Carrier 30GX090, 30HXA086, 30GX105, 30GX106, 30GX115 Controls, Start-up, Operation, Service, And Troubleshooting

...
Page 1
Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and servicemechanicsshould install, start up, and service this equipment.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
To prevent potential damage to heat exchanger tubes al­ways run fluid through heat exchangers when adding or removing refrigerant charge.
DO NOT VENT refrigerant relief valves within a build­ing. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Soci­ety of Heating, Refrigeration and Air Conditioning En­gineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide ad­equate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT attempt to unbraze factory joints when ser­vicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use com­pressor oil.
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
GENERAL ...................................2
MAJOR SYSTEM COMPONENTS ..............3
Processor Module (PSIO-1) ...................3
DSIO-HV Relay Module .......................3
Electronic Expansion Device Module .........3
Compressor Protection Module (CPM) .........3
PSIO-2 (8052) Module ........................3
Keypad and Display Module
(Also Called HSIO-II) .......................3
Control (LOR) Switch .........................3
OPERATION DATA ..........................3-42
Electronic Expansion Device (EXD) ...........3
• EXV OPERATION
• ECONOMIZER OPERATION
Oil Pumps ...................................4
Motor Cooling ...............................4
Back Pressure Valve (30GX and 30HXA only) ..4
Sensors .....................................4
Compressor Protection Module (CPM) .........4
• OUTPUTS
• INPUTS
Wye-Delta vs Across-the-Line (XL)
Starting Option ............................5
Capacity Control .............................6
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LOADING SEQUENCE
• CLOSE CONTROL
• LEAD/LAG DETERMINATION
• CAPACITY SEQUENCE DETERMINATION
• MINIMUM LOAD VALVE
• CAPACITY CONTROL OVERRIDES
Head Pressure Control .......................8
• GENERAL
• AIR COOLED UNITS (30GX)
• WATER COOLED UNITS (30HX)
• ADJUSTING PID ROUTINES
Cooler and Condenser (30HXC)
Pump Control .............................10
30GX080-265
30HXA,HXC076-271
ECOLOGIC™ Air-Cooled and Fluid Cooled Chillers
50/60Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-062 Printed in U.S.A. Form 30G,H-3T Pg 1 1-98 Replaces: 30G,H-2T
Series 0,1,2
Page 2
CONTENTS (cont)
Page
• COOLER PUMP CONTROL
• CONDENSER PUMP CONTROL
Cooler Heater Control .......................13
Keypad and Display Module
(Also Called HSIO-II) ......................13
• ACCESSING FUNCTIONS
AND SUBFUNCTIONS.......................13
• AUTOMATIC DEFAULT DISPLAY.............13
• STATUS FUNCTION .........................16
• TEST FUNCTION ...........................25
• HISTORY FUNCTION........................25
• SET POINT FUNCTION ......................25
• SERVICE FUNCTION ........................30
• SCHEDULE FUNCTION......................37
Temperature Reset ..........................39
• EXTERNAL TEMPERATURE RESET
• EXTERNALLY POWERED RESET
• RETURN FLUID TEMPERATURE RESET
Demand Limit ...............................39
• DEMAND LIMIT
• EXTERNALLY POWERED DEMAND LIMIT
• DEMAND LIMIT (CCN Loadshed Controlled)
TROUBLESHOOTING ......................43-52
Checking Display Codes ....................43
Unit Shutoff ................................43
Complete Unit Stoppage .....................43
Single Circuit Stoppage .....................43
Restart Procedure ...........................43
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts ...........................43
Compressor Alarm/Alert Circuit ..............43
EXD Troubleshooting Procedure .............50
• INSPECTING/OPENING ELECTRONIC EXPANSION VALVES
• INSPECTING/OPENING ECONOMIZERS
SERVICE ..................................52-66
Servicing Coolers and Condensers ..........52
• TUBE PLUGGING
• RETUBING
• TIGHTENING COOLER/CONDENSER HEAD BOLTS
Inspecting/Cleaning Heat Exchangers ........53
• COOLERS
• CONDENSERS (30HX Only)
Water Treatment ............................53
Condenser Coils (30GX Only) ................53
• COIL CLEANING
Condenser Fans (30GX Only) ................54
Refrigerant Charging/Adding Charge .........54
Oil Charging/Low Oil Recharging ............55
Oil Filter Maintenance .......................56
• REPLACING THE EXTERNAL OIL FILTER
• REPLACING THE INTERNAL OIL FILTER
Compressor Changeout Sequence ...........56
• BURNOUT CLEAN-UP PROCEDURE
Moisture-Liquid Indicator ....................58
Filter Drier ..................................58
Liquid Line Service Valve ....................58
Thermistors ................................58
• LOCATION
• THERMISTOR REPLACEMENT
Pressure Transducers .......................59
• PRESSURE TRANSDUCER CALIBRATION
• TROUBLESHOOTING
Safety Devices ..............................62
• COMPRESSOR PROTECTION
• OIL SEPARATOR HEATERS (30GX)
• COOLER PROTECTION
Relief Devices ..............................62
• PRESSURE RELIEF VALVES
Control Modules ............................64
• PROCESSOR MODULE (PSIO-1), HIGH VOLTAGE RELAY MODULE (DSIO-HV), AND EXV DRIVER MODULE (DSIO-EXV), 12/6 MODULE (PSIO-2)
• RED LED
• GREEN LED
Carrier Comfort Network (CCN) Interface .....64
• PROCESSOR MODULE (PSIO-1)
• HIGH VOLTAGE RELAY MODULE (DSIO-HV)
Replacing Defective Processor Module .......66
Winter Shutdown Preparation ................66
PRE-START-UP PROCEDURE ................67
START-UP AND OPERATION .................67
FIELD WIRING ............................68-73
APPENDIX A
(Compressor Must Trip Amps) ...........74-76
APPENDIX B
(Capacity Loading Sequence) ............77-79
APPENDIX C (Available Accessories) .........80
APPENDIX D (CPM Configurations) .........81-85
APPENDIX E (Cooler and
Condenser Pressure Drop) ...............86-88
APPENDIX F
(Typical System Components) ............89,90
INDEX ......................................91
START-UP CHECKLIST ..............CL-1 to CL-8
GENERAL
IMPORTANT: The 30GX/HX units use refrigerant R-134a. Compressor oil used with R-134a is Polyo­lester oil.
This publication contains Start-Up, Service, Controls, Operation and Troubleshooting data for the 30GX080-265 and 30HXA,C076-271 screw chillers.
Circuits are identified as circuits A and B, and compres­sors are identified as A1 or A2 in circuit A, and B1 in circuit B.
The 30GX/HX Series chillers feature microprocessor­based electronic controls and electronic expansion devices (EXD) in each refrigeration circuit.
The control system cycles compressor loaders and/or com­pressors to maintain the selected leaving fluid temperature set point. The system automatically positions the EXD to maintain the specified refrigerant level in the cooler.Thesys­tem also has capabilities to control a condenser water valve to maintain suitable leaving-water temperature for the30HXC unit. Safeties are continuously monitored to prevent the unit from operating under unsafe conditions. A scheduling func­tion can be programmed by the user to control the unit’s oc­cupied and unoccupied schedules. The control also operates a test function and a manual control function that allows the operator to check output signals and ensure components are operable.
The control system consists of a processor module (PSIO-1), an EXD driver module (DSIO-EXV), a high volt­age relay module on 30GX units (DSIO-HV), 2 six-pack re­lay boards, a keypad and display module (also called HSIO­II), 2 electronic expansion devices (EXDs), 1 compressor protection module (CPM) per compressor, a PSIO-2 mod­ule, 6 thermistors, and 8 transducers. Aremoteenhanceddis­play is available as an accessory.
2
Page 3
MAJOR SYSTEM COMPONENTS
Processor Module (PSIO-1) —
This module is an upgrade to the original PSIO (8088) module, with superior electrical noise immunity capability. It contains the operat­ing software and controls the operation of the machine. It has 12 input channels and 6 output channels.
The PSIO-1 continuously monitors input/output channel information received from all the modules and controls all output signals for all output channels. It also controls the relays on the six-pack relay board. The processor module also controls the EXD driver module (as required), com­manding it to open or close each EXD in order to maintain the proper cooler level. Information is transmitted between the processor module, CPM modules, the EXD driver mod­ule, and the HSIO-II standarddisplaymodulethrougha3-wire communications bus called COMM3. The remote enhanced display (accessory) is connectedtothePSIO-1modulethrough a 3-wire communications bus, but uses a different commu­nication bus called COMM1. The COMM1 bus is also used to communicate to other CCN (Carrier Comfort Network) devices when the unit is installed in a network application.
DSIO-HV Relay Module — The DSIO-HV module has
4 inputs and 8 outputs and is installed on 30GX units only. The module communicates the status of the inputs with the PSIO-1 module and operates the oil heater, outdoor fan, and minimum load control outputs.
Electronic Expansion Device Module — The elec-
tronic expansion device module has 4 inputs and 2 outputs. It receives signals from the PSIO-1 module and operates the electronic expansion devices. The electronic expansion de­vice module also sends the PSIO-1 module the status of its 4 input channels.
CompressorProtectionModule(CPM)— The com-
pressor protection module monitors several of the compres­sor safeties and controls 4 of the outputs used to control each compressor. The CPM monitors compressor current, com­pressor voltage, high pressure switch status, and compressor motor temperature. The CPM controls the compressor con­tactors, oil solenoid, and motor cooling solenoid. Each CPM sends the PSIO-1 its circuit’s motor temperature, alarm sta­tus of the module, and the compressor relay status.
PSIO-2 (8052) Module — This module is used as an
input/output module only,as there is no unit software loaded in the module. This module has 12 input channels and 6 out­put channels.
Keypad and Display Module (Also Called HSIO-II) —
This device consists of a keypad with 8 func­tion keys, 4 operative keys, 12 numeric keys, and a 2-line 24-character alphanumeric LCD (liquid crystal display). Key usage is explained in the Accessing Functions and Subfunc­tions section on page 13.
Control (LOR) Switch — Control of the chiller is de-
fined by the position of the LOCAL/OFF/REMOTE (LOR) switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own controls (LO­CAL), manually stopped (OFF), or controlled through a set of remote contacts (REMOTE). This switch is different than the switch that is used in the Flotronic™ II controls con­figuration. The CCN control is enabled through the HSIO-II. The switch allows unit operation as shown in Table 1.
In the LOCAL position, the chiller is allowed to operate and respond to the scheduling configuration, CCN configu­ration, and set point data. In the remote position, the unit operates similarly to the LOCAL position, except the remote contacts must be closed for the unit to operate.
Table 1 — Unit Mode from LOR Switch
and CCN State
SWITCH
POSITION
REMOTE
CONTACTS
CCN
CONFIGURATION
CCN
STATE
UNIT
MODE
OFF NR NR NR LOCAL OFF
LOCAL NR
DISABLE NR LOCAL ON
ENABLE
RUN CCN ON
STOP CCN OFF
REMOTE
OPEN NR NR LOCAL OFF
CLOSED
DISABLE NR LOCAL ON
ENABLE
RUN CCN ON
STOP CCN OFF
LEGEND
CCN — Carrier Comfort Network NR — Input Not Read by Processor
NOTE: Iftheunit is configured for aclock,then the unit isunderclock control if it is in an ON mode.
OPERATION DATA
Electronic Expansion Device (EXD) —
The micro­processor controls the EXD through the EXD driver mod­ule. The EXD will either be an EXV (electronic expansion valve) or an economizer. Inside both these devices is a linear actuator stepper motor.
EXV OPERATION — High-pressure liquid refrigerant en­ters the valve through the bottom. Aseriesof calibrated slots are located inside the orifice assembly. As refrigerant passes through the orifice, the pressure drops and the refrigerant changes to a 2-phase condition (liquid and vapor). To con­trol refrigerant flow for different operating conditions, the sleeve moves up and down over the orifice, thereby chang­ing orifice size. The sleeve is moved by a linear stepper mo­tor.The stepper motor moves in increments and is controlled directly by the processor module. As the stepper motor ro­tates, motion is transferred into linear movement by the lead screw. Through the stepper motor and lead screw, 1500 dis­crete steps of motion are obtained. The large number of steps and long stroke result in very accurate control of refrigerant flow.
Each circuit has a liquid level sensor mounted vertically in the top of the cooler shell. The level sensor consists of a small electric resistance heater and 3 thermistors wired in series, positioned at different heights inside the body of the well. The heater is designed so that the thermistors read ap­proximately 200 F (93.3 C) in dry air.Astherefrigerantlevel rises (falls) in the cooler, the resistance of the closest ther­mistor(s) will increase (decrease) as it is cooled by the rising liquid refrigerant (heated by the heater). This large resis­tance difference allows the control to accurately maintain a specified level.
The level sensor monitors the refrigerant liquid level in the cooler and sends this information to the PSIO-1. At ini­tial start-up, the EXV position is at zero.After that, the micro­processor keeps accurate track of the valve position in order to use this information as input for the other control func­tions. The processor does this by initializing the EXVs at start-up. The processor sends out enough closing pulses to the valve to move it from fully open to fully closed, then resets the position counter to zero. From this point on, until the next initialization, the processor counts the total number of open and closed steps it has sent to each valve.
3
Page 4
ECONOMIZER OPERATION — Economizers are factory installed on 30GX105-265 units and 30HXA,C161-271 units. All other sizes use standard EXVs. The economizer im­proves both the chiller capacity and efficiency as well as pro­viding compressor motor cooling. Inside the economizer are both a linear stepper motor (same as standard EXV motor) and a float valve. The stepper motor is controlled by the pro­cessor to maintain the desired liquid level in the cooler (as is done for chillers without economizers). The float valve maintains a liquid level in the bottom of the economizer.
Liquid refrigerant is supplied from the condenser through the end to the bottom of the economizer.Abubbler tube sup­plies a small amount of discharge gas to ensure that the float will be able to workproperly. As the refrigerantpassesthrough the EXD, its pressure is reduced to an intermediate level of about 75 psig (517 kPag). This pressure is maintained inside the economizer shell. Next, the refrigerant flows through the float valve where its pressure is further reduced to slightly above the pressure in the cooler.
The increase in performance is achieved when some of the refrigerant passing through the EXD flashes to vapor, further subcooling the liquid that is maintained at the bottom of the economizer. This increase in subcooling provides ad­ditional capacity. Also, since the additional power required to accomplish this is minimal, the efficiency of the machine improves. The vapor that flashes rises to the top of the econo­mizer where it passes to the compressor and is used to pro­vide motor cooling. After passing over the motor windings, the refrigerant reenters the cycle at an intermediate port in the compression cycle.
Oil Pumps — The 30GX/HX screw chillers use one ex-
ternally mounted prelubricating oil pump per circuit. This pump is operated as part of the start-up sequence. On 30GX units, the pumps are mounted to the base rails on the oil sepa­rator side of the unit. The pumps are mounted to a bracket on the condensers of 30HXC units and to the oil separator on 30HXA units.
When a circuit is required to start, the controls energize the oil pump first and read the oil pressure transducer read­ing. The pump is operated for a period of 20 seconds, after which the oil solenoid is energized to open the oil inlet valve at the compressor. The control again reads the pressure from the oil pressure transducer. If the pump has built up suffi­cient oil pressure, the compressor is allowed to start.
Once the compressor has started, the oil pump is turned off within 10 seconds and is not used again until the next start-up. If the pump is not able to build up enough oil pres­sure, the pump is turned off. Within 3 seconds, the pump is re-energized and makes one additional attempt to build oil pressure. The control generates an alarm if the second at­tempt fails.
Motor Cooling — Compressor motor winding tempera-
tures are controlled to a set point of 200 F (93.3 C). The control accomplishes this by cycling the motor cooling olenoid valve to allow liquid refrigerant to flow across the motor windings as needed. On units equipped with econo­mizers, flash gas leaves the top of the economizer and con­tinually flows to the motor windings. All refrigerant used for motor cooling re-enters the rotors through a port located mid­way along the compression cycle and is compressed to dis­charge pressure.
Back Pressure Valve (30GX and 30HXA only) —
This valve is located on the oil separator outlet on 30GX units and mounted on the oil separator shell of 30HXAunits. The valve’s function is to ensure that there is sufficient sys­tem differential pressure to allow for oil to be driven back to the compressor. A small copper line (economizer pressure) is connected to the top of the valve, which contains an in­ternal spring that closes a piston if the pressure in the oil separator is not at least 15 psig greater than the economizer pressure.
Sensors — The 30GX,HX control system (based on the
Flotronic™ II chiller control system)gathersinformationfrom sensors to control the operation of the chiller. The units use up to 9 standard pressure transducers, 7 standard thermistors (including 3 motor temperature thermistors), and 2liquidlevel thermistors to monitor and control system operation. The sen­sors are listed in Table 2.
Compressor Protection Module (CPM) — Each
compressor has its own CPM. The CPM provides the fol­lowing functions:
• compressor main contactor control
• Wye-Delta contactor transition
• compressor ground current protection
• motor temperature reading
• high-pressure protection
• reverse rotation protection
• voltage imbalance protection
• current imbalance protection
• compressor oil solenoid control
• motor cooling solenoid control
• sensor bus communications
• starting and running overcurrent protection
The CPM has the following 4 output relays and 4 inputs:
OUTPUTS:
• compressor contactor
• compressor oil solenoid
• compressor motor cooling solenoid
• Wye-Delta transition relay INPUTS:
• motor temperature
• three-phase voltage
• three-phase current
• high-pressure switch
Adiagram of the CPM board is shown in Fig. 1. There are line voltage inputs at L1, L2, and L3. Below these inputs are the current toroid inputs at Plug 1. Below Plug 1 are the 3 COMM3 communication terminals. In the lower left corner of the board are the inputs for motor winding temperature. The address DIP (dual-in-line package) switch and com­pressor must-trip amps header are factory set. For compres­sor A1, switches 2 and 4 should be set. For compressor A2 (30HXA,C206-271AND 30GX205-265), switches 2, 3, and 4 should be set. For compressor B1, switches 1 and 4 should be set.
T overifypropermusttripampsheaderconfiguration,press
and use the up arrow key on the HSIO to locate the
must trip amp values. Press the reset button on the HSIO/ fuse panel to update these values. See Appendix A. If the values do not match those in Appendix A, verify with Ap­pendix D that the configuration headers have been properly punched out.
4
Page 5
Table 2 — Thermistor and Transducer Locations
THERMISTORS
Sensor Description Location Connection Terminals
T1 Cooler Leaving Fluid Temp Cooler Head Leaving Fluid Side PSIO-2, J7 pins 2,3 T2 Cooler Entering Fluid Temp Cooler Head Entering Fluid Side PSIO-2, J7 pins 5,6 Motor Temp A1 Motor Temperature A1 Compressor A1 Junction Box CPM-A1, T terminals Motor Temp A2* Motor Temperature A2 Compressor A2 Junction Box CPM-A2, T terminals Motor Temp B1 Motor Temperature B1 Compressor B1 Junction Box CPM-B1, T terminals T5 Discharge Gas TempA Top of Condenser Circuit A (30HXC Only) PSIO-2, J7 pins 8,9
Top of Oil Separator Circuit A (All Other Units)
T6 Discharge Gas Temp B Top of Condenser Circuit B (30HXC Only) PSIO-2, J7 pins 11,12
Top of Oil Separator Circuit B (All Other Units)
LL-A (T3) Liquid Level Circuit A Top of Cooler Circuit A PSIO-1, J7 pins 5,6 LL-B (T4) Liquid Level Circuit B Top of Cooler Circuit B PSIO-1, J7 pins 8,9 T7 (optional)† Outdoor Air Thermistor Outside Air Stream PSIO-2, J7 pins 20,21 STP (optional)† Space Temperature Conditioned Space PSIO-2, J7 pins 23,24 T8 (optional)† Condenser Entering Water Temp Condenser Entering Fluid Line PSIO-2, J7 pins 14,15 T9 (optional)† Condenser Leaving Water Temp Condenser Leaving Fluid Line PSIO-2, J7 pins 17,18
PRESSURE TRANSDUCERS
Sensor Description Location Connection Terminals DPT-A Discharge Pressure Circuit A Top of Condenser Circuit A (30HXC Only) PSIO-1, J7 pin 22
Top of Oil Separator Circuit A (All Other Units)
SPT-A Suction Pressure Circuit A Top of Cooler Circuit A PSIO-1, J7 pin 19 EPT-A Economizer Pressure Circuit A Economizer Line Entering Comp A PSIO-1, J7 pin 10 OPT-A1 Oil Pressure Compressor A1 Compressor A1 Oil Connection PSIO-1, J7 pin 25 OPT-A2* Oil Pressure Compressor A2 Compressor A2 Oil Connection PSIO-1, J7 Pin 1
DPT-B Discharge Pressure Circuit B Top of Condenser Circuit B (30HXC Only) PSIO-1, J7 pin 16
Top of Oil Separator Circuit B (All Other Units)
SPT-B Suction Pressure Circuit B Top of Cooler Circuit B PSIO-1, J7 pin 31 EPT-B Economizer Pressure Circuit B Economizer Line Entering Comp B PSIO-1, J7 pin 13 OPT-B Oil Pressure Compressor B Compressor B1 Oil Connection PSIO-1, J7 pin 28
*30HX206-271 only.
†Sensors are available as accessories for field installation.
The CPM communicates on the COMM3 communication bus to the PSIO-1 module. Proper operation of theCPMboard can be verified by observing the 3 LEDs (light-emitting di­odes) located on the board. The top LED is red and blinks at a rate of once every 1 to 2 seconds. This indicates that the module is powered and operating correctly.ThemiddleLED is yellow and blinks when there is an automatic reset alarm condition. The yellow LED remains on and does not blink for manual reset alarm conditions. The bottom LED is green and blinks when the module is satisfactorily communicating with the PSIO-1 module. The CPM communicates the status of its inputs and outputs, and reports 18 different alarm con­ditions to the PSIO-1. The alarms are listed in Table 3.
The CPM module has many features that are specifi­cally designed to protect the compressor, including re­verse rotation protection. Do not attempt to bypass or alter any of the factory wiring. Any compressor opera­tion in the reverse direction will result in a compressor failure that will require compressor replacement.
The PSIO-1 will generate an alert when it receives an alarm input from the CPM. The alert will be generated in a y.xx format, where ‘‘y’’ refers to the compressor and ‘‘xx’’ to the alarm value in Table 3 (decimal point removed). For ex­ample, the HSIO might displayAlarm 1.70 for a voltage phase reversal occurring on compressor A1. Similarly, the display would read 5.85 for a motor overtemperature condition on compressor B1.AlertsforcompressorsA2 and B2 (if present) would be generated as ‘‘2.xx’’and ‘‘6.xx,’’respectively. Alarm codes 3 and 4 would not be used. Ending zeros are not displayed.
The high-pressure switch is wired in series with the relay coils of the 4 relays on the CPM. If this switch opens during
operation, all relays on the CPM are deenergized and the compressor is stopped. The failure is reported to the PSIO-1 and the processor module locks off the compressor from re­starting until the alarm is manually reset.
Table 3 — Compressor Protection Module
Feedback Codes
ALARM CONDITION VALUE
High Pressure Switch Trip 1.0 No Motor Current 2.0 Current Imbalance Alarm 10% 2.5 Current Imbalance Warning 10% 2.7 Current Imbalance 18% 3.0 Single Phase Current Loss 3.5 High Motor Current 4.0 Ground Fault 5.0 Voltage Imbalance Alarm 3% 5.5 Voltage Imbalance Warning 3% 5.7 Voltage Imbalance 7% 6.0 Voltage Phase Reversal 7.0 Contactor Failure 7.5 Current Phase Reversal 8.0 Motor Overtemperature 8.5 Open Thermistor 9.0 Configuration Header Fault 9.5 Shorted Thermistor 10.0 No Error 0
Wye-Delta vs Across-the-line (XL) Starting Option —
All 30GX,HX chillers operating at voltages of 208/230-3-60 or 230-3-50 (5 or 8 at Position 12 in model number) are supplied with factory installed Wye-Deltastart­ers. All other voltage options can be ordered with either Wye-Delta or XL starting options. The XL starting method is the most cost effective and simply starts the compressor motor in a Delta configuration (the motors are designed for continuous operation in this configuration) using a single con­tactor. See Fig. 2. This is the simplest starting method to use and is ideal where starting current does not require limiting.
5
Page 6
Where current limitations exist, the Wye-Deltaoptionmay be used. See Fig. 3. This option uses a factory-installed starter assembly for each compressor, which consists of 3 contac­tors labelled 1M, 2M, and S. As the compressor is started, the CPM module energizes contactors 1M and S, which con­nects and energizes the motor windings in a Wye configu­ration. The starting current required will be approximately 60% less than that required for an XL start due to the higher impedance of the motor windings when Wye connected. The compressor will attain about 100% of its normal operating speed (approximately 3 to 6 seconds) before the CPM mod­ule deenergizes the S contactor and energizes the 2M con­tactor, switching the compressor windings to a Delta wiring configuration. The S and 2M contactors in the starter assem­bly are both mechanically and electrically interlocked so that they will not both be energized at the same time.
Do not alter the factory-installed power wiring from the control box terminal block to the compressor junction block.
Doing so will cause permanent damage to the compressor and will require that the compressor be replaced.
Capacity Control — The control system cycles com-
pressors, loaders, and minimum load control valves to main­tain the user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the microproces­sor to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automatically reset by the return temperature reset or space and outdoor-air temperature reset features. It can also be re­set from an external 4 to 20 mA signal (requires field­supplied 500-ohm,1⁄2watt resistor), or from a network signal.
The capacity routine runs every 30 seconds. The routine attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio (Load/Unload Fac-
tor under ) is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from − 100 to + 100%. If the next stage of capacity is a compressor, the
control starts (stops) a compressor when the ratio reaches + 100% (− 100%). If the next stage of capacity is a loader, the control energizes (deenergizes) a loader when the ratio reaches + 60% (− 60%). Loaders are allowed to cycle faster than compressors, to minimize the number of starts and stops on each compressor.Adelay of 90 seconds occurs after each capacity step change.
MINUTES LEFT FOR START — This value is displayed in the Status subfunction and represents the amount of time to elapse before the unit is started. This value can be zero with­out the machine running in many situations. This can in­clude being unoccupied, LOR switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME ( ) — This user config­urable time period is used by the control to determine how
long unit operation is delayed after power is applied/ restored to the unit. It is also used to delay compressor re­starts after the unit has shut off its lowest stage of capacity. Typically, this time period is configured when multiple ma­chines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running.
LOADING SEQUENCE — The 30GX,HX chiller effi­ciency is greatest at full load. Therefore, the following se­quence list applies to capacity control.
1. Thenextcompressor is not started until all others are run­ning at 100%.
2. The second unloading stage is only used during initial capacity staging of the unit at start-up.
3. Whenever a compressor is started in a circuit, the loaders in the circuit are deenergized for 15 seconds before the compressor is started. The loaders are energized 90 sec­onds after the compressor is started.
L1 L2
L3
CURRENT TOROID INPUT PLUG
1
2 3
T T
TEMPERATURE
ADDRESS DIP SWITCH
COMM3
24/115/230 VAC
INPUTS/OUTPUTS
COMPRESSOR PROTECTION MODULE (CPM)
COMPRESSOR MUST TRIP AMPS HEADER
1 2
RED LED
YELLOW LED
GREEN LED
MOTOR INPUT
PUSH THIS SIDE OF SWITCH DOWN TO SET ADDRESS
1234
ROCKER DOWN
1
0
2
3
4
5
Fig. 1 — Compressor Protection Module
LED — Light-Emitting Diode
NOTES:
1. The red LED blinks continuously when the module is operating properly.
2. The yellowLEDblinks during automaticreset alarm, and is continuously lit when the manual reset alarm is active.
3. The green LID blinks continuously when communi­cating properly with PSIO-1.
6
Page 7
CLOSE CONTROL( ) — When configured for Close Control, the control is allowed to use any loading/capacity
control devices required to maintain better leaving fluid tem­perature regulation.Allstagesofunloadingareavailable.See Appendix B for an example.
LEAD/LAG DETERMINATION ( ) — This is a con­figurable choice and is factory set to be automatic. The value
can be changed to Circuit A or Circuit B leading, as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter (Version 3.0 and later) of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are made when shut­ting off compressors.
On 30HX206-271 and 30GX205-265 units set for staged loading, the control fully loads the lead circuit before start­ing the lag circuit and unloads the lag circuit first. When these units are set for equal loading, the control maintains nearly equal capacities in each circuit when the chiller is loading and unloading.
CAPACITY SEQUENCE DETERMINATION ( ) — This is configurable as equal circuit loading or staged circuit
loading with the default set at staged. The control deter­mines the order in which the steps of capacity for each cir­cuit are changed. This control choice does NOT have any impact on machines with only 2 compressors.
MINIMUM LOAD VALVE ( ) — When this option is installed and configured, the first stage of capacity is ini­tiated by energizing the Minimum Load valve relay.The con­trol energizes loaders as needed thereafter. Similarly, the Minimum Load valve relay will be energized forthelaststage of capacity to be used before the circuit is shut down.
CAPACITY CONTROLOVERRIDES—The following over­rides will modify the normal operation of the routine.
Deadband Multiplier — The user configurableDeadbandMul­tiplier ( ) has a default value of 1.0. The range is from
1.0 to 4.0. When set to other than 1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay between adding or re­moving stages of capacity. Figure 4 shows how compressor starts can be reduced over time if the leaving water tempera­ture is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override — If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on add­ing the first stage to reduce cycling. This factor is also ap­plied when the control is attempting to remove the last stage of capacity.
L1
L2
L3
T1
T1
T3
3
2
1
1
2
3
4
6
5
COMPRESSOR JUNCTION BOX
JUMPER BARS
COMPRESSOR CONTACTOR
1
2
3
21
22
23
TERMINAL BLOCK
Fig. 2 — Across-the-Line (XL) Compressor Wiring
1
2
3
4
5
6
1
2
3
T1
T1
T1
T2
T2
T2
T3
T3
T3
S
2M
1M
L3
L3
L3
L2
L2
L2
L1
L1
L1
1
2
3
22
21
23
TERMINAL BLOCK
COMPRESSOR STARTER ASSEMBLY
COMPRESSOR JUNCTION BOX
21
22
23
4
6
5
Fig.3—Wye-Delta Compressor Wiring
7
Page 8
Slow Change Override —The control prevents the capacity stages from being changed when the leaving fluid tempera­ture is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading ( ) —Limitstherate of change of leav­ing fluid temperature. If the unit is in a cooling mode and
configured for Ramp Loading, the control makes 2 compari­sons before deciding to change stages of capacity. The con­trol calculates a temperature difference between the control point and leaving fluid temperature. If the differenceisgreater than 4° F (2.2° C) and the rate of change (°F or °Cperminute) is less than the configured Cooling Ramp Loading value
( ), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading — When the entering fluid temperature is below the control point, the con­trol will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control re­moves an amount greater than 25%, but no more than nec­essary. The lowest stage will not be removed.
Low Discharge Superheat — If a circuit’s discharge super­heat is less than 15° F (8.3° C), the control does not increase the current capacity stage and the EXD is not opened any further. If the discharge superheat is less than 10° F (5.6° C) and decreasing, the EXD is closed 50 steps every 10 seconds. If the discharge superheat is less than 5° F (2.8° C) and decreasing, the circuit is unloaded every 30 seconds until the superheat is greater than 5° F (2.8° C). The final capacity stage is not unloaded unless an alarm condition exists. This override is ignored for the first 3 minutes after a compressor is started.
Low Saturated Suction Temperature — To avoid freezing the cooler,thecontrol will compare the circuit Saturated Suc­tion temperature with a predetermined freeze point. For wa­ter circuits, the freeze point is 28 F (−2.2 C). For brine cir­cuits, the freeze point is 8° F (4.4° C) below the cooling set point (lower of 2 cooling set points for dual configuration). If the saturated suction temperature is below the freeze point, the unit capacity is not allowed to increase. For brine cir-
cuits, the freeze point can be entered by pressing and scrolling 12 items down. The control will use the Brine
Freeze Point value less 6°F (3.3°C) as the freeze point to compare with the Saturated Suction temperature. The de­fault for the Brine Freeze Point is 34 F (1.1 C) which means the control will use 28 F (−2.2 C) as the freeze point. This value is adjustable from −15 F to 34 F (−26.1 to 1.1 C). For
water (brine) circuits, if the Saturated Suction temperature falls below 34 F (1.1 C) (the Brine Freeze Point), the unit capacity will not increase. If the Saturated Suction tempera­ture falls below 28 F (−2.2 C), the Brine Freeze Point minus 6° F (3.3° C), for 90 seconds, all loaders in the circuit are turned off. If this condition continues for a total of 3 min­utes, the circuit will shut down.
High Condensing Temperature Unloading — Every 10 sec­onds the control checks for the conditions below. Loaders will be cycled as needed to control the saturated condensing temperature below the configured maximum condensing tem­perature. Configured maximums are 154 F (67.8 C) for30GX, 152 F (66.7 C) for 30HXA, and 122 F (50 C) for 30HXC units. If a circuit’s saturated condensing temperature is more than 12° F (6.7 C) below the maximum condensing tem­perature, the circuit capacity is not allowed to increase. If the saturated condensing temperature is more than 2° F (1.1° C) above the maximum condensing temperature for 60 seconds, a loader is turned off. If the saturated condensing temperature rises to more than 5° F (2.8° C) above the maxi­mum condensing temperature during the 60 seconds, a loader is turned off immediately. If all the loaders were already off, the compressor is shut down and an alarm is generated.
MOP(Maximum Operating Pressure) Override —Thecon­trol monitors saturated condensing and suction temperature for each circuit as well as differential oil pressure. Based on a configurable maximum operating set point (saturated suction temperature), set maximum condensing tempera­ture, and minimum differential oil pressure, the control may reduce the number of capacity stages being used and/or may lower the EXD position when system pressures approach the set parameters.
Head Pressure Control
GENERAL — The microprocessor controls the condenser fans (30GX) or analog water valve (30HXC) to maintain the saturated condensing temperature to a configurable set point. The fans are staged or speed varied (30GX) or water valve controlled (30HX) based on each circuit’s saturated con­densing temperature and compressorstatus.Water cooled units (30HXC) operating at less than 70 F (21.1 C) for entering condenser water require the use of head pressure control.
The chiller must be field configured for the options shown
in Table 4. Fan stage settings are shown in Table 5. AIR COOLED UNITS (30GX) — See Fig. 5 for condenser
fan locations.
47 46 45 44
43 42 41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED DEADBAND
STANDARD DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water
Temperature
Fig. 4 — Deadband Multiplier
8
Page 9
No Motormastert Control — The fans are controlled based on Saturated Condensing Temperature. The first fan stage for each circuit is turnedonwheneverthecompressoristurned on.Afan stage is added when the Saturated Condensing Tem­perature (SCT) exceeds the Head Pressure Set Point. The Head Pressure Set Point is configurable in the Set Point sub­function. The default is 113 F (45 C). Once a fan stage has been added, the software temporarily modifies the head pres­sure set point by adding 15° F (8.3° C) for 35 seconds. A fan stage will be removed when the Saturated Condensing Temperature has been less than the Head Pressure Set Point minus 35 F (19.4 C) for 2 minutes.Thecontrolusesthehigher of the 2 Saturated Condensing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-265 units, each circuit’s fan stages are independently controlled based on the circuit Saturated Condensing Temperature. Refer to Table 6 for condenser fan control information. See Fig. 6A.
With Motormaster Control — For low-ambient operation, the lead fan in each circuit can be equipped with the optional or accessory Motormaster III head pressure controller. This controller can be used in one of 2 ways. If factory installed, the controller will be configured for 4 to 20 mA control. With the Motormaster III option enabled, the PSIO-1 module cal­culates the required output based on Saturated Condensing temperature, Head Pressure set point, and a PID (propor­tional integral derivative) loop calculation. This 4 to
20 mA output is driven through the PSIO-2 module. To ob­tain this accessory for field installation, order by part num­ber 30GX-900---012forasinglecontroller package (30GX080­150 and 160). Order part number 30GX-900---014 for a dual controller package (30GX151 and 161-265). These packages contain all the hardware required to install the accessory. See Fig. 6B.
The control will use the higher of the 2 Saturated Con­densing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-265 units, each circuit’s fan stages are independently controlled based on the circuit Saturated Condensing Temperature. Refer to Table6 for condenser fan staging information.
WATER-COOLED UNITS (30HX) — The 30HX chillers can be configured to control direct or reverse-acting water valves that are controlled bya4to20mAsignal. A 2 to 10 VDC signal can be used by installing a 500-ohm resistor across the 2 output terminals of the 4 to 20 mA signal. This control scheme reads the saturated condensing temperature and uses a PID (proportional integral deriative) loop to control the head pressure. Proportional, Integral and Deriva­tive gain parameters for both the water and air cooled con­trols are adjustable and can be found in the Service subfunc­tion. Checkout and adjustment of the PID loop should only be performed by certified Carrier Comfort Network technicians.
Table 4 — Field Configured Chiller Options
CONFIGURATION OPTION DESCRIPTION HSIO LOCATION FACTORY CONFIGURED?
