Centrifugal liquid chillers are designed to provide safe and
reliable service when operated within design specifications. When operating this equipment, use good judgment
and safety precautions to avoid damage to equipment and
property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions as
well as those listed in this guide.
ONLY QUALIFIED Electrical Personnel familiar with the construction
and operation of this equipment and the hazards involved should install,
adjust, operate, or service this equipment.
READ AND UNDERSTAND this manual and other applicable manuals in
their entirety before proceeding. Failure to observe this precaution could
result in severe bodily injury or loss of life.
DO NOT install modification kits with power applied to the drive. Disconnect and lock out incoming power before attempting such installation or
removal. Failure to observe this precaution could result in severe bodily
injury or loss of life
UNUSED WIRES in conduit must be grounded at both ends to avoid a
possible shock hazard caused by induced voltages. Also, if a drive sharing
a conduit is being serviced or installed; all drives using this conduit should
be disabled to eliminate the possible shock hazard from cross-coupled
motor leads. Failure to observe these precautions could result in bodily
injury.
DO NOT VENT refrigerant relief valves within a building. Outlet from
rupture disc or relief valve must be vented outdoors in accordance with the
latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigerating, and Air Conditioning
Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and
reduces the amount of oxygen available for breathing. Product causes eye
and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any
purpose. Oxygen gas reacts violently with oil, grease, and other common
substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test
pressure by checking the instruction literature and the design pressures on
the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any chiller.
THERE IS A RISK OF INJURY OR DEATH by electrocution. High voltage may be present on the motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or
terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all
refrigerant (liquid and vapor) has been removed from chiller. Traces of
vapor should be displaced with dry air or nitrogen and the work area
should be well ventilated. Refrigerant in contact with an open flame pro-duces toxic gases.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including control panels,
switches, VFD, or oil heater until you are sure ALL POWER IS OFF and
no residual voltage can leak from capacitors or solid-state components.
19XRV
with PIC III Controls
Rockwell PowerFlex 755 VFD Option
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS
INTERRUPTED, confirm that all circuits are deenergized before resuming
work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.
USE SAFETY GOGGLES. Wash any spills from the skin with soap and
water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES
with water and consult a physician.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is
under pressure or while chiller is running. Be sure pressure is at 0 psig (0
kPa) before breaking any refrigerant connection.
TO AVOID an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus
voltage at the Power Terminal Block by measuring between the +DC and DC terminals, between the +DC terminal and the chassis, and between the
-DC terminal and the chassis. The voltage must be zero for all three measurements.
THE USER is responsible to conform with all applicable local, national,
and international codes. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
THIS DRIVE contains ESD (Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if
ESD control procedures are not followed. For static control procedures,
reference Rockwell publication Guarding Against Electrostatic Damage, or
any other applicable ESD protection handbook.
DO NOT alter the setting of any jumper. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.
USE OF power correction capacitors on the output of the drive can result
in erratic operation of the motor, nuisance tripping, and/or permanent damage to the drive. Remove power correction capacitors before proceeding.
Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
MOST CODES require that upstream branch circuit protection be provided to protect input power wiring. If fuses are chosen as the protection
method, refer to the PowerFlex 750 user manual. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
DO NOT route signal and control wiring with power wiring in the same
conduit. This can cause interference with drive operation. Failure to
observe this precaution could result in damage to, or destruction of, the
equipment.
DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rating of the drive. Failure to observe this precaution could result in damage
to, or destruction of, the equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow
safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move
inspection covers or other heavy components. Even if components are
light, use mechanical equipment when there is a risk of slipping or losing
your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE
THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the
VFD, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements of
the original equipment.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion,
rust, leaks, or damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190012-01Printed in U.S.A.Form 19XRV-3SSPg 1711 3-11Replaces: New
Start-Up and Service Manual must be used with the following
manuals:
• The latest version of the PowerFlex 750-Series AC
Drives manuals
• The latest revision of the Start-Up, Operation, and Maintenance Instructions for the 19XRV with PIC III Controls
Getting Assistance from Rockwell Automation — Contact the local Rockwell Automation sales office
with any questions or problems relating to the products described in this manual. For technical support on drives between
the hours of 7:00 am and 6:00 pm CST, M-F, call 1-262-512-
8176. For information about after-hours phone support and on-
site support call 1-800-800-0522.
