Carrier 19XR User Manual

AquaEdge
19XR
Two-Stage Semi-Hermetic Centrifugal Liquid Chillers
with PIC 5 Controls and HFC-134a
50/60 Hz
Start-Up, Operation, and Maintenance Instructions

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifi­cations. When operating this equipment, use good judg­ment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.
DANGER
Failure to follow these procedures will result in severe per­sonal injury or death.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented out­doors in accordance with the latest edition of ANSI/ ASHRAE 15 (American National Standards Institute/ American Society of Heating, Refrigerating, and Air­Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harm­ful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures; VERIFY the allowable test pressure by checking the instruction litera­ture and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly
installed and functioning before operating any chiller. RISK OF INJURY OR DEATH by electrocution. High
voltage is present on motor leads even though the motor is not running when a solid-state or wye-delta mechanical starter is used. Open the power supply disconnect before touching motor leads or terminals.
WARNING
Failure to follow these procedures may result in personal injury or death.
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig­erant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
DO NOT USE eyebolts or eyebolt holes to rig chiller sec­tions or the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servic­ing. IF WORK IS INTERRUPTED, confirm that all cir­cuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refriger­ant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLE­GAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
(Warnings continued on next page.)
Manufacturer reserves the right to discontinue, or change at any time, specificatio ns or designs without not ice and without incurring obligations.
Catalog No. 04-53190038-01 Printed in U.S.A. Form 19XR-CLT-12SS Pg 1 12-15 Replaces: 19XR-CLT-11SS
WARNING
Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this chiller with other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a com-
pressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.
CAUTION
Failure to follow these procedures may result in personal injury or damage to equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the water­box has been completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations.
DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to pre­vent oil contamination when timely repairs cannot be completed.

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1,2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ABBREVIATIONS AND EXPLANATIONS . . . . . . . . . . . . 4
CHILLER FAMILIARIZATION. . . . . . . . . . . . . . . . . . . . . . .4-6
Chiller Information Nameplate . . . . . . . . . . . . . . . . . . . . . . 4
System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Motor-Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Economizer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Free-Standing Starter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MOTOR AND OIL COOLING CYCLE. . . . . . . . . . . . . . . . . 8
LUBRICATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,9
Summary
Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Oil Reclaim System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• PRIMARY OIL RECOVERY MODE
• SECONDARY OIL RECOVERY METHOD
STARTING EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Solid-State Starter (Optional) . . . . . . . . . . . . . . . . . . . . . 10
Freestanding Medium Voltage VFD (Optional) . . . . . 10
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• ANALOG SIGNAL
• DISCRETE SIGNAL
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PIC 5 System Components . . . . . . . . . . . . . . . . . . . . 10,11
START-UP/SHUTDOWN/RECYCLE
SEQUENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
Local Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Lubrication Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . . . . . .13-28
Job Data Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Equipment Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Remove Shipping Packaging . . . . . . . . . . . . . . . . . . . . . . 13
Open Oil Circuit Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Tighten All Gasketed Joints . . . . . . . . . . . . . . . . . . . . . . . 13
Check Chiller Tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Tracer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Leak Test Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Standing Vacuum Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chiller Dehydration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspect Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Check Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Check Starter
• MECHANICAL STARTER
• SOLID-STATE STARTER
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Power Up the Controls and
Check the Oil Heater
Software Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Input the Design Set Points. . . . . . . . . . . . . . . . . . . . . . . 20
Input the Local Occupied Schedule. . . . . . . . . . . . . . . . 20
Input Service Configurations
•PASSWORD
• LOGIN/LOGOUT
• INPUT TIME AND DATE
• MODIFY CONTROLLER IDENTIFICATION
IF NECESSARY
• CONFIGURE SERVICE TABLES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . 20
2
CONTENTS (cont)
Page
Field Set Up and Verification . . . . . . . . . . . . . . . . . . . . . . .22
• LABEL LOCATIONS
• STARTER/DRIVE PROTECTION AND OTHER INCOMING WIRING
• FINE TUNING VPF (VARIABLE PRIMARY FLOW) SURGE PREVENTION
• MODIFY EQUIPMENT CONFIGURATION IF NECESSARY
Perform a Control Test (Quick Test) . . . . . . . . . . . . . . . .24
Charge Refrigerant Into Chiller
• CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT
• CHILLER EQUALIZATION WITH FREE-STANDING PUMPOUT UNIT
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29,30
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Check Motor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Check Oil Pressure and Compressor Stop . . . . . . . . .29
To Prevent Accidental Start-Up. . . . . . . . . . . . . . . . . . . . .29
Check Chiller Operating Condition . . . . . . . . . . . . . . . . .29
Instruct the Customer Operator . . . . . . . . . . . . . . . . . . . .29
• COOLER-CONDENSER
• OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM
• MOTOR COMPRESSOR ASSEMBLY
• MOTOR COMPRESSOR LUBRICATION SYSTEM
• ECONOMIZER
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• DESCRIBE CHILLER CYCLES
• REVIEW MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• REVIEW THE START-UP, OPERATION, AND MAINTENANCE MANUAL
OPERATING INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . 30,31
Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Prepare the Chiller for Start-Up. . . . . . . . . . . . . . . . . . . . .30
To Start the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Check the Running System. . . . . . . . . . . . . . . . . . . . . . . . .30
To Stop the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
After Limited Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Preparation for Extended Shutdown. . . . . . . . . . . . . . . .30
After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . .30
Cold Weather Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Manual Guide Vane Operation. . . . . . . . . . . . . . . . . . . . . .31
Refrigeration Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-36
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Operating the Optional Pumpout Unit . . . . . . . . . . . . . .33
• TO READ REFRIGERANT PRESSURES
• POSITIVE PRESSURE CHILLERS WITH STORAGE
TANKS
• CHILLERS WITH ISOLATION VALVES
• DISTILLING THE REFRIGERANT
GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . .36-38
Refrigerant Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Adjusting the Refrigerant Charge. . . . . . . . . . . . . . . . . . .36
Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
. . . . . . . . . . . . . . . . . . . 25
Page
Test After Service, Repair, or Major Leak. . . . . . . . . . .36
• TESTING WITH REFRIGERANT TRACER
• TESTING WITHOUT REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test. . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Checking Guide Vanes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Trim Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . .38
WEEKLY MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . .38
Check the Lubrication System . . . . . . . . . . . . . . . . . . . . .38
SCHEDULED MAINTENANCE . . . . . . . . . . . . . . . . . . . 38-41
Service Ontime. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Inspect the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . .38
Changing Oil Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
• TO CHANGE THE OIL
Refrigerant Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Reclaim Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Inspect Refrigerant Float System. . . . . . . . . . . . . . . . . . . 39
• ECONOMIZER FLOAT SYSTEM
• ECONOMIZER DAMPER VALVE
Inspect Relief Valves and Piping . . . . . . . . . . . . . . . . . . .40
Compressor Bearing and Gear
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Inspect the Heat Exchanger Tubes
and Flow Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
• COOLER AND OPTIONAL FLOW DEVICES
• CONDENSER AND OPTIONAL FLOW DEVICES
Water Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Inspect the Starting Equipment . . . . . . . . . . . . . . . . . . . .41
Recalibrate Pressure Transducers . . . . . . . . . . . . . . . . . 41
Optional Pumpout System Maintenance. . . . . . . . . . . .41
• OPTIONAL PUMPOUT COMPRESSOR OIL
CHARGE
• OPTIONAL PUMPOUT SAFETY CONTROL
SETTINGS
Ordering Replacement Chiller Parts. . . . . . . . . . . . . . . . 41
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . 42-87
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Checking Display Messages . . . . . . . . . . . . . . . . . . . . . . . 42
Checking Temperature Sensors. . . . . . . . . . . . . . . . . . . . 42
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers . . . . . . . . . . . . . . . . . . .46
• TRANSDUCER REPLACEMENT
• COOLER AND CONDENSER PRESSURE
TRANSDUCER CALIBRATION
• OPTIONAL THERMAL DISPERSION FLOW
SWITCH CALIBRATION
• HYDRAULIC STATUS
High Altitude Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Quick Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pumpdown/Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
APPENDIX A — PIC 5 SCREEN AND
MENU STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . .. .88-91
APPENDIX B — CCN COMMUNICATION WIRING
FOR MULTIPLE CHILLERS (TYPICAL) . . . . . . . . . . .92
APPENDIX C — MAINTENANCE SUMMARY
AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93-95
INDEX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
INITIAL START-UP CHECKLIST FOR
19XR SEMI-HERMETIC TWO-STAGE
CENTRIFUGAL LIQUID CHILLER. . . . . . .CL-1 to CL- 10
3

INTRODUCTION

Prior to initial start-up of the 19XR unit, those involved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. Procedures in this manual are arranged in the sequence re­quired for proper chiller start-up and operation. This book also outlines the control system for those involved in the start-up, operation and maintenance of the unit before performing start­up procedures. It is intended to be used in combination with the 19XR Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers Controls Operation and Troubleshooting man­ual that describes PIC 5 controls in detail.
CAUTION
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio com­munications. The PIC 5 control boards have been tested and found to comply with the limits for a Class A comput­ing device pursuant to International Standard in North America EN 61000-2/3 which are designed to provide rea­sonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interfer­ence.
Always store and transport replacement or defective boards in anti-static shipping bag.
CAUTION
Do NOT punch holes or drill into the top surface of the starter enclosure for field wiring. Knockouts are provided for field wiring connections.
CAUTION
PROVIDE MACHINE PROTECTION. Store machine and starter indoors, protected from construction dirt and moisture. Inspect under shipping tarps, bags or crates to be sure water has not collected during transit. Keep protective shipping covers in place until machine is ready for installation.
CAUTION
WHEN FLUSHING THE WATER SYSTEMS isolate the chiller from the water circuits to prevent damage to the heat exchanger tubes.

