Centrifugal liquid chillers are designed to provide safe and
reliable service when operated within design specifications. When operating this equipment, use good judgment
and safety precautions to avoid damage to equipment and
property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions as
well as those listed in this guide.
ONLY QUALIFIED Electrical Personnel familiar with the construction
and operation of this equipment and the hazards involved should install,
adjust, operate, or service this equipment.
READ AND UNDERSTAND this manual and other applicable manuals in
their entirety before proceeding. Failure to observe this precaution could
result in severe bodily injury or loss of life.
DO NOT install modification kits with power applied to the drive. Disconnect and lock out incoming power before attempting such installation or
removal. Failure to observe this precaution could result in severe bodily
injury or loss of life
UNUSED WIRES in conduit must be grounded at both ends to avoid a
possible shock hazard caused by induced voltages. Also, if a drive sharing
a conduit is being serviced or installed; all drives using this conduit should
be disabled to eliminate the possible shock hazard from cross-coupled
motor leads. Failure to observe these precautions could result in bodily
injury.
DO NOT VENT refrigerant relief valves within a building. Outlet from
rupture disc or relief valve must be vented outdoors in accordance with the
latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigerating, and Air Conditioning
Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and
reduces the amount of oxygen available for breathing. Product causes eye
and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any
purpose. Oxygen gas reacts violently with oil, grease, and other common
substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test
pressure by checking the instruction literature and the design pressures on
the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any chiller.
THERE IS A RISK OF INJURY OR DEATH by electrocution. High voltage may be present on the motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or
terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all
refrigerant (liquid and vapor) has been removed from chiller. Traces of
vapor should be displaced with dry air or nitrogen and the work area
should be well ventilated. Refrigerant in contact with an open flame pro-duces toxic gases.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including control panels,
switches, VFD, or oil heater until you are sure ALL POWER IS OFF and
no residual voltage can leak from capacitors or solid-state components.
19XRV
with PIC III Controls
Rockwell PowerFlex 755 VFD Option
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS
INTERRUPTED, confirm that all circuits are deenergized before resuming
work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.
USE SAFETY GOGGLES. Wash any spills from the skin with soap and
water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES
with water and consult a physician.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is
under pressure or while chiller is running. Be sure pressure is at 0 psig (0
kPa) before breaking any refrigerant connection.
TO AVOID an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus
voltage at the Power Terminal Block by measuring between the +DC and DC terminals, between the +DC terminal and the chassis, and between the
-DC terminal and the chassis. The voltage must be zero for all three measurements.
THE USER is responsible to conform with all applicable local, national,
and international codes. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
THIS DRIVE contains ESD (Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if
ESD control procedures are not followed. For static control procedures,
reference Rockwell publication Guarding Against Electrostatic Damage, or
any other applicable ESD protection handbook.
DO NOT alter the setting of any jumper. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.
USE OF power correction capacitors on the output of the drive can result
in erratic operation of the motor, nuisance tripping, and/or permanent damage to the drive. Remove power correction capacitors before proceeding.
Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
MOST CODES require that upstream branch circuit protection be provided to protect input power wiring. If fuses are chosen as the protection
method, refer to the PowerFlex 750 user manual. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
DO NOT route signal and control wiring with power wiring in the same
conduit. This can cause interference with drive operation. Failure to
observe this precaution could result in damage to, or destruction of, the
equipment.
DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rating of the drive. Failure to observe this precaution could result in damage
to, or destruction of, the equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow
safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move
inspection covers or other heavy components. Even if components are
light, use mechanical equipment when there is a risk of slipping or losing
your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE
THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the
VFD, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements of
the original equipment.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion,
rust, leaks, or damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190012-01Printed in U.S.A.Form 19XRV-3SSPg 1711 3-11Replaces: New
Start-Up and Service Manual must be used with the following
manuals:
• The latest version of the PowerFlex 750-Series AC
Drives manuals
• The latest revision of the Start-Up, Operation, and Maintenance Instructions for the 19XRV with PIC III Controls
Getting Assistance from Rockwell Automation — Contact the local Rockwell Automation sales office
with any questions or problems relating to the products described in this manual. For technical support on drives between
the hours of 7:00 am and 6:00 pm CST, M-F, call 1-262-512-
8176. For information about after-hours phone support and on-
site support call 1-800-800-0522.
Before calling, have the following information available
from the Allen-Bradley data nameplate located inside the enclosure on the right wall. See Fig. 1.
• Allen-Bradley ID or CAT. NO.
• Carrier VFD Code
• Allen-Bradley serial number
INTRODUCTION
The Carrier VFD option Start-Up and Service Manual is intended for trained and qualified service personnel, and is to be
used during start up, operation, and maintenance of Rockwell/
Allen-Bradley PF755L drive.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCM— Chiller Control Module
DC— Direct Current
DPI— Drive Peripheral Interface
ENET— Ethernet
ICVC— International Chiller Visual Controller
IGBT— Insulated Gate Bipolar Transistor
I/O— Inputs/Outputs
IP— Internet Protocol
IPWM— Inverter Pulse Width Modulation
MCB— Main Control Board
MOV— Metal Oxide Varistor
PE— Protective Earthing Conductor
SIO— Sensor Input/Output
STS— Status
IDENTIFYING DRIVE COMPONENTS
A chiller control schematic and a VFD schematic are in-
cluded in Appendix A.
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input
power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter rated
for the DC bus voltage to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could result in severe bodily
injury or loss of life.
An isolated multimeter will be needed to measure DC bus
voltage and to make resistance checks. The drive’s DC bus
capacitors retain hazardous voltages after input power has
been disconnected.
711
2
Opening the VFD Access Door
Fig. 2 — Opening Access Door
A19-1831
Fig. 3 — Check DC Bus Terminals
A19-1814
21P 1 0248 3 - 3 -0-0 C-
21P PF755 VFD
Voltage Rating
1
2
3
Customer
C –Carrier
Meter Package
0 – No Meter Package
1 –Analog Meter Package
– 460 to 480 v, 60 Hz
– 380 to 415 v, 50 Hz
– 380 to 400 v, 60 Hz
Input Reactor
0 – No Input Reactor
1 – 3% Input Line Reactor
– 401 to 439 v, 60 Hz
0477–477
3–65 KAIC Capacity Breaker
4 – 100 KAIC Capacity Breaker
Drive Assembly
3 – Unit Mount NEMA 1 Liquid Cooled
Fig. 4 — Drive Assembly Catalog Number Nomenclature
A19-1842
* For Carrier applications, maximum continuous amp
ratings are 230, 335, and 445.
WARNING
Before removing the drive enclosure, open access door and
verify that the DC bus voltage has dropped to zero by
checking the terminals behind the access door. Failure to
observe this precaution could result in severe bodily injury
or loss of life.
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat
or T20 star, open access door. See Fig. 2.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 3.
Drive Assembly Catalog Number — See Fig. 4 for
an example Catalog Number.
Components and Physical Data — The Allen-
Bradley PF755 Frame 6 drive is used for the 230-amp rated application (carrier Part No. 19XRV0230...). See Fig. 5.
The Allen-Bradley PF755 Frame 7 drive is used for the
335-amp and 445-amp rated application (Carrier Part No.
19XVR0335... and 19XVR0445... respectively). See Fig. 6.
PE Grounding StudsTerminating point to chassis ground
for incoming motor shield
3
DC Bus and Brake
Te r mi n a ls
+DC, -DC, BR1, BR2
4PE-A and PE-BMOV and CMC Jumper Wires
5DC+ and DC-Bus Voltage Test Points
A19-1833
4
Fig. 7 — Enclosure Dimensions - Frames 6 and 7
A19-1834
CAUTION
If other than refrigerant cooling is used, before connecting
the drive to the incoming power, make sure that the coolant
is circulating and has no leaks.
CAUTION
When working with the Drive Explorer, never use the
Rotate function as the motor will immediately start and
severe compressor damage could result.
START-UP
DANGER
Internal components and circuit boards of the drive are live
when the drive is connected to incoming power. Coming
into contact with this voltage is extremely dangerous and
will result in severe personal injury or death.
The motor terminals U, V, W and the DC-link/brake resistor terminals B+/R+, R- are live when the drive is connected to incoming power, even if the motor is not running.
Do not make any connections when the drive is connected
to the incoming power.
After having disconnected the drive, wait until the indicators on the keypad go out (if no keypad is attached see the
indicator through the keypad base). Wait 5 more minutes
before doing any work on drive connections. Do not even
open the cover before this time has expired..
Before connecting the drive to the incoming power, make
sure that the switchgear enclosure door is closed.
WARNING
The control I/O-terminals are isolated from the mains
potential. However, the relay outputs and other I/O terminals may have a dangerous control voltage present even
when the drive is disconnected from incoming power.
Coming into contact with this voltage could result in severe
personal injury.
Alternate Wire Lugs —
In the case where the incoming
power wire size does not fit the standard lug, alternate lugs may
be used. See Table 1. Note that lugs rated for a higher current
than the circuit breaker may be used.