Before calling, have the following information available
from the Allen-Bradley data nameplate located inside the enclosure on the right wall. See Fig. 1.
• Allen-Bradley ID or CAT. NO.
• Carrier VFD Code
• Allen-Bradley serial number
INTRODUCTION
The Carrier VFD option Start-Up and Service Manual is intended for trained and qualified service personnel, and is to be
used during start up, operation, and maintenance of Rockwell/
Allen-Bradley PF755L drive.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCM— Chiller Control Module
DC— Direct Current
DPI— Drive Peripheral Interface
ENET— Ethernet
ICVC— International Chiller Visual Controller
IGBT— Insulated Gate Bipolar Transistor
I/O— Inputs/Outputs
IP— Internet Protocol
IPWM— Inverter Pulse Width Modulation
MCB— Main Control Board
MOV— Metal Oxide Varistor
PE— Protective Earthing Conductor
SIO— Sensor Input/Output
STS— Status
IDENTIFYING DRIVE COMPONENTS
A chiller control schematic and a VFD schematic are in-
cluded in Appendix A.
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input
power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter rated
for the DC bus voltage to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could result in severe bodily
injury or loss of life.
An isolated multimeter will be needed to measure DC bus
voltage and to make resistance checks. The drive’s DC bus
capacitors retain hazardous voltages after input power has
been disconnected.
711
2
Opening the VFD Access Door
Fig. 2 — Opening Access Door
A19-1831
Fig. 3 — Check DC Bus Terminals
A19-1814
21P 1 0248 3 - 3 -0-0 C-
21P PF755 VFD
Voltage Rating
1
2
3
Customer
C –Carrier
Meter Package
0 – No Meter Package
1 –Analog Meter Package
– 460 to 480 v, 60 Hz
– 380 to 415 v, 50 Hz
– 380 to 400 v, 60 Hz
Input Reactor
0 – No Input Reactor
1 – 3% Input Line Reactor
– 401 to 439 v, 60 Hz
0477–477
3–65 KAIC Capacity Breaker
4 – 100 KAIC Capacity Breaker
Drive Assembly
3 – Unit Mount NEMA 1 Liquid Cooled
Fig. 4 — Drive Assembly Catalog Number Nomenclature
A19-1842
* For Carrier applications, maximum continuous amp
ratings are 230, 335, and 445.
WARNING
Before removing the drive enclosure, open access door and
verify that the DC bus voltage has dropped to zero by
checking the terminals behind the access door. Failure to
observe this precaution could result in severe bodily injury
or loss of life.
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat
or T20 star, open access door. See Fig. 2.
2. Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before
proceeding. See Fig. 3.
Drive Assembly Catalog Number — See Fig. 4 for
an example Catalog Number.
Components and Physical Data — The Allen-
Bradley PF755 Frame 6 drive is used for the 230-amp rated application (carrier Part No. 19XRV0230...). See Fig. 5.
The Allen-Bradley PF755 Frame 7 drive is used for the
335-amp and 445-amp rated application (Carrier Part No.
19XVR0335... and 19XVR0445... respectively). See Fig. 6.
PE Grounding StudsTerminating point to chassis ground
for incoming motor shield
3
DC Bus and Brake
Te r mi n a ls
+DC, -DC, BR1, BR2
4PE-A and PE-BMOV and CMC Jumper Wires
5DC+ and DC-Bus Voltage Test Points
A19-1833
4
Fig. 7 — Enclosure Dimensions - Frames 6 and 7
A19-1834
CAUTION
If other than refrigerant cooling is used, before connecting
the drive to the incoming power, make sure that the coolant
is circulating and has no leaks.
CAUTION
When working with the Drive Explorer, never use the
Rotate function as the motor will immediately start and
severe compressor damage could result.
