Carrier 19XRV User Manual

Start-Up and Service Instructions
DANGER
WARNING
CAUTION
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifica­tions. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
ONLY QUALIFIED Electrical Personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment.
READ AND UNDERSTAND this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. DO NOT install modification kits with power applied to the drive. Discon­nect and lock out incoming power before attempting such installation or removal. Failure to observe this precaution could result in severe bodily injury or loss of life
UNUSED WIRES in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced voltages. Also, if a drive sharing a conduit is being serviced or installed; all drives using this conduit should be disabled to eliminate the possible shock hazard from cross-coupled motor leads. Failure to observe these precautions could result in bodily injury.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Insti­tute/American Society of Heating, Refrigerating, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can dis­place oxygen and cause asphyxiation. PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high con­centrations of vapor is harmful and may cause heart irregularities, uncon­sciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate. DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any chiller. THERE IS A RISK OF INJURY OR DEATH by electrocution. High volt­age may be present on the motor leads even though the motor is not run­ning. Open the power supply disconnect before touching motor leads or terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame pro- duces toxic gases.
DO NOT work on high-voltage equipment unless you are a qualified elec­trician.
DO NOT WORK ON electrical components, including control panels, switches, VFD, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
19XRV
with PIC III Controls
Rockwell PowerFlex 755 VFD Option
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
TO AVOID an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and ­DC terminals, between the +DC terminal and the chassis, and between the
-DC terminal and the chassis. The voltage must be zero for all three mea­surements.
THE USER is responsible to conform with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. THIS DRIVE contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. For static control procedures, reference Rockwell publication Guarding Against Electrostatic Damage, or any other applicable ESD protection handbook.
DO NOT alter the setting of any jumper. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
USE OF power correction capacitors on the output of the drive can result in erratic operation of the motor, nuisance tripping, and/or permanent dam­age to the drive. Remove power correction capacitors before proceeding. Failure to observe this precaution could result in damage to, or destruction of, the equipment. MOST CODES require that upstream branch circuit protection be pro­vided to protect input power wiring. If fuses are chosen as the protection method, refer to the PowerFlex 750 user manual. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
DO NOT route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rat­ing of the drive. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury. DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the VFD, tower fans, or pumps. USE only repair or replacement parts that meet the code requirements of the original equipment.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190012-01 Printed in U.S.A. Form 19XRV-3SS Pg 1 711 3-11 Replaces: New
CONTENTS
Fig. 1 — Allen Bradley Data Nameplate
A19-1830
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ABBREVIATIONS AND EXPLANATIONS . . . . . . . . . . 2
Required Publications. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Getting Assistance from Rockwell Automation . . . 2
IDENTIFYING DRIVE COMPONENTS. . . . . . . . . . . . 2-5
Opening the VFD Access Door . . . . . . . . . . . . . . . . . . . 3
Drive Assembly Catalog Number . . . . . . . . . . . . . . . . . 3
Components and Physical Data . . . . . . . . . . . . . . . . . . 3
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Alternate Wire Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Verify Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Configure the VFD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Commissioning the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 6
Check Internal Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27
Troubleshooting the Drive . . . . . . . . . . . . . . . . . . . . . . . . 8
• ICVC ALERT CODES
• ICVC ALARM CODES
• TEST EQUIPMENT NEEDED TO TROUBLESHOOT
• VERIFYING THAT DC BUS CAPACITORS ARE DISCHARGED
• HIGH TEMPERATURE ALARMS
• MAIN CONTROL BOARD (MCB) COMPONENTS
Checking Power Modules and Motor Input
with Input Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Servicing the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
• REMOVING THE DRIVE
• RIGGING THE ENCLOSURE
• REPLACING THE GATEWAY (A-B20-750-20COMM OPTION CARD)
• CHILL PLATE FAN AND INTERNAL FAN REPLACEMENT
Parts Identification and Location . . . . . . . . . . . . . . . . 26
APPENDIX A — WIRING SCHEMATICS . . . . . . . 28-31
APPENDIX B — OPTIONAL BACNET
COMMUNICATIONS WIRING . . . . . . . . . . . . . . . 32-38
Page
Required Publications — The Carrier VFD option
Start-Up and Service Manual must be used with the following manuals:
• The latest version of the PowerFlex 750-Series AC Drives manuals
• The latest revision of the Start-Up, Operation, and Main­tenance Instructions for the 19XRV with PIC III Controls
Getting Assistance from Rockwell Automa­tion — Contact the local Rockwell Automation sales office
with any questions or problems relating to the products de­scribed in this manual. For technical support on drives between the hours of 7:00 am and 6:00 pm CST, M-F, call 1-262-512-
8176. For information about after-hours phone support and on-
site support call 1-800-800-0522.
Before calling, have the following information available
from the Allen-Bradley data nameplate located inside the en­closure on the right wall. See Fig. 1.
• Allen-Bradley ID or CAT. NO.
• Carrier VFD Code
• Allen-Bradley serial number
INTRODUCTION
The Carrier VFD option Start-Up and Service Manual is in­tended for trained and qualified service personnel, and is to be used during start up, operation, and maintenance of Rockwell/ Allen-Bradley PF755L drive.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCM Chiller Control Module DC Direct Current DPI Drive Peripheral Interface ENET Ethernet ICVC International Chiller Visual Controller IGBT Insulated Gate Bipolar Transistor I/O Inputs/Outputs IP Internet Protocol IPWM Inverter Pulse Width Modulation MCB Main Control Board MOV Metal Oxide Varistor PE Protective Earthing Conductor SIO Sensor Input/Output STS Status
IDENTIFYING DRIVE COMPONENTS
A chiller control schematic and a VFD schematic are in-
cluded in Appendix A.
WARNING
DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter rated for the DC bus voltage to ensure the DC bus capacitors are discharged before touching any internal components. Fail­ure to observe this precaution could result in severe bodily injury or loss of life.
An isolated multimeter will be needed to measure DC bus voltage and to make resistance checks. The drive’s DC bus capacitors retain hazardous voltages after input power has been disconnected.
711
2
Opening the VFD Access Door
Fig. 2 — Opening Access Door
A19-1831
Fig. 3 — Check DC Bus Terminals
A19-1814
21P 1 0248 3 - 3 -0-0 C-
21P PF755 VFD
Voltage Rating 1 2
3
Customer C –Carrier
Meter Package 0 – No Meter Package 1 –Analog Meter Package
– 460 to 480 v, 60 Hz – 380 to 415 v, 50 Hz – 380 to 400 v, 60 Hz
4
PF755 Full Load Amp Rating (Maximum Continuous Amps)* 0248 – 248 0361 – 361
Disconnect/Breaker Options
Input Reactor 0 – No Input Reactor 1 – 3% Input Line Reactor
– 401 to 439 v, 60 Hz
0477–477
3–65 KAIC Capacity Breaker
4 – 100 KAIC Capacity Breaker
Drive Assembly
3 – Unit Mount NEMA 1 Liquid Cooled
Fig. 4 — Drive Assembly Catalog Number Nomenclature
A19-1842
* For Carrier applications, maximum continuous amp ratings are 230, 335, and 445.
WARNING
Before removing the drive enclosure, open access door and verify that the DC bus voltage has dropped to zero by checking the terminals behind the access door. Failure to observe this precaution could result in severe bodily injury or loss of life.
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat or T20 star, open access door. See Fig. 2.
2. Check to be sure that the voltage between DC+ and DC­and from each DC terminal to the chassis is zero before proceeding. See Fig. 3.
Drive Assembly Catalog Number — See Fig. 4 for
an example Catalog Number.
Components and Physical Data — The Allen-
Bradley PF755 Frame 6 drive is used for the 230-amp rated ap­plication (carrier Part No. 19XRV0230...). See Fig. 5.
The Allen-Bradley PF755 Frame 7 drive is used for the 335-amp and 445-amp rated application (Carrier Part No. 19XVR0335... and 19XVR0445... respectively). See Fig. 6.
See Fig. 7 for the dimensions of Frames 6 and 7.
1
L1 L2 L3
I
LOCKOUT/TAGOUT
DC BUS TEST TERMINALS LOCATED INSIDE ACCESS DOOR
2
DC+ DC–
0V
O
0V
MULTIMETER
3
LEGEND
Fig. 5 — Frame 6 Drive Components
NO. NAME DESCRIPTION
1 Power Terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
2
PE Grounding Studs Terminating point to chassis ground
for incoming motor shield
3
DC Bus and Brake Terminals
+DC, -DC, BR1, BR2
4 PE-A and PE-B MOV and CMC Jumper Wires 5 DC+ and DC- Bus Voltage Test Points
A19-
1832
LEGEND
Fig. 6 — Frame 7 Drive Components
NO. NAME DESCRIPTION
1 Power Terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
2
PE Grounding Studs Terminating point to chassis ground
for incoming motor shield
3
DC Bus and Brake Te r mi n a ls
+DC, -DC, BR1, BR2
4 PE-A and PE-B MOV and CMC Jumper Wires 5 DC+ and DC- Bus Voltage Test Points
A19-1833
4
Fig. 7 — Enclosure Dimensions - Frames 6 and 7
A19-1834
CAUTION
If other than refrigerant cooling is used, before connecting the drive to the incoming power, make sure that the coolant is circulating and has no leaks.
CAUTION
When working with the Drive Explorer, never use the Rotate function as the motor will immediately start and severe compressor damage could result.
START-UP
DANGER
Internal components and circuit boards of the drive are live when the drive is connected to incoming power. Coming into contact with this voltage is extremely dangerous and will result in severe personal injury or death.
The motor terminals U, V, W and the DC-link/brake resis­tor terminals B+/R+, R- are live when the drive is con­nected to incoming power, even if the motor is not running.
Do not make any connections when the drive is connected to the incoming power.
After having disconnected the drive, wait until the indica­tors on the keypad go out (if no keypad is attached see the indicator through the keypad base). Wait 5 more minutes before doing any work on drive connections. Do not even open the cover before this time has expired..
Before connecting the drive to the incoming power, make sure that the switchgear enclosure door is closed.
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O termi­nals may have a dangerous control voltage present even when the drive is disconnected from incoming power. Coming into contact with this voltage could result in severe personal injury.
Alternate Wire Lugs —
In the case where the incoming power wire size does not fit the standard lug, alternate lugs may be used. See Table 1. Note that lugs rated for a higher current than the circuit breaker may be used.
Table 1 — Wire Lugs
CIRCUIT
BREAKER
65 KAIC
(Standard)
100 KAIC
(Optional)
STANDARD
ABB LUG
K6TJ
STANDARD
LUG CABLE
RANGE
(3) 2/0 - 400
MCM
ALTERNATE
ABB LUG
K6TH
ALTERNATE LUG CABLE
RANGE
(2) 250 - 500
MCM
Verify Installation — Record the following job
information:
1. Job Name
2. Job Number
3. City
4. State
5. Zip Code
Record the following nameplate information:
1. From the Allen-Bradley nameplate (Fig. 1) located inside the VFD enclosure:
a. Allen-Bradley ID or CAT NO. b. Allen-Bradley Serial Number c. Carrier Part Number
2. From the machine nameplete (Fig. 8) located inside the VFD enclosure:
a. Chiller Serial Number b. Chiller Model c. Motor rated load amps d. Motor nameplate rpm e. Motor nameplate kW f. Motor nameplate voltage g. IPWM (pulse width modulation) frequency h. Voltage
3. From the drive module label (Fig. 9) located on the drive module:
a. Model or Cat. Number b. Serial Number
4. From the ICVC control panel screen: a. Carrier Part Number and Revision b. ICVC Software Number
Rockwell PowerFlex 750 drive start-up must be registered on the Rockwell website. Rockwell Registration site URL: http://www.automation.rockwell.com/warp/default.asp
5
MODEL NUMBER
SERIAL NUMBER
VOLTS/PHASE/HERTZ
LOCKED ROTOR AMPS
OVERLOAD TRIP AMPS
MAX FUSE/CIRCUIT BREAKER SIZE
MIN SUPPLY CIRCUIT AMPACITY
MOTOR NAMEPLATE VOLTAGE
COMPRESSOR 100% SPEED
RATED LINE VOLTAGE
RATED LINE AMPS
RATED LINE KILOWATTS
MOTOR RATED LOAD KW
MOTOR RATED LOAD AMPS
MOTOR NAMEPLATE AMPS
MOTOR NAMEPLATE RPM
MOTOR NAMEPLATE KW
INTERTER PWM FREQUENCY
MACHINE NAMEPLATE SUPPLY DATA
MACHINE ELECTRICAL DATA
SAFETY CODE CERTIFICATION
THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE IN ACCORDANCE WITH CARRIER SPECIFICATION Z-420.