Table 1 — Wire Lugs
CIRCUIT
BREAKER
65 KAIC
(Standard)
100 KAIC
(Optional)
STANDARD
ABB LUG
K6TJ
STANDARD
LUG CABLE
RANGE
(3) 2/0 - 400
MCM
ALTERNATE
ABB LUG
K6TH
ALTERNATE
LUG CABLE
RANGE
(2) 250 - 500
MCM
Verify Installation — Record the following job
information:
1. Job Name
2. Job Number
3. City
4. State
5. Zip Code
Record the following nameplate information:
1. From the Allen-Bradley nameplate (Fig. 1) located inside
the VFD enclosure:
a. Allen-Bradley ID or CAT NO.
b. Allen-Bradley Serial Number
c. Carrier Part Number
2. From the machine nameplete (Fig. 8) located inside the
VFD enclosure:
a. Chiller Serial Number
b. Chiller Model
c. Motor rated load amps
d. Motor nameplate rpm
e. Motor nameplate kW
f. Motor nameplate voltage
g. IPWM (pulse width modulation) frequency
h. Voltage
3. From the drive module label (Fig. 9) located on the drive
module:
a. Model or Cat. Number
b. Serial Number
4. From the ICVC control panel screen:
a. Carrier Part Number and Revision
b. ICVC Software Number
Rockwell PowerFlex 750 drive start-up must be registered
on the Rockwell website. Rockwell Registration site URL:
http://www.automation.rockwell.com/warp/default.asp
5
MODEL NUMBER
SERIAL NUMBER
VOLTS/PHASE/HERTZ
LOCKED ROTOR AMPS
OVERLOAD TRIP AMPS
MAX FUSE/CIRCUIT BREAKER SIZE
MIN SUPPLY CIRCUIT AMPACITY
MOTOR NAMEPLATE VOLTAGE
COMPRESSOR 100% SPEED
RATED LINE VOLTAGE
RATED LINE AMPS
RATED LINE KILOWATTS
MOTOR RATED LOAD KW
MOTOR RATED LOAD AMPS
MOTOR NAMEPLATE AMPS
MOTOR NAMEPLATE RPM
MOTOR NAMEPLATE KW
INTERTER PWM FREQUENCY
MACHINE NAMEPLATE SUPPLY DATA
MACHINE ELECTRICAL DATA
SAFETY CODE CERTIFICATION
THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE
IN ACCORDANCE WITH CARRIER SPECIFICATION Z-420.
19XV05008701 REV. 3
A United Technologies Company
Fig. 8 — Machine Nameplate
a19-
1846
Fig. 9 — Drive Module Label
a191924
Configure the VFD — All configurations required by
the VFD are supplied by the ICVC through the VFD Gateway.
Any configuration changes necessary and possible are made on
the ICVC screens. A complete set of configurations is transmitted to the VFD each time the controls are powered up.
The following is from the 19XRV PIC III ICVC screen. Parameters in italics are to be entered or confirmed at start-up. Parameters in bold are to be changed only after consulting with
Carrier service engineering. See Table 2.
Table 2
PARAMETERDEFAULT VALUE
Motor Nameplate Voltage460
Compressor 100% Speed
Line Freq=60 Hz? (No=50) Yes
Rated Line Voltage*460
Rated Line Amps* 200
Rated Line Kilowatts *100
Motor Rated Load kW* 100
Motor Rated Load Amps* 200
Motor Nameplate Amps100
Motor Nameplate RPM 3456
Motor Nameplate KW 100
Inverter PWM Frequency (0 = 4 kHz, 1 =
2kHz)
Skip Frequency 1 (Hz)102.0
Skip Frequency 2 (Hz)102.0
Skip Frequency 3 (Hz)102.0
Skip Frequency Band Line (Hz) 0.0
Voltage % Imbalance10
Line Volt Imbalance Time (sec)10
Line Current % Imbalance 40
Line Current Imbal Time (sec)10
Motor Current % Imbalance 40
Motor Current Imbal Time 10
Increase Ramp Time (sec)30
Decrease Ramp Time (sec)30
Single Cycle Dropout (DSABLE/ENABLE)DSABLE
* Parameters marked with an * are not downloadable to the VFD but are used
in other calculations and algorithms in the ICVC.
NOTES:
1. Parameters in italics are to be entered or confirmed at start-up.
2. Parameters in bold are to be changed only after consultation with service engineering.
— VFD Configurations
1
Commissioning the Unit — The commission proce-
dure is as follows:
1. If the chiller has been stored outdoors, allow at least 24
hours room temperature stabilization prior to commissioning. Ensure any condensation that occurs as a result
of the ambient temperature is allowed to evaporate.
2. Enter parameters in the VFD_CONF screen.
3. Install surge suppression devices if required.
4. Review the power wiring and grounding to ensure that it
has been properly connected.
5. Visually examine the inside of the drive enclosure to:
a. Look for signs of corrosion or moisture residue.
b. Remove any dirt or debris.
c. Make sure all vents are clear.
6. Apply power to the drive and take thermal measurements
of the capacitor bank and power connections. Do this
again before start-up.
7. Measure and record the incoming line voltage. Line-toline voltages should be balanced within 3% as calculated
by Rockwell’s procedure below:
Measure voltages phase-to-phase and phase-to-ground.
6
Vmax = Maximum measured phase-to-phase voltage
LEGEND
NO.NAMEDESCRIPTION
1HIM ConnectorDPI Port 1 (HIM Cradle) connection.
2
Fan ConnectorPower supply for internal cooling fan
(Frames 2 & 3).
3
Battery
Receptacle
User installed CR1220 lithium coin cell
battery provides power to the Real Time
Clock (Optional, not supplied).
4
DPI Port 2Cable connection for handheld and
remote HIM options.
5
Embedded EtherNet/
IP Address Selectors
Rotary switches for setting lowest octet
of EtherNet address (forces address to
192.168.1.xxx).
6
Embedded EtherNet/
IP Connector
Network cable connection.
7
Jumper J2 SAFETY Safety enable jumper. Removed when
safety option is installed.
8
Jumper J1 ENABLE Hardware enable jumper. Removed
when a hardware enable configuration is
utilized.
9TB1I/O terminal block.
Fig. 10 — PF755 Main Control Board
TB1 I/O Terminal Designations
FIXED I/OTERMINALNAMEDESCRIPTION
Di 0ac
Digital Input 120V ACConnections for AC power supply.
Di C
Digital Input CommonDigital input common
Di 0dc
Digital Input 24V DCConnections for DC power supply.
+24V
+24 Volt PowerConnections for drive supplied 24V power.
24VC
24 Volt Common
IMPORTANT: Wiring to pluggable terminal block connectors
should be supported by wire ties or other means to help prevent unintentional disconnection
Di 0ac
Di C
Di 0dc
+24V
24VC
a19-1921
(A to B, B to C, C to A)
Vmin = Minimum measured phase-to-phase voltage
Imbalance Calculation Formula
Va v g=
Imbalance %=
(VAB + VBC + VCA)
3
(Vmax – Vmin) x 100
Va v g
8. Take a final thermal measurement of the capacitor bank
and power after finalizing the installation to ensure all
connections are good.
9. If a ground fault occurs, then do the following:
a. Check for a ground in the motor or motor wiring.
b. Check for damage to wiring insulation and that
wiring is dry.
c. Verify the motor wiring is separated from ground
and there is no connection between phases.
d. Check for failed IGBTs.
10. If an Overcurrent fault occurs, then do the following:
a. Check for excessive load and verify load limit set-
tings on the ICVC.
b. Check motor and wiring insulation.
c. Check parameter settings on VFD_CONF screen
in the ICVC.
Check Internal Jumpers — On the Main VFD Con-
trol board there are two jumpers labeled J1 HARDWARE ENABLE and J2 SAFETY ENABLE. J1 should be removed and
J2 should be in place. See Fig. 10.
There are two jumper wires that connect a particular terminal to chassis ground. The MOV and AC EMI jumper should
be connected to the PE-A terminal. The COMMON MODE
CAPACITORS to GROUND jumper should be connected to a
standoff rather than the PE-B terminal.
Use the recommended tools as follows when connecting
jumper wires in Frame 6 and in Frame 7:
• Recommended torque (screws and nuts) = 1.36 N·m
(120.0 lb·in)
• Recommended hex socket = 7 mm
• Recommended screwdriver = T20 star type
See Fig. 11A and Fig. 11B for the correct positions of the
jumpers.
7
Troubleshooting the Drive —
Fig. 11A — Jumper Wire Locations — Frame 6
A19-1835
Fig. 11B — Jumper Wire Locations — Frame 7
A19-1836
2
8
5
79
13
46
Allen-Bradley
Fig. 12 — Drive Status Indicator
A1
91815
The drive can display
two kinds of error codes on the ICVC called the Alert and
Alarm codes. These codes signal a problem detected during
self tuning or drive operation. Alert and Alarm codes are located in the 19XRV Start-Up, Operation and Maintenance Instructions. Note the following differences between Carrier and
Allen-Bradley terminology:
• A warning message on the ICVC is an ALERT.
• The same warning viewed with Rockwell Drive Explorer
is a VFD ALARM.
• A failure resulting in a shutdown is seen as an ALARM
on the ICVC and as a VFD FAULT when viewed with
Drive Explorer.
CONDITION CODES
ICVC ALERT =VFD ALARM
ICVC ALARM =VFD FAULT
See Tables 3-6 and Fig. 12.
ICVC ALERT CODES — An alert condition is indicated by
a message at the top of the ICVC default screen. In addition, an
exclamation point (!) will appear next to any affected point on
an ICVC display screen. The drive will continue to operate
during the alert condition. Investigate the cause of the alert to
ensure it does not lead to a fault condition. The alert code will
automatically be cleared from the ICVC when the condition
causing the alert no longer exists. See Table 4.
ICVC ALARM CODES — An alarm condition is also indicated by a message at the top of the ICVC default screen. If an
alarm occurs, the drive coasts to stop. The STS (status) light on
the drive will turn from Green to Red or Yellow (see Table 3).
The detected fault message is maintained on the display until it
is cleared by pressing the RESET softkey. See Table 5.
TEST EQUIPMENT NEEDED TO TROUBLESHOOT —
An isolated multimeter adequately rated for the DC bus voltage will be needed to measure DC bus voltage and to make
resistance checks. Note that dedicated troubleshooting test
points are not provided.
SERVICE
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input
power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter to
ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
8
Table 3
SWING UP KEY PAD
MOUNT TO ACCESS
CONTROL BOARDS
Fig. 13 — Drive Module with Cover Removed
a19-1843
NAMECOLORSTATEDESCRIPTION
GreenFlashingDrive ready but not running, and no faults are present.
