R 1997 Carrier Corporation • Syracuse, New York 13221
Form 30GX-4SB Supersedes 30GX-3SBPrinted in U.S.A.12-97Catalog No. 513-450
Date:Supersedes:30GX080-265
AIR-COOLED LIQUID CHILLER
30GX
JOB NAME:LOCATION:
BUYER:BUYER P.O. #CARRIER #
UNIT NUMBER:MODEL NUMBER:
PERFORMANCE DATA CERTIFIED BY:DATE:
DESCRIPTION
Packaged air-cooled liquid chiller factory wired, piped, and charged with HFC-134a. Upward
discharge airflow minimizes directional sound and dissipates heat away from surrounding areas.
FEATURES
Cooler is mechanically cleanable ‘‘flooded’’ shell-and-tube type
with removable heads. It is tested and stamped in accordance
with ASME Code for a refrigerant working side pressure of
220 psig (1517 kPa) and a maximum fluid side pressure of
300 psig (2068 kPa) (250 psig [1724 kPa] in Canada) and is
insulated with
Cooler can be equipped with electric heater to help protect against
cooler freeze-up (use of inhibited glycol anti-freeze recommended
for freeze protection).
Compressor is semi-hermetic twin screw design with refrigerant
gas cooled motor and integral oil filter and discharge gas muffler.
Complete thermal and electrical protection is provided.
Air-cooled condenser is constructed of fins mechanically bonded
to seamless copper tubes. Coils are leak and pressure tested at
450 psig (3103 kPa).
Condenser fans are direct driven 11-blade, shrouded axial type,
statically and dynamically balanced, discharging air vertically
upward, protected by coated steel wire safety guards.
Condenser fan motors are totally enclosed 3-phase with permanently lubricated bearings and Class F insulation (except speed
control motors).
Each refrigerant circuit includes oil separator, high side pressure
relief device, liquid and discharge line shutoff valve, filter drier,
moisture indicating sight glass, expansion/level control device.
Microprocessor control includes keypad with diagnostic display
displaying set points, time, system status (including temperatures,
pressures and % loading) and the alarm conditions.
Automatic compressor lead/lag.
Capacity control based on leaving chilled water temperature with
return water temperature sensing.
7-Day time scheduling of pump(s) and chiller.
60-Hz Models: 080, 090, 106, 115, 125, 136, 151, 161, 176, 206,
Capacity
Compressor Input PowerkW
Unit Input Power
Minimum Outdoor Operating Temperature
Capacity Control Steps
Minimum Capacity %%
EER
Entering Air Temperature
Weight
kW
ELECTRICAL DATA
Power Supply to UnitVoltsPhHz
Power Supply to Control Circuit
Minimum Amps Circuit 1
Maximum Fuse Amps Circuit 1
M
M
M
M
VoltsPhHz
Amps
Amps
OPTIONS
COOLER
Cooler Fluid
Entering Fluid Temperature
Leaving Fluid Temperature
Flow Rate
Pressure Drop
Fouling Factor
Control Circuit Fuse Amps
Maximum Instantaneous Current Flow
Minimum Amps Circuit 2
Maximum Fuse Amps Circuit 2
1. Unit must have clearances for air flow as follows:
Top — Do not restrict in any way
Ends — (1524 mm) 5 ft (from solid surface)
Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow as
follows:
Top — Do not restrict in any way
Ends — (1829 mm) 6 ft
Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See installation instructions for all other values.
1. Unit must have clearances for air flow as follows:
Top — Do not restrict in any way
Ends — (1524 mm) 5 ft (from solid surface)
Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow
as follows:
Top — Do not restrict in any way
Ends — (1829 mm) 6 ft
Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See installation instructions for all other values.
1. Unit must have clearances for air flow as follows:
Top — Do not restrict in any way
Ends — (1524 mm) 5 ft (from solid surface)
Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow
as follows:
Top — Do not restrict in any way
Ends — (1829 mm) 6 ft
Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See
installation instructions for all other values.
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for all
units. Maximum incoming wire size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source through a field
supplied fused disconnect with 30 amp maximum protection for 115voltcontrolcircuits
and 15 amp maximum protection for 230 volt control circuit. Connect control circuit
power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4.
Control circuit conductors for all units must be coppr only. 380/415 control power wired
at factory. Requires field supplied neutral connection.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The
contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA
load.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water
pump interlock (CWPI) functions. The contacts must be rated for dry circuit application
capable of handling a 24 vac to 50 mA load.
6. Terminals T3 and T4 on relay board are for chilled water pump. The maximum load
allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or
230 volt.
LEGEND
CCN— Carrier Comfort Network
CWFS— Chilled Water Flow Switch
CWP— Chilled Water Pump
CWPI— Chilled Water Pump Interlock
EQUIP— Equipment
GND,GRD — Ground
TB— Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring
11
12
FIELD WIRING DIAGRAM
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for
all units. Maximum incoming wire size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source through a field
supplied fused disconnect with 30 amp maximum protection for 115 volt control
circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to
terminal 2 of TB4. Control circuit conductors for all units must be coppr only. 380/
415 control power wired at factory. Requires field supplied neutral connection.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF.
The contacts must be rated for dry circuit application capable of handling a 24 vac
to 50 mA load.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled
water pump interlock (CWPI) functions. The contacts must be rated for dry circuit
application capable of handling a 24 vac to 50 mA load.
6. TerminalsT3andT4on relay board are for chilled water pump. The maximum load
allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or
230 volt. Minimum load required is 25 va sealed.
CCN— Carrier Comfort Network
CWFS — Chilled Water Flow Switch
CWP— Chilled Water Pump
CWPI — Chilled Water Pump Interlock
EQUIP — Equipment
GND— Ground
LEGEND
TB — Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.