START-UP
DANGER
Internal components and circuit boards of the drive are live
when the drive is connected to incoming power. Coming
into contact with this voltage is extremely dangerous and
will result in severe personal injury or death.
The motor terminals U, V, W and the DC-link/brake resistor terminals B+/R+, R- are live when the drive is connected to incoming power, even if the motor is not running.
Do not make any connections when the drive is connected
to the incoming power.
After having disconnected the drive, wait until the indicators on the keypad go out (if no keypad is attached see the
indicator through the keypad base). Wait 5 more minutes
before doing any work on drive connections. Do not even
open the cover before this time has expired..
Before connecting the drive to the incoming power, make
sure that the switchgear enclosure door is closed.
WARNING
The control I/O-terminals are isolated from the mains
potential. However, the relay outputs and other I/O terminals may have a dangerous control voltage present even
when the drive is disconnected from incoming power.
Coming into contact with this voltage could result in severe
personal injury.
Alternate Wire Lugs —
In the case where the incoming
power wire size does not fit the standard lug, alternate lugs may
be used. See Table 1. Note that lugs rated for a higher current
than the circuit breaker may be used.
Table 1 — Wire Lugs
CIRCUIT
BREAKER
65 KAIC
(Standard)
100 KAIC
(Optional)
STANDARD
ABB LUG
K6TJ
STANDARD
LUG CABLE
RANGE
(3) 2/0 - 400
MCM
ALTERNATE
ABB LUG
K6TH
ALTERNATE
LUG CABLE
RANGE
(2) 250 - 500
MCM
Verify Installation — Record the following job
information:
1. Job Name
2. Job Number
3. City
4. State
5. Zip Code
Record the following nameplate information:
1. From the Allen-Bradley nameplate (Fig. 1) located inside
the VFD enclosure:
a. Allen-Bradley ID or CAT NO.
b. Allen-Bradley Serial Number
c. Carrier Part Number
2. From the machine nameplete (Fig. 8) located inside the
VFD enclosure:
a. Chiller Serial Number
b. Chiller Model
c. Motor rated load amps
d. Motor nameplate rpm
e. Motor nameplate kW
f. Motor nameplate voltage
g. IPWM (pulse width modulation) frequency
h. Voltage
3. From the drive module label (Fig. 9) located on the drive
module:
a. Model or Cat. Number
b. Serial Number
4. From the ICVC control panel screen:
a. Carrier Part Number and Revision
b. ICVC Software Number
Rockwell PowerFlex 750 drive start-up must be registered
on the Rockwell website. Rockwell Registration site URL:
http://www.automation.rockwell.com/warp/default.asp
5
MODEL NUMBER
SERIAL NUMBER
VOLTS/PHASE/HERTZ
LOCKED ROTOR AMPS
OVERLOAD TRIP AMPS
MAX FUSE/CIRCUIT BREAKER SIZE
MIN SUPPLY CIRCUIT AMPACITY
MOTOR NAMEPLATE VOLTAGE
COMPRESSOR 100% SPEED
RATED LINE VOLTAGE
RATED LINE AMPS
RATED LINE KILOWATTS
MOTOR RATED LOAD KW
MOTOR RATED LOAD AMPS
MOTOR NAMEPLATE AMPS
MOTOR NAMEPLATE RPM
MOTOR NAMEPLATE KW
INTERTER PWM FREQUENCY
MACHINE NAMEPLATE SUPPLY DATA
MACHINE ELECTRICAL DATA
SAFETY CODE CERTIFICATION
THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE
IN ACCORDANCE WITH CARRIER SPECIFICATION Z-420.
19XV05008701 REV. 3
A United Technologies Company
Fig. 8 — Machine Nameplate
a19-
1846
Fig. 9 — Drive Module Label
a191924
Configure the VFD — All configurations required by
the VFD are supplied by the ICVC through the VFD Gateway.
Any configuration changes necessary and possible are made on
the ICVC screens. A complete set of configurations is transmitted to the VFD each time the controls are powered up.
The following is from the 19XRV PIC III ICVC screen. Parameters in italics are to be entered or confirmed at start-up. Parameters in bold are to be changed only after consulting with
Carrier service engineering. See Table 2.