SteadyDrive running, no faults are present.
YellowFlashingDrive is not running. A type 2 (non-configurable) alarm condition exists and the
SteadyDrive is not running, a type 1 alarm condition exists. The drive can be started.
STS (Status)
ENET
LINK
NOTES:
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms
are user configurable.
RedFlashingA major fault has occurred. Drive cannot be started until fault condition is
SteadyA non-resettable fault has occurred.
Red/YellowFlashing AlternatelyA minor fault has occurred. When running, the drive continues to run. System is
Green/RedFlashing AlternatelyDrive is flash updating.
None (Unlit)OffAdapter and/or network is not powered, adapter is not properly connected to
RedFlashingAn EtherNet/IP connection has timed out.
SteadyAdapter failed the duplicate IP address detection test.
Red/GreenFlashing AlternatelyAdapter is performing a self-test.
GreenFlashingAdapter is properly connected but is not communicating with any devices on
SteadyAdapter is properly connected and communicating on the network.
None (Unlit)OffAdapter is not powered or is not transmitting on the network.
GreenFlashingAdapter is properly connected and transmitting data packets on the network.
SteadyAdapter is properly connected but is not transmitting on the network.
— Drive Status Indicator Descriptions
drive cannot be started.
cleared.
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major
fault.
the network, or adapter needs an IP address.
the network.
2. A Type 2 alarm indicates that a configuration error exists and
the drive cannot be started. Type 2 alarms are not configurable.
VERIFYING THAT DC BUS CAPACITORS ARE DISCHARGED — The drive’s DC bus capacitors retain hazardous voltages after input power has been disconnected. Perform
the following steps before touching any internal components:
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power
terminals.
3. Measure the DC bus potential with a voltmeter while
standing on a non-conductive surface and wearing insulated gloves (1000 V). Measure the DC bus potential. See
Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and
477-amp drives. The voltage between DC+ and DC-, and
from each DC terminal to the chassis must be zero before
proceeding.
4. Once the drive has been serviced, reapply input power.
HIGH TEMPERATURE ALARMS — Coolant flow
through the cold plate is controlled by an orifice in the refrigerant line leaving the cold plate. The orifice looks like one of the
O-ring face seal connectors and in fact is used as one of the
connections on the coolant tubing. The difference is that the
passage through the fitting is 0.375 in. (9.5 mm). If the orifice
is present and condenser liquid flow is present, the liquid will
flash to cooler temperature at the orifice. This temperature difference is great enough to be easily felt.
MAIN CONTROL BOARD (MCB) COMPONENTS —
Figure 13 shows the drive module with the cover removed. To
access the control boards, loosen the screw on the face of the
keypad mount and swing the keypad mount upward.
The components on the main control board (MCB) are
shown in Fig. 14. Note the location of the terminals labeled
MCB I/O. The high pressure switch is wired to these terminals
as shown in Fig. 15. In the event of a high condenser pressure
alarm, the connections at these terminals should be checked
and tightened if necessary.
A typical wiring schematic is shown in Appendix A.
*Located outside of starter; connected by field wiring.
Fig. 15 — High Pressure Switch Wiring
a19-1925
10
Table 4 — ICVC Alert Codes
PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
ICVC FAULT
STATE
100PRESTART
101PRESTART
102PRESTART
103PRESTART
104PRESTART
105PRESTART
106PRESTART
107PRESTART
108PRESTART
109PRESTART
110PRESTART
111PRESTART
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
SECONDARY
MESSAGE
STARTS LIMIT
EXCEEDED
HIGH BEARING
TEMPERATURE
HIGH MOTOR
TEMPERATURE
HIGH
DISCHARGE
TEMP
LOW
REFRIGERANT
TEMP
LOW OIL
TEMPERATURE
HIGH
CONDENSER
PRESSURE
LOW LINE
VOLTAGE
HIGH LINE
VOLTAGE
GUIDE VANE
CALIBRATION
HIGH
RECTIFIER
TEMP
HIGH
INVERTER
TEMP
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
100Excessive compressor starts
(8 in 12 hours).
101Comp Thrust Brg Temp [VALUE]
exceeded limit of [LIMIT]*.
102Comp Motor Winding Temp
[VALUE] exceeded limit of [LIMIT]*.
103Comp Discharge Temp [VALUE]
exceeded limit of [LIMIT]*.
104Evaporator Refrig Temp [VALUE]
exceeded limit of [LIMIT]*.
105Oil Sump Temp [VALUE]
exceeded limit of [LIMIT]*.
106Condenser Pressure [VALUE]
exceeded limit of [LIMIT]*.
107Percent Line Voltage [VALUE]
exceeded limit of [LIMIT]*.
108Percent Line Voltage [VALUE]
exceeded limit of [LIMIT]*.
109Actual Guide Vane Pos
Calibration Required Before Startup.
110Rectifier Temperature [VALUE]
exceeded limit of [LIMIT]*.
111Inverter Temperature [VALUE]
exceeded limit of [LIMIT]*.
Depress the RESET softkey if additional start
is required. Reassess start-up requirements.
Check oil heater for proper operation.
Check for low oil level, partially closed oil supply valves, clogged oil filters.
Check the sensor wiring and accuracy.
Check Comp Thrust Brg Alert setting in
SETUP1 screen.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation,
or restrictions.
Check for excessive starts within a short time
span.
Check Comp Motor Temperature Override
setting in SETUP1 screen.
Allow discharge sensor to cool.
Check sensor wiring and accuracy.
Check for excessive starts.
Check Comp Discharge Alert setting in
SETUP1 screen.
Check transducer wiring and accuracy.
Check for low chilled fluid supply
temperatures.
Check refrigerant charge.
Check Refrig Override Delta T in SETUP1
screen.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
Check transducer wiring and accuracy.
Check for high condenser water
temperatures.
Check high condenser pressure switch wiring.
Check voltage supply.
Check voltage transformers and switch gear.
Consult power utility if voltage is low.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
Press STOP button on ICVC and perform
Guide Vane Calibration in Controls Test
screen.
Check guide vane actuator feedback
potentiometer.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
11
NORMAL RUN WITH OVERRIDES
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
120RUN CAPACITY
121RUN CAPACITY
122RUN CAPACITY
123RUN CAPACITY
124RUN CAPACITY
125RUN CAPACITY
126RUN CAPACITY
127RUN CAPACITY
128RUN CAPACITY
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
SECONDARY
MESSAGE
HIGH CONDENSER
PRESSURE
HIGH MOTOR
TEMPERATURE
LOW EVAP REFRIG
TEMP
HIGH COMPRESSOR
LIFT
MANUAL GUIDE VANE
TA R GE T
LOW DISCHARGE
SUPERHEAT
HIGH RECTIFIER TEMP 126Rectifier Temperature
MANUAL SPEED
CONTROL
HIGH INVERTER TEMP 128Inverter Temperature
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
120Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
121Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.
122Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
123Surge Prevention
Override: Lift Too High For
Compressor
No Alert message.Check for oil loss or excess refrigerant charge.
[VALUE] exceeded limit of
[LIMIT]*.
No Alert message.Chiller is not in automatic temperature control.
[VALUE] exceeded limit of
[LIMIT]*.
Check condenser water pump operation.
Check for high condenser water temperatures or
low flow rate. Verify that isolation valves are
open.
Check Cond Press Override setting in SETUP1.
Check for closed valves or restriction in motor
cooling lines.
Check for closed refrigerant isolation valves.
Check Comp Motor Temp Override setting in
SETUP1.
Check refrigerant charge.
Check that optional cooler liquid line isolation
valve is fully open.
Check for excessive condenser flow or low
chilled water flow.
Check for low entering cooler temperature.
Check that condenser inlet and outlet water
nozzles are piped correctly.
Check for waterbox division plate gasket bypass.
Check for high condenser water temperature or
low suction temperature.
Check for high Evaporator or Condenser
approaches.
Check surge prevention parameters in
OPTIONS screen.
Target Guide Vane Position has been forced in
the COMPRESS screen. Select and RELEASE
force to return to normal (automatic) operation.
Verify that the valves in the oil reclaim lines are
open.
Check Rectifier Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
Check Inverter Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
12
CHILLER ALERTS
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
140SENSOR ALERTLEAVING COND WATER
141SENSOR ALERTENTERING COND WATER
142LOW OIL
143AUTORESTART
144AUTORESTART
145AUTORESTART
146AUTORESTART
147AUTORESTART
148AUTORESTART
149SENSOR ALERTHIGH DISCHARGE TEMP 149
150SENSOR ALERTHIGH BEARING
151CONDENSER
152RECYCLE ALERTEXCESSIVE RECYCLE
153no message:
154POTENTIAL
155OPTION SENSOR
156OPTION SENSOR
157OPTION SENSOR
158SENSOR ALERTSPARE TEMPERATURE#1158Spare Temperature 1
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
PRESSURE ALERT
PENDING
PENDING
PENDING
PENDING
PENDING
PENDING
PRESSURE ALERT
ALERT
only
FREEZE-UP
FAULT
FAULT
FAULT
SECONDARY
MESSAGE
TEMP
TEMP
CHECK OIL FILTER142Low Oil Pressure Alert.
LINE CURRENT
IMBALANCE
LINE VOLTAG E
DROP OUT
HIGH LINE VOLTAGE145High Percent Line
LOW LINE VOLTAGE146Low Percent Line
VFD MODULE RESET147->VFD Module Power-On
POWER LOSS148Control Power-Loss
TEMPERATURE
PUMP RELAY
ENERGIZED
STARTS
no message; ALERT only153Lead/Lag Disabled-
COND PRESS/TEMP
TOO LOW
REMOTE RESET
SENSOR
AUTO CHILLED WATER
RESET
AUTO DEMAND LIMIT
INPUT
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
140Sensor Fault: Check
Leaving Cond Water Sensor.
141Sensor Fault: Check
Entering Cond Water Sensor.