ABBREVIATIONS AND EXPLANATIONS

Frequently used abbreviations in this manual include:
CCN Carrier Comfort Network ECDW — Entering Condenser Water ECW Entering Chilled Water EMS Energy Management System HGBP Hot Gas Bypass HMI Human Machine Interface I/O Input/Output ISM Integrated Starter Module LCDW — Leaving Condenser Water LCW Leaving Chilled Water LED Light-Emitting Diode OLTA Overload Trip Amps PIC 5 Product Integrated Controls 5 RLA Rated Load Amps SCR Silicon Controlled Rectifier TXV Thermostatic Expansion Valve VFD Variable Frequency Drive
Factory-installed additional components are referred to as options in this manual; factory-supplied but field-installed ad­ditional components are referred to as accessories.
®
CHILLER FAMILIARIZATION (Fig. 1 and 2) Chiller Information Nameplate —
nameplate is located on the right side of the chiller control panel.
The information
System Components — The components include the
cooler and condenser heat exchangers in separate vessels, motor-compressor, lubrication package, control panel, econo­mizer, and motor starter. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is lo-
cated underneath the compressor. The cooler is maintained at lower temperature/pressure so evaporating refrigerant can re­move heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher tem-
perature/pressure than the cooler and has water flowing through its internal tubes in order to remove heat from the re­frigerant.
Motor-Compressor — This component maintains sys-
tem temperature and pressure differences and moves the heat­carrying refrigerant from the cooler to the condenser. The 19XR two-stage frame 6 and frame 7 compressors are two­stage compressors with two impellers.
Control Panel — The control panel is the user interface
for controlling the chiller. It regulates the chiller’s capacity as required to maintain proper leaving chilled water temperature. The control panel:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating condition and alarm shutdown
conditions
• records the total chiller operating hours
• sequences chiller start, stop, and recycle under micropro-
cessor control
• displays status of motor starter
• provides access to other CCN (Carrier Comfort Net-
• supports languages that may be pre-installed at factory,
®
work
) devices and energy management systems
including English, Chinese, Spanish, French, and
German.
4
Economizer — This chamber reduces the refrigerant pres-
636
Motor Size Code
Compressor Frame Size 6
G (2250 HP, copper rotor) H (2375 HP, copper rotor) J (2500 HP, copper rotor) K (2625 HP, copper rotor) L (2750 HP, copper rotor) N — 1500 HP P — 1625 HP Q — 1750 HP R — 1875 HP S — 2000 HP T — 2100 HP
Compressor Frame Size 7
U — 2250 HP V — 2375 HP W — 2500 HP
X — 2625 HP Y — 2750 HP Z — 2900 HP
Motor V oltage Code Code Volts-Phase-Hertz
Special Order Indicator – — Standard S — Special Order
M
N7
Gear Code
Compressor Frame Size 6
E J M P
Compressor Frame Size 7
R T V X Y
Compressor Size Code
Frame Size (12th Digit)
6 — Frame Size 6 7 — Frame Size 7
Centrifugal Liquid Chiller
Description 19XR– — High Efficiency Semi-Hermetic
19XR
A45
A47
Cooler Size Code (Digits 6, 7, 8)
A40-A42 A45-A47 A4A-A4C* A4F-A4H* A60-A62 A65-A67 A6A-A6C* A6F-A6H* B60-B62 B65-B67 B80-B82** B85-B-87** B6A-B6C* B6F-B6H* B8A-B8C** B8F-B8H C60-C62 C65-C67 C6A-C6C* C6F-C6H*
Condenser Size Code (Digits 9, 10, 11)
A40-A42 A45-A47 A4A-A4C* A4F-A4H* A60-A62 A65-A67 A6A-A6C* A6F-A6H* B40-B42 B45-B47 B4A-B4C* B4F-B4H* B60-B62 B65-B67 B6A-B6C* B6F-B6H* C60-C62 C65-C67 C80-C82 ** C85-C87** C6A-C6C* C6F-C6H* C8A-C8C** CF-C8H D60-D62 D65-D67 D6A-D6C* D6F-D6H*
Shroud Size (13th Digit)
1 2 3 4 (Frame Size 6 Only)
Impeller Diameter (14th Digit)
2 4 6 8 0
3000-3-50 3300-3-50
6300-3-50 10000-3-50 11000-3-50
2400-3-60
3300-3-60
4160-3-60
6900-3-60 11000-3-60 13800-3-60
— — — — — — — — — — —
4 5 6 7
8 E F
G H
J
K
Fig. 1 — 19XR Two-Stage Chiller Model Number Nomenclature
*Frame sizes with A-C and F-H are with 1-in. OD evaporator tubing.
sure to an intermediate level between the cooler and condenser vessels. In the economizer, vapor is separated from the liquid, the separated vapor flows to the second stage of the compres­sor, and the liquid flows into the cooler. The energy removed from the vaporized refrigerant in the economizer allows the
liquid refrigerant in the cooler to absorb more heat when it evaporates and benefits the overall cooling efficiency cycle.
Free-Standing Starter — The starter allows for the
proper start and disconnect of electrical energy for the com­pressor-motor, oil pump, oil heater, and control panel.
Week of Year
Year of Manufacture
SERIAL NUMBER STRUCTURE
5
12 15 Q 19843
Unique Number
Place of Manufacture
a19-2271
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Fig. 2 — Typical 19XR 1500-3000 Ton Two-Stage Compressor Chiller Compone nts
(XR6 Shown)
REAR VIEW
FRONT VIEW
LEGEND
1—Guide Vane Actuator 2—Suction Elbow 3—Chiller Identification Nameplate 4—Control Panel 5—Condenser Auto. Reset Relief Valves 6—Condenser Return End Waterbox Cover 7—Cooler Return End Waterbox Cover 8—Cooler Auto. Reset Relief Valves
9—Cooler Pressure Transducer 10 — Liquid Line Isolation Valve (Optional) 11 — Refrigerant Storage Tank Connection Valve 12 — HMI (Human Machine Interface) Control Panel 13 — Typical Flange Connection 14 — Oil Level Sight Glasses 15 — Compressor Motor Housing
LEGEND
16 — Oil Cooler
17 — Oil Drain Changing Valve (Hidden)
18 — Motor Sight Glass
19 — Cooler In/Out Temperature Thermistors
20 — Typical Waterbox Drain Port
21 — Vessel Take-Apart Connector
22 — Condenser In/Out Temperature Thermistors
23 — ASME Nameplate
24 — Refrigerant Moisture/Flow Indicator
25 — Refrigerant Filter/Drier
26 — High Side Float Chamber
27 — High Side Float Ball Valve Assembly (Inside)
28 — Economizer Assembly 29 — Economizer Float Ball Assembly (Inside) 30 — Cooler Auto. Reset Relief Valve 31 — Condenser Pressure Transducer 32 — Refrigerant Charging Valve/Pumpout
Connection
33 — Damper Valve 34 — Discharge Isolation Valve (Optional)
6

REFRIGERATION CYCLE

Fig. 3 — Refrigeration Cycle — 19XR Two-Stage Compressor Frame Sizes 6 and 7
The compressor continuously draws refrigerant vapor from the cooler at a rate set by the amount of guide vane opening. As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low temperature (typical­ly 38 to 42 F [3 to 6 C]). The energy required for boiling is ob­tained from the water flowing through the cooler tubes. With heat energy removed, the water becomes cold enough to use in an air-conditioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90 F [18 to 32 C]) water flowing into the condenser tubes removes heat from the refrig­erant, and the vapor condenses to liquid. The liquid refrigerant passes through orifices into the FLASC (flash subcooler) chamber. Since the FLASC chamber is at a lower pressure, part of the liquid refrigerant flashes to vapor, thereby cooling the re­maining liquid. The FLASC vapor is recondensed on the tubes which are cooled by entering condenser water. The liquid
ISOLATION VALVE (OPTION)
drains into a high side float valve chamber between the FLASC chamber and the economizer. The refrigerant is then metered into the economizer. In the economizer, due to lower pressure, as liquid enters the chamber, some liquid will flash into a vapor and cool the remaining liquid. The separated vapor flows to the second stage of the compressor for greater cycle efficiency. A damper valve located on the economizer line to the compressor acts as a pressure regulating device to stabilize low load, low condensing pressure operating conditions. The damper will back up gas flow and thereby raises the economizer pressure to permit proper refrigerant flow through the economizer valve during those conditions.
The cooled liquid left in the economizer flows through a low side float valve and then into the cooler. The float valve forms a liquid seal to keep vapor from entering the cooler. Liq­uid refrigerant passes through the low side valve into the cool­er. The refrigerant is now at a temperature and pressure at which the cycle began. Fig. 3 summarizes the refrigeration cycle.
FLASC CHAMBER
THERMOSTATIC EXPANSION VALVE (TXV)
ROTOR
ORIFICE FITTING
OIL COOLER
TRANSMISSION
IMPELLERS
BACK PRESSURE ORIFICE (INTEGRAL TO MOTOR SHELL)
COMPRESSOR
HIGH SIDE FLOAT CHAMBER
HIGH SIDE FLOAT VALVE
DAMPER VALVE
REFRIGERANT
ISOLATION VALVE
ECONOMIZER
LOW SIDE FLOAT VALVE
HOT GAS BYPASS
HGBP VALVE
CONDENSER WATER
REFRIGERANT LIQUID
REFRIGERANT VAPOR
REFRIGERANT LIQUID/VAPOR
CHILLED WATER
COOLER ISOLATION VALVE (OPTION)
7

MOTOR AND OIL COOLING CYCLE

The motor and the lubricating oil are cooled by liquid refriger­ant taken from the bottom of the condenser vessel (Fig. 3 and
4). Refrigerant flow is maintained by the pressure differential that exists due to compressor operation. After the refrigerant flows past an isolation valve, an in-line filter, and a sight glass/ moisture indicator, the flow is split between the motor cooling and oil cooling systems.
Flow to the motor cooling system passes through an orifice and into the motor. Once past the orifice, the refrigerant is di­rected over the motor by spray nozzles. The refrigerant collects in the bottom of the motor casing and is then drained back into the cooler through the motor refrigerant drain line. An orifice (in the motor shell) maintains a higher pressure in the motor shell than in the cooler. The motor is protected by a tempera­ture sensor embedded in the stator windings. An increase in motor winding temperature past the motor override set point overrides the temperature capacity control to hold, and if the motor temperature rises 10 F (5.5 C) above this set point, the controls close the inlet guide vanes. If the temperature rises above the safety limit, the compressor shuts down.
Refrigerant that flows to the oil cooling system is regulated by expansion valves. The expansion valves regulate flow into the oil/refrigerant plate and frame-type heat exchanger (the oil cooler in Fig. 3), and control oil temperature to the bearings. The refrigerant leaving the oil cooler heat exchanger returns to the chiller cooler.

LUBRICATION CYCLE

Summary —
up a package located partially in the transmission casing of the compressor-motor assembly. The oil is pumped into a filter assembly to remove foreign particles and is then forced into an oil cooler heat exchanger where the oil is cooled to proper op­erational temperatures. After the oil cooler, part of the flow is directed to the gears and the high speed shaft bearings; the re­maining flow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to complete the cycle (Fig. 3 and
4).
The oil pump, oil filter, and oil cooler make
Details — Oil is charged into the lubrication system through
a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump tem­perature is displayed on the HMI default screen. During com­pressor operation, the oil sump temperature ranges between 125 and 150 F (52 and 66 C).
The oil pump suction is fed from the oil reservoir. An oil pressure relief valve maintains differential pressure in the sys­tem at the pump discharge. A range of 18 to 40 psid (124 to 172 kPad) is normal. This differential pressure can be read di­rectly from the default HMI screen. The oil pump discharges oil to the oil filter assembly. This filter can be closed to permit removal of the filter without draining the entire oil system. The oil is then piped to the oil cooler heat exchanger. The oil cooler uses refrigerant from the condenser as the coolant. The refrig­erant cools the oil to a temperature between 120 and 140 F (49 and 60 C).
As the oil leaves the oil cooler, it passes the oil pressure transducer and the sensor for the refrigerant expansion valve on the oil cooler. The oil is then divided. Part of the oil flows to the thrust bearing, forward pinion bearing, and gear spray. The rest of the oil lubricates the motor shaft bearings and the rear pinion bearing. The oil temperature is measured in the bearing hous­ing as it leaves the bearings. The oil then drains into the oil res­ervoir at the base of the compressor. The control measures the temperature of the oil in the sump and maintains the tempera­ture during shutdown. This temperature is read on the HMI de­fault screen. See the Controls Operation and Troubleshooting Manual for details.
During the chiller start-up, the oil pump is energized and provides 40 seconds of lubrication to the bearings after pres­sure is verified before starting the compressor. During shut­down, the oil pump runs for 60 seconds to ensure lubrication as the compressor coasts to a stop.
The oil pump is a gerotor-style pump with external filters. A gerotor pump has two rotors, one is inside the other; their center points are offset with respect to each other. This type of pump provides a smooth continuous flow. It is also quieter than other designs. See Fig. 5.
Bearings — The 19XR compressor assemblies include a
combination of radial bearings and thrust bearings. The low speed shaft assembly is supported by two journal bearings lo­cated on each end of the low speed shaft. The bearing closer to the bull gear includes a smaller babbitted thrust face, designed to handle axial forces.
Oil Reclaim System — The oil reclaim system returns
oil lost from the compressor housing back to the oil reservoir by recovering the oil from 2 areas on the chiller. The guide vane housing is the primary area of recovery. Oil is also recov­ered by skimming it from the operating refrigerant level in the cooler vessel.
PRIMARY OIL RECOVERY MODE — Oil is normally re­covered through the guide vane housing on the chiller. This is possible because oil is normally entrained with refrigerant in the chiller. As the compressor pulls the refrigerant up from the cooler into the guide vane housing to be compressed, the oil normally drops out at this point and falls to the bottom of the guide vane housing where it accumulates. Using discharge gas pressure to power an eductor, the oil is drawn from the housing and is discharged into the oil reservoir.
SECONDARY OIL RECOVERY METHOD — The sec­ondary method of oil recovery is significant under light load conditions, when the refrigerant going up to the compressor suction does not have enough velocity to bring oil along. Under these conditions, oil collects in a greater concentration at the top level of the refrigerant in the cooler. Using discharge gas to power eductors, this oil and refrigerant mixture is skimmed from the side of the cooler and is then drawn up to the guide vane housing. There is a filter in this line. Because the guide vane housing pressure is much lower than the cooler pressure, the refrigerant boils off, leaving the oil behind to be collected by the primary oil recovery method.
8
10
Fig. 4 — 19XR Two-Stage Compressor Lubrication System
LEGEND
1—Motor Stator 6— Oil Heater 2—Impellers 7— Oil Pump 3—Variable Inlet Guide Vanes 8— Oil Filters 4—Transmission 9— Motor Rotor 5—High Speed Shaft Bearings 10— Motor Shaft Bearings
a19-
1
2
3
4
5
6
7
8
Fig. 5 — Gerotor Oil Pump
a19-2116
LEGEND
1—Gerotor Oil Pump 2—Oil Pressure Regulator Valve 3—Oil Sump Pressure Transducer 4—Oil Sump Drain Valve 5—High Speed Compressor End Bearing,
Temperature Terminal Block
6—Low Speed Compressor End Bearing,
Temperature Cable
7—Compressor Oil Sump Temperature 8—Oil Heater
9
OIL LINE VENT LINE
1
2
3
4
5
6
7
8
9

