in advance before initial installation, start-up and any maintenance. Contact your local sales representative or the factory with any questions BEFORE proceeding.
Table 1 lists physical data for each unit size. See Fig. 1 for model number nomenclature. Figure 1 shows unit dimensions. Table shows components that may or may not be used for a particular installation.
Fig. 1 — Model Number Nomenclature
2
Table 1 — 40VMF Physical Data
UNIT 40VMF 009 012 015 018 024 030 036 048 POWER SUPPLY (V-Ph-Hz) 208/230-1-60 COOLING CAPACITY (Btuh) 9,000 12,000 15,000 19,100 24,000 30,000 36,000 48,000 HEATING CAPACITY (Btuh) 10,900 13,600 17,000 21,500 27,000 34,000 42,000 54,000 ELECTRICAL CHARACHTERISTICS
Typ e DC Input (W) 40
INDOOR COIL
Number of Rows 23 Fin Spacing (fins/in.) 17 Fin Type Hydrophilic Aluminum Tube Diameter, OD (in.) 0.276 Tube Type Inner Groove Number of Circuits 412
INDOOR AIRFLOW (cfm)
Low 330 Medium 390 High 460
INDOOR NOISE LEVEL (dBA)
Low 32.1 Medium 34.0 High 36.7
UNIT
Unit Dimensions, W x H x D (in.) 33 Packing Dimensions, W x H x D (in.) 37 5/8 x 10 5/8 x 37 5/ Panel / Grille Dimensions, W x H x D (in.) 37 3/8 x 1 3/4 x 37 3/ Panel / Grille Dimensions (in.) 40 7/8 x 3 5/8 x 40 7/ Unit Net/Gross Weight (lb) 54/71 69/86
Panel/Grille Net/Gross Weight (lb) 13.2/20 REFRIGERATION TYPE R-410A EXPANSION DEVICE EEV DESIGN PRESSURE, High/Low (psig) 580/320 AIR FILTER REFRIGERANT PIPING (in.)
Liquid Side, OD (Flare)
Suction Side, OD (Flare) CONNECTING WIRING
Power Wiring Sized per NEC and local codes based on nameplate electrical data
Signal Wiring 2-core shielded twisted pair cable 20 AWG-16 AWG CONDENSATE DRAIN PIPE DIAMETER, OD (in.)
LEGEND
AWG — American Wire Gage EEV Electronic Expansion Valve
54
390 460 560
33.0
37.3
41.4
1
/8 x 9 x 33 1/
1
/
4
1
/
2
67 153.5 85.4 131.7 182.7 202.3
460 610 610 680 800 950 560 700 700 800 950 1100 680 1000 800 950 1100 1200
37.0 40.2 40.2 42.1 47.3 50.5
41.5 43.1 42.5 45.1 50.4 54.0
45.6 52.5 44.7 49.5 53.9 55.4
8
8
1
33 1/8 x 11 3/4 x 33 1/
37 5/8 x 13 x 37 5/
8
8
1
/
4
8
8
3
/
8
5
/
8
3
Table 2 — Components Shipped With Unit
NAME SHAPE QUANTITY FUNCTION
Nut 8 To connect the construction cover board to the fan motor
Washer 8 To connect the construction cover board to the fan motor
Construction cover board 1 Used to cover the fan motor
Bolt 4 To connect the construction cover board to the fan motor
Insulation 2 For covering the coil stub outs
Insulation 1 For covering the condensate drain
Clamp 1 For connecting the drain
Tie rope 5 For insulation
Condensate connection 1 For connecting drain
PQE connection wire 2 To connect outdoor unit, indoor unit, and sub MDC
Copper nut 1 Connect piping
Flexible conduit and connectors 1 Routing power lines
Connecting wire 1 For connecting occupancy sensor
Copper pipe for gas side 1 For connecting the refrigerant pipe
Copper pipe for liquid side 1 For connecting the refrigerant pipe
LEGEND MDC — Multiport Distribution Controller
4
Fig. 1 — 40VMF009-048 Dimensions
NOTE: All dimensions shown in inches.
40VMF UNIT SIZE DIMENSION A
009
9012
015 018
11
3
/
4
024 030 036 048
´
´-1
´
Install hanger
Panel
Ceiling
Main body
Hexagon nut (For adjust to balance)
í
í
í
í
A
Drainage pipe
2í
í
í
 í
DRAIN CONNECTION
í
5
Step 1 — Unpack and Inspect Units —
Fig. 2 — False Ceiling Installation
40VMF UNIT SIZE
DIMENSION (in.)
AH
009-015 9 ³ 10
1
/
4
018-048 11 3/
4
³ 13
A
H
>8-1/4 ft.
Connect to the outlet of
drainage pipe
Connection port of
(Gas side)
refrigerant pipe
(Liquid side)
Connection port of refrigerant pipe
Floor
Ceiling
Panel
Air outlet Air inlet
2-7/8 ft. (Ceiling hole)
Air outlet
packaged for shipment to avoid damage during normal transit and handling. It is the receiving party’s responsibility to inspect the equipment upon arrival. Any obvious damage to the carton and/or its contents should be reported on the bill of lading and a claim should be filed with the transportation company and the factory. Unit should always be stored in a dry place, and in the proper orientation as marked on the carton.
To avoid equipment damage, do not lift unit by the drain pipe or refrigerant piping. Unit should be lifted using the mounting brackets.
After determining the condition of the carton exterior, carefully remove each unit from the carton and inspect for hidden damage. Check to make sure that items such as thermostats, controller etc. are accounted for whether packaged separately or shipped at a later date. Any hidden damage should be recorded, a claim should be filed with the transportation company, and the factory should be notified. In the event a claim for shipping damage is filed, the unit, shipping carton, and all packing must be retained for physical inspection by the transportation company. All units should be stored in the factory shipping carton with internal packaging in place until installation.
PROTECTING UNITS FROM DAMAGE — Do not apply force or pressure to the coil, piping, or drain stub-outs during handling. All units should be handled by the chassis or as close as possible to the unit mounting point locations.
The unit must always be properly supported. Temporary supports used during installation or service must be adequate to hold the unit securely. To maintain warranty, protect units against hostile environments (such as rain, snow or extreme temperature), theft, vandalism, and debris on jobsite. Equipment covered in this manual is not suitable for outdoor installations. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor, fan wheels and coils. Failure to do so may have serious adverse effects on unit operation and in the case of motor and blower assembly, may result in immediate or premature failure. Failure of any unit caused by deposits of foreign material on the motor or blower wheels will not be covered by the manufacturer’s warranty. Some units and/or job conditions may require some form of temporary covering during construction.
PREPARING JOBSITE FOR UNIT INSTALLATION — To save time and to reduce the possibility of costly errors, set
up a complete sample installation in a typical room at jobsite. Check all critical dimensions such as pipe, wire, and duct connections requirements. Refer to job drawings and product dimension drawings as required. Instruct all trades in their parts of the installation. Units must be installed in compliance with all applicable local code requirements.
IDENTIFYING AND PREPARING UNITS — Be sure power requirements match available power source. Refer to unit nameplate and wiring diagram. In addition:
• Check all tags on unit to determine if shipping screws are
to be removed. Remove screws as directed.
• Rotate the fan wheel by hand to ensure that the fan is
unrestricted and can rotate freely. Check for shipping
damage and fan obstructions. Adjust blower motor as
required.

