Carrier 19XR User Manual

Positive Pressure Storage System
Installation, Operating, and
Maintenance Instructions
19XR
50/60 Hz

SAFETY CONSIDERATIONS

Positive pressure storage systems are designed to provide safe and reliable service when operated within design spec­ifications. When operating this equipment, use good judg­ment and safety precautions to avoid damage to equipment and property or injury to personnel.
Installation, start-up, and servicing of this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service techni­cians should install, start up, and service this equipment.
Be sure you understand and follow the procedures and safety precautions contained in this guide.
DANGER
Failure to follow these procedures will result in severe per­sonal injury or death.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented out­doors in accordance with the latest edition of ASHRAE 15 (American Society of Heating, Refrigerating, and Air­Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15, especially for enclosed and low overhead spaces. Inhala­tion of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxy­gen available for breathing. Product causes eye and skin irrita­tion. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed
and functioning before operating any machine.
WARNING
Failure to follow these procedures may result in personal injury or death.
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low-pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter,
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
DO NOT USE eyebolts or eyebolt holes to rig machine sec­tions or the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including con­trol panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are de-energized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If any enters the eyes, IMMEDI­ATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110°F [43°C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
(Warnings continued on next page.)
Catalog No. 04-531900050-01 Printed in U.S.A. Form 19XR-CLT-16SI Rev. A Pg 1 8-19 Replaces: 19XR-6SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
WARNING
CHECK THE REFRIGERANT TYPE before transferring refrigerant to the machine. The introduction of the wrong refrigerant can cause damage or malfunction to this machine.
Operation of this equipment with refrigerants other than those cited herein should comply with ASHRAE 15 (latest edition). Contact Carrier for further information on use of this machine with other refrigerants.
ENSURE that refrigerant is only pumped to or stored in tanks that are ASME (American Society of Mechanical Engineers) certified for the pressures appropriate to the refrigerant being handled.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If machine operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mecha­nism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed
spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.
CAUTION
Failure to follow these procedures may result in personal injury or damage to equipment.
EQUIPMENT should be operated by certified personnel only. DO NOT STEP on refrigerant lines. Broken lines can whip
about and cause personal injury and damage to the machine. DO NOT climb over a machine. Use platform, catwalk, or
staging. Follow safe practices when using ladders. USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift
or move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
DO NOT MIX REFRIGERANT from chillers that use differ­ent compressor oils. Compressor damage can result.
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations.
DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil con­tamination when timely repairs cannot be completed.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 1 — Complete Pre-Installation Checks . . . . . . 3
• IDENTIFY UNIT
• INSPECT SHIPMENT
Step 2 — Mount the Pumpout Unit . . . . . . . . . . . . . . 3
• MOUNTING ON THE CHILLER
• FLOOR MOUNTING
Step 3 — Rig the Storage Tank . . . . . . . . . . . . . . . . . 3
Step 4 — Make Piping Connections . . . . . . . . . . . . . 6
• INSTALL VENT PIPING TO RELIEF DEVICES
Step 5 — Make Electrical Connections . . . . . . . . . . 6
CONTROLS AND COMPONENTS . . . . . . . . . . . . . . 10
Pumpout Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• CONTROLS
• SAFETY CONTROL SETTINGS
•COMPRESSOR
• CONDENSER
•OIL SEPARATOR
• SUCTION AND DISCHARGE VALVES
Storage Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
•DRAIN VALVE
• DUAL RELIEF VALVES
• PRESSURE GAGE
• LEVEL GAGE
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• REFRIGERANT TRANSFER
• TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER COOLER TO THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK
• TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK TO THE CHILLER COOLER
• DISTILLING THE REFRIGERANT
Pumpout and Refrigerant Transfer Procedures . . 12
• PREPARATION
• OPERATING THE OPTIONAL PUMPOUT UNIT (FIG. 9)
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Storage Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ordering Replacement Parts . . . . . . . . . . . . . . . . . . 17
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 17

INTRODUCTION

The 19XR Positive Pressure Storage (PPS) system has been de­signed to help owners and operators of positive pressure chillers store HFC-134a refrigerant during service and repair work. The 19XR system conserves this refrigerant and prevents the release of excessive amounts of refrigerant into the atmosphere. The proper use of this equipment minimizes the loss of HFCs.
The 19XR PPS system shown in Fig. 1 consists of a pump-out unit mounted on a storage tank. The pumpout unit is offered as a free-standing unit that can be used with chillers that have an exist­ing storage tank or with chillers that have isolation valves that per­mit built-in refrigerant storage.
The 19XR PPS systems are factory tested and certified to the American Society of Mechanical Engineers (ASME) pres-sure vessel code. The tanks are constructed of certified steel and are pressure rated at 185 psig (1276 kPa). The PPS storage tank is equipped with dual relief valves for proper venting per ASHRAE 15 (American Society of Heating, Refrigerating, and Air-Condi­tioning Engineers) guidelines. An automatic level switch is pre­wired to the control circuit to ensure proper storage levels.
2
The 19XR pumpout unit is a complete, hermetic, compact unit that consists of:
a hermetic compressor with a direct-drive motor.
a water-cooled refrigerant condenser.
an oil separator.
suction and discharge valves to control refrigerant flow.
prewired safety and control devices.

INSTALLATION

Step 1 — Complete Pre-Installation Checks

IDENTIFY UNIT

Identify the assembly number (see Table 1) printed on the pum­pout unit and storage tank nameplates. Check this information against the job requirements. Figure 1 shows the PPS system and its major components. Refer to Tables 2 and 3 for physical data.

INSPECT SHIPMENT

Inspect unit for damage before removing unit from shipping con-
ping inspector before removal. File a claim with the shipping com­pany if shipment is damaged or incomplete. The manufacturer is not responsible for damage incurred during transit.
Check all components. Notify the supplier immediately if any item is missing. To prevent loss or damage, leave all parts in their original package until they are needed.
Step 2 —
Mount the Pumpout Unit
The pumpout unit, if purchased separately, may be mounted di­rectly on the chiller or it may be floor mounted.

MOUNTING ON THE CHILLER

See instructions provided with the chiller for mounting the pum­pout unit. A typical chiller mount is shown in Fig. 2.