STARTING EQUIPMENT

The 19XR chiller requires a motor starter to operate the cen­trifugal hermetic compressor motor, the oil pump, and various auxiliary equipment components. The starter is the main field wiring interface for the contractor.
See Carrier’s specification for specific starter requirements. All starters must meet these specifications in order to properly start and satisfy mechanical safety requirements.
It is possible that there are two separate circuit breakers in­side the starter. These include (1) the main compressor motor circuit breaker, and (2) a circuit breaker which provides power to the chiller control panel. The latter is typically wired in par­allel with the first so that power is provided to those services when the main breaker is open. The disconnect switch on the starter front cover is connected to the main breaker. Typically, separate 3-phase power sources as per job requirements are supplied to the control panel to power the oil pump, heater, and controls.
The display on the front of the solid-state starter is useful for
troubleshooting and starter checkout. The display indicates:
• line voltage
• control voltage status
• power indication
• proper phasing for rotation
• start circuit energized
• ground fault
• current unbalance
•run state The starter is further explained in the Check Starter section,
page 19.
Freestanding Medium Voltage VFD (Optional) —
can be combined with a VFD (variable frequency drive). This option is a freestanding, medium voltage current source drive that does not require a transformer between the power source and the drive. The drive meets IEEE-519 specifications.
For optimum efficiency, the 19XR chiller
WARNING
The main circuit breaker on the front of the starter discon­nects the main motor power only. Power may be still ener­gized for other circuits. Always check wiring diagrams before initiating any work on the chiller and follow appli­cable lock-out/tag-out procedures. Failure to disconnect power will result in personal injury.
All starters must include a Carrier control module called the Integrated Starter Module (ISM). This module controls and monitors all aspects of the starter. See the Controls Operation and Troubleshooting guide for additional ISM information. Contact Carrier’s Replacement Component Division (RCD) for replacement parts.
Solid-State Starter (Optional) — The 19XR chiller
may be equipped with a solid-state, reduced-voltage starter. This starter’s primary function is to provide on-off control of the compressor motor. This type of starter reduces the peak starting torque, controls the motor inrush current, and decreases mechanical shock. This capability is summed up by the phrase “soft starting.” Consult E-Cat for full information about starter offerings. The solid-state starter manufacturer’s name is locat­ed inside the starter access door.
A solid-state, reduced-voltage starter operates by reducing the starting voltage. The starting torque of a motor at full volt­age is typically 125% to 175% of the running torque. When the voltage and the current are reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting voltage to adjust the voltage necessary to develop the torque re­quired to get the motor moving. The voltage is reduced by sili­con controlled rectifiers (SCRs). The voltage and current are then ramped up in a desired period of time. Once full voltage is reached, a bypass contactor is energized to bypass the SCRs.
WARNING
When voltage is supplied to the solid-state circuitry (CB1 is closed), the heat sinks in the starter as well as the wires leading to the motor and the motor terminal are at line volt­age. Do not touch the heat sinks, power wiring, or motor terminals while voltage is present or serious injury will result.

CONTROLS

Definitions

ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an analog device be­cause its resistance changes in proportion to the temperature, generating many values.)
DISCRETE SIGNAL — A discrete signal is a 2-position rep­resentation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.)
General — The 19XR centrifugal liquid chiller contains a
microprocessor-based control center that monitors and controls all operations of the chiller. The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and reg­ulating the inlet guide vane via a mechanically linked actuator motor. The guide vane is a variable flow pre-whirl assembly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor. An increase in guide vane opening increases capacity. A decrease in guide vane opening decreases capacity. The microprocessor­based control center protects the chiller by monitoring the digi­tal and analog inputs and executing capacity overrides or safety shutdowns, if required.
PIC 5 System Components — The chiller control
system is called the PIC 5 (Product Integrated Control 5). See Table 1. As with previous PIC versions, the PIC 5 system con­trols the operation of the chiller by monitoring all operating conditions. The PIC 5 control system can diagnose a problem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to maintain leav­ing chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off and regulates the hot gas bypass valve, if installed. The PIC 5 controls provide critical protec­tion for the compressor motor and control the motor starter.
10
Table 1 — Major PIC 5 Components and
Fig. 6 — Chiller Start/Stop Icon
Fig. 7 — Local On
a19-2118
Panel Locations
PIC 5 COMPONENT PANEL LOCATION
Chiller Human Machine Interface (HMI) and Display
Integrated Starter Module (ISM) Starter Cabinet Chiller IO Boards Control Panel Oil Heater Contactor (1C) Control Panel Oil Pump Contactor (2C) Control Panel Hot Gas Bypass Relays (HCLR, HOPR)
(Optional) Control Transformers (T1, T2, T3) Control Panel Temperature Sensors See Fig. 2 and Fig. 5 Pressure Transducers See Fig. 2 and Fig. 5
HMI Control Panel
Control Panel
NOTE: For detailed information about the PIC 5 HMI (human machine interface), see the 19XR with PIC 5 Controls Opera­tion and Troubleshooting manual.
START-UP/SHUTDOWN/
RECYCLE SEQUENCE
Local Start/Stop Control —
start-up) is initiated by pressing the the gray Start/Stop icon on the HMI interface. See Fig. 6.
This initiates the PIC 5 starting sequence by displaying the list of operating modes. Press Local On to initiate start-up. See Fig. 7.
Local start-up (or manual
When start-up is initiated the status screen displays the start-
up progress and the Start/Stop icon blinks green.
Once local start-up begins, the PIC 5 control system per­forms a series of pre-start tests to verify that all pre-start alerts and safeties are within acceptable limits. Table 2 shows appro­priate Prestart Alerts/Alarms conditions. If a test is not success­ful, the start-up is delayed or aborted. If the tests are successful, the start-up will be in progress and the COMPRESSOR RUN STATUS shall be “Startup.” The control shall then energize the chilled water/brine pump relay.
Five seconds later, the condenser pump relay energizes. Thirty seconds later the PIC 5 control system monitors the chilled water and condenser water flow devices and waits until the WATER FLOW VERIFY TIME (operator-configured, de­fault 5 minutes) expires to confirm flow. After flow is verified, the chilled water temperature is compared to CONTROL POINT plus 1/2 CHILLED WATER DEADBAND. If the tem­perature is less than or equal to this value, the PIC 5 control system turns off the condenser pump relay and goes into a Re­cycle mode.
If the water/brine temperature is high enough, the start-up sequence continues and checks the guide vane position. If the guide vanes are more than 4% open, the start-up waits until the PIC 5 control system closes the vanes. If the vanes are closed and the oil pump pressure is less than 4 psi (27.6 kPa), the oil pump relay energizes. The PIC 5 control system then waits un­til the oil pressure (OIL PRESS VERIFY TIME, operator-con­figured, default of 40 seconds) reaches a maximum of 18 psi (124 kPa). After oil pressure is verified, the PIC control system waits 40 seconds, and the compressor start relay (1CR) ener­gizes to start the compressor.
Compressor ontime and service ontime timers start, and the compressor STARTS IN 12 HOURS counter and the number of starts over a 12-hour period counter advance by one.
Failure to verify any of the requirements up to this point will result in the PIC 5 control system aborting the start and display­ing the applicable pre-start alert alarm state number near the bottom of the home screen on the HMI panel. A prestart failure does not advance the STARTS IN 12 HOURS counter. Any fail- ure after the 1CR relay has energized results in a safety shut­down, advances the starts in 12 hours counter by one, and dis­plays the applicable shutdown status on the display.
The minimum time to complete the entire prestart sequence is approximately 185 seconds. See Fig. 8 for normal start-up timing sequence. See Table 2 for a list of prestart checks.
Unit Start/Stop
NOTE: Prior to start-up the start-to-start timer and the stop-to­start timer must have elapsed and all alarms must be cleared (see Troubleshooting Guide section on page 42).
11
Table 2 — Prestart Checks
AB
CDE
F
G
O/A
A—START INITIATED: Pre-start checks are made; evaporator pump
started.*
B—Condenser water pump started (5 seconds after A). C—Water flows verified (30 seconds to 5 minutes maximum after B).
Chilled water temperatures checked against control point. Guide vanes checked for closure. Oil pump started; tower fan control enabled.
D—Oil pressure verified (15 seconds minimum, 300 seconds maximum
after C).
E—Compressor motor starts; compressor ontime and service ontime
start, 15-minute inhibit timer starts (10 seconds after D), total com­pressor starts advances by one, and the number of starts over a 12-hour period advances by one.
F—SHUTDOWN INITIATED — Compressor motor stops; compressor
ontime and service ontime stop, and 1-minute inhibit timer starts.
G—Oil pump and evaporator pumps deenergized (60 seconds after F).
Condenser pump and tower fan control may continue to operate if condenser pressure is high. Evaporator pump may continue if in RECYCLE mode.
O/A — Restart permitted (both inhibit timers expired: minimum of 15 min-
utes after E; minimum of 1 minute after F).
Fig. 8 — Control Timing Sequence
for Normal Start-Up
* Auto Restart After Power Failure Timing sequence will be faster.
Fig. 9 — Confirm Stop
a19-2122
Unit Start/Stop
PRESTART CHECK CONDITION* STATE NUMBER
STARTS IN 12 HOURS 8 (not counting recycle restarts or auto restarts after power failure) Alert – 100 OIL SUMP TEMP 140° F (60° C) and OIL SUMP TEMP EVAP_SAT + 50° F (27.8° C) Alert – 101 COND PRESSURE COND PRESS OVERRIDE – 20 psi Alert – 102 #RECYCLE RESTARTS LAST 4 HOURS > 5 Alert – 103 COMP BEARING TEMPS COMP BEARING ALERT– 10° F (5.6° C) Alarm – 230 COMP MOTOR WINDING TEMP COMP MOTOR WINDING– 10° F (5.6° C) Alarm – 231 COMP DISCHARGE TEMPERATURE COMP DISCHARGE ALERT– 10° F (5.6° C) Alarm – 232 EVAP_SAT <Evap trip point** + EVAP OVERRIDE DELTA T Alarm – 233 EVAP REFRIG LIQUID TEMP <Evap trip point** + EVAP OVERRIDE DELTA T Alarm – 233 AVERAGE LINE VOLTAGE UNDERVOLTAGE THRESHOLD Alarm – 234 AVERAGE LINE VOLTAGE OVERVOLTAGE THRESHOLD Alarm – 235 CHECK FOR GUIDE VANE CALIBRATION Alarm – 236
* If Prestart Check Condition is True, then resulting State is as indicated in the State Number column.
See the Controls Operation and Troubleshooting guide for alarm and alert codes.
**Evap trip point = 33 F (0.6 C) (water) or EVAP REFRIG TRIPPOINT (brine)
The oil heater relay is energized whenever the chiller com­pressor is off and the oil sump temperature is less than 140 F (60 C) or the oil sump temperature is less than the evaporator saturated refrigerant temperature plus 53° F (29.4° C). The oil heater is turned off when either of the following conditions is true:
• Oil sump temperature is more than 152 F (66.7 C)
• Oil sump temperature is more than 144 F (62.2 C) and
more than the evaporator saturated refrigerant tempera-
ture plus 55° F (30.6° C) The oil heater is always off when the compressor is running.
The oil pump is also energized for 30 seconds after each 30 minutes of oil heat relay being energized in order to stir the oil for more evenly distributed heating.
Shutdown — The unit can be stopped locally using the
HMI by pressing the green Start/Stop icon . The Unit Start/ Stop screen is displayed. Press Confirm Stop (see Fig. 9).
Lubrication Control — As part of the prestart checks
executed by the controls, the oil sump temperature is compared to the evaporator saturated refrigerant temperature. If the oil temperature is less than 140 F (60 C) and less than evaporator saturated refrigerant temperature plus 50° F (27.8° C), the start-up will be delayed until either of these conditions is no longer true. Once this temperature is confirmed, the start-up continues.
12

BEFORE INITIAL START-UP

Fig. 10 — Typical Wet-Bulb Type
Vacuum Indicator

Job Data Required

• list of applicable design temperatures and pressures (product data submittal)
• chiller certified prints
• starting equipment details and wiring diagrams
• diagrams and instructions for special controls or options
• 19XR Installation Instructions