INSTALLATION

CAUTION
Units are

Step 2 — Position the Unit

DANGER
Units must not be installed where they may be exposed to potentially explosive or flammable atmosphere. If this instruction is not followed exactly, a fire or explosion may result, causing property damage, injury, or loss of life.
Install the unit in a location that meets the following requirements:
• Allow adequate space for installation, service clearance, piping and electrical connections, and necessary ductwork. For specific unit dimensions, refer to Table 1 and Fig. 1. Allow clearance according to local and national codes.
• Confirm that the ceiling is able to support the weight of the unit. See Table 1 for nominal weight.
• There should be enough room within the false ceiling for installation and maintenance. See Fig. 2 below.
• The false ceiling should be horizontal and leveled.
• Install the unit in a location within the room that allows uniform air flow in all directions.
Select the unit position with the following points in mind:
• The unit should be installed in a position that is suitable to support the total weight of the unit, refrigerant piping and condensate.
• Proper access should be provided for maintenance for refrigerant piping, EEV (electronic expansion valve), electrical box, and condensate pump. A 2-ft clearance is recommended all around the unit.
• The unit should be at least 3 obstruction. See Fig. 3 below.
6
1
/4 ft from a wall or similar
• Do not position where the discharge air could blow
Fig. 3 — Distance from Wall or Obstruction
40 in. MIN.
40 in. MIN.
40 in. MIN.
40 in. MIN.
a40-1720
Unit body
Install the paper board
Central hole
Screw M6×12
Fig. 4 — Paper Board Mounting Hole Locations
Fig. 5 — Example of Buffer Locations
Buffer
Fig. 6 — Mounting Hole Locations
í
í
í
í
directly on the thermostat.
• Recommended distance between 2 units is 10 ft to avoid conflicting airflow and recirculation.
• The unit should not be positioned directly above any obstruction.
• The unit must be installed square and level.
• The condensate drain should have sufficient downward slope (1 in. per 100 in.) in any horizontal run between unit and drain. Maximum condensate lift is 29
1
/2 inches.
See Fig. 5 for an example of some buffer locations.
The actual quantity shall prevail

