Carrier 38EB User Manual

Number One AirCoxIitbning l\Mer
Installation, Start-Up '
Division of Carrier Corporatio
e
and Service Instructions
Air-Cooled Condensing Units
INDEX
SAFETY CONSIDERATIONS......................
INSTALLATION
Step 1 — Check Equipment and
Jobsite..............................................................I
• UNPACK UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER SYSTEM REQUIREMENTS
Step 2 — Make Piping Connections
• REPLACE THE ACCURATER™ REFRIGERANT CONTROL PISTON IN THE INDOOR COIL IF REQUIRED
• CONNECT REFRIGERANT LINES
Step 3 — Make Electrical
Connections....................................................5
• INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC
• ROUTE LINE POWER LEADS INTO UNIT
• CONNECT GROUND LEAD AND POWER WIRING
• CONNECT CONTROL POWER WIRING
START-UP
SERVICE............................................................. 8-10
MAINTENANCE..................................................11,12
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic mainten ance functions of cleaning coils and filters and re placing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing opera tions. Have fire extinguisher available for all brazing operations.
...........................................
_______
...........................................................
SAFETY CONSIDERATIONS
Page
.. 1
. 1-6
2
6-8
WAR-NiNG: Before perfosrmisg service or majnteiiatice орегайоиз or system, tarn off
vaaia power to isdoor tmit tsml outdoor
■ask. Тош off accessory beater power switch is
appiicaMe, E^ecfircal sihock, could cause per­s<mal injury.
Table 1 — Physical Data (Refer to Fig. 1)
MODEL38EB OPER WT(lb) DIMENSIONS (ft-in.)
Diameter A Height B
CONNECTIONS (in.)
Suction (ODF) Liquid (ODF)
REFRIG LINES
Suction (in. ODF) Liquid (in ODF)
*Fora1-1/8in suction line on 38EB048,060, a 3/4-in x 1-1/8 in suction
valve connection adapter is available as an accessory See Table 3
015 018
024
030
116
1-9-3/4
Recommended Field-Supplied Sizes
5/8 i 3/4 i 7/8 1 1-1/8
130
2-2-3/8 ) 2-8
5/8
137 165 181
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Slide from carton taking special care not to damage serv ice valves or grilles.
INSPECT EQUIPMENT — File claim with ship ping company if damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Maintain a minimum of 4 ft clearance from obstruc tions above and 18 in. on sides of unit. Maintain a distance of 24 in. between condensing units. Posi tion so water from roof or eaves does not flow directly on unit.
Install on a solid, level mounting pad. It is not necessary to attach unit to pad but if desired or required by local code, position tiedown bolts in pad. Fasten unit to pad using 2 holes provided in unit base. See Fig. 1.
036
2-2-3/8 1 2-8 1 3-2
3/
8
3/8
042
048 060 212 230.
2-5-1/4
3/4*
© Carrier Corporation 1982
Form 38EB-3SI
4'-0" OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW
LIQUID VALVE SERVICE PORT
CONDENSER AIRFLOW
KW r-6''AIRFL0W
■•••••■ AND SERVICE CLEARANCE
SUCTION VALVE SERVICE PORT
rectly sized for an evaporator of the same capacity as the condensing unit, so piston change is not neces sary. Mix-matching of condensing unit with evap orator requires field replacement of piston. Refer to Table 2. Replace piston, if required, before connec ting refrigerant lines. Piston replacement instruc tions are included in evaporator installation book.
After system installation is complete, use Charging Chart to check and/or adjust refrigerant charge.
Condensing Units Connected to Carrier-Approved Evaporators — Condensing units contain correct system refrigerant charge for operation with evap orator of the same size when connected by 25 ft or less of field-supplied or Carrier accessory tubing. Check refrigerant charge for maximum efficiency (see Refrigerant Charging, page 6).
Table 2 — Optimization Chart
(Outdoor air design temperature, db-F,
100 F and below)
COND
UNIT
38EB
015 TWl 46 i 018 ’ . 4
024 030 036 042 048 060
Factory-installed piston. Obtain replacement pistons thru
local Carrier distributor.