Fan Staging Select Air cooled staging method
Yes. See Table 5
Motormaster Control Select Applies to air cooled units only
Yes. 0 = None
Set to 1 to enable (Motormaster only)
Water Valve Type Applies to water cooled unit only
Yes. 0 = None
Setto1=4−20mA,2=0−10V,
3=20−4mA,4=10−0V
Table 5 — Fan Staging Settings for Air Cooled (30GX) Units
UNIT 30GX DESCRIPTION OPTION NUMBER
080-105
1st stage compressor status 2nd stage common control based on highest SCT
12
106-125
1st stage compressor status 2nd and 3rd stage common control based on highest SCT
14
136, 150, 160
1st stage compressor status 2nd through 4th stage common control based on highest SCT
16
151, 161, 175,
205, 225
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd and 3rd stage Circuit A independent
7
176
1st stage each circuit, compressor status 2nd and 3rd stage each circuit independent
3
206, 226, 250
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd, 3rd and 4th stage Circuit A independent
9
251, 265
1st stage each circuit, compressor status 2nd, 3rd and 4th stage each circuit independent
5
LEGEND
SCT — Saturated Condensing Temperature
9
Page 10
ADJUSTING PID ROUTINES — The 30GX and 30HXC head pressure control routines use PID (proportional inte­gral derivative) loops to maintain a user-configurable head pressure set point. Gain default values are located in the Serv­ice function. See page 30. The current values can be read
under from the HSIO. The control calculates a new fan speed (30GX) or water valve position (30HXC) every
5 seconds based on these gain values and an error term equal to saturated condensing temperature minus head pressure set point. If the control routine is not responding fast enough to large changes (circuit starting, for example), increase the pro­portional term.
When the routine is making too great a change to valve position or fan speed, decrease the proportional term.To mini­mize hunting, keep the integral term positive and as low as possible. The default for the derivative term is zero. This valve is used to control ‘‘droop,’’which is common in master/ submaster control schemes. The value should not need to be changed.
Cooler and Condenser (30HXC) Pump Control —
The 30GX and 30HX chillers can be configured forcooler and condenser (30HXC) pump control. Inputs for a cooler flow switch or interlock and condenser flow switch are also provided.
COOLER PUMP CONTROL ( ) — The factory de­fault setting for cooler pump control is ‘‘Not Controlled.’’
All chillers are enabled at the factory for cooler pump in­terlock. See page 71 of Field Wiring section for wiring of cooler flow switch and/or cooler pump interlock contacts. Whether cooler pump control is enabled or not, the control generates an alarm if this input does not close within one minute after the unit switches to an occupied mode or the cooler pump is turned on. See Alarms and Alerts section, page 43 for a description of Alarms 53-55. If cooler pump control is enabled, the control waits one minute and checks the interlock or switch input before starting to determine if cooling is needed. The cooler pump is turned on when the chiller is in the occupied mode and turned offotherwise.The cooler pump is turned on in either of two override condi­tions: If the cooler freeze protection alarm has been gener­ated, the cooler pump is turned on if not already running. If a cooler heater is being used and has been on for more than 15 minutes during saturated suction freeze protection, the cooler pump is turned on.
1
2
3
4
CONTROL BOX END
5
6
7
8
9
10
CONTROL BOX END
4
2
1
3
CONTROL BOX END
13 5 7
24 6 8
CONTROL BOX END
4
6
1
3
5
2
5
CONTROL BOX END
7911
12
6810
4
2
3
1
CONTROL BOX END
1
3
5
7
2
4
6
8
CONTROL BOX END
14
12
10
13
11
9
1
3
5
7
2
4
6
8
9
11
12
10
Fig. 5 — 30GX Condenser Fan Locations
30GX080-105 30GX106-125
30GX151, 161, 175, 205, 225 30GX176
30GX206, 226, 250
30GX136, 150, 160
30GX251, 265
10
Page 11
Table 6 — 30GX080-265 Condenser Fan Staging (PSIO-1 Controlled)
30GX UNIT SIZE FAN TYPE FAN CONTACTOR FANS CONTROLLED FAN RELAY NO.*
080-105
Standard
FC-1 1, 2 5 FC-2 3, 4 1
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1
106-125
Standard
FC-1 1, 2 5 FC-2 3, 4 1 FC-3 5, 6 2
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2
136, 150,
160
Standard
FC-1 1, 2 5 FC-2 3, 4 1 FC-3 5, 6 2 FC-4 7, 8 2
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 2
151, 161, 175
205, 225
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 2 FC-4 7, 8 Comp. A1/A2 contactor† FC-5 9, 10 1
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 1
176
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 4 FC-4 7, 8 Comp. A1 contactor† FC-5 9, 10 1 FC-6 11, 12 2
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 4 FC-4, 4A 7, 8 Comp. A1 contactor† FC-5, 5A 9, 10 1 FC-6, 6A 11, 12 2
206, 226, 250
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 1 FC-4 7, 8 Comp. A1/A2 contactor† FC-5 9, 10 2 FC-6 11, 12 2
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 1 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 2 FC-6, 6A 11, 12 2
251, 265
Standard
FC-1 2, 4 1 FC-2 6, 8 2 FC-3 1 Comp B1 contactor† FC-4 3 3 FC-5 5, 7 4 FC-6 9, 10 Comp. A1/A2 contactor† FC-7 11, 12 2 FC-8 13, 14 2
High Static
FC-1, 1A 2, 4 1 FC-2, 2A 6, 8 2
FC-3 1 Comp. B1 contactor†
FC-4 3 3 FC-5, 5A 5, 7 4 FC-6, 6A 9, 10 Comp. A1/A2 contactor† FC-7, 7A 11, 12 2 FC-8, 8A 13, 14 2
LEGEND
Comp. — Compressor FC — Fan Contactor
*Fan Relay number displayed when using to test fans.
†Proper rotationof these fans tobe checked whencompressor(s) is running.SeeFig. 5 forcondenser fan locationswhen viewing
from the control box end.
11
Page 12
CONDENSER PUMP CONTROL ( ) — Factory de­faults for both condenser pump control and condenser flow
switch are set to ‘‘Not Controlled’’and ‘‘Disabled,’’ respec­tively. The condenser pump can be controlled in one of two ways: In the first method, the pump can be controlled like the cooler pump — it is turned on whenever the machine is in the on state and turned off otherwise (set to Type 1 using
the Service function). The second method of control is to turn the pump on when the first compressor is started and off when the last compressor is turned off (set to Type 2 using the Service function). With the flow switched enabled, the control checks the status of the input one minute after start­ing the pump. An alarm is generated if the flow switch input is not closed.
READ CIRCUIT SATURATED CONDENSING TEMPERATURE AND CURRENT FAN STAGE
IS SCT GREATER THAN HEAD PRESSURE SET POINT?
INCREASE CURRENT FAN STAGE BY ONE
ADD 15° F TO HEAD PRESSURE SET POINT FOR NEXT 35 SECONDS
DECREASE CURRENT FAN STAGE BY ONE
HAS SCT BEEN 35° F LESS THAN HEAD PRESSURE SET POINT 2 MINUTES?
NO
NO
YES
YES
LEGEND
SCT — Saturated Condensing Temperature
Fig. 6A — 30GX Head Pressure Control Without MotormasterT III Control
30GX UNITS — MOTORMASTER III CONTROL NOT INSTALLED
30GX UNITS — MOTORMASTER III CONTROL INSTALLED
DECREASE CURRENT FAN STAGE BY ONE
NO
NO
YES
IS SCT GREATER THAN HEAD PRESSURE SET POINT PLUS 15F?
INCREASE CURRENT FAN STAGE BY ONE
YES
READ CIRCUIT SATURATED CONDENSING TEMPERATURE AND CURRENT FAN STAGE
NO
INCREASE CURRENT FAN STAGE BY ONE
YES
CALCULATE NEW PID VALUE. DOSE OUTPUT REQUIRE MORE FANS?
OUTPUT NEW mA SIGNAL TO CONTROLLER
DOES PID OUTPUT REQUIRE LESS FANS?
LEGEND
PID — Proportional Integral Derivative SCT — Saturated Condensing Temperature
Fig. 6B — 30GX Head Pressure Control With Motormaster III Control
12
Page 13
Cooler Heater Control — Accessory cooler heaters
can be ordered for the 30GX chillers. If installed and en­abled, these heaters are turned on only when the machine is in the off state and the chiller is in a saturated suction tem­perature freeze condition.
Keypad and Display Module (Also Called HSIO-II) —
This module allows the operator to commu­nicate with the processor. It is used to enter configurations and set points and to read data, perform tests, and set sched­ules. The device consists of a keypad with 7 function keys, 5 operative keys, 12 numeric keys (0 to 9, •, and -), and a 2-line, 24-character alphanumeric liquid crystal display. See Fig. 7.
ACCESSING FUNCTIONS AND SUBFUNCTIONS — Table 7 shows a brief description of the keypad buttons. Table 8A shows the 6 functions (identified by name) and the subfunctions (identified by number). Table 8B shows the 6 functions (identified by name) and the subfunctions (iden­tified by number) when using the optional LID-2B control­ler. Table 9 shows a brief example on how to access subfunctions.
NOTE: It is not necessary to use the through every item in a subfunction. For example, if you wanted to read
the oil pressure for the A1 compressor, press , then press to go directly to A1 Oil Pressure. Use a simi-
lar procedure to view an item near the bottom of a subfunc­tion. To view the Circuit A Oil Switch status, press and . Use a similar procedure to view an item near
the bottom of a subfunction. Toview Condenser Pump Flow Switch status, press , , and . This proce-
dure is available in all functions except the TEST function. AUTOMATIC DEFAULT DISPLAY — When the keypad
has not been used for 10 minutes, the display automatically switches to the rotating automatic default display. This dis­play contains the 5 parts shown below.
Entering Fluid Temp
xx.x° F
Leaving Fluid Temp
xx.x° F
Percent Total Capacity
xxx.x%
Total Number of Alarms
xx
MODES : MODE_TBL Current active modes
All functions are made up of a group of subfunctions. To enter a subfunction, first press the subfunction number de­sired. Then press the function key in which the subfunction resides. To move within that subfunction, press the up or down arrow keys. Another subfunction may be entered at any time by pressing the subfunction number, then the func­tion key. Depending on system type and configuration, all displays may not be shown.
Table 7 — Keypad and Display Module Usage
FUNCTION
KEYS
USE
STATUS — For displaying diagnostic codes and current operating information about the machine.
HISTORY — For displaying run time, cycles, and previous alarms.
SERVICE — For entering specific unit configuration information and enabling manual control function.
SCHEDULE — For entering occupied/unoccupied schedules for unit operation.
ALGORITHM — Not used. SET POINT — For entering operating set points
and day/time information. TEST — For testing operating of the analog and
discrete outputs.
OPERATIVE
KEYS
USE
EXPAND — For displaying a non-abbreviated expansion of the display.
CLEAR — For clearing the screen of all displays. UP ARROW — For returning to previous display
position. DOWN ARROW — For advancing to next display
position. ENTER — For entering data.
CLEAR
ENTER
1
2
3
4
5
6
7
8
9
0
.
-
STAT
SET
SCHD
EXPN EDIT
SRVC
HIST
ALGO
TEST ALRM
TWENTY-FOUR CHARACTER TWO-LINE LCD DISPLAY
LEGEND
LCD — Liquid Crystal Display
Fig. 7 — Keypad and Display Module
13
Page 14
Table 8A — HSIO Functions and Subfunctions
SUBFUNCTION
NO.
FUNCTIONS
Status
Test Schedule Service History Set Point
1
Alarm Display
Circuit A Discrete Outputs
Ice Build Occupancy Schedule
Factory Configuration
Operating Hours Set Points
2
General Parameters Display
Circuit B Discrete Outputs
Local/Normal Occupancy Schedule
Options Configuration 1
Alarm History English/Metric
3
Circuit A Analog Values
Unit Discrete Outputs
Remote CCN Occupancy Schedule
Options Configuration 2
— Bus Address
4
Circuit A Discrete Inputs/ Outputs Table
Valves and MotormasterT Control
Holiday 01 Configuration
Reset/Demand Limit Configuration
— Time/Date
Configuration
5
Circuit B Analog Values
— Holiday 02
Configuration
Machine Configuration Codes
— CCN
Enable/Disable
6
Circuit B Discrete Inputs/ Outputs Table
— Holiday 03
Configuration
———
7
Unit Analog Parameters
— Holiday 04
Configuration
Transducer Calibration
——
8
Miscellaneous Inputs/Outputs
— Holiday 05
Configuration
Manual Control — —
9
Operating Modes — Holiday 06
Configuration
Master/Slave Configuration
——
10
Capacity Control — Holiday 07
Configuration
———
11
Dual Chiller — Holiday 08
Configuration*
———
*Subfunctions through are for configuring Holidays 09 through 30.
14
Page 15
Table 8B — Functions and Subfunctions Cross-Reference for the Optional LID-2B Controller
The optional LID-2B controller cross reference table be­low can be used as a guide to access the same information outlined in the HSIO functions and subfunctions table (see Table 8A). For example, in Table 8A, the alarm history is accessed through the HSIO by pressing 2 and the History button on the keypad (see Table 7). The LID-2B cross
reference table lists the menu item from the LID-2B which contains the alarm history information. In another example, from Table 8A, pressing 3 and the Status button on the HSIO keypad will access the circuit A analog values. In the table below, the circuit A analog values are accessed by selecting STATUS CIRCA_AN from the appropriate LID-2B menu.
HSIO
SUBFUNCTION
NO.
HSIO FUNCTION KEY
Status
Test Schedule Service History Set Point
1
STATUS A_UNIT_1
SERVICE CONTROL TEST
SCHEDULE OCCPC012
SERVICE EQUIPMENT CONFIGURATION
SERVICE EQUIPMENT CONFIGURATION STRTHOUR
SETPOINT
2
STATUS A_UNIT_1
SERVICE CONTROL TEST
SCHEDULE OCCPC02S
SERVICE EQUIPMENT CONFIGURATION OPTIONS1
SERVICE ALARM HISTORY
SERVICE LID CONFIGURATION
3
STATUS CIRCA_AN
SERVICE CONTROL TEST
SCHEDULE OCCPC65S
SERVICE EQUIPMENT CONFIGURATION OPTIONS2
—
SERVICE CONTROLLER IDENTIFICATION
4
STATUS CIRA_DIO
SERVICE CONTROL TEST
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_01
SERVICE EQUIPMENT CONFIGURATION RESETCON
—
SERVICE TIME AND DATE
5
STATUS CIRCB_AN
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_02
SERVICE EQUIPMENT CONFIGURATION CONCODES
—
STATUS A_UNIT_1
6
STATUS CIRB_DIO
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_03
———
7
STATUS UNIT_2
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_04
SERVICE EQUIPMENT SERVICE CALIBRTE
——
8
STATUS UNIT_3
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_05
SERVICE EQUIPMENT SERVICE MAN_CTRL
——
9
STATUS MODE_TBL
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_06
SERVICE EQUIPMENT CONFIGURATION MSTR_SLV
——
10
SERVICE CONTROL ALGORITHM STATUS LOADFACT
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_07
———
11
SERVICE CONTROL ALGORITHM STATUS LEADLAG
—
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_08*
——
—
*Subfunctions through are for configuring Holidays 09 through 30, and are also found under Service, Equipment
Configuration.
NOTE: The optional LID-2B controller uses the same password (1111) as the HSIO.
15
Page 16
Table 9 — Accessing Functions and Subfunctions
OPERATION KEYPAD ENTRY DISPLAY RESPONSE
To access a function, press subfunction no. and function name key. Display shows sub­function group.
Circuit A Discrete Outputs Loader A1
Relay is OFF
To move to other elements, scroll up or down using arrow keys.
Loader A2 Relay is OFF
Minimum Load Valve A Relay is OFF
Circuit A Oil Heater Relay is OFF
A1 Mtr. Cooling Solenoid Relay is OFF
A2 Mtr. Cooling Solenoid Relay is OFF
Circuit A Oil Pump Relay is OFF
Oil Solenoid A1 Relay is OFF
Oil Solenoid A2 Relay is OFF
When the last element in a subfunction has been displayed, the first element is repeated.
Loader A1 Relay is OFF
To move to next subfunction it is not necessary to use subfunction number. Press function name key to advance display through all subfunctions within a function and then back to the first.
Circuit B Discrete Outputs
Loader B1 Relay is OFF
Unit Discrete Outputs Valves and Motor Master
Circuit A Discrete Outputs
To move to another function, either depress function name key for desired function (display shows the first subfunction), or Access a specific sub­function by using the sub­function number and the function name key.
Alarms : xx Reset Alarms : 1 <ENTER>
CIR. A DISCRETE OUTPUTS
STATUS FUNCTION — This function shows the rotating display, current status of alarm and alert (diagnostic) codes, capacity stages, operating modes, chilled water set point, all measured system temperatures and pressures, analog inputs, and switch inputs. Refer to Table 10 for a complete descrip­tion of the function.
Alarms/Alerts — Alarms and alerts are messages that one or more faults have been detected. The alarms and alerts in­dicate failures that cause the unit to shut down, terminate an option (such as reset) or result in the use of a default value such as a set point. Refer to the Troubleshooting section for more information.
Up to 10 alarms/alerts can be stored at once. Toviewthem,
press . The control will display the current total number of alarms/alerts. Use the arrow keys to scroll through
the list. Press the key when needed to view the full description of an alarm or alert. Press to clear
all the alarms. See Table 11.
IMPORTANT: Do not clear the alarms without first reviewing the full list and investigating and correcting the cause of the alarms.
When an alarm or alert is stored in the display and the
machine automatically resets, the alarm/alert is deleted. Codes
for safeties which do not automatically reset are not deleted until the problem is corrected and the machine is reset. To clear manual reset alarms from the CPM modules, the reset button on the HSIO bracket must be pressed. Next, switch the LOR switch to OFF and back to Local or Remote position (default alarm clearing method). Press
and then to clear the alarm from the PSIO
if the default LOR reset function has been disabled. General Parameters — General operating parameters are
displayed including control mode, run status, CCN status, and the 5 most current alarms. Press to display these
and the other values as shown in Table 10. CircuitAand B Analog and Discrete Information —Circuit
A Analog Values can be viewed bypressing and scroll­ing down to see current system operating conditions such as
pressures and temperatures. Pressing will bring up Circuit A Discrete Inputs and Outputs. Scroll down to view
the On/Off status of the compressor(s), loaders, solenoids, and pumps. Oil switch and feedback inputs are also dis-
played. Press and to view the identical ana­log values and discrete inputs and outputs for Circuit B. See
Table 10 for a complete display.
16
Page 17
Unit Analog Parameters and Temperature Reset — Press
and scroll down to display the unit entering and leav-
ing fluid temperatures as well as the temperature reset signal and calculated values.
Miscellaneous Inputs and Outputs — Pressing and scrolling down will reveal the On/Off status of the con-
denser fans (30GX only). Also found here are the Demand Limit settings, pump relay and switch status, and miscella­neous items such as Heat/Cool and Dual Set Point switch positions. See Table 10 for a complete list.
Modes —Theoperatingmodesaredisplayed to indicate the operating status of the unit at a given time. See Table 12 for a complete list of all modes.
To enter the MODES subfunction, press and use
the key to view all current modes of operation. See Table 13.
Capacity Control — Pressing , this subfunc­tion displays the load/unload factor, control point, and leav-
ing water temperature. Scrolling down will also reveal the liquid level sensor values in degrees format.
Dual Chiller — Pressing will access the dual chiller control status. This subfunction will display whether
or not the chiller is operating as a Master or Slave, any alarm conditions present for dual chiller control, and lead/lag in­formation for changeover. Dual chiller control is configured
under .
17
Page 18
Table 10 — Status Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Alarms
Alarm : xx Reset Alarms: 1 <ENTER>
All current alarms are displayed Use as needed
2 General Parameters GENERAL PARAMETERS
Displays LOCAL ON/OFF or CCN ON/OFF
Force/clear value with HSIO or CCN device. Must be ON for CCN clock control.
Control Mode Run Status
Off/On Occupied ?
Yes/No CCN Enable
Off/On CCN Chiller Start/Stop
Start/Stop Alarm State
Normal/Alarm Current Alarm 1
x.xx Current Alarm 2
x.xx Current Alarm 3
x.xx Current Alarm 4
x.xx Current Alarm 5
x.xx Active Demand Limit
xxx.x% Percent Total Capacity
xxx.x% Water/Brine Setpoint
xx.x dF Control Point
xx.x dF Entering Fluid Temperature
xx.x dF Leaving Fluid Temperature
xx.x dF Emergency Stop
Emstop Minutes Left for Start
xx min Heat-Cool Status
Heat/Cool
3 Circuit A Analog Values
CIRCUIT A ANALOG VALUES
Percentage of total circuit capacity currently in use.
Percentage of Total Capacity value not in an alarm or fault condition.
Total Capacity xxx.x%
Available Capacity xxx.x%
Discharge Pressure xxx.x PSI
Suction Pressure xxx.x PSI
A1 Oil Pressure Diff. xxx.x PSI
A2 Oil Pressure Diff. xxx.x PSI
A1 Oil Pressure xxx.x PSI
A2 Oil Pressure xxx.x PSI
Discharge Gas Temperature xxx.x dF
A1 Motor Temperature xxx.x dF
A2 Motor Temperature xxx.x dF
See Legend on page 23.
18
Page 19
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Circuit A Analog Valves (cont)
SAT Condensing Temp xxx.x dF
Saturated Suction Temp xxx.x dF
EXV Percent Open xxx.x%
Motormaster Speed xxx.x%
Water Valve Position xxx.x%
Cooler Level Indicator x.xx
CPM A1 Feedback x.x Volts
See Table 3.
CPM A2 Feedback x.x Volts
See Table 3.
Circuit A Econ Pressure xxx.x PSI
4 Circuit A Discrete Inputs/Outputs
CIR. A DISCRETE OUTPUTS Compressor A1
Off/On Compressor A2
Off/On Loader A1
Off/On Loader A2
Off/On Minimum Load Valve A
Off/On Circuit A Oil Heater
Off/On A1 Mtr Cooling Solenoid
Off/On A2 Mtr Cooling Solenoid
Off/On Circuit A Oil Pump
Off/On Oil Solenoid A1
Off/On Oil Solenoid A2
Off/On CIR. A DISCRETE INPUTS
Circuit A Oil Switch Open/Close
Compressor A1 Feedback Off/On
Compressor A2 Feedback Off/On
5 Circuit B Analog Values
CIRCUIT B ANALOG VALUES
Percentage of total circuit capacity currently in use.
Percentage of Total Capacity value not in an alarm or fault condition.
Total Capacity xxx.x%
Available Capacity xxx.x%
Discharge Pressure xxx.x PSI
Suction Pressure xxx.x PSI
B1 Oil Pressure Diff. xxx.x PSI
B2 Oil Pressure Diff. xxx.x PSI
B1 Oil Pressure xxx.x PSI
B2 Oil Pressure xxx.x PSI
Discharge Gas Temperature xxx.x dF
19
Page 20
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
5 Circut B Analog Valves (cont)
B1 Motor Temperature xxx.x dF
B2 Motor Temperature xxx.x dF
SAT Condensing Temp xxx.x dF
Saturated Suction Temp xxx.x dF
EXV Percent Open xxx.x%
Motormaster Speed xxx.x%
Water Valve Position xxx.x%
Cooler Level Indicator x.xx
CPM B1 Feedback x.x Volts
See Table 3.
CPM B2 Feedback x.x Volts
See Table 3.
Circuit B Econ Pressure xxx.x PSI
6 Circuit B Discrete Inputs/Outputs
CIR. B DISCRETE OUTPUTS Compressor B1
Off/On Compressor B2
Off/On Loader B1
Off/On Loader B2
Off/On Minimum Load Valve B
Off/On Circuit B Oil Heater
Off/On B1 Mtr Cooling Solenoid
Off/On B2 Mtr Cooling Solenoid
Off/On Circuit B Oil Pump
Off/On Oil Solenoid B1
Off/On Oil Solenoid B2
Off/On CIR. B DISCRETE INPUTS
Circuit B Oil Switch Open/Close
Compressor B1 Feedback Off/On
Compressor B2 Feedback Off/On
7 Unit Analog Parameters
UNIT ANALOG PARAMETERS Cooler Entering Fluid
xx.x dF Cooler Leaving Fluid
xx.x dF Condenser Entering Fluid
xx.x dF Condenser Leaving Fluid
xx.x dF Reclaim Entering Fluid
xx.x dF Reclaim Leaving Fluid
xx.x dF 5 Volt Supply
x.x Volts
See Legend on page 23.
20
Page 21
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
7 Unit Analog Parameters (cont)
TEMPERATURE RESET 4-20 mA Reset Signal
xx.x mA Return Reset Signal
xx.x dF External Reset Signal
xx.x dF Outdoor Air Temp
xx.x dF Calculated Reset
xx.x dF
8 Misc. Inputs/Outputs
MISC INPUTS/OUTPUTS FAN_1
Off/On FAN_2
Off/On FAN_3
Off/On FAN_4
Off/On FAN_5
Off/On FAN_6
Off/On DEMAND LIMIT
4-20 mA Demand Signal xx.x mA
Demand Switch 1 Off/On
Demand Switch 2 Off/On
CCN Loadshed Signal Normal/Alarm
Max Allowable CAP xxx.x%
PUMPS Cooler Pump Relay
Off/On Cooler Pump Flow Switch
Off/On Condenser Pump Relay
Off/On Condenser Pump Flow Switch
Off/On MISCELLANEOUS
Ice Valve Off/On
Ice Build Complete Yes/No
Heat/Cool Switch Heat/Cool
Dual Set point Switch Off/On
Cooler Heater Off/On
Options Temperature 1 xx.x dF
Not Used
Options Temperature 2 xx.x dF
Not Used
9 Operating Modes
MODES :MODE_TBL mode name ON/OFF
Only active modes displayed LOCAL OFF Scroll with down arrow key to display CCN OFF
21
Page 22
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
9 Operating Modes (cont)
CLOCK OFF LOCAL ON CCN ON CLOCK ON DUAL SP ACTIVE (1st SP) DUAL SP ACTIVE (2nd SP) TEMPERATURE RESET
ACTIVE DEMAND LIMIT ACTIVE
LOAD LIMIT ACTIVE LOW SOURCE TEMP PROTECT RAMP LOADING ACTIVE TIMED OVERRIDE ACTIVE LOW COOLER SUCTION TEMP WSM CONTROLLING SLOW CHANGE OVERRIDE OFF TO ON DELAYACTIVE FSM CONTROLLING 2 CHILLR LEAD LAG ACTIVE 2 CHILLR LL COMM FAILURE CIR A LOW DISCHG SUPERHT CIR B LOW DISCHG SUPERHT CIR A HIGH SDT CIR B HIGH SDT
10 Capacity Control
CAPACITY CONTROL Load/Unload Factor
xxx.x% Control Point
xx.x dF Leaving Water Temp
xx.x dF MISC. INDICATORS
Liquid Lvl Sensor Cir. A xx.x dF
Liquid Lvl Sensor Cir. B xx.x dF
22
Page 23
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 11 Dual Chiller
DUAL CHILLER Unit Master / Slave
0/1/2
0 = Neither 1 = Slave 2 = Slave
Master / Slave Ctrl Active Yes/No
Lead Chiller 1/2
1 = Master 2 = Slave
Slave Chiller State 0/1/3/5/6
0 = Chiller OFF 1 = Valid Run State in CCN Mode 3 = Chiller in Local Mode 5 = Shutdown on Alarm 6 = Communications Failure
Slave Chiller Total Cap xxx.x%
Lead / Lag Changeover Yes if Lead / Lag Balance Enabled Master / Slave Error
1/2/3/4/5/6
1 = Master / Slave Have Same Address 2 = Master / Slave Communication Failure 3 = Chiller in Local Mode 4 = Slave Shutdown on Alarm(s) 5 = Master Configured for Heating 6 = No Slave Configured
LEGEND
CCN — Carrier Comfort Network CPM — Compressor Protection Module dF — Degrees Fahrenheit EXV — Electronic Expansion Valve FSM — Flotronic™ System Manager LL — Lead/Lag SAT — Saturated SDT — Saturated Discharge Temperature SP — Set Point WSM — Water System Manager
Table 11 — Reading and Clearing Alarms
KEYPAD ENTRY DISPLAY COMMENT
Alarm: 02 Reset Alarms: 1 <ENTER>
Comp A1 Fail - 1.70 Volt Alarm : 15:12 04/15/96
Comp A1 Fail - 1.70 Volts Phase Reversal Alarm : 15:12 04/15/96
Compressor A1 Low Oil Pr Alarm : 10:34 04/15/96
Compressor A1 Low Oil Pressure Alarm : 10:34 04/15/96
Alarm: 02 Reset Alarms: 1 <ENTER>
Press Reset button first
Alarm: 00 Reset Alarms: 1 <ENTER>
Alarms reset and cleared
Entering Fluid Temp xx.x dF
Returns to rotating default display
Leaving Fluid Temp xx.x dF
Percent Total Capacity xxx.x%
Total Number of Alarms xx
MODES: MODE
TBL
List of All Current Modes
23
Page 24
Table 12 — Operational and Mode Display Codes
CODE DESCRIPTION
LOCAL OFF Unit is off. LOCAL/OFF/REMOTE switch is
in OFF position or LOCAL/OFF/REMOTE switch is in REMOTE position and remote contacts are open.
CCN OFF Unit is off. LOCAL/OFF/REMOTE switch is
in LOCAL position and CCN control is enabled (Stop state) or CCN is enabled (Stop state) with LOR switch in REMOTE position and remote contacts closed.
CLOCK OFF Unit is off due to internal clock schedule.
LOR switch is in LOCAL position.
LOCAL ON Unit is on. LOR switch is in LOCAL position
and CCN is disabled or LOR switch is in REMOTE position with contacts closed and CCN is disabled.
CCN ON Unit is on due to CCN command. LOR
switch is in LOCAL position and CCN is enabled (Run state) or LOR switch is in REMOTE position with contacts closed and CCN is enabled (Run state)
CLOCK ON Unit is on due to internal clock schedule or
occupied override function. LOR switch is in LOCAL position.
DUAL SP ACTIVE (1st SP)
Dual set point is in effect. In this mode, unit continues to run in an occupied condition, and leaving fluid set point is automatically controlled to the CSP1 set point in the SET POINT function.
DUAL SP ACTIVE (2nd SP)
Dual set point is in effect. In this mode, unit continues to run in unoccupied condition, but leaving fluid set point is automatically increased to a higher level (CSP2 set point is in SET POINT function).
TEMPERATURE RESET ACTIVE
Temperature reset is in effect. In this mode, unit is using temperature reset to adjust leaving fluid set point upward, and unit is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air temperature, space temperature, or 4 to 20 mA signal.*
DEMAND LIMIT ACTIVE
Demand limit is in effect. This indicates that capacity of unit is being limited by demand limit control option. Because of this limitation, the unit may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by a switch or 4 to 20 mA signal.*
FSM CONTROLLING
Flotronic™ System Manager (FSM) is controlling the chiller.
RAMP LOADING ACTIVE
Ramp load (pulldown) limiting is in effect. In this mode, the rate at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See CRAMP set point in the SET function in (page 25). The pulldown limit can be modified, if desired, to any rate from
0.2° F to 2° F (0.1° to 1° C)/minute.
TIMED OVERRIDE ACTIVE
Timed override is in effect. This isa1to 4 hour temporary override of the pro­grammed schedule, forcing unit to occupied mode. Override can be implemented with unit under LOCAL/REMOTE or CCN control. Override expires after each use.
WSM CONTROLLING
Water System Manager is controlling the chiller.
SLOW CHANGE OVERRIDE
Slow change override is in effect. The leaving fluid temperature is close to and moving towards the control point.
CODE DESCRIPTION
OFF TO ON DELAY ACTIVE
Chiller is being held off by Minutes Off Time found by keying . Also, normal
operation of the chiller includes a minimum
1.5 minute delay after a capacity stage change has been made. This delay is adjustable from 1.5 to 6 minutes.
LOAD LIMIT ACTIVE
This function determines the maximum allowable capacity that can be running and is accomplished through the Flotronic System Manager. The unit may not be able to produce the desired leaving fluid temperature.
2 CHILLR LEAD LAG ACTIVE
Future Use.
2 CHILLR LL COMM FAILURE
Future Use.
CIRCUIT A LOW DISCHARGE SUPERHT
If the circuit discharge superheat is less than 15° F (8.3° C), the capacity control routine will not add any stages (to either circuit).
If the compressor has been running for at least 3 minutes, the EXV will not be opened any further. If the circuit discharge superheat is less than 10° F (5.6° C) and falling, the circuit EXV will be closed 50 steps every 10 seconds.
If the discharge superheat is less than 5° F (2.8° C) and falling, a circuit loader will be deenergized every 30 seconds. The final stage will not be unloaded unless an alarm condition is present.
CIRCUIT B LOW DISCHARGE SUPERHT
See description for Circuit A above.
CIRCUIT A HIGH SCT
If the circuit is running and the Saturated Condensing Temperature (SCT) is greater than the Maximum Condensing Temperature Set point (MCT_SP) minus 12° F (6.7° C), the control will not add any stages.
If the SCT is greater than the MCT_SP plus 5° F (2.8° C), the circuit will be unloaded and shut down if necessary. If the SCT is greater than the MCT_SP plus 2° F (1.1° C) for one minute, a loader will be deenergized.
If the SCT is greater than the MCT_SP minus 4° F (2.2° C), the control will compare the maximum operating pressure set point (MOP_SP) with the modified MOP_SP (MOP_CTRL).
If the MOP_CTRL is greater than the MOP_SP, the mode will be cleared. Otherwise the control will display the high SCT override mode. The capacity control routine will not add any stages. If the circuit is at its lowest capacity, this mode will be ignored.
CIRCUIT B HIGH SCT
See description for Circuit A above.
LEGEND
CCN — Carrier Comfort Network CSP — Cooling Set Point CRAMP — Cooling Ramp Loading EXV — Electronic Expansion Valve LOR — Local/Off/Remote SP — Set Point WSM — Water System Manager
*Afield-supplied500Ohm
1
⁄2W resistor must be installed across the
input terminals when usinga4to20mAsignal.
Table 13 — Reading Current Operating Modes
KEYPAD ENTRY DISPLAY
MODES :MODE_TBL CCN ON
DEMAND LIMIT ACTIVE
24
Page 25
TEST FUNCTION — The test function operates the diag­nostic program. To initiate the test function, the LOCAL/ OFF/REMOTE switch must be in the OFF position.
To reach a particular test, press its subfunction number followed by the key then scroll to the desired test by pressing the down arrow key. Refer to Table 14 for a com-
plete description of the test function.
To start a test of discrete outputs, press . To end the test, simply press the key or press . Pressing the key after a test has started advances the system to
the next test, whether the current test is operating or has timed out. Circuit A discrete outputs can be tested in and
include loaders, minimum load valve, oil heater (if equipped), motor cooling solenoids, oil pump, and oil solenoids. Simi­larly, Circuit B discrete outputs can be tested in
.Additionaldiscrete outputs, including condenser fans,
cooler heater, water pumps, and remote alarms can be tested in .
Press to access Valves and Motormastert device analog outputs. Scroll down to display Circuit A EXV Valve
with a target percent of 0%. Press to step the EXV to 25%. Pressing three additional times will move
the EXV to 50%, 75%, and 100%. The EXV may be closed in 25% steps by pressing for each desired step. Wait
30 seconds between each step when opening and closing for the valve to stop moving. Pressing the down arrow will dis­play Circuit B EXV Valve and it is tested in the same man­ner as Circuit A. Also available for test are Circuit A water valve (if equipped) and the Circuit A and B Fan speed % (direct control Motormaster device) outputs for 30GX chill­ers. These are tested in the same manner as the EXV valves. Note that condenser fan motors are NOT started during fan speed quick tests. Measure 4 to 20 mA dc output using meter in series with violet wire to controller. See page 72 of Field Wiring section.
While the unit is in test, you can leave the test function and access another display or function by pressing the ap­propriate keys. However,a component that is operating when another function is accessed remains operating. You must
re-enter the test function and press to shut down the component. Components with a timed operating limit time
out normally even if another function is accessed.
Since the Test function checks only certain outputs, it is a good practice to also check all inputs and outputs acces­sible through the status function. These can be located by
pressing through . If keypad is not used for 10 minutes, the unit automatically leaves the test function
and resumes the normal rotating display. See Table 15. HISTORY FUNCTION — Pressing displays total
machine operating hours. Scroll down to display machine run time and starts, and total run time and starts for each compressor. Refer to Table 16 for a complete description of the function. When the PSIO-1 module is replaced or down­loaded with Version 4.0 or later software, the number of starts and run hours may be changed one time. Record the current values from the PSIO before removing the module or down­loading new software. The number of starts and hours may be changed by entering the desired value at the HSIO and
pressing the key.
Pressing displays the last 10 alarms along with a description and time and date of occurrence of each alarm.
SET POINT FUNCTION — Set points are entered through the keypad. Set points can be changed within the upper and lower limits, which are fixed. The ranges are listed below. Refer to Table 17 for a complete description of the function.
Cooling Set Point 1,2
Water:
Medium
Temperature Brine:
Low
Temperature Brine:
38 to 70 F
(3.3 to 21.1 C)
14 to 70 F
(−10 to 21.1 C)
−13 to 70 F
(−25 to 21.1 C)
Reset Set Points
Maximum
Reset Range:
−30 to 30 F
(−17 to 17 C)
External Temperature
Reset:
−40 to 240 F
(−40 to 118 C)
Chiller Fluid D:
0° to 15 F
(0° to 8 C)
External Signal Reset: 4 to 20 mA (2-10 vdc with
500 Ohm resistor) Demand Limit Set Points Switch Input: Step1—0to100% Capacity Reduction
Step2—0to100% Capacity Reduction
External Signal: Maximum Demand Limit 4 to 20 mA
(2-10 vdc with 500 Ohm resistor) Minimum Demand Limit 4 to 20 mA
(2-10 vdc with 500 Ohm resistor) Loadshed Demand Delta: 0 to 60% Maximum Loadshed Time: 0 to 120 min.
