Consult local building codes and National Electrical
Code (NEC) for special installation requirements.
When installing unit, allow sufficient space for airflow
clearance, wiring, refrigerant piping and servicing unit.
Recommended minimum requirement is 3 ft (Fig. 1).
Position unit so water from roof or eaves will not pour
directly on top of unit.
Install unit on a solid, level mounting pad. Position
tie-down bolts in pad. Any 2 holes in unit base may be used
to fasten unit to pad.
38GR Condensing Units Connected to Carrier-Approved
Evaporators with Carrier Accessory Tubing — 38GR units
contain correct refrigerant charge when evaporator is same
size, or one size larger than condensing unit and are
connected with Carrier accessory tubing. Check refrigerant
38SE,GR
SUCTION LINE CONN (ON SERVICE VALVE)
LIQUID LINE
CONN.(ON SERVICE,!
VALVE)
5." |3'*
16 “ ' 8
MTG SLOTS
(USE ANY 2)
uSl SPACE REQUIRED FOR SERVICE
--------------
10^
CONCRETE MOUNTING PAD^(SQUARE OR CIRCULAR)
^CONCRETE PAD SHOULD WEIGH |-| TO 2 TIMES WEIGHT OF UNIT
DIAM HOLE
FOR CONTROL
WIRIN(3
Fig. 1 — Dimensions, Connections and Mounting Pad
Table 1 — Installation Data
CONDENSING UNIT
OPERATING WT (lb)
DIMENSIONS
(ft-in.)
REFRIG
CONN.
*38GR005,006 and 38SE004,045,055 supplied with 3/4-in to 1 1 /8-in suction valve connection adapter (field installed) for 1 1 /8-in suction
line (field supplied)
Diam A
Height В
Suet ODF
Liq ODF
002
151170182194 1 234
2-4
003
2-42-42-4
%
y.
38GR
004
2-5У4
L
V
4
charge when tubing lengths are above 50 feet. See Refrig
erant Charging for details.
38SE Condensing Units Connected to Carrier-Approved
Evaporators — 38SE units contain correct system refrig
erant charge when evaporator is same size as condensing
unit, and they are connected with 25 ft or less of
field-supplied tubing of recommended size (see Piping
Connections) or 50 ft or less of Carrier accessory tubing.
Check refrigerant charge for maximum system efficiency.
See Refrigerant Charging for details.
38GR,SE Condensing Units Connected to Non-Carrier
Evaporators — Check refrigerant charge when the 38GR,SE
is added to a system in which other than a Carrier approved
evaporator is being used or where the evaporator has been
previously installed. Field-supplied refrigerant piping must
be in accordance with Refrigerant Piping Data table.
Use an evaporator coil with a bleed-type expansion
device. If coil does not have a bleed-type expansion device
it may be necessary to add an accessory start capacitor and
relay to condensing unit. This would require removing
compressor start thermistor (PTC device) on units so
equipped.
PIPING CONNECTIONS
The 38GR,SE condensing units can be connected to
evaporator sections using Carrier accessory tubing package
or field-supplied tubing of refrigerant grade (Accessory
tubing not available for 38GR006.) See Table 2 for
accessory tubing sizes and Table 3 for recommended
field-supplied tubing sizes. (Where evaporator is 20 ft or
more below condensing unit, reduce liquid line size one
diameter — min 1/4-in. OD.)
A capacity reduction results if accessory tubing is used
in 38SE004,045,055 systems. For example, when a 25 ft
accessory tubing package is used, there is a capacity
reduction of 2 1/2% on 38SE004, 3 3/4% on 38SE045 and
5% on 38SE055 systems. For maximum capacity from
these systems, use tubing sizes shown in Table 3.
Connection Recommendations — Do not use damaged or
contaminated tubing. Do not use less than 10 ft of liquid
line. Do not cut 5/16-in or 1/4-in. liquid line. Bend or coil
to fit.
If accessory tubing package or evaporator section has
been open for more than 15 seconds per connection,
evacuate or purge evaporator coil and tubing system (use
field-supplied refrigerant, not unit refrigerant) Always
evacuate or purge if field-supplied tubing is used.
When making piping connections, be sure to provide
clearance at unit for electrical connections.
Connect refrigerant liquid and suction lines to condensing
unit (Fig 1). Unit compatible fittings permit mechanical
(quick-connect) or sweat connections.
Table 2 — Accessories
PART NO.