ACCURATER™ PISTON NO.
Evap Size (Coil or Fan Coil)
ÒTFI”M4TCÌ301
> I j_V'
52
57
036
TXV
65 6? 70
048 060
042
TXV
TXV
76
,...78...
_
62
TXV
i 82
^CONCRETE PAD SHOULD WEIGH 1^ TO 2 TIMES WEIGHT OF UNIT
Certified dimension drawings available upon request
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 1)
Carrier Cooling System Capacity Optimization —
AccuRater™ (bypass type) refrigerant control, with field-replaceable piston (see Fig. 2), is supplied on evaporator. Use Optimization Chart, Table 2 to find AccuRater piston size required for condenser/ evaporator system being installed. Pistons are cor-
njmm
Fig. 2 — AccuRater (Bypass Type)
Components
Step 2 — Make Piping Connections — Con
densing units may be connected to evaporator sec tions using Carrier accessory tubing package (Table
3) or field-supplied tubing of refrigerant grade, correct size and condition (Table 1). For tubing requirements beyond 50 ft, obtain information from local Carrier distributor.
If or
1$ osigd wism saaldog
If 1-1/8 in. tubing is used (38EB048,060), braze
it to the accessory 1 -1 / 8 x 3/4-in. suction connection
adapter (Carrier Part No. 28VQ900011) or to cor rectly sized field-supplied adapter, then make Com patible Fitting connections.
WARNING: iX> NOT BURY UNESETS- If
fdfigerans
E b. veitkaS Ui« to the vah;« irastxsciioiis m
Isolate interconnecting tubing from framing and ductwork or where tubing runs thru stud spaces, en closed ceilings or pipe chases. Use isolation type hanger (Fig. 3) since rigid fastening transmits pulsa tions to structure creating objectionable sound.
For maximum capacity on 38EB048 and 060 sys^ terns use 1 -1 / 8 in. suction line. A capacity reduction results if Carrier accessory tubing is used on these systems. (Example; When a 25-ft accessory tubing package is used on a 38EB048 system, the smaller suction line results in a 3% capacity reduction.)
Length of interconnecting tubing may necessitate refrigerant charge adjustment. Follow special re quirements described in Start-Up, Refrigerant Charging, page 6. Do not use less than 10 ft of inter connecting tubing. On Carrier accessory tubing packages, do not cut 5/ 16-in. or 1/4-in. liquid line or 7/8-in. suction line. These tubing packages have swaged ends that, if cut, will not fit into refrigerant line fittings. Bend or coil excess tubing to fit.
Do not use damaged, undersized or contaminated tubing. Always evacuate or purge evaporator coil
and tubing system. When purging, use field-supplied refrigerant, not unit holding charge refrigerant.
When making tubing connections, be sure to pro
vide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG ERANT CONTROL PISTON IN THE INDOOR COIL, if required, before connecting refrigerant lines. See Carrier Cooling System Capacity Optimi zation, page 2.
CONNECT REFRIGERANT LINES to fittings on condensing unit suction and liquid service valves (Fig. 1). Unit Compatible Fittings permit mechanical
(quick connect) or sweat connections. Models 38EB048,060 — When using 1 -1 / 8 in. field-
supplied suction line, use field-supplied 3/4-in. by
1-1/8 in. suction valve connection adapter (28VQ900011). Sweat connect refrigerant suction line to 1-1/8 in. end of adapter. Be sure to provide a heat sink at the service valve to prevent damage during sweating operation. Connect 3/4-in. end of
adapter to unit suction line Compatible Fitting. Connect liquid refrigerant line to unit. When a 7/8-in. field-supplied suction line is used, provide a field-supplied 3/ 4-in. to 7/ 8-in. suction line adapter. (Not necessary if 38LS accessory tubing is used.)
Mechanical Connection — (Mate one set of connec
tions at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure O-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length, deburr and size as necessary.
4. Insert tube into Compatible Fitting until it bottoms. Tighten nut until it bottoms on back coupling flange. Keep tube bottomed in Compat ible Fitting while tightening nut.