Step 3 — Mount the Unit

INSTALLING HANGER BOLTS — Install the hanger bolts at the locations shown in Fig. 6. Use For unit weight, see Table 3.
3
/8-in. all-threaded rod.
IMPORTANT: Be sure that the ceiling grid is supported separately from the unit. The ceiling grid must not be supported by an part of the unit or any associated wiring or piping work.
In case of new construction, once the unit is installed, please
cover the fan motor opening using the construction cover board to avoid any dust and debris from settling inside the unit. Use the M6 bolt, washer and nut as shown in Fig. 4 below.
Remove all buffers between the fan and the flared mouth before installing the indoor unit. Failure to do so will cause
CAUTION
damage to the fan motor.
CAUTION
To avoid equipment damage ensure the unit is placed horizontally.
Table 3 — Unit Weight
40VMF UNIT WEIGHT (lb)*
009 71.0 012 71.0 015 71.0 018 86.0 024 86.0 030 86.0 036 86.0 048 86.0
*Includes grille weight.
MOUNTING UNIT — The unit can now be lifted on to the hanging rods for mounting.
1. Use rods and fasteners to suspend the unit at the factory­provided mounting holes.
2. Adjust the height of the unit until the bottom (without grille) is level with the false ceiling.
3. Secure the unit in position with locknuts and washers on both sides of the unit bracket. Ensure that the threaded rod does not protrude more than 2 in. below the mounting brackets as shown in Fig. 7.
7

INSTALLING PANEL

Fig. 7 — Threaded Rod
a40-1722
Fig. 8 — Removing Grille from Panel
GRILLE LATCHE
S
CORD
45°
Fig. 9 — Mounting Panel
Louver motor
Louver motor
Drainage pipe joint
Hook
Panel hook
Piping joint
Hook bolt
Phillips screwdriver
Fig. 10 — Condensate Piping
MIN. GRADIENT
2
5
8
TO 3
14
ft
INSULATION
INDOOR
UNIT
FLEXIBLE DRAIN
CONDENSATE HOSE CLAMP
CONNECTOR
PVC DRAIN
PIPE
Fig. 11 — Condensate Drain Connection
NOTE: Panel is ordered separately.
1. Remove the grille from the panel by sliding the grille latches toward the center of the panel.
2. Lift the grille up at a 45-degree angle and pull to detach it from the panel.
3. Unscrew the bolts on the 4 corners of the cover panel. Remove the cover by loosening the cord. See Fig. 8.
5. When the panel is secure, insert the grille at a 45-degree angle and latch it in place.