Check Oil Filter.
143Line Current Imbalance: Check VFD Fault History for Values.
144Single Cycle Line
Voltage Dropout.
Voltage [VALUE].
Voltage [VALUE].
Reset When Running.
When Running.
Comp Discharge Temp
[VALUE] Exceeded Limit of
[LIMIT]*.
150Comp Thrust Brg Temp
[VALUE] exceeded limit of
[LIMIT]*.
151High Condenser Pressure [VALUE]: Pump Energized to Reduce Pressure.
156Sensor Fault/Option
Disabled: Auto Chilled Water
Reset.
157Sensor Fault/Option
Disabled: Auto Demand Limit
Input.
[VALUE] exceeded limit of
[LIMIT]*.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.
Power loss has been detected in any phase.
Chiller automatically restarting.
A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically restarting if Auto Restart is
enabled in OPTIONS screen.
Check phase to phase and phase to ground line
power.
Check phase to phase and phase to ground line
power.
VFD Module has detected a hardware fault due
to electrical noise, power loss or software and
has reset. Chiller automatically restarting.
Check for power loss and sources of electromagnetic interference.
Check 24 vac control power supply to ICVC.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for fouled tubes or noncondensables in
the chiller.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil temperature.
Check sensor wiring and accuracy.
Check condenser flow and water temperature.
Check for fouled tubes.
This alarm is not caused by the High Pressure
Switch.
Chiller load is too low to keep compressor on
line and there has been more than 5 starts in
4 hours.
Increase chiller load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T from
SETUP1 Screen.
Illegal chiller address configuration in Lead/Lag
screen. Both chillers require a different address.
The condenser pressure transducer is reading a
pressure that could freeze the condenser tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN mode if the
vessel is evacuated.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #1 Limit in SETUP1 screen.
13
CHILLER ALERTS (cont)
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
159SENSOR ALERTSPARE TEMPERATURE#2159Spare Temperature 2
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #2 Limit in SETUP1 screen.
Check settings in WSMDEFME screen.
Check CCN communications link with WSM
(Water System Manager) Module.
Check Supervisory Part of WSM.
Check that refrigerant charge level is adequate,
waterbox division plate gaskets are sealing,
evaporator tubes are not fouled and that oil
reclaim system is working.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check Evap Approach Alert setting in SETUP1
screen.
Check sensors resistance or voltage drop.
Check for proper wiring.
Check Cond Approach Alert setting in SETUP1
screen.
Check for noncondensable gas in the
condenser.
Check that the condenser tubes are not fouled.
Actual VFD Speed on COMPRESS screen must
be at least 90% of Target VFD Speed.
Verify phase to phase and phase to ground line
voltage.
Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient voltage conditions.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for excessive starts.
Check Comp Discharge Alert setting in SETUP1
screen.
Check humidity sensor wiring on CCM connectors J3 and J5. CCM switch SW2-1 must be in
“OFF” position.
Check Humidity Sensor Input in Controls Test.
14
CHILLER PROTECTIVE LIMIT FAULTS
Table 5 — ICVC Alarm Codes
ICVC FAULT
STATE
200PROTECTIVE LIMIT RECTIFIER POWER
201PROTECTIVE LIMIT INVERTER POWER FAULT 201Inverter Power Fault:
202PROTECTIVE LIMIT MOTOR AMPS NOT
203FAILURE TO START MOTOR ACCELERATION
204FAILURE TO STOP VFD SHUTDOWN FAULT204VFD Shutdown Fault:
205PROTECTIVE LIMIT HIGH DC BUS VOLTAGE205High DC Bus Voltage:
206PROTECTIVE LIMIT VFD FAULT206VFD Fault Code:
207PROTECTIVE LIMIT HIGH CONDENSER
208PROTECTIVE LIMIT EXCESSIVE MOTOR
209PROTECTIVE LIMIT LINE CURRENT
210PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210Single Cycle Line Volt-
211PROTECTIVE LIMIT HIGH LINE VOLTAGE211High Percent Line Volt-
212PROTECTIVE LIMIT LOW LINE VOLTAGE212Low Percent Line Volt-
Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient voltage conditions. VFD Circuit Board malfunction.
Call Carrier Service.
See VFD Fault Code description and corrective
action.
Check Compressor Discharge High Pressure
switch wiring and accuracy.
Check for high condenser water temperatures,
low water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables in refrigerant.
Check Motor Rated Load Amps in VFD_CONF
screen. Percent Load Current > 110
Check Motor Rated Load Amps setting.
Check phase to phase and phase to ground
power distribution bus voltage.
Check Line Current % Imbalance in VFD_CONF
screen. Consult power company.
Temporary loss of voltage. Disable Single Cycle
Dropout in VFD_CONF screen.
Check phase to phase and phase to ground distribution bus voltage. Consult power company.
Check phase to phase and phase to ground distribution bus voltage. Consult power company.
Temporary loss of VFD control voltage. Check
VFD control power breaker, transformer and
fuses.
Check phase to phase and phase to ground distribution bus voltage.
Check VFD fuses.
Check 24 vac power supply to ICVC.
Consult power company.
Verify phase-to-phase and phase-to-ground line
voltage. VFD Circuit Board malfunction.
Call Carrier Service.
Check phase-to-phase and phase-to-ground
distribution bus voltage. Increase Line Voltage
% Imbalance in VFD_CONF screen.
Any phase current > 106% Rated Load Amps.
Can result from significant load side current
imbalance when running at full load.
Check entering condenser water temperature
and water flow rate.
Check Motor Rated Load Amps in VFD_CONF
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation and
blockage.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation and
blockage.
231PROTECTIVE LIMIT HIGH DISCHARGE TEMP 231Comp Discharge Temp
232PROTECTIVE LIMIT LOW REFRIGERANT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
COMMUNICATION
SECONDARY
MESSAGE
WITH VFD GATEWAY
MODULE
FAULT
IMBALANCE
FAULT
FLOW
WATER FLOW
TEMP
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
Check Motor and Current
Sensors.
[VALUE] exceeded limit of
[LIMIT]; Check Power Supply.
223Loss of SIO Comm with
VFD Gateway: Check VFG
Module and Power.
224Loss of DPI Comm with
VFD Gateway: Check VFG to
VFD Comm.
225Motor Current Imbalance: Check VFD Fault
History for Values.
Check Line Phases.
227Oil Pressure Delta P
[VALUE] (Pump Off): Check
Pump/Transducers.
Pressure [VALUE]: Check Oil
Pump and Filter.
229Low Chilled Water Flow;
Check Switch/Delta P Config
& Calibration.
230Low Condenser Water
Flow; Check Switch/Delta P
Config & Calibration.
[VALUE] Exceeded Limit of
[LIMIT]*.
232Evaporator Refrig Temp
[VALUE] exceeded limit of
[LIMIT]*.
Check for condensation on motor terminals.
Check motor power leads for phase to phase or
phase to ground shorts. Disconnect motor from
VFD and megger motor.
Call Carrier Service.
If operating from a generator, check generator
size and speed.
Check utility power supply.
Check VFD communication wiring and
connectors on VFD Gateway and DPI board.
Check for compatibility between ICVC and
Gateway software.
Check VFD communication wiring and
connectors.
Check status lights on DPI Communications
Interface Board.
Call Carrier Service.
Check Motor Current % Imbalance in
VFD_CONF screen.
Reverse connections of any two line conductors
to circuit breaker.
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check transducer calibration.
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check oil level.
Check for partially closed service valves.
Check oil filters.
Check for foaming oil at start-up.
Check transducer calibration.
Perform pump control test.
Check optional transducer calibration and
wiring.
Check Evaporator Refrigerant Temperature
sensor.
Check chilled water valves.
Check for evaporator saturation temperature
< 34 F if not in Pumpdown Lockout mode. Place
unit in Pumpdown mode before removing
charge.
Perform pump control test.
Check optional transducer calibration and
wiring.
Check condenser water valves.
Check for COND PRESS OVERRIDE + 5 psig.
Check for closed compressor discharge isolation valve.
Check if chiller was operating in surge.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper condenser flow and
temperature.
Check compressor discharge isolation valve.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper refrigerant charge.
Check float valve operation.
Check for closed condenser liquid line isolation
valve. If problem occurs at high load, check for
low condenser pressure which causes inadequate flasc orifice differential pressure.
Check for proper water flow and temperature.
Confirm that condenser water enters bottom row
of condenser tubes first.
Check Evaporator Refrigerant Temperature
sensor.
Check for division plate gasket bypass.
Check for fouled tubes.
16
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
233PROTECTIVE LIMIT HIGH MOTOR
234PROTECTIVE LIMIT HIGH BEARING
235PROTECTIVE LIMIT HIGH CONDENSER
236PROTECTIVE LIMIT COMPRESS SURGE/
237PROTECTIVE LIMIT SPARE SAFETY
238PROTECTIVE LIMIT EXCESSIVE COMPR
239PROTECTIVE LIMIT TRANSDUCER
240PROTECTIVE LIMIT LOW DISCHARGE
241PROTECTIVE LIMIT RECTIFIER
242LOSS OF
243POTENTIAL
244POTENTIAL
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
COMMUNICATION
FREEZE-UP
FREEZE-UP
SECONDARY
MESSAGE
TEMPERATURE
TEMPERATURE
PRESSURE
LOW SPEED
DEVICE
SURGE
VOLTAGE FAULT
SUPERHEAT
OVERCURRENT
WITH CCM MODULE242Loss of Communica-
EVAP PRESS/TEMP
TOO LOW
COND PRESS/TEMP
TOO LOW
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
233Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.
234Comp Thrust Brg Temp
[VALUE] exceeded limit of
[LIMIT]*.
235Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
236Compressor Surge:
Check condenser water temp
and flow.
237Spare Safety Device.Spare safety input has tripped or factory installed
238Compressor Surge:
Check condenser water temp
and flow.