HH01AD040
HH93AZ040
HH51AR001
HH07AT070,
HH07AT074
HH93AZ076
HH01AD042
HH93AZ042
HH01YA092
HH93YZ094
32LT900301
Low-Voltage Control — Honeywell Deluxe Thermostat
Thermostat Subbase
Comfort Control Center (Use with HH01AD040.)
Low-Voltage Control — Honeywell Thermostat
Thermostat Subbase (with Automatic Changeover)
Low-Voltage Control — Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control — Grayson Thermostat
Thermostat Subbase
Solid State Head Pressure Control,
and/or motor required.
38GR005,006; 38SE004.045.055 Units - When using
1 1/8-in. field-supplied siictlSff'line, remove suction line
adapter taped to compressor suction line. Connect 3/4-in.
end of adapter to unit suction line compatible fitting.
Sweat connect refrigerant suction line to 1 1/8-in. end of
adapter. Connect liquid refrigerant line to unit. When a
7/8-in. field-supplied suction line is used on 38SE003 or
38GR045, a field-supplied 3/4-in. to 7/8-in. suction line
adapter must be provided.
MECHANICAL CONNECTION (Mate one set of connec
tions at a time.)
1. Loosen nut on compatible fitting one turn. Do not
remove.
2. Remove plug and be sure 0-ring is in the groove inside
the compatible fitting.
3. Cut tubing to correct length.
4. Use gage on tag attached to service valve to mark tube
end for correct insertion depth. Insert tube into com
patible fitting until it bottoms. (Tube should be inserted
at least as far as mark on tubing.)
5. Tighten nut until it bottoms on back coupling flange
SWEAT CONNECTION (Use refrigerant grade tubing.)
1. Remove locking nut, rubber 0-ring and Schrader core
from valve.
NOTES:
1 Systems with over 50 ft separation between condensing unit and evaporator require refrigerant
2 Reduce liquid line diameter by 1/8-in OD (minimum 1/4-in OD) when evaporator is 20 ft or
REFRIGERANT LINE LENGTH (ft)
25-50
Below
Evap
50
90
50
90
90
50
90
90
50
charge adjustment to ensure the proper superheat at compressor See Refrigerant Charging, page
5 Oil charge adjustment may also be required
Suet
%
^4%
%
IVs
iVs
V
u
Vs
IVa
IVs
iVa
Liq
%V4
%
%
%
%
V
'8
V
'8
%
\
%
Suet
51-75 76-100
Line Diameter (in. OD)
SuetLiq
Liq
VsV4
V4VsV4
V4VsVs
Vs
V
IVs
V
IVs
Vs
V
VsVs
/A
V
Vs
'8
IVs
%
IVs
V
IVs
V
VsV.
IVs
IVsVs
Vs
IVs
IVs
IVs
Vs
VsV4
VsVsV2
V
Vs
Vs
Vs
V2
V.
101-125
SuetLiq
V4
Vs
IVs
IVs
V
/8Vs
Vs
IVs
IVs
IVs
Vs
Vs
V
V
Vs
Vs
Vs
V
Va
126-150
Suet
V4Vs
V,Vs
Vs
Vs
IVs
IVs
VsVs
Vs
IVs
IVs
IVs
Liq
Va
Va
Vs
Vs
V
'8
Vs
Va
Vs
more below condensing unit
3. Insert tube into compatible fitting. Wrap top and
bottom of service valves in wet cloth to prevent damage
by heat. Solder with low-temperature (450 F) silver
alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied refrigerant.
SERVICE DOOR
Service door can be opened or removed for wiring or
servicing unit
Remove 3 screws from left side of service door (Fig. 1)
to swing door open.
Door Removal — Turn power off. Disconnect wiring from
control panel mounted on door. Refer to Fig. 7 and 8.
After wiring is disconnected, lift door from roll pin hinges.
ELECTRICAL DATA AND WIRING
Field wiring must comply with local and national fire,
safety and electrical codes. Voltage to unit must be within
± 10% of voltage indicated on nameplate. On 3-phase units,
phases must be balanced within 2%. Contact local power
company for correction of improper line voltage.
See Table 4 for recommended wire and fuse sizes. When
making electric connections, provide clearance at unit for
refrigerant piping connections.