Step 4 — Connect Piping

CONDENSATE PIPING — The unit is supplied with a 1 1/4­inch OD drain connection to connect copper or plastic drain piping. When installing condensate piping, follow these recommendations:
• Maximum pump lift is 29
• The highest point in the condensate piping should be as close to the unit as possible. See Fig. 10-12 below.
1
/2 inches.
4. Secure the panel (without the grille) onto the unit, using M5 x 16 screws and washers. Before tightening the screws, be sure the panel is flush with the false ceiling. See Fig. 9.
8
• Condensate piping should slope downward in the
Fig. 12 — Using a Main Drain to Serve Multiple Indoor Units with Internal Condensate Pumps
2“~4”
2“~4”
2“~4”
Max. 3-3/4 ft.
7-7/8”
7-7/8”
7-7/8”
Connection assembly of water outlet Main drainage pipe
Gradient: 1/50~1/100
direction of condensate flow, with a minimum gradient of 1 in. per 100 inches.
• When multiple units are connected to a common condensate drain, ensure that the drain is large enough to accommodate the volume of condensate from all units. It is also recommended to have an air vent in the condensate piping to prevent air lock.
• Condensate piping must not be installed where it may be exposed to freezing temperatures.
REFRIGERANT PIPING
CAUTION
When connecting from an indoor unit to an outdoor unit, the isolation valve at the outdoor unit should be in the closed position throughout the refrigerant piping process. Failure to follow this procedure may result in equipment damage.
When connecting from an indoor unit to an outdoor unit,
follow these procedures:
• Check maximum height drop and length of refrigerant piping between the indoor and outdoor units. To ensure the drop and length are acceptable, refer to the refrigerant piping allowable limits in the outdoor unit installation manual.
• The number of bends in the refrigeration piping must be fewer than 15.
• Refrigerant piping connection between indoor and outdoor units should be performed once the units are secured at their respective installation locations.
• The refrigeration piping starts at the indoor unit and ends at the outdoor unit or Multiport Distribution Controller (Heat Recovery systems).
• The refrigerant piping should be dry and free of dust and other impurities.
• The bending angle of the refrigerant pipe should not exceed 90 degrees and the bending radius should be as large as possible to prevent any breakage in piping.
• Use proper cutting and flaring tools to avoid leakage.
• Use a torque wrench for flare nuts. Refer to Table 4 for flare nut torque recommendations.
Table 4 — Flare Nut Torque Recommendations
OUTSIDE DIAMETER (in.) RECOMMENDED TORQUE (ft-lb)
1/4 15 3/8 26 1/2 41 5/8 48
• Before insulating the suction and liquid refrigeration pipes, perform pressure and leak tests. For details, see the outdoor unit installation manual. Insulating both suction and liquid refrigerant pipes is mandatory.
• Vacuuming and charging of the system should be carried out as described in the outdoor unit installation manual.

Step 5 — Complete Electrical Connections

Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA (American National Standards Institute/ National Fire Protection Association) 70, current editions. Units must be electrically grounded in conformance with the code. In Canada, wiring must comply with CSA (Canadian Standards Association) C22.1, Electrical Code.
WARNING
Electrical shock can cause personal injury and death. Disconnect power supply before making wiring connections. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
All units must be wired strictly in accordance with the wiring diagram furnished with the unit. Any wiring different from the wiring diagram could result in personal injury and property damage.
CAUTION
Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 221 F.
Ensure supply voltage to the unit, as indicated on the serial plate, is not more than 10% over the rated voltage or 10% under the rated voltage.
Failure to follow these recommendations may result in equipment damage.
This equipment in its standard form is designed for an
electrical supply of 208/230-1-60. Any damage to or failure of units caused by incorrect wiring or voltage is not covered by warranty.
Electric wiring must be sized to carry the full load amp
draw of the motor, starter, and any other controls that are used with the unit. See Table 5 for electrical data.
After the pipe work is complete, the electrical supply can be
connected by routing the cable through the appropriate casing holes or knockouts and connecting the supply and ground cables to the unit’s power terminal.
9
Be sure the power wiring and control wiring do not cross, as
Fig. 13 — 40VMF009-048 Typical Wiring Diagram
LEGEND
NOTE: Field wiring must use copper conductors only.
ACB Auxiliary Control Board AUXH Output For Auxiliary Heat CS Condensate Switch CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor GM Louver Motor HTON Output For Heating Operation MDC Multiport Distribution Controller PUMP Pump Motor T1 Indoor Temperature Sensor T2A Evaporator Temperature Sensor T2B Evaporator Outlet Temperature Sensor XP1-9 Plug XS1-9 Jack XT1-2 Terminal Block
----------- Optional Component or Field Wiring
Main Board
HA
HB
To wired controller comm. bus
ENC2
SW8
T2A T1
T2B
XP1-XP3
XS1-XS3
BLUE
WHITE
RED
XS4
XP4
XP6
XS6
XP5
XS5
CN2
POWER IN
Attention: For the convenience of
terminals can be pulled
wiring, the
communication
out from the main board.
SW1
CS
CN12
CN11
MDC units comm. bus
T
o outdoor/indoor/
BLUE
RED
CN3
CN18
XT1
FM
ALARM
CN24
CN52
CN9
EEV
CN21
CN5
CN8
CN50
15NC15NC
ACB interface
PUMP
GM
GM
Display board
CN15
L1 L2
Y/G
( Current range: 0-1A)
FAN
CTON
HTON
AUXH
( Voltage range: 0-24V AC/DC)
CN54
ON/OFF SWITCH
XP7
XP8
P Q
P Q
CN14
Occupancy sensor/ON-OFF (Dry contact)
ENC1
“ +5V GND +12V ” ONLY USED FOR TESTING
this might cause disturbance on the controls side. See Fig. 13 for wiring diagram.
NOTE: The indoor unit requires its own power supply. Indoor units are not powered through outdoor units.
Table 5 — 40VMF Electrical Data
40VMF UNIT SIZE
009 0.73 15 012 0.91 15 015 1.10 15 018 2.00 15 024 1.30 15 030 1.70 15 036 2.30 15 048 2.40 15
LEGEND
MCA — Minimum Circuit Amps MOPD — Maximum Overcurrent
Protective Device
POWER SUPPLY
MCA MOPD
10

