Carrier 19XR User Manual

AquaEdge
19XR
Two-Stage Semi-Hermetic Centrifugal Liquid Chillers
with PIC 5 Controls and HFC-134a
50/60 Hz
Start-Up, Operation, and Maintenance Instructions

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifi­cations. When operating this equipment, use good judg­ment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.
DANGER
Failure to follow these procedures will result in severe per­sonal injury or death.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented out­doors in accordance with the latest edition of ANSI/ ASHRAE 15 (American National Standards Institute/ American Society of Heating, Refrigerating, and Air­Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harm­ful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures; VERIFY the allowable test pressure by checking the instruction litera­ture and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly
installed and functioning before operating any chiller. RISK OF INJURY OR DEATH by electrocution. High
voltage is present on motor leads even though the motor is not running when a solid-state or wye-delta mechanical starter is used. Open the power supply disconnect before touching motor leads or terminals.
WARNING
Failure to follow these procedures may result in personal injury or death.
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig­erant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
DO NOT USE eyebolts or eyebolt holes to rig chiller sec­tions or the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servic­ing. IF WORK IS INTERRUPTED, confirm that all cir­cuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refriger­ant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLE­GAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
(Warnings continued on next page.)
Manufacturer reserves the right to discontinue, or change at any time, specificatio ns or designs without not ice and without incurring obligations.
Catalog No. 04-53190038-01 Printed in U.S.A. Form 19XR-CLT-12SS Pg 1 12-15 Replaces: 19XR-CLT-11SS
WARNING
Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this chiller with other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a com-
pressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.
CAUTION
Failure to follow these procedures may result in personal injury or damage to equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the water­box has been completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations.
DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to pre­vent oil contamination when timely repairs cannot be completed.