Head Pressure Set Points Air cooled chillers (30GX): 80 to 135 F (26.7 to 57.2 C) Water cooled chillers (30HX): 80 to 128 F (26.7 to 53.3 C) Set Point Table — The unit operating set points can be found
under . Use the down arrow key to scroll through the set points. The first set point is Cool Set Point 1. This is
the occupied chilled fluid set point. Scroll down to Cool Set Point 2 and then to the Cooling Ramp load multiplier which is configurable from 0.2 to 2.0° F/min. (0.11 to 1.1° C/min.). This value is the maximum rate at which the leaving fluid temperature is allowed to drop without adding a stage. Cool­ing Set Point 2 is used in conjunction with the dual set point switch function. This is used as the low temperature set point for ice duty or as the unoccupied set point. Press the down arrow key to display the Circuit A and B head pressure set points. The remaining set points in this subfunction include demand limit, LCW (leaving chilled water) delta alarm limit, minutes off time, and motor temperature set point.
Display Units — Press to display the units of mea­sure being used. Type 0 is for English and type 1 is for
Metric. Address — For CCN configurations, press and
scroll down to display the address and bus number of the chiller.
Time — Press and scroll down to read and change the unit day of week, time, day of month, month of year and
year of century. See the examples in Table 17 for making changes to these values.
CCN Enable/Disable — Press to disable the CCN control of the chiller. This function will override CCN con-
trol commands. The CCN Enable value under must be ON to activate this function. With CCN Enable set to ON
and Disable CCN Control set to ‘‘0,’’ the chiller will func­tion normally under CCN control. With Disable CCN Con­trol set to ‘‘1,’’ the chiller will operate in a local mode under its own control.
Reading and Changing Set Points — Table 18 shows how to read and change the chilled fluid set point. Other set points can be changed by following the same procedure. Refer to Table 17 for the sequence of display of set points in each subfunction.
25
Page 26
Table 14 —Test Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Circuit A Discrete Output
Circuit A Discrete Output Loader A1 Relay is OFF
Loader A1 Relay is ON
Loader A2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn an output off.
Minimum Load Valve A Circuit A Oil Heater A1 Mtr. Cooling Solenoid A2 Mtr. Cooling Solenoid Circuit A Oil Pump Oil Solenoid A1 Oil Solenoid A2
NOTE: Output will display Relay is ABSENT when not configured
2 Circuit B Discrete Outputs
Circuit B Discrete Outputs Loader B1 Relay is OFF
Loader B1 Relay is ON
Loader B2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn the output off.
Minimum Load Valve B Circuit B Oil Heater B1 Mtr. Cooling Solenoid B2 Mtr. Cooling Solenoid Circuit B Oil Pump Oil Solenoid B1 Oil Solenoid B2
NOTE: Output will display Relay is ABSENT when not configured
3 Unit Discrete Output
Unit Discrete Output Fan 1 Relay is OFF
Fan 1 Relay is ON
Fan 2 Similarly use to test remaining outputs. Press the
down arrow key or to turn output off.
Fan 3 Fan 4 Fan 5 Energizes Circuit A fans for 30HXA units. Fan 6 Energizes Circuit B fans for 30HXA units. Cooler Pump Condenser Pump Cooler Heater Alarm Remote Alarm 1 Currently not supported.
26
Page 27
Table 14 —Test Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Unit Discrete Output (cont)
Remote Alarm 2 Currently not supported. Remote Alarm 3 Currently not supported. Remote Alarm 4 Currently not supported. Remote Alarm 5 Currently not supported. Remote Alarm 6 Currently not supported. Remote Alarm 7 Currently not supported. Remote Alarm 8 Currently not supported. Remote Alarm 9 Currently not supported. Remote Alarm 10 Currently not supported. Remote Alarm 11 Currently not supported. Remote Alarm 12 Currently not supported. Remote Alarm 13 Currently not supported. Remote Alarm 14 Currently not supported. Remote Alarm 15 Currently not supported. Remote Alarm 16 Currently not supported.
4 Valves and Motormaster
Valves and Motor Master Circuit A EXV Valve Target Percent = 0%
Circuit A EXV Valve Target Percent = 25%
Step in 25% increments.
Circuit A EXV Valve Target Percent = 50%
Wait 30 seconds between each step for valve to stop moving.
Circuit A EXV Valve Target Percent = 75%
Valve may be closed in 25% increments by keying in . Wait 30 seconds between each step for valve to stop moving.
Circuit A EXV Valve Target Percent = 100%
Circuit B EXV Valve Target Percent = 0%
Test same method as for Circuit A
Circuit A Water Valve Target Percent = 0%
Test same method as for EXV valves Circuit A% Fan Speed Test same method as for EXV valves Circuit B% Fan Speed Test same method as for EXV valves
LEGEND
EXV — Electronic Expansion Valve
Table 15 — Using Test Function
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
Circuit A Discrete Output Loader A1 Relay is OFF
Appears on screen momentarily, then will switch to Loader A1.
Loader A1 Relay is ON
Compressor Loader A1 solenoid energized
Loader A1 Relay is OFF
Compressor Loader A1 solenoid deenergized
Valves and Motor Master Circuit A EXV Valve Target Percent = 0%
Circuit A EXV Valve Target Percent = 25%
Continue pressing to step to 50%, 75%, and 100%.
Circuit A EXV Valve Target Percent = 0
Continue pressing to step closed.
LEGEND
EXV — Electronic Expansion Valve
27
Page 28
Table 16 — History Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Operating Hours
Machine Operating Hours xxx.x hours
Number of hours unit has at least 1 compressor running
Number of unit starts from zero capacity
These values may be changed once, when new software is down­loaded or when the PSIO-1 module is replaced (Version 4.0 and later).
Machine Starts xxx
Circuit A Operating Hours
xxx.x hours Compressor A1 Hours
xxx.x hours Compressor A2 Hours
xxx.x hours Starts
Compressor A1 Starts xxx
Compressor A2 Starts xxx
Circuit B Operating Hours
xxx.x hours Compressor B1 Hours
xxx.x hours Compressor B2 Hours
xxx.x hours Starts
Compressor B1 Starts xxx
Compressor B2 Starts xxx
2 Alarm History
Previous Alarm 1 - description Alarm description, time/day of occurrence
Lists 10 most recent alarms. Use key when necessary
Previous Alarm 2 - description Alarm description, time/day of occurrence
Previous Alarm 3 - description Alarm description, time/day of occurrence
Previous Alarm 4 - description Alarm description, time/day of occurrence
Previous Alarm 5 - description Alarm description, time/day of occurrence
Previous Alarm 6 - description Alarm description, time/day of occurrence
Previous Alarm 7 - description Alarm description, time/day of occurrence
Previous Alarm 8 - description Alarm description, time/day of occurrence
Previous Alarm 9 - description Alarm description, time/day of occurrence
Previous Alarm 10- description Alarm description, time/day of occurrence
28
Page 29
Table 17 — Set Point Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Set Point Table
COOLING Cool Setpoint 1
xx.x dF
Default: 44.0
Cool Setpoint 2 xx.x dF
Default: 44.0
Cooling Ramp Loading xx.x dF
Default: 0.5 HEATING NOT SUPPORTED Heat Setpoint 1
xx.x dF
NOT SUPPORTED
Default: 98.0 Heat Setpoint 2
xx.x dF
NOT SUPPORTED
Default: 98.0 Heating Ramp Loading
xx.x dF
NOT SUPPORTED
Default: 0.5 HEAD PRESSURE
Head Pressure Setpoint A xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
Head Pressure Setpoint B xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
DEMAND LIMIT Demand Switch 1 Setpoint
xxx.x%
Default: 80.0% Demand Switch 2 Setpoint
xxx.x%
Default: 50.0% LCW Delta Alarm Limit
xxx.x dF
Default: 50.0 dF Minutes Off Time
xxx min
Default: 0 min Motor Temp Set Point
xxx.x dF
Default: 200.0 dF
2 Units
US IMPERIAL/METRIC 0
0 = English (Default)
1 = Metric
3 Address
TARGETADDRESS x
Default: 1 TARGET BUS NUMBER
x
Default: 0
4 Time
Day of Week Monday
Mon=1, Tues=2, etc. Day of Week
Wednsday
Day of week set TIME (HOUR:MIN)
00:00
Enter military format TIME (HOUR:MIN)
10:30
Time of day set DAY OF MONTH
xx DAY OF MONTH
20
Day of month set MONTH OF YEAR
xx MONTH OF YEAR
05
Month of year set YEAR OF CENTURY
xx YEAR OF CENTURY
96
Year of century set
5 CCN Disable
Disable CCN Control x
0=no, 1=yes
Default: 0
LEGEND
CCN — Carrier Comfort Network LCW — Leaving Chilled Water
NOTE: If metric option is selected under , temperatures are expressed in degrees Celsius and pressures are expressed in kPa.
29
Page 30
Table 18 — Reading and Changing
Chilled Fluid Set Point
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
COOLING Change set point from
default to 48 F.
Cool Set point 1
44.0 F default Cool Set point 1
48.0 F
Set point change complete
SERVICE FUNCTION — This function allows the techni­cian to view and input configuration data. Factory configu­ration data, field configuration data, and service configura­tion data may be viewed or entered through the keypad and display module. See Table 19 for a complete listing of con­figurable items. Whenever a processor module is replaced in the field, the complete list of configuration codes should be checked for correct settings. The current software version can be displayed. See Table 20.
Scroll down in this function to display configuration in­formation including number of compressors, tonnage, and compressor must-trip amps.
Password Protection of HSIO Configurable Service Points — To modify configurations and values and to use the manual control subfunction, the password must be entered before the first change can be made. The default password is set to
. See Table 21 for an example of how to
enter the password to change the Lead/Lag configuration. Options Configuration Tables 1 and 2 — These subfunc-
tions can be accessed by pressing or and scroll­ing down to display the configuration options. See Table 19
for a complete list of these options. Temperature Reset, Demand Limit and Head Pressure PID
Configurations —Press andscrolldowntoview the configuration information. See Table 19 for a complete list.
Factory Configuration Codes — Pressing allows entry into the factory and service configuration codes
subfunction. Under this subfunction, there are 5 configura­tion codes that are downloaded at the factory. Each code is made up of 8 digits. If the processor module is replaced in the field, these 5 configuration codes should be checked us­ing the keypad and HSIO display module. See Table 22 for a descriptionofthefactory configuration codes (codes 1 through
3) and service configuration codes (codes 4 and 5).
The factory and service configuration codes are found by pressing . These are preset from the factory.They can
be verified by following the description in Table 22. These codes MUST be checked and corrected in the field if the PSIO-1 module is replaced.
NOTE: The LOCAL/OFF/REMOTE switch must be in the OFF position to change configuration codes.
A label is applied to a control box panel with a list of factory and service codes for particular units. Table23shows how to configure a new PSIO-1 module for use in a 30HXC­106---501CA water cooled chiller.
Transducer Calibration — Press and scroll down to view the transducer calibration information. See Table 19
for a complete list, and the Pressure Transducers section on page 59 for a description of this subfunction.
Manual Control Mode — This control allows the user to have full control over the compressors, loaders, and the mini­mum load valve (if installed) of the machine. Normal safe­ties such as high pressure, oil level and pressure, and CPM related alarms are NOT bypassed in this control mode. The capacity control function and overrides ARE bypassed when using the manual control mode. To enter this mode, switch
the LOR switch to OFF. Press at the HSIO. The dis­play will read Manual Control Enable - Disable. Press
and switch the LOR switch to Local. The display will change to Manual Control Enable - Enable. The Disable and Enable will appear on the second line of the display. See Table 19 for a complete list of this function.
Scroll down and press to start the desired com-
pressor.The control will start the compressor if the pre-lube cycle is passed, just as in normal operation. Press to add loaders as desired and press to turn off loaders
and compressors. The Minimum Load Valve can be ener­gized using the same procedure.
Dual Chiller Configuration — Press to enter the Dual Chiller control configuration. This method of control is for
a stand-alone Master/Slave combination of chillers and will NOT work with the Flotronic™ System Manager (FSM). The Minus One Pass Cooler option is required for this configuration.
The chillers should be piped for series flow through the coolers. The Master chiller must be downstream from the Slave chiller leaving water.BoththeMasterand Slave chiller must be connected to the same CCN Level II communica­tions bus with different addresses. To enable the dual chiller
configuration the CCN Enable function must be set to Enable for each chiller, otherwise each chiller will oper-
ate independently. This value can be activated through the HSIO or through a CCN device. Both chillers should be con-
figured for Close Control and require flow switches to be installed. For cooler pump control, wire both Master
and Slave chiller outputs to the cooler pump starter.All sys­tem inputs (temperature reset, demand limit, dual set point, etc.) should be connected to the Master chiller. If Lead/Lag Balance is disabled, the Master chiller will always be the lead chiller. If Lead/Lag Balance is enabled, the control will alternate between the Master and Slave chillers to keep their respective run hours balanced within the value configured for Lead/Lag Balance Delta. The desired leaving fluid set
point for the Duplex chiller must be configured in the Master chiller. CCN Control of the chillers can be dis-
abled locally through the HSIO by entering and en­abling the Disable CCN Control value. This value must be
disabled before the chiller will return to Duplex control.
30
Page 31
Table 19 — Service Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Service Configuration
Software CESR_500100 Ver xxx
Unit Type x
1 = Air-cooled,2=Water-cooled 3 = Split system
Number of Cir A Comp x
Compressor A1 Tonnage xx
Compressor A2 Tonnage xx
Oil Switch Configuration x
Number of Cir B Comp x
Compressor B1 Tonnage xx
Compressor B2 Tonnage xx
Max. Cond. Temp Setpoint xxx.x dF
30GX = 154 F (68 C) 30HXA = 152 F (67 C) 30HXC = 122 F (50 C)
MOP Set point xx.x dF
Default = 52 F (11.1 C)
Fan Staging Select x
Displays ‘‘Not Used’’ or a number. See Table 5
CPM Board Used? Yes
Compr. A1 Must Trip Amps xxx.x
Value from CPM module. See Appendix A.
Compr. A2 Must Trip Amps xxx.x
Value from CPM module. See Appendix A.
Compr. B1 Must Trip Amps xxx.x
Value from CPM module. See Appendix A.
Compr. B2 Must Trip Amps xxx.x
CURRENTLY NOT USED
2 Options Configuration 1
Cooler Fluid Select x
1 = Water (Default), 2 = Medium Temp Brine 3 = Low Temp Brine (HX only)
Min. Load Valve Select x
Displays Enable/Dsable Default: Dsable
Loading Sequence Select x
1 = Equal circuit, 2 = Staged circuit Default: 2. See page 6
Lead/Lag Sequence Select x
1 = Automatic (Default), 2 = Circuit A leads, 3 = Circuit B leads
Head Press. Control Type x
0 = None (Default, HX), 1 = Air cooled (Default, GX),2=Water cooled
Motormaster Select x
0 = None (Default), 1 = Direct control
Water Valve Type x
0 = None (Default), 1 = 4-20 mA, 2 = 0-10 V, 3 = 20-4 mA, 4 = 10-0 V
Ext. Reset Sensor Select x
0 = Space Temp Thermistor (Default) 1 = Outside Air Thermistor
Cooler Pump Interlock x
0 = No interlock 1 = Interlock enabled (Default)
Cooler Pump Control x
0 = Not controlled (Default) 1 = On/Off Control
Condenser Pump Control x
0 = Not controlled (Default) 1 = On/Off Control 2 = Off when stages equal 0 (unit off)
Condenser Flow Switch x
Displays Enable/Dsable Default: Dsable
Condenser Water Sensors x
0 = Not used (Default), 1 = Used
Heat Reclaim Sensors x
CURRENTLY NOT SUPPORTED
3 Options Configuration 2
Cooling Setpoint Select x
0 = Single set point (Default), 1 = Dual set point (switch controlled), 2 = Dual set point (clock controlled)
Heating Setpoint Select x
0 = Single set point (Default), 1 = Dual set point (switch controlled), 2 = Dual set point (clock controlled) CURRENTLY NOT SUPPORTED
See Legend on page 34.
31
Page 32
Table 19 — Service Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Options Configuration 2 (cont)
Ramp Load Select x
0 = Disabled, 1 = Enabled (Default) See page 8
Clock Control Select x
0 = No clock control (Default) 1 = Local clock control 65 = CCN Clock Control
Ice Configuration Selectx0 = Disabled (Default)
1 = Clock Control 2 = Demand Limit Control
OAT Sensor Select x
0 = Disabled, 1 = Enabled Default: 0
Remote Alarm Select x
0 = Disabled, 1 = Enabled Default: 0
Alarm Reset Select x
0 = Not selected, 1 = Selected (Default, allows use of LOR switch to reset alarms)
Close Control Select x
0 = Disabled, 1 = Enabled Default: 0. See page 7
Deadband Multiplier x.x
Default: 1.0
Current Unbalance AlarmxAlarm at 10% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
Voltage Unbalance AlarmxAlarm at 3% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
4 Reset Configuration Table
COOLING RESET TYPE1See Demand Limit section, page 39 Degrees Reset at 20 mA
xx.x dF
Default: 0
COOLING RESET TYPE 2
Remote temp=No Reset xx.x dF
Default: 20
Remote temp=Full Reset xx.x dF
Default: 125
Degrees Reset xx.x dF
Default: 0
COOLING RESET TYPE 3
CHW Delta T=No Reset xx.x dF
Default: 15
CHW Delta T=Full Reset xx.x dF
Default: 0
Degrees Reset xx.x dF
Default: 0 COOLING RESET Select/Enable Reset Typex0 = No Reset (Default),1=4-20 mA Reset,
2 = External Reset, 3 = Return Fluid Reset HEATING RESET TYPE1CURRENTLY NOT SUPPORTED
Degrees Reset at 20 mA xx.x dF
Default: 0 HEATING RESET TYPE2CURRENTLY NOT SUPPORTED Remote temp=No Reset
xx.x dF
Default: 125 Remote temp=Full Reset
xx.x dF
Default: 20 Degrees Reset
xx.x dF
Default: 0 HEATING RESET TYPE3CURRENTLY NOT SUPPORTED HTW Delta T=No Reset
xx.x dF
Default: 15 HTW Delta T=Full Reset
xx.x dF
Default: 0 Degrees Reset
xx.x dF
Default: 0 HEATING RESET Select/Enable Reset Typex0 = No Reset (Default), 1 = 4-20 mA reset,
2 = External reset, 3 = Return Fluid reset DEMAND LIMIT See Demand Limit section, page 39
Demand Limit at 20 mA xxx.x%
Enter 0-100, Default: 0%
32
Page 33
Table 19 — Service Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
4 Reset Configuration Table (cont)
Demand Limit Select x
0 = None (Default), 1 = Two step switch, 2 = 4-20 mA, 3 = CCN Loadshed
Loadshed Group Numberx0-99, Default: 0 Loadshed Demand Delta
xxx%
0-60%,Default: 0
Maximum Loadshed Time xx min
0-120 min, Default: 60 min WATER VALVE PID Proportional PID Gain
x.x
Default = 1.0
Adjustable from -20.0 to 20.0 Integral PID Gain
x.x
Default = 0.1
Adjustable from -20.0 to 20.0 Derivative PID Gain
x.x
Default = 0.0
Adjustable from -20.0 to 20.0 AIR MOTOR MASTER
PID Proportional PID Gain
x.x
Default = 1.0
Adjustable from -20.0 to 20.0 Integral PID Gain
x.x
Default = 0.1
Adjustable from -20.0 to 20.0 Derivative PID Gain
x.x
Default = 0.0
Adjustable from -20.0 to 20.0
5 Factory Configuration Codes
FACTORY CODES Configuration Code 1
xxxxxxxx
Factory set. See Table 22. Configuration Code 2
xxxxxxxx
Factory set. See Table 22. Configuration Code 3
xxxxxxxx
Factory set. See Table 22. SERVICE CODES Configuration Code 4
xxxxxxxx
Factory set. See Table 22. Configuration Code 5
xxxxxxxx
Factory set. See Table 22.
6 NOT USED 7 Transducer Calibration
CALIBRATION OFFSET See Pressure Transducer Calibration, page 59 CIRCUIT A PRESSURE Discharge Pressure
xxx.x PSI Suction Pressure
xxx.x PSI A1 Oil Pressure
xxx.x PSI A2 Oil Pressure
xxx.x PSI Economizer Pressure
xxx.x PSI CALIBRATION OFFSET
CIRCUIT B PRESSURE Discharge Pressure
xxx.x PSI Suction Pressure
xxx.x PSI B1 Oil Pressure
xxx.x PSI B2 Oil Pressure
xxx.x PSI Economizer Pressure
xxx.x PSI Calibrate All at 0 PSIG
No Last Calibration Date
mmm dd - yy
See Legend on page 34.
33
Page 34
Table 19 — Service Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
8 Manual Control Table
Manual Control Enable Dsable
LOR switch should be in OFF position
Password Protected Enter:
Will be displayed if not entered earlier in current HSIO use
Manual Control Enable Dsable
Manual Control Enable Enable
Switch LOR switch to Local before proceeding
Circuit A Compressor 1 Off
Circuit A Compressor 1 On
Provided no alarms exist, control will attempt circuit start within 2 minutes.
Press to stop circuit.
Circuit A Compressor 2 Off
to enable, to stop
Circuit A Loader 1 Off
to enable, to stop
Circuit A Loader 2 Off
to enable, to stop
Circuit A Min Load Valve Off
to enable, to stop
Circuit B Compressor 1 Off
to enable, to stop
Circuit B Compressor 2 Off
to enable, to stop
Circuit B Loader 1 Off
to enable, to stop
Circuit B Loader 2 Off
to enable, to stop
Circuit B Min Load Valve Off
to enable, to stop
9 Dual Chiller Configuration
MST SLV Master/Slave Select
0/1/2
0 = Disabled 1 = Master 2 = Slave
Slave Address 0
Default = 0 Adjustable from 0-236
Lead/Lag Balance 0/1
0 = Disabled 1 = Enabled
Lead/Lag Balance Delta xxx hours
Default = 168 Adjustable from 40-400
LEGEND
CCN — Carrier Comfort Network CHW — Chilled Water CPM — Compressor Protection Module HSIO — Standard Keypad HTW — Hot Water LOR — Local/Off/Remote MOP — Maximum Operating Pressure OAT — Outdoor-Air Temperature PID — Proportional Integral Derivative
34
Page 35
Table 20 — Displaying Current Software Version
FUNCTION
KEYPAD
ENTRY
DISPLAY COMMENT
Software Version
Software CESR_500100 Ver XXX
Carrier Software Part Number, where XXX is the revision number.
Table 21 — Compressor Lead/Lag Configuration
SUB-FUNCTION KEYPAD
ENTRY
DISPLAY
Options Configuration 1
Cooler Fluid Select 1
Min. Load Valve Select Dsable
Loading Sequence Select 1
Lead/Lag Sequence Select 1
PASSWD PROTECTED FUNC Enter Password:
Lead/Lag Sequence Select 0
Lead/Lag Sequence Select 2
NOTE: Configurationsmay be modified afterentering the password.Thepassword is only required to be entered once. After a period of 10 minutes of no HSIO activity, the user is automatically logged out and the control requires that the password be entered on the next use.
35
Page 36
Table 22 — Factory and Service Configuration Code Values
UNIT MODEL NUMBER CONF. CODE 1* CONF. CODE 2 CONF. CODE 3 CONF. CODE 4 CONF. CODE 5
30GX080 11460010 13900000 00000170 15400521 12000093 30GX090,105 11560010 13900000 00000180 15400521 12000093 30GX106 11560010 13900000 00000180 15400521 14000095 30GX115 11660010 13900000 00000190 15400521 14000095 30GX125 11660010 14600000 00000161 15400521 14000095 30GX136 11660010 15600000 00000162 15400521 14000095 30GX150 11560010 18000000 00000095 15400521 16000097 30GX151 11800010 15600000 00000176 15400521 07000088 30GX160 11660010 18000000 00000105 15400521 16000097 30GX161 11800010 16600000 00000177 15400521 07000088 30GX175 11800010 18000000 00000119 15400521 07000088 30GX176 11800010 18000000 00000119 15400521 03000084 30GX205 12663910 18000000 00000145 15400521 07000088 30GX206 12803910 16600000 00000217 15400521 09000090 30GX225 12804610 18000000 00000166 15400521 07000088 30GX226 12804610 18000000 00000166 15400521 09000090 30GX250 12806610 18000000 00000186 15400521 09000090 30GX251 12808010 16600000 00000258 15400521 05000086 30GX265 12808010 18000000 00000200 15400521 05000086
30HXA076 31390010 13900000 00000183 15200521 02000063 30HXA086 31460010 13900000 00000190 15200521 02000063 30HXA096 31560010 13900000 00000200 15200521 02000063 30HXA106 31660010 13900000 00000210 15200521 02000063 30HXA116 31660010 14600000 00000181 15200521 02000063 30HXA126 31660010 15600000 00000182 15200521 02000063 30HXA136 31800010 15600000 00000196 15200521 02000063 30HXA146 31800010 16600000 00000197 15200521 02000063 30HXA161 31800010 15600000 00000196 15200521 02000063 30HXA171 31660010 18000000 00000125 15200521 02000063 30HXA186 31800010 18000000 00000139 15200521 02000063 30HXA206 32663910 18000000 00000165 15200521 02000063 30HXA246 32805610 18000000 00000196 15200521 02000063 30HXA261 32806610 18000000 00000206 15200521 02000063 30HXA271 32808010 18000000 00000220 15200521 02000063
30HXC076 21390010 13900000 00000173 12200521 00000058 30HXC086 21460010 13900000 00000180 12200521 00000058 30HXC096 21560010 13900000 00000190 12200521 00000058 30HXC106 21660010 13900000 00000200 12200521 00000058 30HXC116 21660010 14600000 00000171 12200521 00000058 30HXC126 21660010 15600000 00000172 12200521 00000058 30HXC136 21800010 15600000 00000186 12200521 00000058 30HXC146 21800010 16600000 00000187 12200521 00000058 30HXC161 21800010 15600000 00000186 12200521 00000058 30HXC171 21660010 18000000 00000115 12200521 00000058 30HXC186 21800010 18000000 00000129 12200521 00000058 30HXC206 22663910 18000000 00000155 12200521 00000058 30HXC246 22805610 18000000 00000186 12200521 00000058 30HXC261 22806610 18000000 00000196 12200521 00000058 30HXC271 22808010 18000000 00000210 12200521 00000058
*Unit Type will be listed as air cooled, water cooled, or remote split system. Unit type is first digit in
Configuration Code1andis 1 for 30GX units,2for 30HXC units, and 3for30HXA cooling onlychillers. For other options, see Table 19 under the Service subfunction. A label listing configuration codes is located on the control box door or panel.
36
Page 37
Table 23 — Entering Configuration Codes
KEYPAD ENTRY DISPLAY RESPONSE
FACTORY CODES Configuration Code 1
00000000 Configuration Code 1
21660010 Configuration Code 2
00000000 Configuration Code 2
13900000 Configuration Code 3
00000000 Configuration Code 3
00000200 SERVICE CODES
Configuration Code 4 00000000
Configuration Code 4 12200521
Configuration Code 5 00000000
Configuration Code 5 00000058
SCHEDULE FUNCTION — This function provides a means to automatically switch the chiller from an occupied mode to an unoccupied mode. Refer to Table 24 for a complete description of the function.
The schedules consist of 8 user-configurable occupied time periods. The control supports time schedules for local con­trol, remote control and ice building. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The ma­chine is in unoccupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, it must be programmed in the following manner: occupied period must end at 24:00 hours (midnight); a new occupied period must be programmed to begin at 00:00 hours.
NOTE: This is true only if the occupied period starts at 00:00 (midnight). If the occupied period starts at a time other than midnight, then the occupied period must end at 24:00 hours (midnight) and new occupied period must be programmed to start at 00:00 in order for the chiller to stay in the occu­pied mode past midnight. Each time schedule can be over­ridden to keep the chiller in an Occupied mode for 1, 2, 3 or 4 hours on a one-time basis.
Dual Set Point Control — This feature can be enabled to allow the use of a second or unoccupied cooling set point. The function can be either switch controlled or clock con­trolled. To enable switch control, set the Cooling Setpoint
selection under to 1. See page 72 or 73 of Field Wiringsection, depending on unit type, for switch input wir-
ing to the PSIO-2 module. Configure Cool Setpoint 2 under
to the desired value. The unit will then control leav-
ing water temperature to Cool Setpoint 2 when the switch input is closed. To enable clock control, set the Cooling
Setpoint selection under to 2. Set Cool Setpoint 2 to the desired unoccupied value. Using , configure lo-
cal operating schedules for the desired occupied and unoc­cupied time periods. The unit will then control leaving water temperature to Cool Setpoint 2 during unoccupied time periods.
37
Page 38
Table 24 — Schedule Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Ice Build Schedule*
SCHEDULES: OCCPC01S Timed Override: 00
Extended Occupied Time
SCHEDULES: OCCPC01S Timed Override: 02
Two hour override entered
MTWTFSSH OCC UNOCC 01- 00000000 00:00 00:00
Displays current stored schedule (First 2 numbers are schedule, 01-08)
MTWTFSSH OCC UNOCC 01- 11111000 00:00 00:00
Monday-Friday now occupied
MTWTFSSH OCC UNOCC 01- 11111000 21:00 00:00
Occupied time now set
MTWTFSSH OCC UNOCC 01- 11111000 21:00 06:30
Unoccupied time now set Ice Build schedule completed
MTWTFSSH OCC UNOCC 02- 00000000 00:00 00:00
Can enter up to 7 additional ice build schedules
2 Local Schedule†
SCHEDULES: OCCPC02S Timed Override: 00
Extended Occupied Time
MTWTFSSH OCC UNOCC 01- 00000000 00:00 00:00
Displays current stored schedule (First 2 numbers are schedule, 01-08)
MTWTFSSH OCC UNOCC 01- 11111000 00:00 00:00
Monday-Friday now occupied
MTWTFSSH OCC UNOCC 01- 11111000 06:30 00:00
Occupied time now set
MTWTFSSH OCC UNOCC 01- 11111000 06:30 21:00
Unoccupied time now set Local schedule completed
MTWTFSSH OCC UNOCC 02- 00000000 00:00 00:00
Can enter up to 7 additional local schedules
3 Remote Schedule (Currently Not Used)
SCHEDULES: OCCPC65S Timed Override: 00
Extended Occupied Time
MTWTFSSH OCC UNOCC 01- 00000000 00:00 00:00
Displays current stored schedule (First 2 numbers are schedule, 01-08)
MTWTFSSH OCC UNOCC 01- 11111000 00:00 00:00
Monday-Friday now occupied
MTWTFSSH OCC UNOCC 01- 11111000 06:30 00:00
Occupied time now set
MTWTFSSH OCC UNOCC 01- 11111000 06:30 21:00
Unoccupied time now set Remote schedule completed
MTWTFSSH OCC UNOCC 02- 00000000 00:00 00:00
Can enter up to 7 additional remote schedules
4 Holiday Configuration**
HOLIDAYS : HOLDY_01 Starts on 00/00 00 days
Can configure holiday start day and duration
HOLIDAYS : HOLDY_01 Starts on 12/23 00 days
Start of holiday set
HOLIDAYS : HOLDY_01 Starts on 12/23 10 days
Holiday duration set
5-33 Holiday Configuration
through
HOLIDAYS : HOLDY_02 Starts on 00/00 00 days
Allows configuration of 29 additional holiday periods
*Ice configuration select must be set to 1 for clock control. The ice configuration can be accessed by pressing and scrolling down.
†Clock control select must be set to 1 for clock control. The clock control can be accessed by pressing and scrolling down. **The BROADCAST function (BRODEFS table) must be activated (change to 9YES9 and download) when using the LID-2B controller, Building
Supervisor or ComfortWorks™ software for the control to recognize holidays.
38
Page 39
Temperature Reset — The control system is capable
of providing leaving fluid temperature reset based on return fluid temperature. Because the temperature difference be­tween leaving and return temperature is a measure of the building load, return fluid temperature reset is essentially an average building load reset method.
Under normal operation, the chiller maintains a constant leaving fluid temperature approximately equal to the chilled fluid set point. As building load drops from 100% down to 0%, entering cooler fluid temperature drops in proportion to load. Thus, the temperature drop across the cooler drops from a typical 10° F (5.5° C) at full load to a theoretical 0° F (0° C) at no load. See Fig. 8.
At partial load, leaving chilled fluid temperature may be lower than required. If this is allowed to increase (reset), the efficiency of the chiller increases. Amount of reset can be defined as a function of cooler temperature drop. This is a simple linear function that requires 3 pieces of input data for the set function that will vary depending on measurement method used. See the following sections and Table 25.
NOTE: Reset set points are not accessible unless the reset function is enabled first. The Control Point will be recalcu­lated taking into account the set point plus the amount of reset. This is done as a field configuration. Select one of the 3 choices for type of reset: Return Fluid Reset, External Tem­perature Reset, or 4 to 20 mA Signal Reset. See Table 25.
If dual set point control is enabled, the amount of reset is applied to whichever set point is in effect at the time.
Tables 26-28 demonstrate how to activate reset. EXTERNAL TEMPERATURE RESET — In this example,
the unit set point is reset from full load at 90 F (32 C) to a maximum reset value of 10° F (5.5° C) at 25 F (−6.7 C) outdoor ambient. This means that if the chilled fluid set point is 44 F (6.7 C), there is no reset if the temperature is 90 F (32 C). At a temperature of 25 F (−6.7 C), the chilled fluid set point would be reset to 54 F (12.2 C). See Fig. 8 and T able26.Afield-suppliedoutdoorairthermistormustbecon­nected to PSIO-2 as shown in Fig. 37.
To activate this function for space temperature reset leave both the External Reset Sensor Select and the OAT Sensor Select at 0, and change the Select/Enable Reset Type to 2, following the procedure in Table 26.
EXTERNALLY POWERED RESET (4 to 20 mA) — In this example, the unit set point is reset from full load at 4 mA to a maximum reset value of 10° F (5.5° C) at 20 mA. See Fig. 9 and Table 27.
RETURN FLUID TEMPERATURE RESET — In this ex­ample, the unit set point is reset from full load based on the chilled fluid return temperature. The example uses a reset value of 10 degrees at full reset. Full reset is at a 2-degree temperature difference across the cooler and no reset would be at a 10° F difference across the cooler. See Fig. 10 and Table 28.
Demand Limit — Demand Limit is a feature that allows
the unit capacity to be limited during periods of peak energy usage. There are 3 types of demand limiting which can be configured. The first type is through 2 switch inputs, which will reduce the maximum capacity to 2 user-configurable per­centages. The second type is bya4to20mAsignal input which will reduce the maximum capacity linearly between 100% ata4mAinput signal (no reduction) down to the user­configurable level at a 20 mA input signal. The third type uses the CCN Loadshed module and has the ability to limit the current operating capacity to maximum and further re­duce the capacity if required.
To use Demand Limit, select the type of demand limiting to use. Then configure the Demand Limit set points based on the type selected.
DEMAND LIMIT (Switch Controlled, 30GX only) — In this example, demand limit by switch control will be configured and the switch set points will be set at 75% and 40%. Ca­pacity steps are controlled by 2 relay switch inputs field wired to PSIO-2, terminal 28 for switch 1 and terminal 25 for switch
2. See Table 29.
For Demand Limit by switch control, closing the first stage demand limit contact will put the unit on the first demand limit level. The unit will not exceed the percentage of ca­pacity entered as Demand Switch 1 set point. Closing con­tacts on the second demand limit switch prevents the unit from exceeding the capacity entered as Demand Switch 2 set point. The demand limit stage that is set to the lowest demand takes priority if both demand limit inputs are closed. If the demand limit percentage does not match unit staging, the unit will limit capacity to the closest capacity stage.
To Disable Demand Limit: Enter as shown in Table 29. Scroll down to Demand Limit Select and press
to select no Demand Limit control.
Table 25 — Temperature Reset Set Point Limits
INPUT DATA DESCRIPTION
MEASUREMENT METHOD
Type 1 — 4-20 mA
(With 500-Ohm Resistor)
Type2—OAT/Occupied Space
(External Sensor)
Type 3 — Return Fluid
Variable Limits Variable Limits Variable Limits
Maximum Reset Amount — Allowable range for maximum amount which LWT set point is reset.
Degrees Reset at 20 mA
(−30 to 30 F)
−34 to −1 C
Degrees Reset (−30 to 30 F)
−34 to −1 C
Degrees Reset (−30 to 30 F)
−34 to −1 C
Maximum Reset Reference — Temperature at which maximum reset occurs.
— — Remote temp =
Full Reset
(20 to 125 F)
−7 to 52 C
CHW Delta T = Full Reset
(0 to 15 degrees F) 0to8°C cooler temperature rise
Minimum Reset Reference — Temperature at which no reset occurs.