Step 6 — Position and Connect Controller

Fig. 14 — Communication Wire Connection
To outdoor/indoor/MDC units
comm. bus
To wired controller comm. bus
XT2
Fig. 15 — Shearing Outdoor Connector
Fig. 16 — Stripping the Wire
Fig. 17 — Connecting Communication Wire to
Outdoor Unit Communication Terminal
Fig. 18 — Connecting the Communication Wires
Wired controllers should be installed in a position that maintains good temperature control:
• Position the thermostat approximately 48 in. above floor level.
• Do not position thermostat where it can be directly affected by the unit’s discharge airstream.
• Avoid external walls and drafts from windows and doors.
• Avoid positioning near shelves and curtains as these restrict air movement.
• Avoid heat sources such as direct sunlight, heaters, dimmer switches, and other electrical devices
• See Fig. 14 for an example of communication wire connection.

CONTROL WIRING

1. Use copper core PVC insulated sheathed shielded twisted cord.
2. For IDU (indoor unit) and ODU (outdoor unit) communication, use ‘P, Q” terminals. Shielded core should be used for ground.
3. Wiring should be done according to wiring diagram.
4. Communication wire must not form a closed loop.
3. Use a suitable screwdriver to fix the communication wire on the outdoor unit communication terminal as shown in Fig. 17 below.
If communication wires are use to connect indoor units, then find the corresponding port and plug it directly as shown in Fig. 18.
OPTION/EXTENSIONS OF COMMUNICATION WIRING — To extend control wiring or make terminal connections, use the PQE connection wire supplied in the accessory kit and follow the steps below.
1. Cut the connector on the outdoor unit side as shown in Fig. 15 below.
If for any reason it is not possible to buy communication wires from Carrier, connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig. 19. See Fig. 20 and 20 for typical communication wiring of the heat pump and heat recovery systems.
CAUTION
Failure to follow these procedures may result in personal injury or damage to equipment.
NEVER CONNECT the main power source to the control or communication terminal block.
USE AN APPROPRIATE SCREWDRIVER for tightening the terminal screws. Do not over tighten the terminal screws.
IMPORTANT: Communication wiring shall be 2 in. or more apart from power source wiring to avoid electric noise. (Do not insert control/communication and power source wire in the same conduit.)
Pay attention to the polarity of the communication wire.
2. Strip a suitable length of the insulation layer as shown in Fig. 16 below.
11
Connector in accessory kitConnector on indoor unit Communication cable
in field
Fig. 19 — Connecting the Communication Cable to Indoor Unit to Outdoor Unit Using the Supplied Connector
12
P Q
X Y
X Y
MDC unit
Centralized controller
outdoor unit
P Q
P Q
P Q
P Q
P Q
P Q
To No.1 indoor
To No.2 indoor
To No.3 indoor
To No.4 indoor
To No.1 indoor
To No.2 indoor
To Sub MDC
To outdoor
Main MDC unit
To outdoor
L1
L2
L3
L3
L3
L3
L4
L4
L5
L6
L7
L8
L9
L10
L11
Indoor unit 1#
HA HB
Indoor unit 2#
HA HB
Indoor unit 3#
HA HB
Indoor unit 4#
HA HB
Indoor unit 5#
HA HB
Indoor unit 6#
HA HB
HA HB
Touch screen
NOTE: 24 v. DC Power
wired controller
(Field Supplied)
wired controller
HA HB
NOTE: Power from IDU
Maximum wiring length: L1+L2 </= 3937 ft 18 AWG, 2-Core Stranded Shield L3 </= 3937 ft 18 AWG, 2-Core Stranded Shield L4 </= 3937 ft 18 AWG, 2-Core Stranded Shield L5 </= 3937 ft 18 AWG, 2-Core Stranded Shield L6+L7+L8+L9 </= 820 ft 18 AWG, 2-Core Stranded Shield L10+L11 </= 820 ft 18 AWG, 2-Core Stranded Shield
LEGEND
MDC
Multiport Distribution Controller
IDU
Indoor Unit
Fig. 20 — Typical Heat Recovery Communication Wiring Diagram
13
Fig. 20 — Typical Heat Pump Communication Wiring Diagram
P Q
X Y
X Y
Centralized controller
outdoor unit
P Q
P Q
P Q
P Q
P Q
P Q
L1
L3
L5
L6
L7
L8
L9
L10
L11
L3
L3
L3
L3
Indoor unit 1#
HA HB
Indoor unit 2#
HA HB
Indoor unit 3#
HA HB
Indoor unit 4#
HA HB
Indoor unit 5#
HA HB
Indoor unit 6#
HA HB
P
Q
Network Resistor
HA HB
Touch screen
NOTE: 24 v. DC Power
wired controller
(Field Supplied)
wired controller
HA HB
NOTE: Power from IDU
Maximum wiring length L1+L3 </= 3937 ft 18 AWG, 2-Core Stranded Shield L5 </= 3937 ft 18 AWG, 2-Core Stranded Shield L6+L7+L8+L9 </= 820 ft 18 AWG, 2-Core Stranded Shield L10+L11 </= 820 ft 18 AWG, 2-Core Stranded Shield
LEGEND
IDU
Indoor Unit
NOTE: Network resistor is shipped with the outdoor unit for field installation on heat pump systems.
14
ACB Interface — The ACB interface is a dry contact
LEGEND
ACB
Auxiliary Control Board
AUXH
Output For Auxiliary Heat
CTON
Output For Cooling Operation
FAN
Output For Fan Operation
HTON
Output For Heating Operation
MAX AMPS 1A
MAX VOLTAGE 24V
Fig. 21 — ACB Interface
CN51