Equipment Required

• mechanic’s tools (refrigeration)
• digital volt-ohmmeter (DVM)
• true RMS (root mean square) digital multimeter with clamp-on current probe or true RMS digital clamp-on ammeter for at least 480 vac
• electronic leak detector
• absolute pressure manometer or wet-bulb vacuum indicator (see Fig. 10)
• insulation tester for compressor motor rated at motor design voltage
Remove Shipping Packaging — Remove any pack-
aging material from the unit and starter.
Open Oil Circuit Valves — Check to ensure the oil fil-
ter isolation valves are open by removing the valve cap and checking the valve stem.
Tighten All Gasketed Joints — Gaskets normally
relax by the time the chiller arrives at the jobsite. Tighten all gasketed joints to ensure a leak-tight chiller (does not apply to refrigerant joints covered by factory insulation). Gasketed joints (excluding O-rings) may include joints at some or all of the following:
• waterbox covers
• compressor suction elbow flanges (at compressor and at the cooler)
• compressor discharge flange
• compressor discharge line spacer (both sides) if no isolation valve
• cooler inlet line spacer (both sides) if no isolation valve
• hot gas bypass valve (both sides of valve)
• hot gas bypass flange at compressor
See Tables 3 and 4 for bolt torque requirements.
Check Chiller Tightness — Figure 11 outlines the
proper sequence and procedures for leak testing.
The 19XR chillers are shipped with the refrigerant con-
tained in the condenser shell and the oil charge in the compres­sor. The cooler is shipped with a 15 psig (103 kPa) refrigerant charge. Units may be ordered with the refrigerant shipped sepa­rately, along with a 15 psig (103 kPa) nitrogen-holding charge in each vessel.
To determine if there are any leaks, the chiller should be
charged with refrigerant. Use an electronic leak detector to check all flanges and solder joints after the chiller is pressur­ized. If any leaks are detected, follow the leak test procedure (page 16).
If the chiller is spring isolated, keep all springs blocked in
both directions to prevent possible piping stress and damage during the transfer of refrigerant from vessel to vessel during the leak test process, or any time refrigerant is being trans­ferred. Adjust the springs when the refrigerant is in operating condition and the water circuits are full.
13
Table 3 — Bolt Torque Requirements, Foot Pounds
SAE 8
HEX HEAD
SA354 GR BD
BOLT SIZE
(in.)
SAE 2, A307 GR A
HEX HEAD
NO MARKS
LOW CARBON STEEL
SOCKET HEAD OR HEX
WITH 3 RADIAL LINES, OR SA499
MEDIUM CARBON STEEL
SAE 5
WITH 6 RADIAL LINES OR
MEDIUM CARBON STEEL
MINIMUM MAXIMUM MINIMUM MAXIMUM MINIMUM MAXIMUM
1
/
4
5
/
16
3
/
8
7
/
16
1
/
2
9
/
16
5
/
8
3
/
4
7
/
8
46 69913
811 13182028 13 19 22 31 32 46 21 30 35 50 53 75 32 45 53 75 80 115 46 65 75 110 115 165 65 95 105 150 160 225
105 150 175 250 260 370 140 200 265 380 415 590
1 210 300 410 580 625 893
1
/
1
8
1
/
1
4
3
1
/
8
1
/
1
2
5
/
1
8
3
1
/
4
7
/
1
8
330 475 545 780 985 1,410 460 660 770 1,100 1,380 1,960 620 885 1,020 1,460 1,840 2,630
740 1060 1,220 1,750 2,200 3,150 1010 1450 1,670 2,390 3,020 4,310 1320 1890 2,180 3,110 3,930 5,610 1630 2340 2,930 4,190 5,280 7,550
2 1900 2720 3,150 4,500 5,670 8,100
1
/
2
4
1
/
2
2
3
/
2
4
2180 3120 4,550 6,500 8,200 11,710 3070 4380 5,000 7,140 11,350 16,210 5120 7320 8,460 12,090 15,710 22,440
3 6620 9460 11,040 15,770 19,900 28,440
Table 4 — Bolt Torque Requirements, Foot Pounds (Metric Bolts)
BOLT SIZE
(METRIC)
MINIMUM MAXIMUM MINIMUM MAXIMUM
M4 1.75 2.5 2.5 3.5 M6 69812
M8 14 20 20 30 M10 28 40 40 57 M12 48 70 70 100 M16 118 170 170 240 M20 230 330 330 470 M24 400 570 570 810 M27 580 830 820 1175
CLASS 8.8 CLASS 10.9
14
5 AND 6)
5 AND 6)
Fig. 11 — 19XR Leak Test Procedures
a19-1151tf.eps
15
Refrigerant Tracer — Carrier recommends the use of an
environmentally acceptable refrigerant tracer for leak testing with an electronic detector.
Ultrasonic leak detectors can also be used if the chiller is
under pressure.
WARNING
Do not use air or oxygen as a means of pressurizing the chiller. Mixtures of HFC-134a and air can undergo combustion, resulting in equipment damage and possible personal injury.
Leak Test Chiller — Due to regulations regarding refrig-
erant emissions and the difficulties associated with separating contaminants from the refrigerant, Carrier recommends the following leak test procedure. Refer to Tables 5 and 6 for re­frigerant pressure/temperature values.
1. If the pressure readings are normal for the chiller condition:
a. Evacuate the holding charge from the vessels, if
present.
b. Raise the chiller pressure, if necessary, by adding
refrigerant until pressure is at the equivalent satu­rated pressure for the surrounding temperature. Follow pumpout procedures in the Transfer Refrig­erant from Pumpout Storage Tank to Chiller sec­tion, Steps 1a-e, page 34.
CAUTION
Never charge liquid refrigerant into the chiller if the pres­sure in the chiller is less than 35 psig (241 kPa) for HFC­134a. Charge as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN/LOCKOUT (located in the Maintenance menu) and TERMINATE LOCKOUT mode on the PIC 5 control interface. Flashing of liquid refrigerant at low pres­sures can cause tube freeze-up and considerable damage.
c. Leak test chiller as outlined in Steps 3 to 9.
2. If the pressure readings are abnormal for the chiller con­dition:
a. Prepare to leak test chillers shipped with refriger-
ant (Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap test all joints. If the test pressure holds for 30 minutes,
prepare the test for small leaks (Steps 2g and 2h). c. Plainly mark any leaks that are found. d. Release the pressure in the system. e. Repair all leaks. f. Retest the joints that were repaired. g. After successfully completing the test for large
leaks, remove as much nitrogen, air, and moisture
as possible, given the fact that small leaks may be
present in the system. This can be accomplished by
following the dehydration procedure outlined in
the Chiller Dehydration section, page 18. h. Slowly raise the system pressure to a maximum of
160 psig (1103 kPa) but no less than 35 psig
(241 kPa) for HFC-134a by adding refrigerant.
Proceed with the test for small leaks (Steps 3 to 9).
3. Check the chiller carefully with an electronic leak detec­tor or soap bubble solution.
4. Leak Determination — If an electronic leak detector indi­cates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chiller. Leakage at rates greater than 0.1% of the total charge per year must be repaired. Note the total chiller leak rate on the start-up report.
5. If no leak is found during the initial start-up procedures, complete the transfer of refrigerant gas from the storage tank to the chiller. Retest for leaks.
6. If no leak is found after a retest: a. Transfer the refrigerant to the storage tank and per-
form a standing vacuum test as outlined in the Standing Vacuum Test section, below.
b. If the chiller fails the standi ng vacuum test, check
for large leaks (Step 2b).
c. If the chiller passes the standing vacuum test,
dehydrate the chiller. Follow the procedure in the Chiller Dehydration section, page 18. Charge the chiller with refrigerant.
7. If a leak is found after a retest, pump the refrigerant back into the storage tank or, if isolation valves are present, pump the refrigerant into the non-leaking vessel. See the Transfer Refrigerant from Pumpout Storage Tank to Chiller section on page 34.
8. Transfer the refrigerant until the chiller pressure is at 18 in. Hg (40 kPa absolute).
9. Repair the leak and repeat the procedure, beginning from Step 2h, to ensure a leak-tight repair. (If the chiller is opened to the atmosphere for an extended period, evacu­ate it before repeating the leak test.)
Standing Vacuum Test — When performing the
standing vacuum test or chiller dehydration, use a manometer or a wet bulb indicator. Dial gages cannot indicate the small amount of acceptable leakage during a short period of time.
1. Attach an absolute pressure manometer or wet bulb indi­cator to the chiller.
2. Evacuate the vessel to at least 18 in. Hg vac (41 kPa [abs]), using a vacuum pump or the pumpout unit.
3. Valve off the pump to hold the vacuum and record the manometer or indicator reading.
4. a.
5. Repair the leak, retest, and proceed with dehydration.
If the leakage rate is less than 0.05 in. Hg (0.17 kPa) in 24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (0.17 kPa)
24 hours, re-pressurize the vessel and test for leaks if refrigerant is available. If not, use nitrogen and a refrigerant tracer. Raise the vessel pressure in incre­ments until the leak is detected. If refrigerant is used, the maximum gas pressure is approximately 70 psig (483 kPa) for HFC-134a at normal ambient temperature. If nitrogen is used, limit the leak test pressure to 160 psig (1103 kPa) maximum.
in
16
Table 5 — HFC-134a Pressure —
Temperature (F)
Table 6 — HFC-134a Pressure —
Temperature (C)
TEMPERATURE
(F)
0 6.50 2 7.52 4 8.60 6 9.66 8 10.79
10 11.96 12 13.17 14 14.42 16 15.72 18 17.06
20 18.45 22 19.88 24 21.37 26 22.90 28 24.48
30 26.11 32 27.80 34 29.53 36 31.32 38 33.17
40 35.08 42 37.04 44 39.06 46 41.14 48 43.28
50 45.48 52 47.74 54 50.07 56 52.47 58 54.93
60 57.46 62 60.06 64 62.73 66 65.47 68 68.29
70 71.18 72 74.14 74 77.18 76 80.30 78 83.49
80 86.17 82 90.13 84 93.57 86 97.09 88 100.70
90 104.40 92 108.18 94 112.06 96 116.02 98 120.08
100 124.23 102 128.47 104 132.81 106 137.25 108 141.79
110 146.43 112 151.17 114 156.01 116 160.96 118 166.01
120 171.17 122 176.45 124 181.83 126 187.32 128 192.93
130 198.66 132 204.50 134 210.47 136 216.55 138 222.76 140 229.09
PRESSURE
(PSIG)
TEMPERATURE
(C)
–18.0 44.8 –16.7 51.9 –15.6 59.3 –14.4 66.6 –13.3 74.4
–12.2 82.5 –11.1 90.8 –10.0 99.4
–8.9 108.0 –7.8 118.0
–6.7 127.0 –5.6 137.0 –4.4 147.0 –3.3 158.0 –2.2 169.0
–1.1 180.0
0.0 192.0
1.1 204.0
2.2 216.0
3.3 229.0
4.4 242.0
5.0 248.0
5.6 255.0
6.1 261.0
6.7 269.0
7.2 276.0
7.8 284.0
8.3 290.0
8.9 298.0
9.4 305.0
10.0 314.0
11.1 329.0
12.2 345.0
13.3 362.0
14.4 379.0
15.6 396.0
16.7 414.0
17.8 433.0
18.9 451.0
20.0 471.0
21.1 491.0
22.2 511.0
23.3 532.0
24.4 554.0
25.6 576.0
26.7 598.0
27.8 621.0
28.9 645.0
30.0 669.0
31.1 6
32.2 7
33.3 746.0
34.4 773.0
35.6 800.0
36.7 828.0
37.8 857.0
38.9 886.0
40.0 916.0
41.1 946.0
42.2 978.0
43.3 1010.0
44.4 1042.0
45.6 1076.0
46.7 1110.0
47.8 1145.0
48.9 1180.0
50.0 1217.0
51.1 1254.0
52.2 1292.0
53.3 1330.0
54.4 1370.0
55.6 1410.0
56.7 1451.0
57.8 1493.0
58.9 1536.0
60.0 1580.0
PRESSURE
(KPA)
94.0
20.0
17
Chiller Dehydration — Dehydration is recommended if
Fig. 12 — Dehydration Cold Trap
the chiller has been open for a considerable period of time, if the chiller is known to contain moisture, or if there has been a complete loss of chiller holding charge or refrigerant pressure.
CAUTION
Do not start or megohm-test the compressor motor or oil pump motor, even for a rotation check, if the chiller is under dehydration vacuum. Insulation breakdown and severe damage may result.
WARNING
Starters must be disconnected by an isolation switch before placing the machine under a vacuum. To be safe, isolate any starter before evacuating the chiller if you are not sure if there are live leads to the hermetic motor.
Dehydration can be done at room temperatures. Using a cold trap (Fig. 12) may substantially reduce the time required to complete the dehydration. The higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum is required to boil off any moisture. If low ambient temperatures are involved, contact a qualified service representative for the dehydration techniques required.
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm [.002 m or larger is recommended) to the refrigerant charging valve (Fig. 2). Tubing from the pump to the chiller should be as short in length and as large in diameter as possible to provide least resistance to gas flow.
2. Use an absolute pressure manometer or a wet bulb vacu­um indicator to measure the vacuum. Open the shutoff valve to the vacuum indicator only when taking a read­ing. Leave the valve open for 3 minutes to allow the indi­cator vacuum to equalize with the chiller vacuum.
3. If the entire chiller is to be dehydrated, open all isolation valves (if present).
4. With the chiller ambient tem perature at 60 F (15.6 C) or higher, operate the vacuum pump until the manometer reads 185 psig (1275 kPa), or a vacuum indicator reads 35 F (1.7 C). Operate the pump an additional 2 hours.
Do not apply a greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (0.56 C) on the wet bulb vacuum indicator. At this temperature and pressure, iso­lated pockets of moisture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low tempera­tures and pressures greatly increases dehydration time.
5. Valve off the vacuum pump, stop the pump, and record the instrument reading.
6. After a 2-hour wait, take another instrument reading. If the reading has not changed, dehydration is complete. If the reading indicates vacuum loss, repeat Steps 4 and 5.
7. If the reading continues to change after several attempts, perform a leak test up to the maximum 160 psig (1103 kPa) pressure. Locate and repair the leak, and re­peat dehydration.
8. Once dehydration is complete, the evacuation process can continue. The final vacuum prior to charging the unit with refrigerant should in all cases be 29.9 in Hg (500 microns,
0.07 kPa [abs]) or less.
3
/s]
Inspect Water Piping — Refer to piping diagrams pro-
vided in the certified drawings and the piping instructions in the 19XR Installation Instructions manual. Inspect the piping to the cooler and condenser. Be sure that the flow directions are correct and that all piping specifications have been met.
Piping systems must be properly vented with no stress on waterbox nozzles and covers. Water flows through the cooler and condenser must meet job requirements. Measure the pres­sure drop across the cooler and the condenser.
CAUTION
Water must be within design limits, clean, and treated to ensure proper chiller performance and to reduce the poten­tial of tube damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage result­ing from untreated or improperly treated water.
Check Relief Valves — Be sure the relief valves have
been piped to the outdoors in compliance with the latest edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections must allow for access to the valve mechanism for periodic inspection and leak testing.
The standard 19XR relief valves are set to relieve at 185 psig (1275 kPa) chiller design pressure.