FLOOR MOUNTING

Select a ventilated and accessible area, free of traffic or other haz­ards. Remove and discard the 4 angle supports at the base of the pumpout unit and bolt the unit to the floor through the holes at the base of the pumpout unit. Special isolation is unnecessary. Contact surface and dimensions for the pumpout unit are given in Fig. 3.
veyance. If unit appears damaged, it should be inspected by a ship-
Table 1 — Positive Pressure System Assembly Numbers (R-134a)
PUMPOUT
SYSTEM
ARRANGEMENT
NUMBER 19XR04027401 19XR04035801 208/230-3-50/60 15.8 105.0 28 cu ft (0.8 cu m) 19XR04027402 19XR04035802 460-3-60 7.8 52.0 28 cu ft (0.8 cu m) 19XR04027403 19XR04035803 400-3-50 7.8 52.0 28 cu ft (0.8 cu m) 19XR04027501 19XR04035801 208/230-3-50/60 15.8 105.0 52 cu ft (1.5 cu m) 19XR04027502 19XR04035802 460-3-60 7.8 52.0 52 cu ft (1.5 cu m) 19XR04027503 19XR04035803 400-3-50 7.8 52.0 52 cu ft (1.5 cu m) 19XR04026801 19XR04035801 208/230-3-50/60 15.8 105.0 Free-standing 19XR04026802 19XR04035802 460-3-60 7.8 52.0 Free-standing 19XR04026803 19XR04035803 400-3-50 7.8 52.0 Free-standing 19XR14017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 1 19XR14017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 1 19XR14017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 1 19XR34017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 2 or 3 19XR34017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 2 or 3 19XR34017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 2 or 3 19XR44017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 4 19XR44017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 4 19XR44017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 4 19XR54017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 5 19XR54017802 19XR04035803 460-3-60 7.8 52.0 Unit-mounted, frame 5 19XR54017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 5 19XR64017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 6 19XR64017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 6 19XR64017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 6 19XR74017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 7 19XR74017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 7 19XR74017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 7 19XR84017801 19XR04035801 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 8 19XR84017802 19XR04035802 460-3-60 7.8 52.0 Unit-mounted, frame 8 19XR84017803 19XR04035803 400-3-50 7.8 52.0 Unit-mounted, frame 8
LEGEND NOTES:
LRA — Locked Rotor Amps RLA — Rated Load Amps
PUMPOUT UNIT
ASSEMBLY NUMBER
COMPRESSOR MOTOR
(V-PH-Hz)
1. All storage vessels are 185 psig (1276 kPa) designs per the ASME
2. All units above are shipped with a 15 psig (103 kPa) nitrogen
3. Nominal horsepower for all pumpout units is 3.0.
MAXIMUM
RLA
(American Society of Mechanical Engineers) Boiler Pressure Ves­sel Code, Section VIII Division 1.
charge.
LRA STORAGE TANK
3
Step 3 —
CONTACTOR
TERMINAL
STRIP
FUSES
TRANSFORMER
SWITCH
19XR PUMPOUT UNIT
19XR CONTROL BOX (INTERIOR)
a19-2444
a19-2444
a19-1569ef
COMPRESSOR
CONTROL
BOX
VALV E
ASSEMBLY
CONDENSER
OIL
SEPARATOR
a19-1570ef
Rig the Storage Tank
The complete 19XR system can be rigged as a single assembly. See the rigging instructions on the label attached to the assembly. Also refer to the rigging guide (Fig. 4), physical data in Tables 2 and 3, and contact surface and dimensions for the complete sys­tem in Fig. 5. Lift the assembly only from the 4 points indicated in the rigging guide. Each rigging cable must be capable of support­ing the entire weight of the assembly.
FRAME
ASSEMBLY
COMPRESSOR
VALVE 2
VALVE 3
VALVE 4
VALVE 5
CONTROL
PANEL
WARNING
Lifting the assembly from points other than those specified may result in serious damage to the assembly and personal injury. Rigging equipment and procedures must be adequate for assembly. See Tables 2 and 3 for weights. (These weights are broken down into pumpout unit and storage tank weights. For the complete assembly weight, add all components together.)
ENTERING
WATER
LEAVING
WATER CONDENSER
OIL
OIL
SEPARATOR
HEATER
Fig. 1 — 19XR Positive Pressure Storage System
Fig. 2 — 19XR Pumpout Unit: Typical Chiller Mount
4
NOTE: Dimensions in inches (millimeters).
VAPOR CONNECTIONS
ELECTRICAL CONNECTION OPTION LIST
TRADE SIZE
(in.)
QTY LOCATION
1
/
2
1TOP
3
/
4
1BOTTOM
1 1 MIDDLE
1
1
/
4
1 MIDDLE
a19-2445
NOTES:
1. Each chain must be capable of supporting the entire weight of the machine.
2. Minimum chain length: 28 ft
3
(0.79 m3) tank — 10-0 (3098 mm)
52 ft
3
(1.47 m3) tank — 15-6 (4724 mm)
STORAGE
TANK
SIZE
CENTER OF
GRAVITY
DIMENSIONS
(APPROX.)
ft-in. (mm)
OVERALL DIMENSIONS
(APPROX.)
ft-in. (mm)
EMPTY
WEIGHT
lb (kg)
ABCDE
28 CU FT
(0.8 CU M)
4-9
1
/8
(1451)
1-77/
8
(505)
10-5
(3175)
2-4
3
/
4
(730)
4-4
1
/
4
(1327)
2,385
(1082)
52 CU FT
(1.5 CU M)
6-11
5
/
8
(2124)
1-8
3
/
4
(527)
14-11
1
/
4
(4553)
2-8
1
/
2
(826)
4-8
1
/
4
(1429)
3,415
(1549)
a19-1572ef
WATER CONNECTIONS
3/4" FNPT
1/2" MALE FLARE
ELECTRICAL
CONNECTION
LOCATION
3.25 (83)
CONTROL PANEL
28.45 (723)
24.75 (629)
VACUUM SWITCH
OIL SEPARATORHIGH-PRESSURE SWITCH
COMPRESSOR
23.00 (584)
13.12 (333)
1.00
9.74
(247)
(25)
2.88 (73)
4.58
(116)
18.13 (461)
11.59 (294)
8.21
(209)
4.25
(108)
9.50 (241)
13.25 (337)
9.48 (250)
19.00 (438)
CONDENSER
(2X) 1.82 (33)
7.94
(202)
Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions
OIL SIGHTGLASS
10.50 (267)
MOUNTING HOLES
Fig. 4 — Rigging Guide
5
Table 2 — Physical Data — 19XR Pumpout Unit
ENGLISH SI
Pumpout Unit Weight* lb (kg) 164 (75) Pumpout Condenser Water Flow Rate gpm (L/s) 7-9 (.45-.58)
Pumpout Condenser Water Pressure Drop psig (kPa) 0.3 (2.0) Maximum Entering Condenser Water Temperature F (C) 85 (29) Maximum Leaving Condenser Water Temperature F (C) 100 (37) Relief Valve psig (kPa) 235 (1620) Condenser Pressure Rating
Refrigerant Side psig (kPa) 450 (3102) Waterside psig (kPa) 450 (3102)
*The pumpout unit weight includes the compressor/condenser, control box, and the oil separator.
NOTES:
1. The motor is hermetic with thermal protection.
2. The control box is mounted and wired with an ON/OFF/AUTO. switch according to NEMA 1 (National Electrical Manufacturing Association).
3. The starter contactor is located in the control box. The overloads on the motor are wired and the internal disconnect switch is sup­plied by the customer.
Table 3 — 19XR Storage Tank Rated Dry Weight and Refrigerant Capacity
SIZE
cu ft (cu m)
28 (0.8) 24.00 (610) 2334 (1059) 1860 (844) 1716 (778) 52 (1.5) 27.25 (692) 3414 (1549) 3563 (1616) 3286 (1491)
LEGEND
ANSI American National Standards Institute ASHRAE — American Society of Heating, Refrigeration,
UL Underwriters’ Laboratories
*The above dry weight includes the pumpout unit weight of 164 lb (75 kg).
and Air-Conditioning Engineers
TANK OD
in. (mm)
DRY WEIGHT*
lb (kg)
MAXIMUM REFRIGERANT CAPACITY LB (KG)
ASHRAE/ANSI 15 UL 1963
R-134a R-134a