Table 2
PARAMETERDEFAULT VALUE
Motor Nameplate Voltage460
Compressor 100% Speed
Line Freq=60 Hz? (No=50) Yes
Rated Line Voltage*460
Rated Line Amps* 200
Rated Line Kilowatts *100
Motor Rated Load kW* 100
Motor Rated Load Amps* 200
Motor Nameplate Amps100
Motor Nameplate RPM 3456
Motor Nameplate KW 100
Inverter PWM Frequency (0 = 4 kHz, 1 =
2kHz)
Skip Frequency 1 (Hz)102.0
Skip Frequency 2 (Hz)102.0
Skip Frequency 3 (Hz)102.0
Skip Frequency Band Line (Hz) 0.0
Voltage % Imbalance10
Line Volt Imbalance Time (sec)10
Line Current % Imbalance 40
Line Current Imbal Time (sec)10
Motor Current % Imbalance 40
Motor Current Imbal Time 10
Increase Ramp Time (sec)30
Decrease Ramp Time (sec)30
Single Cycle Dropout (DSABLE/ENABLE)DSABLE
* Parameters marked with an * are not downloadable to the VFD but are used
in other calculations and algorithms in the ICVC.
NOTES:
1. Parameters in italics are to be entered or confirmed at start-up.
2. Parameters in bold are to be changed only after consultation with service engineering.
— VFD Configurations
1
Commissioning the Unit — The commission proce-
dure is as follows:
1. If the chiller has been stored outdoors, allow at least 24
hours room temperature stabilization prior to commissioning. Ensure any condensation that occurs as a result
of the ambient temperature is allowed to evaporate.
2. Enter parameters in the VFD_CONF screen.
3. Install surge suppression devices if required.
4. Review the power wiring and grounding to ensure that it
has been properly connected.
5. Visually examine the inside of the drive enclosure to:
a. Look for signs of corrosion or moisture residue.
b. Remove any dirt or debris.
c. Make sure all vents are clear.
6. Apply power to the drive and take thermal measurements
of the capacitor bank and power connections. Do this
again before start-up.
7. Measure and record the incoming line voltage. Line-toline voltages should be balanced within 3% as calculated
by Rockwell’s procedure below:
Measure voltages phase-to-phase and phase-to-ground.
6
Vmax = Maximum measured phase-to-phase voltage
LEGEND
NO.NAMEDESCRIPTION
1HIM ConnectorDPI Port 1 (HIM Cradle) connection.
2
Fan ConnectorPower supply for internal cooling fan
(Frames 2 & 3).
3
Battery
Receptacle
User installed CR1220 lithium coin cell
battery provides power to the Real Time
Clock (Optional, not supplied).
4
DPI Port 2Cable connection for handheld and
remote HIM options.
5
Embedded EtherNet/
IP Address Selectors
Rotary switches for setting lowest octet
of EtherNet address (forces address to
192.168.1.xxx).
6
Embedded EtherNet/
IP Connector
Network cable connection.
7
Jumper J2 SAFETY Safety enable jumper. Removed when
safety option is installed.
8
Jumper J1 ENABLE Hardware enable jumper. Removed
when a hardware enable configuration is
utilized.
9TB1I/O terminal block.
Fig. 10 — PF755 Main Control Board
TB1 I/O Terminal Designations
FIXED I/OTERMINALNAMEDESCRIPTION
Di 0ac
Digital Input 120V ACConnections for AC power supply.
Di C
Digital Input CommonDigital input common
Di 0dc
Digital Input 24V DCConnections for DC power supply.
+24V
+24 Volt PowerConnections for drive supplied 24V power.
24VC
24 Volt Common
IMPORTANT: Wiring to pluggable terminal block connectors
should be supported by wire ties or other means to help prevent unintentional disconnection
Di 0ac
Di C
Di 0dc
+24V
24VC
a19-1921
(A to B, B to C, C to A)
Vmin = Minimum measured phase-to-phase voltage
Imbalance Calculation Formula
Va v g=
Imbalance %=
(VAB + VBC + VCA)
3
(Vmax – Vmin) x 100
Va v g
8. Take a final thermal measurement of the capacitor bank
and power after finalizing the installation to ensure all
connections are good.