19XV05008701 REV. 3
A United Technologies Company
Fig. 8 — Machine Nameplate
a19-
1846
Fig. 9 — Drive Module Label
a19­1924
Configure the VFD — All configurations required by
the VFD are supplied by the ICVC through the VFD Gateway. Any configuration changes necessary and possible are made on the ICVC screens. A complete set of configurations is transmit­ted to the VFD each time the controls are powered up.
The following is from the 19XRV PIC III ICVC screen. Pa­rameters in italics are to be entered or confirmed at start-up. Pa­rameters in bold are to be changed only after consulting with Carrier service engineering. See Table 2.
Table 2
PARAMETER DEFAULT VALUE Motor Nameplate Voltage 460 Compressor 100% Speed
Line Freq=60 Hz? (No=50) Yes
Rated Line Voltage* 460 Rated Line Amps* 200
Rated Line Kilowatts * 100 Motor Rated Load kW* 100 Motor Rated Load Amps* 200 Motor Nameplate Amps 100
Motor Nameplate RPM 3456 Motor Nameplate KW 100
Inverter PWM Frequency (0 = 4 kHz, 1 = 2kHz)
Skip Frequency 1 (Hz) 102.0 Skip Frequency 2 (Hz) 102.0 Skip Frequency 3 (Hz) 102.0 Skip Frequency Band Line (Hz) 0.0 Voltage % Imbalance 10 Line Volt Imbalance Time (sec) 10 Line Current % Imbalance 40 Line Current Imbal Time (sec) 10 Motor Current % Imbalance 40 Motor Current Imbal Time 10
Increase Ramp Time (sec) 30 Decrease Ramp Time (sec) 30 Single Cycle Dropout (DSABLE/ENABLE) DSABLE
* Parameters marked with an * are not downloadable to the VFD but are used in other calculations and algorithms in the ICVC. NOTES:
1. Parameters in italics are to be entered or confirmed at start-up.
2. Parameters in bold are to be changed only after consultation with ser­vice engineering.
VFD Configurations
1
Commissioning the Unit — The commission proce-
dure is as follows:
1. If the chiller has been stored outdoors, allow at least 24 hours room temperature stabilization prior to commis­sioning. Ensure any condensation that occurs as a result of the ambient temperature is allowed to evaporate.
2. Enter parameters in the VFD_CONF screen.
3. Install surge suppression devices if required.
4. Review the power wiring and grounding to ensure that it has been properly connected.
5. Visually examine the inside of the drive enclosure to: a. Look for signs of corrosion or moisture residue. b. Remove any dirt or debris. c. Make sure all vents are clear.
6. Apply power to the drive and take thermal measurements of the capacitor bank and power connections. Do this again before start-up.
7. Measure and record the incoming line voltage. Line-to­line voltages should be balanced within 3% as calculated by Rockwell’s procedure below:
Measure voltages phase-to-phase and phase-to-ground.
6
Vmax = Maximum measured phase-to-phase voltage
LEGEND
NO. NAME DESCRIPTION
1 HIM Connector DPI Port 1 (HIM Cradle) connection.
2
Fan Connector Power supply for internal cooling fan
(Frames 2 & 3).
3
Battery Receptacle
User installed CR1220 lithium coin cell battery provides power to the Real Time Clock (Optional, not supplied).
4
DPI Port 2 Cable connection for handheld and
remote HIM options.
5
Embedded EtherNet/ IP Address Selectors
Rotary switches for setting lowest octet of EtherNet address (forces address to
192.168.1.xxx).
6
Embedded EtherNet/ IP Connector
Network cable connection.
7
Jumper J2 SAFETY Safety enable jumper. Removed when
safety option is installed.
8
Jumper J1 ENABLE Hardware enable jumper. Removed
when a hardware enable configuration is utilized.
9 TB1 I/O terminal block.
Fig. 10 — PF755 Main Control Board
TB1 I/O Terminal Designations
FIXED I/O TERMINAL NAME DESCRIPTION
Di 0ac
Digital Input 120V AC Connections for AC power supply.
Di C
Digital Input Common Digital input common
Di 0dc
Digital Input 24V DC Connections for DC power supply.
+24V
+24 Volt Power Connections for drive supplied 24V power.
24VC
24 Volt Common
IMPORTANT: Wiring to pluggable terminal block connectors should be supported by wire ties or other means to help pre­vent unintentional disconnection
Di 0ac
Di C
Di 0dc
+24V
24VC
a19-1921
(A to B, B to C, C to A)
Vmin = Minimum measured phase-to-phase voltage
Imbalance Calculation Formula
Va v g =
Imbalance % =
(VAB + VBC + VCA)
3
(Vmax – Vmin) x 100
Va v g
8. Take a final thermal measurement of the capacitor bank and power after finalizing the installation to ensure all connections are good.
9. If a ground fault occurs, then do the following: a. Check for a ground in the motor or motor wiring. b. Check for damage to wiring insulation and that
wiring is dry.
c. Verify the motor wiring is separated from ground
and there is no connection between phases.
d. Check for failed IGBTs.
10. If an Overcurrent fault occurs, then do the following: a. Check for excessive load and verify load limit set-
tings on the ICVC.
b. Check motor and wiring insulation. c. Check parameter settings on VFD_CONF screen
in the ICVC.
Check Internal Jumpers — On the Main VFD Con-
trol board there are two jumpers labeled J1 HARDWARE EN­ABLE and J2 SAFETY ENABLE. J1 should be removed and J2 should be in place. See Fig. 10.
There are two jumper wires that connect a particular termi­nal to chassis ground. The MOV and AC EMI jumper should be connected to the PE-A terminal. The COMMON MODE CAPACITORS to GROUND jumper should be connected to a standoff rather than the PE-B terminal.
Use the recommended tools as follows when connecting jumper wires in Frame 6 and in Frame 7:
• Recommended torque (screws and nuts) = 1.36 N·m
(120.0 lb·in)
• Recommended hex socket = 7 mm
• Recommended screwdriver = T20 star type
See Fig. 11A and Fig. 11B for the correct positions of the jumpers.
7
Troubleshooting the Drive —
Fig. 11A — Jumper Wire Locations — Frame 6
A19-1835
Fig. 11B — Jumper Wire Locations — Frame 7
A19-1836
2
8
5
79
13
46
Allen-Bradley
Fig. 12 — Drive Status Indicator
A1 9­1815
The drive can display two kinds of error codes on the ICVC called the Alert and Alarm codes. These codes signal a problem detected during self tuning or drive operation. Alert and Alarm codes are locat­ed in the 19XRV Start-Up, Operation and Maintenance Instruc­tions. Note the following differences between Carrier and Allen-Bradley terminology:
• A warning message on the ICVC is an ALERT.
• The same warning viewed with Rockwell Drive Explorer
is a VFD ALARM.
• A failure resulting in a shutdown is seen as an ALARM
on the ICVC and as a VFD FAULT when viewed with Drive Explorer.
CONDITION CODES ICVC ALERT = VFD ALARM ICVC ALARM = VFD FAULT See Tables 3-6 and Fig. 12.
ICVC ALERT CODES — An alert condition is indicated by a message at the top of the ICVC default screen. In addition, an exclamation point (!) will appear next to any affected point on an ICVC display screen. The drive will continue to operate during the alert condition. Investigate the cause of the alert to ensure it does not lead to a fault condition. The alert code will automatically be cleared from the ICVC when the condition causing the alert no longer exists. See Table 4.
ICVC ALARM CODES — An alarm condition is also indi­cated by a message at the top of the ICVC default screen. If an alarm occurs, the drive coasts to stop. The STS (status) light on the drive will turn from Green to Red or Yellow (see Table 3). The detected fault message is maintained on the display until it is cleared by pressing the RESET softkey. See Table 5.
TEST EQUIPMENT NEEDED TO TROUBLESHOOT — An isolated multimeter adequately rated for the DC bus volt­age will be needed to measure DC bus voltage and to make resistance checks. Note that dedicated troubleshooting test points are not provided.
SERVICE
WARNING
DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are discharged before touch­ing any internal components. Failure to observe this pre­caution could result in severe bodily injury or loss of life.
8
Table 3
SWING UP KEY PAD MOUNT TO ACCESS
CONTROL BOARDS
Fig. 13 — Drive Module with Cover Removed
a19-1843
NAME COLOR STATE DESCRIPTION
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running. A type 2 (non-configurable) alarm condition exists and the
Steady Drive is not running, a type 1 alarm condition exists. The drive can be started.
STS (Status)
ENET
LINK
NOTES:
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms are user configurable.
Red Flashing A major fault has occurred. Drive cannot be started until fault condition is
Steady A non-resettable fault has occurred.
Red/Yellow Flashing Alternately A minor fault has occurred. When running, the drive continues to run. System is
Green/Red Flashing Alternately Drive is flash updating. None (Unlit) Off Adapter and/or network is not powered, adapter is not properly connected to
Red Flashing An EtherNet/IP connection has timed out.
Steady Adapter failed the duplicate IP address detection test. Red/Green Flashing Alternately Adapter is performing a self-test. Green Flashing Adapter is properly connected but is not communicating with any devices on
Steady Adapter is properly connected and communicating on the network. None (Unlit) Off Adapter is not powered or is not transmitting on the network. Green Flashing Adapter is properly connected and transmitting data packets on the network.
Steady Adapter is properly connected but is not transmitting on the network.
Drive Status Indicator Descriptions
drive cannot be started.
cleared.
brought to a stop under system control. Fault must be cleared to continue. Use parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major fault.
the network, or adapter needs an IP address.
the network.
2. A Type 2 alarm indicates that a configuration error exists and the drive cannot be started. Type 2 alarms are not configurable.
VERIFYING THAT DC BUS CAPACITORS ARE DIS­CHARGED — The drive’s DC bus capacitors retain hazard­ous voltages after input power has been disconnected. Perform the following steps before touching any internal components:
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power terminals.
3. Measure the DC bus potential with a voltmeter while standing on a non-conductive surface and wearing insu­lated gloves (1000 V). Measure the DC bus potential. See Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and 477-amp drives. The voltage between DC+ and DC-, and from each DC terminal to the chassis must be zero before proceeding.
4. Once the drive has been serviced, reapply input power.
HIGH TEMPERATURE ALARMS — Coolant flow through the cold plate is controlled by an orifice in the refriger­ant line leaving the cold plate. The orifice looks like one of the O-ring face seal connectors and in fact is used as one of the connections on the coolant tubing. The difference is that the passage through the fitting is 0.375 in. (9.5 mm). If the orifice is present and condenser liquid flow is present, the liquid will flash to cooler temperature at the orifice. This temperature dif­ference is great enough to be easily felt.
MAIN CONTROL BOARD (MCB) COMPONENTS — Figure 13 shows the drive module with the cover removed. To access the control boards, loosen the screw on the face of the keypad mount and swing the keypad mount upward.
The components on the main control board (MCB) are shown in Fig. 14. Note the location of the terminals labeled MCB I/O. The high pressure switch is wired to these terminals as shown in Fig. 15. In the event of a high condenser pressure alarm, the connections at these terminals should be checked and tightened if necessary.
A typical wiring schematic is shown in Appendix A.
9
DPI PORT 02 (COMPUTER PORT)
DIGITAL INPUT TERMINAL BLOCKS (SLOTS 04 & 05)
ETHERNET/IP ADDRESS SWITCHES
DIGITAL OUTPUT TERMINAL BLOCKS (SLOTS 04 & 05)
EMBEDDED ETHERNET/IP PORT
MCB I/O TERMINALS (AUX FAULT / HIGH PRESSURE FAULT / ENABLE INPUT)
Fig. 14 — MCB (Main Control Board) Components
a19-1844
*Located outside of starter; connected by field wiring.
Fig. 15 — High Pressure Switch Wiring
a19-1925
10
Table 4 — ICVC Alert Codes
PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
ICVC FAULT
STATE
100 PRESTART
101 PRESTART
102 PRESTART
103 PRESTART
104 PRESTART
105 PRESTART
106 PRESTART
107 PRESTART
108 PRESTART
109 PRESTART
110 PRESTART
111 PRESTART
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
SECONDARY
MESSAGE
STARTS LIMIT EXCEEDED
HIGH BEARING TEMPERATURE
HIGH MOTOR TEMPERATURE
HIGH DISCHARGE TEMP
LOW REFRIGERANT TEMP
LOW OIL TEMPERATURE
HIGH CONDENSER PRESSURE
LOW LINE VOLTAGE
HIGH LINE VOLTAGE
GUIDE VANE CALIBRATION
HIGH RECTIFIER TEMP
HIGH INVERTER TEMP
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
100Excessive compressor starts (8 in 12 hours).
101Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*.
102Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*.
103Comp Discharge Temp [VALUE] exceeded limit of [LIMIT]*.
104Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*.