Step 4 — Make Piping Connections

Figure 5 represents typical pumpout unit/chiller piping connec­tions. Standard connections for
1
/2-in. OD copper tubing are pro­vided. Install the field-supplied FPT tee with pipe plug in the pip­ing as shown in Fig. 5. This tee is used for refrigerant charging.
NOTE: If any field piping runs exceed 50 ft in length, use
7
/8-in.
OD copper tubing to minimize pressure drop. Pumpout unit water piping connections are shown in Fig. 5. Both
connections are
3
/4-in. NPT (female). A shutoff valve should be installed in the water line. Provide a means for blowing water from the condenser coil at winter shutdown to prevent freeze-up damage. Refer to the Job Data for water piping particulars.

INSTALL VENT PIPING TO RELIEF DEVICES

The pumpout storage tank is factory-equipped with relief devices. Refer to Fig. 6 and Table 4 for size and location of the relief devic­es. Vent the relief devices to the outdoors in accordance with ANSI/ASHRAE 15 Safety Code (latest edition) for Mechanical Refrigeration and all other applicable codes. Pumpout unit relief devices are set to relieve at 235 psig (1620 kPa). Storage tank re­lief devices are set to relieve at 185 psig (1276 kPa).
DANGER
Refrigerant discharged into confined spaces can displace oxy­gen and cause asphyxiation.
1. If relief devices are manifolded, the cross-sectional area of the relief pipe must at least equal the sum of the areas required for individual relief pipes.
2. Provide a pipe plug near outlet side of each relief device for leak testing. Provide pipe fittings that allow vent piping to be disconnected periodically for inspection of valve mechanism.
3. Piping to relief devices must not apply stress to the device. Adequately support piping. A length of flexible tub­ing or piping near the device is essential on spring-isolated machines.
4. Cover the outdoor vent with a rain cap and place a condensa­tion drain at the low point in the vent piping to prevent water build-up on the atmospheric side of the relief device.
Step 5 —
Make Electrical Connections
See nameplate on compressor of pumpout unit and Table 1 for motor electrical data. Wire unit according to the diagram inside the control box.
Figure 7 is the wiring schematic for a complete system that in­cludes the 19XR storage tank and the pumpout unit. Figure 8 is the wiring schematic for the pumpout unit. Use this schematic for in­stallations that do not include an auxiliary pumpout storage tank.
NOTE: Use copper conductors only.
6
0’- 3 1/2"
[89mm]
2’- 9 7/8"
[860mm]
2’- 5"
[737mm]
0’- 9 7/8"
[249mm]
4’- 9 1/2" [1451mm]
6’- 4 3/16"
[1935mm]
1" NPT LIQUID CONN.
0’- 9"
[229mm]
TYPICAL
3’- 1 1/4"
[946mm]
3’- 4 5/8"
[1032mm]
3’- 4 7/8"
[1038mm]
2’- 9 9/16"
[852mm]
VAPOR
3/4" NPT PUMPOUT CONDENSER WATER INLET CONN.
1/2" MALE FLARE VAPOR CONN.
3/4" NPT PUMPOUT CONDENSER WATER OUTLET CONN.
ELECTRICAL SERVICE ACCESS SPACE 20 3/4" X 8 3/4" X 4 1/2" (BOTH SIDES)
28 CU.FT. [.79 CU. METER]
STORGE TANK WITH PUMPOUT UNIT
10’- 5 "
[3175mm]
NOTES:
1. Denotes center of gravity.
2. Dimensions in [ ] are in millimeters.
3. The weights and center of gravity values given are for an empty storage tank.
4. For additional information on the pumpout unit, see certified drawings.
5. Conduit knockout is located on the side of the control box.
6. Storage tank weight: 2334 lb (1059 kg).
TOP VIEW
FRONT VIEW
1’-0 3/4" [324mm]
3/8" MALE FLARE RELIEF VALVE CONN.
1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER) (FAR SIDE)
3’- 11 3/8"
[1203mm]
3’- 9"
[1143mm]
0’- 3 1/4"
[83mm]
0’- 10"
[254mm]
1’- 7 7/8"
[505mm]
4’- 4 1/4" [1327mm]
0’- 2 3/4"
[70mm]
0’- 7 15/16"
[202mm]
(FARSIDE)
28 CU FT [0.8 CU METER] STORAGE TANK WITH PUMPOUT UNIT
LEFT SIDE VIEW
LEVEL GAGE
a19-2442
a19-1585
a19-1584
0' - 5 1/2"
[140mm]
2'- 5 3/4"
[756mm]
3/8" MALE FLARE RELIEF VALVE CONN.
1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER)
0' - 9 "
[229mm]
TYPICAL
2' - 4 3/4 "
[730mm]
PRESSURE GAGE
2' - 0 3/8"
[619mm]
1' - 7 "
[483mm]
5' - 0 1/4 " [1530mm]
9' - 10 "
[2997mm]
(2) 1-1/4" NPT RELIEF VALVE OUTLET (SEE FIELD INSTALLATION NOTES)
0' - 5 7/8 "
[149mm]
1' - 2 3/8 "
[365mm]
Fig. 5 — Storage Tank with Pumpout Unit
7
2'-6"
[762mm]
3/8" MALE FLARE RELIEF VALVE CONN.
1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER)
0'-9" [229 mm] TYPICAL
2'-8 1/2" [826 mm]
1'-4 1/4"
[413 mm]
14'-4 1/2"
[4381mm]
0'-5 7/8" [149mm]
(2) 1-1/4" NPT RELIEF VALVE OUTLET (SEE FIELD INSTALLATION NOTES)
5'-0 1/2"
[1537mm]
1'-7"
[483mm]
2'-0 5/8" [625mm]
PRESSURE GAGE
0'-5 1/2" [140mm]
LEVEL GAGE
0’ - 3 3/8"
[86mm]
2’ - 10 1/8"
[867mm]
2’ - 5 1/4"
[742mm]
6’ - 11 5/8"
[2124mm]
0’ - 9 7/8"
[249mm]
7’ - 2 1/4"
[2191mm]
14’ - 11 1/4"
[4553mm]
1" NPT
LIQUID CONN.
52 CU. FT. [1.47 CU. METER]
STORAGE TANK WITH PUMPOUT UNIT
3’ - 8 3/4" [1137mm]
3’ - 1 7/16"
[951mm]
0’ - 9 "
[229mm]
TYPICAL
3’ - 8 1/2 " [1130mm]
3’ - 4 1/2"
[1029mm]
ELECTRICAL SERVICE ACCESS SPACE 20 3/4" X 8 3/4" X 4 1/2" (BOTH SIDES)