Table 4 — Electrical Data
COND
UNIT
V/PH
OPER
VOLTS*
COMPR
LRAFLA
MaxMin
38GR002---
38GR0023I0
38GR003---
38GR003310
38GR004---
230/1253207
38GR0043J0
38GR045---
38GR005---
38GR006---
38GR003---
38GR0034Í0
38GR004---
38GR0044J0200/3
38GR045---
220180
72.0
72.0
90.0
90.0
100.0
100 0
94.0
106.0
135.0
60.0
70.0
69.0
80 0
79.0
38GR005---87.0
38GR006---
38GR003---
38GR0035Í0
113.024.0
50.0
60.0
38GR004---60.0
38GR0045J0230/3
38GR045--38GR005---
38GR006--38GR004---
38GR004610
38GR045---
460/3
38GR005--38GR006---
38SE002--.
38SE003--38SE004---
230/1
38SE045---
38SE055---
L
__
253
506
253
20770.0
414
207
67.0
70.0
98.0
30.0
35.0
35 0
35.0
49.0
65.0
72.0
90.0
94.0
106.0
Corresponding wire sizes and wire lengths
FLA — Full Load Amps
LRA — Locked Rotor Amps
--------Electrical data shown applicable to all units for which com
plete model numbers are not shown Example: 38GR003--applies to all 003 models except 38GR003Ji0.
FANBRANCH CIRCUIT
Wire
FLA
Sizet
(AWG)
14.8
14.81 012
19.2
19.2
22.91 3
22 9
23.91.3
27.92.0842 0 Í
39.02.06
13.0
13.0
14 0
14 0
16.71.312
18.32.0
11.5
11.5
12.6
12.6
14 3
16.4
19.9
6.5
6.5
7.2
8 8
10 4
10.3
14.8
19 2
23 9
28.0
1.01232.030
1.11039 040
1.1
1 3
1.1
1 112
1.312
1.3
2 0
1 1
1 112
1.3
1 312
1 3
2 010
2 01047 0
5
5
.5
1.3
1.3
.8
.8
.8
1 3
2.2
1. '32 030
10
10
10
849.0
1242.0
Ì
121.'^ zL.
Í
10
r
8
1225
mf.
12
1242 0
14
\-xi:
14
14
i n ;
14
1 n
14
14
1210
10
10»
10
39.0 L40
33.0
33-0
47.0
42.0
39.0
39.0 i: '30
33 0 i
46.040
64.0 /50
52.0 1
47.0
47.0
56.035
110.0
110.0
100.0 1
81.0 Í
70.{'
29 1 '■
40.0
*Permissible limits of the voltage range at which the unit will oper
ate satisfactorily
tCopper wire sizes and lengths Use latest National Electrical Code
(NEC) for aluminum wire sizing
-> Maximum dual element fuse size
NOTE Control circuit voltage is 24 volts on all units On 3-phase
units, phases must be balanced within 2%
Max
Ftt
Wire
32 0 $XÙ
32 0 SBJB
430
Fuse
Ampst
50
50
50
60
80
30
30
30
35
25
25
25
30
45
15
15
15
20
20
20
30
40
50
60
3-PHASE
CONN.TO
FUSED
DISCONNECT
I-PHASE
CONN TO
FUSED
DISCONNECT
— GROUND LEAD-
L
—
-
-----------------
■
---------------
--------
COND UNIT
GROUNDING LUG
BRN _
ORN
-----------
BLK
-----------
(38GR ONLY)
A—A Splice Connections
---------
Field Wiring
---------
Factory Wiring
Fig. 2 — Line Power Connections
Install a Branch Circuit Fused Disconnect of adequate size
to handle unit starting current Locate disconnect within
sight of and readily accessible to the unit, per section
440-14 of National Electrical Code (NEC).
1076
Bring Line Power Leads Into Unit — Extend leads from
fused disconnect thru hole provided in base pan (Fig. 1)
and into unit junction box.
CONNECT GROUND LEAD TO GROUND LUG OR
SCREW IN JUNCTION BOX for safety. Connect power
wiring. See Fig. 2. Splice line power leads to brown and
orange pigtails on 1-phase units or brown, orange and black
pigtails on 3-phase units. Use wire nuts supplied with unit.
Tape each connection. When aluminum field wire is used,
lubricate splices with splice compound (also supplied)
before using wire nuts.
Control Power (24 v) wiring is brought thru hole provided
in unit base pan (Fig. 1) and into low-voltage section of
unit junction box. Splice control leads to yellow pigtails on
control relay. See Fig. 3. For aluminum wire splices use
factory supplied and lubricated wire nuts. Furnace or fan
coil transformer must be used as 24-v supply for system as
shown in Fig. 3. All 38SE units are equipped with
transformer used to power contactor thru unit control
circuit only, and must not be used to power thermostat
circuit.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.