239Transducer Voltage Ref
[VALUE] exceeded limit of
[LIMIT]*.
240Check for Oil in Or
Overcharge of Refrigerant.
243Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
244Condenser Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
Check motor sensors wiring and accuracy.
Check motor cooling line and spray nozzle for
proper operation, or restrictions.
Check for excessive starts within a short time
span.
Check oil heater for proper operation.
Check for low oil level, par tially closed oil supply
valves, or clogged oil filter.
Check oil cooler refrigerant thermal expansion
valves.
Confirm that TXV (thermostatic expansion valve)
bulb is secured in place and insulated.
Check for sensor wiring and accuracy.
This fault can result from extended operation at low
load with low water flow to the evaporator or
condenser.
Check for high condenser water temperatures, low
water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables.
Check transducer wiring and accuracy.
Check for high condenser water temperatures, low
water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables.
Check surge prevention parameters in OPTIONS
screen. Increase VFD Increase Step in SETUP2.
Check VFD Minimum Speed in SETUP2 screen.
jumper is not present on Terminal Block 4 terminals
17 and 20 in the VFD enclosure.
Check for high condenser water temperatures, low
water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables.
Check surge prevention parameters in OPTIONS
screen.
Check cooling tower control settings and performance to design/selection temperatures across the
entire operating range of the chiller.
Check cooler approach and water flow.
Check that CCM transducer voltage reference is
between 4.5 v and 5.5 v.
Check that pressure transducers are not shorted to
ground. This fault is normally declared the first time
an ICVC is powered up if it was downloaded with
software when it was not connected to a CCM.
Call Carrier Service.
Check for oil loss or excessive refrigerant. If oil level
is low, refrigerant charge may be too low resulting in
ineffective oil reclaim. Excessive refrigerant charge
may cause liquid carryover into compressor.
Check calibration of evaporator pressure and condenser pressure sensors.
Check calibration of compressor discharge temperature sensor.
Check for high water temperatures or changes in
water flow rates.
Check wiring and control power to CCM.
Confirm that all CCM SW1 switches are in the
“OFF” position.
Check for proper refrigerant charge.
Check float valve operation.
Check for proper fluid flow and temperature.
Confirm that condenser water enters bottom row
of condenser tubes first.
Check Evaporator Refrigerant Temperature
sensor.
Check for division plate gasket bypass.
Check for fouled tubes.
Condenser water too cold or chiller shut down with
brine below 32 F in cooler so equalization temperature in chiller approached 32 F.
Check condenser pressure transducer.
Check refrigerant charge.
17
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
245PROTECTIVE LIMIT HIGH VFD SPEED245Actual VFD Speed
246PROTECTIVE LIMIT INVALID DIFFUSER
247PROTECTIVE LIMIT DIFFUSER POSITION
248PROTECTIVE LIMIT SPARE TEMPERATURE #1248Spare Temperature #1
249PROTECTIVE LIMIT SPARE TEMPERATURE #2249Spare Temperature #2
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
SECONDARY
MESSAGE
CONFIG.
FAULT
CALIBRATION
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
exceeded limit of Target VFD
Speed + 10%.
246Diffuser Control Invalid
Configuration: Check SETUP2
Entries.
247Diffuser Position Fault:
Check Guide Vane/Diffuser
Actuator.
[VALUE] exceeded limit of
[LIMIT]*.
[VALUE] exceeded limit of
[LIMIT]*.
(VFD Uploaded): Verify to
Reset Alarm.
(VFD Downloaded): Verify to
Reset Alarm.
253Guide Vane Fault
[VALUE]. Check Calibration.
Press Reset to Restore
Configuration
ant Too Cold. Check Solenoid
& Cond T.
Check Temp Switch and Cooling Fans.
VFD Diagnostic Parameters
212/214.
Actual VFD Speed on COMPRESS screen must
not exceed Target VFD Speed by more than
10%.
Check 25%, 50%, and 75% Guide Vane and Diffuser Load Point entries in SETUP2 screen.
Confirm that Diffuser Option in SETUP 2 screen
has not been Enabled if compressor does not
have a split ring diffuser. May indicate rotating
stall condition.
Check rotating stall transducer wiring accuracy
and sealing.
Check diffuser schedule and guide vane schedule in SETUP2 screen.
Check for proper operation of diffuser and inlet
guide vane actuators including inlet guide vane
calibration.
Check diffuser actuator coupling for rotational
slip.
Check RC snubber on CCM J4-23 and J4-24.
Check 4.3k ohm resistor between CCM terminals J3-7 and J3-8.
Check for electrical noise in CCM Diffuser Pressure wiring. Do not continue to operate compressor except for diagnostic purposes.
Check Spare Temperature Enable and Spare
Temperature Limit in SETUP1 Screen.
Check Spare Temperature Enable and Spare
Temperature Limit in SETUP1 Screen.
The VFD_CONF table in the Gateway does not
match that which is in the ICVC. This is a normal
fault if an ICVC has been uploaded with software when it was not attached to the CCM.
Enter VFD_CONF screen and then exit
VFD_CONF screen by pressing EXIT then
CANCEL. Re-enter the VFD_CONF screen,
press EXIT then SAVE. Parameters stored in
the Gateway will be uploaded into the ICVC.
Confirm valid settings in VFD_CONF screen.
The VFD_CONF table in the Gateway does not
match that which is in the ICVC.
Enter CONTROL TEST and execute Guide
Vane Calibration.
Check CCM guide vane feedback terminals J4-9
and J4-10.
Check guide vane feedback potentiometer.
Alarm before start indicates guide vane opening
is not less than 4%. Alarm running indicates
guide vane position is < -1% or > 103%, or feed-
back voltage is < .045 or > 3.15 VDC.
Actual VFD checksum does not match calculated value.
VFD COLDPLATE TEMP is too close to dew
point based on VFD ENCLOSURE TEMP and
RELATIVE HUMIDITY in POWER screen.
Check for moisture in VFD enclosure.
Check Humidity Sensor in CONTROLS TEST.
Check for contamination on CCM J3-7 and J3-9
Humidity Sensor.
Check that VFD refrigerant cooling modulating
valve is closing.
Check for cooling fan air flow obstructions.
The VFD Start Inhibit is derived from the Alarm
bit being set in the VFD. The conditions causing
the alarm must be corrected in the VFD to
enable subsequent starts and operation. See
VFD parameters 212/214.
CCN has signaled the chiller to stop.This fault
must be manually reset from the default screen
of the ICVC.
LINE FREQUENCY in POWER screen must be
maintained between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). LINE FREQUENCY must be maintained between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
Check high pressure switch and connections to
TB4-24 and TB4-25.
COMPRESSOR 100% SPEED in VFD_CONF
screen must be set between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). COMPRESSOR 100% SPEED must be set between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
VFD Gateway and VFD software versions are
not compatible.
Call Carrier Service.
VFD Gateway and ICVC software versions are
not compatible.
Call Carrier Service.
Check for high entering water temperature or
low condenser water flow.
Check current settings in VFD_CONF screen.
ICVC FAULT
STATE
260SENSOR FAULTLEAVING CHILLED WATER 260Sensor Fault: Check
265Sensor Fault: Check
Comp Motor Winding Temp
Sensor.
Comp Discharge Temp Sensor.
Sump Temp Sensor.
Pump Delta P Sensor.
Chilled Water Delta P Sensor.
Cond Water Delta P Sensor.
Evap Saturation Temp Sensor.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor wiring.
Check for disconnected or shorted wiring.
Check for condensation in transducer
connector.
Check sensor wiring.
Check for disconnected or shorted wiring.
Check for condensation in transducer
connector.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor wiring and accuracy.
Check for disconnected or shorted wiring.
If pressure transducers are not installed,
check for presence of resistors and jumpers
on lower CCM terminal block J3.
Check sensor wiring and accuracy.
Check for disconnected or shorted wiring.
If pressure transducers are not installed,
check for presence of resistors and jumpers
on lower CCM terminal block J3.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
19
Table 6
VFD
FAULT
CODE
ON VFD
HIST
SCREEN
NONE206Processor memory faultConsult VFD manual to resolve generic fault.
0No Entry
2207Auxiliary InputInput is open.
3210Power LossLine voltage dropout
4215UndervoltageLow DC bus voltage
5166OvervoltageHigh DC bus voltage
7217Motor OverloadAn internal electronic overload trip has occurred.
8219
9219
12286HW Overcurrent
13220Ground Fault
14206Ground Warning
15206Load Loss
17216
20206TorqPrv Spd Band See VFD Fault Code 15 See VFD Fault Code 15
21225Output PhaseLoss
24204Decel Inhibit
33206AuRsts Exhausted See VFD Fault Code 15 See VFD Fault Code 15
36286SW Overcurrent
ICVC
FAULT
STATE
Heat Sink Overtemp
Transistor Overtemp
The DC bus ripple
has exceeded a
preset level.
— Powerflex 755 Fault Code Descriptions and Corrective Actions
FAULT TYPEDESCRIPTIONCORRECTIVE ACTION
Check Compressor Discharge High Pressure
switch wiring and accuracy.
Check for high condenser water temperatures,
low water flow, fouled tubes.
Check for division plate/gasket bypass. Check for
noncondensables in refrigerant.
Temporary loss of voltage. Disable Single Cycle
Dropout in VFD_CONF sceen.
Verify phase-to-phase and phase-to-ground line
voltage. VFD Circuit Board malfunction.
Call Carrier Service.
Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient voltage
conditions.
Any phase current > 106% RLA. Can result from
significant load side current imbalance when
running at full load.
Check entering condenser water temperature
and water flow rate.
Check Motor Rated Load Amps in VFD_CONF
screen.
Check that VFD refrigerant isolation valves are
Heat sink temperature has exceeded the maximum operating temperature
The output transistors have exceeded the maximum operating temperature
The drive output current has exceeded the hardware current limit.