3/4" NPT PUMPOUT CONDENSER WATER OUTLET CONN.
1/2" MALE FLARE
VAPOR CONN.
3/4" NPT PUMPOUT CONDENSER WATER INLET CONN.
VAPOR
1’ - 0 3/4"
[324mm]
3/8" MALE FLARE RELIEF VALVE CONN.
1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER) (FAR SIDE)
0’ - 0 15/16"
[202mm]
(FARSIDE)
0’ - 2 3/4"
[70mm]
4’ - 3 1/4" [1302mm]
4’ - 1"
[1225mm]
0’ - 3 1/4"
[83mm]
0’ - 10"
[254mm]
1’ - 8 3/4"
[527mm]
4’ - 8 1/4"
[1429mm]
NOTES:
1. Denotes center of gravity.
2. Dimensions in [ ] are in millimeters.
3. The weights and center of gravity values given are for an empty storage tank.
4. For additional information on the pumpout unit, see certified drawings.
5. Conduit knockout is located on the side of the control box.
6. Storage tank weight: 3414 lb (1549 kg).
FRONT VIEW
TOP VIEW
LEFT SIDE VIEW
52 CU FT [1.5 CU METER] STORAGE TANK WITH PUMPOUT UNIT
a19-2443
a19-1583
a19-1582
Fig. 5 — Storage Tank with Pumpout Unit (cont)
8
SERVICE VALVES
PUMPOUT
COMPRESSOR
PRESSURE RELIEF
VALV E
OIL
SEPARATOR
PUMPOUT
CONDENSER
WATER
CONNECTIONS
2
3
4
5
TO TOP OF
STORAGE TANK
STORAGE TANK
VAPOR VALVE
FROM BOTTOM
OF STORAGE TANK
STORAGE TANK
LIQUID REFRIGERANT VALVE
TEE FOR
REFRIGERANT
CHARGING
TO TOP OF
CHILLER
CONDENSER
SEE NOTE
# 1
TO TOP OF
CHILLER
COOLER
SEE NOTES
# 1 AND 2
CHECK VALV E
SERVICE VALVES
PUMPOUT
COMPRESSOR
PRESSURE RELIEF
VALV E
OIL
SEPARATOR
PUMPOUT
CONDENSER
WATER
CONNECTIONS
2
3
4
5
TO TOP OF
STORAGE TANK
STORAGE TANK
VAPOR VALVE
FROM BOTTOM
OF STORAGE TANK
STORAGE TANK
LIQUID REFRIGERANT VALVE
TEE FOR
REFRIGERANT
CHARGING
TO BOTTOM OF
COOLER AND
CHILLER
CONDENSER
SEE NOTE
# 1
TO TOP OF
CHILLER COOLER
OR CONDENSER
SEE NOTES
# 1 AND 2
TO ADDITIONAL
CHILLERS
CHECK
VALV E
CHILLERS WITHOUT ISOLATION VALVES
CHILLERS WITH ISOLATION VALVES
(WITH OR WITHOUT PUMPOUT STORAGE TANKS)
GENERAL PIPING CONNECTION SIZES
NOTES:
1. The field-supplied tubing is to be 1/2-in. OD tubing (min.) and must be arranged and supported to avoid stresses on the equip­ment, transmission of vibrations, and interference with routine access during the reading, adjusting, and servicing of the equip­ment. If the distance from the chiller to the pumpout unit is over 50 ft, then
7
/8-in. OD tubing (min.) must be used. Provisions should be made for adjustment in each plane of the tubing and for both periodic and major servicing of the equipment. Special care must be taken so that the safety head does not experience tubing strain. Vent the safety head per ASHRAE 15 (American Society of Heating, Refrigerating, and Air-Conditioning Engi­neers), latest revision.
2. The tubing and valve from the storage tank to the pumpout com­pressor is factory supplied when the unit is factory mounted.
CONNECTION SIZE (in.)
Refrigerant Transfer Connections
1
/2 Flare (male)
Condenser Water Cooling Connectors
3
/4 NPT (female)
Safety Relief Head Pumpdown
3
/8 Flare (male)
LEGEND
Factory-Supplied Tubing
Field-Supplied Tubing
Field-Supplied Tubing (Multiple Chillers)
Service Valve (Factory Supplied)
Service Valve (Field Supplied)
a19-1575ef
a19-1576ef
STORAGE TANK SIZE cu ft (cu m)
28 (0.8)
52 (1.5)
Fig. 6 — Typical Pumpout Unit/Chiller Connection Schematic
RELIEF VALVE
OUTLET SIZE
1
1
/4 in. NPT
Female Connector
1
1
/4 in. NPT
Female Connector
Table 4 — Relief Devices
QUANTITY
2 34.5 15.6
2 52.3 23.7
9
REQUIRED “C” FACTOR
lb air
min
kg air
min
a19-2447
LOW PRESSURE CONTROL NC OPEN < 7 psia (-15.7 in. HG) CLOSE > 9 psia (-11.6 in. HG)
HIGH PRESSURE
SAFETY
NC OPEN > 185psig
CONTROL POWER
TRANSFORMER
XFMR-1
69 VA
PUMP OUT
COMPRESSOR
CRANKCASE HEATER
240-600v
27-40 WATT
COPELAND PN 081-0031-03
WHT
RED
ORN
HIGH LEVEL GAGE ALARM (NC-OPEN AT 90% STORAGE TANK LEVEL)
WHT
X2
C
5
4
X2
X2
1
X1
FU3
0.5A
H1
H4
FU1
FU2
0.25A
0.25A
GND
2
2
3
SS-1 OFF
AUTO ON
2
L2
L1
8
7
HTR-1
MTR-1
2 OL
2 OL
2 OL
C
C
C
LEVEL GAGE
ALARM SWITCH
NO
NC
LEGEND
C—Contactor FU Fuse GND — Ground HTR — Heater MTR — Motor NC Normally Closed OL Overload SS Selector Switch
a19-2448
LOW PRESSURE CONTROL NC OPEN < 7 psia {-15.7 in. HG} CLOSE > 9 psia {-11.6 in. HG}
HIGH PRESSURE
SAFETY
NC OPEN > 185psig
CONTROL POWER
TRANSFORMER
XFMR-1
69 VA
PUMP OUT
COMPRESSOR
CRANKCASE HEATER
240-600v
27-40 WATT
X2
C
5
4
X2
X2
1
X1
FU3
0.5A
H1
H4
FU1
FU2
0.25A
0.25A
GND
2
2
3
SS-1
OFF
AUTO ON
2
L2
L1
8
7
HTR-1
MTR-1
2 OL
2 OL
2 OL
C
C
C
LEGEND
C—Contactor FU Fuse GND — Ground HTR — Heater MTR — Motor NC Normally Closed OL Overload SS Selector Switch
Fig. 7 — 19XR Pumpout System Wiring Schematic
Figure 1 shows the major components of the PPS system.

Pumpout Unit

The pumpout unit consists of a hermetic compressor, a water cooled refrigerant condenser, an oil separator, and prewired safety and control devices. The pumpout unit comes equipped with a 4­way transfer valve manifold to interconnect both liquid and vapor

CONTROLS AND COMPONENTS

Fig. 8 — Pumpout Unit Wiring Schematic
transfer and to pressurize the chiller during transfer of refrigerant from chiller to storage tank.