Inspect Wiring

WARNING
Do not check the voltage supply without proper equipment and precautions. Serious injury may result. Follow power company recommendations.
CAUTION
Do not apply any kind of test voltage, even for a rotation check, if the chiller is under a dehydration vacuum. Insula­tion breakdown and serious damage may result.
1. Examine the wiring for conformance to the job wiring di­agrams and all applicable electrical codes.
2. Compare the ampere rating on the starter nameplate to rating on the compressor nameplate. The overload trip amps must be 108% to 120% of the rated load amps.
3. The starter for a centrifugal compressor motor must contain the components and terminals required for PIC 5 controls platform. Check the certified drawings.
4. Check the voltage to the components and compare it to the nameplate values.
5. Ensure that fused disconnects or circuit breakers have been supplied for the control panel.
18
6. Ensure all electrical equipment and controls are properly grounded in accordance with job drawings, certified drawings, and all applicable electrical codes.
7. Ensure the customer’s contractor has verified proper op­eration of the pumps, cooling tower fans, and associated auxiliary equipment. This includes ensuring motors are properly lubricated and have proper electrical supply and proper rotation.
8. Test the chiller compressor motor and its power lead insu­lation resistance with an insulation tester such as a meg­ohmmeter. (Use a tester rated for motor voltage.)
a. Open the starter main disconnect switch and follow
lockout/tagout rules.
CAUTION
Ensure the starter (with relay 1CR closed) goes through a complete and proper start cycle.

SOLID-STATE STARTER

WARNING
This equipment is at line voltage when AC power is con­nected. Pressing the STOP button does not remove voltage.
CAUTION
An isolation switch or circuit breaker must be open ahead of any solid-state starter when the chiller is in a vacuum. If not, damage to the machine may result.
If the motor starter is a solid-state starter, the motor leads must be disconnected from the starter before an insulation test is performed. The voltage generated from the tester can damage the starter solid-state components.
b. With the tester connected to the motor leads, take
10-second and 60-second megohm readings as follows:
3-Lead Motor and test between the group and ground.
c. Divide the 60-second resistance reading by the
10-second reading. The ratio, or polarization index, must be one or higher. Both the 10 and 60-second readings must be at least 50 megohms.
If the readings on a field-installed starter are unsat­isfactory, repeat the test at the motor with the power leads disconnected. Satisfactory readings in this second test indicate the fault is in the power leads.
— Tie terminals 1, 2, and 3 together

Check Starter

WARNING
BE AWARE that certain automatic start arrangements can engage the starter. Open the disconnect ahead of the starter
in addition to shutting off the chiller or pump. Failure to follow this procedure may result in personal injury by elec­tric shock.
Use the instruction and service manual supplied by the start­er manufacturer to verify the starter has been installed correct­ly, to set up and calibrate the starter, and for complete trouble­shooting information.
WARNING
The main disconnect on the starter front panel may not deenergize all internal circuits. Open all internal and remote disconnects before servicing the starter. Failure to follow this procedure may result in personal injury by elec­tric shock.

MECHANICAL STARTER

1. Check all field wiring connections for tightness, clear­ance from moving parts, and correct connection.
2. Check the contactor(s) to ensure they move freely. Check all other electro-mechanical devices, such as relays, for free movement. If the devices do not move freely, contact the starter manufacturer for replacement components.
3. Reapply starter control power (not main chiller power) to check the electrical functions.
1. Ensure all wiring connections are properly terminated to the starter.
2. Verify the ground wire to the starter is installed properly and is sufficient size.
3. Verify the motors are properly grounded to the starter.
4. Verify the proper ac input voltage is brought into the start­er according to the certified drawings.
5. Apply power to the starter.
Oil Charge — The oil charge for the 19XR two-stage com-
pressor frame size 6 is 29 gal (110 L); for frame size 7 the oil charge is 44.5 gal (168 L).
The chiller is shipped with oil in the compressor. When the sump is full, the oil level should be no higher than the middle of the upper sight glass, and minimum level is the bottom of the lower sight glass (Fig. 2). If oil is added, it must meet Carri­er’s specification for centrifugal compressor use as described in the Oil Specification section on page 39. Charge the oil through the oil charging valve located near the bottom of the transmission housing. The oil must be pumped from the oil container through the charging valve due to higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down.
Power Up the Controls and Check the Oil Heater —
sor and the chiller is not in a vacuum before energizing the con­trols. Typically a circuit breaker in the starter energizes the oil heater and the control circuit.
The oil heater is energized by powering the control circuit. This should be done several hours before start-up to minimize oil-refrigerant migration. The oil heater is controlled by the PIC 5 and is powered through a contactor in the control panel. A separate circuit breaker powers the heater, oil pump, and the control circuit. This arrangement allows the heater to energize when the main motor circuit breaker is off for service work or extended shutdowns.
Ensure that an oil level is visible in the compres-

Software Configuration

WARNING
Do not operate the chiller before the control configurations have been checked and a Control Test has been satisfacto­rily completed. Protection by safety controls cannot be assumed until all control configurations have been confirmed.
See the 19XR with PIC 5 Controls Operation and Trouble­shooting manual for instructions on using the PIC 5 interface to configure the 19XR unit. As the unit is configured, all configu­ration settings should be written down. A log, such as the one
19
shown on pages CL-1 to CL-8, provides a list for configuration
Fig. 13 — Main Menu Icon
Fig. 14 — Main Menu — Setpoint Table Icon
a19-2121
SETPOINT - Setpoint Table
Fig. 15 — Setpoint Table Screen
values.
Input the Design Set Points — To access the set
point screen, press the Main Menu icon on the home screen. See Fig. 13.
The Main Menu screen is displayed. Press the Setpoint Ta-
ble icon (Fig. 14).
Main Menu
The Setpoint screen is displayed (see Fig. 15). Set the base demand limit set point, and either the LCW set point or the ECW set point. To set a value, press the appropriate set point, enter the value, and press OK. For more information, see the the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
Input the Local Occupied Schedule — Access
the schedule screen and set up the occupied time schedule ac­cording to the customer’s requirements. If no schedule is avail­able, the default is factory set for 24 hours occupied, 7 days per week including holidays. The Schedule Menu as well as the Holiday Menu can be reached through the Configuration Menu (see Appendix A on page 88 for an overview of the available menus). When the control mode is LOCAL SCHEDULE, the chiller will be automatically started if the configured local schedule is occupied; it will be shut down by the unoccupied schedule, EMSTOP software point, STOP button on HMI screen, or remote emergency stop contact.
The Network Schedule should be configured if a CCN sys­tem is being installed. When control mode is NETWORK, the chiller can be started and stopped by the CHIL_S_S software point as written by other equipment through the network com­mand and network schedule. The chiller can be shut down by EMSTOP software point and remote emergency stop contact.
For more information about setting time schedules, see the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
Input Service Configurations — For specific values
for the following configurations, refer to the chiller perfor­mance data or job-specific data sheet:
• password
• log in/logout
• input time and date
• service parameters
• equipment configuration
• automated control test PASS W OR D — The PIC 5 control system provides different
levels of access: Basic access, User access, Advanced User/ Service access and Factory access. User access provides basic access to the chiller controls. Advanced User access has access to all Service tables, and Factory user has access to factory ta­bles. The PIC 5 default password configurations are as follows:
• Basic: No password required
• User: 1111
• Advanced User / Service Access: 2222
• Factory: 4444
When accessing the SERVICE tables, a password must be entered. The password can be changed from the Configuration Menu. USER CONFIGURATION allows change of the User access password. SERVICE PARAMETERS allows change of the Advanced User/Service password, and FACTORY PA­RAMETERS allows change of the Factory password. Pass­words must be from 1 to 5 digits (range from 1 to 65535).
IMPORTANT: Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless accessed by a Carrier representative.
LOGIN/LOGOUT — Press the lock icon on the home screen to enter the password. See Fig. 16.
20
Fig. 16 — Lock Icon
User Login Screen
Fig. 17 — User Login Screen
The User Login Screen is displayed. Enter the password on this screen. See Fig 17. The language and system of measure­ment can also be changed on this screen. For details, see the 19XR with PIC 5 Controls Operation and Troubleshooting guide.
INPUT TIME AND DATE — Set day and time and if appli­cable Holidays through MAIN MENU CONFIGURATION MENU  DATE/TIME CONFIGURATION. See the Con­trols Operation and Troubleshooting guide for details. Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and date have been set.
NOTE: The date format is MM-DD-YY for English units and
MODIFY CONTROLLER IDENTIFICATION IF NECES­SARY — The module address can be changed from the Con­figuration Menu. Change this address under CONTROL IDENTIFICATION for each chiller if there is more than one chiller at the jobsite. Write the new address on the HMI module for future reference.
CONFIGURE SERVICE TABLES — Access the SER­VICE tables through MAIN MENU  CONFIGURATION MENU to modify or view the job site parameters shown in Ta­ble 7. For details, see the 19XR with PIC 5 Controls Operation and Troubleshooting guide.
DD-MM-YY for SI units.
Table 7 — Job Site Parameters
PARAMETER TABLE
Starter Type Motor Rated Line Voltage CONF_ISM — Motor rated voltage from chiller information nameplate. Volt Transformer Ratio Motor Rated Load Amps CONF_ISM — Per chiller nameplate data. RL AMPS on compressor nameplate.
Motor Locked Rotor Trip CONF_ISM — Per chiller iden tification nameplate. Starter LRA Rating
Motor Current CT Ratio Current % Imbalance CONF_ISM — Current imbalance trip threshold. Enter up to 100% for starter type 3 (VFD).
Ground Fault Current Transformers CONF_ISM — Ent er 0 if no ground fault CTs are wired to terminal J5 of ISM. Enter 1 if gr ound fault CTs are used. Ground Fault CT Ratio CONF_ISM — Enter ratio (reduced to a ratio to 1) of ground fault CT. Single Cycle Dropout CONF_ISM — ENABLE if motor protection required from drop in line voltage within one cycle. Line Frequency CONF_ISM — Enter YES for 60 Hz or NO for 50 Hz. Line Frequency Faulting CONF_ISM — ENABLE if motor protection required for drop in line frequency.
Hot Gas Bypass Option Minimum Load Points (Tsmin, IGVmin) CFGSURGE — Per job data — See modify load points section. Refer to table located in the control panel. Full (Maximum) Load Points (Tsmax, IGVmax) Surge Line Shape Factor (shapefac) CFGSURGE — Per Chiller Requisition (shapefac). Refer to table located in the control panel.
Chilled Medium FACTORY — Enter water or brine. Evaporator Refrigerant Trippoint CFGLIMIT — Usually 3° F (1.7° C) below design refrigerant temperature. Evaporator Flow Delta P Cutout CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).* Condenser Flow Delta P Cutout CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).* High Condenser Water Delta P CFGLIMIT — Enter the maximum allowable value for condenser water pressure drop.
Motor Rated Kilowatts
*With variable flow systems this point may be configured to the lower end of the range.
NOTE: Other parameters: Screens are normally left at the default settings; they may be changed as required. The time and persistence settings on the CONF_ISM table can be adjusted to increase or decrease the sensitivity to a fault condition. Increasing time or persistence decreases sensitivity. Decreas­ing time or persistence increases sensitivity to the fault condition.
CONF_ISM — Select 0 for full voltage, 1 for reduced voltage, 2 for solid state, or 3 for freestanding variable frequency drive.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of power transformer wired to ter minal J3 of ISM. If no transf ormer is used enter 1.
CONF_ISM — Enter value from nameplate in starter cabinet MAXIMUM FUSE. This value shall always be “9999” for Benshaw RediStart MX3 wye-delta and solid-state starters.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of current transf ormers wired to terminal J4 of ISM. This value shall always be “100” for Benshaw RediStart MX3 and solid-state starters.
CONF_OPT — 1 = HGBP for Surge Correction; 2 = HGBP for Low Load Operation; 3 = Combination HGBP; 0 = no HGBP or HGBP is Disabled.
CFGSURGE — Chiller Requisition (TSmin, IGV min) or per job data — See modify load points section. Refer to table located in the control panel.
FACTORY — Enter value from chiller requisition form (product data submittal) if DEMAND LIMIT SOURCE is set to kW.
21