9. If a ground fault occurs, then do the following:
a. Check for a ground in the motor or motor wiring.
b. Check for damage to wiring insulation and that
wiring is dry.
c. Verify the motor wiring is separated from ground
and there is no connection between phases.
d. Check for failed IGBTs.
10. If an Overcurrent fault occurs, then do the following:
a. Check for excessive load and verify load limit set-
tings on the ICVC.
b. Check motor and wiring insulation.
c. Check parameter settings on VFD_CONF screen
in the ICVC.
Check Internal Jumpers — On the Main VFD Con-
trol board there are two jumpers labeled J1 HARDWARE ENABLE and J2 SAFETY ENABLE. J1 should be removed and
J2 should be in place. See Fig. 10.
There are two jumper wires that connect a particular terminal to chassis ground. The MOV and AC EMI jumper should
be connected to the PE-A terminal. The COMMON MODE
CAPACITORS to GROUND jumper should be connected to a
standoff rather than the PE-B terminal.
Use the recommended tools as follows when connecting
jumper wires in Frame 6 and in Frame 7:
• Recommended torque (screws and nuts) = 1.36 N·m
(120.0 lb·in)
• Recommended hex socket = 7 mm
• Recommended screwdriver = T20 star type
See Fig. 11A and Fig. 11B for the correct positions of the
jumpers.
7
Troubleshooting the Drive —
Fig. 11A — Jumper Wire Locations — Frame 6
A19-1835
Fig. 11B — Jumper Wire Locations — Frame 7
A19-1836
2
8
5
79
13
46
Allen-Bradley
Fig. 12 — Drive Status Indicator
A1
91815
The drive can display
two kinds of error codes on the ICVC called the Alert and
Alarm codes. These codes signal a problem detected during
self tuning or drive operation. Alert and Alarm codes are located in the 19XRV Start-Up, Operation and Maintenance Instructions. Note the following differences between Carrier and
Allen-Bradley terminology:
• A warning message on the ICVC is an ALERT.
• The same warning viewed with Rockwell Drive Explorer
is a VFD ALARM.
• A failure resulting in a shutdown is seen as an ALARM
on the ICVC and as a VFD FAULT when viewed with
Drive Explorer.
CONDITION CODES
ICVC ALERT =VFD ALARM
ICVC ALARM =VFD FAULT
See Tables 3-6 and Fig. 12.
ICVC ALERT CODES — An alert condition is indicated by
a message at the top of the ICVC default screen. In addition, an
exclamation point (!) will appear next to any affected point on
an ICVC display screen. The drive will continue to operate
during the alert condition. Investigate the cause of the alert to
ensure it does not lead to a fault condition. The alert code will
automatically be cleared from the ICVC when the condition
causing the alert no longer exists. See Table 4.
ICVC ALARM CODES — An alarm condition is also indicated by a message at the top of the ICVC default screen. If an
alarm occurs, the drive coasts to stop. The STS (status) light on
the drive will turn from Green to Red or Yellow (see Table 3).
The detected fault message is maintained on the display until it
is cleared by pressing the RESET softkey. See Table 5.
TEST EQUIPMENT NEEDED TO TROUBLESHOOT —
An isolated multimeter adequately rated for the DC bus voltage will be needed to measure DC bus voltage and to make
resistance checks. Note that dedicated troubleshooting test
points are not provided.
SERVICE
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input
power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter to
ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
8
Table 3
SWING UP KEY PAD
MOUNT TO ACCESS
CONTROL BOARDS
Fig. 13 — Drive Module with Cover Removed
a19-1843
NAMECOLORSTATEDESCRIPTION
GreenFlashingDrive ready but not running, and no faults are present.
SteadyDrive running, no faults are present.
YellowFlashingDrive is not running. A type 2 (non-configurable) alarm condition exists and the
SteadyDrive is not running, a type 1 alarm condition exists. The drive can be started.
STS (Status)
ENET
LINK
NOTES:
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms
are user configurable.