A current path to earth ground greater than 25%
of drive rating has occurred.
The ground current has exceeded the level set in
P467
If this fault appears, there may be a problem with
software configuration.
Line Voltage imbalance
The current in one or more phases has been lost
or remains below a preset level.
The drive is not following a commanded deceleration because it is attempting to limit the bus voltage.
The drive output current has exceeded the 1 ms
current rating.
open.
Check VFD refrigerant cooling orifice and refrigerant strainer.
Check for proper VFD cooling fan operation and
air flow blockage.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling orifice and refrigerant strainer.
Check for proper VFD cooling fan operation and
air flow blockage.
Check for high entering water temperature or low
condenser water flow. Check current settings in
VFD_CONF screen.
Check the motor, motor terminals, and external
wiring to the drive output terminals for a
grounded condition.
—
To reset the processor, cycle power to chiller,
check ICVC VFD_CONF settings and save settings when exiting VFD_CONF screen.
Check VFD parameters with Drive Explorer.
Check phase-to-phase and phase-to-ground distribution bus voltage. Increase Line Voltage %
Imbalance in VFD_CONF screen.
Check Motor Current % Imbalance in
VFD_CONF screen.
Verify input voltage is within drive specified limits.
Verify system ground impedance follows proper
grounding techniques.
Disable bus regulation P186 and/or add dynamic
brake resistor and/or extend deceleration time
P537 and P538.
Check for excess load, improper DC boost setting, DC brake volts set too high.
DC-T0.5 V
DC+UInfinite (OL)
DC+VInfinite (OL)
DC+WInfinite (OL)
DC-U0.5 V
DC-V0.5 V
DC-W0.5 V
NOTE: Digital meters require a special diode check function
because the current sourced by the meter during a normal resistance (Ohms) test is too low to accurately test a diode. Make sure
the meter is set to the diode test function. Voltage readings may not
be exact as shown in above tables, but look for consistency during
each of the 4 tests. When performing a test that should return infinity
(OL) as shown in above tables, you may see a value slowly climbing
toward infinity. This is a result of the meter charging a capacitor and
is normal.
— Diode Checks
METER READING
22
Servicing the Drive
Fig. 16 — Open Access Door
A19-1831
1
L1 L2 L3
O
I
2
DC+ DC–
0V
0V
LOCKOUT/TAGOUT
MULTIMETER
DC BUS TEST
TERMINALS
LOCATED INSIDE
ACCESS DOOR
Fig. 17 — Check DC Bus Terminals
A19-1814
90°
SLIDE
ENCLOSURE
FORWARD
LOOSEN
ENCLOSURE
FASTENERS
Fig. 18 — Removing Enclosure
A19-1816
WARNING
To guard against possible personal injury and/or equipment
damage:
1. Inspect all lifting hardware for proper attachment before lifting drive.
2. Do not allow any part of the drive or lifting mechanism to make contact with electrically charged conductors or components.
3. Do not subject the drive to high rates of acceleration
or deceleration while transporting to the mounting location or when lifting.
Do not allow personnel or their limbs directly underneath
the drive when it is being lifted and mounted.
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input
power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter to
ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat
or T20 star, open access door. See Fig. 16.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
REMOVING THE DRIVE — The dimensions and weights
specified must be taken into consideration when removing the
drive. All lifting equipment and lifting components (hooks,
bolts, lifts, slings, chains, etc.) must be properly sized and rated
to safely lift and hold the weight of the drive while removing it.
See Fig. 19. The drive weights are as follows:
• Drive weight for Frame 6: 85 lb.
• Drive weight for Frame 7: 160 - 249 lb.
When replacing the drive, reverse the procedures and tighten to the torques for the Frames 6 and 7 Power Terminal Block
referred to in Table 8.
Table 8
FRAME
RIGGING THE ENCLOSURE —
— Frames 6 and 7 Power Terminal Block
MAXIMUM LUG
WIDTH
634.6 mm (1.36 in.) 11.3 N
743.5 mm (1.71 in.) 11.3 N
RECOMMENDED
TORQUE
·m (100 in.-lb)M8 x 1.25
·m (100 in.-lb)M8 x 1.25
Where overhead room
TERMINAL
BOLT SIZE
and/or clearance in front of the drive enclosure is insufficient to
allow the drive to be safely removed from the enclosure, the
entire enclosure may have to be removed from the chiller.
The dimensions and weights specified must be taken into
consideration when removing the enclosure. The total weight
for Frames 6 and 7, including drive weight and enclosure, is
720 lb. All lifting equipment and lifting components (hooks,
bolts, lifts, slings, chains, etc.) must be properly sized and rated
to safely lift and hold the weight of the enclosure and drive
while removing. See Fig. 20A and Fig. 20B.
23
DRIVE RIGGING ACCESS
DRIVE WIDTH + 4 IN.
FRONT VIEW
SIDE VIEW
DRIVE RIGGING
ACCESS
2 IN.
2 IN.
DRIVE POSITIONED FOR
VERTICAL LIFT
SUPPORT FROM
BELOW
DRIVE EXTENDS
BEHIND MAIN
ENCLOSURE
Fig. 19 — Enclosure Access for Removing Drive
A19-1818
a19-1817
>
1
/
2 A
A
<45°
Fig. 20A — Rigging the Enclosure, Frame 6
A19-1837
>
1
/
2 A
A
<45°
Fig. 20B — Rigging the Enclosure, Frame 7
A19-1838
REPLACING THE GATEWAY (A-B20-750-20COMM
OPTION CARD) — The following are the steps for removing and replacing the existing gateway.
1. Disconnect power to the drive. Before removing the enclosure, open the access door on the front of the drive.
See Fig. 16.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove the 2 screws securing the mounting plate and remove the mounting plate and COMM card. See Fig. 21.
5. Mount the new COMM card and mounting plate and attach with the 2 screws removed in Step 4. See Fig. 22.
6. Use the shorter ribbon cable to connect the plug on the
COMM card to the connector on the mounting plate. See
Fig. 21.
7. Install the enclosure. See Fig. 18.
24
0.45-0.67 N-m
(4.0-6.0 lb.-in.)
3 PLACES
MOUNTING PLATE
GATEWAY
RIBBON CABLE
Fig. 21 — COMM Card
A19-1819
MOUNTING PLATE
GATEWAY
Fig. 22 — Mount COMM Card Plate to Drive
A19-1820
T20
2.6 N•m (23 lb•in.)
CHILL PLATE
FAN POWER
CONNECTION
CHILL PLATE FAN
Fig. 23 — Chill Plate Fan, Frame 6
A19-1839
T20
2.6 N•m
(23 lb•in.)
T20
2.6 N•m
(23 lb•in.)
INTERNAL FAN
Fig. 24 — Internal Fan, Frame 6
A19-1840
CHILL PLATE FAN AND INTERNAL FAN REPLACEMENT — The following are the steps to replace the chill plate
fan and internal fan in Frames 6 and 7.
Frame 6:
1. Disconnect power to the drive. Before removing the enclosure, open the access door on the front of the drive.
See Fig. 16.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove and replace the chill plate fan. See Fig. 23.
5. Remove and replace the internal fan. See Fig. 24.
1. Disconnect power to the drive. Before removing the enclosure, open the access door on the front of the drive.
See Fig. 16.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove and replace the Heat Sink and Internal and fans.
See Fig. 25.
Install the enclosure. See Fig. 18.
Part Identification and Location — See Fig. 26-28
for parts descriptions and locations.
INTERNAL FANS
2.6 N•m (23 lb•in.)
X2
5.20 N•m
(46 lb•in.)
T15
T15
T20
2.6 N•m (23 lb•in.)
CHILL PLATE FANS
26
LEGEND
1—PF750 Series, Precharge Kit
2—PF750 Series, Gate Interface
3—PF750 Series, Power Interface
4—PowerFlex 750 Series, Flange Gasket
5—PF755 Main Control Board
6—PF750 Series, Backplane Interface
7—PF750 Series, Type 4X/12 Chill Plate
(Heatsink) Fan Kit
8— Chill Plate Fan
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked
“J1 ENABLE” must be removed and the jumper marked “J1 SAFETY” must be
left in place.
a19-1848
Fig. 27 — Frame 6 Parts
Fig. 28 — Frame 7 Parts
LEGEND
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked “J1 ENABLE” must be
removed and the jumper marked “J1 SAFETY” must be left in place.