Field Set Up and Verification

SAFETY CODE CERTIFICATION
COMPRESSOR MOTOR DATA
R-
REFRIGERATION MACHINE
CARRIER CHARLOTTE 9701 OLD STATESVILLE ROAD CHARLOTTE, NORTH CAROLINA 28269 MADE IN USA PRODUCTION YEAR: 20XX
19XR05009801
A United Technologies Company
T
M
THIS UNIT IS DESIGNED,CONSTRUCTED, AND TESTED IN CONFORMANCE WITH ANSI/ASHRAE 15 (LATEST REVISION),
SPECIFICATION Z-415.
IN ACCORDANCE WITH CARRIER
AND OVERLOAD PROTECTION MUST BE
THE COMPRESSOR MOTOR CONTROLLER
REFRIGERATION.
SAFETY CODE FOR MECHANICAL
TEST PRESSURE
DESIGN PRESSURE CLR.WATER PRESSURE COND.WATER PRESSURE
PSI PSI PSI PSI
KPA KPA KPA KPA
CAZTREH/ESAHP/STLOV RL AMPS OLT AMPS
LR AMPS Y-
LR AMPS D­MAX FUSE/CIRCUIT BKR MIN. CIRCUIT AMPACITY
LBS. CHARGED
KGS.REFRIGERANT
MODEL NUMBER
SERIAL NO. MACHINE COMP'R COOLER CONDENSER ECON STOR TANK
RATED iKW
RATED TONS
Fig. 18 — Machine Identification Nameplate
CHILLER ID NAMEPLATE — CONSTANT SPEED CHILLER
a19-1881
IMPORTANT: Some parameters are specific to the chiller configuration and will need to be verified prior to operation. All command functions must be initiated from the HMI.
Use the HMI touch screen to confirm that the ISM values match the chiller paramter labels and Chiller Builder design data sheet. The ISM values can be located from MAIN MENU CONFIGURATION MENU ISM CONFIGURATION.
LABEL LOCATIONS — Verify the following labels have been installed properly and match the chiller requisition:
• Surge Parameters — Located inside the chiller control panel.
• Chiller identification nameplate — Located on the right side of the control panel. (See Fig. 18.)
STARTER/DRIVE PROTECTION AND OTHER INCOM­ING WIRING
1. Verify that the branch disconnects or other local discon­nects are open and properly tagged out.
2. Verify that the branch circuit protection and AC input wiring to the starter are in accordance with NEC/CEC (National Electrical Code/California Energy Commis­sion) and all other local codes.
3. Verify that the fuses are per the field wiring diagram.
4. Verify that the incoming source does not exceed the SCCR (short circuit current rating) of the equipment marking.
5. Verify the power lugs in the starter/VFD and branch pro­tection are properly secured. Inspect the ground cable and ensure it is properly connected at the branch and to the
6. Verify the conduit for the power wiring in securely con-
ground lug in the starter.
nected to the starter flanged cover and runs continuously to the branch protection.
7. Ensure the control and signal wires connected to the chiller controller or the starter/VFD are in separate con­duits.
FINE TUNING VPF (VARIABLE PRIMARY FLOW) SURGE PRE VENTION — Figures 19-22 show how the pa­rameters defined below will affect the configured surge line. The menu can be found under MAIN MENU CONFIGU- RATION MENU SURGE CORRECTION CONFIG.
NOTE: Before tuning surge prevention, check for VFD (vari­able frequency drive) speed limitation or capacity overrides. If the source of low capacity is found in one of these places, do not proceed with an attempt to tune the Surge Prevention con­figurations.
If capacity is not reached and
1. ACTUAL GUIDE VANE POSITION < GUIDE VANE TRAVEL RANGE
and
2. SURGE PREVENTION ACTIVE = YES (can be identi­fied in MAIN MENU  MAINTENANCE MENU SURGE CORRECTION)
and
3. PERCENT LINE CURRENT < 100%
then the surge line is probably too conservative. Note the following parameters from HMI when maximum
ACTUAL LINE CURRENT achieved:
• EVAPORATOR REFRIGERANT TEMP
• EVAPORATOR PRESSURE
• CONDENSER REFRIG TEMP
• CONDENSER PRESSURE
• ACTUAL GUIDE VANE POSITION
• ACTUAL LINE CURRENT The ACTIVE DELTA Tsat and the CALC REF DELTA
TSAT can be monitored on the MAINTENANCE MENU SURGE CORRECTION screen. When DELTA TSAT exceeds CALC REF DELTA TSAT + ENVELOPE LINE OFFSET surge prevention will occur.
If ACTUAL GUIDE VANE POSITION is less than 30%,
then increase SURGE DELTA TSMIN in steps of 2º F (1.2º C) until one of the three conditions listed above no longer applies. Do not change SURGE DELTA TSMAX.
If ACTUAL GUIDE VANE POSITION is greater than
60%, then increase SURGE DELTA TSMAX in steps of 2º F (1.2º C) until cooling capacity is reached or one of conditions listed above no longer applies. Do not change SURGE/HGBP DELTA TSMIN.
If ACTUAL GUIDE VANE POSITION is more than 30%
AND less than 60%, then:
1. Increase SURGE DELTA TSMIN in steps of 2º F (1.2º C).
2. Increase SURGE DELTA TSMAX in steps of 2º F (1.2º C).
3. Repeat Steps 1 and 2 until one of the conditions listed above no longer applies.
NOTE: DELTA TSMIN should seldom need to be increased more than 10 degrees above the selection program value. Like­wise, DELTA TSMAX rarely requires more than a 2º F (1.2º C) increase.
If surge is encountered then the surge line is probably too optimistic or high. Note following parameters from HMI at surge:
• EVAPORATOR REFRIGERANT TEMP
• EVAPORATOR PRESSURE
• CONDENSER REFRIG TEMP
• CONDENSER PRESSURE
• ACTUAL GUIDE VANE POSITION
• AVERAGE LINE CURRENT
22
40
Fig. 19 — Effect of SURGE DELTA TSMIN on
Surge Prevention
a19-1959
0
5
10
15
20
25
30
35
40
45
0 102030405060708090100110
Tsmax= 60
Tsmax= 70
Tsmax= 80
GV_POS
Delta Tsat
Fig. 20 — Effect of SURGE DELTA TSMAX on
Surge Prevention
a19-1960
Fig. 21 — Effect of SURGE LINE SHAPE FACTOR
on Surge Prevention
a19-1961
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
0 102030405060708090100110
Speed Factor =1.60
Speed Factor =1.85
Speed Factor =2.00
GV_POS
Delta Tsat
Fig. 22 — Effect of SURGE LINE SPEED FACTOR
on Surge Prevention
a19-1962
35
30
25
20
Delta Tsat
15
10
5
0
0 102030405060708090100110
60.00
55.00
50.00
45.00
40.00
35.00
30.00
Delta Tsat
25.00
20.00
15.00
10.00
5.00
0.00 0 10 20 30 40 50 60 70 80 90 100 110
GV_POS
GV_POS
Tsmin= 30
Tsmin= 40
Tsmin= 50
Shape factor = -0.020
Shape factor = -0.040
Shape factor = -0.050
If ACTUAL GUIDE VANE POSITION is less than 30%, go to Step 1. If ACTUAL GUIDE VANE POSITION is greater than 60%, then go to Step 3.
1. Do not change SURGE LINE SHAPE FACTOR from the value selected by Chiller Builder (ECAT). Decrease SURGE DELTA TSMIN in 1° F steps up to 5 times. Monitor chiller for surge.
2. If ACTUAL GUIDE VANE POSITION is still less than 30 and Step 1 failed, then increase the value of SURGE LINE SHAPE FACTOR in steps of 0.01 up to 2 times. For example, if surge is encountered when shape factor is –0.06, increase the SURGE LINE SHAPE FACTOR to –0.05. If this does not solve the problem, go to Step 5, even if ACTUAL GUIDE VANE POSITION is less than 30%.
3. Do not change SURGE LINE SHAPE FACTOR from the value selected by Chiller Builder (ECAT). Decrease SURGE DELTA TSMAX by 1° F steps up to 5 times. Monitor chiller for surge.
4. If ACTUAL GUIDE VANE POSITION is greater than 60% and Step 3 failed to eliminate surge, then set SURGE DELTA TSMAX to 5° F below the value speci­fied by Chiller Builder (ECAT). Increase the value of the SURGE LINE SHAPE FACTOR in steps of 0.01 up to 2 times. For example, if surge is encountered when the SURGE LINE SHAPE FACTOR is –0.06, increase the SURGE LINE SHAPE FACTOR to –0.05. If this does not solve the problem, go to Step 5, even if ACTUAL GUIDE VANE POSITION is greater than 60%.
5. If ACTUAL GUIDE VANE POSITION is greater than 30% but less than 60% or if Step 2 failed (with ACTUAL GUIDE VANE POSITION less than 30) or if Step 4 failed (with ACTUAL GUIDE VANE POSITION great­er than 60), then perform this step. Do not change SURGE LINE SHAPE FACTOR from the value speci­fied by Chiller Builder (ECAT). Reset SURGE DELTA TSMIN and SURGE DELTA TSMAX to the value spec­ified by Chiller Builder (ECAT). Decrease SURGE DEL­TA TSMIN and SURGE DELTA TSMAX in steps of 1° F up to 5 times. Monitor chiller for surge.
If the chiller is equipped with a VFD and the drive does not slow down adequately at part load, then the machine is likely operating at a point above the configured “software” surge line and the machine is in surge prevention mode. Check for a surge protection message on the HMI. If the unit is not in a surge pro­tection state, then the ENVELOPE SPEED FACTOR may
23
need to be increased (more aggressive surge line protection) in combination with a decrease in the SURGE LINE SHAPE FACTOR.
MODIFY EQUIPMENT CONFIGURATION IF NECES­SARY — The EQUIPMENT SERVICE table has screens to select, view, or modify parameters. Carrier’s certified drawings have the configuration values required for the jobsite. Modify these values only if requested. Modifications can include:
• Chilled water reset
• Entering chilled water control (Enable/Disable)
• 4 to 20 mA demand limit
• Auto restart option (Enable/Disable)
• Remote contact option (Enable/Disable) See the 19XR with PIC 5 Controls Operation and Trouble-
shooting guide for more details about these functions.
Perform a Controls Test (Quick Test) — Check
the safety controls status by performing an automated controls test. The path to the QUICK TEST is MAIN MENU QUICK TEST TABLE. (The QUICK TEST screen can only be accessed when the chiller is in STOP mode.) On the
QUICK TEST table screen, select a test to be performed (see Table 8).
The Quick Test checks all outputs and inputs for function. In order to successfully proceed with the controls test, the com­pressor should be off, no alarms showing, and voltage should be within ±10% of rating plate value. Each test asks the opera­tor to confirm the operation is occurring and whether or not to continue. If an error occurs, the operator can try to address the problem as the test is being done or note the problem and pro­ceed to the next test.
NOTE: If during the controls test the guide vanes do not open, verify the low pressure alarm is not active. (An active low pressure alarm causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if cooler pressure is below –5 psig (–35 kPa).
When the controls test is finished the test stops and the QUICK TEST menu displays. If a specific automated test pro­cedure is not completed, access the particular control test to test the function when ready. For information about calibration, see the sections Checking Pressure Transducers, page 46, and High Altitude Locations, page 46.
Table 8 — Quick Test Table
CCN TABLE NAME: QCK_TEST PIC 5 PATH: Main Menu Quick Test
LINE PIC 5 DESCRIPTION CCN NAME RANGE
1 Quick Test Enable QCK_TEST DSABLE/ENABLE DSABLE RW 2 GV 1 Calibration Enable GV1_CAL DSABLE/ENABLE DSABLE RW 3 GV1 Calibration Status
0=No Calibration or Failure
1=In Progress, 2=Completed 4 Guide Vane 1 Actual Ohms GV1_OHM 0.00 to 12000.00 RO 5 Guide Vane 1 Actual mA GV1_MAF 0.0 to 20.8 mA RO 6 Guide Vane 1 Forced Position Q_GV1POS 0.0 to 100.0 0.0 % RW 7 Quick Test GV1 Open Q_GV1OP OFF/ON OFF RW 8 Quick Test GV1 Close Q_GV1CL OFF/ON OFF RW 9 Quick Test Oil Pump Q_OILP OFF/ON OFF RW
10 Oil Pres Test Passed OP_PASS NO/YES RO 11 Oil Pump Delta Pressure OIL_PDQ –6.7 t o 420.0 psig RO 12 Quick Test Oil Heater Q_OILH OFF/ON OFF RW 13 Quick Test HGBP Open Q_HGBPOP OFF/ON OFF RW 14 Quick Test HGBP Close Q_HGBPCL OFF/ON OFF RW 15 Quick Test Damper Open Q_DMPOP OFF/ON OFF RW 16 Quick Test Damper Close Q_DMPCL OFF/ON OFF RW 17 Quick Test Cond Pump Q_CDWP OFF/ON OFF RW 18 Condenser Water Flow CDW_FLOW NO/YES RO 19 Quick Test Chilled Pump Q_CHWP OFF/ON OFF RW 20 Chileld Water Flow CHW_FLOW NO/YES RO 21 Condenser Water Flow CDW_FLOW NO/YES RO 22 Chilled Water Flow CHW_FLOW NO/YES RO 23 Quick Test Head Val Pos Q_HDP 0.0 to 100.0 0.0 % RW 24 Quick Test Diffuser Pos Q_SRD 0.0 to 100.0 0.0 % RW 25 Quick Test Chiller Status Q_CHST 4.0 to 20.0 4.0 mA RW 26 Quick Test Oil EXV Q_EXV 4.0 to 20.0 4.0 mA RW 27 Condenser Water Delta T CDW_DT –40.0 to 245.0 °F RO 28 Chilled Water Delta T CHW_DT –40.0 to 245.0 °F RO 29 Cond Water Deviation CDWT_DV OFF/ON RO 30 Chilled Water Deviation CHWT_DV OFF/ON RO 31 Quick Test Alarm Output Q_ALM OFF/ON OFF RW 32 Quick Test Alert Output Q_ALE OFF/ON OFF RW 33 Guide Vane 1 Ohms 100% GV1_MAXO 0.00 to 12000.00 RO 34 Guide Vane 1 Ohms 0% GV1_MINO 0.00 to 12000.00 RO 35 Guide Vane 1 mA 100% GV1_MAXA 0.0 to 20.8 mA RO 36 Guide Vane 1 mA 0% GV1_MINA 0.0 to 20.8 mA RO
LEGEND
GV Guide Vane HGBP — Hot Gas Bypass RO Read Onl y RW Read Write
*Default value is shown only if configurable in this table.
GV1_STAT 0 to 2 RO
NOTES:
1. Quick Test ENABLE defaults back to DISABLE after 1 hour.
2. During any of the tests, an out-of-range reading will have an asterisk (*) next to the reading and a message will be displayed if the diffuser control is enabled.
DEFAULT
VALUE*
UNIT READ/WRITE
24