— — Remote temp =
No Reset
(20 to 125 F)
−7 to 52 C
CHW Delta T = No Reset
(0 to 15 degrees F) 0to8°C cooler temperature rise
LEGEND
CHW — Chilled Water OAT — Outdoor-Air Temperature LWT — Leaving Fluid Temperature
39
Page 40
-18 (0) -12 (10) -7 (20) -1 (30) 4 (40) 10 (50) 16 (60)
21 (70) 27 (80)
32 (90)
38(100)
RESET REFERENCE TEMPERATURE-OUTDOOR AIR OR SPACE TEMPERATURE THERMISTOR C (F)
100
80
60
40
20
0
0.0 (0)
1.1 (2)
2.2 (4)
3.3 (6)
4.4 (8)
5.5 (10)
6.7 (12)
RESET AMOUNT C (F)
RESET AMOUNT
BUILDING LOAD
PERCENT BUILDING LOAD
Fig. 8 — Cooling External Temperature Reset
0 (0)
2 (1)
4 (2)
6 (3)
8 (4)
10 (5)
12 (6)
14 (7)
16 (8)
18 (9)
20 (10)
RESET REFERENCE – 4-20 mA SIGNAL INPUT (VOLTS DC)
0 (0)
1.1 (2)
2.2 (4)
3.3 (6)
4.4 (8)
5.5 (10)
6.7 (12)
RESET AMOUNT C (F)
Fig.9—4to20mACooling Temperature Reset
Fig. 10 — Cooling Return Water Reset
40
Page 41
Table 26 — Setting External Temperature Reset
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
Cooler Fluid Select 1
Min. Load Valve Select Disable
Loading Sequence Select 1
Lead/Lag Sequence Select 1
Head Press. Control Type 0
Motormaster Select 0
Water Valve Type 0
Ext. Reset Sensor Select 0
Ext. Reset Sensor Select1Outdoor Ambient
sensor selected for reset
Cooling Setpoint Select 0
Heating Setpoint Select 0
Ramp Load Select 0
Clock Control Select 1
Ice Configuration Select 0
OAT Sensor Select 0
OAT Sensor Select 1
OAT sensor enabled
COOLING RESET TYPE 1
Degrees Reset at 20 mA
0.0 dF COOLING RESET TYPE
2 Remote temp = No Reset
20.0 dF Remote temp = No Reset
25.0 dF Remote temp = Full Reset
125.0 dF Remote temp = Full Reset
90.0 dF Degrees Reset
0.0 dF Degrees Reset
10.0 dF COOLING RESET Scroll down
to this point.
Select/Enable Reset Type 0
Select/Enable Reset Type2External reset
selected
Table 27 — Setting Externally Powered Reset
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COOLING RESET TYPE 1
Degrees Reset at 20 mA
0.0 dF Degrees Reset at 20 mA
10.0 dF COOLING RESET Scroll down to
this point
Select/Enable Reset Type 0
Select/Enable Reset Type14-20 mA reset
selected
Table 28 — Setting Return Fluid
Temperature Reset
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COOLING RESET TYPE 1
COOLING RESET TYPE3Scroll down
to this point.
CHW Delta T = No Reset
15.0 dF CHW Delta T = No Reset
10.0 dF CHW Delta T = Full Reset
0.0 dF CHW Delta T = Full Reset
2.0 dF Degrees Reset
0.0 dF Degrees Reset
10.0 dF COOLING RESET
Select/Enable Reset Type 0
Select/Enable Reset Type3Return Fluid reset
selected
41
Page 42
EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled) — In this example, the 4 to 20 mADemandLimit will be configured and the 20 mA demand limit percentage will be set to 50%. See Table 30 and Fig. 11.
DEMAND LIMIT (CCN Loadshed Controlled) — In this example, the CCN Loadshed Demand Limit will be config­ured. The loadshed group will be set to 1, demand delta will be set to 40% and the maximum loadshed time will be set to 90 minutes. See Table 31.
The Loadshed Group number is established by the CCN system designer. The PIC (product integrated control) will respond to a Redline command from the Loadshed control. When the Redline command is received, the current stage of capacity is set to the maximum stages available. Should the loadshed control send a Loadshed command, the PIC will reduce the current stages by the value entered for Loadshed Demand delta. For the above example the Loadshed De­mand delta is 40%. If the chiller is operating at 80% of total capacity when a Redline command is received, the maxi­mum available capacity is set to 80%. WhenaLoadshedcom­mand is received, the chiller capacity will be reduced by 40%. The chiller can now operate at a total capacity of no more than 48% [80% − (80% x 40%)] until a Cancel Redline or Cancel Loadshed command is received. The control will dis­able the Redline/Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit.
Table 29 — Setting Switch-Controlled Demand Limit
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COOLING RESET TYPE 1
DEMAND LIMIT Scroll down to this
point
Demand Limit at 20 mA
0.0% Demand Limit Select
0 Demand Limit Select
1
Two step switch configured
COOLING DEMAND LIMIT Scroll down to this
point
Demand Switch 1 Setpoint
80.0% Demand Switch 1 Setpoint
75.0 Demand Switch 2 Setpoint
50.0% Demand Switch 2 Setpoint
40.0%
Configuration complete
Table 30 — Setting Demand Limit
(4 to 20 mA Controlled;
2 to 10 vdc With 500-Ohm Resistor)
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COOLING RESET TYPE 1
DEMAND LIMIT Scroll down to this
point
Demand Limit at 20 mA
0.0% Demand Limit at 20 mA
50.0% Demand Limit Select
0 Demand Limit Select
2
4-20 mA control configured
Table 31 — Setting Demand Limit
(CCN Loadshed Controlled)
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COOLING RESET TYPE 1
DEMAND LIMIT Scroll down to
this point
Demand Limit at 20 mA
0.0% Demand Limit Select
0 Demand Limit Select
3
CCN Loadshed control configured
Loadshed Group Number 0
Loadshed Group Number 1
Loadshed Demand Delta 0
Loadshed Demand Delta 40%
Maximum Loadshed Time 60 min
Maximum Loadshed Time 90 min
Configuration complete
50% CAPACITY AT 20 mA
75% CAPACITY AT 12 mA
100% CAPACITY AT 4 mA
0 (0)
2 (1)
4 (2)
6 (3)
8 (4)
10 (5)
12 (6)
14 (7)
16 (8) 18 (9)
20 (10)
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT (VOLTS DC)
100
80
60
40
20
0
MAX. ALLOWABLE LOAD (%)
Fig. 11—4to20mADemand Limiting
42
Page 43
TROUBLESHOOTING
The 30GX,HX screw chiller control has many features to aid in troubleshooting. By using the keypad and display mod­ule and the Status function, operating conditions of the chiller are displayed while the unit is running. The Test function allows for operational checkout of compressor loaders, fans, EXVs, solenoids, and other components while the chiller is stopped. TheServicefunctiondisplayshowconfigurable items are configured and provides a manual control mode where the compressors can be started and loaded. If an operating fault is detected, an alarm is generated and an alarm code
is displayed under the subfunction along with an explanation of the fault. Up to 10 current alarm codes are
stored under this subfunction. For checking specific items, see Table 10.
Checking Display Codes — To determine how the
machine has been programmed to operate, check the diag­nostic information displayed in the Status function and the configuration information displayed in the Service function.
Unit Shutoff — To shut the unit off, move the LOCAL/
OFF/REMOTE switch to OFF position. All compressors and solenoids stop immediately.
Complete Unit Stoppage — Complete unit stoppage
can be caused by any of the following conditions:
• cooling load satisfied
• remote on/off contacts open
• programmed schedule
• emergency stop command from CCN
• general power failure
• blown fuse in control power feed disconnect
• open control circuit fuse(s)
• LOCAL/OFF/REMOTE switch moved to OFF position
• freeze protection trip
• low flow protection trip
• open contacts in chilled water flow switch (optional)
• Open contacts in any auxiliary interlock. Terminals that
are jumpered from factory are in series with control switch. Opening the circuit between these terminals places unit in Stop mode, similar to moving the control switch to OFF position. Unit cannot start if these contacts are open. If they open while unit is running, the unit stops
• cooler entering or leaving fluid thermistor failure
• low/high transducer supply voltage
• loss of communications between processor module and other
control modules
• low refrigerant pressure
• off-to-on delay is in effect
If a stoppage occurs more than once as a result of any of the above safety devices, determine and correct the cause before attempting another restart.
Single Circuit Stoppage — Single circuit stoppage
can be caused by the following:
• low oil pressure
• open contacts in high pressure switch
• low refrigerant pressure
• thermistor failure
• transducer failure
• alarm condition from CPM module
• Overload relay trip. Stoppage of one circuit by a safety
device action does not affect other circuit. When a safety device trips, the circuit is shut down immediately and EXV closes
If a stoppage occurs more than once as a result of any of the preceding safety devices, determine and correct the cause before attempting another restart.
Restart Procedure — After the cause for stoppage has
been corrected, restart is either automatic or manual, de­pending on the fault. Manual reset requires that the alarm(s)
be reset via the HSIO. Press and then to clear manual reset alarms. If the Alarm Reset Select feature
is selected ( ), a manual reset alarm can also be reset by switching the LOR switchfromLOCAL/REMOTEtoOFF
and back to LOCAL/REMOTE again. If an alarm was from the CPM module, depress theresetbuttonlocatedontheHSIO or fuse bracket before clearing the alarm through the HSIO. Some typical fault conditions are described in Table 32. For a complete list of fault conditions, codes, and reset type, see Table 33.
POWER FAILURE EXTERNAL TO THE UNIT — Unit restarts automatically when power is restored.
Table 32 — Typical Stoppage Faults
and Reset Types
STOPPAGE FAULT RESET TYPE
Loss of Condenser Flow (30HXC) Manual reset Cooler Freeze Protection
(Chilled Fluid, Low Temperature)
Auto reset first time, manual if repeated in same day
Chilled Fluid Pump Interlock Automatic reset (Manual for
closed contacts when pump is off)
Control Circuit Fuse Blown Unit restarts automatically when
power is restored
High-Pressure Switch Open Manual reset Low Sat. Suction Temperature Manual reset Low Oil Pressure Manual reset Loss of Communications with
WSM or FSM controller
Automatic reset
LEGEND
FSM — Flotronic™ System Manager WSM — Water System Manager
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described in Table 33. The alarm descriptions are displayed
on the HSIO when the subfunction is entered. When a communication loss occurs to a hardware point, an alert or
alarm may be generated. Refer to Table 34. The PSIO also recognizes illegal configurations. Illegal configurations are shown in Table 35.
Table 33 contains a detailed description of each alarm and
alert code error and possible cause. Manual reset is accomplished by entering from the HSIO and press-
ing or moving the LOCAL/OFF/REMOTE Switch to the OFF position, then back to LOCAL or REMOTE po-
sition (If Alarm Reset Select is enabled).
CompressorAlarm/AlertCircuit — Each compres-
sor is controlled by its own CPM processor, which closes contacts between plug terminals PL2-3 and PL2-6 to start the compressor. Power is supplied to the CPM logic circuit through each compressor high-pressure switch and into plug terminal PL2-2. If the high-pressure switch opens, the CPM generates an alarm.
NOTE: Similar connections for each compressor can be fol­lowed on the unit wiring diagrams located on the unit.
43
Page 44
Table 33 — Alarm and Alert Codes
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
0 — No Alarms or Alerts
Exist
— ———
1.xx See CPM subcodes below
Compressor A1 Failure See CPM subcodes
below
See CPM subcodes below
Manual See CPM subcodes
below
2.xx See CPM subcodes below
Compressor A2 Failure See CPM subcodes
below
See CPM subcodes below
Manual See CPM subcodes
below
5.xx See CPM subcodes below
Compressor B1 Failure See CPM subcodes
below
See CPM subcodes below
Manual See CPM subcodes
below
6.xx See CPM subcodes below
Compressor B2 Failure See CPM subcodes
below
See CPM subcodes below
Manual See CPM subcodes
below
CPM SUBCODES
(xx)
x.0 — No Error — — — — x.1 Alarm High Pressure Switch
Trip
HPS input to CPM module open
Comp. shut down Manual/Button Loss of condenser air/
water flow. Operation beyond chiller capability. Liquid valve not open.
x.2 Alarm No Motor Current CPM reads less than
10% of MTA on all legs for >3 seconds
Comp. shut down Manual/Button Power supply discon-
nected, blown fuse(s), wiring error, contactor not energized, faulty current toroid, motor overload tripped
x.25* Alarm Current Imbalance
>10% (Alarm)
CPM measures current balance between phases greater than 10% for 25 minutes
Circuit shut down Manual/Button Loose terminals on
power wires. Poor power supply. Disabled only if alarm feature is
enabled in
x.27* Alert Current Imbalance
>10% (Warning)
CPM measures current balance between phases greater than 10% for 25 minutes
None — Loose terminals on
power wires. Poor power supply. Displayed only if alarm feature is
disabled in
x.3 Alarm Current Imbalance
>18%
CPM measures current balance between phases greater than 18% for 25 minutes
Circuit shut down Manual/Button Loose terminals on
power wires. Poor power supply.
x.35 Alarm Single Phase Current
Loss
CPM measures current imbalance between phases greater than 20%
Circuit shut down Manual/Button Blown fuse, wiring error,
loose terminals.
x.4 Alarm High Motor Current CPM detects high cur-
rent compared to MTA setting
Comp. shut down Manual/Button Operation beyond chiller
capability, improperly punched configuration header, blown fuse
x.5 Alarm Ground Fault CPM detects ground
current (2.5 ± 2.0 amps)
Comp. shut down Manual/Button Motor winding(s) gone
to ground, wiring error, loose plug connector, current toroid plugs not facing same direction.
x.55* Alarm Voltage Imbalance >3%
(Alarm)
CPM measures voltage imbalance between phases greater than 3% for 25 minutes
Circuit shut down Manual/Button Compressor fault, local
utility supply imbalance, Poor power supply. Dis­played only if alarm fea­ture is enabled in
x.57* Alert Voltage Imbalance >3%
(Warning)
CPM measures voltage imbalance between phases greater than 3% for 25 minutes
None — Compressor fault, local
utility supply imbalance. Displayed only if alarm feature is disabled in
x.6 Alarm Voltage Imbalance >7% CPM measures voltage
imbalance between phases greater than 7% for 25 minutes
Circuit shut down Manual/Button Compressor fault, local
utility supply imbalance
x.7 Alarm Volt Phase Reversal CPM detects incoming
power supply out of phase
Chiller shut down and not allowed to start
Manual/Button Leads at CPM board
not connected. Supply power not in phase; interchange any 2 incoming leads.
x.75 Alarm Contactor Failure CPM detects min. 10%
of MTA for 10 seconds after shutting off com­pressor contactor. Oil solenoid is energized.
All remaining compres­sors shut down. All loaders deenergized. Min. load valve of af­fected circuit energized (if equipped)
Manual/Button Faulty contactor, con-
tactor welded, wiring error.
x.8 Alarm Current Phase Reversal CPM detects phase re-
versal from toroid reading
Circuit shut down Manual/Button Multiple terminal block
power supply leads not in phase. Toroid wire harness crossed, toroid not all facing same direction
44
Page 45
Table 33 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
CPM SUBCODES
(xx)
x.85 Alarm Motor Over Temperature CPM detects high motor
temperature
Comp. shut down Manual/Button Motor cooling (all) or
Economizer (2 comp. circuits) solenoid failure, low refrigerant charge.
x.9 Alarm Open Thermistor CPM detects open
circuit in motor temp thermistor
Comp. shut down Manual/Button Wiring error or faulty
thermistor.†
x.95 Alarm Config. Header Fault CPM finds error with
MTAvalue punched out in header
Comp. shut down Manual/Button Header pins on CPM
board either all or none punched out, header not fully seated in CPM board.
x.10 Alarm Shorted Thermistor CPM detects short
circuit in motor tempt thermistor
Comp. shut down Manual/Button Wiring error or faulty
thermistor.†
ALARM/ALERT
CODE
7 Alert Cir. A Discharge Gas
Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C) or DGT >210 F (98.9 C)
Circuit A shut down Manual Thermistor failure, motor
cooling solenoid failure or wiring error.
8 Alert Cir. B Discharge Gas
Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C) or DGT >210 F (98.9 C)
Circuit B shut down Manual Thermistor failure, motor
cooling solenoid failure or wiring error.
9 Alarm Cooler Leaving Fluid
Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Chiller shut down. Automatic Thermistor failure, dam-
aged cable/wire or wir­ing error.
10 Alarm Cooler Entering Fluid
Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C).
Uses 0.1° F/% Total Ca­pacity as rise/ton.
Automatic Thermistor failure, dam-
aged cable/wire or wir­ing error.
11 Alert Condenser Leaving
Fluid Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C)
None. Chiller continues to run.
Automatic Thermistor failure, dam-
aged cable/wire or wir­ing error.
12 Alert Condenser Entering
Fluid Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C)
None. Chiller continues to run.
Automatic Thermistor failure, dam-
aged cable/wire or wir­ing error.
15 Alert Compressor A1 High
Motor Temperature
Thermistor outside range of −39.9 to 245 F (−39.9 to 118 C) for 5 consecutive readings
Compressor A1 shut down
Manual Thermistor failure, motor
cooling (all) or Econo­mizer (2 comp. circuits) solenoid failure.
16 Alert Compressor A2 High
Motor Temperature
Thermistor outside range of −39.9 to 245 F (−39.9 to 118 C) for 5 consecutive readings
Compressor A2 shut down
Manual Thermistor failure, motor
cooling (all) or Econo­mizer (2 comp. circuits) solenoid failure.
17 Alert Compressor B1 High
Motor Temperature
Thermistor outside range of −39.9 to 245 F (−39.9 to 118 C) for 5 consecutive readings
Compressor B1 shut down
Manual Thermistor failure, motor
cooling (all) or Econo­mizer (2 comp. circuits) solenoid failure.
18 Alert Compressor B2 High
Motor Temperature
Thermistor outside range of −39.9 to 245 F (−39.9 to 118 C) for 5 consecutive readings
Compressor B2 shut down
Manual Thermistor failure, motor
cooling (all) or Econo­mizer (2 comp. circuits) solenoid failure.
21 Alert External Reset Tem-
perature Thermistor Failure
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Reset disabled. Runs under normal control/ set points.
Automatic Thermistor failure or
wiring error.
22 Alert Circuit ADischarge
Pressure Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit A shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
23 Alert Circuit B Discharge
Pressure Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit B shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
24 Alert Circuit ASuction Pres-
sure Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit A shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
25 Alert Circuit B Suction Pres-
sure Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit B shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
26 Alert Comp A1 Oil Pressure
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Comp A1 shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
27 Alert Comp A2 Oil Pressure
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Comp A2 shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
45
Page 46
Table 33 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
28 Alert Comp B1 Oil Pressure
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Comp B1 shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
29 Alert Comp B2 Oil Pressure
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Comp B2 shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
30 Alert Circuit A Economizer
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit A shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
31 Alert Circuit B Economizer
Transducer Failure
Calibration offset more than 6 PSIG or Voltage ratio (volts read/ref. volt­age) more than 99.9% or less than 0.5%.
Circuit B shut down Automatic Transducer failure,
power supply failure or wiring damage/error.
32 Alarm Transducer Supply Out-
side 4.5 to 5.5 Volts
Reference voltage mea­sured at PSIO-1, J7-34,35 less than 4.5 V or greater than 5.5 V.
Chiller shut down Automatic Power supply failure or
wiring error. Low trans­former voltage.
34 Alert 4-20 mA Reset Input
Out of Range
If configured and input signal to PSIO-2, J7-19,20(HX), J7-22,23(GX) less than 2 mA or greater than 20 mA
Reset function disabled. Normal set point used
Automatic Faulty signal generator,
wiring error, 500 ohm resistor missing or not properly installed.
35 Alert 4-20 mA Demand Limit
Input Out of Range
If configured and input signal to PSIO-2, J7-22,23(HX), J7-13,14(GX) less than 2 mA or greater than 20 mA
Demand limit ignored. Runs under normal con­trol based on 100% de­mand limit.
Automatic Faulty signal generator,
wiring error, 500 ohm resistor missing or not properly installed.
36 Alarm Loss of Communication
with ‘‘Hardware Point’’
PSIO-1 has lost com­munication with one of the points in Table 34.
See Table 34. Automatic Failed module, wiring
error, failed transformer, loose connection plug, wrong address
37 Alert Circuit A Low Saturated
Suction Temperature
SST reads 6 F (3.3 C) or more below the freeze point for 3 min­utes. Point is 28 F (−2.2 C) for water, set point minus 8 F (4.4 C) for brines.
Circuit A shut down Manual Low refrigerant charge,
plugged strainer, faulty expansion valve. Low water flow.
38 Alert Circuit B Low Saturated
Suction Temperature
SST reads 6 F (3.3 C) or more below the freeze point for 3 min­utes. Point is 30 F (−1.1 C) for water, cool­ing set point minus 8 F (4.4 C) for brines.
Circuit B shut down Manual Low refrigerant charge,
plugged strainer, faulty expansion valve. Low water flow.
40 Alert Compressor A1 Low Oil
Pressure
See Note 1. Comp A1 shut down Manual Low Water Temperature,
low refrigerant charge, plugged oil filter, closed oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer.
41 Alert Compressor A2 Low Oil
Pressure
See Note 1. Comp A2 shut down Manual Low Water Temperature,
low refrigerant charge, plugged oil filter, closed oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
42 Alert Compressor B1 Low Oil
Pressure
See Note 1. Comp B1 shut down Manual Low Water Temperature,
low refrigerant charge, plugged oil filter, closed oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
43 Alert Compressor B2 Low Oil
Pressure
See Note 1. Comp B2 shut down Manual Low Water Temperature,
low refrigerant charge, plugged oil filter, closed oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
44 Alarm Circuit A Condenser
Freeze Protection (alarm ignored for brine chillers)
For W/C chillers only, if SCT <34 F (1.1 C)
Chiller shut down. Turn Cond pump On if Chiller is Off
Automatic Failed/bad discharge
pressure transducer, refrigerant leak, configured for water­cooled condenser
46
Page 47
Table 33 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
45 Alarm Circuit B Condenser
Freeze Protection (alarm ignored for brine chillers)
For W/C chillers only , if SCT <34 F (1.1 C)
Chiller shut down. Turn Cond pump On if Chiller is Off
Automatic Failed/bad discharge
pressure transducer, refrigerant leak, configured for water­cooled condenser
46 Alarm Cooler Freeze Protec-
tion
Cooler EWT or LWT less than freeze point. Freeze point is 34 F (1.1 C) for water, cool­ing set point minus 8 F (4.4 C) for brines.
Chiller shut down. Leave Cooler pump on. Turn Cooler pump On if Chiller is Off.
Automatic** Faulty thermistor, low
water flow
47 Alert Circuit A High Saturated
Suction Temperature
After first 90 seconds, SST > 55 F (12.8 C) and EXV < 1% for 5 minutes
Circuit A shut down Manual Faulty expansion valve,
liquid level sensor or transducer.
48 Alert Circuit B High Saturated
Suction Temperature
After first 90 seconds, SST > 55 F (12.8 C) and EXV < 1% for 5 minutes
Circuit B shut down Manual Faulty expansion valve,
liquid level sensor or transducer.
49 Alarm Loss of Condenser Flow Flow switch not closed
within 1 minute after pump is started or if flow switch opens dur­ing normal operation for >10 seconds
Chiller shut down Manual Low condenser water
flow, failed condenser pump
50 Alarm Illegal Configuration x Illegal Configuration has
been entered. Correc­tion needed.
Chiller cannot start. See Table 35.
Manual Configuration error.
51 Alarm Initial Configuration
Required
No configuration has been entered.
Chiller cannot start Manual Configuration omitted.
52 Alarm Unit is in Emergency
Stop
CCN command received to shut unit down.
Chiller shut down CCN/
Automatic
Network command.
53 Alarm Cooler Pump Interlock
Failed at Start-Up
Interlock did not close within 1 minute after transition
Chiller shut down. Pump turned off.
Automatic Failure of cooler pump
or controls
54 Alarm Cooler Pump Interlock
Opened Unexpectedly
Interlock opened for at least 5 seconds during operation
Chiller shut down. Pump turned off.
Automatic Failure of cooler pump
or controls
55 Alarm Cooler Pump Interlock
Closed When Pump OFF
Interlock closed when pump relay is off
Cooler pump remains off. Unit prevented from starting.
Manual Failure of cooler pump
relay or interlock, welded contacts
56 Alert Loss of Communication
with WSM
No communications have been received by PSIO-1 within 5 minutes of last transmission.
WSM forces removed. Runs under own control
Automatic Failed module, wiring
error, failed transformer, loose connection plug, wrong address
57 Alert Circuit A Liquid Level
Sensor Failure
Sensor reads 245 F (118 C) or −40 F (−40 C) with SST > 9 F (−12.8 C)
Runs, but controls EXV based on Disch. Super­heat
Automatic Thermistor circuit open,
faulty liquid level sensor, wiring error
58 Alert Circuit B Liquid Level
Sensor Failure
Sensor reads 245 F (118 C) or −40 F (−40 C) with SST > 9 F (−12.8 C)
Runs, but controls EXV based on Disch. Super­heat
Automatic Thermistor circuit open,
faulty liquid level sensor, wiring error
59 Alarm Compressor A1
Pre-Start Oil Pressure
Oil Pump did not build sufficient pressure dur­ing pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure,
oil solenoid failure, oil transducer failure, check valve failed open, oil shutoff valve closed
60 Alarm Compressor A2
Pre-Start Oil Pressure
Oil Pump did not build sufficient pressure dur­ing pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure,
oil solenoid failure, oil transducer failure, check valve failed open, oil shutoff valve closed
61 Alarm Compressor B1
Pre-Start Oil Pressure
Oil Pump did not build sufficient pressure dur­ing pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure,
oil solenoid failure, oil transducer failure, check valve failed open, oil shutoff valve closed
62 Alarm Compressor B2
Pre-Start Oil Pressure
Oil Pump did not build sufficient pressure dur­ing pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure,
oil solenoid failure, oil transducer failure, check valve failed open, oil shutoff valve closed
63 Alarm Circuit A&B OFF for
Alerts. Unit down
Control has shut down both circuits due to alerts.
None Automatic Check individual alarms
64 Alert Circuit A Loss of Charge Discharge pressure
reading <10 PSIG for 30 seconds
Circuit A shut down Manual Refrigerant leak or
transducer failure
65 Alert Circuit B Loss of Charge Discharge pressure
reading <10 PSIG for 30 seconds
Circuit B shut down Manual
66 Alarm Loss of Communication
with FSM
No communications have been received by PSIO-1 within 5 minutes of last transmission.
FSM forces removed Runs under own control
Automatic Wiring faulty or module
failure
67 Alert Circuit A High Discharge
Pressure
SCT > MCT_SP + 5 F (2.8 C)
Circuit shut down Automatic** Faulty transducer/high
pressure switch, low/ restricted condenser air/water flow.††
47
Page 48
Table 33 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
68 Alert Circuit B High Dis-
charge Pressure
SCT > MCT_SP + 5 F (2.8 C)
Circuit shut down Automatic** Faulty transducer/high
pressure switch, low/ restricted condenser air/water flow.††
70 Alert High Leaving Chilled
Water Temperature
LCW read > LCW Delta Alarm limit and total ca­pacity is 100% and cur­rent LCW > LCW reading 1 minute ago
Alert only. None Automatic Building load greater
than unit capacity, low water/brine flow, or compressor fault. Check for other alarms or alerts.
71 Alert Circuit A Low Oil Level Level switch input open
for 4th time in same day.
Circuit A shut down Manual Low oil level, failed
switch, wiring error, failed DSIO module
72 Alert Circuit B Low Oil Level Level switch input open
for 4th in same day.
Circuit B shut down Manual Low oil level, failed
switch, wiring error, failed DSIO module
73 Alert Circuit A Low Discharge
Superheat
Superheat <5 F (2.8 C) for 10 minutes
Circuit A shut down Manual Faulty thermistor,
transducer or EXV or Economizer. Motor cool­ing solenoid stuck open.
74 Alert Circuit B Low Discharge
Superheat
Superheat <5 F (2.8 C) for 10 minutes
Circuit B shut down Manual Faulty thermistor,
transducer or EXV or Economizer. Motor cool­ing solenoid stuck open.
75 Alarm Comp. A1 Max. Oil
Delta P, check oil line
(Discharge press − Oil press) >100 PSI for more than 5 seconds
Comp. A1 shut down Manual Plugged oil filter, closed
oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
76 Alarm Comp. A2 Max. Oil
Delta P, check oil line
(Discharge press − Oil press) >100 PSI for more than 5 seconds
Comp. A2 shut down Manual Plugged oil filter, closed
oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
77 Alarm Comp. B1 Max. Oil
Delta P, check oil line
(Discharge press − Oil press) >100 PSI for more than 5 seconds
Comp. B1 shut down Manual Plugged oil filter, closed
oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
78 Alarm Comp. B2 Max. Oil
Delta P, check oil line
(Discharge press − Oil press) >100 PSI for more than 5 seconds
Comp. B2 shut down Manual Plugged oil filter, closed
oil valve, bad oil sole­noid, compressor oil check valve stuck, oil line check valve stuck, plugged oil strainer
79 Alarm Comp. A1 Failed Oil
Solenoid
Diff. Oil pressure >2.5 PSI during period after oil pump starts and before oil solenoid opens
Comp. A1 not allowed to start
Manual Faulty oil solenoid valve
80 Alarm Comp. A2 Failed Oil
Solenoid
Diff. Oil pressure >2.5 PSI during period after oil pump starts and before oil solenoid opens
Comp. A2 not allowed to start
Manual Faulty oil solenoid valve
81 Alarm Comp. B1 Failed Oil
Solenoid
Diff. Oil pressure >2.5 PSI during period after oil pump starts and before oil solenoid opens
Comp. B1 not allowed to start
Manual Faulty oil solenoid valve
82 Alarm Comp. B2 Failed Oil
Solenoid
Diff. Oil pressure >2.5 PSI during period after oil pump starts and before oil solenoid opens
Comp. B2 not allowed to start
Manual Faulty oil solenoid valve
LEGEND
CCN — Carrier Comfort Network CPM — Compressor Protection Module DGT — Discharge Gas Temperature EWT — Entering Water Temperature EXV — Electronic Expansion Valve FSM — Flotronic™ System Manager HPS — High-Pressure Switch LCW — Leaving Chilled Water LWT — Leaving Water Temperature MCT
SP — Maximum Condensing Temperature Set Point MTA — Compressor Must Trip Amps SCT — Saturated Condensing Temperature SST — Saturated Suction Temperature W/C — Water-Cooled WSM — Water System Manager
*Current and voltage imbalance alarms x.25 and x.55 may be changed to
warnings x.27 and x.57 after successful start-up of the chiller.
†Compressors are equipped with 2 motor winding temperature ther-
mistors. Verify first thatthe problem isnot a wiringerror before usingbackup thermistor.
**Reset automatic first time, manual if repeated on the same date.
††Note that the high-pressureswitch should trip before this alertis generated.
Check HPS operation if this alert is generated.
NOTES:
1. Low Oil Pressure Alert Criteria and Set Points Where: Pd= Discharge pressure, Ps= Suction pressure, Po= Oil pressure and Pe= Economizer pressure Two oil pressure set points are used. Oil Set point 1 is always 15 psig.
a. If (Pd−Ps) <125, then Oil Set point 2 = 0.235 x (Pd−Ps) + 0.588 b. If (Pd−Ps) > = 125 and <165, then Oil Set point2=2.0x(Pd−Ps)
− 220.0
c. If (Pd−Ps) > = 165, then Oil Set point 2 = 0.6364 x (Pd−Ps) + 5.0 The 2 set points are used by the control for the Low Oil Pressure alert trip
criteria below: a. Oil Pressure is ignored during the first 5 seconds after a compressor is
started.
b. In period between 5 and 30 seconds after starting, the alert will begen-
erated if (Po−Pe) < [(Oil Set point 1)/30] x (Compressor Run time in seconds) for 3 consecutive readings
c. After 30 seconds run time, the alert will be generated if:
1) (Po−Pe) < Oil Set point 1 for 15 seconds OR
2) (Po−Ps) < Oil Set point 2 for 25 seconds
2. (Po−Pe) is theOilpressure differential displayed in for Circuit A and for Circuit B.
48
Page 49
Table 34 — Hardware Point Communications Loss/Action Taken
HARDWARE POINT CONTROL POINT NAME
ACTION TAKEN UNTIL
COMMUNICATION RESTORED
ALARM Alarm Relay No Action CFLOW_SW Cooler Flow Switch Chiller shut down COND_ENT Condenser Entering Water Thermistor Same as Alert 12 COND_LWT Condenser Leaving Water Thermistor Same as Alert 11 COND_PMP Condenser Pump Relay Chiller shut down COOL_EWT Cooler Entering Water Thermistor Same as Alarm 10 COOL_LWT Cooler Leaving Water Thermistor Chiller shut down COOL_HTR Cooler Heater Turn ON Cooler Pump relay COOL_PMP Cooler Pump Relay No Action DFLOW_SW Condenser Flow Switch Chiller shut down DISTMP_A Discharge Gas Temp Circuit A (Oil Temp) Circuit shut down DISTMP_B Discharge Gas Temp Circuit A (Oil Temp) Circuit shut down DISTMP_B Discharge Gas Temp Circuit B (Oil Temp) Circuit shut down DMD_SW1 Demand Limit Switch 1 No Action DMD_SW2 Demand Limit Switch 2 No Action DPA Discharge Pressure Circuit A Circuit shut down DPB Discharge Pressure Circuit B Circuit shut down DUAL Dual Setpoint Switch Control to Setpoint 1 ECN_PR_A Circuit A Economizer Pressure Circuit shut down ECN_PR_B Circuit B Economizer Pressure Circuit shut down EXVA Expansion Valve, Circuit A Circuit shut down EXVB Expansion Valve, Circuit B Circuit shut down FAN_1 Fan Relay 1 No Action FAN_2 Fan Relay 2 No Action FAN_3 Fan Relay 3 No Action FAN_4 Fan Relay 4 No Action FAN_5 Fan Relay 5 No Action FAN_6 Fan Relay 6 No Action HC_SW Heat/Cool Switch Chiller shut down HR_EWT Heat Reclaim Entering Water Thermistor No Action HR_LWT Heat Reclaim Leaving Water Thermistor No Action ICE_DONE Ice Complete Indicator Disable function ICE_VALV Ice Valve Disable function K_A1_FBK Compressor A1 Feedback Compressor shut down K_A1_RLY Compressor A1 Relay Compressor shut down K_A2_FBK Compressor A2 Feedback Compressor shut down K_A2_RLY Compressor A2 Relay Compressor shut down K_B1_FBK Compressor B1 Feedback Compressor shut down K_B1_RLY Compressor B1 Relay Compressor shut down K_B2_FBK Compressor B2 Feedback Compressor shut down K_B2_RLY Compressor B2 Relay Compressor shut down LOADR_A1 Compressor A1 Loader No Action LOADR_A2 Compressor A2 Loader No Action LOADR_B1 Compressor B1 Loader No Action LOADR_B2 Compressor B2 Loader No Action LMT_MA Demand Limit 4-20 mA Input Disable function LOR_SW Local/Off/Remote Switch Chiller shut down MLV_A Min. Load Valve Relay Circuit A Disable function MLV_B Min. Load Valve Relay Circuit B Disable function MOTOR_A Circuit A MotormasterT Output Disable function MOTOR_B Circuit B Motormaster Output Disable function MTRCL_A1 Compressor A1 Motor Cooling Compressor shut down MTRCL_A2 Compressor A2 Motor Cooling Compressor shut down MTRCL_B1 Compressor B1 Motor Cooling Compressor shut down MTRCL_B2 Compressor B2 Motor Cooling Compressor shut down OAT Outside Air Temperature Disable function OIL_A1 Compressor A1 Oil Pressure Transducer Compressor shut down OIL_A2 Compressor A2 Oil Pressure Transducer Compressor shut down OIL_B1 Compressor B1 Oil Pressure Transducer Compressor shut down OIL_B2 Compressor B2 Oil Pressure Transducer Compressor shut down OILA_HTR Circuit A Oil Heater Disable function OILA_SW Circuit A Oil Level Circuit shut down OILB_HTR Circuit B Oil Heater Disable function OILB_SW Circuit B Oil Level Circuit shut down OILPMP_A CircuitA Oil Pump NoAction OILPMP_B Circuit B Oil Pump No Action OILSOL_A Circuit A Oil Solenoid Circuit shut down OILSOL_B Circuit B Oil Solenoid Circuit shut down P_REF 5 Volt Transducer Reference Chiller shut down RALARMx Remote Alarm Relay x (1-16) Disable function RST_MA Temp. Reset 4-20 mA signal Disable function SPA Circuit A Suction Transducer Circuit shut down SPB Circuit B Suction Transducer Circuit shut down TLEV_A Circuit A Cooler Level Sensor Control EXV-A by discharge superheat TLEV_B Circuit B Cooler Level Sensor Control EXV-B by discharge superheat TMTR_A1 Compressor A1 Motor Thermistor Compressor shut down TMTR_A2 Compressor A2 Motor Thermistor Compressor shut down TMTR_B1 Compressor B1 Motor Thermistor Compressor shut down TMTR_B2 Compressor B2 Motor Thermistor Compressor shut down T_SPACE External Space Temp Thermistor Disable function VALVE_A Circuit A Water Valve Control Circuit shut down VALVE_B Circuit B Water Valve Control Circuit shut down
49
Page 50
Table 35 — Illegal Configurations Recognized
by PSIO-1
CODE
NUMBER
ILLEGAL CONFIGURATION
DESCRIPTION
1
Incorrect Check Sum in configuration code (factory or service code)
2 Unit type outside range of (1-3) 3
Number of compressors in a circuit outside the range of 0-2
4
Air cooled chiller with a fan type outside the range of 1-16
5
Air cooled chiller with Low Temperature Brine fluid
6
Water cooled chiller configured for air cooled head pressure
7
Selecting both OAT and Space Temp sensors for External Reset operation
8 Air cooled chiller with condenser water pump 9 Air cooled chiller with condenser thermistors
10
MOP Set point is outside the range of 40 - 55 F (4.4 - 12.8 C)
11
Maximum Condensing Temperature Set point (MCT_SP) is outside the range of 0 - 158 F (-17.8 - 70 C)
LEGEND
MOP — Minimum Operating Temperature OAT — Outdoor-Air Temperature
EXD Troubleshooting Procedure — Follow steps
below to diagnose and correct EXV/Economizer problems.