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1,2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ABBREVIATIONS AND EXPLANATIONS . . . . . . . . . . . . 4
CHILLER FAMILIARIZATION. . . . . . . . . . . . . . . . . . . . . . .4-6
Chiller Information Nameplate . . . . . . . . . . . . . . . . . . . . . . 4
System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Motor-Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Economizer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Free-Standing Starter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MOTOR AND OIL COOLING CYCLE. . . . . . . . . . . . . . . . . 8
LUBRICATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,9
Summary
Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Oil Reclaim System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• PRIMARY OIL RECOVERY MODE
• SECONDARY OIL RECOVERY METHOD
STARTING EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Solid-State Starter (Optional) . . . . . . . . . . . . . . . . . . . . . 10
Freestanding Medium Voltage VFD (Optional) . . . . . 10
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• ANALOG SIGNAL
• DISCRETE SIGNAL
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PIC 5 System Components . . . . . . . . . . . . . . . . . . . . 10,11
START-UP/SHUTDOWN/RECYCLE
SEQUENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
Local Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Lubrication Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . . . . . .13-28
Job Data Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Equipment Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Remove Shipping Packaging . . . . . . . . . . . . . . . . . . . . . . 13
Open Oil Circuit Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Tighten All Gasketed Joints . . . . . . . . . . . . . . . . . . . . . . . 13
Check Chiller Tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Tracer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Leak Test Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Standing Vacuum Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chiller Dehydration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspect Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Check Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inspect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Check Starter
• MECHANICAL STARTER
• SOLID-STATE STARTER
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Power Up the Controls and
Check the Oil Heater
Software Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Input the Design Set Points. . . . . . . . . . . . . . . . . . . . . . . 20
Input the Local Occupied Schedule. . . . . . . . . . . . . . . . 20
Input Service Configurations
•PASSWORD
• LOGIN/LOGOUT
• INPUT TIME AND DATE
• MODIFY CONTROLLER IDENTIFICATION
IF NECESSARY
• CONFIGURE SERVICE TABLES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . 20
2
CONTENTS (cont)
Page
Field Set Up and Verification . . . . . . . . . . . . . . . . . . . . . . .22
• LABEL LOCATIONS
• STARTER/DRIVE PROTECTION AND OTHER INCOMING WIRING
• FINE TUNING VPF (VARIABLE PRIMARY FLOW) SURGE PREVENTION
• MODIFY EQUIPMENT CONFIGURATION IF NECESSARY
Perform a Control Test (Quick Test) . . . . . . . . . . . . . . . .24
Charge Refrigerant Into Chiller
• CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT
• CHILLER EQUALIZATION WITH FREE-STANDING PUMPOUT UNIT
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29,30
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Check Motor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Check Oil Pressure and Compressor Stop . . . . . . . . .29
To Prevent Accidental Start-Up. . . . . . . . . . . . . . . . . . . . .29
Check Chiller Operating Condition . . . . . . . . . . . . . . . . .29
Instruct the Customer Operator . . . . . . . . . . . . . . . . . . . .29
• COOLER-CONDENSER
• OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM
• MOTOR COMPRESSOR ASSEMBLY
• MOTOR COMPRESSOR LUBRICATION SYSTEM
• ECONOMIZER
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• DESCRIBE CHILLER CYCLES
• REVIEW MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• REVIEW THE START-UP, OPERATION, AND MAINTENANCE MANUAL
OPERATING INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . 30,31
Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Prepare the Chiller for Start-Up. . . . . . . . . . . . . . . . . . . . .30
To Start the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Check the Running System. . . . . . . . . . . . . . . . . . . . . . . . .30
To Stop the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
After Limited Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Preparation for Extended Shutdown. . . . . . . . . . . . . . . .30
After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . .30
Cold Weather Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Manual Guide Vane Operation. . . . . . . . . . . . . . . . . . . . . .31
Refrigeration Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-36
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Operating the Optional Pumpout Unit . . . . . . . . . . . . . .33
• TO READ REFRIGERANT PRESSURES
• POSITIVE PRESSURE CHILLERS WITH STORAGE
TANKS
• CHILLERS WITH ISOLATION VALVES
• DISTILLING THE REFRIGERANT
GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . .36-38
Refrigerant Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Adjusting the Refrigerant Charge. . . . . . . . . . . . . . . . . . .36
Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
. . . . . . . . . . . . . . . . . . . 25
Page
Test After Service, Repair, or Major Leak. . . . . . . . . . .36
• TESTING WITH REFRIGERANT TRACER
• TESTING WITHOUT REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test. . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Checking Guide Vanes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Trim Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . .38
WEEKLY MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . .38
Check the Lubrication System . . . . . . . . . . . . . . . . . . . . .38
SCHEDULED MAINTENANCE . . . . . . . . . . . . . . . . . . . 38-41
Service Ontime. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Inspect the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . .38
Changing Oil Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
• TO CHANGE THE OIL
Refrigerant Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Oil Reclaim Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Inspect Refrigerant Float System. . . . . . . . . . . . . . . . . . . 39
• ECONOMIZER FLOAT SYSTEM
• ECONOMIZER DAMPER VALVE
Inspect Relief Valves and Piping . . . . . . . . . . . . . . . . . . .40
Compressor Bearing and Gear
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Inspect the Heat Exchanger Tubes
and Flow Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
• COOLER AND OPTIONAL FLOW DEVICES
• CONDENSER AND OPTIONAL FLOW DEVICES
Water Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Inspect the Starting Equipment . . . . . . . . . . . . . . . . . . . .41
Recalibrate Pressure Transducers . . . . . . . . . . . . . . . . . 41
Optional Pumpout System Maintenance. . . . . . . . . . . .41
• OPTIONAL PUMPOUT COMPRESSOR OIL
CHARGE
• OPTIONAL PUMPOUT SAFETY CONTROL
SETTINGS
Ordering Replacement Chiller Parts. . . . . . . . . . . . . . . . 41
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . 42-87
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Checking Display Messages . . . . . . . . . . . . . . . . . . . . . . . 42
Checking Temperature Sensors. . . . . . . . . . . . . . . . . . . . 42
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers . . . . . . . . . . . . . . . . . . .46
• TRANSDUCER REPLACEMENT
• COOLER AND CONDENSER PRESSURE
TRANSDUCER CALIBRATION
• OPTIONAL THERMAL DISPERSION FLOW
SWITCH CALIBRATION
• HYDRAULIC STATUS
High Altitude Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Quick Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pumpdown/Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
APPENDIX A — PIC 5 SCREEN AND
MENU STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . .. .88-91
APPENDIX B — CCN COMMUNICATION WIRING
FOR MULTIPLE CHILLERS (TYPICAL) . . . . . . . . . . .92
APPENDIX C — MAINTENANCE SUMMARY
AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93-95
INDEX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
INITIAL START-UP CHECKLIST FOR
19XR SEMI-HERMETIC TWO-STAGE
CENTRIFUGAL LIQUID CHILLER. . . . . . .CL-1 to CL- 10
3