105Oil Sump Temp [VALUE] exceeded limit of [LIMIT]*.
106Condenser Pressure [VALUE] exceeded limit of [LIMIT]*.
107Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*.
108Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*.
109Actual Guide Vane Pos Calibration Required Before Startup.
110Rectifier Temperature [VALUE] exceeded limit of [LIMIT]*.
111Inverter Temperature [VALUE] exceeded limit of [LIMIT]*.
Depress the RESET softkey if additional start is required. Reassess start-up requirements.
Check oil heater for proper operation. Check for low oil level, partially closed oil sup­ply valves, clogged oil filters. Check the sensor wiring and accuracy. Check Comp Thrust Brg Alert setting in SETUP1 screen.
Check motor sensors for wiring and accuracy. Check motor cooling line for proper operation, or restrictions. Check for excessive starts within a short time span. Check Comp Motor Temperature Override setting in SETUP1 screen.
Allow discharge sensor to cool. Check sensor wiring and accuracy. Check for excessive starts. Check Comp Discharge Alert setting in SETUP1 screen.
Check transducer wiring and accuracy. Check for low chilled fluid supply temperatures. Check refrigerant charge. Check Refrig Override Delta T in SETUP1 screen.
Check oil heater contactor/relay and power. Check oil level and oil pump operation.
Check transducer wiring and accuracy. Check for high condenser water temperatures. Check high condenser pressure switch wiring.
Check voltage supply. Check voltage transformers and switch gear. Consult power utility if voltage is low.
Check voltage supply. Check power transformers. Consult power utility if voltage is high.
Press STOP button on ICVC and perform Guide Vane Calibration in Controls Test screen. Check guide vane actuator feedback potentiometer.
Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage.
Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage.
11
NORMAL RUN WITH OVERRIDES
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
120 RUN CAPACITY
121 RUN CAPACITY
122 RUN CAPACITY
123 RUN CAPACITY
124 RUN CAPACITY
125 RUN CAPACITY
126 RUN CAPACITY
127 RUN CAPACITY
128 RUN CAPACITY
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
SECONDARY
MESSAGE
HIGH CONDENSER PRESSURE
HIGH MOTOR TEMPERATURE
LOW EVAP REFRIG TEMP
HIGH COMPRESSOR LIFT
MANUAL GUIDE VANE TA R GE T
LOW DISCHARGE SUPERHEAT
HIGH RECTIFIER TEMP 126Rectifier Temperature
MANUAL SPEED CONTROL
HIGH INVERTER TEMP 128Inverter Temperature
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
120Condenser Pressure [VALUE] exceeded limit of [LIMIT]*.
121Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*.
122Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*.
123Surge Prevention Override: Lift Too High For Compressor
124Run Capacity Limited: Manual Guide Vane Target.
No Alert message. Check for oil loss or excess refrigerant charge.
[VALUE] exceeded limit of [LIMIT]*.
No Alert message. Chiller is not in automatic temperature control.
[VALUE] exceeded limit of [LIMIT]*.
Check condenser water pump operation. Check for high condenser water temperatures or low flow rate. Verify that isolation valves are open. Check Cond Press Override setting in SETUP1.
Check for closed valves or restriction in motor cooling lines. Check for closed refrigerant isolation valves. Check Comp Motor Temp Override setting in SETUP1.
Check refrigerant charge. Check that optional cooler liquid line isolation valve is fully open. Check for excessive condenser flow or low chilled water flow. Check for low entering cooler temperature. Check that condenser inlet and outlet water nozzles are piped correctly. Check for waterbox division plate gasket bypass.
Check for high condenser water temperature or low suction temperature. Check for high Evaporator or Condenser approaches. Check surge prevention parameters in OPTIONS screen.
Target Guide Vane Position has been forced in the COMPRESS screen. Select and RELEASE force to return to normal (automatic) operation.
Verify that the valves in the oil reclaim lines are open.
Check Rectifier Temp Override in SETUP1 screen. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid. Check for proper VFD cooling fan operation and blockage.
Check Inverter Temp Override in SETUP1 screen. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid. Check for proper VFD cooling fan operation and blockage.
12
CHILLER ALERTS
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
140 SENSOR ALERT LEAVING COND WATER
141 SENSOR ALERT ENTERING COND WATER
142 LOW OIL
143 AUTORESTART
144 AUTORESTART
145 AUTORESTART
146 AUTORESTART
147 AUTORESTART
148 AUTORESTART
149 SENSOR ALERT HIGH DISCHARGE TEMP 149
150 SENSOR ALERT HIGH BEARING
151 CONDENSER
152 RECYCLE ALERT EXCESSIVE RECYCLE
153 no message:
154 POTENTIAL
155 OPTION SENSOR
156 OPTION SENSOR
157 OPTION SENSOR
158 SENSOR ALERT SPARE TEMPERATURE#1158Spare Temperature 1
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
PRESSURE ALERT
PENDING
PENDING
PENDING
PENDING
PENDING
PENDING
PRESSURE ALERT
ALERT only
FREEZE-UP
FAULT
FAULT
FAULT
SECONDARY
MESSAGE
TEMP
TEMP CHECK OIL FILTER 142Low Oil Pressure Alert.
LINE CURRENT IMBALANCE
LINE VOLTAG E DROP OUT
HIGH LINE VOLTAGE 145High Percent Line
LOW LINE VOLTAGE 146Low Percent Line
VFD MODULE RESET 147->VFD Module Power-On
POWER LOSS 148Control Power-Loss
TEMPERATURE
PUMP RELAY ENERGIZED
STARTS
no message; ALERT only 153Lead/Lag Disabled-
COND PRESS/TEMP TOO LOW
REMOTE RESET SENSOR
AUTO CHILLED WATER RESET
AUTO DEMAND LIMIT INPUT
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
140Sensor Fault: Check Leaving Cond Water Sensor.
141Sensor Fault: Check Entering Cond Water Sensor.
Check Oil Filter.
143Line Current Imbal­ance: Check VFD Fault His­tory for Values.
144Single Cycle Line Voltage Dropout.
Voltage [VALUE].
Voltage [VALUE].
Reset When Running.
When Running.
Comp Discharge Temp [VALUE] Exceeded Limit of [LIMIT]*.
150Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*.
151High Condenser Pres­sure [VALUE]: Pump Ener­gized to Reduce Pressure.
152Excessive recycle starts.
Config: Duplicate Chiller Address.
154Condenser freeze up prevention.
155Sensor Fault/Option Disabled: Remote Reset Sensor.
156Sensor Fault/Option Disabled: Auto Chilled Water Reset.
157Sensor Fault/Option Disabled: Auto Demand Limit Input.
[VALUE] exceeded limit of [LIMIT]*.
Check sensor resistance or voltage drop. Check for proper wiring.
Check sensor resistance or voltage drop. Check for proper wiring.
Check for partially or closed shut-off valves. Check oil filter. Check oil pump and power supply. Check oil level. Check for foaming oil at start-up. Check transducer wiring and accuracy.
Power loss has been detected in any phase. Chiller automatically restarting.
A drop in line voltage has been detected within 2 voltage cycles. Chiller automatically restarting if Auto Restart is enabled in OPTIONS screen.
Check phase to phase and phase to ground line power.
Check phase to phase and phase to ground line power.
VFD Module has detected a hardware fault due to electrical noise, power loss or software and has reset. Chiller automatically restarting. Check for power loss and sources of electro­magnetic interference.
Check 24 vac control power supply to ICVC.
Check sensor resistance or voltage drop. Check for proper wiring. Check for proper inlet guide vane and optional diffuser actuator operation. Check for proper condenser flow and temperature. Check for high lift or low load. Check for fouled tubes or noncondensables in the chiller.
Check sensor resistance or voltage drop. Check for proper wiring. Check for partially closed service valves. Check oil cooler TXV. Check oil level and oil temperature.
Check sensor wiring and accuracy. Check condenser flow and water temperature. Check for fouled tubes. This alarm is not caused by the High Pressure Switch.
Chiller load is too low to keep compressor on line and there has been more than 5 starts in 4 hours. Increase chiller load, adjust hot gas bypass, increase RECYCLE RESTART DELTA T from SETUP1 Screen.
Illegal chiller address configuration in Lead/Lag screen. Both chillers require a different address.
The condenser pressure transducer is reading a pressure that could freeze the condenser tubes. Check for condenser refrigerant leaks. Check fluid temperature. Check sensor wiring and accuracy. Place the chiller in PUMPDOWN mode if the vessel is evacuated.
Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4.
Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4. Check Spare Temp #1 Limit in SETUP1 screen.
13
CHILLER ALERTS (cont)
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
159 SENSOR ALERT SPARE TEMPERATURE#2159Spare Temperature 2
161 LOSS OF
162 SENSOR ALERT EVAPORATOR
163 SENSOR ALERT CONDENSER APPROACH 163Condenser Approach
164 VFD SPEED ALERT LOW VFD SPEED 164Actual VFD Speed
165 AUTORESTART
166 AUTORESTART
167 SYSTEM ALERT HIGH DISCHARGE TEMP 167Comp Discharge Temp
168 SENSOR ALERT HUMIDITY SENSOR
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
COMMUNICATION
PENDING
PENDING
SECONDARY
MESSAGE
WITH WSM 161WSM Cool Source —
APPROACH
LOW DC BUS VOLTAGE 165Low DC Bus Voltage:
HIGH DC BUS VOLTAGE 166High DC Bus Voltage:
INPUT
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
[VALUE] exceeded limit of [LIMIT]*.
Loss of Communication.
162Evaporator Approach [VALUE] Exceeded Limit of [LIMIT]*.
[VALUE] Exceeded Limit of [LIMIT]*.
exceeded limit of Target VFD Speed –10%.
[VALUE] Exceeded Limit of [LIMIT]*.
[VALUE] Exceeded Limit of [LIMIT]*.
[VALUE] exceeded limit of [LIMIT]*.
168Sensor Fault: Check Humidity Sensor Input Sensor.
Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4. Check Spare Temp #2 Limit in SETUP1 screen.
Check settings in WSMDEFME screen. Check CCN communications link with WSM (Water System Manager) Module. Check Supervisory Part of WSM.
Check that refrigerant charge level is adequate, waterbox division plate gaskets are sealing, evaporator tubes are not fouled and that oil reclaim system is working. Check sensor resistance or voltage drop. Check for proper wiring. Check Evap Approach Alert setting in SETUP1 screen.
Check sensors resistance or voltage drop. Check for proper wiring. Check Cond Approach Alert setting in SETUP1 screen. Check for noncondensable gas in the condenser. Check that the condenser tubes are not fouled.
Actual VFD Speed on COMPRESS screen must be at least 90% of Target VFD Speed.
Verify phase to phase and phase to ground line voltage.
Verify phase to phase and phase to ground line voltage. Monitor AC line for high transient volt­age conditions.
Check sensor resistance or voltage drop. Check for proper wiring. Check for excessive starts. Check Comp Discharge Alert setting in SETUP1 screen.
Check humidity sensor wiring on CCM connec­tors J3 and J5. CCM switch SW2-1 must be in “OFF” position. Check Humidity Sensor Input in Controls Test.
14
CHILLER PROTECTIVE LIMIT FAULTS
Table 5 — ICVC Alarm Codes
ICVC FAULT
STATE
200 PROTECTIVE LIMIT RECTIFIER POWER
201 PROTECTIVE LIMIT INVERTER POWER FAULT 201Inverter Power Fault:
202 PROTECTIVE LIMIT MOTOR AMPS NOT
203 FAILURE TO START MOTOR ACCELERATION
204 FAILURE TO STOP VFD SHUTDOWN FAULT 204VFD Shutdown Fault:
205 PROTECTIVE LIMIT HIGH DC BUS VOLTAGE 205High DC Bus Voltage:
206 PROTECTIVE LIMIT VFD FAULT 206VFD Fault Code:
207 PROTECTIVE LIMIT HIGH CONDENSER
208 PROTECTIVE LIMIT EXCESSIVE MOTOR
209 PROTECTIVE LIMIT LINE CURRENT
210 PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210Single Cycle Line Volt-
211 PROTECTIVE LIMIT HIGH LINE VOLTAGE 211High Percent Line Volt-
212 PROTECTIVE LIMIT LOW LINE VOLTAGE 212Low Percent Line Volt-
213 PROTECTIVE LIMIT VFD MODULE RESET 213VFD Module Power-On
214 PROTECTIVE LIMIT POWER LOSS 214Control Power Loss
215 PROTECTIVE LIMIT LOW DC BUS VOLTAGE 215Low DC Bus Voltage:
216 PROTECTIVE LIMIT LINE VOLTAGE
217 PROTECTIVE LIMIT MOTOR OVERLOAD TRIP 217Motor Overload Trip;
218 PROTECTIVE LIMIT VFD RECTIFIER
219 PROTECTIVE LIMIT VFD INVERTER
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
NOTE: ICVC Alarms 212-226 are declared as a result of VFD Faults.