CONTROLS

The pumpout unit has the following controls: manual/off/automat­ic selector switch, transformer, .25 amp fuses for the primary side of the transformer, 5 amp fuse for the secondary side of the trans­former, contactor, terminal strip, high pressure cutout switch and low pressure switch.
10

SAFETY CONTROL SETTINGS

The pumpout unit high-pressure switch (Fig. 3) is set to open at the settings listed in Table 5. The switch setting is checked by op­erating the pumpout condenser and slowly throttling the pumpout condenser water.
When the selector switch is in the Automatic position, the pum­pout will cycle on a low pressure/vacuum switch. This switch will shut down the pumpout compressor when suction pressure reach­es 7 ± 1.5 psia or 15 ± 3 in. Hg vacuum (51.7 kPa absolute). When the selector switch is in the On position, the pumpout compressor will continue to run until refrigerant vapor flow is so low that the compressor motor overheats. At this time the compressor motor overload will shut off the compressor. This is NOT recommended.
Table 5 — High Pressure Switch Settings
REFRIGERANT
R-134a
HIGH-PRESSURE SWITCH
CUTOUT CUT-IN
185 ± 10 psig
(1276 ± 69 kPa)
140 ± 10 psig
(965 ± 69 kPa)

COMPRESSOR

The hermetic compressor assembly comes equipped with internal thermal protection on the motor and a self-regulating crankcase heater.

CONDENSER

The water-cooled condenser is a brazed plate heat exchanger. During transfer, it condenses refrigerant vapor to liquid.

OIL SEPARATOR

The pumpout unit includes an in-line oil separator to remove oil that becomes mixed with refrigerant and returns the oil to the com­pressor.

SUCTION AND DISCHARGE VALVES

The pumpout unit comes with a 4-way transfer valve manifold to interconnect both liquid and vapor transfer and to pressurize the chiller during transfer of refrigerant from chiller to storage tank or from one chiller vessel to another.

Storage Tank

The storage tank is rated for positive pressure refrigerants under ASME Section VIII pressure vessel codes with a minimum of 185 psig (1276 kPa) rating. The tank components include:

DRAIN VALVE

Located at its lowest point of drain with a minimum of 1 in. NPT.

DUAL RELIEF VALVES

Two relief valves and a 3-way shut-off valve.

PRESSURE GAGE

A 30 in. Hg vacuum -0-400 psig (101-0-2760 kPa) compound pressure gage.

LEVEL GAGE

Liquid level gage (magnetically coupled dial type) with electronic shut-off at 90% liquid capacity.
WARNING
During transfer of refrigerant into and out of the pumpout stor­age tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank and personal injury. For maximum refrigerant capacity, refer to Table 3.

OPERATION

Overview

Transferring refrigerant from one vessel to another is accom­plished by using either gravity or pressure differential. A differ­ence in elevation between 2 vessels results in a gravity flow of liq­uid; a difference in pressure forces the liquid from one vessel to the other. The latter method requires lowering the pressure in one vessel. If there is liquid in that vessel, its temperature must be low­ered, and the pressure in the other vessel must be simultaneously increased.
Under most circumstances, creating the pressure differential is not a difficult process. Some applications, such as ice storage, outdoor installations, or installations with high temperature differentials between the storage tank and the chiller may require additional consideration. In some instances, it may be necessary to add auxil­iary heat to one of the vessels or to insulate the storage tank at job sites where high ambient temperature or sun load make it difficult to reduce the temperature and pressure in the tank. Outdoor instal­lations must have a roof or cover over the storage tank to ensure that the pressure in the tank does not exceed the chiller relief pres­sure setting.

REFRIGERANT TRANSFER

When refrigerant is being evacuated from the chiller cooler or condenser vessels, any liquid refrigerant left in a vessel will flash off, lowering the temperature in that vessel enough to freeze the fluid (usually water) flowing through the cooler or condenser tubes. This event, called tube freeze-up, can cause extensive dam­age to the chiller; therefore, all liquid refrigerant must be removed from a vessel before evacuation of refrigerant vapor is started. If all the liquid cannot be removed, then the cooler water and con­denser water pumps must be operated throughout the process of evacuating refrigerant vapor to keep fluid moving through the cooler and condenser tubes.

TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER COOLER TO THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK

Chiller and pumpout unit valves are set to permit the pumpout compressor to discharge refrigerant vapor into the cooler vessel, lowering pressure in the condenser vessel/storage tank. The pres­sure differential forces liquid from the cooler vessel into the con­denser vessel/storage tank. After all the liquid is transferred, the refrigerant vapor remaining in the cooler vessel can be drawn off by reducing pressure in the chiller and discharging the vapor through the pumpout unit condenser into the condenser vessel/ storage tank.
NOTE: The pumpout selector switch can be placed in On or Auto­matic mode. In Automatic mode, the compressor will shut off au­tomatically once the suction pressure drops to 7 psia or 15 in. Hg vacuum (51.7 kPa absolute). In On mode, the unit will continue to pumpout regardless of the suction (vacuum) pressure.

TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK TO THE CHILLER COOLER

Chiller and pump-out unit valves are set to increase pressure in the chiller condenser vessel/storage tank and to reduce pressure in the cooler vessel. Pressure in the cooler vessel is lowered to corre­spond to a saturated refrigerant liquid temperature 2°F (1.1°C) above the freezing temperature of the liquid circulating through the chiller cooler/condenser tubes (34°F [1.1°C] for water). The valves are set so that the pressure in the cooler vessel is lower than that of the condenser vessel/storage tank, forcing the liquid into the cooler vessel.
NOTE: The pumpout selector switch can be placed in On or Auto­matic mode. In Automatic mode, the compressor will shut off au­tomatically once the suction pressure drops to 7 psia or 15 in. Hg
11
vacuum (51.7 kPa absolute). In On mode, the unit will continue to pumpout regardless of the suction (vacuum) pressure.
NOTE: During this operation, maintain water circulation through the chiller cooler and condenser vessels to prevent tube freeze-up.

DISTILLING THE REFRIGERANT

Refrigerant vapor is transferred from the chiller cooler vessel or pumpout storage tank through the pumpout condenser, condensed to a liquid, and pumped to the chiller condenser vessel. During this operation, water circulation must be maintained in the pump-out condenser. Refrigerant impurities left in the chiller cooler vessel or storage tank are then drained off. This operation can take from 4 to 14 hours, depending on the type and amount of refrigerant being distilled.
The Pumpout and Refrigerant Transfer Procedures section gives step-by-step instructions on performing these operations.