INTRODUCTION

Prior to initial start-up of the 19XR unit, those involved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. Procedures in this manual are arranged in the sequence re­quired for proper chiller start-up and operation. This book also outlines the control system for those involved in the start-up, operation and maintenance of the unit before performing start­up procedures. It is intended to be used in combination with the 19XR Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers Controls Operation and Troubleshooting man­ual that describes PIC 5 controls in detail.
CAUTION
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio com­munications. The PIC 5 control boards have been tested and found to comply with the limits for a Class A comput­ing device pursuant to International Standard in North America EN 61000-2/3 which are designed to provide rea­sonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interfer­ence.
Always store and transport replacement or defective boards in anti-static shipping bag.
CAUTION
Do NOT punch holes or drill into the top surface of the starter enclosure for field wiring. Knockouts are provided for field wiring connections.
CAUTION
PROVIDE MACHINE PROTECTION. Store machine and starter indoors, protected from construction dirt and moisture. Inspect under shipping tarps, bags or crates to be sure water has not collected during transit. Keep protective shipping covers in place until machine is ready for installation.
CAUTION
WHEN FLUSHING THE WATER SYSTEMS isolate the chiller from the water circuits to prevent damage to the heat exchanger tubes.

ABBREVIATIONS AND EXPLANATIONS

Frequently used abbreviations in this manual include:
CCN Carrier Comfort Network ECDW — Entering Condenser Water ECW Entering Chilled Water EMS Energy Management System HGBP Hot Gas Bypass HMI Human Machine Interface I/O Input/Output ISM Integrated Starter Module LCDW — Leaving Condenser Water LCW Leaving Chilled Water LED Light-Emitting Diode OLTA Overload Trip Amps PIC 5 Product Integrated Controls 5 RLA Rated Load Amps SCR Silicon Controlled Rectifier TXV Thermostatic Expansion Valve VFD Variable Frequency Drive
Factory-installed additional components are referred to as options in this manual; factory-supplied but field-installed ad­ditional components are referred to as accessories.
®
CHILLER FAMILIARIZATION (Fig. 1 and 2) Chiller Information Nameplate —
nameplate is located on the right side of the chiller control panel.
The information
System Components — The components include the
cooler and condenser heat exchangers in separate vessels, motor-compressor, lubrication package, control panel, econo­mizer, and motor starter. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is lo-
cated underneath the compressor. The cooler is maintained at lower temperature/pressure so evaporating refrigerant can re­move heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher tem-
perature/pressure than the cooler and has water flowing through its internal tubes in order to remove heat from the re­frigerant.
Motor-Compressor — This component maintains sys-
tem temperature and pressure differences and moves the heat­carrying refrigerant from the cooler to the condenser. The 19XR two-stage frame 6 and frame 7 compressors are two­stage compressors with two impellers.
Control Panel — The control panel is the user interface
for controlling the chiller. It regulates the chiller’s capacity as required to maintain proper leaving chilled water temperature. The control panel:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating condition and alarm shutdown
conditions
• records the total chiller operating hours
• sequences chiller start, stop, and recycle under micropro-
cessor control
• displays status of motor starter
• provides access to other CCN (Carrier Comfort Net-