PRIMARY
MESSAGE
SECONDARY
MESSAGE
FAULT
SENSED
FAULT
PRESSURE
AMPS
IMBALANCE
IMBALANCE
OVERTEMP
OVERTEMP
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
200Rectifier Power Fault: Check VFD Status.
Check VFD Status. 202Motor Amps Not
Sensed — Average Load Current [VALUE].
203Motor Acceleration Fault — Average Load Current [VALUE].
Check Inverter Power Unit.
[VALUE] exceeded limit of [LIMIT]*.
[VALUE]; Check VFD Fault Code List.
207High Cond Pressure trip. [VALUE] exceeded Switch Trippoint.
208Percent Load Current [VALUE] exceeded limit of [LIMIT]*.
209Line Current Imbal­ance: Check VFD Fault His­tory for Values.
age Dropout.
age [VALUE].
age [VALUE].
Reset When Running.
When Running.
[VALUE] exceeded limit of [LIMIT]*.
216Line Voltage Imbal­ance. Check VFD Fault His­tory for Values.
Check VFD configurations.
218VFD Rectifier Temp Exceeded: Check Cooling and VFD Config.
219VFD Inverter Temp Exceeded: Check Cooling and VFD Config.
Malfunction within VFD Power Module. Call Carrier Service.
Malfunction within VFD Power Module. Call Carrier Service.
Check main circuit breaker for trip. Increase Current % Imbalance in VFD_CONF screen.
Check that inlet guide vanes are fully closed at start-up. Check Motor Rated Load Amps in VFD_CONF screen. Reduce unit pressure if possible.
VFD Circuit Board malfunction. Call Carrier Service.
Verify phase to phase and phase to ground line voltage. Monitor AC line for high transient volt­age conditions. VFD Circuit Board malfunction. Call Carrier Service.
See VFD Fault Code description and corrective action.
Check Compressor Discharge High Pressure switch wiring and accuracy. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables in refrigerant.
Check Motor Rated Load Amps in VFD_CONF screen. Percent Load Current > 110 Check Motor Rated Load Amps setting.
Check phase to phase and phase to ground power distribution bus voltage. Check Line Current % Imbalance in VFD_CONF screen. Consult power company.
Temporary loss of voltage. Disable Single Cycle Dropout in VFD_CONF screen.
Check phase to phase and phase to ground dis­tribution bus voltage. Consult power company.
Check phase to phase and phase to ground dis­tribution bus voltage. Consult power company.
Temporary loss of VFD control voltage. Check VFD control power breaker, transformer and fuses.
Check phase to phase and phase to ground dis­tribution bus voltage. Check VFD fuses. Check 24 vac power supply to ICVC. Consult power company.
Verify phase-to-phase and phase-to-ground line voltage. VFD Circuit Board malfunction. Call Carrier Service.
Check phase-to-phase and phase-to-ground distribution bus voltage. Increase Line Voltage % Imbalance in VFD_CONF screen.
Any phase current > 106% Rated Load Amps. Can result from significant load side current imbalance when running at full load. Check entering condenser water temperature and water flow rate. Check Motor Rated Load Amps in VFD_CONF screen.
Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage.
Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage.
%.
15
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
220 PROTECTIVE LIMIT GROUND FAULT 220Ground Fault Trip;
221 PROTECTIVE LIMIT UNUSED 221UNUSED 222 PROTECTIVE LIMIT LINE FREQUENCY TRIP 222Line Frequency —
223 LOSS OF
224 PROTECTIVE LIMIT VFD COMMUNICATIONS
225 PROTECTIVE LIMIT MOTOR CURRENT
226 PROTECTIVE LIMIT LINE PHASE REVERSAL 226Line Phase Reversal:
227 PROTECTIVE LIMIT OIL PRESS SENSOR
228 PROTECTIVE LIMIT LOW OIL PRESSURE 228Low Operating Oil
229 PROTECTIVE LIMIT LOW CHILLED WATER
230 PROTECTIVE LIMIT LOW CONDENSER
231 PROTECTIVE LIMIT HIGH DISCHARGE TEMP 231Comp Discharge Temp
232 PROTECTIVE LIMIT LOW REFRIGERANT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
COMMUNICATION
SECONDARY
MESSAGE
WITH VFD GATEWAY MODULE
FAULT
IMBALANCE
FAULT
FLOW
WATER FLOW
TEMP
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
Check Motor and Current Sensors.
[VALUE] exceeded limit of [LIMIT]; Check Power Supply.
223Loss of SIO Comm with VFD Gateway: Check VFG Module and Power.
224Loss of DPI Comm with VFD Gateway: Check VFG to VFD Comm.
225Motor Current Imbal­ance: Check VFD Fault History for Values.
Check Line Phases. 227Oil Pressure Delta P
[VALUE] (Pump Off): Check Pump/Transducers.
Pressure [VALUE]: Check Oil Pump and Filter.
229Low Chilled Water Flow; Check Switch/Delta P Config & Calibration.
230Low Condenser Water Flow; Check Switch/Delta P Config & Calibration.
[VALUE] Exceeded Limit of [LIMIT]*.
232Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*.
Check for condensation on motor terminals. Check motor power leads for phase to phase or phase to ground shorts. Disconnect motor from VFD and megger motor. Call Carrier Service.
If operating from a generator, check generator size and speed. Check utility power supply.
Check VFD communication wiring and connectors on VFD Gateway and DPI board. Check for compatibility between ICVC and Gateway software.
Check VFD communication wiring and connectors. Check status lights on DPI Communications Interface Board. Call Carrier Service.
Check Motor Current % Imbalance in VFD_CONF screen.
Reverse connections of any two line conductors to circuit breaker.
Check transducer wiring and accuracy. Check power supply to pump. Check pump operation. Check transducer calibration.
Check transducer wiring and accuracy. Check power supply to pump. Check pump operation. Check oil level. Check for partially closed service valves. Check oil filters. Check for foaming oil at start-up. Check transducer calibration.
Perform pump control test. Check optional transducer calibration and wiring. Check Evaporator Refrigerant Temperature sensor. Check chilled water valves. Check for evaporator saturation temperature < 34 F if not in Pumpdown Lockout mode. Place unit in Pumpdown mode before removing charge.
Perform pump control test. Check optional transducer calibration and wiring. Check condenser water valves. Check for COND PRESS OVERRIDE + 5 psig.
Check for closed compressor discharge isola­tion valve. Check if chiller was operating in surge. Check sensor resistance or voltage drop. Check for proper wiring. Check for proper condenser flow and temperature. Check compressor discharge isolation valve. Check for proper inlet guide vane and optional diffuser actuator operation.
Check for proper refrigerant charge. Check float valve operation. Check for closed condenser liquid line isolation valve. If problem occurs at high load, check for low condenser pressure which causes inade­quate flasc orifice differential pressure. Check for proper water flow and temperature. Confirm that condenser water enters bottom row of condenser tubes first. Check Evaporator Refrigerant Temperature sensor. Check for division plate gasket bypass. Check for fouled tubes.
16
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
233 PROTECTIVE LIMIT HIGH MOTOR
234 PROTECTIVE LIMIT HIGH BEARING
235 PROTECTIVE LIMIT HIGH CONDENSER
236 PROTECTIVE LIMIT COMPRESS SURGE/
237 PROTECTIVE LIMIT SPARE SAFETY
238 PROTECTIVE LIMIT EXCESSIVE COMPR
239 PROTECTIVE LIMIT TRANSDUCER
240 PROTECTIVE LIMIT LOW DISCHARGE
241 PROTECTIVE LIMIT RECTIFIER
242 LOSS OF
243 POTENTIAL
244 POTENTIAL
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
COMMUNICATION
FREEZE-UP
FREEZE-UP
SECONDARY
MESSAGE
TEMPERATURE
TEMPERATURE
PRESSURE
LOW SPEED
DEVICE
SURGE
VOLTAGE FAULT
SUPERHEAT
OVERCURRENT WITH CCM MODULE 242Loss of Communica-
EVAP PRESS/TEMP TOO LOW
COND PRESS/TEMP TOO LOW
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
233Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*.
234Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*.
235Condenser Pressure [VALUE] exceeded limit of [LIMIT]*.
236Compressor Surge: Check condenser water temp and flow.
237Spare Safety Device. Spare safety input has tripped or factory installed
238Compressor Surge: Check condenser water temp and flow.
239Transducer Voltage Ref [VALUE] exceeded limit of [LIMIT]*.
240Check for Oil in Or Overcharge of Refrigerant.
241Rectifier Overcurrent Fault: Check VFD Status.
tion With CCM, Check Comm. Connectors.
243Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*.
244Condenser Refrig Temp [VALUE] exceeded limit of [LIMIT]*.
Check motor sensors wiring and accuracy. Check motor cooling line and spray nozzle for proper operation, or restrictions. Check for excessive starts within a short time span.
Check oil heater for proper operation. Check for low oil level, par tially closed oil supply valves, or clogged oil filter. Check oil cooler refrigerant thermal expansion valves. Confirm that TXV (thermostatic expansion valve) bulb is secured in place and insulated. Check for sensor wiring and accuracy. This fault can result from extended operation at low load with low water flow to the evaporator or condenser.
Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check transducer wiring and accuracy.
Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check surge prevention parameters in OPTIONS screen. Increase VFD Increase Step in SETUP2. Check VFD Minimum Speed in SETUP2 screen.
jumper is not present on Terminal Block 4 terminals 17 and 20 in the VFD enclosure.
Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check surge prevention parameters in OPTIONS screen. Check cooling tower control settings and perfor­mance to design/selection temperatures across the entire operating range of the chiller. Check cooler approach and water flow.
Check that CCM transducer voltage reference is between 4.5 v and 5.5 v. Check that pressure transducers are not shorted to ground. This fault is normally declared the first time an ICVC is powered up if it was downloaded with software when it was not connected to a CCM. Call Carrier Service.
Check for oil loss or excessive refrigerant. If oil level is low, refrigerant charge may be too low resulting in ineffective oil reclaim. Excessive refrigerant charge may cause liquid carryover into compressor. Check calibration of evaporator pressure and con­denser pressure sensors. Check calibration of compressor discharge temper­ature sensor.
Check for high water temperatures or changes in water flow rates.
Check wiring and control power to CCM. Confirm that all CCM SW1 switches are in the “OFF” position.
Check for proper refrigerant charge. Check float valve operation. Check for proper fluid flow and temperature. Confirm that condenser water enters bottom row of condenser tubes first. Check Evaporator Refrigerant Temperature sensor. Check for division plate gasket bypass. Check for fouled tubes.
Condenser water too cold or chiller shut down with brine below 32 F in cooler so equalization tempera­ture in chiller approached 32 F. Check condenser pressure transducer. Check refrigerant charge.
17
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
245 PROTECTIVE LIMIT HIGH VFD SPEED 245Actual VFD Speed
246 PROTECTIVE LIMIT INVALID DIFFUSER
247 PROTECTIVE LIMIT DIFFUSER POSITION
248 PROTECTIVE LIMIT SPARE TEMPERATURE #1248Spare Temperature #1
249 PROTECTIVE LIMIT SPARE TEMPERATURE #2249Spare Temperature #2
250 UNUSED UNUSED 250Unused State. 251 PROTECTIVE LIMIT VFD CONFIG CONFLICT 251VFD Config Conflict
252 PROTECTIVE LIMIT VFD CONFIG CONFLICT 252VFD Config Conflict
253 PROTECTIVE LIMIT GUIDE VANE
254 PROTECTIVE LIMIT VFD CHECKSUM ERROR 254Checksum Error:
255 PROTECTIVE LIMIT VFD DEW PREVENTION 255Dew Prevention - Cool-
256 PROTECTIVE LIMIT INDUCTOR OVERTEMP 256Inductor Overtemp Trip -
257 PROTECTIVE LIMIT VFD START INHIBIT 257VFD Start Inhibit: Check
258 UNUSED STATE UNUSED 258Unused.
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
SECONDARY
MESSAGE
CONFIG.
FAULT
CALIBRATION
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
exceeded limit of Target VFD Speed + 10%.
246Diffuser Control Invalid Configuration: Check SETUP2 Entries.
247Diffuser Position Fault: Check Guide Vane/Diffuser Actuator.
[VALUE] exceeded limit of [LIMIT]*.
[VALUE] exceeded limit of [LIMIT]*.
(VFD Uploaded): Verify to Reset Alarm.
(VFD Downloaded): Verify to Reset Alarm.
253Guide Vane Fault [VALUE]. Check Calibration.
Press Reset to Restore Configuration
ant Too Cold. Check Solenoid & Cond T.
Check Temp Switch and Cool­ing Fans.