Charge Refrigerant into Chiller

CAUTION
The transfer, addition, or removal of refrigerant in spring isolated chillers may place severe stress on and damage external piping if springs have not been blocked in both up and down directions.
CAUTION
Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups.
1. Access the terminate lockout function on the PUMP­DOWN/LOCKOUT screen (located in the Maintenance Menu).
2. IMPORTANT: Turn on the chilled water and condenser water pumps to prevent freezing.
3. Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 23 and 24. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process takes approximately 15 minutes.
4. Once the pressures have equalized, the discharge isola­tion valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves 1a and 1b, and all pumpout unit valves.
The standard 19XR chiller is shipped with the refrigerant already charged in the vessels. However, the 19XR chiller may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the nitrogen from the entire chiller, and charge the chiller from refrigerant cylinders.

CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT

CAUTION
When equalizing refrigerant pressure on the 19XR chiller after service work or during the initial chiller start-up, do not use the discharge isolation valve to equalize. A charging hose (connected between the charging valves on top of the cooler and condenser) should be used as the equalization valve. Failure to follow this procedure may damage equipment.
To equalize the pressure differential on a refrigerant isolated 19XR chiller, use the terminate lockout function of PUMP­DOWN/LOCKOUT (located in the Maintenance Menu). This helps to turn on pumps and advises the operator on proper pro­cedures.
The following steps describe how to equalize refrigerant pressure in an isolated 19XR chiller without a pumpout unit.
1. Access terminate lockout function on the Maintenance Menu. (Alternatively, the Quick Test provides a means for cooler and condenser pump control.)
2. IMPORTANT: Turn on the chilled water and condenser water pumps to prevent freezing.
3. Slowly open the refrigerant charging valves. The chiller cooler and condenser pressures will gradually equalize. This process takes approximately 15 minutes.
4. Once the pressures have equalized, the cooler isolation valve, the condenser isolation valve, and the hot gas isola­tion valve may now be opened. Refer to Fig. 23 and 24 for the location of the valves.
WARNING
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation. Failure to follow this procedure may damage equipment and result in bodily injury.
CHILLER EQUALIZATION WITH FREE-STANDING PUMPOUT UNIT — The following steps describe how to equalize refrigerant pressure on an isolated 19XR chiller using the pumpout unit.
WARNING
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation. Failure to follow this procedure may damage equipment and result in bodily injury.
The full refrigerant charge on the 19XR chiller will vary with chiller components and design conditions, as indicated on the job data specifications. An approximate charge may be de­termined by adding the condenser charge to the cooler charge as listed in the Heat Exchanger Data tables in the Physical Data section that begins on page 48.
CAUTION
Always operate the condenser and chilled water pumps whenever charging, transferring, or removing refrigerant from the chiller. Always confirm that water flow is estab­lished. Failure to follow this procedure may result in equip­ment damage.
Use the PUMPDOWN/LOCKOUT terminate lockout func­tion to monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge refrigerant is added through the pumpout charging connection (Fig. 23 and 24, valve 1b). First evacuate the nitrogen holding charge from the chiller vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig (241 kPa) for HFC­134a. After the chiller is beyond this pressure the refrigerant should be charged as a liquid until all the recommended refrig­erant charge has been added. The charging valve (Fig. 23 and 24, valve 7) can be used to charge liquid to the cooler if the cooler isolation valve (11) is present and is closed. Do not charge liquid through the linear float to the condenser.
TRIMMING REFRIGERANT CHARGE — The 19XR chiller is shipped with the correct charge for the design duty of the chiller. Trimming the charge can best be accomplished when the design load is available. To trim the charge, check the temperature difference between the leaving chilled water tem­perature and cooler refrigerant temperature at full load design conditions. If necessary, add or remove refrigerant to bring the temperature difference to design conditions or minimum differential. See the 19XR Installation Instructions manual for required chiller refrigerant charge.
The 19XR chiller refrigerant charges are shown in Tables 9 and 10. Total refrigerant charge is the sum of the cooler, con­denser, and economizer charge.
, the
25
STORAGE
TANK LIQUID
VALVE
OIL SEPARATOR
PUMPOUT CONDENSER WATER SUPPLY AND RETURN
PUMPOUT CONDENSER
STORAGE TANK VAPOR VALVE
2
3
4
5
PRESSURE RELIEF SAFETY VALVE
PUMPOUT COMPRESSOR
TEE FOR CHARGING
REFRIGERANT CHARGING VALVE
COOLER REFRIGERANT ISOLATION VALVE
LIQUID LINE SERVICE VALVE
CHILLER CONDENSER VESSEL
CHILLER COOLER VESSEL
10
6
7
11
1a
1b
SERVICE VALVE ON PUMPOUT UNIT
=
SERVICE VALVE ON CHILLER (FIELD SUPPLIED)
=
=
MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND STORAGE TANK FOR SERVICE AND OPERATION WORK.
REFRIGERANT CHARGING VALVE
Fig. 23 — Typical Optional Pumpout System Piping Schematic with Storage Tank
a19-1721
OIL SEPARATOR
PUMPOUT CONDENSER WATER SUPPLY AND RETURN
PUMPOUT CONDENSER
2
3
4
5
PRESSURE RELIEF SAFETY VALVE
PUMPOUT COMPRESSOR
COOLER REFRIGERANT ISOLATION VALVE
REFRIGERANT CHARGING VALVE
CHILLER CONDENSER VESSEL
CHILLER COOLER VESSEL
7
11
1a
1b
SERVICE VALVE ON PUMPOUT UNIT
=
SERVICE VALVE ON CHILLER
=
LIQUID LINE SERVICE VALVE
REFRIGERANT CHARGING VALVE
Fig. 24 — Typical Freestanding Pumpout System Piping Schematic without Storage Tan k
a19-1722
26
Table 9 — 19XR Two-Stage Compressor Frame Size 6 Heat Exchanger Refrigerant Charge
ENGLISH SI
CODE*
COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY
A40 1647 927 360 747 420 163 A41 1773 927 360 804 420 163 A42 1887 927 360 856 420 163 A45 1599 927 360 725 420 163 A46 1714 927 360 777 420 163 A47 1837 927 360 833 420 163
A60 1878 1074 360 852 48 7 163 A61 2022 1074 360 917 48 7 163 A62 2152 1074 360 976 48 7 163 A65 1823 1074 360 827 48 7 163 A66 1954 1074 360 886 48 7 163 A67 2095 1074 360 950 48 7 163
A4A 1681 861 360 762 391 163 A4B 1792 861 360 813 391 163 A4C 1897 861 360 860 391 163 A4F 1626 861 360 738 391 163 A4G 1736 861 360 787 391 163 A4H 1890 861 360 857 391 163
A6A 1917 998 360 870 453 163 A6B 2044 998 360 927 453 163 A6C 2164 998 360 982 453 163 A6F 1854 998 360 841 453 163 A6G 1979 998 360 898 453 163 A6H 2156 998 360 978 453 163
MACHINE CHARGE MACHINE CHARGE
REFRIGERANT WEIGHT (lb) REFRIGERANT WEIGHT (kg)
B40 1233 360 559 163 B41 1233 360 559 163 B42 1233 360 559 163 B45 1233 360 559 163 B46 1233 360 559 163 B47 1233 360 559 163
B60 1423 360 645 163 B61 1423 360 645 163 B62 1423 360 645 163 B65 1423 360 645 163 B66 1423 360 645 163 B67 1423 360 645 163
B4A 1148 360 521 163 B4B 1148 360 521 163 B4C 1148 360 521 163 B4F 1148 360 521 163 B4G 1148 360 521 163 B4H 1148 360 521 163
B6A 1326 360 601 163 B6B 1326 360 601 163 B6C 1326 360 601 163 B6F 1326 360 601 163 B6G
H 1326 360 60
B6
*See Model Number Nomenclature on page 5.
1326 360 601 163
1 163
27
Table 10 — 19XR Two-Stage Compressor Frame Size 7 Heat Exchanger Refrigerant Charge
ENGLISH SI
CODE*
COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY
B60 2273 646 1031 293 B61 2355 646 1068 293 B62 2460 646 1116 293 B65 2185 646 991 293 B66 2275 646 1032 293 B67 2379 646 1079 293
B6A 2081 646 944 293 B6B 2162 646 981 293 B6C 2256 646 1023 293
B6F 1951 646 885 293 B6G 2019 646 916 293 B6H 2120 646 962 293
C60 2647 1610 646 1201 730 293
C61 2751 1610 646 1248 730 293
C62 2875 1610 646 1304 730 293
C65 2562 1610 646 1162 730 293
C66 2666 1610 646 1209 730 293
C67 2793 1610 646 1267 730 293
C6A 2443 1497 646 1108 679 293 C6B 2534 1497 646 1149 679 293 C6C 2627 1497 646 1192 679 293
C6F 2334 1497 646 1059 679 293 C6G 2415 1497 646 1095 679 293 C6H 2500 1497 646 1134 679 293
MACHINE CHARGE MACHINE CHARGE
REFRIGERANT WEIGHT (lb) REFRIGERANT WEIGHT (kg)
D60 2097 646 951 293
D61 2097 646 951 293
D62 2097 646 951 293
D65 2097 646 951 293
D66 2097 646 951 293
D67 2097 646 951 293
D6A 1947 646 883 293 D6B 1947 646 883 293 D6C 1947 646 883 293
D6F 1947 646 883 293 D6G 1947 646 883 293 D6H 1947 646 883 293
*See Model Number Nomenclature on page 5.
28