• supports languages that may be pre-installed at factory,
®
work
) devices and energy management systems
including English, Chinese, Spanish, French, and
German.
4
Economizer — This chamber reduces the refrigerant pres-
636
Motor Size Code
Compressor Frame Size 6
G (2250 HP, copper rotor) H (2375 HP, copper rotor) J (2500 HP, copper rotor) K (2625 HP, copper rotor) L (2750 HP, copper rotor) N — 1500 HP P — 1625 HP Q — 1750 HP R — 1875 HP S — 2000 HP T — 2100 HP
Compressor Frame Size 7
U — 2250 HP V — 2375 HP W — 2500 HP
X — 2625 HP Y — 2750 HP Z — 2900 HP
Motor V oltage Code Code Volts-Phase-Hertz
Special Order Indicator – — Standard S — Special Order
M
N7
Gear Code
Compressor Frame Size 6
E J M P
Compressor Frame Size 7
R T V X Y
Compressor Size Code
Frame Size (12th Digit)
6 — Frame Size 6 7 — Frame Size 7
Centrifugal Liquid Chiller
Description 19XR– — High Efficiency Semi-Hermetic
19XR
A45
A47
Cooler Size Code (Digits 6, 7, 8)
A40-A42 A45-A47 A4A-A4C* A4F-A4H* A60-A62 A65-A67 A6A-A6C* A6F-A6H* B60-B62 B65-B67 B80-B82** B85-B-87** B6A-B6C* B6F-B6H* B8A-B8C** B8F-B8H C60-C62 C65-C67 C6A-C6C* C6F-C6H*
Condenser Size Code (Digits 9, 10, 11)
A40-A42 A45-A47 A4A-A4C* A4F-A4H* A60-A62 A65-A67 A6A-A6C* A6F-A6H* B40-B42 B45-B47 B4A-B4C* B4F-B4H* B60-B62 B65-B67 B6A-B6C* B6F-B6H* C60-C62 C65-C67 C80-C82 ** C85-C87** C6A-C6C* C6F-C6H* C8A-C8C** CF-C8H D60-D62 D65-D67 D6A-D6C* D6F-D6H*
Shroud Size (13th Digit)
1 2 3 4 (Frame Size 6 Only)
Impeller Diameter (14th Digit)
2 4 6 8 0
3000-3-50 3300-3-50
6300-3-50 10000-3-50 11000-3-50
2400-3-60
3300-3-60
4160-3-60
6900-3-60 11000-3-60 13800-3-60
— — — — — — — — — — —
4 5 6 7
8 E F
G H
J
K
Fig. 1 — 19XR Two-Stage Chiller Model Number Nomenclature
*Frame sizes with A-C and F-H are with 1-in. OD evaporator tubing.
sure to an intermediate level between the cooler and condenser vessels. In the economizer, vapor is separated from the liquid, the separated vapor flows to the second stage of the compres­sor, and the liquid flows into the cooler. The energy removed from the vaporized refrigerant in the economizer allows the
liquid refrigerant in the cooler to absorb more heat when it evaporates and benefits the overall cooling efficiency cycle.
Free-Standing Starter — The starter allows for the
proper start and disconnect of electrical energy for the com­pressor-motor, oil pump, oil heater, and control panel.
Week of Year
Year of Manufacture
SERIAL NUMBER STRUCTURE
5
12 15 Q 19843
Unique Number
Place of Manufacture
a19-2271
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Fig. 2 — Typical 19XR 1500-3000 Ton Two-Stage Compressor Chiller Compone nts
(XR6 Shown)
REAR VIEW
FRONT VIEW
LEGEND
1—Guide Vane Actuator 2—Suction Elbow 3—Chiller Identification Nameplate 4—Control Panel 5—Condenser Auto. Reset Relief Valves 6—Condenser Return End Waterbox Cover 7—Cooler Return End Waterbox Cover 8—Cooler Auto. Reset Relief Valves
9—Cooler Pressure Transducer 10 — Liquid Line Isolation Valve (Optional) 11 — Refrigerant Storage Tank Connection Valve 12 — HMI (Human Machine Interface) Control Panel 13 — Typical Flange Connection 14 — Oil Level Sight Glasses 15 — Compressor Motor Housing
LEGEND
16 — Oil Cooler
17 — Oil Drain Changing Valve (Hidden)
18 — Motor Sight Glass
19 — Cooler In/Out Temperature Thermistors
20 — Typical Waterbox Drain Port
21 — Vessel Take-Apart Connector
22 — Condenser In/Out Temperature Thermistors
23 — ASME Nameplate
24 — Refrigerant Moisture/Flow Indicator
25 — Refrigerant Filter/Drier
26 — High Side Float Chamber
27 — High Side Float Ball Valve Assembly (Inside)
28 — Economizer Assembly 29 — Economizer Float Ball Assembly (Inside) 30 — Cooler Auto. Reset Relief Valve 31 — Condenser Pressure Transducer 32 — Refrigerant Charging Valve/Pumpout
Connection
33 — Damper Valve 34 — Discharge Isolation Valve (Optional)
6