ACB interface

CN50
FAN
CTON
HTON
AUXH
board, it can output up to four signals controlling devices. Please refer to Fig. 21 for connecting devices to the ACB interface board.
Pre-Start Check —
the following pre-start checks:
1. All indoor and outdoor units are properly installed.
2. All piping and insulation is complete.
3. All electrical connections (both power and control) are properly terminated.
4. All condensate drains are installed correctly.
5. The power supply is of the right voltage and frequency.
6. The units are properly grounded in accordance with current electrical codes.
7. Suction and liquid line isolation valves are in open position.

System Operation CheckOnce the installation

and pre-start checks are completed, follow these steps:
1. Using remote controller, select cooling or heating mode to check the operation of the system.
2. While the system is in operation, check the following on indoor unit:
a. Switches or buttons on the remote controller are easy to
push.
b. Indicator light is showing normal operation and no
error is indicated.
c. Swing mode of air louvers is working (if applicable to
unit).
d. Drain pump operation is normal (if applicable).
e. No abnormal vibration or noise is noticed.
3. While the system is in operation, check the following on outdoor unit:
a. No abnormal vibration or noise is noticed.

START-UP

Once installation is complete, make
b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no
error is indicated.
NOTE: If the unit is turned off or restarted, there is a time delay of 3 minutes for the compressor to start from the time the power is restored.

MAINTENANCE

CAUTION
When servicing or repairing this unit, use only factory­approved service replacement parts. Refer to the rating plate on the unit for complete unit model number, serial number and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk and may result in equipment damage.
CAUTION
To avoid equipment damage, do not attempt to reuse any mechanical or electrical controllers that have been wet. Replace defective controller.
EVERY 3 MONTHS:
• Check the air filter condition. Clean or replace if necessary.
EVERY 6 MONTHS — Follow 3-month maintenance schedule. In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel.
EVERY 12 MONTHS — Follow 6-month maintenance schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation.
• Check the heating and cooling action to confirm proper operation.

INDOOR UNIT ADDRESSING

For proper system operation each indoor unit must have a
unique address set from 0 to 63. When setting an address by remote controller the outdoor units, indoor units, and MDC must be powered on. If “FE” is displayed on the LED screen or display board this unit has no address. After setting all indoor units’ addresses, turn off the power supply to all indoor units to clear errors.
Indoor units’ addressing can be distributed automatically in
the heat pump system. When dip switch “S6” on the outdoor units main PCB board is set to 00 (default set in factory) indoor unit’s are set for auto-addressing. When powering on for the first time it takes 6 minutes or more to finish auto-addressing each indoor unit. The heat recovery system cannot accomplish this function at this time.

