Carrier 28GH User Manual

Carrier
Instaliation instructions
Direct Expansion Evaporator Coil

GENERAL

These encased coils must be used in a hori zontal position with the air flow in the direction as indicated in Fig. 1.
Transportation Damage — If any damage is noted
NIPPLE AUXILIARY CONDENSATE CONN
28GH002,003

INSTALLATION

Install coil in the horizontal run of a supply air duct from any furnace. Fig. 2 shows typical installations. Attach ductwork to encased coil. Use straps for hanging. Do not drill or screw into coil condensate pan. Coil must be level for proper condensate drainage.
If the duct cross-sectional area between coil and furnace is smaller than entering air opening of encased coil, a transition must be made in the duct. The ratio of transition in the duct must not exceed more than one inch for every seven in both the horizontal and vertical planes.
Where it is necessary to reduce fan noise or vibration, install a canvas connection in the duct work on the entering air side of the coil.
When encased coil is installed in a crawl space, attic or basement with less than 18 in. service
clearance above the unit, it is not possible to
service unit thru the access panel. In these cases,
part of the ductwork must be cut away or unit
must be removed from duct for servicing.
UNIT 28GH 002 003 i 004 i 005 006
DIM. (fi-in.)
CONN, (in, ODF)
Suction Liquid Condensate
Duct iniet (in.)
Duct Outlet (in.)
A
s I
C i
D j
V,
E i
F i G ;
K i 14%
J i
K j __14%
i 2-G%l 2-4% 3-0%
1-3%
1 -4%
V
%
7/
/A
13%
22% i 26%
13% i
13%
18% i
22% i 26%

Fig. 1 — Dimensions

©Carrier Corporation 1969
1%
%
34%
34%
Fig. 2 — Typical Installation
Refrigerant Piping — Connection sizes are given in
Fig. I. COILS 002 THRU 005 use Carrier Compatible
Fittings and accessory tubing package for connec tions. Detailed instructions are included with the tubing package. Do not remove rubber plugs from Carrier Compatible Fittings on the coil until ready to connect the suction or liquid line into the fitting. If coil piping is left open, vapor holding charge will escape and allow moisture to enter.
Form 28GH-1SI
COIL 006 must have the liquid and suction lines soldered to the unit.
Refrigerant Control is a factory-installed thermal
expansion valve. For proper operation, locate the feeler bulb outside the encased coil about 45 degrees above the horizontal center line of the suction line.
Do not mount bulb such that capillary tube extends from bottom of bulb. Clean suction line for good contact with bulb. Secure bulb tightly to suction Une with metal straps provided. If this is not done, liquid may slug to the compressor.
Suction Line Insulation — Insulate entire suction
line. Tubing package has an insulated suction line.
Insulate suction line from encased coil to, and
surrounding, expansion valve feeler bulb on 28GH
Coils.
Refrigerant Charge — Coils 002 thru 005 have
vapor holding charge. Do not evacuate if accessory tubing package with Carrier Compatible Fittings is used. If sweat connections are used, purge or evacuate coil and piping.
Coil 006 is shipped without charge. Purge or evacuate coil and piping.
Refer to Standard Service Techniques Manual, Chapter 1, pages 1-8 thru 1-14, and condensing unit and/or tubing package instructions for details.

Condensate Drain

1. Connect the rubber elbow (furnished with unit) to the primary drain. See Fig. 1.
2. Connect 7/8-in. copper tube to the elbow.
3. Form a trap in the 7/8-in. copper tube and run the tubing to an open drain. Drain tube should be pitched at least 1 in. per 10 ft.
4. Run individual condensate lines to the primary and secondary drain pans. The condensate line
should discharge at a point where it can be
readily observed if a correction is needed.
HOW TO APPLY HOSE CLAMPS
1. Pull ends apart (Fig. 3).
2. Wrap around hose with toothed end beneath. Prelatch by compressing until last ratchet teeth
catch behind small tabs.
LOCKiNG
CLAMP IN LOCKING POSiTiON
Fig. 3 — Hose Clamp
3. Grip adjacent bridges with pliers and compress to tight position. Pliers can be held parallel to hose where space is limited.
4. To remove, lift the locking tongue with screwdriver.
Protective Plastic Film — Peel from unit panels
when installation is complete.

AIR QUANTITY

To prevent moisture blowoff do not exceed
cfm shown in Table 1.
Table 1 — Maximum Allowable CFM for 28GH Coil
COIL 28GH 002
Horizontal 975
003 004 005
1200 1580 1920
006
2560
Manufacturer reserves the right to change any product specifications without notice.
CARRIER AIR CONDITIONING COMPANY • SYRACUSE, NEW YORK
Tab 7
Form28GH-1SI New
Printed in U.S.A.
6-69
Codes D and MS
Catalog No. 532-841
Loading...