REFRIGERATION CYCLE

Fig. 3 — Refrigeration Cycle — 19XR Two-Stage Compressor Frame Sizes 6 and 7
The compressor continuously draws refrigerant vapor from the cooler at a rate set by the amount of guide vane opening. As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low temperature (typical­ly 38 to 42 F [3 to 6 C]). The energy required for boiling is ob­tained from the water flowing through the cooler tubes. With heat energy removed, the water becomes cold enough to use in an air-conditioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90 F [18 to 32 C]) water flowing into the condenser tubes removes heat from the refrig­erant, and the vapor condenses to liquid. The liquid refrigerant passes through orifices into the FLASC (flash subcooler) chamber. Since the FLASC chamber is at a lower pressure, part of the liquid refrigerant flashes to vapor, thereby cooling the re­maining liquid. The FLASC vapor is recondensed on the tubes which are cooled by entering condenser water. The liquid
ISOLATION VALVE (OPTION)
drains into a high side float valve chamber between the FLASC chamber and the economizer. The refrigerant is then metered into the economizer. In the economizer, due to lower pressure, as liquid enters the chamber, some liquid will flash into a vapor and cool the remaining liquid. The separated vapor flows to the second stage of the compressor for greater cycle efficiency. A damper valve located on the economizer line to the compressor acts as a pressure regulating device to stabilize low load, low condensing pressure operating conditions. The damper will back up gas flow and thereby raises the economizer pressure to permit proper refrigerant flow through the economizer valve during those conditions.
The cooled liquid left in the economizer flows through a low side float valve and then into the cooler. The float valve forms a liquid seal to keep vapor from entering the cooler. Liq­uid refrigerant passes through the low side valve into the cool­er. The refrigerant is now at a temperature and pressure at which the cycle began. Fig. 3 summarizes the refrigeration cycle.
FLASC CHAMBER
THERMOSTATIC EXPANSION VALVE (TXV)
ROTOR
ORIFICE FITTING
OIL COOLER
TRANSMISSION
IMPELLERS
BACK PRESSURE ORIFICE (INTEGRAL TO MOTOR SHELL)
COMPRESSOR
HIGH SIDE FLOAT CHAMBER
HIGH SIDE FLOAT VALVE
DAMPER VALVE
REFRIGERANT
ISOLATION VALVE
ECONOMIZER
LOW SIDE FLOAT VALVE
HOT GAS BYPASS
HGBP VALVE
CONDENSER WATER
REFRIGERANT LIQUID
REFRIGERANT VAPOR
REFRIGERANT LIQUID/VAPOR
CHILLED WATER
COOLER ISOLATION VALVE (OPTION)
7

MOTOR AND OIL COOLING CYCLE

The motor and the lubricating oil are cooled by liquid refriger­ant taken from the bottom of the condenser vessel (Fig. 3 and
4). Refrigerant flow is maintained by the pressure differential that exists due to compressor operation. After the refrigerant flows past an isolation valve, an in-line filter, and a sight glass/ moisture indicator, the flow is split between the motor cooling and oil cooling systems.
Flow to the motor cooling system passes through an orifice and into the motor. Once past the orifice, the refrigerant is di­rected over the motor by spray nozzles. The refrigerant collects in the bottom of the motor casing and is then drained back into the cooler through the motor refrigerant drain line. An orifice (in the motor shell) maintains a higher pressure in the motor shell than in the cooler. The motor is protected by a tempera­ture sensor embedded in the stator windings. An increase in motor winding temperature past the motor override set point overrides the temperature capacity control to hold, and if the motor temperature rises 10 F (5.5 C) above this set point, the controls close the inlet guide vanes. If the temperature rises above the safety limit, the compressor shuts down.
Refrigerant that flows to the oil cooling system is regulated by expansion valves. The expansion valves regulate flow into the oil/refrigerant plate and frame-type heat exchanger (the oil cooler in Fig. 3), and control oil temperature to the bearings. The refrigerant leaving the oil cooler heat exchanger returns to the chiller cooler.