VFD Diagnostic Parameters 212/214.
Actual VFD Speed on COMPRESS screen must not exceed Target VFD Speed by more than 10%.
Check 25%, 50%, and 75% Guide Vane and Dif­fuser Load Point entries in SETUP2 screen.
Confirm that Diffuser Option in SETUP 2 screen has not been Enabled if compressor does not have a split ring diffuser. May indicate rotating stall condition. Check rotating stall transducer wiring accuracy and sealing. Check diffuser schedule and guide vane sched­ule in SETUP2 screen. Check for proper operation of diffuser and inlet guide vane actuators including inlet guide vane calibration. Check diffuser actuator coupling for rotational slip. Check RC snubber on CCM J4-23 and J4-24. Check 4.3k ohm resistor between CCM termi­nals J3-7 and J3-8. Check for electrical noise in CCM Diffuser Pres­sure wiring. Do not continue to operate com­pressor except for diagnostic purposes.
Check Spare Temperature Enable and Spare Temperature Limit in SETUP1 Screen.
Check Spare Temperature Enable and Spare Temperature Limit in SETUP1 Screen.
The VFD_CONF table in the Gateway does not match that which is in the ICVC. This is a normal fault if an ICVC has been uploaded with soft­ware when it was not attached to the CCM. Enter VFD_CONF screen and then exit VFD_CONF screen by pressing EXIT then CANCEL. Re-enter the VFD_CONF screen, press EXIT then SAVE. Parameters stored in the Gateway will be uploaded into the ICVC. Confirm valid settings in VFD_CONF screen.
The VFD_CONF table in the Gateway does not match that which is in the ICVC.
Enter CONTROL TEST and execute Guide Vane Calibration. Check CCM guide vane feedback terminals J4-9 and J4-10. Check guide vane feedback potentiometer. Alarm before start indicates guide vane opening is not less than 4%. Alarm running indicates guide vane position is < -1% or > 103%, or feed- back voltage is < .045 or > 3.15 VDC.
Actual VFD checksum does not match calcu­lated value.
VFD COLDPLATE TEMP is too close to dew point based on VFD ENCLOSURE TEMP and RELATIVE HUMIDITY in POWER screen. Check for moisture in VFD enclosure. Check Humidity Sensor in CONTROLS TEST. Check for contamination on CCM J3-7 and J3-9 Humidity Sensor. Check that VFD refrigerant cooling modulating valve is closing.
Check for cooling fan air flow obstructions.
The VFD Start Inhibit is derived from the Alarm bit being set in the VFD. The conditions causing the alarm must be corrected in the VFD to enable subsequent starts and operation. See VFD parameters 212/214.
18
Table 5 — ICVC Alarm Codes (cont)
CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
STATE
259 PROTECTIVE LIMIT CCN OVERRIDE STOP 259CCN Emergency/
282 PROTECTIVE LIMIT INVALID VFD CONFIG 282Line Frequency
283 PROTECTIVE LIMIT INVALID VFD CONFIG 283Compressor 100%
284VFD GATEWAY COMPATIBILITY
285VFD GATEWAY COMPATIBILITY
286 PROTECTIVE LIMIT INVERTER
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
OUT-OF-RANGE SENSOR
PRIMARY
MESSAGE
SECONDARY
MESSAGE
CONFLICT
CONFLICT
OVERCURRENT
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
Override Stop.
[VALUE] Exceeded Configura­tion Range.
Speed Config Ranges: 50=Hz 45-52; 60 Hz=55-62.
284VFD Gateway Compati­bility Conflict: Check VFG/ VFD Versions.
285VFD Gateway Compati­bility Conflict: Check VFG/ ICVC Versions.
286Inverter Overcurrent Fault: Check VFD Status.
CCN has signaled the chiller to stop.This fault must be manually reset from the default screen of the ICVC.
LINE FREQUENCY in POWER screen must be maintained between 45-52 Hz if LINE FREQ=60Hz? is set to NO(50 Hz). LINE FRE­QUENCY must be maintained between 55-62 Hz if LINE FREQ=60Hz? is set to YES (60 Hz). Check high pressure switch and connections to TB4-24 and TB4-25.
COMPRESSOR 100% SPEED in VFD_CONF screen must be set between 45-52 Hz if LINE FREQ=60Hz? is set to NO(50 Hz). COMPRES­SOR 100% SPEED must be set between 55-62 Hz if LINE FREQ=60Hz? is set to YES (60 Hz).
VFD Gateway and VFD software versions are not compatible. Call Carrier Service.
VFD Gateway and ICVC software versions are not compatible. Call Carrier Service.
Check for high entering water temperature or low condenser water flow. Check current settings in VFD_CONF screen.
ICVC FAULT
STATE
260 SENSOR FAULT LEAVING CHILLED WATER 260Sensor Fault: Check
261 SENSOR FAULT ENTERING CHILLED
262 SENSOR FAULT CONDENSER PRESSURE 262Sensor Fault: Check
263 SENSOR FAULT EVAPORATOR
264 SENSOR FAULT COMPRESSOR BEARING
265 SENSOR FAULT COMPRESSOR MOTOR
266 SENSOR FAULT COMP DISCHARGE TEMP 266Sensor Fault: Check
267 SENSOR FAULT OIL SUMP TEMP 267Sensor Fault: Check Oil
268 SENSOR FAULT COMP OIL PRESS DIFF 268Sensor Fault: Check Oil
269 SENSOR FAULT CHILLED WATER FLOW 269Sensor Fault: Check
270 SENSOR FAULT COND WATER FLOW 270Sensor Fault: Check
271 SENSOR FAULT EVAP SATURATION TEMP 271Sensor Fault: Check
PRIMARY
MESSAGE
SECONDARY
MESSAGE
WATER
PRESSURE
TEMP
TEMP
PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
Leaving Chilled Water Sensor.
261Sensor Fault: Check Entering Chilled Water Sensor.
Condenser Pressure Sensor.
263Sensor Fault: Check Evaporator Pressure Sensor.
264Sensor Fault: Check Comp Thrust Brg Temp Sensor.
265Sensor Fault: Check Comp Motor Winding Temp Sensor.
Comp Discharge Temp Sensor.
Sump Temp Sensor.
Pump Delta P Sensor.
Chilled Water Delta P Sensor.
Cond Water Delta P Sensor.
Evap Saturation Temp Sensor.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor wiring. Check for disconnected or shorted wiring. Check for condensation in transducer connector.
Check sensor wiring. Check for disconnected or shorted wiring. Check for condensation in transducer connector.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
Check sensor wiring and accuracy. Check for disconnected or shorted wiring. If pressure transducers are not installed, check for presence of resistors and jumpers on lower CCM terminal block J3.
Check sensor wiring and accuracy. Check for disconnected or shorted wiring. If pressure transducers are not installed, check for presence of resistors and jumpers on lower CCM terminal block J3.
Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring.
19
Table 6
VFD FAULT CODE
ON VFD
HIST
SCREEN
NONE 206 Processor memory fault Consult VFD manual to resolve generic fault.
0 No Entry
2 207 Auxiliary Input Input is open.
3 210 Power Loss Line voltage dropout
4 215 Undervoltage Low DC bus voltage
5 166 Overvoltage High DC bus voltage
7 217 Motor Overload An internal electronic overload trip has occurred.
8 219
9 219
12 286 HW Overcurrent
13 220 Ground Fault
14 206 Ground Warning
15 206 Load Loss
17 216
20 206 TorqPrv Spd Band See VFD Fault Code 15 See VFD Fault Code 15
21 225 Output PhaseLoss
24 204 Decel Inhibit
33 206 AuRsts Exhausted See VFD Fault Code 15 See VFD Fault Code 15
36 286 SW Overcurrent
ICVC FAULT STATE
Heat Sink Over­temp
Transistor Over­temp
The DC bus ripple has exceeded a preset level.
Powerflex 755 Fault Code Descriptions and Corrective Actions
FAULT TYPE DESCRIPTION CORRECTIVE ACTION
Check Compressor Discharge High Pressure switch wiring and accuracy. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables in refrigerant.
Temporary loss of voltage. Disable Single Cycle Dropout in VFD_CONF sceen.
Verify phase-to-phase and phase-to-ground line voltage. VFD Circuit Board malfunction. Call Carrier Service.
Verify phase to phase and phase to ground line voltage. Monitor AC line for high transient voltage conditions.
Any phase current > 106% RLA. Can result from significant load side current imbalance when running at full load. Check entering condenser water temperature and water flow rate. Check Motor Rated Load Amps in VFD_CONF screen.
Check that VFD refrigerant isolation valves are
Heat sink temperature has exceeded the maxi­mum operating temperature
The output transistors have exceeded the maxi­mum operating temperature
The drive output current has exceeded the hard­ware current limit.
A current path to earth ground greater than 25% of drive rating has occurred.
The ground current has exceeded the level set in P467
If this fault appears, there may be a problem with software configuration.
Line Voltage imbalance
The current in one or more phases has been lost or remains below a preset level.
The drive is not following a commanded decelera­tion because it is attempting to limit the bus volt­age.
The drive output current has exceeded the 1 ms current rating.
open. Check VFD refrigerant cooling orifice and refrig­erant strainer. Check for proper VFD cooling fan operation and air flow blockage.
Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling orifice and refrig­erant strainer. Check for proper VFD cooling fan operation and air flow blockage.
Check for high entering water temperature or low condenser water flow. Check current settings in VFD_CONF screen.
Check the motor, motor terminals, and external wiring to the drive output terminals for a grounded condition.
To reset the processor, cycle power to chiller, check ICVC VFD_CONF settings and save set­tings when exiting VFD_CONF screen. Check VFD parameters with Drive Explorer.
Check phase-to-phase and phase-to-ground dis­tribution bus voltage. Increase Line Voltage % Imbalance in VFD_CONF screen.
Check Motor Current % Imbalance in VFD_CONF screen.
Verify input voltage is within drive specified limits. Verify system ground impedance follows proper grounding techniques. Disable bus regulation P186 and/or add dynamic brake resistor and/or extend deceleration time P537 and P538.
Check for excess load, improper DC boost set­ting, DC brake volts set too high.
20
Table 6
VFD FAULT CODE
ON VFD
HIST
SCREEN
38 39 Phase V to Gnd
40 Phase W to Gnd
41 42 Phase VW Short
43 Phase WU Short
44 206
45 206 Phase VNot ToGnd
46 206
55 NONE Inverter Overtemp
61 206 Shear Pin 1 See VFD Fault Code 15 See VFD Fault Code 15 62 206 Shear Pin 2 See VFD Fault Code 15 See VFD Fault Code 15
64 206 Drive Overload Drive is overloaded
65 206 OW TrqLvlTimeout See VFD Fault Code 15 See VFD Fault Code 15 77 206 IR Volts Range See VFD Fault Code 15 See VFD Fault Code 15
78 206
79 206 Excessive Load
80 206 AutoTune Aborted See VFD Fault Code 15 See VFD Fault Code 15
87 206 IXo VoltageRange
91 206 Pri VelFdbk Loss See VFD Fault Code 15 See VFD Fault Code 15 93 206 HW Enable Check See VFD Fault Code 15 See VFD Fault Code 15 94 206 Alt VelFdbk Loss See VFD Fault Code 15 See VFD Fault Code 15 95 206 Aux VelFdbk Loss See VFD Fault Code 15 See VFD Fault Code 15 96 97 206 Auto Tach Switch See VFD Fault Code 15 See VFD Fault Code 15
100 206 Parameter Chksum
107 NONE Replaced MCB-PB
113 206 Tracking DataErr Internal data error.
124 206 App ID Changed Application firmware changed. Verify application version. 141 206 Autn Enc Angle P78 [Encdrlss AngComp] is out of range See VFD Fault Code 15 142 206 Autn Spd Rstrct See VFD Fault Code 15 See VFD Fault Code 15 143 206 Autotune CurReg See VFD Fault Code 15 See VFD Fault Code 15 144 206 Autotune Inertia See VFD Fault Code 15 See VFD Fault Code 15 145 206 Autotune Travel See VFD Fault Code 15 See VFD Fault Code 15
ICVC FAULT STATE
220
246
206 PositionFdbkLoss See VFD Fault Code 15 See VFD Fault Code 15
Powerflex 755 Fault Code Descriptions and Corrective Actions (cont)
FAULT TYPE DESCRIPTION CORRECTIVE ACTION
Phase U to Gnd
Phase UV Short
Phase UNot
Phase WNot
FluxAmpsRef Rang
GROUND FAULT
GROUND FAULT
GROUND FAULT (no LF2 equivalent)
The temperature sensor on the main control board detected excessive heat.
See VFD Fault Code 15 See VFD Fault Code 15
Motor did not come up to speed in the allotted time
Ixo voltae calculated from motor nameplate data is too high.