Wireless Remote Controller (40VM900001)

Indoor unit addressing can be performed using the wireless
remote controller. When using the wireless controller, the user must maintain a line of sight with the receiver on the indoor unit. See Fig. 22 for a description of the buttons on the wireless remote.
15
Use a tool to press and hold the LOCK button for at least 10
RESET
TIMERON
TIMEROFF
SWING
AIRDIRECTION
CLOCK
OK
SWING
MODE
FAN
AUTO
COOL
DRY
HEAT
FAN
TEMP
SET
CLOCK
SET
HOUR
FANSPEED
LOCK
C/H
6 – AIR DIRECTION
2 – FAN SPEED SETTING
4 – ADJUST UP
9 – CLOCK SETTING
14 – OK (CONFIRM)
10 – TIMER ON
11 – TIMER OFF
1 – MODE SETTING
3 – ADJUST DOWN
12 – RESET
13 – LOCK
15 – COOL/HEAT
5 – ON/OFF
7 – AIR VERT. SWING
A40-1734
Fig. 22 — Wireless Remote Controller
(40VM900001)
MODE
FAN TEMP. DOWN
OK
TEMP. UP ON/OFF
TIMER
ROOM TEMP.
SWING
#
Fig. 23 — Non-Programmable Controller
(40VM900002) IDU Addressing Menu
#
MODE
FAN TEMP. DOWN
OK
ON/OFFTEMP. UP
TIMER
ROOM TEMP.
SWING
Fig. 24 — Non-Programmable Controller
(40VM900002) Setting IDU Address
Fig. 25 — Programmable Controller
(40VM900003) IDU Addressing Menu
MODE
FAN
MENU
TEMP. DOWN
TEMP. UP
OK
BACK
ON/OFF
seconds, then press to activate. Click or to select an address and press to send the setting.
To display an indoor unit address, use a tool to press and hold the LOCK button for at least 10 seconds, and press to query the addresses.

Non-Programmable Controller (40VM900002)

When setting an address, connect only one wired controller to an indoor unit.
Press ROOM TEMP and SWING simultaneously for 3 seconds. If there is no address for this indoor unit, the display shows FE# 00 (see Fig. 23). Otherwise, the display shows the current address of the indoor unit.
Click TEMP. UP or TEMP. DOWN to change 00 to the desired address as shown in Fig. 24. Then press OK to confirm and exit the setting interface.
Programmable Controller (40VM900003) —
When setting an address, connect only one wired controller to an indoor unit.
1. Press FA N and BACK simultaneously for 5 seconds to access parameter settings as shown in Fig. 25.
2. Press TEMP. UP or TEMP. DOWN to move the cursor and choose IDU ADDRESSING, then MENU/OK to access this setting.
16
3. Press TEMP. UP or TEMP. DOWN to choose the
Fig. 26 — Programmable Controller
(40VM900003) Setting IDU Address
MODE
FAN
MENU
TEMP. DOWN
OK
TEMP. UP
BACK
ON/OFF
Fig. 27 — LED Display Panel
A40-1716
OPERATION TIMER DEF./FAN ALARM
a40-1842
address you want to set, see Fig. 26. Press MENU/OK to send this address to the IDU.
4. Press BACK twice or wait 30 sec. to automatically exit the parameter settings menu.