Pumpout and Refrigerant Transfer Procedures

PREPARATION

The 19XR chiller may come equipped with an optional pumpout storage tank, pumpout system, or pumpout compressor. The re­frigerant can be pumped for service work to either the chiller com­pressor vessel or chiller condenser vessel by using the optional pumpout system. If a pumpout storage tank is supplied, the refrig­erant can be isolated in the storage tank. The following procedures describe how to transfer refrigerant from vessel to vessel and per­form chiller evacuation.
CAUTION
Do not mix refrigerants from chillers that use different com­pressor oils. Compressor damage can result. The pumpout oil separator comes pre-charged with 13 oz of ISO viscosity 220 POE (Polyol Ester) oil. The pumpout compressor is approved for use with ISO viscosity 220 POE oil or ISO viscosity 68 POE oil. The pumpout compressor is also factory precharged with oil.

OPERATING THE OPTIONAL PUMPOUT UNIT (Fig. 9)

Oil should be visible in the pumpout unit compressor sight glass under all operating conditions and during shutdown. If oil is low, add oil as described under Maintenance section, page 17. The pumpout unit control wiring schematic is detailed in Fig. 8.
To Read Refrigerant Pressures (during pumpout or leak testing):
1. The ICVC display on the chiller control panel is suitable for determining refrigerant-side pressures and low (soft) vacuum. To assure the desired range and accuracy when measuring evacuation and dehydration, use a quality vacuum indicator or manometer. This can be placed on the Schrader connec­tions on each vessel by removing the pressure transducer.
2. To determine pumpout storage tank pressure, a 30 in. Hg vac­uum -0-400 psi (-101-0-2769 kPa) gage is attached to the storage tank.
3. Refer to Fig. 10 and 11 for valve locations and numbers.
CAUTION
The power to the pumpout compressor oil heater must be on whenever any valve connecting the pumpout compressor to the chiller or storage tank is open. Leaving the heater off will result in oil dilution by refrigerant and can lead to compressor failure.
If the compressor is found with the heater off and a valve open the heater must be on for at least 4 hours to drive the refriger­ant from the oil. When heating the oil the compressor suction must be open to a vessel to give the refrigerant a means to leave the compressor.
CAUTION
Always run the chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when the chiller pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly caus­ing tube freeze-up.
DANGER
During transfer of refrigerant into and out of the optional stor­age tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank or the release of refrigerant which will result in personal injury or death.
CAUTION
Transfer, addition, or removal of refrigerant in spring-isolated chillers may place severe stress on external piping if springs have not been blocked in both up and down directions.
Positive Pressure Chillers With Storage Tanks
In the Valve/Condition tables that accompany these instructions, the letter “C” indicates a closed valve. Figures 9 and 10 show the locations of the valves.
CAUTION
Always run chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when chiller ves­sel pressure is less than 35 psig (241 kPa). Below these pres­sures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up.
CAUTION
The power to the pumpout compressor oil heater must be on whenever any valve connecting the pumpout compressor to the chiller or storage tank is open. Leaving the heater off will result in oil dilution by refrigerant and can lead to compressor failure.
If the compressor is found with the heater off and a valve open the heater must be on for at least 4 hours to drive the refriger­ant from the oil. When heating the oil the compressor suction must be open to a vessel to give the refrigerant a means to leave the compressor.
12
a19-2446
FRAME
ASSEMBLY
CONTROL
PANEL
VALVE 2
VALVE 4
VALVE 5
VALVE 3
ENTERING
WATER
LEAVING
WATER CONDENSER
OIL
SEPARATOR
OIL
HEATER
COMPRESSOR
a19-
2444
Fig. 9 — Pumpout Unit
Transfer Refrigerant from Storage Tank Vessel to Chiller
WARNING
During transfer of refrigerant into and out of the 19XR storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank and personal injury.
1. Equalize refrigerant pressure. a. Turn on chiller water pumps, establishing water flow
(assumes vacuum condition in chiller system).
b. Close pumpout and storage tank valves 2, 4, 5, 7, 8, 10
(if present open isolation valve 11 and other isolation valves between cooler and condenser). Open storage tank valve 6; open chiller valves 1A and 1B.
VALVE 1A 1B 2 3 4 5 6 7 8 10 11
CONDITION C C C C C C
c. Gradually open valve 5 to slowly increase chiller pres-
sure to 35 psig (241 kPa) to reduce the potential of tube freeze up.
d. Open valve 5 fully after the chiller pressure reaches
35 psig (241 kPa) or greater. Let chiller pressure reach 40 psig (276 kPa), then chiller water pumps can be turned off. Fully close valve 5.
VALVE 1A1B23456781011
CONDITION C C C C C C
CONDITION C C C C
2. Push liquid to chiller, them remove remaining vapor from
CONDITION C C C
e. Open valve 8 and 10 to let higher pressure in the recov-
ery tank push liquid refrigerant into the condenser float chamber and heat exchangers until the refrigerant pres­sure equalizes between the recovery tank and chiller.
VALVE 1A1B23456781011
storage tank:
a. To prepare for liquid, push open valve 4.
VALVE 1A1B23456781011
OIL FILL 1/4-IN. FLARE VALVE
b. Ensure pumpout condenser water is off, then turn on the
pumpout compressor in manual mode to push liquid to chiller. Monitor the storage tank level until tank is empty
of liquid refrigerant. c. Close charging valves 8 and 10. d. Turn off the pumpout compressor. e. To prepare for removal of remaining refrigerant vapor in
storage tank, close pumpout valves 3 and 4 and open
valves 2 and 5.
VALVE 1A1B23456781011
CONDITION C C C C C
f. Turn on pumpout condenser water. g. Run pumpout unit in auto until the vacuum switch is sat-
isfied. This occurs approximately at 15 in Hg vacuum
(48 kPa absolute or 7 psia), removing the residual refrig-
erant vapor from the recovery tank and condensing to a
liquid in the chiller. h. Close valves 1A, 1B, 2, 5, 6.
VALVE 1A1B23456781011
CONDITIONCCCCCCCCCC
i. Turn off pumpout condenser water.
Transfer Refrigerant from Chiller to Storage Tank Vessel
1. Equalize refrigerant pressure. a. Dehydrate the refrigerant storage vessel, and connected
hoses/piping so there are no non-condensables mixed with the refrigerant.
b. Locate valves as identified below:
VALVE 1A1B23456781011
CONDITION C C C C C C
c. Slowly open valve 5 until the refrigerant pressure
reaches 35 psig (241 kPa) in the storage tank, followed by valves 7 and 10 to allow liquid refrigerant to drain by gravity.
VALVE 1A1B23456781011
CONDITION C C C
13
2. Push remaining liquid, followed by refrigerant vapor removal from chiller.
a. To prepare for liquid push, turn off the pumpout con-
denser water. Place valves in the following positions:
VALVE 1A1B23456781011
CONDITION C C C
b. Run the pumpout compressor in manual until all liquid is
pushed out of the chiller (approximately 45 minutes). Close valves 2, 5, 7, and 10, then stop compressor.
VALVE 1A1B23456781011
CONDITION CCCC CCC
c. Turn on pumpout condenser water. d. Open valves 3 and 4, and place valves in the following
positions:
VALVE 1A1B23456781011
CONDITION C C C C C
e. Run the pumpout compressor until the chiller pressure
reaches 35 psig (241 kPa), followed by turning off the pumpout compressor. Warm chiller condenser water will boil off any entrapped liquid refrigerant, and chiller pres­sure will rise.
f. When chiller pressure rises to 40 psig (276 kPa), turn on
the pumpout compressor until the pressure reaches 35 psig (241 kPa) again; then turn off the pumpout com­pressor. Repeat this process until the chiller pressure no longer rises.
g. Start the chiller water pumps (condenser and cooler),
establishing water flow. At this point, turn on the pum­pout compressor in auto until the vacuum switch is satis­fied. This occurs at approximately 15 in Hg vacuum (48 kPa absolute or 7 psia).
h. Close valves.
VALVE 1A1B23456781011
CONDITIONCCCCCCCCCC
i. Turn off the pumpout condenser water.
Chillers With Isolation Valves
In the Valve/Condition tables that accompany these instructions, the letter “C” indicates a closed valve.