The checksum read from the board does not match the checksum calculated.
The main control board was moved to a different power structure. Data set to default values.
Check the wiring between the drive and the motor. Check motor for grounded phase. Check Motor terminals. d. Replace drive.
Check the wiring between the drive and the motor. Check Motor terminals. Replace drive.
Check the wiring between the drive and the motor. Check Motor terminals. Replace drive.
Check that VFD refrigerant isolation valves are open.Check VFD refrigerant strainer
Check for high entering water temperature or low condenser water flow. Check current settings in VFD_CONF screen.
Check that guide vanes are closed completely. Check for high entering water temperature or low condenser flow. Repeat Autotune
Re-enter motor nameplate data in VFD_CONF screen.
Press ICVC reset. Check VFD_CONF parameters. Cycle power to the drive.
Press ICVC reset. Check VFD_CONF parameters. Cycle power to the drive.
Press ICVC reset. Cycle power to the drive
21
Table 6
VFD FAULT CODE
ON VFD
HIST
SCREEN
168 206
210 206
211 206 Safety Brd Fault See VFD Fault Code 15 See VFD Fault Code 15 213 206 Safety Jumper In See VFD Fault Code 15 See VFD Fault Code 15 291 206 HSFan Lifwe See VFD Fault Code 15 See VFD Fault Code 15 292 206 InFan Life See VFD Fault Code 15 See VFD Fault Code 15 293 206 MtrBrg Life See VFD Fault Code 15 See VFD Fault Code 15 294 206 MtrBrg Lube See VFD Fault Code 15 See VFD Fault Code 15 295 206 MachBrg life See VFD Fault Code 15 See VFD Fault Code 15 296 206 MachBrg Lube See VFD Fault Code 15 See VFD Fault Code 15 315 206 Excess Psn Error See VFD Fault Code 15 See VFD Fault Code 15 316 206 Node Fault Error See VFD Fault Code 15 See VFD Fault Code 15
ICVC FAULT STATE
Powerflex 755 Fault Code Descriptions and Corrective Actions (cont)
FAULT TYPE DESCRIPTION CORRECTIVE ACTION
HeatSinkUnder­Tmp
HW En Jumper Out
Heatsink temperature sensor is reporting a value below -18.7 C (-1.66 F) or the sensor feedback circuit is open.
See VFD Fault Code 15 See VFD Fault Code 15
Check heat sink temperature sensor. Check heat sink temperature.
Checking Power Modules and Motor Input with Input Power Off — Use the following procedure
to check the drive’s power module circuitry with power off:
1. Turn off and lock out input power. Wait five minutes.
2. Verify there is no voltage at the drive’s input power termi­nals.
3. Using a voltmeter, check the DC bus potential as de­scribed above to ensure the DC bus capacitors are dis­charged.
4. Disconnect the motor from the drive.
5. Check all AC line and DC bus fuses.
6. Use a multimeter to check the input diodes and output IGBTs if a fuse is open.
7. Check motor impedance.
8. Reconnect the motor to the drive.
9. Reapply input power. See Tables 7 and 8.
WARNING
Confirm that the DC bus has discharged before performing diode checks.
Table 7
METER LEAD
(+) (-)
R DC+ 0.5 V
S DC+ 0.5 V T DC+ 0.5 V
R DC- infinite (OL)
S DC- Infinite (OL) T DC- Infinite (OL)
U DC+ 0.5 V
V DC+ 0.5 V
W DC+ 0.5 V
U DC- infinite (OL)
V DC- Infinite (OL)
W DC- Infinite (OL) DC+ R Infinite (OL) DC+ S Infinite (OL) DC+ T Infinite (OL)
DC- R 0.5 V DC- S 0.5 V
DC- T 0.5 V DC+ U Infinite (OL) DC+ V Infinite (OL) DC+ W Infinite (OL)
DC- U 0.5 V
DC- V 0.5 V
DC- W 0.5 V
NOTE: Digital meters require a special diode check function because the current sourced by the meter during a normal resis­tance (Ohms) test is too low to accurately test a diode. Make sure the meter is set to the diode test function. Voltage readings may not be exact as shown in above tables, but look for consistency during each of the 4 tests. When performing a test that should return infinity (OL) as shown in above tables, you may see a value slowly climbing toward infinity. This is a result of the meter charging a capacitor and is normal.
Diode Checks
METER READING
22
Servicing the Drive
Fig. 16 — Open Access Door
A19-1831
1
L1 L2 L3
O
I
2
DC+ DC–
0V
0V
LOCKOUT/TAGOUT
MULTIMETER
DC BUS TEST TERMINALS LOCATED INSIDE ACCESS DOOR
Fig. 17 — Check DC Bus Terminals
A19-1814
90°
SLIDE ENCLOSURE FORWARD
LOOSEN ENCLOSURE FASTENERS
Fig. 18 — Removing Enclosure
A19-1816
WARNING
To guard against possible personal injury and/or equipment damage:
1. Inspect all lifting hardware for proper attachment be­fore lifting drive.
2. Do not allow any part of the drive or lifting mecha­nism to make contact with electrically charged con­ductors or components.
3. Do not subject the drive to high rates of acceleration or deceleration while transporting to the mounting lo­cation or when lifting.
Do not allow personnel or their limbs directly underneath the drive when it is being lifted and mounted.
WARNING
DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are discharged before touch­ing any internal components. Failure to observe this pre­caution could result in severe bodily injury or loss of life.
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat or T20 star, open access door. See Fig. 16.
2. Check to be sure that the voltage between DC+ and DC­and from each DC terminal to the chassis is zero before proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
REMOVING THE DRIVE — The dimensions and weights specified must be taken into consideration when removing the drive. All lifting equipment and lifting components (hooks, bolts, lifts, slings, chains, etc.) must be properly sized and rated to safely lift and hold the weight of the drive while removing it. See Fig. 19. The drive weights are as follows:
• Drive weight for Frame 6: 85 lb.
• Drive weight for Frame 7: 160 - 249 lb.
When replacing the drive, reverse the procedures and tight­en to the torques for the Frames 6 and 7 Power Terminal Block referred to in Table 8.
Table 8
FRAME
RIGGING THE ENCLOSURE —
Frames 6 and 7 Power Terminal Block
MAXIMUM LUG
WIDTH 6 34.6 mm (1.36 in.) 11.3 N 7 43.5 mm (1.71 in.) 11.3 N
RECOMMENDED
TORQUE
·m (100 in.-lb) M8 x 1.25
·m (100 in.-lb) M8 x 1.25
Where overhead room
TERMINAL BOLT SIZE
and/or clearance in front of the drive enclosure is insufficient to allow the drive to be safely removed from the enclosure, the entire enclosure may have to be removed from the chiller.
The dimensions and weights specified must be taken into consideration when removing the enclosure. The total weight for Frames 6 and 7, including drive weight and enclosure, is 720 lb. All lifting equipment and lifting components (hooks, bolts, lifts, slings, chains, etc.) must be properly sized and rated to safely lift and hold the weight of the enclosure and drive while removing. See Fig. 20A and Fig. 20B.
23
DRIVE RIGGING ACCESS DRIVE WIDTH + 4 IN.
FRONT VIEW
SIDE VIEW
DRIVE RIGGING ACCESS
2 IN.
2 IN.
DRIVE POSITIONED FOR VERTICAL LIFT
SUPPORT FROM BELOW
DRIVE EXTENDS BEHIND MAIN ENCLOSURE
Fig. 19 — Enclosure Access for Removing Drive
A19-1818
a19-1817
>
1
/
2 A
A
<45°
Fig. 20A — Rigging the Enclosure, Frame 6
A19-1837
>
1
/
2 A
A
<45°
Fig. 20B — Rigging the Enclosure, Frame 7
A19-1838
REPLACING THE GATEWAY (A-B20-750-20COMM OPTION CARD) — The following are the steps for remov­ing and replacing the existing gateway.
1. Disconnect power to the drive. Before removing the en­closure, open the access door on the front of the drive. See Fig. 16.
2. Check to be sure that the voltage between DC+ and DC­and from each DC terminal to the chassis is zero before proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove the 2 screws securing the mounting plate and re­move the mounting plate and COMM card. See Fig. 21.
5. Mount the new COMM card and mounting plate and at­tach with the 2 screws removed in Step 4. See Fig. 22.
6. Use the shorter ribbon cable to connect the plug on the COMM card to the connector on the mounting plate. See Fig. 21.
7. Install the enclosure. See Fig. 18.
24
0.45-0.67 N-m
(4.0-6.0 lb.-in.)
3 PLACES
MOUNTING PLATE
GATEWAY
RIBBON CABLE
Fig. 21 — COMM Card
A19-1819
MOUNTING PLATE
GATEWAY
Fig. 22 — Mount COMM Card Plate to Drive
A19-1820
T20
2.6 N•m (23 lb•in.)
CHILL PLATE FAN POWER CONNECTION
CHILL PLATE FAN
Fig. 23 — Chill Plate Fan, Frame 6
A19-1839
T20
2.6 N•m
(23 lb•in.)
T20
2.6 N•m
(23 lb•in.)
INTERNAL FAN
Fig. 24 — Internal Fan, Frame 6
A19-1840
CHILL PLATE FAN AND INTERNAL FAN REPLACE­MENT — The following are the steps to replace the chill plate fan and internal fan in Frames 6 and 7.
Frame 6:
1. Disconnect power to the drive. Before removing the en­closure, open the access door on the front of the drive. See Fig. 16.
2. Check to be sure that the voltage between DC+ and DC­and from each DC terminal to the chassis is zero before proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove and replace the chill plate fan. See Fig. 23.
5. Remove and replace the internal fan. See Fig. 24.
6. Install the enclosure. See Fig. 18.
25
711
Frame 7:
Fig. 25 — Chill Plate and Internal Fans, Removal
and Replacement, Frame 7
A19-1841
3P
KTK/FNQ-R
30A
111
222
1 2 3 4 5 6
7 8 9 10 11 12 13
14 15 16 17 18
19 20 21 22 23 24 25
TB4
26 27 28 29 30 31
32 33 34 35 36 37 38 39 40 41 42 43 44
45 46 47 48 49 50 51 52
53 54 55 56 57
58 59 60 61 62 63 64 65 66 67 68 69 70 71
72 73 74 75 76 77 78 79 80
876 5
4 3 21
9
14
12 11 10
13
CR1
876 5
4 3 21
9
14
12 11 10
13
CR2
876 5
4 3 21
9
14
12 11 10
13
CR3
876 5
4 3 21
9
14
12 11 10
13
CR4
876 5
4 3 21
9
14
12 11 10
13
CR5
876 5
4 3 21
9
14
12 11 10
13
CR6
EA1
CB1
CABLE ACCESS CUTOUT
SECONDARY SIDE
PT1
CB
1 2 3 4 5 6 7 8
9 10 11 12
1314 15
16 1718 19 20 21
22 2324 25
TB4
2627 2829 30
31 32 3334 35
36 3738 3940
4142 43 4445 4647 4849 50 51 52 53
54 5556 57 5859 60 61 62 63
64 6566 67 68 69 707172 7374
75 76 7778 79 80
87654
3
21
9
14
1211 10
13
CR1
87654
3
21
9
14
1211 10
13
CR2
876
5
4
3
21
9
14
1211 10
13
CR3
876
5
4
3
21
9
14
1211 10
13
CR4
87654
3
21
9
14
1211 10
13
CR5
876
5
4
3
21
9
14
1211 10
13
CR6
PT1
SECONDARY SIDE
TOWARD DOOR
CB2
FRONT VIEW DOOR REMOVED
LEFT SIDEWALL
VIEW FROM INSIDE
1
80
LINE-
PE
6
5
3
2
4
1
TB1,TB2, FU1-FU3
TB4
CR1
CR6
DIST. SIDE
TB1 TB2
FU2
FU1 FU3
Fig. 26 — Assembly Parts
LEGEND
1—Power Module 2—Input Circuit Breaker 3—15 Amp Control Circuit Breaker 4—Control Transformer 5—Control Fuses 6—Control Relays (CR1 - CR5)
a19-1847
1. Disconnect power to the drive. Before removing the en­closure, open the access door on the front of the drive. See Fig. 16.
2. Check to be sure that the voltage between DC+ and DC­and from each DC terminal to the chassis is zero before proceeding. See Fig. 17.
3. Remove the enclosure. See Fig. 18.
4. Remove and replace the Heat Sink and Internal and fans. See Fig. 25.
Install the enclosure. See Fig. 18.
Part Identification and Location — See Fig. 26-28
for parts descriptions and locations.