On 30HX units with economizers, verify that the valve
for the bubbler tube (bottom of economizer) is open. Check EXV motor operation first. Press on the HSIO II
keypad and select the appropriate EXV. Press to move the valve to 25%. You should be able to feel the ac-
tuator moving by placing your hand on the EXV or econo­mizer body (the actuator is located about one-half to two­thirds of the way up from the bottom of the economizer shell).
Press three more times until the display reads 100% for a Target Percent (waiting until actuator stops each time).
A hard knocking should be felt from the actuator when
it reaches the top of its stroke (can be heard if surroundings are relatively quiet). Press again if
necessary to confirm this. Press four times to step the actuator closed in 25% increments, waiting again in be-
tween each move. The actuator should knock when it reaches the bottom of its stroke. If it is believed that the valve is not working properly, continue with the checkout procedure below:
Check the EXV output signals at appropriate terminals
on EXV driver module (see Fig. 12). Connect positive test lead to terminal 1 on the EXV driver for Circuit A and to terminal 7 for Circuit B. Set meter for approximately 20 vdc. Enter Valves and Motor Master test subfunction by pressing
on the HSIO. The EXV for Circuit A will be dis-
played; if desired, press the down arrow key for Circuit B. When at the desired valve, press . The display should change to show a Target Percent of 25%. The driver should
drive the circuit EXV under test. During the next several sec­onds, connect negative test lead to pins 2, 3, 4, and 5 in suc­cession (pins 8, 9, 10 and 11 for Circuit B). Voltage should rise and fall at each pin. If it remains constant at a voltage or shows 0 volts, remove the connector to the valve and recheck.
Press to close the circuit EXV. Check the DSIO
address setting (the address should be 50). If a problem still exists, replace the EXV driver module. If the voltage read­ing is correct, the expansion valve and EXV wiring should be checked. Check the EXV terminal strip and interconnect­ing wiring.
1. Checkcolorcodingand wire connections. Make sure they
are connected to the correct terminals at the EXV driver and EXV plug and that the cables are not crossed.
2. Check for continuity and tight connection at all pin
terminals.
Check the resistance of the EXV motor windings.
Remove the DSIO-EXV plug J4 terminal strip and check the resistance between the common lead (red wire, terminal D) and remaining leads, A, B, C, and E (see Fig. 12). The re­sistance should be 25 ohms ± 2 ohms.
RED
GRN
WHT
BLK
BRN
D
C
E
B
A
RED
GRN
WHT
BLK
BRN
D
C
E
B
A
EXV-A
EXV-B
7
2
1
1
2
3
4
5
8
9
10
11
EXV DRIVER BOARD, J4
EXV — Electronic Expansion
Valve
Fig. 12 — EXV Cable Connections to EXV Driver Module, DSIO-EXV
50
Page 51
INSPECTING/OPENING ELECTRONIC EXPANSION VALVES
IMPORTANT:ObtainreplacementO-ringbeforeopen­ing EXV. Do not reuse O-rings.
To check the physical operation of an EXV, the following
steps must be performed:
1. Close the liquid lineservicevalveof the circuit to bechecked. Put the LOR switch in the OFF position. Using the HSIO, enter the manual service mode by pressing
. Enable the mode by pressing . Switch
the LOR switch to the Local position. Scroll down to the desired compressor and press to turn it on. Let
compressor run until gage on suction pressure port reads between 5 and 10 psig. Press to turn the com-
pressor off. Immediately after the compressor shuts off, close the discharge valve.
2. Remove any remaining refrigerant from the system low side using proper reclaiming techniques. Drain oil from cooler using Schrader port in cooler inlet line. Turn off the line voltage power supply to the compressors and con­trol circuit power.
3. Remove screws holding top cover of EXV. Carefully re­move the top cover from the EXV making sure EXV plug is still connected.
IMPORTANT: When removing top cover from EXVs, be careful to avoid damage to motor leads.
4. Entertheappropriate EXVtest step for EXV-A or EXV-B by pressing on the HSIO. Scroll down to display
the desired EXV. Press and to initiate the test. Observe the operation of the valve motor and lead screw.
The motor shouldturncounterclockwise,andthe lead screw should move up out of the motor hub until the valve is fully open. Lead screw movement should be smooth and uniform from fully closed to fully open position. Press
as needed to reach 100% open. Wait 30 seconds
in between each step for motor to stop moving. Press
to check open to closed operation. If the valve is
properly connected to the processor and receiving correct signals, yet does not operate as described above, the valve should be replaced.
INSPECTING/OPENING ECONOMIZERS — To check the physical operation of an economizer (see Fig. 13), the fol­lowing steps must be performed:
1. Close the liquid lineservicevalveof the circuit to bechecked. Put the LOR switch in the OFF position. Using the HSIO, enter the manual service mode by pressing
. Enable the mode by pressing . Switch
the LOR switch to the Local position. Scroll down to the desired compressor and press to turn it on. Let
compressor run until gage on suction pressure port reads between 5 and 10 psig. Press to turn the com-
pressor off. Immediately after the compressor shuts off, close the discharge valve and the bubbler valve on 30HX units (located in elbow fitting on condenser shell).
2. Remove any remaining refrigerant from the system low side and discharge piping using proper reclaiming tech­niques. For 30GX units, there is no shutoff valve in the bubbler tube line. Drain oil from cooler using Schrader port in cooler inlet line. Turn off the line voltage power supply to the compressors and control circuit power.
3. Remove the shell retaining bolts on the bottomoftheecono­mizer and the bolts that secure the shell to the unit frame or mounting bracket. Cut the motor cooling line leaving the top of the economizer.Carefullyremovetheshellfrom the economizer. Make sure EXV plug is still connected.
IMPORTANT: When removing shell from econo­mizer, it must be lifted off as close to vertical as possible to prevent damage to any of the internal parts. Use a catch pan beneath the economizer as oil will come out when the shell is removed. Be careful to avoid damage to motor leads.
4. Entertheappropriate EXVtest step for EXV-A or EXV-B by pressing on the HSIO. Scroll down to display
the desired EXV. Press and to initiate the test. Observe the operation of the valve motor and lead screw.
The motor shouldturncounterclockwise,andthe lead screw should move up out of the motor hub until the valve is fully open. Lead screw movement should be smooth and uniform from fully closed to fully open position. Press
as needed to reach 100% open. Wait 30 seconds
in between each step for motor to stop moving. Press
to check open to closed operation. If the valve is
properly connected to the processor and receiving correct signals, yet does not operate as describedabove,theecono­mizer should be replaced.
5. Additional items to check for: a. Verify that float assembly (see cross section view in
Fig. 13) moves up and down freely. It should take only a minimal force (less than one pound) to move the float and there should be no binding.
b. Check the bubbler tube (found by carefully lifting the
float) for crimps, etc. and verify that the end of the tube is open.
6. Reassemble economizer; retorque shell retaining bolts to 35 ft-lb (48 N-m).
If operating problems persist after reassembly, they may be due to a bad liquid level sensor, suction pressure trans­ducer or intermittent connections between the processor board terminals and EXV plug. Recheck all wiring connections and voltage signals.
Other possible causes of improper refrigerant flow con­trol could be restrictions in the liquid line. Check for plugged strainer(s) or restricted metering slots in the EXV or econo­mizer. Formation of ice or frost on lower body of electronic expansion valve is one symptom of restricted metering slots. However, frost or ice formation is normally expected when leaving fluid temperature from the cooler is below 40 F. Clean or replace valve if necessary.
NOTE (non-economizer units only): Frosting of valve is nor­mal during compressor test steps and at initial start-up. Frost should dissipate after 5 to 10 minutes operation in a system that is operating properly. If valve is to be replaced, wrap valve with a wet cloth to prevent excessive heat from dam­aging internal components.
51
Page 52
SERVICE
ServicingCoolersandCondensers—
When cooler heads and partition plates are removed, tube sheets are ex­posed showing the ends of tubes. The 30GX,HX units use a flooded cooler design. Water flows inside the tubes.
TUBE PLUGGING — A leaky tube can be plugged until retubing can be done. The number of tubes plugged deter­mines how soon the cooler must be retubed. All tubes in the 30GX and 30HX coolers and 30HX condensers can be re­moved. Loss of unit capacity and efficiency as well as in­creased pump power will result from plugging tubes. Failed tubes should be replaced as soon as possible. Up to 10% of the total number of tubes can be plugged before retubing is necessary. Figure 14 shows an Elliot tube plug and a cross­sectional view of a plug in place. The same components for plugging and rolling tubes can be used for all coolers and 30HXC condensers. See Table 36.
Use extreme care when installing plugs to prevent dam­age to the tube sheet section between the holes.
RETUBING (See Table 37) — When retubing is to be done, obtain service of qualified personnel experienced in boiler maintenance and repair.Moststandardprocedurescanbefol­lowed when retubing the 30GX and 30HX heat exchangers. A7%crushisrecommended when rolling replacement tubes into the tubesheet. A 7% crush can be achieved by setting the torque on the gun at 48 to 50 in.-lb (5.4 to 5.6 N-m).
The following Elliot Co. tube rolling tools are required:
B3400 Expander Assembly B3401 Cage
B3405 Mandrel B3408 Rolls
Place one drop of Loctite No. 675 or equivalent on top of tube prior to rolling. This material is intended to ‘‘wick’’ into the area of the tube that is not rolled into the tube sheet, and prevent fluid from accumulating between the tube and the tube sheet. New tubes must also be rolled into the center tube sheet to prevent circuit-to-circuit refrigerant leakage.
Table 36 — Plugging Components
COMPONENTS FOR PLUGGING PART NUMBER For Tubes
Brass Pin 853103-1A* Brass Ring 853002-640*
For Holes without Tubes
Brass Pin 853103-1A* Brass Ring 853002-738*
Roller Extension S82-112/11 Loctite No. 675† Locquic ‘‘N’’†
*Order directly from: Elliot Tube Company, Dayton, Ohio.
†Can be obtained locally.
Table 37 — Tube Diameters
ITEM INCHES MILLIMETERS
Tube sheet hole diameter: 0.756 19.20 Tube OD 0.750 19.05 Tube ID after rolling:
(includes expansion due to clearance)
0.704 to
0.710
17.88 to
18.03
NOTE: Tubes replaced along heat exchanger head partitions must be flush with tube sheet.
TIGHTENING COOLER/CONDENSER HEAD BOLTS O-Ring Preparation — When reassembling cooler and con-
denser heads, always check the condition of the O-ring(s) first. The O-ring should be replaced if there are any visible signs of deterioration, cuts or damage. Apply a thin film of grease to the O-ring before installation. This will aid in hold­ing the O-ring into the groove while the head is installed. Torque all bolts to the following specification and in the sequence shown in Fig. 15.
3
⁄4-in. Diameter Perimeter and
Plate Bolts ........................200to225ft-lb.
(271 to 305 N-m)
SHELL BOLTS
OUTLET FOR MOTOR COOLING LINE CONNECTION
STEPPER MOTOR HARNESS
MOUNTING BRACKET BOLTS
STEPPER MOTOR
FLOAT ASSEMBLY
DISCHARGE GAS BUBBLER TUBE
OUTLET TO BOTTOM OF COOLER
LIQUID INLET TUBE FROM CONDENSER
Fig. 13 — 30GX,HX Cutaway View of
Economizer Assembly
PIN AND RING INSTALLED
TUBE SHEET
PIN
TUBE
RING
PIN
RING
Fig. 14 — Tube Plugging
52
Page 53
1. Install all bolts finger tight.
2. Follow numbered sequence shown for head type being installed. This will apply even pressure to the O-ring.
3. Apply torque in one-third steps until required torque is reached. Load all bolts to each one-third step before pro­ceeding to the next one-third step.
4. No less than one hour later, retighten all bolts to required torque values.
5. Restore water/brine flow and check for leaks. Fix leaks as necessary. Replace insulation (on cooler heads only).
Inspecting/Cleaning Heat Exchangers
COOLERS — Inspect and clean the cooler tubes at the end of the first operating season. Because these tubes have in­ternal ridges, a rotary-type tube cleaning system is neces­sary to fully clean the tubes. Tube condition in the cooler will determine the scheduled frequency for cleaning, and will indicate whether water treatment is adequate in the chilled water/brine circuit. Inspect the entering and leaving ther­mistors for signs of corrosion or scale. Replace the sensor if corroded or remove any scale if found.
CONDENSERS (30HX Only) — Since this water circuit is usually an open-type system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at regular intervals, and more often if the water is contaminated. Inspect the entering and leaving condenser water thermistors (if installed) for signs of corrosion or scale. Replace the sensor if corroded or re­move any scale if found.
Higher than normal condenser pressures, together with in­ability to reach full refrigeration load, usually indicate dirty tubes or air in the machine. If the refrigeration log indicates a rise above normal condenser pressures, check the con­denser refrigerant temperature against the leaving condenser water temperature. If this reading is more than what the de­sign difference is supposed to be, then the condenser tubes
may be dirty, or water flow may be incorrect. Due to the pressure in the R-134a system, air usually will not enter the machine; the refrigerant will leak out.
During the tube cleaning process, use brushes specially designed to avoid scraping and scratching the tube wall. Con­tact your Carrier representative to obtain these brushes. Do not use wire brushes.
Hard scale may require chemical treatment for its pre­vention or removal. Consult a water treatment specialist for proper treatment procedures.
Water Treatment — Untreated or improperly treated
water may result in corrosion, scaling, erosion, or algae. The services of a qualified water treatment specialist should be obtained to develop and monitor a treatment program.
Water must be within designflowlimits,cleanandtreated to ensure proper machine performance and reduce the potential of tubing damage due to corrosion, scaling, ero­sion, and algae. Carrier assumes no responsibility for chiller or condenser damage resulting from untreated or improperly treated water.
Condenser Coils (30GX Only)
COIL CLEANING — Clean coils with a vacuum cleaner, fresh water,compressedair, or a bristle brush (not wire). Units installed in corrosive environments should have coil clean­ing as part of a planned maintenance schedule. In this type of application, all accumulations of dirt should be cleaned off the coil.
2
5
9
11
6
3
1
8
14
13
7
4
10
12
11
9
5
2
4
7
3
1
8
13
15
14
16
10
12
6
9
5
2
4
7
12
14
11
13
8
1
3
6
10
BLANK PLATE
BLANK PLATES
9
5
2
4
7
11
12
8
1
3
6
10
Fig. 15 — Cooler and Condenser Head Recommended Bolt Torque Sequence
53
Page 54
Do not use high-pressure water or air to clean coils as fin damage may result.
Condenser Fans (30GX Only) — Each fan is sup-
ported by a formed wire mount bolted to a fan deck and covered with a wire guard. The exposed end of the fan motor shaft is protected from weather by grease. If the fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan cover, retaining clips, and fan guard. For proper performance, the fans should be positioned as shown in Fig. 16 or 17. Tighten setscrews to 14 ± 1 ft-lb (18 ± 1.3 N-m).
Check for proper rotation of the fan(s) once reinstalled (clockwise for high static and counterclockwise for standard viewed from above). If necessary to reverse, switch leads at contactor(s) in control box.
Refrigerant Charging/Adding Charge
IMPORTANT: These units are designed for use with R-134a only. DO NOT USE ANY OTHER REFRIG­ERANT in these units without first consulting your Carrier representative.
When adding or removing charge,circulatewaterthrough the condenser (30HXC) and cooler at all times to pre­vent freezing. Freezing damage is considered abuse and may void the Carrier warranty.
DO NOT OVERCHARGE system. Overcharging re­sults in higher discharge pressure with higher cooling fluid consumption,possiblecompressordamageand higher power consumption.
Indication of low charge on a 30HXC system: NOTE: To check for low refrigerant charge on a 30HXC,
several factors must be considered.A flashing liquid-line sight glass is not necessarily an indication of inadequate charge. There are many system conditions where a flashing sightglass occurs under normal operation. The 30HXC metering de­vice is designed to work properly under these conditions.
1. Make sure that the circuit is running at a full-load con-
dition. To check whether circuit A is fully loaded, enter
on the HSIO keypad. The display will read
‘‘CIRCUIT AANALOG VALUES.’’Using the down ar­row key on the keypad, scroll down once to ‘‘Total Capacity.’’Ifthisvalue is 100%, the circuit is at full load. To check circuit B, follow the same procedure, but enter
on the keypad.
2. It may be necessary to use the Manual Control feature to
force the circuit into a full-load condition. If this is the case, see the instructions for using the Manual Control feature in Table 19 of this manual.
3. With the circuit running at full load, verify that the cooler
leaving fluid temperature is in the range of 38 to 46 F (3.3 to7.8C).Checkpressure drop across liquid line strainer and replace strainer if necessary.
4. Atthis condition, observe the refrigerant in the liquid line
sight glass. If there is a clear sight glass, and no signs of flashing, then the circuit is adequately charged. Skip the remaining steps.
5. Iftherefrigerantappearstobe flashing, the circuit is prob­ably low on charge. Verify this by checking the EXV Percent Open. This information can be accessed by
entering on the HSIO keypad for Circuit A, or
for Circuit B. Scroll down using the down arrow
key on the keypad, until EXV Percent Open is displayed.
6. If the EXV Percent Open is greater than 60%, and the liquid-line sight glass is flashing, then the circuit is low on charge. Follow the procedure for adding charge for 30HXC units.
To add charge to the 30HXC systems:
1. Make sure that the unit is running at full load, and that the cooler leaving fluid temperature is in the range of 42 to 46 F (5.6 to 7.8 C).
2. At these operating conditions, check the liquid line sight glass. If there is a clear sight glass, then the unit has suf­ficient charge. If the sight glass is flashing, then check the EXV Percent Open. If this is greater than 60%, then be­gin adding charge.
NOTE:Aflashing liquid line sight glass at operating con­ditions other than those mentioned above is not neces­sarily an indication of low refrigerant charge.
3. Add 5 lb of liquid charge into the cooler using the
1
⁄4-in. Schrader-type fitting located on the tube entering the bot­tom of the cooler.Thisfittingislocated between the Elec­tronic Expansion Valve (EXV) (size 076-146 units), or the economizer (size 161-271 units) and the cooler.
4. Observe the EXV Percent Open value. The EXV should begin closing as charge is being added. Allow the unit to stabilize. If the EXV Percent Open remains above 60%, and the sight glass continues flashing, add an additional 5 lb of liquid charge.
5. Allow the unit to stabilize, and again check the EXV Per­cent Open. Continue adding 5 lb at a time of liquid re­frigerant charge, and allow the unit to stabilize before checking the EXV position.
PLASTIC FAN PROPELLER
CLEARANCE OF 0.25 INCHES (6.4 MM) FOR STANDARD CONDENSER FANS
FAN DECK SURFACE
FAN ORIFICE
Fig. 16 — Condenser Fan Position (Standard Fan)
POSITION TOP OF HIGH STATIC FAN PROPELLER HUB
2.15 INCHES (54.6 mm) ABOVE FAN DECK SURFACE
FAN DECK SURFACE
STATIC FAN PROPELLER
FAN HUB
2.15 IN.
MOTOR SHAFT
Fig. 17 — Condenser Fan Position (High Static Fan)
54
Page 55
6. WhentheEXVPercentOpenisintherangeof 40 to 60%, check the liquid line sight glass. Slowly add enough ad­ditional liquid charge to ensure a clear sight glass. This should be done slowly to avoid over-charging the unit.
7. Verify adequate charge by continuing to run at full load with 42 to 46 F (5.6 to 7.8 C) cooler leaving fluid tem­perature. Check that the refrigerant is not flashing in the liquid-line sight glass. The EXV Percent Open should be between 40 and 60%. The cooler level indicator should be in the range of 1.5 to 2.2.
Indication of low charge on a 30HXA, GX systems:
1. Make sure that the circuit is running at a full load con­dition and all condenser fans are energized and running at full speed. To check whether circuit A is fully loaded,
enter on the HSIO keypad. The display will read ‘‘CIRCUIT AANALOG VALUES.’’Using the down ar-
row key on the keypad, scroll down once to ‘‘Total Capacity.’’Ifthisvalue is 100%, the circuit is at full load. To check circuit B, follow the same procedure, but enter
on the keypad.
2. It may be necessary to use the Manual Control feature to force the circuit into a full-load condition. If this is the case, see the instructions for using the Manual Control feature in Table 19 on page 31 of this manual.
3. With the circuit running at full-load, verify that the cooler leaving fluid temperature is in the range of 38 to 48 F (5.6 to 7.8 C).
4. For 30HXA chillers, raise the compressor discharge to approximately 125 F (51.7 C) saturated discharge tem­perature (185 psig [1276 kPa]). For 30GX chillers, raise the compressor discharge to approximately 130 F (54.4 C) saturated discharge temperature (198 psig [1366 kPa]). Measure the liquid temperature entering the expansion device for 30HXAunits. For 30GX units, mea­sure the liquid temperature after the tee where all liquid lines have joined. The liquid temperature should be ap­proximately 107 F (41.7 C) for optimum charge. If the temperature is greater than 107 F (41.7 C) and the sight glass is flashing, the circuit is undercharged.
5. Add 5 lb of liquid charge into the cooler using the
1
⁄4-in. Schrader-type fitting located on the tube entering the bot­tom of the cooler.Thisfittingislocated between the Elec­tronic Expansion Valve (EXV) (30HXA076-146 units, 30GX080-090 units), or the economizer (30HXA161­271 units, 30GX105-176 units) and the cooler.
6. Allow the system to stabilize and then recheck the liquid temperature. Repeat Step 5 as needed allowing the sys­tem to stabilize between each charge addition. Slowly add charge as the sight glass begins to clear to avoid overcharging.
Oil Charging/Low Oil Recharging
Addition of oil charge to 30HX,GX systems:
1. If the 30HX,GX unit shuts off repeatedly on Low Oil Level (Alert number 71 or 72), this may be an indica­tion of inadequate oil charge. It could also mean simply that oil is in the process of being reclaimed from the low-side of the system.
2. Begin by running the unit at full load for 1
1
⁄2hours. Use the Manual Control feature of the software if the unit does not normally run at full load.
3. After running the unit for 1
1
⁄2hours, allow the unit to restart and run normally. If the Low Oil Level alarms persist, continue following this procedure.
4. Close the liquid line service valve, and place a pressure gage on top of the cooler. Enable the manual control feature using the HSIO keypad, and turn the LOR switch to local. Start the desired compressor by pressing
on the keypad, at the appropriate line on the
display.
5. Before starting the compressor, the unit will go through its normal pre-lube pump routine. If there is an insuf­ficient level of oil in the oil separator, the compressor will not start, and a pre-start oil pressure alarm will be posted. Skip to Step 8.
6. If the compressor starts successfully, observe the cooler pressure gage. When this gage reads approximately
10 psig, press on the HSIO keypad, and move the LOR switch to the off position.
7. Open the liquid line service valve and allow the unit to restart and run normally. If the Low Oil Level alarms persist, continue following this procedure.
8. If none of the previous steps were successful, the unit is low on oil charge. Add oil to the oil separator using the
1
⁄4-in. Schrader-type fitting on the discharge line enter­ing the top of the oil separator (30HX units) or through the Schrader fitting on the top of the oil separator (30GX units).
Do not add oil at any other location as improper unit operation may result.
9. Make sure that the unit is not running when adding oil, as this will make the oil charging process easier. Be­cause the system is under pressure even when the unit is not running, it will be necessary to use a suitable pump (hand pump or electric pump) to add oil to the system.
10. Using a suitable pump, add
1
⁄2gal. (1.89 L) of Castrol Icematict SW-220 Polyolester oil (Carrier Specifica­tion number is PP47-32; absolutely no substitutes are approved) to the system. Make sure that the oil level safety switch is NOT jumpered, and allow the unit to restart and run normally. Do not exceed maximum oil change. See Table 38.
11. If low oil level problems persist, add another 1.89 L (
1
⁄2gal.) of oil. Continue adding oil in 1.89 L (1⁄2gal.) increments until the problem is resolved. If it is neces­sary to add more than 5.75 L (1.5 gallons) of oil to the system, contact your Carrier distributor service department.
Table 38 — Maximum Oil Charges
UNIT SIZE
CIRCUIT A
(gal)
CIRCUIT A
(L)
CIRCUIT B
(gal)
CIRCUIT B
(L)
30GX080-176 5.0 18.9 5.0 18.9
30GX205-265 7.0 26.5 5.0 18.9 30HXA076-186 5.0 18.9 5.0 18.9 30HXC076-186 4.5 17.0 4.5 17.0 30HXC206-271 7.5 28.4 5.0 18.9
55
Page 56
OilFilter Maintenance — Each compressor has its own
internal oil filter and each circuit also has an in-line external filter. The internal oil filter pressure drop should be checked and filter changed (if necessary) after the initial 200-300hours of compressor operation. It is recommended that oil line pres­sure loss checks be made on an annual basis thereafter to determine the need for filter changes.Theneedforfiltermain­tenance can be monitored through system pressure drop. Dis­charge pressure is read at the oil separator and oil pressure is read at the compressor. This pressure differential is typi­cally 15 to 20 psi (103 to 138 kPa) for a system with clean internal and external filters. See Pressure Transducers sec­tion, page 59 for information on removing discharge pres­sure transducers to measure discharge pressure. Figure 18 shows the location of the oil pressure bleed port on the com­pressor.A gage can be attached to this point so that two pres­sure drops can be measured.Thedifference between discharge pressure and the gage pressure will be the pressure loss due mainly to the external oil filter. If this value exceeds 10 psi (69 kPa), replace the external filter. The difference between the gage pressure and compressor oil pressure is the pres­sure drop through the internal oil filter. Replace the internal oil filter if the pressure drop is greater than 30 psi (207 kPa).
REPLACING THE EXTERNAL OIL FILTER
Compressor oil is pressurized. Use proper safety pre­cautions when relieving pressure.
Fully front seat (close) the angle valve on the filter. Connect a charging hose to the oil pressure bleed port and drain the oil trapped between the filter and the internal check valve.
Use the function to cycle the oil solenoid a few times to properly seat the internal check valve as the pressure is
being relieved. If the oil pressure does not bleed off using this method it will be necessary to remove the entire circuit charge.Apint of oil is typically what is removed during this process. Remove the charging hose.
Unscrew the nut from the other side of the filter and remove the old filter. Remove protective plastic caps from new filter and install. Draw a vacuum at the bleed port. Remove charg­ing hose. Open angle valve enough to let oil flow. Check both fittings for leaks and repair if necessary.Backseat angle valve.
REPLACING THE INTERNALOILFILTER — Follow the procedure above to the point that the oil has been drained from the bleed port. Using a
3
⁄4-in. allen wrench, remove the internal filter access cover (see Fig. 18). Remove the old fil­ter. Replacement filters (one for each compressor) are fac­tory supplied to cover the first changeout. After that, filters are field supplied. Remove the old O-ring from internal check valve. Lightly oil O-ring and install into groove. Install new filter open end first into the housing. Replace access cover and retorque to 150 ft-lb (203 N-m). Follow procedure in previous section for opening angle valve and purging lines. Check for leaks and repair if necessary.
Compressor Changeout Sequence
NOTE: Replacement compressors can be ordered by calling 800-CARLYLE (800-227-5953). In most cases, replace­ment compressors can be shipped in 1 to 2 business days.
Compressor service requires metric tools and hardware.
Change compressors according to the following procedure:
1. Turn off all main and control circuit power supplying the machine.
2. Close the discharge and liquid valve(s), suction valve, and cooler inlet line service valve (if equipped), oil line shutoff valve, economizer bubble tube valve (30HXA,C161-271 only) andminimumloadshutoff valve (if equipped) for circuit to be changed. Disconnect the oil inlet line from the compressor. Disconnect oil filter with fitting at shutoff valve side and set filter and com­pressor inlet line assembly aside.
3. Removeanyremainingrefrigerantinthecompressorand refrigerant lines using proper reclaiming techniques.All of the refrigerant that is in the cooler must be removed if there is no suction service valve installed on the cooler.
IMPORTANT: Cooler and condenser pumps must be energized. Fluid must be flowing through heat exchangers whenever adding or removing charge.
4. Removejunctionboxcoverofcompressortobechanged. Check main power leads for marked numbers. If no num­bers are visible on leads, mark leads with appropriate numbers to match those printed on the ends of the ter­minal lugs. This is extremely important as powerleads
MUST be installed on the exact terminals fromwhich they were removed.
5. Disconnectmain power leads from compressor terminal lugs. Mark remaining control circuit wires (connected together with wire nuts) for ease of reconnecting later. The following color scheme applies (verify with label diagram on panel):
Loader 1 2 Violet wires Loader 2 2 Pink wires Motor Cooling Solenoid 1 Blue wire, 1 Brown wire * Oil Solenoid 1 Orange wire, 1 Brownwire* High-Pressure Switch 2 Red wires
*One lead from the motor cooling and oil solenoids are con-
nected together with a single brown wire.
6. Remove loader (mark solenoids no. 1 and 2 for replace­ment) and oil solenoids and high-pressure switch from compressor. Using 2 wrenches, carefully remove the oil pressure transducer from the compressor. These will all be reconnected to the replacement compressor.
NOTE: Some oil will leak out of the transducer fitting when the transducer is removed. See Fig. 18.
7. Mark motor temperature leads (2 blue wires) and re­move from quick connect terminals in the junction box.
The next steps involve compressor unbolting and removal. Compressor seals are made using O-rings. Use care when removing bolts and disconnecting flanges. The O-rings must NOT be re-used. New O-rings are provided with the replacement com­pressor. The 06N screw compressors weigh ap- proximately 900 pounds. Be sure that an appro­priate lifting cart or hoist is used to avoid injury. See Fig. 19 for lifting locations and center of grav­ity dimensions. Make sure compressor is properly rigged before unbolting.
8. Remove the 2 bolts securing the motorcooling/economizer line flange to the compressor.
56
Page 57
9. Remove the four M14 bolts securing the discharge line flange to the compressor. Two of the bolts also secure the mounting bracket for the external oil filter. Support the oil line to prevent damage to the line while the com­pressor is being changed. For 30GX units, place tem­porary protectionovercoilstoprevent fin and tube damage.
10. Movelifting apparatus into place and attach to the 2 lift­ing rings on the compressor. Apply minimal tension to hold the compressor while the remaining bolts are removed.
11. Remove the
3
⁄8-in. holddown bolt securing the foot at the dischargeendof the compressor to themountingbracket on the cooler.A foot bracket will be mounted to the re­placement compressor.
12. Remove the 4 lockwashers and nuts securing the com­pressor to the suction flange of the cooler. The compres­sor is held in place using four M14 x 2 studs through the suction nozzle of the cooler. The studs have an E-12 external Torx drive head. If possible, remove studs; if studs hit the cooler insulation, leave them in place — they will not interfere with compressor removal or in­stallation. Save all the hardware as it will be needed to install the replacement compressor.
13. After checking to ensure all lines, wires, conduits, etc. are free and out of the way, remove compressor from cooler.Apply a light film of O-ring grease to new O-ring and place back into groove in mounting flange of com­pressor. If the new compressor is the A1 or A2 (30HX units) compressor, remove the compressor junction box and rotate it 180 degrees. Tighten screws to 6.8 to
9.5 N-m (5 to 7 ft-lb). The A1 and A2 compressors are on the right side of the unit when facing the unit control box.
14. Remove suction cover plate and bolts from new com­pressor and set compressor on unit flange. Thread the studs all the way back into the compressor. Install the 4 lockwashers and nuts finger-tight. Tighten bolts in a crossing pattern to a range of 81.4 to 135.6 N-m (60 to 100 ft-lb). Do NOT overtighten as damage may result to O-ring. Install and tighten hold down bolt in mounting foot.
15. Remove motor cooling/economizer and discharge line cover plates from new compressor.
16. Apply a light film of O-ring grease to motor cooling/ economizer and discharge line O-rings, place back into grooves and install flange bolts. Tighten discharge line bolts in a crossing pattern to a range of 81.4 to
135.6 N-m (60 to 100 ft-lb). Tighten motor cooling/ economizer bolts to a range of 81.4 to 108.5 N-m (60 to 80 ft-lb). Do NOT overtighten as damage may result to O-rings.
17. Reconnect the oil filter to the shutoff valve and oil line to the compressor. Install oil line straight into fitting un­til ferrule seats against fitting. Thread packing nut onto fitting and tighten finger tight. Use a backup wrench to finish tightening the nut. Do not overtighten.
18. Reinstall the loader and oil solenoids, high-pressureswitch, and oil pressure transducer. Make sure the loader sole­noids are installed on the correct number loader.
19. Reconnect conduits back into compressor junction box. Reconnect all wiring that was removed in Steps 4, 5, and 7. The replacement compressor comes with a re­verse rotation switch. This switch must be wired in se­ries with the high-pressure switch for compressor pro­tection. Reconnect these wires as shown in Fig. 20.
20. Leak check compressor and refrigerant lines with nitro­gen. Repair any leaks found. Remove nitrogen from sys­tem. Evacuate compressor and refrigerant lines. Refer to the Refrigerant and Oil Charging sections on pages 54 and 55 for recharging procedures.
21. Open all shutoff valves and leak check the circuit and all fittings and joints. Repair any leaks found.
JUNCTION BOX OIL BLEED PORT
HIGH PRESSURE SWITCH
LOADER SOLENOID NO. 1
INTERNAL OIL FILTER ACCESS (3/4 in.)
OIL PRESSURE TRANSDUCER
OIL SOLENOID
LOADER SOLENOID NO. 2
LOADER COVER PLATE
Fig. 18 — Transducer Removal
DISCHARGE END
GEAR COVER END
CENTER OF GRAVITY OF COMPRESSOR
508 mm (20.0 in.)
178 mm (7.0 in.)
95 mm (3.75 in.)
CENTER OF GRAVITY OF COMPRESSOR
DISCHARGE END
GEAR COVER END
MINIMUM 381 mm (15 in.)
MINIMUM 381 mm (15 in.)
COMPRESSOR LIFTING MECHANISM
NOTE: Locatestrapfrom center ofgravitylifting ring andsupportmo­tor casing to provide 3-point level rigging.
Fig. 19 — Compressor Lifting Diagrams
COMPRESSOR LIFTING MECHANISM
ONE LUG AT OUTSIDE EDGE, RING AT
DISCHARGE CENTER
LIFTING LUGS BOTH OUTSIDE EDGES
RED
PL1-5
HPS
RRS
RED
PL1-6
LEGEND
HPS — High-Pressure Switch PL — Plug RRS — Reverse Rotation Switch
Fig. 20 — High-Pressure Switch Wiring
57
Page 58
22. Restore main and control power to the machine. Using the HSIO, enter the quick test function by pressing
(for compressor A1 or A2 replacement) or
(for compressor B1 replacement). Test the op-
eration of the solenoids. Press totesteachloader solenoid, then use the key to find the motor cool-
ing and oil solenoids and test them in the same manner. Pressing the key after each output turns the solenoid off (or press ). It is important that the
loaders are located properly (loader 1 on right hand side when viewed from side opposite control box on 30HX units, on left hand side when reaching over compressor to far side on 30GX units).
23. Start the compressor using the Manual mode. Press
at the HSIO.Press to enable the Manual
mode. When display changes to ‘‘Enable,’’ switch the Local-Off-Remote switch to the Local position. Select the desired compressor using the down arrow key. Press
to start the compressor. Use the down arrow
key and press to energize both loaders. Let the circuit stabilize with both loaders energized. Refer to the
Refrigerant and Oil Charging sections of this document for recharging procedures and performance criteria.
BURNOUT CLEANUP PROCEDURE — If a screw com­pressor motorburnsouton a 30GX,HX chiller,asimplecleanup should be performed. The following procedure provides the minimum steps to be taken before restarting the circuit.
1. Remove the oil from the oil separator. This can be fa­cilitated by connecting a hose to the port located on the service valve entering the external oil filter.Run the hose to a container(s) that can hold up to 5 to 6 gallons of oil. To force out most of the oil in the separator pressurize the circuit. To remove the remaining oil, the pre-lube
pump can be run in mode from the HSIO. To pre­vent wear to the gears, do not allow the pre-lube pump
to operate ‘‘dry.’’
2. Remove the failed compressor following the Compres­sor Changeout Sequence procedure above.
3. Oncethecompressoris removed access the oil catch pan through the cooler-compressor mounting flange. Clean out any debris which may have collected in the oil catch pan.
4. Install a new compressor.
5. To dilute and remove any residual oil left in the sepa­rator, pump approximately
1
⁄2gallon of compressor oil into the oil separator using the Schrader port located on top oftheseparator(30GX) or on the dischargeline(30HX) and remove using the pre-lube pump described in Step 1.
6. Disconnect the hose from the external oil filter service valve.
7. Install a new filter drier and compressor external oil filter.
8. Measure in the amount of Castrol SW 220 Polyolester oil as specified on the nameplate of the chiller.
9. Leak check, evacuate and recharge the machine as de­scribed in this manual with the amount of R-134a stated on the chiller nameplate.
10. Perform periodic acid checks on the circuit and change the filter drier in the motor cooling line as necessary.
Use the Carrier Standard Service Techniques Manual as a source of reference.
Moisture-Liquid Indicator — Clear flow of liquid
refrigerant indicates sufficient charge in the system. Note, however, that bubbles in the sight glass do not necessarily indicate insufficient charge. Moisture in the system is measured in parts per million (ppm), changes of color of indicator are:
Green — moisture is below 80 ppm; Yellow-green (chartreuse) — 80 to 225 ppm (caution); Yellow (wet) — above 225 ppm.
Change filter drier at the first sign of moisture in the
system.