SweatT/onnection — (Use refrigerant grade tubing.-)
1. Remove locking nut, rubber O-ring and Schrader core and cap from valve service port.
2. Cut tubing to correct length, deburr and size as necessary.
3. Insert tube in Compatible Fitting until it bottoms. Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low­temperature (430 F) silver alloy solder.
4. Replace Schrader core and cap.
5. Evacuate or purge system using field-supplied refrigerant.
Table 3 — Accessories
PART NO.
38CQ900141 HH01AD040
HH93AZ040 HH07AT170
&
HH07AT174 HH93AZ176
HH01AD042 HH93AZ042
HH01YA192 HH93YZ194
38GS900102 38GS900212 HT32BH246 38UE900201 HC95DE088
HN61HB513
HC95DD121 HN61HB515
HC95DE066 HN61HB513
HC95DE088 HN61HB515
HC95DE088 HN61HB506
38EB660002 09WQ036,060 38GS900321
28VQ900011 Twelve 3/4- x 1-1/8 in Connection Adapters
PACKAGES
38LS958151 15 38LS958201 20
. 38LS958251 25 3/8
38LS958301 38LS958351 38LS958401 38LS958501
38LS934151 15 38LS934201 38LS934251 38LS934301 38LS934351 38LS934401 38LS934501
38LS978151 38LS978201 38LS978251 25 38LS978301 30 38LS978351 38LS978401 40
38LS978501
Solid-State Time Guard (Six 38CQ900152)
Low-Voltage Control Honeywell Deluxe Thermostat Thermostat Subbase
Low-Voltage Control
Honeywell Thermostat Thermostat Subbase
Low-Voltage Control Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control Grayson Thermostat
Thermostat Subbase
Indoor Fan Relay (Six HN61KJ210) Low-Voltage Transformer (Six 38GS900091) Crankcase Heater* Crankcase Heater Relay (Six 38UE900212)* Start Capacitor*
Relay* Start Capacitor*
Relay* Start Capacitor*
Relay* Start Capacitor*
Relay* Start Capacitor*
Relay*
Wire Bundle for Start Capacitors and Relays*
Refrigerant-to-Water Heat Exchanger for Chilled Water Systems Liquid Line Filter Drier
Length
(ft)
30 35 40 50
20 25 30 35 40
50 15
20
35
50
OD
(in.)
3/8 3/8 3/8 3/8
5/16 5/16 5/16 1/4
3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8 3/8
3/8 3/8
DESCRIPTION
Liquid
Tube End
OD (in.)
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8
3/8
TUBlNGt
Suctionj;
OD
(in.)
5/8 5/8 5/8 5/8 5/8 5/8 5/8
3/4 3/4 3/4 3/4
3/4 3/4 3/4 3/4 3/4
3/4 3/4
3/4
7/8
7/8
7/8
7/8
7/8
7/8
7/8
Tube End
OD (in.)
Evap
3/4** 3/4**
3/4**
3/4** 3/4** 3/4** 3/4**
3/4 3/4
3/4 3/4 3/4
3/4 3/4 3/4
3/4
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cond
MODEL
38EB
All
015300, 018300
024300, 030300
036310
042360
048310
All
048, 060
38EB
5/8
5/8
5/8
5/8 5/8 5/8 5/8
3/4 030, 036
3/4
3/4 3/4
3/4 3/4
015, 018, 024
r:'
*Available thru Carrier Service Parts tFor maximum capacities, use suction line sizes recommended in
Table 1 Use of accessory tubing packages smaller than recom
mended may result in slight capacity loss (see Note 2)
tSuction line is insulated and has a 90 degree bend at one end
**For 5/8-in evaporator connection, cut off 3/4-in end
NOTES
1 Do not cut 3/8-in OD liquid line toa length shorterthan 10feet
Do not cut 5/16-or 1/4-in liquid line Do not cut 7/8-in OD suction lines
2 Field-supplied 1-1/8 in suction line is recommended on
38EB048 and 060 If accessory tubing package is used, a capacity reduction can result
Loading...
+ 8 hidden pages