INTERNAL FANS
2.6 N•m (23 lb•in.)
X2
5.20 N•m (46 lb•in.)
T15
T15
T20
2.6 N•m (23 lb•in.)
CHILL PLATE FANS
26
LEGEND
1—PF750 Series, Precharge Kit 2—PF750 Series, Gate Interface 3—PF750 Series, Power Interface 4—PowerFlex 750 Series, Flange Gasket 5—PF755 Main Control Board 6—PF750 Series, Backplane Interface 7—PF750 Series, Type 4X/12 Chill Plate
(Heatsink) Fan Kit
8 — Chill Plate Fan
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked “J1 ENABLE” must be removed and the jumper marked “J1 SAFETY” must be left in place.
a19-1848
Fig. 27 — Frame 6 Parts
Fig. 28 — Frame 7 Parts
LEGEND
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked “J1 ENABLE” must be removed and the jumper marked “J1 SAFETY” must be left in place.
1—Slot for Gateway (Gateway Not Shown) 2—PF750 Series, Backplane Interface 3—PF750 Series, Type 4X/12 Heatsink Fan Kit 4—PF750 Series, Power Interface 5—PF750 Series, Bus Cap Assembly 6—PF750 Series, Power Interface Cable 7—PF750 Series, Current Transducer Kit 8 PF750 Series, Precharge Kit 9—Slot for 24V I/O Module (24V I/O Module Not Shown)
10 — PF755 Main Control Board
a19-1849
27
AUTO DEMAND LIMIT
a19-1946
(OPTIONAL)
AUTO CHILLED WATER RESET (OPTIONAL)
EVAP ENT WATER TEMP
EVAP LVG WATER TEMP
COND ENT WATER TEMP
COND LVG WATER TEMP
G.V. POSITION FEEDBACK
EVAP REFRIG
LIQUID TEMP
REMOTE TEMP RESET (OPTIONAL)
COMP'R DISCH TEMP
COMP'R THRUST BRG TEMP
COMP'R OIL SUMP TEMP
COMP'R MOTOR TEMP
NOISE SUPPRESSOR
SPARE TEMP #1 (OPTIONAL)
SPARE TEMP #2 (OPTIONAL)
OIL SUMP PRESS
OIL PUMP DISCH PRESS
LOAD RESISTOR
RELATIVE
HUMIDITY
(WHT)
LOAD RESISTOR
LOAD RESISTOR
JUMPER
LOAD RESISTOR
JUMPER
EVAP PRESS
COND PRESS
APPENDIX A — WIRING SCHEMATICS
CHILLER CONTROL SCHEMATIC
+
+
(SHIELD)
SWITCH POSITION
O
1
32
N
SW "ON" = EXT 4-20mA
SW "OFF" = EXT 1-5Vdc
SW2
1 "OFF"
2 "ON"
3 "ON"
ALL SWITCHES SET TO "OFF" POSITION
6
J6
CCM
(SHIELD)
+-
1J7234
3
SW1
12345678
0
N
2
J1
1
-+-+
1J82
J9J10
3
2
J11
1
6
5
4
J12
3
2
1
(RED)
CB1
(GRY) (GRY)
(GRY)
(CLR)
(BLK)
(SHIELD)
4-20mAkw
OUTPUT
(CLR)
(RED)
(BLK)
(BLK)
(
(BLU)
(BLK)
(WHT)
(ORN)
SERVICE
DIFFUSER ACTUATOR
COMMON
G.V. INCREASE
G.V. DECREASE
GUIDE VANE ACTUATOR
CB2
)NRB
31
C2
(WHT)
(RED)
(GRY)
(BLK)
(CLR)
(RED)
(RED)
(BLK)
(CLR)
(
(BLU)
(ORN)
)KLB
3C
C2 C1
C1
1C
(RED)
6
2C
(RED)
(GRY)
L1
L2
L1
L2
(YEL)
(BLK)
(BRN)
(BRN)
(BRN)
)RLC(
J7
J1
5
4
3
2G
J8
X
3
2
24VAC
+-1
(BLK)
(WHT)
VFD COOLANT SOLENOID
*
)RLC
(
HGBP (OPTIONAL)
(BRN)
COMP'R OIL PUMP
COMP'R OIL HEATER
ALARM
R
STOP
NOTE: GND SHIELDS AT THIS END ONLY
)
DLEIHS()DLEIHS(
(RED)
+
(
G
)KLB
()KLB(
-
SP
1
2
ICVC
(YEL)
(RED)
(BLK)
(CLR)
(BLK)
(BRN)
(WHT)
(RED)
(GRY)
(WHT)
(BLK)
)THW(
NCC)THW
EXT 4-20mA
(1-5vdc)
EXT 4-20mA
(1-5vdc)
+-+-+-
6
5432J51
(RED)
(BLK)
(RED)
(BLK)
(RED)
(BLK)
(RED)
(BLK)
4
(CLR)
78
(BLK)
10K
(SHIELD)
(RED)
(BLK)
(WHT)
(BLK)
(RED)
(BLK)
1
(CLR)
2
(BLK)
3
(SPARE)
(RED)
(BLK)
1
(CLR)
2
(BLK)
3
(SPARE)
(WHT)
(BLK)
(WHT)
(BLK)
-
+
-
+
RMS
-
+
-
+
(BLK)
(CLR)
(RED)
(BLK)
(CLR)
(RED) (BLK)
-
4.3K
S
(RED)
+
10K
4.3K
4.3K
(BLK)
(CLR)
(RED)
(BLK)
(CLR)
(RED)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
J4 (UPPER)
J4 (LOWER)
100»f
100»f
J3 (UPPER)
J3 (LOWER)
J2
28
APPENDIX A — WIRING SCHEMATICS (cont)
(RED)
(BLK)
(BRN) (BRN)
(WHT)
T2
24VAC
(GRN)
(RED)
(RED)
(BLU)
(BLU)
(BLK)
SOLENOID
HGBP
(YEL)
(YEL)
(BLK)
(BLK)
2123
3C
42
(WHT)
(BLK)
3
6
5
4
2
1
HOT GAS BYPASS
(FR #7 & 8 HT EXCH)
115V CONTROL ONLY
(RED)
ACTUATOR
HGBP
COM
OPEN
CLOSE
(GRN)
(BLK)
(BLU)
3C
3C
42
65
(WHT)
230V WIRING MODIFICATION
COMP'R OIL HEATER
(BLK)
(BLK)
(WHT)
(WHT)
(BLK)
13
11
12
1C
1C
1C
(FR #1 - 6 HT EXCH)
HOT GAS BYPASS
(BLU)
(BLK)
(GRN)
(RED)
(RED)
(BLU)
(BLU)
(BLK)
SOLENOID
HGBP
(YEL)
(YEL)
(BLK)
(BLK)
3C
SHOWN WIRED FOR 115V
230V WIRING MODIFICATION
42
(WHT)
(RED)
(BLK)(BLK)
(WHT)
WHT
)THW()TH
W(
COMP'R OIL PUMP MOTOR
WINDING HIGH TEMPERATURE
WHT
(WHT)
(BLK)
(BLK)
COMP'R DISCH
HIGH PRESS
(CLR)
(RED)
(SHIELD)
(BLK)
A
C
17
51
50
43
B
(BRN)
(RED)
(ORN)
(BLK)
COMP'R OIL HEATER
(WHT)
(BLK)
(WHT)
(WHT)
(BLK)
(BLK)
23
21
22
13
11
12
1C
1C
1C
115V
230V
COM
TO TB-G **
(RED)
(YEL)
(BLK)
RED
YEL
BLK
23
21
22
2C
2C
2C
13
11
12
VOLTAGE
PER JOB
REQM'T
M
COMP'R OIL
PUMP MOTOR
(1-1/2 HP)
TO VFD
T1
24VAC
(RED)
(BLK)
(BRN) (BRN)
(WHT)
(RED) (GRY)
(RED)
(GRY)
(WHT)
(WHT)
(BLK)
(BLK)
(BRN)
(YEL)
(RED)
(CLR)
(BLK)
(RED)
(BLK)
(BRN) (BRN)
(WHT)
T3
24VAC
(RED) (GRY)
UPC
1
2
a19-1947
LEGEND
* Standard on LF2 drive; optional on machines equipped with other VFDs.
CB Circuit Breater CCM Chiller Control Module HGBP Hot Gas Bypass ICVC International Chiller Visual Controller RHS Relative Humidity Sensor UPC Universal Protocol Controller VFD Var iabl e Fre quency Drive
Denotes Control Panel Terminal
Denotes Oil Pump Terminal
Denotes Power Panel Terminal
**
Denotes Motor Starter Panel Conn Denotes Component Terminal Wire Splice Denotes Conductor male/Female Connector Option Wiring
CHILLER CONTROL SCHEMATIC (cont)
29
NOTNOT
USEDUSED
a19-1966
APPENDIX A — WIRING SCHEMATICS (cont)
ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical)
CONTINUED ON FAC IN G PAGE
611
30
APPENDIX A — WIRING SCHEMATICS (cont)
3434
3333
TB4
TB4
CARRIER F
ACTORY
WIRING
DETAIL A
SEE
DETAIL
A
3535
3636
TB4
TB4
CARRIER F
ACTORY WIRING
DETAIL B
POWER
PANEL
POWER
PANEL
SEE
DETAIL
B
43
19
a19-1967
LEGEND
CAP Capacitor CB Circuit Breaker COM Common COMM Communication COND Condenser CR Control Relay DPI/SI Internal Communication Protocols Connections EA Electrical Assembly EMI Electro-Magnetic Interference EVAP Evaporator FU Fuse GND Ground JMPR Jumper M—Motor NC Normally Closed NO Normally Open PE Potential Earth (Ground) POD I/O Card Mounting Slot Board REM Remote ROC Relay Output Common SHLD Shield TB Terminal Block
* Located outside of starter; connected by field wiring.
ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont)
31
611
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING
Fig. B — Address Rotary Switches
a48-8578
Fig. A — UPC Open Controller
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
BACNET BAUD RATE DIP SWITCHES
ADDRESS ROTARY SWITCHES
POWER LED
RUN LED
ERROR LED
BACNET CONNECTION (BAS PORT)
BT485 TERMINATOR
Tx2 LED
Rx2 LED
Tx1 LED
Rx1 LED
EIA-485 JUMPERS
* Sponsored by ASHRAE (American Society of Heating, Refrigerat­ing and Air Conditioning Engineers).
a48-8579
Optional BACnet* Communications Wiring —
The following section is used to configure the UPC Open con­troller which is used when the BACnet communications option is selected. The UPC Open controller is mounted in a separate enclosure below the main control box.
TO ADDRESS THE UPC OPEN CONTROLLER — The user must give the UPC Open controller an address that is unique on the BACnet network. Perform the following proce­dure to assign an address:
1. If the UPC Open controller is powered, pull the screw ter­minal connector from the controller's power terminals la­beled Gnd and HOT. The controller reads the address each time power is applied to it.
2. Using the rotary switches (see Fig. A and B), set the con­troller's address. Set the Tens (10's) switch to the tens dig­it of the address, and set the Ones (1's) switch to the ones digit.
As an example in Fig. B, if the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on the Ones (1's) switch to 5.
0
1
9
2
8
3
7
8
7
10's
4
6
5
0
1
9
2
3
1's
4
6
5
BACNET DEVICE INSTANCE ADDRESS — The UPC Open controller also has a BACnet Device Instance address. This Device Instance MUST be unique for the complete BAC­net system in which the UPC Open controller is installed. The Device Instance is auto generated by default and is derived by adding the MAC address to the end of the Network Number. The Network Number of a new UPC Open controller is 16101, but it can be changed using i-Vu
®
Tools or BACView device. By default, a MAC address of 20 will result in a Device In­stance of 16101 + 20 which would be a Device Instance of
1610120.
32
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. C — DIP Switches
a48-
8580
Fig. D — Network Wiring
a48-8581
CONFIGURING THE BAS PORT FOR BACNET MS/ TP — Use the same baud rate and communication settings for all controllers on the network segment. The UPC Open con­troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this protocol's communications.
If the UPC Open controller has been wired for power, pull the screw terminal connector from the controller's power termi­nals labeled Gnd and HOT. The controller reads the DIP Switches and jumpers each time power is applied to it.
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS Port DIP switch DS4 to “EIA-485.” Set the BMS Protocol DIP switches DS8 through DS5 to “MSTP.” See Table A.
Table A — SW3 Protocol Switch Settings
for MS/TP
DS8 DS7 DS6 DS5 DS4 DS3
OffOffOffOffOnOff
Verify that the EIA-485 jumpers below the CCN Port are set to EIA-485 and 2W.
The example in Fig. C shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP.
Set the BAS Port DIP Switches DS2 and DS1 for the appro­priate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. C and Table B.