The valves referred to in the following instructions are shown in Fig. 9 and 11. The cooler/condenser vessels can be used for refrig­erant isolation for certain service conditions when the isolation valve package is specified.
Transfer Refrigerant from Cooler to Condenser
a. Turn off chiller water pumps and pumpout condenser
water supply (if applicable). It is assumed that the start­ing point is as shown in the following table and that pres­sures in both vessels are above 35 psig (241 kPa).
VALVE 1A1B23457811
CONDITION CCCCCCCCC
b. Keeping valves 7 and 8 closed, install charging hose
from liquid line charging valve 7 to valve 8 on the con­denser float chamber. Evacuate or purge hose of non­condensables. Note that this creates a flow path between cooler and condenser that bypasses the linear float, reducing the potential for damage during refrigerant transfer.
c. Open valves 1A, 1B, 2, 5, and 8.
VALVE 1A1B23457811
CONDITION C C C C
d. Turn on pumpout compressor, generating a refrigerant
pressure differential of 10 to 20 psi (69 to 138 kPa) to push liquid out of the chiller cooler vessel.
e. Slowly
open valve 7 to allow liquid transfer. Rapid open-
ing of valve 7 can result in float valve damage.
f. When all liquid has been pushed into the chiller con-
denser vessel, close valve 8.
VALVE 1A1B23457811
CONDITION C C C C
g. Turn off the pumpout compressor. h. Close pumpout valves 2 and 5 while opening valve 3 and
4 to prepare for removal of remaining refrigerant vapor in cooler vessel.
VALVE 1A1B23457811
CONDITION C C C C
i. Turn on pumpout condenser water. j. Turn on pumpout compressor. Turn on the chiller water
pump to establish water flow when the cooler refrigerant pressure is 35 psig (241 kPa). The water pumps have to
be in operation whenever the refrigerant pressure is equal to or less than 35 psig (241 kPa) to reduce the potential of tube damage.
k. Run the pumpout compressor until the cooler pressure
reaches 35 psig (241 kPa), then turn off the pumpout compressor. Warm chiller cooler water will boil off any entrapped liquid refrigerant, and chiller pressure will rise. Repeat this process until the chiller pressure no lon­ger rises.
l. Run pumpout unit in auto until the vacuum switch is sat-
isfied; this occurs at approximately 15 in. Hg vacuum (48 kPa absolute or 7 psia). Close valve 1A.
VALVE 1A1B23457811
CONDITION C C C C C
m. Monitor that cooler pressure does not rise (if it does, then
repeat previous step).
n. With service valve 1A closed, shut down pumpout com-
pressor (if still running).
o. Close remaining valves.
VALVE 1A1B23457811
CONDITION CCCCCCCCC
p. Remove charging hose between 7 and 8 (evacuate prior
to removal). q. Turn off pumpout condenser water. r. Turn off chiller water pumps, and lockout chiller com-
pressor.
Transfer Refrigerant from Condenser to Cooler
a. Turn off chiller water pumps and pumpout condenser
water supply (if applicable). It is assumed that the start-
ing point is as shown in the following table and that pres-
sures in both vessels are above 35 psig (241 kPa).
VALVE 1A1B23457811
CONDITION CCCCCCCCC
b. Set valves as shown below to allow the refrigerant to
equalize:
VALVE 1A 1B 2 3 4 5 7 8 11
CONDITION C C C C C
c. Turn on pumpout compressor, and develop a 10 to 20 psi
(69 to 138 kPa) refrigerant differential pressure between
the vessels.
14
d. Partially open valve 11 while maintaining a refrigerant
pressure differential to push liquid refrigerant out of the chiller condenser to the cooler.
e. When all liquid is out of the chiller condenser, close
valve 11 and any other isolation valves on the chiller. f. Turn off the pumpout compressor. g. Close pumpout valves 3 and 4 while opening valve 2 and
5 to prepare for removal of remaining refrigerant vapor
in condenser vessel.
VALVE 1A1B23457811
CONDITION C C C C C
h. Turn on pumpout condenser water. i. Turn on pumpout compressor. j. Turn on the chiller water pumps, establishing water flow
when the condenser refrigerant pressure is 35 psig
(241 kPa). The water pumps have to be in operation
whenever the refrigerant pressure is equal to or less
than 35 psig (241 kPa) to reduce the potential of tube
damage.
k. Run the pumpout compressor until the condenser refrig-
erant pressure reaches 35 psig (241 kPa) then turn off the
pumpout compressor. Warm condenser water will boil
off any entrapped liquid refrigerant, and chiller pressure
will rise. Repeat this process until the chiller pressure no
longer rises. l. Run pumpout unit in auto until the vacuum switch is sat-
isfied; this occurs at approximately 15 in. Hg vacuum
(48 kPa absolute or 7 psia). Close valve 1B.
VALVE 1A1B23457811
CONDITION C C C C C C
m. Monitor that condenser pressure does not rise (if it does,
then repeat previous step). n. With service valve 1B closed, shut down pumpout com-
pressor (if still running). o. Close remaining valves.
VALVE 1A1B23457811
CONDITION CCCCCCCCC
p. Turn off pumpout condenser water. q. Turn off chiller water pumps, and lock out chiller com-
pressor.
Return Chiller to Normal Operating Conditions
1. Vapor Pressure Equalization: a. Ensure that the chiller vessel that was exposed to ambi-
ent has been evacuated. Final vacuum prior to charging with refrigerant should in all cases be 29.9 in. Hg
(500 microns, 0.07 kPa [abs]) or less. b. Turn on chiller water pumps. c. Open valves 1A, 1B, and 2.
VALVE 1A1B23457811
CONDITION CCCCCC
d. Slowly open valve 4, gradually increasing pressure in the
evacuated vessel to 35 psig (241 kPa). e. Leak test to ensure chiller vessel integrity. f. Open valve 4 fully for cooler and condenser pressure
equalization (vapor equalization).
VALVE 1A1B23457811
CONDITION C C C C C
g. Close valves 1A, 1B, 2, and 4.
VALVE 1A1B23457811
CONDITION CCCCCCCCC
1. Liquid equalization: a. If refrigerant is stored in cooler, install a charging hose
between valves 7 and 8, and open both the valves and any other isolation valves (except valve 11) for liquid to drain into the condenser while bypassing the linear float valve. If refrigerant is stored in the condenser, keep valve 11 and any other isolation valves open for liquid drain.
VALVE 1A1B23457811
CONDITION
(CHARGE IN
COOLER)
CONDITION
(CHARGE IN
CONDENSER)
CCCCCC C
CCCCCCCC
b. If valves 7 and 8 were used to bypass the linear float
valve, once the liquid transfer is complete, close these valves, and slowly open valve 11.
c. Turn off chiller water pumps.
Distilling the Refrigerant
1. Transfer the refrigerant from the chiller to the pumpout stor­age tank as described in the Transfer Refrigerant from Chiller to Storage Tank Vessel section.
2. Equalize the refrigerant pressure.
a. Turn on chiller water pumps and monitor chiller pres-
sures.
b. Close pumpout and storage tank valves 2, 4, 5, and 10,
and close chiller charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present.
c. Open pumpout and storage tank valves 3 and 6; open
chiller valves 1a and 1b.
VALVE 1A1B2345671011
CONDITION C C C C C
d. Gradually crack open valve 5 to increase chiller pressure
to 35 psig (241 kPa). Slowly feed refrigerant to prevent freeze-up.
e. Open valve 5 fully after the chiller pressure rises above
the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize.
3. Transfer remaining refrigerant.
a. Close valve 3. b. Open valve 2.
VALVE 1A1B2345671011
CONDITION C C C C
c. Turn on pumpout condenser water. d. Run the pumpout compressor until the storage tank pres-
sure reaches 5 psig (34 kPa), 18 in. Hg vacuum (41 kPa
absolute) in Manual or Automatic mode. e. Turn off the pumpout compressor. f. Close valves 1a, 1b, 2, 5, and 6. Turn off pumpout con-
denser water.
VALVE 1A1B2345671011
CONDITION CCCCCCCCC
4. Drain the contaminants from the bottom of the storage tank into a container. Dispose of contaminants safely.
15
a19-2434
5
COMPRESSOR
CONDENSER
NOTES:
1. Maintain at least 2 feet (610 mm) clearance around storage tank for service and operation work.
2. Valve 8 is only applicable for products with linear float valves.
a19-2435
5
PUMPOUT COMPRESSOR
OIL SEPARATOR
V
NOTE: Valve 8 is only applicable for products with linear float valves.
PUMPOUT
8
2
RELIEF VALVE
OIL SEPARATOR
PUMPOUT CONDENSER
7
COOLER
6
STORAGE VESSEL
CHECK VALVE
10
Fig. 10 — Typical Optional Pumpout System Piping Schematic with Storage Tank
RELIEF
ALVE
CONDENSER
8
2
7
COOLER
Fig. 11 — Typical Optional Pumpout System Piping Schematic without Storage Tank
16
PUMPOUT CONDENSER
CHECK VALVE