IMPORTANT: Unit must in operation for at least 12 hours before moisture indicator can give an accu­rate reading. With the unit running, the indicating el­ement must be in contact with liquid refrigerant to give true reading.
Filter Drier — Whenever moisture-liquid indicator shows
presence of moisture, replace filter drier. Refer to Carrier Standards Service Technique Manual, Chapter 1, Refrig­erants, for details on servicing filter driers.
Liquid Line Service Valve — This valve is located
ahead of the filter drier and provides a1⁄4-in. Schrader con­nection (30GX only) for field charging. In combination with compressor dischargeservicevalve,each circuit can be pumped down into the high side for servicing.
Thermistors — To aid in verifying thermistor perfor-
mance, resistances at various temperatures are listed for all thermistors (except motor thermistors) inTables 39Aand39B. See Table 40 for motor thermistor values.
LOCATION — General location of thermistor sensors and terminal connections in the control box are listed in Table 2.
THERMISTOR REPLACEMENT
Liquid level thermistors are installed in the top of the cooler using compression fittings. All other thermistors are installed in wells and will slide out of the wells eas­ily. The wells are under refrigerant pressure (cooler EWT and LWT are under waterside pressure) and do not need to be removed to replace a faulty thermistor.
To replace thermistors T1, T2, T5, or T6 (Entering,
Leaving Water; Discharge Gas Temperature):
Disconnect appropriate wires from PSIO-2 in unit control box. Remove thermistor cable from harness. Remove and discard original thermistor from well. Insert new thermistor in well body to its full depth. Add a small amount of thermal conductive grease to thermistor probe and well. Thermistors are friction-fit thermistors and will slip back into well lo­cated at the cooler head (T1, T2) or at the top of the con­denser shell (T5, T6). Secure thermistor to well body with a wire tie to prevent thermistor from working its way out of the well. See Fig. 21.
See the Inspecting/Opening Economizers section on page 51 for information on transferring the refrigerant charge
58
Page 59
to the high side. Transfer refrigerant and reclaim any refrig­erant remaining in the low side.
NOTE: A new packing nut and ferrule will be required as the old one is not removable from the old thermistor.
For 30GX080-176 and all 30HX units cut wire nuts apart to appropriate blue leads at PSIO-1 (J7-5,6 for T3; J7-8,9 for T4) and red leads connecting wires to TRAN-7. Remove old leads from control box harness. For 30GX205-265 units, dis­connect plug assembly at liquid level sensor .Loosen the pack­ing nut fully from the well threads. Remove and discard old thermistor and packing nut. Slide new packing nut then fer­rule up onto new thermistor probe from inserted end. Inser­tion depth is dependent on unit model number. See Fig. 22 and Table 41.
Hand tighten packing nut to position ferrule while hold­ing thermistor in position. With wrench, tighten enough to firmly secure thermistor in place in well. Run new harness wires into main control box for 30GX080-176 and all 30HX units. Reconnect blue wires at PSIO-1 for thermistor read­ing and red wires to TRAN-7. Reconnect plug assembly to new liquid level sensor for 30GX205-265 units. Restore unit control power only and verify that level thermistor is read­ing correctly. Check system low side for leaks and repair as necessary.Evacuate low side and open circuit discharge and liquid valves.
To service compressor motor thermistors:
Two thermistors are factory installed in each compressor. Connections for the thermistors are located in the compres­sor junction box. There are 3 terminals for the thermistors: S1, S2, and C. Motor temperature is measured by leads con­nected to one of the S terminals and the C terminal. If a com­pressor motor thermistor failure occurs, verify that there is a true short or open circuit at these terminals. If one of the thermistors fails, disconnect and relocate the wire on one of the S terminals to the other S terminal (S1 to S2 or S2 to S1). The thermistors are not serviceable in the field. If both of the compressor motor thermistors fail, compressor replacement is required. See Table 40 for motor thermistor temperature and resistance values.
Pressure Transducers — A single style of pressure
transducer is used for both high- and low-pressure sensing on the 30GX,HX chillers. The transducers operate on a 5 vdc supply. The power supply for this is a 24 vac to 5 vdc full wave rectified power supply, PS1. See unit com­ponent arrangement label for mounting location and termi­nal connections in the control box. Refer to Fig. 23A and 23B for pressure transducer locations.
PRESSURE TRANSDUCER CALIBRATION — Pressure transducers are factory installed on all models to read Dis­charge, Suction, Economizer (reads leaving condenser pres­sure on models without economizer), and Oil pressure. DO NOT attempt to calibrate any of these transducers by the pres­sure gage method unless the transducer is connected to a fully charged refrigerant system. A more accurate method of cali­bration is used by the 30GX,HX software and corrects for
ambient temperature when calibrating. Calibrating a trans­ducer when the system is under nitrogen charge will result in an incorrect offset being applied to the reading (due to temperature correction).Althoughthese transducers are cali­brated at the factory, replacement transducers require cali­bration for accurate readings.Calibrationisalsorequiredwhen replacing a PSIO. Access to the transducer calibration area is through the Service function and the transducers can be calibrated at the current system pressure using a pressure gage at the same point or exposed to atmospheric pressure. In the example in Table 42, the CircuitADischarge Pressure transducer has been replaced and needs to be calibrated. A pressure gage has been installed at the transducer and reads 85 psi (must be in the range of −5.0 to 185.0 psi). See Table 42.
Use care when removingtheoilpressuretransducersfrom the compressor fitting. The fitting that the transducers mount in is sealed with an O-ring Schrader fitting into the compressor casting. Do NOT overtigthen the trans­ducer when replacing after calibration. Hold both fit­tings with wrenches when removing and reinstalling.
The control will apply the 0.8 psi offset from the calibra­tion example in Table 42 to all future readings. The cali­bration process for any of the other pressure transducers is done in a similar manner.Atransducer can also be calibrated at atmospheric pressure by removing the transducer from the system. To do this, carefully unplug the transducer connec­tor. Unscrew the transducer from its mounting location and reconnect the connector. Follow the steps in Table 42 to read the current pressure and enter 0.0 psig as the gage pressure. Remove the connector from the transducer, thread the trans­ducer back onto the fitting from which it was removed (do NOT use thread sealant/compound), and reinstall the connector.
If it is necessary, all of the transducers may be calibrated at 0.0 psig. All of the transducers must be removed from the system and reconnected in atmosphere as described.
When complete, scroll down under to ‘‘Calibrate All at 0 PSIG’’ and press . A ‘‘Yes’’ will be dis-
played at this stepandwillautomaticallychangebackto‘‘No’’ once all transducers have been successfully calibrated. Re­connect the transducers and connectors as described above. All transducers are mounted on Schrader fittings. Therefore, it is NOT necessary to remove system refrigerant charge. Use a catch pan when removing the oil pressure transducer for calibration as oil will leak out through the Schrader fitting.
TROUBLESHOOTING — If transducer is suspected of be­ing faulty, first check supply voltage to transducer. Supply voltage should be 5 vdc ± .2 v. If supply voltage is correct, compare pressure reading displayed on keypad and display module against pressure shown on a calibrated pressure gage. If the 2 pressure readings are not reasonably close, replace pressure transducer.
59
Page 60
Table 39A — Thermistor Temperatures (°F) vs Resistance/Voltage Drop
(NOTE: These values do NOT Apply to the Motor Temperature Thermistors )
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−25 4.821 98,010
−24 4.818 94,707
−23 4.814 91,522
−22 4.806 88,449
−21 4.800 85,486
−20 4.793 82,627
−19 4.786 79,871
−18 4.779 77,212
−17 4.772 74,648
−16 4.764 72,175
−15 4.757 69,790
−14 4.749 67,490
−13 4.740 65,272
−12 4.734 63,133
−11 4.724 61,070
−10 4.715 59,081
−9 4.705 57,162
−8 4.696 55,311
−7 4.688 53,526
−6 4.676 51,804
−5 4.666 50,143
−4 4.657 48,541
−3 4.648 46,996
−2 4.636 45,505
−1 4.624 44,066 0 4.613 42,679 1 4.602 41,339 2 4.592 40,047 3 4.579 38,800 4 4.567 37,596 5 4.554 36,435 6 4.540 35,313 7 4.527 34,231 8 4.514 33,185 9 4.501 32,176
10 4.487 31,202 11 4.472 30,260 12 4.457 29,351 13 4.442 28,473 14 4.427 27,624 15 4.413 26,804 16 4.397 26,011 17 4.381 25,245 18 4.366 24,505 19 4.348 23,789 20 4.330 23,096 21 4.313 22,427 22 4.295 21,779 23 4.278 21,153 24 4.258 20,547 25 4.241 19,960 26 4.223 19,393 27 4.202 18,843 28 4.184 18,311 29 4.165 17,796 30 4.145 17,297 31 4.125 16,814 32 4.103 16,346 33 4.082 15,892 34 4.059 15,453 35 4.037 15,027 36 4.017 14,614 37 3.994 14,214 38 3.968 13,826 39 3.948 13,449 40 3.927 13,084 41 3.902 12,730 42 3.878 12,387 43 3.854 12,053 44 3.828 11,730 45 3.805 11,416 46 3.781 11,112 47 3.757 10,816 48 3.729 10,529 49 3.705 10,250 50 3.679 9,979 51 3.653 9,717 52 3.627 9,461 53 3.600 9,213 54 3.575 8,973 55 3.547 8,739 56 3.520 8,511 57 3.493 8,291 58 3.464 8,076
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
59 3.437 7,868 60 3.409 7,665 61 3.382 7,468 62 3.353 7,277 63 3.323 7,091 64 3.295 6,911 65 3.267 6,735 66 3.238 6,564 67 3.210 6,399 68 3.181 6,238 69 3.152 6,081 70 3.123 5,929 71 3.093 5,781 72 3.064 5,637 73 3.034 5,497 74 3.005 5,361 75 2.977 5,229 76 2.947 5,101 77 2.917 4,976 78 2.884 4,855 79 2.857 4,737 80 2.827 4,622 81 2.797 4,511 82 2.766 4,403 83 2.738 4,298 84 2.708 4,196 85 2.679 4,096 86 2.650 4,000 87 2.622 3,906 88 2.593 3,814 89 2.563 3,726 90 2.533 3,640 91 2.505 3,556 92 2.476 3,474 93 2.447 3,395 94 2.417 3,318 95 2.388 3,243 96 2.360 3,170 97 2.332 3,099 98 2.305 3,031
99 2.277 2,964 100 2.251 2,898 101 2.217 2,835 102 2.189 2,773 103 2.162 2,713 104 2.136 2,655 105 2.107 2,597 106 2.080 2,542 107 2.053 2,488 108 2.028 2,436 109 2.001 2,385 110 1.973 2,335 111 1.946 2,286 112 1.919 2,239 113 1.897 2,192 114 1.870 2,147 115 1.846 2,103 116 1.822 2,060 117 1.792 2,018 118 1.771 1,977 119 1.748 1,937 120 1.724 1,898 121 1.702 1,860 122 1.676 1,822 123 1.653 1,786 124 1.630 1,750 125 1.607 1,715 126 1.585 1,680 127 1.562 1,647 128 1.538 1,614 129 1.517 1,582 130 1.496 1,550 131 1.474 1,519 132 1.453 1,489 133 1.431 1,459 134 1.408 1,430 135 1.389 1,401 136 1.369 1,373 137 1.348 1,345 138 1.327 1,318 139 1.308 1,291 140 1.291 1,265 141 1.289 1,240 142 1.269 1,214
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
143 1.250 1,190 144 1.230 1,165 145 1.211 1,141 146 1.192 1,118 147 1.173 1,095 148 1.155 1,072 149 1.136 1,050 150 1.118 1,029 151 1.100 1,007 152 1.082 986 153 1.064 965 154 1.047 945 155 1.029 925 156 1.012 906 157 0.995 887 158 0.978 868 159 0.962 850 160 0.945 832 161 0.929 815 162 0.914 798 163 0.898 782 164 0.883 765 165 0.868 750 166 0.853 734 167 0.838 719 168 0.824 705 169 0.810 690 170 0.797 677 171 0.783 663 172 0.770 650 173 0.758 638 174 0.745 626 175 0.734 614 176 0.722 602 177 0.710 591 178 0.700 581 179 0.689 570 180 0.678 561 181 0.668 551 182 0.659 542 183 0.649 533 184 0.640 524 185 0.632 516 186 0.623 508 187 0.615 501 188 0.607 494 189 0.600 487 190 0.592 480 191 0.585 473 192 0.579 467 193 0.572 461 194 0.566 456 195 0.560 450 196 0.554 445 197 0.548 439 198 0.542 434 199 0.537 429 200 0.531 424 201 0.526 419 202 0.520 415 203 0.515 410 204 0.510 405 205 0.505 401 206 0.499 396 207 0.494 391 208 0.488 386 209 0.483 382 210 0.477 377 211 0.471 372 212 0.465 367 213 0.459 361 214 0.453 356 215 0.446 350 216 9.439 344 217 0.432 338 218 0.425 332 219 0.417 325 220 0.409 318 221 0.401 311 222 0.393 304 223 0.384 297 224 0.375 289 225 0.366 282
60
Page 61
Table 39B — Thermistor Temperatures (°C) vs Resistance/Voltage Drop
(NOTE: These Values do NOT Apply to the Motor Temperature Thermistors)
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−40 4.896 168 230
−39 4.889 157 440
−38 4.882 147 410
−37 4.874 138 090
−36 4.866 129 410
−35 4.857 121 330
−34 4.848 113 810
−33 4.838 106 880
−32 4.828 100 260
−31 4.817 94 165
−30 4.806 88 480
−29 4.794 83 170
−28 4.782 78 125
−27 4.769 73 580
−26 4.755 69 250
−25 4.740 65 205
−24 4.725 61 420
−23 4.710 57 875
−22 4.693 54 555
−21 4.676 51 450
−20 4.657 48 536
−19 4.639 45 807
−18 4.619 43 247
−17 4.598 40 845
−16 4.577 38 592
−15 4.554 38 476
−14 4.531 34 489
−13 4.507 32 621
−12 4.482 30 866
−11 4.456 29 216
−10 4.428 27 633
−9 4.400 26 202
−8 4.371 24 827
−7 4.341 23 532
−6 4.310 22 313
−5 4.278 21 163
−4 4.245 20 079
−3 4.211 19 058
−2 4.176 18 094
−1 4.140 17 184 0 4.103 16 325 1 4.065 15 515 2 4.026 14 749 3 3.986 14 026 4 3.945 13 342 5 3.903 12 696 6 3.860 12 085 7 3.816 11 506 8 3.771 10 959 9 3.726 10 441
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
10 3.680 9 949 11 3.633 9 485 12 3.585 9 044 13 3.537 8 627 14 3.487 8 231 15 3.438 7 855 16 3.387 7 499 17 3.337 7 161 18 3.285 6 840 19 3.234 6 536 20 3.181 6 246 21 3.129 5 971 22 3.076 5 710 23 3.023 5 461 24 2.970 5 225 25 2.917 5 000 26 2.864 4 786 27 2.810 4 583 28 2.757 4 389 29 2.704 4 204 30 2.651 4 028 31 2.598 3 861 32 2.545 3 701 33 2.493 3 549 34 2.441 3 404 35 2.389 3 266 36 2.337 3 134 37 2.286 3 008 38 2.236 2 888 39 2.186 2 773 40 2.137 2 663 41 2.087 2 559 42 2.039 2 459 43 1.991 2 363 44 1.944 2 272 45 1.898 2 184 46 1.852 2 101 47 1.807 2 021 48 1.763 1 944 49 1.719 1 871 50 1.677 1 801 51 1.635 1 734 52 1.594 1 670 53 1.553 1 609 54 1.513 1 550 55 1.474 1 493 56 1.436 1 439 57 1.399 1 387 58 1.363 1 337 59 1.327 1 290
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
60 1.291 1 244 61 1.258 1 200 62 1.225 1 158 63 1.192 1 118 64 1.160 1 079 65 1.129 1 041 66 1.099 1 006 67 1.069 971 68 1.040 938 69 1.012 906 70 0.984 876 71 0.949 836 72 0.920 805 73 0.892 775 74 0.865 747 75 0.838 719 76 0.813 693 77 0.789 669 78 0.765 645 79 0.743 623 80 0.722 602 81 0.702 583 82 0.683 564 83 0.665 547 84 0.648 531 85 0.632 516 86 0.617 502 87 0.603 489 88 0.590 477 89 0.577 466 90 0.566 456 91 0.555 446 92 0.545 436 93 0.535 427 94 0.525 419 95 0.515 410 96 0.506 402 97 0.496 393 98 0.486 385
99 0.476 376 100 0.466 367 101 0.454 357 102 0.442 346 103 0.429 335 104 0.416 324 105 0.401 312 106 0.386 299 107 0.370 285
THERMISTOR JACKETED CABLE SENSOR TUBE BEND SLIGHTLY BEFORE WELL INSERTION
3/16 in.
4 in.
THERMISTOR WELL
Fig. 21 — Thermistor Replacement (T1, T2, T5, or T6)
X
COOLER
MEASURE TO TOP OF WELD COUPLING FOR PROPER INSERTION (SEE TABLE 41)
PACKING NUT
FERRULE
LEAD END (30GX080-176, ALL 30HX) PLUG END (30GX205-265)
Fig. 22 — Thermistor (Liquid Level Sensor) Replacement
61
Page 62
Table 40 — Thermistor Temperatures vs
Resistance, Motor Temperature Thermistors
TEMP
(F)
TEMP
(C)
RESISTANCE
(Ohms)
−22 −30 88,480.0
−13 −25 65,205.0
−4 −20 48,536.0 5 −15 36,476.0
14 −10 27,663.0 23 −5 21,163.0 32 0 16,325.0 41 5 12,696.0 50 10 9,949.5 59 15 7,855.5 68 20 6,246.0 77 25 5,000.0 86 30 4,028.4 95 35 3,265.7
104 40 2,663.2
113 45 2,184.2 122 50 1,801.2 131 55 1,493.1 140 60 1,243.9 149 65 1,041.4 158 70 875.8 167 75 739.7 176 80 627.6 185 85 534.9 194 90 457.7 203 95 393.3 212 100 339.3 221 105 293.8 230 110 255.3 239 115 222.6 248 120 194.8
NOTE: Motor temperature thermistor values must be verified using resistance. Voltage drop cannot be used.
Table 41 — Thermistor Depth
UNIT MODEL
NUMBER
THERMISTOR DEPTH
‘‘X’’-in. (mm)
30GX080-090 6.00 (152.4) 30GX105-115 4.25 (108.0) 30GX125-136 5.56 (141.2) 30GX150,151 6.00 (152.4) 30GX160,161 4.25 (108.0) 30GX175,176 4.25 (108.0) 30GX205-226 3.94 (100.0) 30GX250-265 4.82 (122.4) 30HXA,C076-086 5.13 (130.3) 30HXA,C096 6.00 (152.4) 30HXA,C106 4.25 (108.0) 30HXA,C116-126 5.13 (130.3) 30HXA,C136-146 6.00 (152.4) 30HXA,C161-171 4.25 (108.0) 30HXA,C186 5.56 (141.2) 30HXA,C206 3.94 (100.0) 30HXA,C246-271 4.82 (122.4)
Table 42 — Calibrating Pressure Transducers
(Pressure Gage Installed)
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
CALIBRATION OFFSET
CIRCUIT A PRESSURE
Discharge Pressure
84.2 PSI
Current reading is displayed.
Discharge Pressure
85.0 PSI
Enter gage pressure reading to nearest tenth. Control will allow offset of up to 6 psig. Transducer calibration is now complete.
Safety Devices — The 30GX/HX chillers contain many
safety devices and protection logic built into the electronic control. Following is a description of the major safeties.
COMPRESSOR PROTECTION Motor Overload — One factory preset solid-state overload
protects each compressor against overcurrent. Do not by­pass the overload or make any changes to the overload setting. Determine the cause for trouble and correct the prob­lem before resetting a tripped overload. In addition to the overload, each compressor is further protected by the Compressor Protection Module. Each module has a factory installed and configured 8-pin header. The configuration of this header defines the must-trip amps at which the CPM will turn the compressor off. SeeAppendixD for correct set­ting of overload and configuration headers.
Each CPM board also reads the status of each compres­sor’s high-pressure switch. All compressors have factory­installed high-pressure switches. For 30GX units, the switch is set to trip at 303 ± 7 psig (2089 ± 48 kPa). The setting for 30HXA units is 275 ± 7 psig (1896 ± 48 kPa) and for 30HXC units the setting is 191 ± 7 psig (1317 ± 48 kPa). If the switch opens during operation, the compressor will be shut down. The CPM will reset automatically when the switch closes, however, a manual reset is required to restart the compressor.
OIL SEPARATOR HEATERS(30GX)— Each oil separator circuit has a heater mounted on the underside of the vessel. The heater is energized with control circuit power. After a prolonged shutdown or service job, additional time may be required before starting the unit. Oil heaters are energized when the discharge gas temperature falls below 105 F (40.6 C). The heaters are deenergized when the discharge gas temperature rises above 110 F (43.3 C). The control will allow the chiller to attempt to start with the heaters ener­gized and will keep the heaters on, even when running, until the discharge gas temperature reaches 110 F (43.3 C). Note that the oil heaters are deenergized if the oil level switch is open.
COOLER PROTECTION Low Water Temperature — Microprocessor is programmed to shut the chiller down if the leaving fluid temperature drops below 34 F (1.1 C) for water or more than 8° F (4.4° C) below set point for brine units. When the fluid temperature rises 6° F (3.3° C) above the leaving fluid set point, the safety resets and the chiller restarts. Reset is automatic as long as this is the first occurrence of the day.
IMPORTANT: If the unit is installed in an area where ambient temperatures fall below 32 F (0° C), inhibited ethylene glycol or other suitable solution must be used in the chilled fluid circuit.
Relief Devices — Fusible plugs are located in each cir-
cuit (30GX only) between the condenser and the liquid line shutoff valve.
PRESSURE RELIEFVALVES — Valves are installed in each circuit and are located on all coolers. One relief valve is also installed on each 30HXC condenser. Both circuits’ oil sepa­rators on 30GX and 30HXA units have factory-installed relief valves as well. These valves are designed to relieve if an abnormal pressure condition arises. Relief valves on all coolers and 30HXC condensers relieve at 220 psi (1517 kPa). Relief valves on 30GX and 30HXA oil separators relieve at 320 psi (2206 kPa). Units with factory-installed suction serv­ice valves also have a relief valve in each compressor dis­charge line. These valves are designed to relieve at 350 psig (2413 kPa). These valves should not be capped. If a valve relieves, it should be replaced. If the valve is not replaced, it may relieve at a lower pressure, or leak due to trapped dirt from the system which may prevent resealing.
62
Page 63
COMPRESSOR A1
COMPRESSOR B1
3
3
2
1
COOLER
CONDENSER (30HXC MODEL) OIL SEPARATOR (30HXA MODEL)
2
1
4
4
1 2
3
3
4
DISCHARGE PRESSURE SUCTION PRESSURE
OIL PRESSURE
ECONOMIZER PRESSURE (LOCATED IN MOTOR COOLING LINE)
COMPRESSOR A2
(206-271 ONLY)
Fig. 23A — 30HX Pressure Transducer Locations
COMPRESSOR A1
COMPRESSOR B1
COOLER
OIL SEPARATORS (ONE VESSEL ON SMALL GX'S, TWO SEPARATE ON LARGER UNITS)
1
2
3
4
DISCHARGE PRESSURE SUCTION PRESSURE
OIL PRESSURE
ECONOMIZER PRESSURE (LOCATED IN MOTOR COOLING LINE)
4
4
3
3
2
2
1
1
3
COMPRESSOR A2 (205-265 ONLY)
Fig. 23B — 30GX Pressure Transducer Locations
63
Page 64
Pressure relief valves locatedoncoolerandcondensershells and 30HXA oil separator shells have3⁄4-in. NPT connec­tions for relief. The 30GX oil separators have1⁄2-in. male flare connections. Some local building codes require that re­lieved gases be removed. This connection allows conform­ance to this requirement.
Control Modules
Turn controller power offbeforeservicingcontrols.This ensures safety and prevents damage to controller.
PROCESSOR MODULE (PSIO-1), HIGH-VOLTAGE RELAY MODULE (DSIO-HV), AND EXV DRIVER MODULE (DSIO-EXV), 12/6 MODULE (PSIO-2) — The PSIO and DSIO modules all perform continuous diagnostic evaluations of the condition of the hardware. Proper opera­tion of these modules is indicated by LEDs on the front sur­face of the DSIOs, and on the top horizontal surface of the PSIOs.
RED LED — Blinking continuously ata1to2second rate indicates proper operation. Lighted continuously indicates a problem requiring replacement of module. Off continuously indicates power should be checked. If there is no input power, check fuses. If fuse is bad, check for shorted secondary of transformer, tripped circuit breaker or bad module. On the PSIO module, if the light is blinking at a rate of twice per second, the module should be replaced.
GREEN LED — On a PSIO module, this is the green LED closest to COMM connectors. The other green LED on mod­ule indicates externalcommunications,whenused.GreenLED should always be blinking when power is on. It indicates modules are communicating properly. If green LED is not blinking, check red LED. If red LED is normal, check mod­ule address switches. Correct addresses are as follows:
PSIO-1 (Processor Module) — 01 CPM-A1 (Protection Module) — 21 CPM-A2 (Protection Module) — 29 CPM-B1 (Protection Module) — 37 DSIO (EXV Driver Module) — 50 DSIO-HV (Relay Module) — 62 PSIO-2 (12/6 I/O Module) — 74
The first number of the address for a DSIO module should
be set on the switch closest to the silver mounting plate.
If all modules indicate communication failure, check COMM plug on PSIO-1 module for proper seating. If a good connection is assured and condition persists, replace PSIO-1 module.
If only a DSIO module indicates communication failure, check COMM plug on that module for proper seating. If a good connection is assured and the condition persists, re­place the DSIO module.
All system operating intelligence rests in the PSIO-1 mod­ule, the module that controls unit. This module monitors conditions through input and output ports and through DSIO modules (high-voltage relay module and EXV driver module).
The machine operator communicates with microproces­sor through keypad and display module. Communication be­tween PSIO and other modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module.
On sensor bus terminal strips, terminal 1 of PSIO module is connected to terminal 1 of each of the other modules. Terminals 2 and 3 are connected in the same manner. See Fig. 24. If a terminal 2 wire is connected to terminal 1, sys­tem does not work.
In the 30GX,HX control box, the processor module (PSIO-1), DSIO-HV, keypad and display module and 5 vdc power supply are all powered from a common 21 vac power source (PSIO-1 and HSIO powered from 24 vac source on 30HX units) which connects to terminals 1 and 2 of the power connector on each module.Aseparate source of 21 vac power is used to power the PSIO-2 module and liquid level sensor heaters. A separate 12.5 vdc power source is used for the DSIO-EXV module through terminals 1 and 2 on the power connector.TheCPMmodulesareconnected to 24 vac power sources. Refer to Table 43 for control troubleshooting information.
Carrier Comfort Network (CCN) Interface — The
30GX,HX chiller units can be connected to the CCN if de­sired.Thecommunicationbuswiringis a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. The system elements are connected to the communi­cation bus in a daisy chain arrangement as shown in Fig. 24. The positive pin of each system element communication con­nector must be wired to the positive pins of the system el­ements on either side of it. This is also required for the nega­tive and signal ground pins of each system element. Wiring connections for CCN should be made at the COMM1 plug on the PSIO-1 module. Consult the CCN Contractor’sManual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Amer­ican Wire Gage) minimum stranded, tinned copper. In­dividual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating tem­perature range of −20 C to 60 C is required. Wire manu­factured byAlpha (2413 or 5463),American(A22503),Belden (8772), or Columbia (02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire net­work to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the com­munication bus cable exits from one building and enters an­other, the shields must be connected to grounds at the light­ning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (−) conductors. (Substitute appropri­ate colors for different colored cables.)
64
Page 65
Table 43 — Compressor Control Troubleshooting
SYMPTOMS CAUSE REMEDY
COMPRESSOR DOES NOT RUN
Power line open Check main disconnect. Control fuse open Check control circuit for ground or short. Replace fuse. High-Pressure Switch (HPS) tripped Move LOCAL/OFF/REMOTE switch to OFF position
then back to LOCAL or REMOTE position. Tripped motor overload Check the controls. Find cause of trip. Reset overload. Loose terminal connection Check connections. Improperly wired controls Check wiring and rewire. Low line voltage Check line voltage. Determine location of voltage drop
and remedy deficiency. Compressor motor defective Check motor winding for open or short. Replace com-
pressor if necessary. Seized compressor Replace compressor. Pre-lubrication not successful Check oil pump operation, oil pressure transducer, verify
oil level/flow switch operation.
COMPRESSOR CYCLES OFF ON LOW PRESSURE
Loss of charge Repair leak and recharge. Bad transducer Replace transducer. Low refrigerant charge Add refrigerant. Failed expansion device Repair/replace as needed.
COMPRESSOR SHUTS DOWN ON HIGH PRES­SURE CONTROL
High-pressure switch erratic in action Replace switch. Compressor discharge valve partially closed Open valve or replace if defective. Condenser fan(s) not operating (air cooled units) Check wiring. Repair or replace motor(s) if defective. Condenser coil plugged or dirty (air cooled units) Clean coil. Condenser water valve not operating (water
cooled units)
Check wiring. Repair or replace valve if defective Circuit overcharged Clean condenser.
Liquid valve closed* Open valve or replace if defective.
UNIT OPERATES LONG OR CONTINUOUSLY
Low refrigerant charge Add refrigerant. Control contacts fused Replace control. Partially plugged or plugged expansion valve or
filter drier
Clean or replace. Defective insulation Replace or repair.
Service load exceeding design capacity Keep doors and windows closed. Inefficient compressor Check loader solenoid valves. Replace if necessary.
SYSTEM NOISES Piping vibration Support piping as required.
Expansion valve hissing Add refrigerant.
Check for plugged liquid line filter drier. Compressor noisy Replace compressor (worn bearings).
Check for loose compressor bolts securing compressor
to cooler.
COMPRESSOR LOSES OIL Leak in system Find and repair leak.
Mechanical damage to rotors Replace compressor.
HOT LIQUID LINE Shortage of refrigerant due to leak Repair leak and recharge. FROSTED LIQUID LINE Shutoff valve partially closed or restricted Open valve or remove restriction. COMPRESSOR LOADERS
NOT WORKING PROPERLY
Burned out coil Replace coil. Defective capacity control valve Replace valve. Miswired solenoid Rewire correctly.
*30GX251, 265 sizes have two Circuit A discharge and liquid valves.
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
CPM-B1CPM-A1HSIO-IIPSIO-2-J8DSIO-EXV-J2
DSIO-HV-J2
PSIO-1-J8
Fig. 24 — Sensor Bus Wiring (Communications)
65
Page 66
3. Removethe 4-pin female plug from the PSIO-1 COMM1 plug and connect the red wire to terminal 1 of the plug, the white wire to terminal 2, and the black wire to ter­minal 3.
4. Insert the plug back into the COMM1 plug.
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector.Ifconditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
PROCESSOR MODULE (PSIO-1) Inputs — Each input channel has 3 terminals; only 2 of the
terminals are used.Applicationofmachinedetermineswhich terminals are used. Always refer to the individual unit wir­ing for terminal numbers.
Outputs — Output is 20 vdc or 4 to 20 mA. There are 3 ter­minals, only 2 of which are used, depending on the appli­cation. Refer to unit the wiring diagram.
NOTE: The 12/6 Input/Output module (PSIO-2) has iden­tical input and output configurations as the PSIO-1. There is NO operating software in the PSIO-2 module.
HIGH VOLTAGE RELAY MODULE (DSIO-HV) Inputs — Inputs on strip J3 are discrete inputs (ON/OFF).
When 24-vac power is applied across the 2 terminals in a channel it reads the input as an On signal. Zero volts input is read as an Off signal.
Outputs — TerminalstripsJ4andJ5areinternalrelayswhose coils are signaled to be turned on and off by the micro­processor (PSIO-1). The relays switch the circuit to which they are connected. No power is supplied to these connec­tions by DSIO-HV module.
Replacing Defective Processor Module — The
PSIO-1 module replacement part number is 30GX500110. The unit model and serial numbers are printed on the unit nameplate located on an exterior corner post (30GX) or the corner of the control box (30HX). The proper software and unit configuration data is factory installed by Carrier in the replacement module. Therefore, when ordering a replace­ment processor module (PSIO-1), specify the replacement part number, full unit model number, and serial number. If these numbers are not provided, the replacement module will be downloaded with the base software. The base software settings must be reconfigured by the installer in the field.
Verify the existing PSIO-1 module is defective by using
the procedure described in the Control Modules section.
Refer to Start-up Checklist for 30GX,HX Liquid Chillers (completed at time of original start-up) found in the job folder . This information is needed later in this procedure. If the checklist does not exist, fill out the current factory and
service configurationcodes( ) sectionsonanew check­list. Tailor the various options and configurations as needed
for this particular installation.
Electrical shock can cause personal injury. Disconnect all electrical power before servicing.
1. Check that all power to unit is off. Carefully disconnect all wires from defective module by unplugging the 6 con­nectors. It is not necessary to remove any of the indi­vidual wires from the connectors. Remove the screws securing the green ground wire and communication drain wire. Save the screws.
2. Remove the defective PSIO-1 module by removing its mounting screws with a Phillips screwdriver, and re­moving the module from the control box. Save thescrews for later use.
3. Use a small screwdriver to set the address switches S1 and S2 on the new PSIO module to exactly match the settings on the defective module.
4. Package the defective module in the carton of the new module for return to Carrier.
5. Mount the new module in the unit control box using a Phillips screwdriver and the screws saved in Step 2.
6. Reinstall all 6 wire connectors, the green ground wire, and the communications drain wire.
7. Carefully check all wiring connections before restoring power.
8. Verify the LOCAL/OFF/REMOTE switch is in the OFF position.
9. Restore control power. Verify the red and green lights on top of the PSIO-1 and on front of each DSIO module respond as described in Control Modules section. The keypad and display module should also begin its rotat­ing display.
Using the keypad and display module, press to verify that the software version number matches the
ER (engineering requirement) number shown on the PSIO-1 label.
10. Press , scroll down one level at a time, and check the 3 factory and 2 service configuration codes as re-
corded on checklist. These codes must exactly match the codes stored in the previous PSIO-1 module for proper unit operation. These should already be downloaded if the proper information was supplied when ordering the replacement module. If the codes do not match, the codes must be entered by the procedure described in the fac­tory service code section of Table 22.
11. Once all codes have been verified, and all configura­tions, set points, and schedules re-entered, return the LOCAL/OFF/REMOTE switch to its previous position.
WinterShutdown Preparation — At the end of each
cooling season the fluid should be drained from the system. However, due to the cooler circuiting, some fluid will re­main in the cooler after draining. To prevent freeze-up dam­age to the cooler tubes perform the following procedure.
1. If accessory cooler heaters have been installed, deener-
gize the heaters to prevent damage and possible safety hazards when draining, or when there is no liquid in the system. Remove Fuse 1 to deenergize the heaters. Drain the fluid from the system.
2. Isolate the cooler from the rest of the system with water
shut off valves.
3. Fill the cooler with an appropriate amount of unhibited
ethylene glycol solution (or other suitable corrosion­inhibitive antifreeze) for 15° F (8.3° C) below the ex­pected low ambient conditions.
4. Leavethe cooler filled with the antifreeze solution for the
winter, or drain if desired. Be sure to deenergize heaters (if installed) as explained in Step 1 to prevent damage. Use an approved method of disposal when removing the antifreeze solution.
66
Page 67
PRE-START-UP PROCEDURE
IMPORTANT: Before beginning Pre-Start-Up or Start­Up, complete the Start-Up Checklist for the 30GX,HX Liquid Chillers on pages CL-1 to CL-8. This Check­list assures proper start-up of the chiller, and provides a record of unit condition, application requirements, system information and operation at initial start-up. The checklist should be removed from the manual and kept with the job file for future reference.
IMPORTANT: DO NOTATTEMPTTOSTARTTHE CHILLER UNTILTHE FOLLOWING CHECKSHAVE BEEN COMPLETED.
System Check
1. Check all auxiliary components such as the chilled fluid circulating pump, air-handlingequipment,orotherequip­ment to which the chiller supplies liquid. Consult the manufacturer’s instructions. If the unit has field-installed accessories, be sure all are properly installed and wired correctly. Refer to the unit wiring diagrams.
2. Check the cooler flow switch for proper configuration and operation ( from HSIO). Ensure the switch
closes when the pump is on and opens when the pump is turned off. A flow switch must be installed.
3. Openthedischargeandliquidvalvesineach circuit. The discharge shutof fvalvesarein-lineballtypeandareopen when parallel with the refrigerant flow.
4. If factory-installed option is installed, open the suction service valves in each circuit. Service valve is located below the compressor in the cooler suction connection flange.
5. Open the oil shutoff valves located by the oil pre-filter. Open bubbler tube valve on 30HX machines equipped with economizers.
6. Check the tightness of all electrical connections. Check incoming power supply for proper nameplate voltage.
7. Check to ensure the unit is level per the installation instructions.
8. Check the incoming power supply for proper phasing. This can be done by turning on both the line voltage and control voltage power supplies. Leave the LOCAL/OFF/ REMOTE switch in the OFF position. If the incoming power is not phased correctly, the CPM will generate
an alarm for voltage phase reversal. Press for CircuitAand for Circuit B at the HSIOtocheck
for this alarm. Scroll up and locate the Feedback value (displayed in units of volts). If a value of 7.0 appears, a voltage phase reversal has been identified and requires incoming power supply phase change. If this is the case, shut down all power supplies and switch any 2 in­coming power leads at the control box terminal block.