TROUBLESHOOTING

Figure 27 shows the LED display panel on the indoor unit. See Table 6 for a summary of display indicators. Table 7 lists problems, possible causes, and possible solutions.
17
Table 6 — Display Indicators
TYPE DIGITAL DISPLAY MODE/STATUS
Setting Temperature Starting “--” Shutdown “--” Standby
[NO ERROR]
ERROR
LEGEND
ACB Auxiliary Control Board EEPROM Electronically Erasable Programmable Read-
EEV Electronic Expansion Valve MDC Multiport Distribution Controller
only Memory
“--” Timing ON “--” Timing OFF Setting Temperature System Defrost ON Setting Temperature System Defrost OFF Room Temperature Only Fan
dd Heating / Cooling Mode Conflict Error E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Temperature Sensor (T1) E4 Check Evaporator Outlet Temperature Sensor (T2B) E5 Check Evaporator Temperature Sensor (T2A) E6 Check DC Fan E7 EEPROM Error (Data Storage) E9 Communication Error Between Indoor Unit and Wired Controller. Eb EEV Error Ed Outdoor Unit Error EE Condensate Overflow FE No Address When Powered ON For First Time
UU MDC In Auto System-Check Mode.
18
Table 7 — Troubleshooting
Fig. 28 — Unit Serial Plate (Example)
MODEL
R410A
HIGH
LOW
4-WAY CASSETTE UNIT
REFRIGERANT
0.73 A
15 A
0.59 A
80W (1/8HP)
40VMF009A--3
208/230V-1Ph- 60Hz
320 PSIG
580 PSIG
DESIGN PRESSURE
POWER SUPPLY
MINIMUM CIRCUIT AMPACITY
FAN MOTOR
FLA
MAX FUSE OR HAC R BREAKER
OUTPUT
CONFORMS TO ULS TD 1995 CERTIFIED TO CSA STD. C22. 2 No. 236
3124627
ELECTRIC CHARACTERISTICS ARE ONLY FOR INDOOR UNIT.
SERIAL NO .
1616V000 01
Carrier Corporation
DIGITAL
DISPLAY
dd Heating/Cooling Mode Conflict
DESCRIPTION POSSIBLE CAUSES POSSIBLE SOLUTIONS
System is in cooling or fan mode only and heating signal is received from a
All units should be in cooling mode for system to stay in cooling mode.
unit in the system. System is in heating mode and cooling
signal is received from a unit in the
All units should be in heating mode.
system.
E1
Communication Error Between Indoor and Outdoor Unit
Signal wires are short-circuited or disconnected.
Signal wires close to electromagnetic source.
Check or reconnect signal wire.
Distance signal wires from electromagnetic
source. PC board fault. Replace PC board. Loose connection at port on PC board. Tighten the connection at port on PC board.
E2, E4, E5 Check Temperature Sensor
Sensor is short-circuited. Using multi-meter, measure resistance of the
sensor. If the resistance is 100 ohms, change
the sensor. PC board fault. Replace PC board. Operating beyond limits. Check and correct external static pressure on the
E6 Check DC Fan Motor
DC motor fault. Replace DC motor.
unit.
PC board fault. Replace PC board.
E7 EEPROM Error (Data Storage) Chip or PC board fault. Replace PC board.
E9
Communication Error Between Indoor Unit and Controller
Signal wires are short-circuited or disconnected.
Signal wires close to electromagnetic source.
Check or reconnect signal wires.
Distance signal wires from electromagnetic
source. PC board fault. Replace PC board.
Eb EEV Error
EEV wires are short-circuited or disconnected.
EEV stop. Replace EEV.
Check or reconnect signal wire.
PC board fault. Replace PC board.
Ed Outdoor Unit Error Outdoor unit fault. Refer to outdoor unit troubleshooting guide.
EE Condensate Overflow
Loose connection or disconnected at port on PC board.
Condensate switch float is stuck. Inspect the float. Trap slope is too steep. Adjust the trap slope.
Tighten the connection or reconnect at port on
PC board.
Drain pipe is too long. Adjust the length of the drain pipe. Drain pump faulty. Replace the drain pump.
Run automatic addressing option at the outdoor
FE
No Address When Powered ON For First Time
Indoor unit without address.
unit.
Use remote wireless or wired controller to
readdress the indoor unit.
UU MDC In Auto System-Check Mode MDC Fault. Refer to MDC troubleshooting guide.
LEGEND EEPROM Electronically Erasable Programmable Read-only
Memory
EEV Electronic Expansion Valve MDC Multiport Distribution Controller PC Process Controller

Replacement PartsQuote the unit type and unit

serial number when ordering replacement parts or contacting the factory about the unit. This information can be found on the serial plate attached to the unit. See Fig. 28.
19

APPENDIX A — DIP SWITCH SETTINGS

ON
OFF
ON
OFF
1234
a40-1923
ON
OFF
1234
a40-1923
ON
OFF
1234
a40-1923
ON
OFF
12
a40-1925
There are 2 DIP switches on the main board. Figures A and B show the settings for each parameter controlled by a switch. Switches are shown in the default settings.
POSITION 1, 2 — NOT USED
POSITION 1 — START-UP
OFF Auto Addressing Mode (Default)
ON Factory Test Mode
POSITION 2
OFF Normal Mode (Default) ON Factory Self-Checking Mode
POSITION 3 — NOT USED
Fig. B — SW8 SETTINGS
POSITION 4 — INDOOR UNIT IDENTIFICATION
OFF Standard Indoor Unit (Default) ON Mode Priority Indoor Unit (HP Only)
(IDU address must be 63)
Fig. A — SW1 SETTINGS
© Carrier Corporation 2018
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 18-40VMF002-01 Printed in U.S.A. Form 40VMF-2SI Pg 20 1-18 Replaces: 40VMF-1SI
Loading...