LUBRICATION CYCLE

Summary —
up a package located partially in the transmission casing of the compressor-motor assembly. The oil is pumped into a filter assembly to remove foreign particles and is then forced into an oil cooler heat exchanger where the oil is cooled to proper op­erational temperatures. After the oil cooler, part of the flow is directed to the gears and the high speed shaft bearings; the re­maining flow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to complete the cycle (Fig. 3 and
4).
The oil pump, oil filter, and oil cooler make
Details — Oil is charged into the lubrication system through
a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump tem­perature is displayed on the HMI default screen. During com­pressor operation, the oil sump temperature ranges between 125 and 150 F (52 and 66 C).
The oil pump suction is fed from the oil reservoir. An oil pressure relief valve maintains differential pressure in the sys­tem at the pump discharge. A range of 18 to 40 psid (124 to 172 kPad) is normal. This differential pressure can be read di­rectly from the default HMI screen. The oil pump discharges oil to the oil filter assembly. This filter can be closed to permit removal of the filter without draining the entire oil system. The oil is then piped to the oil cooler heat exchanger. The oil cooler uses refrigerant from the condenser as the coolant. The refrig­erant cools the oil to a temperature between 120 and 140 F (49 and 60 C).
As the oil leaves the oil cooler, it passes the oil pressure transducer and the sensor for the refrigerant expansion valve on the oil cooler. The oil is then divided. Part of the oil flows to the thrust bearing, forward pinion bearing, and gear spray. The rest of the oil lubricates the motor shaft bearings and the rear pinion bearing. The oil temperature is measured in the bearing hous­ing as it leaves the bearings. The oil then drains into the oil res­ervoir at the base of the compressor. The control measures the temperature of the oil in the sump and maintains the tempera­ture during shutdown. This temperature is read on the HMI de­fault screen. See the Controls Operation and Troubleshooting Manual for details.
During the chiller start-up, the oil pump is energized and provides 40 seconds of lubrication to the bearings after pres­sure is verified before starting the compressor. During shut­down, the oil pump runs for 60 seconds to ensure lubrication as the compressor coasts to a stop.
The oil pump is a gerotor-style pump with external filters. A gerotor pump has two rotors, one is inside the other; their center points are offset with respect to each other. This type of pump provides a smooth continuous flow. It is also quieter than other designs. See Fig. 5.
Bearings — The 19XR compressor assemblies include a
combination of radial bearings and thrust bearings. The low speed shaft assembly is supported by two journal bearings lo­cated on each end of the low speed shaft. The bearing closer to the bull gear includes a smaller babbitted thrust face, designed to handle axial forces.
Oil Reclaim System — The oil reclaim system returns
oil lost from the compressor housing back to the oil reservoir by recovering the oil from 2 areas on the chiller. The guide vane housing is the primary area of recovery. Oil is also recov­ered by skimming it from the operating refrigerant level in the cooler vessel.
PRIMARY OIL RECOVERY MODE — Oil is normally re­covered through the guide vane housing on the chiller. This is possible because oil is normally entrained with refrigerant in the chiller. As the compressor pulls the refrigerant up from the cooler into the guide vane housing to be compressed, the oil normally drops out at this point and falls to the bottom of the guide vane housing where it accumulates. Using discharge gas pressure to power an eductor, the oil is drawn from the housing and is discharged into the oil reservoir.
SECONDARY OIL RECOVERY METHOD — The sec­ondary method of oil recovery is significant under light load conditions, when the refrigerant going up to the compressor suction does not have enough velocity to bring oil along. Under these conditions, oil collects in a greater concentration at the top level of the refrigerant in the cooler. Using discharge gas to power eductors, this oil and refrigerant mixture is skimmed from the side of the cooler and is then drawn up to the guide vane housing. There is a filter in this line. Because the guide vane housing pressure is much lower than the cooler pressure, the refrigerant boils off, leaving the oil behind to be collected by the primary oil recovery method.
8
10
Fig. 4 — 19XR Two-Stage Compressor Lubrication System
LEGEND
1—Motor Stator 6— Oil Heater 2—Impellers 7— Oil Pump 3—Variable Inlet Guide Vanes 8— Oil Filters 4—Transmission 9— Motor Rotor 5—High Speed Shaft Bearings 10— Motor Shaft Bearings
a19-
1
2
3
4
5
6
7
8
Fig. 5 — Gerotor Oil Pump
a19-2116
LEGEND
1—Gerotor Oil Pump 2—Oil Pressure Regulator Valve 3—Oil Sump Pressure Transducer 4—Oil Sump Drain Valve 5—High Speed Compressor End Bearing,
Temperature Terminal Block
6—Low Speed Compressor End Bearing,
Temperature Cable
7—Compressor Oil Sump Temperature 8—Oil Heater
9
OIL LINE VENT LINE
1
2
3
4
5
6
7
8
9