MAINTENANCE

Periodic maintenance is necessary to keep all components func­tioning as designed. A maintenance log is recommended to ensure a proper maintenance schedule is followed.

Pumpout Compressor Oil Charge

Use oil conforming to Carrier specifications for centrifugal or screw compressor use. Oil requirements are listed in Table 6.
Monitor and adjust compressor oil level as often as necessary. When replacing lost oil, add the same type of oil that is used in the chiller being pumped out.
Table 6 — Pumpout Compressor Requirements
REFRIGERANT
R-134a
ISO
VISCOSITY
68 PP47-31
220 PP47-32
The pumpout oil separator comes pre-charged with 13 oz of ISO viscosity 220 POE (Polyol Ester) oil. The pumpout compressor is approved for use with ISO viscosity 220 POE oil or ISO viscosity 68 POE oil. The pumpout compressor is also factory precharged with POE oil.
Oil should be visible in the pumpout compressor sight glass both during operation and at shutdown. Always check the oil level be­fore operating the pumpout compressor.
Oil can be added to the 1/4-in. SAE flare access valve port running from the top of the oil separator to the compressor while the com­pressor is running. Be careful not to overfill.
NOTE: Compressor access valve has a self-sealing fitting which will require a hose connection with a depressor to open.
To change or remove oil, the compressor will have to be removed from the assembly. Compressor can be disconnected from con­nected tubing by the quick connect fittings at suction and dis­charge and oil recovery line.
Prior to removal, close service valves 2, 3, 4, and 5, and run the pumpout compressor in AUTOMATIC until the vacuum switch is satisfied and the compressor shuts off. Move pumpout selector switch to OFF, and turn off all power to unit prior to removing
CARRIER
SPECIFICATION NO.
compressor unit from pumpout assembly frame and connecting tubing.
Service valves 2, 3, 4, and 5 remain closed while compressor is re­moved. Put compressor back in place. Use the torque values listed in Table 7 for reassembly:
Table 7 — Torque Values for Reassembly
PARAMETER
Suction 80 to 100 109 to 136
Discharge 50 to 60 68 to 81
O-ring Face Seal 7 to 9 10 to 12
VALUES
ft-lb Nm
Be sure to use backup wrench and pull a deep vacuum in the ser­viced pumpout tubing prior to any refrigerant exposure. At this point, confirm that the oil level is satisfactory and put the pumpout back in service.

Storage Tank

To prevent moisture and contaminants from entering the storage tank, maintain positive pressure in the tank when not transferring refrigerant. Leak test the storage tank periodically.

Ordering Replacement Parts

The following information must accompany an order for Carrier specified parts:
machine model number and serial number
name, quantity, and part number of the part required
delivery address and method of shipment

TROUBLESHOOTING

Information on troubleshooting for the PPS system is included in Tab le 8.
Table 8 — Troubleshooting
SYMPTOM PROBABLE CAUSE REMEDY
Compressor Does Not Run
Compressor Cycles On High-Pressure Control
Unit Operates Too Long Isolation valves partially open Close valves. System Noises Piping vibrations Support piping as required. Check for loose pipe connectors.
Compressor Loses Oil Leak in system Locate and repair leak.
Main power line open Replace fuse or reset circuit breaker. Loose terminal connection Check connections. Improperly wired controls Check wiring and rewire. Low line voltage Check line voltage; determine location of voltage drop. Compressor motor defective Check motor winding for open or short. Replace compressor if
Seized compressor Replace compressor. High level gage alarm Check refrigerant level and remove excess. High-pressure control erratic in action Check capillary tube for pinches. Set control as required. Discharge valve partially closed. Open valve. Air in system Purge system. Condenser scaled. Clean condenser. Condenser water pump or fans not
operating.
Insufficient compressor oil Add oil.
Plugged or stuck compressor oil return check valve
Liquid refrigerant carries oil out of compressor
Motor shutdown on internal thermal protec­tion high temperature cutout.
necessary.
Start pump or fans.
Repair or replace valve.
Check to ensure only refrigerant vapor enters compressor suction line. Add oil as necessary.
High temperature cutout should reset within 120 minutes.
17
© Carrier Corporation 2019
Catalog No. 04-531900050-01 Printed in U.S.A. Form 19XR-CLT-16SI Rev. A Pg 20 8-19 Replaces: 19XR-6SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Loading...