Carrier 30GX080-265 User Manual

30GX080-265
AIR-COOLED LIQUID CHILLER
PERFORMANCE DATA — CERTIFIED DIMENSION PRINT
30GX-4SB
FIELD WIRING DIAGRAM
R 1997 Carrier Corporation • Syracuse, New York 13221
Form 30GX-4SB Supersedes 30GX-3SB Printed in U.S.A. 12-97 Catalog No. 513-450
AIR-COOLED LIQUID CHILLER
30GX
JOB NAME: LOCATION: BUYER: BUYER P.O. # CARRIER # UNIT NUMBER: MODEL NUMBER: PERFORMANCE DATA CERTIFIED BY: DATE:
DESCRIPTION
Packaged air-cooled liquid chiller factory wired, piped, and charged with HFC-134a. Upward
discharge airflow minimizes directional sound and dissipates heat away from surrounding areas.
FEATURES
Cooler is mechanically cleanable ‘‘flooded’’ shell-and-tube type with removable heads. It is tested and stamped in accordance with ASME Code for a refrigerant working side pressure of 220 psig (1517 kPa) and a maximum fluid side pressure of 300 psig (2068 kPa) (250 psig [1724 kPa] in Canada) and is insulated with
Cooler can be equipped with electric heater to help protect against cooler freeze-up (use of inhibited glycol anti-freeze recommended for freeze protection).
Compressor is semi-hermetic twin screw design with refrigerant gas cooled motor and integral oil filter and discharge gas muffler.
Complete thermal and electrical protection is provided. Air-cooled condenser is constructed of fins mechanically bonded
to seamless copper tubes. Coils are leak and pressure tested at 450 psig (3103 kPa).
Condenser fans are direct driven 11-blade, shrouded axial type, statically and dynamically balanced, discharging air vertically upward, protected by coated steel wire safety guards.
3
⁄4-in. (19 mm) closed-cell polyvinyl chloride foam.
Condenser fan motors are totally enclosed 3-phase with perma­nently lubricated bearings and Class F insulation (except speed control motors).
Each refrigerant circuit includes oil separator, high side pressure relief device, liquid and discharge line shutoff valve, filter drier, moisture indicating sight glass, expansion/level control device.
Microprocessor control includes keypad with diagnostic display displaying set points, time, system status (including temperatures, pressures and % loading) and the alarm conditions.
Automatic compressor lead/lag. Capacity control based on leaving chilled water temperature with
return water temperature sensing. 7-Day time scheduling of pump(s) and chiller. 60-Hz Models: 080, 090, 106, 115, 125, 136, 151, 161, 176, 206,
226, 251, and 265.
50-Hz Models: 080, 090, 105, 106, 115, 125, 136, 150, 160, 161,
175, 205, 225, 226, 250, and 265.
Rev.:
-4SB
PERFORMANCE DATA
UNIT
Capacity Compressor Input Power kW Unit Input Power Minimum Outdoor Operating Temperature Capacity Control Steps Minimum Capacity % % EER Entering Air Temperature Weight
kW
ELECTRICAL DATA
Power Supply to Unit Volts Ph Hz Power Supply to Control Circuit Minimum Amps Circuit 1 Maximum Fuse Amps Circuit 1
M
M
M
M
Volts Ph Hz
Amps
Amps
OPTIONS
COOLER
Cooler Fluid Entering Fluid Temperature Leaving Fluid Temperature Flow Rate Pressure Drop Fouling Factor
Control Circuit Fuse Amps Maximum Instantaneous Current Flow Minimum Amps Circuit 2 Maximum Fuse Amps Circuit 2
M
M
M
M
Amps Amps Amps Amps
2
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CERTIFIED DIMENSION PRINT
3
4
CERTIFIED DIMENSION PRINT
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CERTIFIED DIMENSION PRINT
5
6
CERTIFIED DIMENSION PRINT
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CERTIFIED DIMENSION PRINT
7
8
CERTIFIED DIMENSION PRINT
TOTAL OPERATING
UNIT
30GX
205 12,184 5,538 13,569 6,168 225 12,364 5,620 13,749 6,250
NOTES:
1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow as follows: Top — Do not restrict in any way Ends — (1829 mm) 6 ft Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See instal­lation instructions for all other values.
WEIGHT
Aluminum Fin Copper Fin
lb kg lb kg
TOTAL OPERATING
WEIGHT
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CERTIFIED DIMENSION PRINT
TOTAL OPERATING
UNIT
30GX
206 12,794 5,815 14,462 6,574 226 12,974 5,897 14,642 6,655 250 13,194 5,997 14,862 6,755
NOTES:
1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow as follows: Top — Do not restrict in any way Ends — (1829 mm) 6 ft Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See in­stallation instructions for all other values.
WEIGHT
Aluminum Fin Copper Fin
lb kg lb kg
TOTAL OPERATING
WEIGHT
9
10
CERTIFIED DIMENSION PRINT
TOTAL OPERATING
UNIT
30GX
251 13,774 6,621 15,549 7,068 265 13,829 6.286 15,604 7,093
NOTES:
1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow as follows: Top — Do not restrict in any way Ends — (1829 mm) 6 ft Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See installation instructions for all other values.
WEIGHT
Aluminum Fin Copper Fin
lb kg lb kg
TOTAL OPERATING
WEIGHT
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
FIELD WIRING DIAGRAM
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifica­tions or additions must be in compliance with all applicable codes.
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source through a field supplied fused disconnect with 30 amp maximum protection for 115voltcontrolcircuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4. Control circuit conductors for all units must be coppr only. 380/415 control power wired at factory. Requires field supplied neutral connection.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI) functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. Terminals T3 and T4 on relay board are for chilled water pump. The maximum load allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.
LEGEND
CCN Carrier Comfort Network CWFS Chilled Water Flow Switch CWP Chilled Water Pump CWPI Chilled Water Pump Interlock EQUIP Equipment GND,GRD — Ground TB Terminal Block
Field Power Wiring Field Control Wiring Factory Installed Wiring
11
12
FIELD WIRING DIAGRAM
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifi­cations or additions must be in compliance with all applicable codes.
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source through a field supplied fused disconnect with 30 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect con­trol circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4. Control circuit conductors for all units must be coppr only. 380/ 415 control power wired at factory. Requires field supplied neutral connection.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI) functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. TerminalsT3andT4on relay board are for chilled water pump. The maximum load allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt. Minimum load required is 25 va sealed.
CCN Carrier Comfort Network CWFS — Chilled Water Flow Switch CWP Chilled Water Pump CWPI — Chilled Water Pump Interlock EQUIP — Equipment GND Ground
LEGEND
TB — Terminal Block
Field Power Wiring Field Control Wiring Factory Installed Wiring
Loading...