1—Slot for Gateway (Gateway Not Shown)
2—PF750 Series, Backplane Interface
3—PF750 Series, Type 4X/12 Heatsink Fan Kit
4—PF750 Series, Power Interface
5—PF750 Series, Bus Cap Assembly
6—PF750 Series, Power Interface Cable
7—PF750 Series, Current Transducer Kit8 — PF750 Series, Precharge Kit
9—Slot for 24V I/O Module (24V I/O Module Not Shown)
10 — PF755 Main Control Board
a19-1849
27
AUTO DEMAND LIMIT
a19-1946
(OPTIONAL)
AUTO CHILLED WATER
RESET (OPTIONAL)
EVAP ENT
WATER TEMP
EVAP LVG
WATER TEMP
COND ENT
WATER TEMP
COND LVG
WATER TEMP
G.V. POSITION
FEEDBACK
EVAP REFRIG
LIQUID TEMP
REMOTE TEMP
RESET
(OPTIONAL)
COMP'R
DISCH TEMP
COMP'R THRUSTBRG TEMP
COMP'R OIL
SUMP TEMP
COMP'R
MOTOR TEMP
NOISE
SUPPRESSOR
SPARE TEMP #1
(OPTIONAL)
SPARE TEMP #2
(OPTIONAL)
OIL SUMP
PRESS
OIL PUMP
DISCH PRESS
LOAD RESISTOR
RELATIVE
HUMIDITY
(WHT)
LOAD RESISTOR
LOAD RESISTOR
JUMPER
LOAD RESISTOR
JUMPER
EVAP PRESS
COND PRESS
APPENDIX A — WIRING SCHEMATICS
CHILLER CONTROL SCHEMATIC
+
+
(SHIELD)
SWITCH POSITION
O
1
32
N
SW "ON" = EXT 4-20mA
SW "OFF" = EXT 1-5Vdc
SW2
1 "OFF"
2 "ON"
3 "ON"
ALL SWITCHES SET
TO "OFF" POSITION
6
J6
CCM
(SHIELD)
+-
1J7234
3
SW1
12345678
0
N
2
J1
1
-+-+
1J82
J9J10
3
2
J11
1
6
5
4
J12
3
2
1
(RED)
CB1
(GRY)(GRY)
(GRY)
(CLR)
(BLK)
(SHIELD)
4-20mAkw
OUTPUT
(CLR)
(RED)
(BLK)
(BLK)
(
(BLU)
(BLK)
(WHT)
(ORN)
SERVICE
DIFFUSER ACTUATOR
COMMON
G.V. INCREASE
G.V. DECREASE
GUIDE VANE ACTUATOR
CB2
)NRB
31
C2
(WHT)
(RED)
(GRY)
(BLK)
(CLR)
(RED)
(RED)
(BLK)
(CLR)
(
(BLU)
(ORN)
)KLB
3C
C2 C1
C1
1C
(RED)
6
2C
(RED)
(GRY)
L1
L2
L1
L2
(YEL)
(BLK)
(BRN)
(BRN)
(BRN)
)RLC(
J7
J1
5
4
3
2G
J8
X
3
2
24VAC
+-1
(BLK)
(WHT)
VFD COOLANT
SOLENOID
*
)RLC
(
HGBP (OPTIONAL)
(BRN)
COMP'R OIL PUMP
COMP'R OIL HEATER
ALARM
R
STOP
NOTE: GND SHIELDS AT THIS END ONLY
)
DLEIHS()DLEIHS(
(RED)
+
(
G
)KLB
()KLB(
-
SP
1
2
ICVC
(YEL)
(RED)
(BLK)
(CLR)
(BLK)
(BRN)
(WHT)
(RED)
(GRY)
(WHT)
(BLK)
)THW(
NCC)THW
EXT
4-20mA
(1-5vdc)
EXT
4-20mA
(1-5vdc)
+-+-+-
6
5432J51
(RED)
(BLK)
(RED)
(BLK)
(RED)
(BLK)
(RED)
(BLK)
4
(CLR)
78
(BLK)
10K
(SHIELD)
(RED)
(BLK)
(WHT)
(BLK)
(RED)
(BLK)
1
(CLR)
2
(BLK)
3
(SPARE)
(RED)
(BLK)
1
(CLR)
2
(BLK)
3
(SPARE)
(WHT)
(BLK)
(WHT)
(BLK)
-
+
-
+
RMS
-
+
-
+
(BLK)
(CLR)
(RED)
(BLK)
(CLR)
(RED)
(BLK)
-
4.3K
S
(RED)
+
10K
4.3K
4.3K
(BLK)
(CLR)
(RED)
(BLK)
(CLR)
(RED)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
J4 (UPPER)
J4 (LOWER)
100»f
100»f
J3 (UPPER)
J3 (LOWER)
J2
28
APPENDIX A — WIRING SCHEMATICS (cont)
(RED)
(BLK)
(BRN) (BRN)
(WHT)
T2
24VAC
(GRN)
(RED)
(RED)
(BLU)
(BLU)
(BLK)
SOLENOID
HGBP
(YEL)
(YEL)
(BLK)
(BLK)
2123
3C
42
(WHT)
(BLK)
3
6
5
4
2
1
HOT GAS BYPASS
(FR #7 & 8 HT EXCH)
115V CONTROLONLY
(RED)
ACTUATOR
HGBP
COM
OPEN
CLOSE
(GRN)
(BLK)
(BLU)
3C
3C
42
65
(WHT)
230V WIRING MODIFICATION
COMP'R OIL HEATER
(BLK)
(BLK)
(WHT)
(WHT)
(BLK)
13
11
12
1C
1C
1C
(FR #1 - 6 HT EXCH)
HOT GAS BYPASS
(BLU)
(BLK)
(GRN)
(RED)
(RED)
(BLU)
(BLU)
(BLK)
SOLENOID
HGBP
(YEL)
(YEL)
(BLK)
(BLK)
3C
SHOWN WIRED FOR 115V
230V WIRING MODIFICATION
42
(WHT)
(RED)
(BLK)(BLK)
(WHT)
WHT
)THW()TH
W(
COMP'R OIL PUMP MOTOR
WINDING HIGH TEMPERATURE
WHT
(WHT)
(BLK)
(BLK)
COMP'R DISCH
HIGH PRESS
(CLR)
(RED)
(SHIELD)
(BLK)
A
C
17
51
50
43
B
(BRN)
(RED)
(ORN)
(BLK)
COMP'R OIL HEATER
(WHT)
(BLK)
(WHT)
(WHT)
(BLK)
(BLK)
23
21
22
13
11
12
1C
1C
1C
115V
230V
COM
TO TB-G **
(RED)
(YEL)
(BLK)
RED
YEL
BLK
23
21
22
2C
2C
2C
13
11
12
VOLTAGE
PER JOB
REQM'T
M
COMP'R OIL
PUMP MOTOR
(1-1/2 HP)
TO VFD
T1
24VAC
(RED)
(BLK)
(BRN) (BRN)
(WHT)
(RED) (GRY)
(RED)
(GRY)
(WHT)
(WHT)
(BLK)
(BLK)
(BRN)
(YEL)
(RED)
(CLR)
(BLK)
(RED)
(BLK)
(BRN) (BRN)
(WHT)
T3
24VAC
(RED) (GRY)
UPC
1
2
a19-1947
LEGEND
* Standard on LF2 drive; optional on machines equipped with
other VFDs.
CBCircuit Breater
CCMChiller Control Module
HGBPHot Gas Bypass
ICVCInternational Chiller Visual Controller
RHSRelative Humidity Sensor
UPCUniversal Protocol Controller
VFDVar iabl e Fre quency Drive
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING
Fig. B — Address Rotary Switches
a48-8578
Fig. A — UPC Open Controller
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
BACNET
BAUD RATE
DIP SWITCHES
ADDRESS
ROTARY
SWITCHES
POWER LED
RUN LED
ERROR LED
BACNET
CONNECTION
(BAS PORT)
BT485
TERMINATOR
Tx2 LED
Rx2 LED
Tx1 LED
Rx1 LED
EIA-485
JUMPERS
* Sponsored by ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers).
a48-8579
Optional BACnet* Communications Wiring —
The following section is used to configure the UPC Open controller which is used when the BACnet communications option
is selected. The UPC Open controller is mounted in a separate
enclosure below the main control box.
TO ADDRESS THE UPC OPEN CONTROLLER — The
user must give the UPC Open controller an address that is
unique on the BACnet network. Perform the following procedure to assign an address:
1. If the UPC Open controller is powered, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the address
each time power is applied to it.
2. Using the rotary switches (see Fig. A and B), set the controller's address. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones
digit.
As an example in Fig. B, if the controller’s address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
0
1
9
2
8
3
7
8
7
10's
4
6
5
0
1
9
2
3
1's
4
6
5
BACNET DEVICE INSTANCE ADDRESS — The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BACnet system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu
®
Tools or BACView device.
By default, a MAC address of 20 will result in a Device Instance of 16101 + 20 which would be a Device Instance of
1610120.
32
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. C — DIP Switches
a48-
8580
Fig. D — Network Wiring
a48-8581
CONFIGURING THE BAS PORT FOR BACNET MS/
TP — Use the same baud rate and communication settings for
all controllers on the network segment. The UPC Open controller is fixed at 8 data bits, No Parity, and 1 Stop bit for this
protocol's communications.
If the UPC Open controller has been wired for power, pull
the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the DIP
Switches and jumpers each time power is applied to it.
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS
Port DIP switch DS4 to “EIA-485.” Set the BMS Protocol DIP
switches DS8 through DS5 to “MSTP.” See Table A.
Table A — SW3 Protocol Switch Settings
for MS/TP
DS8DS7DS6DS5DS4DS3
OffOffOffOffOnOff
Verify that the EIA-485 jumpers below the CCN Port are set
to EIA-485 and 2W.
The example in Fig. C shows the BAS Port DIP Switches
set for 76.8k (Carrier default) and MS/TP.
Set the BAS Port DIP Switches DS2 and DS1 for the appropriate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. C and Table B.
Table B — Baud Selection Table
BAUD RATEDS2DS1
9,600OffOff
19,200OnOff
38,400OffOn
76,800OnOn
WIRING THE UPC OPEN CONTROLLER TO THE MS/
TP NETWORK — The UPC Open controller communicates
using BACnet on an MS/TP network segment communications
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last controller on
a network segment to add bias and prevent signal distortions
due to echoing. See Fig. B, D, and E.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS port’s
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not currently connected.
5. Verify communication with the network by viewing a
module status report. To perform a module status report
using the BACview keypad/display unit, press and hold
the “FN” key then press the “.” Key.
33
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. E — BT485 Terminator Installation
a48-8582
To install a BT485 terminator, push the BT485 terminator
on to the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
i-Vu Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS — Recommen-
dations are shown in Tables C and D. The wire jacket and UL
Conductor 22 or 24 AWG stranded copper (tin plated)
Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Color Code Black/White
Twi st Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Shielding Aluminum/Mylar shield with 24 AWG TC drain wire
Jacket
DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor
Characteristic Impedance 100 Ohms nominal
Weight 12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Vo lt ag e 300 Vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
DC— Direct Current
FEP— Fluorinated Ethylene Polymer
NEC— National Electrical Code
O.D.— Outside Diameter
TC— Tinned Copper
UL— Underwriters Laboratories
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
temperature rating specifications list two acceptable alternatives. The Halar specification has a higher temperature rating
and a tougher outer jacket than the SmokeGard specification,
and it is appropriate for use in applications where the user is
concerned about abrasion. The Halar jacket is also less likely to
crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum
signal integrity.