RedFlashingA major fault has occurred. Drive cannot be started until fault condition is
SteadyA non-resettable fault has occurred.
Red/YellowFlashing AlternatelyA minor fault has occurred. When running, the drive continues to run. System is
Green/RedFlashing AlternatelyDrive is flash updating.
None (Unlit)OffAdapter and/or network is not powered, adapter is not properly connected to
RedFlashingAn EtherNet/IP connection has timed out.
SteadyAdapter failed the duplicate IP address detection test.
Red/GreenFlashing AlternatelyAdapter is performing a self-test.
GreenFlashingAdapter is properly connected but is not communicating with any devices on
SteadyAdapter is properly connected and communicating on the network.
None (Unlit)OffAdapter is not powered or is not transmitting on the network.
GreenFlashingAdapter is properly connected and transmitting data packets on the network.
SteadyAdapter is properly connected but is not transmitting on the network.
— Drive Status Indicator Descriptions
drive cannot be started.
cleared.
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major
fault.
the network, or adapter needs an IP address.
the network.
2. A Type 2 alarm indicates that a configuration error exists and
the drive cannot be started. Type 2 alarms are not configurable.
VERIFYING THAT DC BUS CAPACITORS ARE DISCHARGED — The drive’s DC bus capacitors retain hazardous voltages after input power has been disconnected. Perform
the following steps before touching any internal components:
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power
terminals.
3. Measure the DC bus potential with a voltmeter while
standing on a non-conductive surface and wearing insulated gloves (1000 V). Measure the DC bus potential. See
Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and
477-amp drives. The voltage between DC+ and DC-, and
from each DC terminal to the chassis must be zero before
proceeding.
4. Once the drive has been serviced, reapply input power.
HIGH TEMPERATURE ALARMS — Coolant flow
through the cold plate is controlled by an orifice in the refrigerant line leaving the cold plate. The orifice looks like one of the
O-ring face seal connectors and in fact is used as one of the
connections on the coolant tubing. The difference is that the
passage through the fitting is 0.375 in. (9.5 mm). If the orifice
is present and condenser liquid flow is present, the liquid will
flash to cooler temperature at the orifice. This temperature difference is great enough to be easily felt.
MAIN CONTROL BOARD (MCB) COMPONENTS —
Figure 13 shows the drive module with the cover removed. To
access the control boards, loosen the screw on the face of the
keypad mount and swing the keypad mount upward.
The components on the main control board (MCB) are
shown in Fig. 14. Note the location of the terminals labeled
MCB I/O. The high pressure switch is wired to these terminals
as shown in Fig. 15. In the event of a high condenser pressure
alarm, the connections at these terminals should be checked
and tightened if necessary.
A typical wiring schematic is shown in Appendix A.
*Located outside of starter; connected by field wiring.
Fig. 15 — High Pressure Switch Wiring
a19-1925
10
Table 4 — ICVC Alert Codes
PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
ICVC FAULT
STATE
100PRESTART
101PRESTART
102PRESTART
103PRESTART
104PRESTART
105PRESTART
106PRESTART
107PRESTART
108PRESTART
109PRESTART
110PRESTART
111PRESTART
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
ALERT
SECONDARY
MESSAGE
STARTS LIMIT
EXCEEDED
HIGH BEARING
TEMPERATURE
HIGH MOTOR
TEMPERATURE
HIGH
DISCHARGE
TEMP
LOW
REFRIGERANT
TEMP
LOW OIL
TEMPERATURE
HIGH
CONDENSER
PRESSURE
LOW LINE
VOLTAGE
HIGH LINE
VOLTAGE
GUIDE VANE
CALIBRATION
HIGH
RECTIFIER
TEMP
HIGH
INVERTER
TEMP
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
100Excessive compressor starts
(8 in 12 hours).
101Comp Thrust Brg Temp [VALUE]
exceeded limit of [LIMIT]*.
102Comp Motor Winding Temp
[VALUE] exceeded limit of [LIMIT]*.
103Comp Discharge Temp [VALUE]
exceeded limit of [LIMIT]*.