INITIAL START-UP

Fig. 25 — Correct Motor Rotation
Preparation —
1. Power is on to the main starter, oil pump relay, tower fan starter, oil heater relay, and the chiller control panel.
2. Cooling tower water is at proper level and at-or-below design entering temperature.
3. Chiller is charged with refrigerant and all refrigerant and oil valves are in their proper operating positions.
4. Oil is at the proper level in the reservoir sight glasses.
5. Oil reservoir temperature is above 140 F (60 C) or above CALC EVAP SAT TEMP plus 50 F (28 C).
6. Valves in the evaporator and condenser water circuits are open.
NOTE: If the pumps are not automatic, ensure water is circulating properly.
Before starting the chiller, verify:
CAUTION
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief valves and result in the loss of refrigerant charge.
7. Access the PUMPDOWN/LOCKOUT feature from the Maintenance Menu. Press the End Lockout button on the touch screen and accept the “press OK to Terminate Lockout?” prompt. The unit is reset to operating mode. The chiller is locked out at the factory in order to prevent accidental start-up.

Check Motor Rotation

1. Disengage the main starter disconnect and engage the control panel power circuit breaker.
NOTE: The circuit breaker may be located in the starter if the disconnect and step down transformer option was or­dered with the starter. If located in the starter, close the door securely after this step.
2. Close the starter enclosure door.
3. The ISM (integrated starter module) mounted in the start­er enclosure checks for proper phase rotation as soon as power is applied to the starter and the PIC 5 controls power up.
4. An alarm message will appear on the HMI screen if the phase rotation is incorrect. If this occurs reverse any 2 of the 3 incoming power leads to the starter and reapply power. The motor is now ready for a rotation check.
5. Start the chiller by Local On (assumes LOCAL operation mode) by pressing the Start/Stop button on the HMI and following the prompts. The PIC 5 control performs start­up checks.
6. When the starter is energized and the motor begins to turn, check for clockwise motor rotation (Fig. 25).
IMPORTANT: Do not check motor rotation during coast­down. Rotation may have reversed during equalization of vessel pressures.

Check Oil Pressure and Compressor Stop

1. When the motor is at full speed, note the differential oil pressure reading on the HMI default screen. It should be between 18 and 40 psid (124 and 206 kPad). The oil pump will geenrate design oil pressure only with the cor­rect electrical phasing of ABC.
2. Press the Stop button and listen for any unusual sounds from the compressor as it coasts to a stop.
To Prevent Accidental Start-Up — A chiller STOP
override setting may be entered to prevent accidental start-up during service or whenever necessary. From the Main Menu, access the General Parameters Menu and use the down arrow to reach Stop Override on the GENUNIT table. Change Stop Override to Yes; then execute the command by touching the lightning button. The message “ALM-276 Protective Limit ­Stop Override” will appear in the Home Screen message area. To restart the chiller, access the same screen change the Stop Override option to No.
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and oil and refrigerant levels indicate the system is functioning properly.
Instruct the Customer Operator — Ensure the op-
erator(s) understand all operating and maintenance procedures. Point out the various chiller parts and explain their function as part of the complete system.
COOL ER-CON DENSE R — High side float chamber, relief valves, refrigerant charging valve, temperature sensor loca­tions, pressure transducer locations, Schrader fittings, water­boxes and tubes, and vents and drains.
OPTIONAL PUMPOUT STORAGE TANK AND PUMP­OUT SYSTEM — Transfer valves and pumpout system, re­frigerant charging and pumpdown procedure, and relief devices.
MOTOR COMPRESSOR ASSEMBLY — Guide vane ac­tuator, transmission, motor cooling system, oil cooling system, temperature and pressure sensors, oil sight glasses, integral oil pump, isolatable oil filter, extra oil and motor temperature sen­sors, synthetic oil, and compressor serviceability.
MOTOR COMPRESSOR LUBRICATION SYSTEM — Oil pump, cooler filter, oil heater, oil charge and specification, operating and shutdown oil level, temperature and pressure, and oil charging connections.
ECONOMIZER — Float valve, drain valve, Schrader fitting, damper valve.
CONTROL SYSTEM — CCN and LOCAL start, reset, menu, softkey functions, HMI operation, occupancy schedule, set points, safety controls, and auxiliary and optional controls.
AUXILIARY EQUIPMENT — Starters and disconnects, separate electrical sources, pumps, and cooling tower.
DESCRIBE CHILLER CYCLES — Refrigerant, motor cooling, lubrication, and oil reclaim.
29
REVIEW MAINTENANCE — Scheduled, routine, and ex­tended shutdowns, importance of a log sheet, importance of water treatment and tube cleaning, and importance of maintain­ing a leak-free chiller.
SAFETY DEVICES AND PROCEDURES — Electrical disconnects, relief device inspection, and handling refriger­ant.
CHECK OPERATOR KNOWLEDGE — Start, stop, and shutdown procedures, safety and operating controls, refrigerant and oil charging, and job safety.
REVIEW THE START-UP, OPERATION, AND MAINTE­NANCE MANUAL.

OPERATING INSTRUCTIONS

Operator Duties

1. Become familiar with the chiller and related equipment before operating the chiller.
2. Prepare the system for start-up, start and stop the chiller, and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any abnormal readings.
4. Inspect the equipment, make routine adjustments, and perform a Control Test. Maintain the proper oil and re­frigerant levels.
5. Protect the system from damage during shutdown periods.
6. Maintain the set point, time schedules, and other PIC functions.
Prepare the Chiller for Start-Up — Follow the steps
described in the Initial Start-Up section, page 29.

To Start the Chiller

1. Start the water pumps, if they are not automatic.
2. Press the Start/Stop icon on the HMI home screen to start the system. If the chiller is in the OCCUPIED mode and the start timers have expired, the start sequence will start. Follow the procedure described in the Start-Up/Shut­down/Recycle Sequence section, page 11.
Check the Running System — After the compres-
sor starts, the operator should monitor the display and observe the parameters for normal operating conditions:
1. The oil reservoir temperature should be above 120 F (49 C) during shutdown.
2. The bearing oil temperature accessed from the Tempera­tures menu should be 120 to 165 F (49 to 74 C) for com­pressors with rolling element bearings. If the bearing tem­perature reads more than 180 F (83 C) with the oil pump running, stop the chiller and determine the cause of the high temperature. Do not restart the chiller until correct­ed.
3. The oil level should be visible anywhere in one of the two sight glasses. Foaming oil is acceptable as long as the oil pressure and temperature are within limits.
4. The oil pressure should be between 18 and 40 psid (124 and 207 kPad) differential, as seen on the HMI Transmis­sion Status screen. Typically the reading will be 18 to 35 psid (124 to 241 kPad) at initial start-up.
5. The moisture indicator sight glass on the ref rigerant mo­tor cooling line should indicate refrigerant flow and a dry condition.
6. The condenser pressure and temperature varies with the chiller design conditions. Typically the pressure will range between 60 and 135 psig (390 and 950 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering water temperature should be controlled below the specified design entering water
temperature to save on compressor kilowatt requirements.
7. Cooler pressure and temperature also will vary with the design conditions. Typical pressure range will be between
29.5 and 40.1 psig (203.4 and 276.4 kPa), with tempera­ture ranging between 34 and 45 F (1.1 and 7.2 C).
8. The compressor may operate at full capacity for a short time after the pulldown ramping has ended, even though the building load is small. The active electrical demand setting can be overridden to limit the compressor kW, or the pulldown rate can be decreased to avoid a high demand charge for the short period of high demand oper­ation. Pulldown rate can be based on load rate or tempera­ture rate and is accessed on the MAINTENANCE MENU CAPACITY CONTROLS  RAMP_DEM (Ramping Demand Limit Value).
9. The economizer (if installed) has two sight glasses that look into the float chamber. When the chiller is operating, the top sight glass is empty and the bottom sight glass is full.

To Stop the Chiller

The occupancy schedule starts and stops the chiller automati­cally once the time schedule is configured.
The unit can be stopped manually using the HMI by press­ing the green Start/Stop icon . The Unit Start/Stop screen is displayed. Press Confirm Stop. The compressor will then fol­low the normal shutdown sequence as described in the Start­Up/Shutdown/Recycle Sequence section on page 11. The chiller is now in the OFF control mode.
IMPORTANT: Do not attempt to stop the chiller by opening an isolating knife switch. High intensity arcing may occur.
If the chiller is stopped by an alarm condition, do not restart the chiller until the problem is diagnosed and corrected.
After Limited Shutdown — No special preparations
should be necessary. Follow the regular preliminary checks and starting procedures.
Preparation for Extended Shutdown — The refrig-
erant should be transferred into the pumpout storage tank (if supplied; see Pumpout and Refrigerant Transfer Procedures on page 31) to reduce chiller pressure and the possibility of leaks. Maintain a holding charge of 5 to 10 lb (2.27 to 4.5 kg) of re­frigerant or nitrogen to prevent air from leaking into the chiller.
If freezing temperatures are likely to occur in the chiller ar­ea, drain the chilled water, condenser water, and the pumpout condenser water circuits to avoid freeze-up. Keep the waterbox drains open. It is recommended not to store the refrigerant in the unit if below freezing temperatures are anticipated. A nitro­gen holding charge is recommended in this case.
Leave the oil charge in the chiller with the oil heater and controls energized to maintain the minimum oil reservoir temperature.
After Extended Shutdown — Ensure the water sys-
tem drains are closed. It may be advisable to flush the water circuits to remove any soft rust that may have formed. This is a good time to brush the tubes and inspect the Schrader fittings on the waterside flow devices for fouling, if necessary.
Check the cooler pressure on the HMI panel and compare it to the original holding charge that was left in the chiller. If (af­ter adjusting for ambient temperature changes) any loss in pres­sure is indicated, check for refrigerant leaks. See Check Chiller Tightness section, page 13.
Recharge the chiller by transferring refrigerant from the pumpout storage tank (if supplied). Follow the Pumpout and Refrigerant Transfer Procedures section on page 31. Observe freeze-up precautions.
30
Loading...
+ 78 hidden pages