STARTING EQUIPMENT

The 19XR chiller requires a motor starter to operate the cen­trifugal hermetic compressor motor, the oil pump, and various auxiliary equipment components. The starter is the main field wiring interface for the contractor.
See Carrier’s specification for specific starter requirements. All starters must meet these specifications in order to properly start and satisfy mechanical safety requirements.
It is possible that there are two separate circuit breakers in­side the starter. These include (1) the main compressor motor circuit breaker, and (2) a circuit breaker which provides power to the chiller control panel. The latter is typically wired in par­allel with the first so that power is provided to those services when the main breaker is open. The disconnect switch on the starter front cover is connected to the main breaker. Typically, separate 3-phase power sources as per job requirements are supplied to the control panel to power the oil pump, heater, and controls.
The display on the front of the solid-state starter is useful for
troubleshooting and starter checkout. The display indicates:
• line voltage
• control voltage status
• power indication
• proper phasing for rotation
• start circuit energized
• ground fault
• current unbalance
•run state The starter is further explained in the Check Starter section,
page 19.
Freestanding Medium Voltage VFD (Optional) —
can be combined with a VFD (variable frequency drive). This option is a freestanding, medium voltage current source drive that does not require a transformer between the power source and the drive. The drive meets IEEE-519 specifications.
For optimum efficiency, the 19XR chiller
WARNING
The main circuit breaker on the front of the starter discon­nects the main motor power only. Power may be still ener­gized for other circuits. Always check wiring diagrams before initiating any work on the chiller and follow appli­cable lock-out/tag-out procedures. Failure to disconnect power will result in personal injury.
All starters must include a Carrier control module called the Integrated Starter Module (ISM). This module controls and monitors all aspects of the starter. See the Controls Operation and Troubleshooting guide for additional ISM information. Contact Carrier’s Replacement Component Division (RCD) for replacement parts.
Solid-State Starter (Optional) — The 19XR chiller
may be equipped with a solid-state, reduced-voltage starter. This starter’s primary function is to provide on-off control of the compressor motor. This type of starter reduces the peak starting torque, controls the motor inrush current, and decreases mechanical shock. This capability is summed up by the phrase “soft starting.” Consult E-Cat for full information about starter offerings. The solid-state starter manufacturer’s name is locat­ed inside the starter access door.
A solid-state, reduced-voltage starter operates by reducing the starting voltage. The starting torque of a motor at full volt­age is typically 125% to 175% of the running torque. When the voltage and the current are reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting voltage to adjust the voltage necessary to develop the torque re­quired to get the motor moving. The voltage is reduced by sili­con controlled rectifiers (SCRs). The voltage and current are then ramped up in a desired period of time. Once full voltage is reached, a bypass contactor is energized to bypass the SCRs.
WARNING
When voltage is supplied to the solid-state circuitry (CB1 is closed), the heat sinks in the starter as well as the wires leading to the motor and the motor terminal are at line volt­age. Do not touch the heat sinks, power wiring, or motor terminals while voltage is present or serious injury will result.