DO NOT make any changes to the factory installed compressor power wiring in the control box or at the compressor junction box. Doing so will cause permanent damage to the compressor and will re­quire compressor replacement. Proper phasing has already been checked at the factory.
For those units with 2 incoming terminal blocks, the volt­age sequence is sensed at one terminal block only.Check the phasing to ensure that both circuits match. If the incoming power is still phased incorrectly at the
second terminal block, a current phase reversal alarm will be generated when an attempt is made to start this compressor. The compressor will be shut down within 15 milliseconds. To correct this, interchange 2 power leads at this terminal block only.
9. Check all field configuration data and set points.
10. Enter correct date, time, and operating schedule(s).
11. Verify operation of solenoids, pumps, valves, compres­sors, fans, etc. as listed in the Checklist.
12. Open condenser water valves. Check condenser water pump for proper operation (30HX).
START-UP AND OPERATION
Actual Start-Up —
Actual start-up should be done only under supervision of a qualified refrigeration mechanic and qualified Carrier Comfort Network personnel.
1. Set leaving fluid temperature. No cooling range adjust-
ment is necessary.
2. Start chilled fluid pump and condenser pump (30HXC) if
not controlled by unit.
3. Switch LOCAL/OFF/REMOTE switch to LOCAL or
REMOTE.
4. Provided there is a load on the chiller, allow the machine
to operate and confirm that everything is functioning prop­erly.Verify that the leaving fluid temperature agrees with the cooling set point (1 or 2), or if reset is being used, the modified set point. Chiller is controlling to the Control
Point displayed under .
OperatingSequence— The chiller is started by switch-
ing the LOCAL/OFF/REMOTE switch to either LOCAL or REMOTE. On a command for cooling, the oil pump is turned on to start the pre-lubrication process. After 20 seconds, the oil solenoid is opened and the control reads the oil pressure from the transducer and determines if sufficient pressure has been built up. If there is not sufficient pressure, an alarm is generated after the second attempt and the compressor is not started.
Upon building pressure, the compressor is allowed to start. For across-the-line (XL) start chillers, the compressor starts and comes up to full speed within 1 to 3 seconds. For Wye­Delta start chillers, contactors 1M and S (starter contactor assembly) are closed and the compressor is started in a Wye configuration. This method reduces the locked rotor current requirements by approximately60%whilemaintainingenough torque to bring the compressor up to full speed.
After 5 seconds, the CPM module switches out contactor S and brings in contactor 2M, which runs the motor in a Delta configuration (same configuration in which XL units run). The oil pump will shut off within 10 seconds after the compressor is started. Once the compressor is successfully running, the control loads the compressor and adds addi­tional stages of capacity as needed to satisfy the leaving fluid set point. Head pressure is controlled by fan cycling (30GX) or can be controlled with a field installed accessory Motor­mastert III controller (30GX) or field installed condenser water valves (30HX).
If cooler pump controlisenabled,thecoolerpumpis started. If condenser pump control (30HXC) is enabled, the con­denser pump is started (Type 1).
67
Page 68
FIELD WIRING
Field wiring is shown in Fig. 25-37.
LEGEND FOR FIG. 25-37
ALM — Alarm C—Contactor CFC — Condenser Fan Contactor CPR — Condenser Pump Relay CWP — Chilled Water Pump DSIO — High Voltage Relay Module EQUIP — Equipment EXV — Electronic Expansion Valve FU — Fuse GFI-CO — Ground Fault Interrupter Convenience Outlet GND — Ground NEC — National Electrical Code PL — Plug PSIO — Processor Sensor Input/Output Module RB — Relay Board
TB — Terminal Block
Field-Wired Factory Wired
FIELD CONTROL POWER SUPPLY
NEC FUSED DISCONNECT
230 V CONTROL CIRCUITS USE 15 AMP MAXIMUM FROM SEPARATE POWER SUPPLY
115 V CONTROL CIRCUITS USE 30 AMP MAXIMUM FROM SEPARATE POWER SUPPLY
2
1
GND
TB4
Fig. 25 — Power Supply Wiring
EQUIP GND
TB2
TB2
BLK
BLK
T1
T2
K6
SEPARATE 115 OR 230 V FIELD POWER SUPPLY
RELAY BOARD 1
2
3
ALM
MAX. LOAD ALLOWED FOR THE ALARM RELAY IS 125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
FIELD SUPPLIED
Fig. 26 — Remote Alarm Relay Accessory Wiring; 30HXA,C
RELAY BOARD 2
K3
T4
T3
SEPARATE 115 OR 230 V FIELD POWER SUPPLY
EQUIP GND
ALM
MAX. LOAD ALLOWED FOR THE ALARM RELAY IS 125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
FIELD SUPPLIED
Fig. 27 — Remote Alarm Relay Accessory Wiring; 30GX
68
Page 69
RELAY BOARD 1
K3
T4
T3
BLK
BLK
TB2
TB2
4
5
C1
C2
EQUIP GND
SEPARATE 115 OR 230 V FIELD POWER SUPPLY
CWP
MAX. LOAD ALLOWED FOR THE CWP RELAY IS 125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
ACCESSORY ONLY
Fig. 28 — Chilled Water Pump Relay Wiring; 30HXA,C
SEPARATE 115 OR 230 V FIELD POWER SUPPLY
K3
RELAY BOARD 1
EQUIP GND
C2C1
T3
T4
CWP
MAX. LOAD ALLOWED FOR THE CWP RELAY IS 125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
ACCESSORY ONLY
Fig. 29 — Chilled Water Pump Relay Wiring; 30GX
69
Page 70
GFI-CO
GRN/YEL
SILVER SCREWSBRASS SCREWS
BLK
BLU
1
15 AMPS
FU1
TEST
RESET
ACCESSORY
TB4
WHT
TB4
2
Fig. 30 — Ground Fault Interrupter-Convenience Outlet Accessory Wiring
BRN
BRN
VIO
VIO
PNK
PNK
ORN BLU
BLU
BLU
RED
REDBLU
ORN
BLK
BLK
BLK
BLK
230V CONTROL CIRCUIT WIRING 115V CONTROL CIRCUIT WIRING
Fig. 31 — Oil Pump Motor Junction Box Wiring
TB4
WHT
2
MINIMUM LOAD CONTROL CIRCUIT B
MINIMUM LOAD CONTROL CIRCUIT A
GRA
PNK
T3
T1
RELAY BOARD 2
NOTE: Gray, Pink, and White wires are included in the control box as part of the factory wire harness. Field supplied and installed wire is needed from control box to solenoid valves.
Fig. 32 — Minimum Load Valve Accessory Wiring
70
Page 71
T6
BLK
K5
RB2PL2-3
RELAY BOARD 2
K4
RB2PL2-5
C1
C2
2
TB2
6
C1
C2
TB2
CPR/
CFCB
BLK
1
CFCA
TB4
FIELD SUPPLIED
Fig. 33 — Condenser Pump Relay Wiring, 30HXC and Remote Condenser Fan On/Off Wiring, 30HXA
COOLER FLOW SWITCH
11
RED
CHILLED WATER PUMP INTERLOCK CONTACTS
TB2
3
DSIO (EXV)-J3
TB2
12
Fig. 34 — Chilled Water Interlock and Flow Switch Input Wiring
13 14
RED
OFF
REMOTE ON/OFF CONTACTS
REMOTE
TB2 TB2
TB2
1
RED
RED
DSIO (EXV)-J3
12
Fig. 35 — Remote On/Off Switch Input Wiring
MAX. LOAD ALLOWED AT TB2-1 AND TB2-6 IS 125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLTS.
71
Page 72
FIELD SUPPLIED AND POWERED 4-20 mA SIGNAL
FIELD SUPPLIED AND POWERED 4-20 mA SIGNAL
OUTDOOR AIR THERMISTOR FIELD SUPPLIED
4-20 mA WATER VALVE
+
-
+
-
4-20 mA SIGNAL GENERATOR TEMPERATURE RESET
4-20 mA SIGNAL GENERATOR DEMAND LIMIT
47
46
36
35
31
28
23
22
20
19
CONDENSER ENTERING WA TER THERMIST OR FIELD SUPPLIED
CONDENSER LEAVING WA TER THERMIST OR FIELD SUPPLIED
+
FIELD SUPPLIED 4-20 mA WATER VALVE (30HXC ONLY)
PSIO-2, J6 PLUG
TOP
18
17
15
14
PSIO-2, J7 PLUGS
REMOTE DUAL SETPOINT
ICE DONE
25
500 OHM, 1/2 WATT FIELD SUPPLIED RESISTOR
500 OHM, 1/2 WATT FIELD SUPPLIED RESISTOR
CONDENSER FLOW SWITCH
BOTTOM
-
32
FIELD SUPPLIED 24 VAC
Fig. 36 — PSIO-2 Wiring for Accessories and Field-Installed Options, 30HX Units
72
Page 73
FIELD SUPPLIED AND POWERED 4-20 mA SIGNAL
FIELD SUPPLIED AND POWERED 4-20 mA SIGNAL
TOP
PSIO-2, J7 PLUGS
BOTTOM
4-20 mA SIGNAL GENERATOR TEMPERATURE RESET
+
-
500 OHM, 1/2 WATT FIELD SUPPLIED RESISTOR
14
13
OUTDOOR AIR THERMISTOR FIELD SUPPLIED
20
21
22
+
-
4-20 mA SIGNAL GENERATOR DEMAND LIMIT
23
500 OHM, 1/2 WATT FIELD SUPPLIED RESISTOR
47
46
PSIO-2, J6 PLUG
49
50
VIO
GRA
VIO
GRA
VIO
GRA
VIO
GRA
MOTORMASTER® OPTION (080-150, 160) CIRCUIT A (151, 161-265)
MOTORMASTER OPTION CIRCUIT B (151, 161-265)
31
28
REMOTE DUAL SETPOINT
ICE DONE
25
34
STAGE 2
STAGE 1
DEMAND LIMIT EXTERNAL SWITCH
35
FIELD SUPPLIED 24 VAC
24
SPACE TEMPERATURE SENSOR FIELD SUPPLIED
Fig. 37 — PSIO-2 Wiring for Accessories and Field-Installed Options, 30GX Units
73
Page 74
APPENDIX A
Compressor Must Trip Amps (Determined by CPM Modules)
COMPRESSOR MUST TRIP AMPS
2-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, B1
Must Trip Amps
30GX080
575-3-60 98, 82 380-3-60 148,124
208/230-3-60 270,226
460-3-60 122,102 230-3-50 256,212
380/415-3-50 156,128
30GX090
575-3-60 120, 82 380-3-60 180,124
208/230-3-60 328,226
460-3-60 148,102 230-3-50 310,212
380/415-3-50 188,128
30GX105
230-3-50 344,238
380/415-3-50 208,144
30GX106
575-3-60 134, 92 380-3-60 202,140
208/230-3-60 368,254
460-3-60 168,114 230-3-50 344,238
380/415-3-50 208,144
30GX115
575-3-60 162, 92 380-3-60 246,140
208/230-3-60 448,254
460-3-60 204,114 230-3-50 418,238
380/415-3-50 254,144
30GX125
575-3-60 162,110 380-3-60 246,168
208/230-3-60 448,306
460-3-60 204,138 230-3-50 418,288
380/415-3-50 254,174
30GX136
575-3-60 162,134 380-3-60 246,202
208/230-3-60 448,368
460-3-60 204,168 230-3-50 418,344
380/415-3-50 254,208
30GX150
230-3-50 344,520
380/415-3-50 208,314
30GX151
575-3-60 198,134 380-3-60 300,202
208/230-3-60 546,368
460-3-60 240,168
30GX160
230-3-50 418,520
380/415-3-50 254,314
30GX161
575-3-60 198,162 380-3-60 300,246
208/230-3-60 546,448
460-3-60 248,204 230-3-50 520,418
380/415-3-50 314,254
30GX175
230-3-50 520,520
380/415-3-50 314,314
30GX176
575-3-60 198,198 380-3-60 300,300
208/230-3-60 546,546
460-3-60 248,248
30HXA076
575-3-60 82, 82 380-3-60 124,124 346-3-50 140,140
208/230-3-60 226,226
460-3-60 102,102 230-3-50 212,212
380/415-3-50 128,128
30HXA086
575-3-60 98, 82 380-3-60 148,124 346-3-50 170,140
208/230-3-60 270,226
460-3-60 122,102 230-3-50 256,212
380/415-3-50 156,128
COMPRESSOR MUST TRIP AMPS
2-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, B1
Must Trip Amps
30HXA096
575-3-60 120, 82 380-3-60 180,124 346-3-50 206,140
208/230-3-60 328,226
460-3-60 148,102 230-3-50 310,212
380/415-3-50 188,128
30HXA106
575-3-60 144, 82 380-3-60 218,124 346-3-50 250,140
208/230-3-60 400,226
460-3-60 180,102 230-3-50 376,212
380/415-3-50 228,128
30HXA116
575-3-60 144, 98 380-3-60 218,148 346-3-50 250,170
208/230-3-60 400,270
460-3-60 180,122 230-3-50 376,256
380/415-3-50 228,156
30HXA126
575-3-60 144,120 380-3-60 218,180 346-3-50 250,206
208/230-3-60 400,328
460-3-60 180,148 230-3-50 376,310
380/415-3-50 228,188
30HXA136
575-3-60 176,120 380-3-60 266,180 346-3-50 306,206
208/230-3-60 486,328
460-3-60 220,148 230-3-50 462,310
380/415-3-50 280,188
30HXA146
575-3-60 176,144 380-3-60 266,218 346-3-50 306,250
208/230-3-60 486,400
460-3-60 220,180 230-3-50 462,376
380/415-3-50 280,228
30HXA161
575-3-60 198,134 380-3-60 300,202 346-3-50 344,228
208/230-3-60 546,368
460-3-60 248,168 230-3-50 520,344
380/415-3-50 314,208
30HXA171
575-3-60 162,198 380-3-60 246,300 346-3-50 278,344
208/230-3-60 448,546
460-3-60 204,248 230-3-50 418,520
380/415-3-50 254,314
30HXA186
575-3-60 198,198 380-3-60 300,300 346-3-50 344,344
208/230-3-60 546,546
460-3-60 248,248 230-3-50 520,520
380/415-3-50 314,314
74
Page 75
APPENDIX A (cont)
Compressor Must Trip Amps (Determined by CPM Modules) (cont)
COMPRESSOR MUST TRIP AMPS
2-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, B1
Must Trip Amps
30HXC076
575-3-60 56, 56 380-3-60 84, 84 346-3-50 96, 96
208/230-3-60 154,154
460-3-60 70, 70 230-3-50 144,144
380/415-3-50 88, 88
30HXC086
575-3-60 68, 56 380-3-60 102, 84 346-3-50 116, 96
208/230-3-60 186,154
460-3-60 84, 70 230-3-50 176,144
380/415-3-50 106, 88
30HXC096
575-3-60 82, 56 380-3-60 124, 84 346-3-50 140, 96
208/230-3-60 226,154
460-3-60 104, 70 230-3-50 212,144
380/415-3-50 128, 88
30HXC106
575-3-60 100, 56 380-3-60 150, 84 346-3-50 168, 96
208/230-3-60 274,154
460-3-60 124, 70 230-3-50 254,144
380/415-3-50 154, 88
30HXC116
575-3-60 100, 68 380-3-60 150,102 346-3-50 168,116
208/230-3-60 274,186
460-3-60 124, 84 230-3-50 254,176
380/415-3-50 154,106
30HXC126
575-3-60 100, 82 380-3-60 150,124 346-3-50 168,140
208/230-3-60 274,226
460-3-60 124,104 230-3-50 254,212
380/415-3-50 154,128
COMPRESSOR MUST TRIP AMPS
2-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, B1
Must Trip Amps
30HXC136
575-3-60 120, 82 380-3-60 180,124 346-3-50 204,140
208/230-3-60 328,226
460-3-60 148,104 230-3-50 308,212
380/415-3-50 186,128
30HXC146
575-3-60 120,100 380-3-60 180,150 346-3-50 204,168
208/230-3-60 328,274
460-3-60 148,124 230-3-50 308,254
380/415-3-50 186,154
30HXC161
575-3-60 130, 90 380-3-60 196,136 346-3-50 220,152
208/230-3-60 358,246
460-3-60 162,112 230-3-50 332,228
380/415-3-50 202,138
30HXC171
575-3-60 108,130 380-3-60 164,196 346-3-50 182,220
208/230-3-60 298,358
460-3-60 136,162 230-3-50 274,332
380/415-3-50 166,202
30HXC186
575-3-60 130,130 380-3-60 196,196 346-3-50 220,220
208/230-3-60 358,358
460-3-60 162,162 230-3-50 332,332
380/415-3-50 202,202
75
Page 76
APPENDIX A (cont)
Compressor Must Trip Amps (Determined by CPM Modules) (cont)
COMPRESSOR MUST TRIP AMPS
3-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, A2, B1
Must Trip Amps
30GX205
230-3-50 418,238,520
380/415-3-50 254,144,314
30GX206
575-3-60 198, 92,162 380-3-60 300,140,246
208/230-3-60 546,254,448
460-3-60 248,114,204
30GX225
230-3-50 520,288,520
380/415-3-50 314,174,314
30GX226
575-3-60 198,110,198 380-3-60 300,168,300
208/230-3-60 546,306,546
460-3-60 248,138,248 230-3-50 520,288,520
380/415-3-50 314,174,314
30GX250
230-3-50 520,418,520
380/415-3-50 314,254,314
30GX251
575-3-60 198,198,162 380-3-60 300,300,246
208/230-3-60 546,546,448
460-3-60 248,248,204
30GX265
575-3-60 198,198,198 380-3-60 300,300,300
208/230-3-60 546,546,546
460-3-60 248,248,248 230-3-50 520,520,520
380/415-3-50 314,314,314
30HXA206
575-3-60 162, 92,198 380-3-60 246,138,300 346-3-50 278,158,344
208/230-3-60 448,254,546
460-3-60 204,116,248 230-3-50 418,238,520
380/415-3-50 254,144,314
30HXA246
575-3-60 198,134,198 380-3-60 300,202,300 346-3-50 344,228,344
208/230-3-60 546,368,546
460-3-60 248,168,248 230-3-50 520,344,520
380/415-3-50 314,208,314
COMPRESSOR MUST TRIP AMPS
3-COMPRESSOR UNITS
Unit Size Unit Voltage
Compressor A1, A2, B1
Must Trip Amps
30HXA261
575-3-60 198,162,198 380-3-60 300,246,300 346-3-50 344,278,344
208/230-3-60 546,448,546
460-3-60 248,204,248 230-3-50 520,418,520
380/415-3-50 314,254,314
30HXA271
575-3-60 198,198,198 380-3-60 300,300,300 346-3-50 344,344,344
208/230-3-60 546,546,546
460-3-60 248,248,248 230-3-50 520,520,520
380/415-3-50 314,314,314
30HXC206
575-3-60 108, 62,130 380-3-60 164, 92,196 346-3-50 182,104,220
208/230-3-60 298,168,358
460-3-60 136, 76,162 230-3-50 274,156,332
380/415-3-50 166, 94,202
30HXC246
575-3-60 130, 90,130 380-3-60 196,136,196 346-3-50 220,152,220
208/230-3-60 358,246,358
460-3-60 162,112,162 230-3-50 332,228,332
380/415-3-50 202,138,202
30HXC261
575-3-60 130,108,130 380-3-60 196,164,196 346-3-50 220,182,220
208/230-3-60 358,298,358
460-3-60 162,136,162 230-3-50 332,274,332
380/415-3-50 202,166,202
30HXC271
575-3-60 130,130,130 380-3-60 196,196,196 346-3-50 220,220,220
208/230-3-60 358,358,358
460-3-60 162,162,162 230-3-50 332,332,332
380/415-3-50 202,202,202
76
Page 77
APPENDIX B
CapacityLoading Sequence Example — The fol-
lowing tables show the loading sequence for a 30HX186 (50/50 split) and a 30HX161 (59/41 split) chiller. Each
compressor has 2 loaders. There is no difference in opera­tion between ‘ ‘Staged’’and ‘‘Equal’’ circuit loadingon2com­pressor chillers.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 2-COMPRESSOR UNIT)
STAGE
COMP
A1
LOADER
A1
LOADER
A2
COMP
B1
LOADER
B1
LOADER
B2
% TOTAL
CAPACITY
(50/50 Split)
% TOTAL
CAPACITY
(59/41 Split)
0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 20.0 23.5 2 1 1 0 0 0 0 35.0 41.1 3 1 1 1 0 0 0 50.0 58.8 4 1 1 0 1 1 0 70.0 70.0 5 1 1 0 1 1 1 85.0 82.4 6 1 1 1 1 1 1 100.0 100.0
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 2-COMPRESSOR UNIT)
STAGE
COMP
A1
LOADER
A1
LOADER
A2
COMP
B1
LOADER
B1
LOADER
B2
% TOTAL
CAPACITY
(50/50 Split)
% TOTAL
CAPACITY
(59/41 Split)
0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 20.0 23.5 2 1 1 0 0 0 0 35.0 41.1
3 1 1 1 0 0 0 50.0 58.8 3A 1 0 0 1 0 0 40.0 40.0 3B 1 0 0 1 1 0 55.0 52.4
4 1 0 0 1 1 1 70.0 64.7
5 1 1 0 1 1 1 85.0 82.4
6 1 1 1 1 1 1 100.0 100.0
LEGEND
0—Off 1—On
NOTES:
1. Stage 3A(and 3Bfor59/41 split) isnotused bythealgorithm when increasing stages.Stage3 (and 2for59/41 split) isnotused when decreasing stages.
2. The % Total Capacities above are calculated based on compres­sor nominal tons. For the case of the 59/41 split above, the 30HX uses compressors with flow rates of 250 and 174 cfm (from com­pressor model numbers 06N_1250 and 06N_1174), which repre­sent nominal tons of 80 and 56 (respectively) at 60 Hz.A factor of 40% is used when no loaders are energized and a factor of 70% is usedwhen Loader 1isenergized. Thecapacityshown for Stage 3B above is calculated as follows:
% Total Capacity = [(0.40 x 80 + 0.70 x 56)/(80 + 56)] x 100%
= 52.4%
Nominal Tons
COMPRESSOR
PART NO.
60 Hz NOM.
TONS
50 Hz NOM.
TONS
06N_1123 39 — 06N_1146 46 39 06N_1174 56 46 06N_1209 66 56 06N_1250 80 66 06N_1300 —80
77
Page 78
APPENDIX B (cont)
The followingtablesshowthe loading sequence for 30HX206
(57/43 split) and 30HX271 (67/33 split) chillers. All
compressors have two loaders and the chillers are config­ured for equal circuit loading. See Note 2.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 3-COMPRESSOR UNIT)
STAGE
COMPA1LOADERA1LOADERA2COMPA2COMPB1LOADERB1LOADER
B2
% TOTAL
CAPACITY
(57/43 Split)
% TOTAL
CAPACITY
(67/33 Split)
0 0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 0 14.3 13.3 2 1 1 0 0 0 0 0 25.0 23.3 3 1 1 1 0 0 0 0 35.7 33.3 4 1 1 0 0 1 1 0 55.2 46.7 5 1 1 0 0 1 1 1 68.2 56.7 6 1 1 1 0 1 1 1 78.9 66.7 7 1 1 0 1 1 1 1 83.0 80.0 8 1 1 1 1 1 1 1 100.0 100.0
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 3-COMPRESSOR UNIT)
STAGE
COMPA1LOADERA1LOADERA2COMPA2COMPB1LOADERB1LOADER
B2
% TOTAL
CAPACITY
(57/43 Split)
% TOTAL
CAPACITY
(67/33 Split)
0 0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 0 14.3 13.3 2 1 1 0 0 0 0 0 25.0 23.3 3 1 1 1 0 0 0 0 35.7 33.3
3A 1 0 0 0 1 0 0 31.6 26.7
4 1 0 0 0 1 1 0 44.5 36.7 5 1 0 0 0 1 1 1 57.5 46.7 6 1 1 0 0 1 1 1 68.2 56.7 7 1 1 1 0 1 1 1 78.9 66.7
7A 1 0 0 1 1 1 1 65.9 60.0
8 1 1 0 1 1 1 1 83.0 80.0 9 1 1 1 1 1 1 1 100.0 100.0
LEGEND
0—Off 1—On
NOTES:
1. Stages 3A and 7A are not used by the algorithm when increasing stages. Stages 3 and 7 are not used by the algorithm when de­creasing stages.
2. The loadingsequencefor 30GX205-265unitsis the sameas those shown for the 30HZ206,271 above.
78
Page 79
APPENDIX B (cont)
The followingtablesshowthe loading sequence for 30HX206 (57/43 split) and 30HX271 (67/33 split) chillers. All com­pressors have two loaders and the chiller is configured for
staged circuit loading. Loaders A1 on compressors A1 and A2 are energized in parallel. The same is true for Loaders A2 on both compressors A1 and A2. See Note 3.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 3-COMPRESSOR UNIT)
STAGE
COMPA1LOADERA1LOADERA2COMPA2COMP
B1
LOADERB1LOADER
B2
% TOTAL
CAPACITY
(57/43 Split)
% TOTAL
CAPACITY
(67/33 Split)
0 0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 0 14.3 13.3 2 1 1 0 0 0 0 0 25.0 23.3 3 1 1 1 0 0 0 0 35.7 33.3 4 1 1 0 1 0 0 0 39.7 46.7 5 1 1 1 1 0 0 0 56.8 66.7 6 1 1 1 1 1 1 0 87.0 90.0 7 1 1 1 1 1 1 1 100.0 100.0
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 3-COMPRESSOR UNIT)
STAGE
COMPA1LOADERA1LOADERA2COMPA2COMP
B1
LOADERB1LOADER
B2
% TOTAL
CAPACITY
(57/43 Split)
% TOTAL
CAPACITY
(67/33 Split)
0 0 0 0 0 0 0 0 0.0 0.0 1 1 0 0 0 0 0 0 14.3 13.3 2 1 1 0 0 0 0 0 25.0 23.3 3 1 1 1 0 0 0 0 35.7 33.3
3A 1 0 0 1 0 0 0 22.7 26.7
4 1 1 0 1 0 0 0 39.7 46.7 5 1 1 1 1 0 0 0 56.8 66.7 6 1 1 1 1 1 0 0 74.1 80.0 7 1 1 1 1 1 1 0 87.0 90.0 8 1 1 1 1 1 1 1 100.0 100.0
LEGEND
0—Off 1—On
NOTES:
1. Stage 3A is not used by the algorithm when increasing stages.
Stage 3 is not used by the algorithm when decreasing stages.
2. The % Total Capacities above are calculated based on compres-
sor nominal tons. For the case of the 57/43 split above, the 30HX uses compressors with flow rates of 209, 123 and 250 cfm (from compressormodelnumbers 06N_1209, 06N_123and 06N_1250),
which represent nominal tons of 66, 39 and 80 (respectively) at 60 Hz.Afactorof 40% is usedwhenno loaders are energizedand a factor of 70% is usedwhenLoader1is energized. The capacity shown for Stage 4 above is calculated as follows:
% Total Capacity = [0.70 x 66 + 0.70 x 39 + 0.0 x 80)/(66 + 39 +
80)] x 100% = 39.7%
3. The loadingsequencefor 30GX205-265unitsis the sameas those shown for the 30HX206,271 above.
79
Page 80
APPENDIX C
The following are the available accessories for 30GX/HXA/HXC units.
ACCESSORY
PART NUMBER
USED ON DESCRIPTION OF ACCESSORY COMMENTS
30GX-900-001 30GX080-105 Condenser Grille Package 30GX-900-002 30GX106-125 Condenser Grille Package 30GX-900-003 30GX136, 150, 160 Condenser Grille Package 30GX-900-013 30GX151, 161, 175, 205, 225 Condenser Grille Package 30GX-900-024 30GX176 Condenser Grille Package 30GX-900-009 30GX206, 226, 250 Condenser Grille Package 30GX-900-010 30GX251, 265 Condenser Grille Package 30GX-900-004 30GX (115 V Control) Minimum Load Valve both circuits 30GX-900-005 30GX (230 V Control) Minimum Load Valve both circuits 30GX-900-006 30GX (460 V) Control Transformer 30GX-900-007 30GX (575 V) Control Transformer 30GX-900-008 30GX (208 V) Control Transformer 30GX-900-012 30GX080-150, 160 3-Phase MotormasterT Control single controller 30GX-900-014 30GX151, 161-265 3-Phase Motormaster Control two controllers 30GX-900-015 30GX080-265 Sound Enclosure/Hail Guard/Wind Baffle header end only 30GX-900-016 30GX080-105 Sound Enclosure/Hail Guard/Wind Baffle one side per package 30GX-900-017 30GX106-125 Sound Enclosure/Hail Guard/Wind Baffle one side per package 30GX-900-018 30GX136, 150, 160 Sound Enclosure/Hail Guard/Wind Baffle one side per package
30GX-900-019 30GX151, 161, 175, 205, 225 Sound Enclosure/Hail Guard/Wind Baffle
one side per package (151, 161, 175) cooler side only (205, 225)
30GX-900-020 30GX176, 206, 226, 250 Sound Enclosure/Hail Guard/Wind Baffle
one side per package (176) cooler side only (206, 226, 250)
30GX-900-028 30GX205, 225 Sound Enclosure/Hail Guard/Wind Baffle control box side only 30GX-900-029 30GX206, 226, 250 Sound Enclosure/Hail Guard/Wind Baffle control box side only 30GX-900-030 30GX251, 265 Sound Enclosure/Hail Guard/Wind Baffle cooler side only 30GX-900-031 30GX251, 265 Sound Enclosure/Hail Guard/Wind Baffle control box side only 30GX-900-021 30GX (230 V Control) Cooler Heater 30GX-900-022 30GX (115 V Control) Cooler Heater 30GX-900-023 30GX080-265 Vibration Isolation Pads
30GX-900-025 30GX105-136, 160-176
Insulation Kit (169, 3 Pass Cooler with Economizer)
tubesheets/heads/economizer
30GX-900-026 30GX150, 151
Insulation Kit (149, 2 Pass Cooler with Economizer)
tubesheets/heads/economizer
30GX-900-027 30GX150, 151
Insulation Kit (149, 1 Pass Cooler with Economizer)
tubesheets/heads/economizer
30HX-900-001 30HX116-271 Sound Enclosure Panels 30HX-900-011 30HX076-106 Sound Enclosure Panels
30HX-900-002
30GX080-090, 150, 151 30HX076-096, 116-146
Victaulic Cooler Connections (14 in.)
30HX-900-003
30GX105-136, 160-176 30HX106, 161-186
Victaulic Cooler Connections (16 in.)
30HX-900-014
30GX205-265 30HX206-271
Victaulic Cooler Connections (18 in.)