104Evaporator Refrig Temp [VALUE]
exceeded limit of [LIMIT]*.
105Oil Sump Temp [VALUE]
exceeded limit of [LIMIT]*.
106Condenser Pressure [VALUE]
exceeded limit of [LIMIT]*.
107Percent Line Voltage [VALUE]
exceeded limit of [LIMIT]*.
108Percent Line Voltage [VALUE]
exceeded limit of [LIMIT]*.
109Actual Guide Vane Pos
Calibration Required Before Startup.
110Rectifier Temperature [VALUE]
exceeded limit of [LIMIT]*.
111Inverter Temperature [VALUE]
exceeded limit of [LIMIT]*.
Depress the RESET softkey if additional start
is required. Reassess start-up requirements.
Check oil heater for proper operation.
Check for low oil level, partially closed oil supply valves, clogged oil filters.
Check the sensor wiring and accuracy.
Check Comp Thrust Brg Alert setting in
SETUP1 screen.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation,
or restrictions.
Check for excessive starts within a short time
span.
Check Comp Motor Temperature Override
setting in SETUP1 screen.
Allow discharge sensor to cool.
Check sensor wiring and accuracy.
Check for excessive starts.
Check Comp Discharge Alert setting in
SETUP1 screen.
Check transducer wiring and accuracy.
Check for low chilled fluid supply
temperatures.
Check refrigerant charge.
Check Refrig Override Delta T in SETUP1
screen.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
Check transducer wiring and accuracy.
Check for high condenser water
temperatures.
Check high condenser pressure switch wiring.
Check voltage supply.
Check voltage transformers and switch gear.
Consult power utility if voltage is low.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
Press STOP button on ICVC and perform
Guide Vane Calibration in Controls Test
screen.
Check guide vane actuator feedback
potentiometer.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
11
NORMAL RUN WITH OVERRIDES
Table 4 — ICVC Alert Codes (cont)
ICVC FAULT
STATE
120RUN CAPACITY
121RUN CAPACITY
122RUN CAPACITY
123RUN CAPACITY
124RUN CAPACITY
125RUN CAPACITY
126RUN CAPACITY
127RUN CAPACITY
128RUN CAPACITY
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
PRIMARY
MESSAGE
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
LIMITED
SECONDARY
MESSAGE
HIGH CONDENSER
PRESSURE
HIGH MOTOR
TEMPERATURE
LOW EVAP REFRIG
TEMP
HIGH COMPRESSOR
LIFT
MANUAL GUIDE VANE
TA R GE T
LOW DISCHARGE
SUPERHEAT
HIGH RECTIFIER TEMP 126Rectifier Temperature
MANUAL SPEED
CONTROL
HIGH INVERTER TEMP 128Inverter Temperature
PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
120Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
121Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.
122Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
123Surge Prevention
Override: Lift Too High For
Compressor
No Alert message.Check for oil loss or excess refrigerant charge.
[VALUE] exceeded limit of
[LIMIT]*.
No Alert message.Chiller is not in automatic temperature control.
[VALUE] exceeded limit of
[LIMIT]*.
Check condenser water pump operation.
Check for high condenser water temperatures or
low flow rate. Verify that isolation valves are
open.
Check Cond Press Override setting in SETUP1.
Check for closed valves or restriction in motor
cooling lines.
Check for closed refrigerant isolation valves.
Check Comp Motor Temp Override setting in
SETUP1.
Check refrigerant charge.
Check that optional cooler liquid line isolation
valve is fully open.
Check for excessive condenser flow or low
chilled water flow.
Check for low entering cooler temperature.
Check that condenser inlet and outlet water
nozzles are piped correctly.
Check for waterbox division plate gasket bypass.
Check for high condenser water temperature or
low suction temperature.
Check for high Evaporator or Condenser
approaches.
Check surge prevention parameters in
OPTIONS screen.
Target Guide Vane Position has been forced in
the COMPRESS screen. Select and RELEASE
force to return to normal (automatic) operation.
Verify that the valves in the oil reclaim lines are
open.
Check Rectifier Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
Check Inverter Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.