34
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. F — BACview6 Device Connection
Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS
Wire Type Description
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
CMP— Communications Plenum Rated
FEP— Fluorinated Ethylene Polymer
TC— Tinned Copper
specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Connect Air
International
W221P-22227—25160PVCLP0520LC
W241P-2000F8284125120-OR—
Belden RMCORP
Contractors
Wire and Cable
LOCAL ACCESS TO THE UPC OPEN CONTROLLER — The user can use a BACview
6
handheld keypad display unit or the Virtual BACview software as a local user interface to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview
6
unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will require an additional USB link cable for connection.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview
To order a BACview
6
Handheld (BV6H), consult Commer-
6
device.
cial Products i-Vu® Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and ComfortLink™
controls must be set to the same CCN Address (Element) number and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are
required, both the ComfortLink and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Address and Bus number in the ComfortLink control. These configurations can be changed using the scrolling marquee display
or accessory Navigator handheld device.
Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Address and Bus Number in the UPC Open controller. These configurations can be changed using the accessory BACview
6
dis-
play.
Navigation: BACview→CCN
Home: Element Comm Stat
Element: 1
Bus: 0
TROUBLESHOOTING — If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
35
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
COMMUNICATION LEDS
— The LEDs indicate if the
controller is communicating with the devices on the network.
See Tables E and F. The LEDs should reflect communication
traffic based on the baud rate set. The higher the baud rate the
more solid the LEDs become. See Fig. B for location of LEDs
on UPC Open module.
REPLACING THE UPC OPEN BATTERY — The UPC
Open controller's 10-year lithium CR2032 battery provides a
minimum of 10,000 hours of data retention during power
outages.
Table E — LED Status Indicators
LEDSTATUS
Power
Rx Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Tx Lights when the controller transmits data to the network segment; there is a Tx LED for Ports 1 and 2.
Run Lights based on controller status. See Table F.
Error Lights based on controller status. See Table F.
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition
that caused the fault returns to normal.
Table F — Run and Error LEDs Controller and Network Status Indication
RUN LEDERROR LEDSTATUS
2 flashes per second Off Normal
2 flashes per second 2 flashes, alternating with Run LED Five minute auto-restart delay after system error
2 flashes per second 3 flashes, then off Controller has just been formatted
2 flashes per second 1 flash per second Controller is alone on the network
2 flashes per second On Exec halted after frequent system errors or control programs halted
5 flashes per second On Exec start-up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second 7 flashes per second, alternating with Run LED Ten second recovery period after brownout
14 flashes per second 14 flashes per second, alternating with Run LED Brownout
IMPORTANT: Power must be ON to the UPC Open when
replacing the battery, or the date, time, and trend data will
be lost.
Remove the battery from the controller, making note of the
battery's polarity. Insert the new battery, matching the battery's
polarity with the polarity indicated on the UPC Open
controller.
NETWORK POINTS LIST — The points list for the controller is shown in Table G.
36
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List
POINT DESCRIPTION
1st Current Alarm StateALARM_01RN/A0-270AV:4alarm_01_1
Active Demand LimitDEM_LIMR/W%N/A40 to 100AV:6dem_lim_1
Actual Guide Vane PositionGV_POSR%N/A0 to 100AV:7gv_pos_1
Actual VFD SpeedVFD_ACTR%N/A0 to 110AV:11vfd_act_1
Calc Evap Sat Temp EATR°FN/A-40 to 245AV:13ert_1
Chilled Water DeadbandCWDBR^F1.00.5 to 2.0AV:14cwdb_1
Chilled Water Delta PCHWPDR^FN/A-6.7 to 420AV:15chwpd_1
Chilled Water Delta TCHW_DTR^FN/A-40 to 245AV:16chw_dt_1
Chilled Water PumpCHLPRN/AOFFOFF/ONBV:4chlp_1
Chilled Water TempCHW_TMPR°FN/A-40 to 245AV:17chw_tmp_1
Chiller Start/StopCHIL_S_SR/WN/ASTOPSTOP/STARTBV:5chil_s_s_1
Comp Discharge TempCMPDR°FN/A-40 to 245AV:18cmpd_1
Comp Motor Winding TempMTRWR°FN/A-40 to 245AV:19mtrw_1
Comp Thrust Brg TempMTRBR°FN/A-40 to 245AV:20mtrb_1
Cond Water FlowCDW_FLOWRN/ANONO/YESBV:6cdw_flow_1
Cond Water PumpCDPRN/AOFFOFF/ONBV:7cdp_1
Condenser PressureCRPRPSIN/A-6.7 to 420AV:21crp_1
Condenser Refrig TempCRTR°FN/A-40 to 245AV:22crt_1
Condenser Water Delta PCDWPDRPSIN/A-6.7 to 420AV:23cdwpd_1
Control PointLCW_STPTR/W°FN/A10 to 120AV:24lcw_stpt_1
Current CHW SetpointCHWSTPTR°FN/A0.00 to 99.9AV:25chwstpt_1
Demand Level 1N/AR%N/A0 to 100AV:1dmv_lvl_1_perct_1
Demand Level 2N/AR%N/A0 to 100AV:2dmv_lvl_2_perct_1
Demand Level 3N/AR%N/A0 to 100AV:3dmv_lvl_3_perct_1
Element Comm StatusN/ARN/AN/ANo Comm/NormalBV:2999element_stat_1
Element Communications
Alarm
Emergency StopEMSTOPRN/AENABLE
Entering Chilled WaterECWR°FN/A-40 to 245AV:26ecw_1
Entering Condenser WaterECDWR°FN/A-40 to 245AV:27ecdw_1
Equipment AlarmN/ARN/AN/A
Evaporator PressureERPRPSIN/A-6.7 to 420AV:28erp_1
Evaporator Refrigerant Temp
Leaving Chilled Water -
Prime Variable
Leaving Condenser WaterLCDWR°FN/A-40 to 245AV:32lcdw_1
Line Active CurrentAMPS_ACTRAN/A0.0 to 99999.0AV:8amps_act_1
Line Active VoltageVOLT_ACTRVN/A0.0 to 99999.0AV:9volt_act_1
Line FrequencyLINEFREQRHzN/A0 to 99AV:30linefreq_1
Line Power FactorLINE_PFRN/A0.00 to 2.00AV:34line_pf_1
Local ScheduleN/ARN/AN/ANo Comm/NormalBV:2schedule_1
Occupied?OCCRN/ANONO/YESBV:10occ_1
Oil Sump TemperatureOILTR°FN/A-40 to 245AV:33oilt_1
Remote Start ContactREM_CONR/WN/AOPENOPEN/CLOSEBV:11rem_con_1
Run StatusSTATUSRN/AN/A
Service OntimeS_HRSR/WhrN/A0 to 32767AV:36s_hrs_1
Surge Line Delta TDELTA_TXR°FN/A0 to 200AV:38delta_tx_1
System Alert/AlarmSYS_ALMRN/AN/A
CCN
POINT NAME
N/ARN/AN/AInactive/ActiveBV:20comm_lost_alm_1
ERTR°FN/A-40 to 245AV:13ert_1
LCWR°FN/A-40 to 245AV:31lcw_1
READ/
WRITE
UNITS
DEFAULT
VAL UE
RANGE
ENABLE/
EMSTOP
Comm Normal
Comm Lost
0=Timeout,
1=Ready,
2=Recyle,
3=Startup,
4=Running,
5=Demand,
6=Ramping,
7=Autorest,
8=Override,
9=Tripout,
10=Control Test,
11=Lockout,
12=Pumpdown,
13=Prestart
1=Normal,
2=Alert, 3=Alarm
BACNET
OBJECT ID
BV:8emstop_1
BV:1element_alarm_1
AV:35status_1
AV:40sys_alm_1
BACNET
OBJECT NAME
37
611
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
POINT DESCRIPTION
System Cooling Demand
Level
System Demand LimitingN/ARN/AN/AOFF/ONBV:3dem_lmt_act_1
Target Guide Vane PositionGV_TRGR%N/A0 to 100AV:41gv_trg_1
Target VFD SpeedVFD_OUTR%N/A0 to 100AV:42vfd_out_1
Tower Fan Relay HighTFR_HIGHRN/AOFFOFF/ONBV:13tfr_high_1
Tow er F an R el ay L owTFR_LOWRN/AOFFOFF/ONBV:14tfr_low_1
User Defined Analog 1N/ARN/AN/AN/AAV:2901user_analog_1_1
User Defined Analog 2N/ARN/AN/AN/AAV:2902user_analog_2_1
User Defined Analog 3N/ARN/AN/AN/AAV:2903user_analog_3_1
User Defined Analog 4N/ARN/AN/AN/AAV:2904user_analog_4_1
User Defined Analog 5N/ARN/AN/AN/AAV:2905user_analog_5_1
User Defined Binary 1N/ARN/AN/AN/ABV:2911user_binary_1_1
User Defined Binary 2N/ARN/AN/AN/ABV:2912user_binary_2_1
User Defined Binary 3N/ARN/AN/AN/ABV:2913user_binary_3_1
User Defined Binary 4N/ARN/AN/AN/ABV:2914user_binary_4_1
User Defined Binary 5N/ARN/AN/AN/ABV:2915user_binary_5_1
LEGEND
CHW— Chilled Water
R—Read
VFD— Va riable Fr equency Drive
W—Write
CCN
POINT NAME
N/ARN/AN/AN/AAV:9006cool_demand_level_1
READ/
WRITE
UNITS
DEFAULT
VAL UE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
38
Copyright 2011 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190012-01Printed in U.S.A.Form 19XRV-3SSPg 40711 3-11Replaces: New
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.