30HX-900-015 30HX206-271 Victaulic Condenser Connection (22 in.) 30HX-900-004 30HX076-146 Victaulic Condenser (18 in.) 30HX-900-005 30HX161-186 Victaulic Condenser (20 in.) 30HX-900-006 30HX (230, 460 V) Control Transformer 30HX-900-013 30HX (575 V) Control Transformer 30HX-900-007 30GX,HX all LID 2B Enhanced Remote Controller 30HX-900-008 30HX (115 V Control) Minimum Load Valve single circuit 30HX-900-009 30HX (230 V Control) Minimum Load Valve single circuit 30HX-900-010 30HX076-271 Vibration Isolation Pad
30HX-900-016
30GX080,090 30HX076-096
Insulation Kit (149, 3 Pass Cooler no Economizer)
tubesheets/heads
30HX-900-017
30GX080,090 30HX076-096
Insulation Kit (149, 2 Pass Cooler no Economizer)
tubesheets/heads
30HX-900-020
30GX105-136,160-176 30HX161-186
Insulation Kit (169, 2 Pass Cooler with Economizer)
tubesheets/heads/economizer
30HX-900-021
30GX160-176 30HX161-186
Insulation Kit (169, 1 Pass Cooler with Economizer)
tubesheets/heads/economizer
30HX-900-022
30GX205-265 30GX206-271
Insulation Kit (189, 2 Pass Cooler with Economizer)
tubesheets/heads/economizer
30HX-900-023
30GX205-265 30HX206-271
Insulation Kit (189, 1 Pass Cooler with Economizer)
tubesheets/heads/economizer
80
Page 81
APPENDIX D
Compressor Protection Module Configuration Header Punch-Outs and Overload Settings
2-Compressor Units
UNIT
MODEL NUMBER
PUNCH OUTS
FOR CPM-A
PUNCH OUTS
FOR CPM-B
COMP A1
OVERLOAD SETTING
COMP B1
OVERLOAD SETTING
30GX-080---1 1,2,3,6,7,8 1,2,3,5,6,7,8 85 71 30GX-080---2 1,2,5,6,7 1,2,4,5,7 128 107 30GX-080---5 1,4,8 1,3,6,7,8 234 195 30GX-080---6 1,2,4,5,7,8 1,2,3,6,8 106 88 30GX-080---8 1,4,5 1,3,5,6,7 223 183 30GX-080---9 1,2,5,7 1,2,4,5 135 111
30GX-090---1 1,2,4,5,6 1,2,3,5,6,7,8 103 71 30GX-090---2 1,3,4,5,6,7 1,2,4,5,7 156 107 30GX-090---5 2,3,4,6 1,3,5,7,8 285 195 30GX-090---6 1,2,5,6,7 1,2,3,6,8 129 88 30GX-090---8 2,3,4,5,6,8 1,3,5,6,7 269 183 30GX-090---9 1,3,4,5,7 1,2,4,5 163 111
30GX-105---8 2,3,5,6 1,3,8 299 207 30GX-105---9 1,3,4 1,2,4 181 125
30GX-106---1 1,2,4,6,8 1,2,3,5,7 116 80 30GX-106---2 1,3,4,7,8 1,2,4,7 175 120 30GX-106---5 2,3 1,4,5,8 320 220 30GX-106---6 1,2,6 1,2,4,5,6,7,8 145 100 30GX-106---8 2,3,5,6 1,3,8 299 207 30GX-106---9 1,3,4 1,2,4 181 125
30GX-115---1 1,2,6,7,8 1,2,3,5,7 141 80 30GX-115---2 1,4,5,6,8 1,2,4,7 213 120 30GX-115---5 3,4,5 1,4,5,8 390 220 30GX-115---6 1,3,4,7 1,2,4,5,6,7,8 176 100 30GX-115---8 2,6,7,8 1,3,8 363 207 30GX-115---9 1,4,5,8 1,2,4 220 125
30GX-125---1 1,2,6,7,8 1,2,3,8 141 96 30GX-125---2 1,4,5,6,8 1,2,6 213 145 30GX-125---5 3,4,5 2,3,4,5,6,7,8 390 265 30GX-125---6 1,3,4,7 1,2,4,7,8 176 120 30GX-125---8 2,6,7,8 1,5 363 250 30GX-125---9 1,4,5,8 1,2,8 220 151
30GX-136---1 1,2,6,7,8 1,2,4,6,8 141 116 30GX-136---2 1,4,5,6,8 1,3,4,7,8 213 175 30GX-136---5 3,4,5 2,3 390 320 30GX-136---6 1,3,4,7 1,2,6 176 145 30GX-136---8 2,6,7,8 2,3,5,6 363 299 30GX-136---9 1,4,5,8 1,3,4 220 181
30GX-150---8 2,3,5,6 4,6 299 451 30GX-150---9 1,3,4 2,3,4,5,7,8 181 273
30GX-151---1 1,3,4,6,8 1,2,4,6,8 172 116 30GX-151---2 1,7 1,3,4,7,8 260 175 30GX-151---5 6,7,8 2,3 475 320 30GX-151---6 1,4,5,6 1,2,6 215 145
30GX-160---8 2,6,7,8 4,6 363 451 30GX-160---9 1,4,5,8 2,3,4,5,7,8 220 273
30GX-161---1 1,3,4,6,8 1,2,6,7,8 172 141 30GX-161---2 1,7 1,4,5,6,8 260 213 30GX-161---5 6,7,8 3,4,5 475 390 30GX-161---6 1,4,5,6 1,3,4,7 215 176 30GX-161---8 4,6 2,6,7,8 451 363 30GX-161---9 2,3,4,5,7,8 1,4,5,8 273 220
30GX-175---8 4,6 4,6 451 451 30GX-175---9 2,3,4,5,7,8 2,3,4,5,7,8 273 273
30GX-176---1 1,3,4,6,8 1,3,4,6,8 172 172 30GX-176---2 1,7 1,7 260 260 30GX-176---5 6,7,8 6,7,8 475 475 30GX-176---6 1,4,5,6 1,4,5,6 215 215
30HXA076---1 1,2,3,5,6,7,8 1,2,3,5,6,7,8 71 71 30HXA076---2 1,2,4,5,7 1,2,4,5,7 107 107 30HXA076---3 1,2,4,7 1,2,4,7 122 122 30HXA076---5 1,3,6,7,8 1,3,6,7,8 195 195 30HXA076---6 1,2,3,6,8 1,2,3,6,8 88 88 30HXA076---8 1,3,5,6,7 1,3,5,6,7 183 183 30HXA076---9 1,2,4,5 1,2,4,5 111 111
30HXA086---1 1,2,3,6,7,8 1,2,3,5,6,7,8 85 71 30HXA086---2 1,2,5,6,7 1,2,4,5,7 128 107 30HXA086---3 1,2,7,8 1,2,4,7 148 122 30HXA086---5 1,4,8 1,3,6,7,8 234 195 30HXA086---6 1,2,4,5,7,8 1,2,3,6,8 106 88 30HXA086---8 1,4,5 1,3,5,6,7 223 183 30HXA086---9 1,2,5,7 1,2,4,5 135 111
81
Page 82
APPENDIX D (cont)
Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)
2-Compressor Units
UNIT
MODEL NUMBER
PUNCH OUTS
FOR CPM-A
PUNCH OUTS
FOR CPM-B
COMP A1
OVERLOAD SETTING
COMP B1
OVERLOAD SETTING
30HXA096---1 1,2,4,5,6 1,2,3,5,6,7,8 103 71 30HXA096---2 1,3,4,5,6,7 1,2,4,5,7 156 107 30HXA096---3 1,3,4,8 1,2,4,7 179 122 30HXA096---5 2,3,4,6 1,3,6,7,8 285 195 30HXA096---6 1,2,5,6,7 1,2,3,6,8 129 88 30HXA096---8 2,3,4,5,6,8 1,3,5,6,7 269 183 30HXA096---9 1,3,4,5,7 1,2,4,5 163 111
30HXA106---1 1,2,4 1,2,3,5,6,7,8 125 71 30HXA106---2 1,3,5,7,8 1,2,4,5,7 190 107 30HXA106---3 1,4,5,7,8 1,2,4,7 217 122 30HXA106---5 2,4 1,3,6,7,8 347 195 30HXA106---6 1,3,4,5,6,7 1,2,3,6,8 157 88 30HXA106---8 2,4,5,6 1,3,5,6,7 326 183 30HXA106---9 1,3,6,7 1,2,4,5 198 111
30HXA116---1 1,2,4 1,2,3,6,7,8 125 85 30HXA116---2 1,3,5,7,8 1,2,5,6,7 190 128 30HXA116---3 1,4,5,6,8 1,2,7,8 217 148 30HXA116---5 2,4 1,4,8 347 234 30HXA116---6 1,3,4,5,6,7 1,2,4,5,7,8 157 106 30HXA116---8 2,4,5,6 1,4,5 326 223 30HXA116---9 1,3,6,7 1,2,5,7 198 135
30HXA126---1 1,2,4 1,2,4,5,6 125 103 30HXA126---2 1,3,5,7,8 1,3,4,5,6,7 190 156 30HXA126---3 1,4,5,7,8 1,3,4,8 217 179 30HXA126---5 2,4 2,3,4,6 347 285 30HXA126---6 1,3,4,5,6,7 1,2,5,6,7 157 129 30HXA126---8 2,4,5,6 2,3,4,5,6,8 326 269 30HXA126---9 1,3,6,7 1,3,4,5,7 198 163
30HXA136---1 1,2 1,2,4,5,6 153 103 30HXA136---2 1,4,7,8 1,3,4,5,6,7 231 156 30HXA136---3 2,3,4,5,6,7,8 1,3,4,8 266 179 30HXA136---5 3,6,8 2,3,4,6 423 285 30HXA136---6 1,3,5,7 1,2,5,6,7 191 129 30HXA136---8 3,4,8 2,3,4,5,6,8 401 269 30HXA136---9 1,5,6 1,3,4,5,7 243 163
30HXA146---1 1,2 1,2,4 153 125 30HXA146---2 1,4,7,8 1,3,5,7,8 231 190 30HXA146---3 2,3,4,5,6,7,8 1,4,5,7,8 266 217 30HXA146---5 3,6,8 2,4 423 347 30HXA146---6 1,3,5,7 1,3,4,5,6,7 191 157 30HXA146---8 3,4,8 2,4,5,6 401 326 30HXA146---9 1,5,6 1,3,6,7 243 198
30HXA161---1 1,3,4,6,8 1,2,4,6,8 172 116 30HXA161---2 1,7 1,3,4,7,8 260 175 30HXA161---3 2,3,4,5 1,3,6,7 299 199 30HXA161---5 6,7,8 2,3 475 320 30HXA161---6 1,4,5,6 1,2,6 215 145 30HXA161---8 4,6 2,3,5,6 451 299 30HXA161---9 2,3,4,5,7,8 1,3,4 273 181
30HXA171---1 1,2,6,7,8 1,3,4,6,8 141 172 30HXA171---2 1,4,5,6,8 1,7 213 260 30HXA171---3 1,5,6,8 2,3,5,6 241 299 30HXA171---5 3,4,5 6,7,8 390 475 30HXA171---6 1,3,4,7 1,4,5,6 176 215 30HXA171---8 2,6,7,8 4,6 363 451 30HXA171---9 1,4,5,8 2,3,4,5,7,8 220 273
30HXA186---1 1,3,4,6,8 1,3,4,6,8 172 172 30HXA186---2 1,7 1,7 260 260 30HXA186---3 2,3,5,6 2,3,5,6 299 299 30HXA186---5 6,7,8 6,7,8 475 475 30HXA186---6 1,4,5,6 1,4,5,6 215 215 30HXA186---8 4,6 4,6 451 451 30HXA186---9 2,3,4,5,7,8 2,3,4,5,7,8 273 273
30HXC076---1 1,2,3,4,5,6 1,2,3,4,5,6 50 50 30HXC076---2 1,2,3,5,6,7 1,2,3,5,6,7 73 73 30HXC076---3 1,2,3,5 1,2,3,5 83 83 30HXC076---5 1,2,5,7,8 1,2,5,7,8 133 133 30HXC076---6 1,2,3,4,6,8 1,2,3,4,6,8 60 60 30HXC076---8 1,2,4 1,2,4 125 125 30HXC076---9 1,2,3,5,6 1,2,3,5,6 76 76
30HXC086---1 1,2,3,4,6,7 1,2,3,4,5,6 58 50 30HXC086---2 1,2,3,6,8 1,2,3,5,6,7 88 73 30HXC086---3 1,2,4,5,6,7 1,2,3,5 101 83 30HXC086---5 1,3,4,5,7,8 1,2,5,7,8 161 133 30HXC086---6 1,2,3,5,6,7 1,2,3,4,6,8 73 60 30HXC086---8 1,2 1,2,4 152 125 30HXC086---9 1,2,3,7,8 1,2,3,5,6 92 76
82
Page 83
APPENDIX D (cont)
Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)
2-Compressor Units
UNIT
MODEL NUMBER
PUNCH OUTS
FOR CPM-A
PUNCH OUTS
FOR CPM-B
COMP A1
OVERLOAD SETTING
COMP B1
OVERLOAD SETTING
30HXC096---1 1,2,3,5,6,7,8 1,2,3,4,5,6 71 50 30HXC096---2 1,2,4,5,7 1,2,3,5,6,7 108 73 30HXC096---3 1,2,4,7 1,2,3,5 122 83 30HXC096---5 1,3,6,7,8 1,2,5,7,8 197 133 30HXC096---6 1,2,3,6 1,2,3,4,6,8 89 60 30HXC096---8 1,3,5,6,7 1,2,4 183 125 30HXC096---9 1,2,4,5 1,2,3,5,6 111 76
30HXC106---1 1,2,3,6,7 1,2,3,4,5,6 86 50 30HXC106---2 1,2,5,6,8 1,2,3,5,6,7 130 73 30HXC106---3 1,2,6 1,2,3,5 146 83 30HXC106---5 1,5,6,7,8 1,2,5,7,8 238 133 30HXC106---6 1,2,4,5,7 1,2,3,4,6,8 108 60 30HXC106---8 1,4,5,8 1,2,4 220 125 30HXC106---9 1,2,5,7,8 1,2,3,5,6 133 76
30HXC116---1 1,2,3,6,7 1,2,3,4,6,7 86 58 30HXC116---2 1,2,5,6,8 1,2,3,6,8 130 88 30HXC116---3 1,2,6 1,2,4,5,6,7 146 101 30HXC116---5 1,5,6,7,8 1,3,4,5,7,8 238 161 30HXC116---6 1,2,4,5,7 1,2,3,5,6,7 108 73 30HXC116---8 1,4,5,8 1,2 220 152 30HXC116---9 1,2,5,7,8 1,2,3,7,8 133 92
30HXC126---1 1,2,3,6,7 1,2,3,5,6,7,8 86 71 30HXC126---2 1,2,5,6,8 1,2,4,5,7 130 108 30HXC126---3 1,2,6 1,2,4,7 146 122 30HXC126---5 1,5,6,7,8 1,3,6,7,8 238 197 30HXC126---6 1,2,4,5,7 1,2,3,6 108 89 30HXC126---8 1,4,5,8 1,3,5,6,7 220 183 30HXC126---9 1,2,5,7,8 1,2,4,5 133 111
30HXC136---1 1,2,4,5,6 1,2,3,5,6,7,8 103 71 30HXC136---2 1,3,4,5,6,7 1,2,4,5,7 156 108 30HXC136---3 1,3,4,7 1,2,4,7 177 122 30HXC136---5 2,3,4,6 1,3,6,7,8 285 197 30HXC136---6 1,2,5,6,7 1,2,3,6 129 89 30HXC136---8 2,3,4,5,6,7 1,3,5,6,7 267 183 30HXC136---9 1,3,4,5,7,8 1,2,4,5 162 111
30HXC146---1 1,2,4,5,6 1,2,3,6,7 103 86 30HXC146---2 1,3,4,5,6,7 1,2,5,6,8 156 130 30HXC146---3 1,3,4,7 1,2,6 177 146 30HXC146---5 2,3,4,6 1,5,6,7,8 285 238 30HXC146---6 1,2,5,6,7 1,2,4,5,7 129 108 30HXC146---8 2,3,4,5,6,7 1,4,5,8 267 220 30HXC146---9 1,3,4,5,7,8 1,2,5,7,8 162 133
30HXC161---1 1,2,4,6,7,8 1,2,3,5,7,8 112 78 30HXC161---2 1,3,4,6,7 1,2,4,6 170 117 30HXC161---3 1,3,5,7 1,2,5,6 192 132 30HXC161---5 2,3,6,8 1,4,5,6,8 310 214 30HXC161---6 1,2,6,7,8 1,2,3 140 97 30HXC161---8 2,4,5,7 1,3,6,7 289 198 30HXC161---9 1,3,4,7,8 1,2,4,7,8 175 120
30HXC171---1 1,2,3,7 1,2,4,6,7,8 94 112 30HXC171---2 1,2,6,7 1,3,4,6,7 142 170 30HXC171---3 1,3,4,5,6,8 1,3,5,7 158 192 30HXC171---5 1,7,8 2,3,6,8 259 310 30HXC171---6 1,2,4,6 1,2,6,7,8 117 140 30HXC171---8 1,5,6,7,8 2,3,4,7 237 289 30HXC171---9 1,2,6,8 1,3,4,7,8 144 175
30HXC186---1 1,2,4,6,7,8 1,2,4,6,7,8 112 112 30HXC186---2 1,3,4,6,7 1,3,4,6,7 170 170 30HXC186---3 1,3,5,7 1,3,5,7 192 192 30HXC186---5 2,3,6,8 2,3,6,8 310 310 30HXC186---6 1,2,6,7,8 1,2,6,7,8 140 140 30HXC186---8 2,3,4,7 2,3,4,7 289 289 30HXC186---9 1,3,4,7,8 1,3,4,7,8 175 175
83
Page 84
APPENDIX D (cont)
Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)
3-Compressor Units
UNIT
MODEL NUMBER
PUNCH OUTS
FOR CPM-A1
PUNCH OUTS
FOR CPM-A2
PUNCH OUTS
FOR CPM-B1
COMP A1
OVERLOAD
SETTING
COMP A2
OVERLOAD
SETTING
COMP B1
OVERLOAD
SETTING
30GX205---8 2,6,7,8 1,3,8 4,6 363 207 451 30GX205---9 1,4,5,8 1,2,4 2,3,4,5,7,8 220 125 273
30GX206---1 1,3,4,6,8 1,2,3,5,7 1,2,6,7,8 172 80 141 30GX206---2 1,7 1,2,4,7 1,4,5,6,8 260 120 213 30GX206---5 6,7,8 1,4,5,8 3,4,5 475 220 390 30GX206---6 1,4,5,6 1,2,4,5,6,7,8 1,3,4,7 215 100 176
30GX225---8 4,6 1,5 4,6 451 250 451 30GX225---9 2,3,4,5,7,8 1,2,8 2,3,4,5,7,8 273 151 273
30GX226---1 1,3,4,6,8 1,2,3,8 1,3,4,6,8 172 96 172 30GX226---2 1,7 1,2,6 1,7 260 145 260 30GX226---5 6,7,8 2,3,4,5,6,7,8 6,7,8 475 265 475 30GX226---6 1,4,5,6 1,2,4,7,8 1,4,5,6 215 120 215 30GX226---8 4,6 1,5 4,6 451 250 451 30GX226---9 2,3,4,5,7,8 1,2,8 2,3,4,5,7,8 273 151 273
30GX250---8 4,6 2,6,7,8 4,6 451 363 451 30GX250---9 2,3,4,5,7,8 1,4,5,6 2,3,4,5,7,8 273 220 273
30GX251---1 1,3,4,6,8 1,3,4,6,8 1,2,6,7,8 172 172 141 30GX251---2 1,7 1,7 1,4,5,6,8 260 260 213 30GX251---5 6,7,8 6,7,8 3,4,5 475 475 390 30GX251---6 1,4,5,6 1,4,5,6 1,3,4,7 215 215 176
30GX265---1 1,3,4,6,8 1,3,4,6,8 1,3,4,6,8 172 172 172 30GX265---2 1,7 1,7 1,7 260 260 260 30GX265---5 6,7,8 6,7,8 6,7,8 475 475 475 30GX265---6 1,4,5,6 1,4,5,6 1,4,5,6 215 215 215 30GX265---8 4,6 4,6 4,6 451 451 451 30GX265---9 2,3,4,5,7,8 2,3,4,5,7,8 2,3,4,5,7,8 273 273 273
30HXA206---1 1,2,6,7,8 1,2,3,5,7 1,3,4,6,8 141 80 172 30HXA206---2 1,4,5,6,8 1,2,4,7 1,7 213 120 260 30HXA206---3 1,5,6,8 1,2,5,8 2,3,5,6 241 137 299 30HXA206---5 3,4,5 1,4,5,8 6,7,8 390 220 475 30HXA206---6 1,3,4,7 1,2,4,5,6,7,8 1,4,5,6 176 100 215 30HXA206---8 2,6,7,8 1,3,8 4,6 363 207 451 30HXA206---9 1,4,5,8 1,2,4 2,3,4,5,7,8 220 125 273
30HXA246---1 1,3,4,6,8 1,2,4,6,8 1,3,4,6,8 172 116 172 30HXA246---2 1,7 1,3,4,7,8 1,7 260 175 260 30HXA246---3 2,3,5,6 1,3,6,7 2,3,5,6 299 199 299 30HXA246---5 6,7,8 2,3 6,7,8 475 320 475 30HXA246---6 1,4,5,6 1,2,6 1,4,5,6 215 145 215 30HXA246---8 4,6 2,3,5,6 4,6 451 299 451 30HXA246---9 2,3,4,5,7,8 1,3,4 2,3,4,5,7,8 273 181 273
84
Page 85
APPENDIX D (cont)
Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)
3-Compressor Units
UNIT
MODEL NUMBER
PUNCH OUTS
FOR CPM-A1
PUNCH OUTS
FOR CPM-A2
PUNCH OUTS
FOR CPM-B1
COMP A1
OVERLOAD
SETTING
COMP A2
OVERLOAD
SETTING
COMP B1
OVERLOAD
SETTING
30HXA261---1 1,3,4,6,8 1,2,6,7,8 1,3,4,6,8 172 141 172 30HXA261---2 1,7 1,4,5,6,8 1,7 260 213 260 30HXA261---3 2,3,5,6 1,5,6,8 2,3,5,6 299 241 299 30HXA261---5 6,7,8 3,4,5 6,7,8 475 390 475 30HXA261---6 1,4,5,6 1,3,4,7 1,4,5,6 215 176 215 30HXA261---8 4,6 2,6,7,8 4,6 451 363 451 30HXA261---9 2,3,4,5,7,8 1,4,5,8 2,3,4,5,7,8 273 220 273
30HXA271---1 1,3,4,6,8 1,3,4,6,8 1,3,4,6,8 172 172 172 30HXA271---2 1,7 1,7 1,7 260 260 260 30HXA271---3 2,3,5,6 2,3,5,6 2,3,5,6 299 299 299 30HXA271---5 6,7,8 6,7,8 6,7,8 475 475 475 30HXA271---6 1,4,5,6 1,4,5,6 1,4,5,6 215 215 215 30HXA271---8 4,6 4,6 4,6 451 451 451 30HXA271---9 2,3,4,5,7,8 2,3,4,5,7,8 2,3,4,5,7,8 273 273 273
30HXC206---1 1,2,3,7 1,2,3,4,5,8 1,2,4,6,7,8 94 53 112 30HXC206---2 1,2,6,7 1,2,3,5,7 1,3,4,6,7 142 80 170 30HXC206---3 1,3,4,5,6,8 1,2,3,6 1,3,5,7 158 90 192 30HXC206---5 1,7,8 1,2,6 2,3,6,8 259 145 310 30HXC206---6 1,2,4,6 1,2,3,4,7 1,2,6,7,8 117 66 140 30HXC206---8 1,5,6,7,8 1,2,5,7 2,3,4,7 237 135 289 30HXC206---9 1,2,6,8 1,2,3,5,8 1,3,4,7,8 144 82 175
30HXC246---1 1,2,4,6,7,8 1,2,3,5,7,8 1,2,4,6,7,8 112 78 112 30HXC246---2 1,3,4,6,7 1,2,4,6 1,3,4,6,7 170 117 170 30HXC246---3 1,3,5,7 1,2,5,6 1,3,5,7 192 132 192 30HXC246---5 2,3,6,8 1,4,5,6,8 2,3,6,8 310 214 310 30HXC246---6 1,2,6,7,8 1,2,3 1,2,6,7,8 140 97 140 30HXC246---8 2,3,4,7 1,3,6,7 2,3,4,7 289 198 289 30HXC246---9 1,3,4,7,8 1,2,4,7,8 1,3,4,7,8 175 120 175
30HXC261---1 1,2,4,6,7,8 1,2,3,7 1,2,4,6,7,8 112 94 112 30HXC261---2 1,3,4,6,7 1,2,6,7 1,3,4,6,7 170 142 170 30HXC261---3 1,3,5,7 1,3,4,5,6,8 1,3,5,7 192 158 192 30HXC261---5 2,3,6,8 1,7,8 2,3,6,8 310 259 310 30HXC261---6 1,2,6,7,8 1,2,4,6 1,2,6,7,8 140 117 140 30HXC261---8 2,3,4,7 1,5,6,7,8 2,3,4,7 289 237 289 30HXC261---9 1,3,4,7,8 1,2,6,8 1,3,4,7,8 175 144 175
30HXC271---1 1,2,4,6,7,8 1,2,4,6,7,8 1,2,4,6,7,8 112 112 112 30HXC271---2 1,3,4,6,7 1,3,4,6,7 1,3,4,6,7 170 170 170 30HXC271---3 1,3,5,7 1,3,5,7 1,3,5,7 192 192 192 30HXC271---5 2,3,6,8 2,3,6,8 2,3,6,8 310 310 310 30HXC271---6 1,2,6,7,8 1,2,6,7,8 1,2,6,7,8 140 140 140 30HXC271---8 2,3,4,7 2,3,4,7 2,3,4,7 289 289 289 30HXC271---9 1,3,4,7,8 1,3,4,7,8 1,3,4,7,8 175 175 175
85
Page 86
APPENDIX E
The following charts list pressure drops for coolers and condensers.
076, 086
116, 126
136, 146
161, 171
246-271
096
106
186
206
100
10
1
100
1000
COOLER FLOW RATE (GPM)
PRESSURE DROP (FT WG)
30HX COOLER PRESSURE DROP — ENGLISH
Unit Size Range
NOTE: Ft of water = 2.31 x change in psig.
076, 086
096
106
116, 126
136, 146
161, 171
186
206 246-271
1000
100
10
1
1
10
100
COOLER FLOW RATE (L/S)
PRESSURE DROP (KPA)
30HX COOLER PRESSURE DROP — SI
Unit Size Range
86
Page 87
APPENDIX E (cont)
30HX CONDENSER PRESSURE DROP — ENGLISH
Unit Size Range
NOTE: Ft of water = 2.31 x change in psig.
30HX CONDENSER PRESSURE DROP — SI
Unit Size Range
87
Page 88
APPENDIX E (cont)
30GX080-176 COOLER PRESSURE DROP —
ENGLISH
NOTE: Ft of water = 2.31 x change in psig.
30GX080-176 COOLER PRESSURE DROP —
SI
100
10
1
100
1000
COOLER FLOW RATE (GPM)
PRESSURE DROP (ft wg)
30GX205, 206
30GX225, 226
30GX250, 251, 265
30GX205-265 COOLER PRESSURE DROP —
ENGLISH
1000
100
10
1
10
100
COOLER FLOW RATE (L/s)
PRESSURE DROP (kpa)
30GX205, 206
30GX225, 226
30GX250, 251, 265
30GX205-265 COOLER PRESSURE DROP —
SI
88
Page 89
Typical System Components, 30GX, With Economizer
LEGEND
EXV — Electronic Expansion Valve
HPS — High Pressure Switch
APPENDIX F
89
Page 90
Typical System Components, 30HX, Without Economizer
LEGEND
EXV — Electronic Expansion Valve
HPS — High Pressure Switch
APPENDIX F (cont)
90
Page 91
INDEX
Accessing Functions and Subfunctions, 13 Actual Start-Up, 67 Adjusting PID Routines, 10 Alarms and Alerts, 43 Automatic Default Display, 13 Back Pressure Valve, 4 Burnout Clean-Up Procedure, 58 Capacity Control Overrides, 7 Capacity Control, 6 Capacity Sequence Determination, 7 Carrier Comfort Network (CCN) Interface, 64 Checking Display Codes, 43 Close Control, 7 Coil Cleaning, 53 Complete Unit Stoppage, 43 Compressor Alarm/Alert Circuit, 43 Compressor Changeout Sequence, 56 Compressor Protection Module (CPM), 3, 4 Compressor Protection, 62 Condenser Coils (30GX Only), 53 Condenser Fans (30GX Only), 54 Condenser Pump Control, 12 Control (LOR) Switch, 3 Control Modules, 64 Cooler and Condenser (30HXC) Pump Control, 10 Cooler Heater Control, 13 Cooler Protection, 62 Cooler Pump Control, 10 Demand Limit, 39 Demand Limit, (CCN Loadshed Controlled), 42 DSIO-HV Relay Module, 3, 64 Economizer Operation, 4 Electronic Expansion Device (EXD), 3 Electronic Expansion Device Module, 3 EXD Troubleshooting Procedure, 50 External Temperature Reset, 39 Externally Powered Demand Limit, 42 Externally Powered Reset, 39 EXV Driver Module (DSIO-EXV), 64 EXV Operation, 3 Field Wiring, 68 Filter Drier, 58 Head Pressure Control, 8 High Voltage Relay Module (DSIO-HV), 64, 66 History Function, 25 Inspecting/Cleaning Heat Exchangers, 53 Inspecting/Opening Economizers, 51 Inspecting/Opening Electronic Expansion Valves, 51 Keypad and Display Module (HSIO-II), 3, 13 Lead/Lag Determination, 7 Liquid Line Service Valve, 58
Loading Sequence, 6 Major System Components, 3 Minimum Load Valve, 7 Minutes Left for Start, 6 Minutes Off Time, 6 Moisture-Liquid Indicator, 58 Motor Cooling, 4 Oil Charging/Low Oil Recharging, 55 Oil Filter Maintenance, 56 Oil Pumps, 4 Oil Separator Heaters (30GX), 62 Operating Sequence, 67 Operation Data, 3 Power Failure External to the Unit, 43 Pre-Start-Up Procedure, 67 Pressure Relief Valves, 62 Pressure Transducer Calibration, 59 Pressure Transducers, 59 Processor Module (PSIO-1), 3, 64, 66 PSIO-2 (8052) Module, 3, 64 Refrigerant Charging/Adding Charge, 54 Relief Devices, 62 Replacing Defective Processor Module, 66 Replacing the External Oil Filter, 56 Replacing the Internal Oil Filter, 56 Restart Procedure, 43 Retubing, 52 Return Fluid Temperature Reset, 39 Safety Considerations, 1 Safety Devices, 62 Schedule Function, 37 Sensors, 4 Service Function, 30 Service, 52 Servicing Coolers and Condensers, 52 Set Point Function, 25 Single Circuit Stoppage, 43 Start-Up and Operation, 67 Start-Up Checklist, CL-1 Status Function, 16 System Check, 67 Temperature Reset, 39 Test Function, 25 Thermistor Replacement, 58 Thermistors, 58 Tightening Cooler/Condenser Head Bolts, 52 Troubleshooting, 43 Tube Plugging, 52 Unit Shutoff, 43 Water Treatment, 53 Winter Shutdown Preparation, 66 Wye-Delta vs. Across-the-Line (XL) Starting Option, 5
91
Page 92
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equip­ment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based for­mats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs that can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab5
PC903 CatalogNo.533-062 PrintedinU.S.A.Form30G,H-3TPg92 1099 1-98Replaces:30G,H-2T
Page 93
START-UP CHECKLIST FOR 30GX,HX LIQUID CHILLERS
(Remove and use for job file.)
A. Preliminary Information
JOB NAME LOCATION INSTALLING CONTRACTOR DISTRIBUTOR START-UP PERFORMED BY
EQUIPMENT:
MODEL
S/N
COMPRESSORS:
CIRCUIT A CIRCUIT B
1) MODEL #
1) MODEL #
S/N S/N
2) MODEL # 2) MODEL # S/N S/N
COOLER:
MODEL #
S/N
CONDENSER: (30HX ONLY)
MODEL #
S/N
AIR-HANDLING EQUIPMENT:
MANUFACTURER
MODEL # S/N
ADDITIONAL AIR-HANDLING UNITS AND ACCESSORIES
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-062 Printed in U.S.A. Form 30G,H-3T Pg CL-1 1-98 Replaces: 30G,H-2T
Page 94
B. Preliminary Equipment Check
IS THERE ANY SHIPPING DAMAGE? IF SO, WHERE
WILL THIS DAMAGE PREVENT UNIT START-UP?
M UNIT IS LEVEL IN ITS INSTALLATION M UNIT IS SUPPLIED WITH THE PROPER CONTROL VOLTAGE
VAC
M ELECTRICAL CIRCUIT WIRING HAS BEEN SIZED AND INSTALLED PROPERLY M UNIT GROUND WIRE HAS BEEN CONNECTED M ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY M ALL TERMINALS ARE TIGHT M ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES M ALL PLUG ASSEMBLIES ARE TIGHT
CHECK AIR-HANDLING SYSTEM
M ALL AIR HANDLERS ARE OPERATING M ALL CHILLED WATER VALVES ARE OPEN M ALL FLUID PIPING IS CONNECTED PROPERLY M ALL AIR HAS BEEN VENTED FROM THE SYSTEM M CHILLED WATER PUMP (CWP) IS OPERATING WITH THE CORRECT ROTATION
CWP AMPERAGE: RATED:
ACTUAL:
PUMP PRESSURES: INLET: OUTLET:
CHECK CONDENSER SYSTEM (30HX ONLY):
M ALL CONDENSER WATER VALVES ARE OPEN M ALL CONDENSER PIPING IS CONNECTED PROPERLY
ALL AIR HAS BEEN VENTED FROM THE SYSTEM M CONDENSER WATER PUMP IS OPERATING WITH THE CORRECT ROTATION
CONDENSER WATER PUMP AMP: RATED:
ACTUAL:
PUMP PRESSURES: INLET: OUTLET:
CHECK REMOTE CONDENSER SYSTEM (30HXA ONLY):
M ALL CONDENSER PIPING IS CONNECTED PROPERLY M CONDENSER LINES/CONDENSER HAS BEEN EVACUATED, AS REQUIRED
CL-2
Page 95
C. Unit Start-Up
M CWP STARTER HAS BEEN PROPERLY INTERLOCKED WITH THE CHILLER M ALL LIQUID VALVES ARE BACKSEATED M ALL DISCHARGE VALVES ARE OPEN M ALL SUCTION VALVES ARE OPEN, IF EQUIPPED M ALL OIL LINE VALVES ARE OPEN M UNIT HAS BEEN LEAK CHECKED
LOCATE, REPAIR, AND REPORT ANY REFRIGERANT LEAKS
M CHECK VOLTAGE IMBALANCE: AB AC BC
AVERAGE VOLTAGE = (SEE INSTALLATION INSTRUCTIONS) MAXIMUM DEVIATION =
(SEE INSTALLATION INSTRUCTIONS)
VOLTAGE IMBALANCE =
(SEE INSTALLATION INSTRUCTIONS) M VOLTAGE IMBALANCE IS LESS THAN 2% DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%. CONTACT LOCAL POWER
COMPANY FOR ASSISTANCE. M ALL INCOMING POWER VOLTAGE IS WITHIN RATED VOLTAGE RANGE
CHECK COMPRESSOR RUNNING CURRENT:
COMPRESSOR NO LOADERS ONE LOADER FULL LOAD
COMP A1,L1
AMPS AMPS AMPS
COMP A1,L2
AMPS AMPS AMPS
COMP A1,L3
AMPS AMPS AMPS
COMP B1,L1
AMPS AMPS AMPS
COMP B1,L2
AMPS AMPS AMPS
COMP B1,L3
AMPS AMPS AMPS
COMP A2,L1
AMPS AMPS AMPS
COMP A2,L2
AMPS AMPS AMPS
COMP A2,L3
AMPS AMPS AMPS
CHECK COOLER WATER LOOP:
WATER LOOP DESIGN VOLUME: GALLONS (LITERS) CALCULATED VOLUME
GALLONS (LITERS) 3 GALLONS/NOMINAL TON (3.32 LITERS/kW) FOR AIR CONDITIONING 6 GALLONS/NOMINAL TON (6.65 LITERS/kW) FOR PROCESS COOLING
M PROPER LOOP VOLUME ESTABLISHED M PROPER LOOP CORROSION INHIBITOR INCLUDED
GALLONS (LITERS) OF
M PROPER LOOP FREEZE PROTECTION INCLUDED, IF REQUIRED
GALLONS (LITERS) OF
M PIPING INCLUDES ELECTRIC HEATER TAPE, IF EXPOSED TO THE OUTSIDE M INLET PIPING TO COOLER INCLUDES A 40 MESH STRAINER
CL-3
Page 96
CHECK PRESSURE DROP ACROSS THE COOLER:
ENTERING COOLER:
PSIG (kPa)
LEAVING COOLER:
PSIG (kPa)
(LEAVING − ENTERING) × 2.31 FT OF H
2
O/PSIG = FT OF H2O
(LEAVING − ENTERING) × 0.334 M OF H
2
O/kPa = MOFH2O
PLOT COOLER PRESSURE DROP ON PERFORMANCE DATA CHART (IN PRODUCT DATA LITERATURE) TO DETERMINE TOTAL GALLONS/MINUTE (GPM) OR LITERS PER SECOND (L/S) AND FIND UNIT’S MINIMUM FLOW RATE.
TOTAL GPM (L/S): GPM/NOMINAL TON (L/S PER TON) =
M TOTAL GPM (L/S) IS GREATER THAN UNIT’S MINIMUM FLOW RATE
M TOTAL GPM (L/S) MEETS JOB SPECIFIED REQUIREMENT OF
GPM (L/S)
M COOLER HEATER FUSE INSTALLED, AND HEATERS ARE ACTIVE (IF USED)
CHECK CONDENSER WATER LOOP:
M PROPER LOOP CORROSION INHIBITOR INCLUDED
GALLONS (LITERS) OF
M INLET PIPING TO CONDENSER INCLUDES A 40 MESH STRAINER
CHECK PRESSURE DROP ACROSS THE CONDENSER (30HXC ONLY):
ENTERING CONDENSER: PSIG (kPa) LEAVING CONDENSER:
PSIG (kPa)
(LEAVING − ENTERING) × 2.31 FT OF H
2
O= FT OF H2O
(LEAVING − ENTERING) × 0.334 M OF H
2
O/kPa = MOFH2O
PLOT CONDENSER PRESSURE DROP ON PERFORMANCE DATACHART (IN PRODUCT DATALITERATURE) TO DETERMINE TOTAL GALLONS/MINUTE (GPM) OR LITERS PER SECOND (L/S) AND FIND UNIT’S MINIMUM FLOW RATE.
TOTAL GPM (L/S): GPM/NOMINAL TON (L/S PER TON) =
M TOTAL CONDENSER GPM (L/S) IS GREATER THAN UNIT’S MINIMUM FLOW RATE
M TOTAL GPM MEETS JOB SPECIFIED REQUIREMENT OF
GPM (L/S)
CL-4
Page 97
PERFORM TEST FUNCTION (INDICATE POSITIVE RESULT):
ONCE POWER IS SUPPLIED TO THE UNIT, CHECK THE DISPLAY FOR ANY ALARMS, SUCH AS PHASE REVER­SAL. FOLLOW THE TEST FUNCTION INSTRUCTIONS IN THE CONTROLS AND TROUBLESHOOTING LITERA­TURE. BE SURE TO CHECK FOR PROPER FAN ROTATION WITH THE FAN TEST SECTIONS. BE SURE ALL SERV­ICE VALVES ARE OPEN BEFORE BEGINNING THE COMPRESSOR TEST SECTION. ITEMS MARKED WITH ‘‘†’’ CAN BE TESTED ONLY IF THE UNIT IS CONFIGURED FOR THIS OPTION. DO NOT RUN OIL PUMPS FOR MORE THAN 20 SECONDS.
M LOADER A1 M LOADER B1
M LOADER A2 M LOADER B2
M MINIMUM LOAD VALVE A† M MINIMUM LOAD VALVE B†
M CIRCUIT A OIL HEATER M CIRCUIT B OIL HEATER
M A1 MOTOR COOLING SOLENOID M B1 MOTOR COOLING SOLENOID
M A2 MOTOR COOLING SOLENOID† M B2 MOTOR COOLING SOLENOID†
M CIRCUIT A OIL PUMP M CIRCUIT B OIL PUMP
M OIL SOLENOID A1 M OIL SOLENOID B1
M OIL SOLENOID A2† M OIL SOLENOID B2†
M CIRCUIT A EXV M FAN 1 (30GX)†
M CIRCUIT B EXV M FAN 2 (30GX)†
M CIRCUIT A WATER VALVE† M FAN 3 (30GX)†
M CIRCUIT A% FAN SPEED (GX)† M FAN 4 (30GX)†
M CIRCUIT B% FAN SPEED (GX)† M FAN 5 (30GX)†
M FAN 6 (30GX)†
M COOLER PUMP†
M COMPRESSOR A1 M CONDENSER PUMP†
M COMPRESSOR A2† M COOLER HEATER†
M COMPRESSOR B1 M ALARM RELAY†
M COMPRESSOR B2†
M CHECK FOR COMMUNICATING MODULES (BLINKING RED AND GREED LEDs) M CORRECT FLUID SET POINTS ARE ENTERED
COOL SET POINT 1 COOL SET POINT 2
M CORRECT DATE, TIME, AND OPERATING SCHEDULE(S) ARE SET
CL-5
Page 98
M REVIEW AND RECORD FACTORY CONFIGURATION CODES,
CONFIGURATION CODE 1: CONFIGURATION CODE 2: CONFIGURATION CODE 3: CONFIGURATION CODE 4: CONFIGURATION CODE 5:
M REVIEW AND RECORD SOFTWARE VERSION,
SOFTWARE CESR500100 VERSION
M REVIEW AND RECORD FIELD CONFIGURATION,
COOLER FLUID SELECT MIN LOAD VALVE SELECT LOADING SEQ. SELECT LEAD/LAG SEQ. SELECT HEAD PRESSURE CONTROL MOTORMASTER SELECT WATER VALVE TYPE EXTERNAL RESET SENSOR COOLER PUMP INTERLOCK
COOLER PUMP CONTROL CONDENSER PUMP CONTROL CONDENSER FLOW SWITCH CONDENSER WATER SENSORS
TO START THE CHILLER:
BE SURE THAT ALL SERVICE VALVESARE OPEN, AND ALL PUMPS ARE ON BEFORE ATTEMPTING TO START THIS MACHINE. ONCE ALL CHECKS HAVE BEEN MADE, MOVE THE SWITCH TO ‘‘LOCAL’’ OR ‘‘REMOTE’’ FROM ‘‘STOP.’’
M UNIT STARTS AND OPERATES PROPERLY.
TEMPERATURES AND PRESSURES:
ONCE THE MACHINE HAS BEEN OPERATING FOR AWHILEAND THE TEMPERATURES AND PRESSURES HAVE STABLIZED, RECORD THE FOLLOWING:
COOLER EWT COOLER LWT AMBIENT TEMPERATURE CONDENSER EWT
(ENTERING WATER TEMP) CONDENSER LWT
(LEAVING WATER TEMP) CIR. A OIL PRESS CIR. A SUCTION PRESS CIR. A DISCHARGE PRESS
CIR. A DISCHARGE TEMP CIR. A LIQUID LINE TEMP CIR. B OIL PRESS CIR. B SUCTION PRESS CIR. B DISCHARGE PRESS CIR. B DISCHARGE TEMP CIR. B LIQUID LINE TEMP
NOTE: OIL FILTER PRESSURE DROPS MUST BE CHECKED AFTER INITIAL 200-300 HOURS OF COMPRESSOR OPERATION. SEE OIL FILTER MAINTENANCE SECTION, PAGE 56.
CL-6
Page 99
NOTES:
CL-7
Page 100
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC903 CatalogNo.533-062 PrintedinU.S.A. Form30G,H-3T PgCL-8 1099 1-98 Replaces:30G,H-2T
Loading...