Table B — Baud Selection Table
BAUD RATE DS2 DS1
9,600 Off Off 19,200 On Off 38,400 Off On 76,800 On On
WIRING THE UPC OPEN CONTROLLER TO THE MS/ TP NETWORK — The UPC Open controller communicates using BACnet on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a dai­sy-chain configuration. Wire specifications for the cable are 22 AWG (American Wire Gage) or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire. The maximum length is 2000 ft.
Install a BT485 terminator on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing. See Fig. B, D, and E.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's BAS Port.
2. Check the communications wiring for shorts and grounds.
3. Connect the communications wiring to the BAS port’s screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network segment.
4. Insert the power screw terminal connector into the UPC Open controller's power terminals if they are not current­ly connected.
5. Verify communication with the network by viewing a module status report. To perform a module status report using the BACview keypad/display unit, press and hold the “FN” key then press the “.” Key.
33
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. E — BT485 Terminator Installation
a48-8582
To install a BT485 terminator, push the BT485 terminator
on to the BT485 connector located near the BACnet connector. NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
i-Vu Open Control System Master Prices. MS/TP WIRING RECOMMENDATIONS — Recommen-
dations are shown in Tables C and D. The wire jacket and UL
Table C — MS/TP Wiring Recommendations
SPECIFICATION RECOMMMENDATION
Cable Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
Conductor 22 or 24 AWG stranded copper (tin plated)
Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Color Code Black/White
Twi st Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal Shielding Aluminum/Mylar shield with 24 AWG TC drain wire
Jacket
DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor
Characteristic Impedance 100 Ohms nominal
Weight 12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Vo lt ag e 300 Vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG American Wire Gage CL2P Class 2 Plenum Cable DC Direct Current FEP Fluorinated Ethylene Polymer NEC National Electrical Code O.D. Outside Diameter TC Tinned Copper UL Underwriters Laboratories
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D. Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
SmokeGard 167°F (75°C) Halar -40 to 302°F (-40 to 150°C)
temperature rating specifications list two acceptable alterna­tives. The Halar specification has a higher temperature rating and a tougher outer jacket than the SmokeGard specification, and it is appropriate for use in applications where the user is concerned about abrasion. The Halar jacket is also less likely to crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum signal integrity.
34
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. F — BACview6 Device Connection
Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS
Wire Type Description
22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for
MS/TP
Network (RS-485)
Rnet 4 conductor, unshielded, CMP, 18 AWG, plenum rated. W184C-2099BLB 6302UE 21450 CLP0442
LEGEND
AWG American Wire Gage CL2P Class 2 Plenum Cable CMP Communications Plenum Rated FEP Fluorinated Ethylene Polymer TC Tinned Copper
specifications. 24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.
Connect Air
International
W221P-22227 25160PV CLP0520LC
W241P-2000F 82841 25120-OR
Belden RMCORP
Contractors
Wire and Cable
LOCAL ACCESS TO THE UPC OPEN CONTROL­LER — The user can use a BACview
6
handheld keypad dis­play unit or the Virtual BACview software as a local user inter­face to an Open controller. These items let the user access the controller network information. These are accessory items and do not come with the UPC Open controller.
The BACview
6
unit connects to the local access port on the UPC Open controller. See Fig. F. The BACview software must be running on a laptop computer that is connected to the local access port on the UPC Open controller. The laptop will re­quire an additional USB link cable for connection.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview
To order a BACview
6
Handheld (BV6H), consult Commer-
6
device.
cial Products i-Vu® Open Control System Master Prices. CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and ComfortLink™ controls must be set to the same CCN Address (Element) num­ber and CCN Bus number. The factory default settings for CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are required, both the ComfortLink and UPC Open configurations must be changed.
The following configurations are used to set the CCN Ad­dress and Bus number in the ComfortLink control. These con­figurations can be changed using the scrolling marquee display or accessory Navigator handheld device.
ConfigurationCCNCCN.A (CCN Address)
ConfigurationCCNCCN.B (CCN Bus Number)
The following configurations are used to set the CCN Ad­dress and Bus Number in the UPC Open controller. These con­figurations can be changed using the accessory BACview
6
dis-
play.
Navigation: BACview→CCN Home: Element Comm Stat Element: 1 Bus: 0
TROUBLESHOOTING — If there are problems wiring or addressing the UPC Open controller, contact Carrier Technical Support.
35
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
COMMUNICATION LEDS
— The LEDs indicate if the
controller is communicating with the devices on the network. See Tables E and F. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become. See Fig. B for location of LEDs on UPC Open module.
REPLACING THE UPC OPEN BATTERY — The UPC Open controller's 10-year lithium CR2032 battery provides a minimum of 10,000 hours of data retention during power outages.
Table E — LED Status Indicators
LED STATUS
Power
Rx Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Tx Lights when the controller transmits data to the network segment; there is a Tx LED for Ports 1 and 2.
Run Lights based on controller status. See Table F.
Error Lights based on controller status. See Table F.
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.
Table F — Run and Error LEDs Controller and Network Status Indication
RUN LED ERROR LED STATUS
2 flashes per second Off Normal 2 flashes per second 2 flashes, alternating with Run LED Five minute auto-restart delay after system error 2 flashes per second 3 flashes, then off Controller has just been formatted 2 flashes per second 1 flash per second Controller is alone on the network 2 flashes per second On Exec halted after frequent system errors or control programs halted 5 flashes per second On Exec start-up aborted, Boot is running 5 flashes per second Off Firmware transfer in progress, Boot is running 7 flashes per second 7 flashes per second, alternating with Run LED Ten second recovery period after brownout 14 flashes per second 14 flashes per second, alternating with Run LED Brownout
IMPORTANT: Power must be ON to the UPC Open when replacing the battery, or the date, time, and trend data will be lost.
Remove the battery from the controller, making note of the battery's polarity. Insert the new battery, matching the battery's polarity with the polarity indicated on the UPC Open controller.
NETWORK POINTS LIST — The points list for the control­ler is shown in Table G.
36
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List
POINT DESCRIPTION
1st Current Alarm State ALARM_01 R N/A 0-270 AV:4 alarm_01_1 Active Demand Limit DEM_LIM R/W % N/A 40 to 100 AV:6 dem_lim_1 Actual Guide Vane Position GV_POS R % N/A 0 to 100 AV:7 gv_pos_1 Actual VFD Speed VFD_ACT R % N/A 0 to 110 AV:11 vfd_act_1 Calc Evap Sat Temp EAT R °F N/A -40 to 245 AV:13 ert_1 Chilled Water Deadband CWDB R ^F 1.0 0.5 to 2.0 AV:14 cwdb_1 Chilled Water Delta P CHWPD R ^F N/A -6.7 to 420 AV:15 chwpd_1 Chilled Water Delta T CHW_DT R ^F N/A -40 to 245 AV:16 chw_dt_1 Chilled Water Pump CHLP R N/A OFF OFF/ON BV:4 chlp_1 Chilled Water Temp CHW_TMP R °F N/A -40 to 245 AV:17 chw_tmp_1 Chiller Start/Stop CHIL_S_S R/W N/A STOP STOP/START BV:5 chil_s_s_1 Comp Discharge Temp CMPD R °F N/A -40 to 245 AV:18 cmpd_1 Comp Motor Winding Temp MTRW R °F N/A -40 to 245 AV:19 mtrw_1 Comp Thrust Brg Temp MTRB R °F N/A -40 to 245 AV:20 mtrb_1 Cond Water Flow CDW_FLOW R N/A NO NO/YES BV:6 cdw_flow_1 Cond Water Pump CDP R N/A OFF OFF/ON BV:7 cdp_1 Condenser Pressure CRP R PSI N/A -6.7 to 420 AV:21 crp_1 Condenser Refrig Temp CRT R °F N/A -40 to 245 AV:22 crt_1 Condenser Water Delta P CDWPD R PSI N/A -6.7 to 420 AV:23 cdwpd_1 Control Point LCW_STPT R/W °F N/A 10 to 120 AV:24 lcw_stpt_1 Current CHW Setpoint CHWSTPT R °F N/A 0.00 to 99.9 AV:25 chwstpt_1 Demand Level 1 N/A R % N/A 0 to 100 AV:1 dmv_lvl_1_perct_1 Demand Level 2 N/A R % N/A 0 to 100 AV:2 dmv_lvl_2_perct_1 Demand Level 3 N/A R % N/A 0 to 100 AV:3 dmv_lvl_3_perct_1 Element Comm Status N/A R N/A N/A No Comm/Normal BV:2999 element_stat_1 Element Communications
Alarm
Emergency Stop EMSTOP R N/A ENABLE
Entering Chilled Water ECW R °F N/A -40 to 245 AV:26 ecw_1 Entering Condenser Water ECDW R °F N/A -40 to 245 AV:27 ecdw_1
Equipment Alarm N/A R N/A N/A
Evaporator Pressure ERP R PSI N/A -6.7 to 420 AV:28 erp_1 Evaporator Refrigerant Temp Leaving Chilled Water -
Prime Variable Leaving Condenser Water LCDW R °F N/A -40 to 245 AV:32 lcdw_1 Line Active Current AMPS_ACT R A N/A 0.0 to 99999.0 AV:8 amps_act_1 Line Active Voltage VOLT_ACT R V N/A 0.0 to 99999.0 AV:9 volt_act_1 Line Frequency LINEFREQ R Hz N/A 0 to 99 AV:30 linefreq_1 Line Power Factor LINE_PF R N/A 0.00 to 2.00 AV:34 line_pf_1 Local Schedule N/A R N/A N/A No Comm/Normal BV:2 schedule_1 Occupied? OCC R N/A NO NO/YES BV:10 occ_1 Oil Sump Temperature OILT R °F N/A -40 to 245 AV:33 oilt_1 Remote Start Contact REM_CON R/W N/A OPEN OPEN/CLOSE BV:11 rem_con_1
Run Status STATUS R N/A N/A
Service Ontime S_HRS R/W hr N/A 0 to 32767 AV:36 s_hrs_1 Surge Line Delta T DELTA_TX R °F N/A 0 to 200 AV:38 delta_tx_1
System Alert/Alarm SYS_ALM R N/A N/A
CCN
POINT NAME
N/A R N/A N/A Inactive/Active BV:20 comm_lost_alm_1
ERT R °F N/A -40 to 245 AV:13 ert_1
LCW R °F N/A -40 to 245 AV:31 lcw_1
READ/ WRITE
UNITS
DEFAULT
VAL UE
RANGE
ENABLE/ EMSTOP
Comm Normal
Comm Lost
0=Timeout,
1=Ready, 2=Recyle, 3=Startup,
4=Running, 5=Demand,
6=Ramping,
7=Autorest, 8=Override,
9=Tripout,
10=Control Test,
11=Lockout,
12=Pumpdown,
13=Prestart
1=Normal,
2=Alert, 3=Alarm
BACNET
OBJECT ID
BV:8 emstop_1
BV:1 element_alarm_1
AV:35 status_1
AV:40 sys_alm_1
BACNET
OBJECT NAME
37
611
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
POINT DESCRIPTION
System Cooling Demand Level
System Demand Limiting N/A R N/A N/A OFF/ON BV:3 dem_lmt_act_1 Target Guide Vane Position GV_TRG R % N/A 0 to 100 AV:41 gv_trg_1 Target VFD Speed VFD_OUT R % N/A 0 to 100 AV:42 vfd_out_1 Tower Fan Relay High TFR_HIGH R N/A OFF OFF/ON BV:13 tfr_high_1 Tow er F an R el ay L ow TFR_LOW R N/A OFF OFF/ON BV:14 tfr_low_1 User Defined Analog 1 N/A R N/A N/A N/A AV:2901 user_analog_1_1 User Defined Analog 2 N/A R N/A N/A N/A AV:2902 user_analog_2_1 User Defined Analog 3 N/A R N/A N/A N/A AV:2903 user_analog_3_1 User Defined Analog 4 N/A R N/A N/A N/A AV:2904 user_analog_4_1 User Defined Analog 5 N/A R N/A N/A N/A AV:2905 user_analog_5_1 User Defined Binary 1 N/A R N/A N/A N/A BV:2911 user_binary_1_1 User Defined Binary 2 N/A R N/A N/A N/A BV:2912 user_binary_2_1 User Defined Binary 3 N/A R N/A N/A N/A BV:2913 user_binary_3_1 User Defined Binary 4 N/A R N/A N/A N/A BV:2914 user_binary_4_1 User Defined Binary 5 N/A R N/A N/A N/A BV:2915 user_binary_5_1
LEGEND
CHW Chilled Water R—Read VFD Va riable Fr equency Drive W—Write
CCN
POINT NAME
N/A R N/A N/A N/A AV:9006 cool_demand_level_1
READ/ WRITE
UNITS
DEFAULT
VAL UE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
38
Copyright 2011 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190012-01 Printed in U.S.A. Form 19XRV-3SS Pg 40 711 3-11 Replaces: New
Loading...