CONTROLS

Definitions

ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an analog device be­cause its resistance changes in proportion to the temperature, generating many values.)
DISCRETE SIGNAL — A discrete signal is a 2-position rep­resentation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.)
General — The 19XR centrifugal liquid chiller contains a
microprocessor-based control center that monitors and controls all operations of the chiller. The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and reg­ulating the inlet guide vane via a mechanically linked actuator motor. The guide vane is a variable flow pre-whirl assembly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor. An increase in guide vane opening increases capacity. A decrease in guide vane opening decreases capacity. The microprocessor­based control center protects the chiller by monitoring the digi­tal and analog inputs and executing capacity overrides or safety shutdowns, if required.
PIC 5 System Components — The chiller control
system is called the PIC 5 (Product Integrated Control 5). See Table 1. As with previous PIC versions, the PIC 5 system con­trols the operation of the chiller by monitoring all operating conditions. The PIC 5 control system can diagnose a problem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to maintain leav­ing chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off and regulates the hot gas bypass valve, if installed. The PIC 5 controls provide critical protec­tion for the compressor motor and control the motor starter.
10
Table 1 — Major PIC 5 Components and
Fig. 6 — Chiller Start/Stop Icon
Fig. 7 — Local On
a19-2118
Panel Locations
PIC 5 COMPONENT PANEL LOCATION
Chiller Human Machine Interface (HMI) and Display
Integrated Starter Module (ISM) Starter Cabinet Chiller IO Boards Control Panel Oil Heater Contactor (1C) Control Panel Oil Pump Contactor (2C) Control Panel Hot Gas Bypass Relays (HCLR, HOPR)
(Optional) Control Transformers (T1, T2, T3) Control Panel Temperature Sensors See Fig. 2 and Fig. 5 Pressure Transducers See Fig. 2 and Fig. 5
HMI Control Panel
Control Panel
NOTE: For detailed information about the PIC 5 HMI (human machine interface), see the 19XR with PIC 5 Controls Opera­tion and Troubleshooting manual.
START-UP/SHUTDOWN/
RECYCLE SEQUENCE
Local Start/Stop Control —
start-up) is initiated by pressing the the gray Start/Stop icon on the HMI interface. See Fig. 6.
This initiates the PIC 5 starting sequence by displaying the list of operating modes. Press Local On to initiate start-up. See Fig. 7.
Local start-up (or manual
When start-up is initiated the status screen displays the start-
up progress and the Start/Stop icon blinks green.
Once local start-up begins, the PIC 5 control system per­forms a series of pre-start tests to verify that all pre-start alerts and safeties are within acceptable limits. Table 2 shows appro­priate Prestart Alerts/Alarms conditions. If a test is not success­ful, the start-up is delayed or aborted. If the tests are successful, the start-up will be in progress and the COMPRESSOR RUN STATUS shall be “Startup.” The control shall then energize the chilled water/brine pump relay.
Five seconds later, the condenser pump relay energizes. Thirty seconds later the PIC 5 control system monitors the chilled water and condenser water flow devices and waits until the WATER FLOW VERIFY TIME (operator-configured, de­fault 5 minutes) expires to confirm flow. After flow is verified, the chilled water temperature is compared to CONTROL POINT plus 1/2 CHILLED WATER DEADBAND. If the tem­perature is less than or equal to this value, the PIC 5 control system turns off the condenser pump relay and goes into a Re­cycle mode.
If the water/brine temperature is high enough, the start-up sequence continues and checks the guide vane position. If the guide vanes are more than 4% open, the start-up waits until the PIC 5 control system closes the vanes. If the vanes are closed and the oil pump pressure is less than 4 psi (27.6 kPa), the oil pump relay energizes. The PIC 5 control system then waits un­til the oil pressure (OIL PRESS VERIFY TIME, operator-con­figured, default of 40 seconds) reaches a maximum of 18 psi (124 kPa). After oil pressure is verified, the PIC control system waits 40 seconds, and the compressor start relay (1CR) ener­gizes to start the compressor.
Compressor ontime and service ontime timers start, and the compressor STARTS IN 12 HOURS counter and the number of starts over a 12-hour period counter advance by one.
Failure to verify any of the requirements up to this point will result in the PIC 5 control system aborting the start and display­ing the applicable pre-start alert alarm state number near the bottom of the home screen on the HMI panel. A prestart failure does not advance the STARTS IN 12 HOURS counter. Any fail- ure after the 1CR relay has energized results in a safety shut­down, advances the starts in 12 hours counter by one, and dis­plays the applicable shutdown status on the display.
The minimum time to complete the entire prestart sequence is approximately 185 seconds. See Fig. 8 for normal start-up timing sequence. See Table 2 for a list of prestart checks.
Unit Start/Stop
NOTE: Prior to start-up the start-to-start timer and the stop-to­start timer must have elapsed and all alarms must be cleared (see Troubleshooting Guide section on page 42).
11
Table 2 — Prestart Checks
AB
CDE
F
G
O/A
A—START INITIATED: Pre-start checks are made; evaporator pump
started.*
B—Condenser water pump started (5 seconds after A). C—Water flows verified (30 seconds to 5 minutes maximum after B).
Chilled water temperatures checked against control point. Guide vanes checked for closure. Oil pump started; tower fan control enabled.
D—Oil pressure verified (15 seconds minimum, 300 seconds maximum
after C).
E—Compressor motor starts; compressor ontime and service ontime
start, 15-minute inhibit timer starts (10 seconds after D), total com­pressor starts advances by one, and the number of starts over a 12-hour period advances by one.
F—SHUTDOWN INITIATED — Compressor motor stops; compressor
ontime and service ontime stop, and 1-minute inhibit timer starts.
G—Oil pump and evaporator pumps deenergized (60 seconds after F).
Condenser pump and tower fan control may continue to operate if condenser pressure is high. Evaporator pump may continue if in RECYCLE mode.
O/A — Restart permitted (both inhibit timers expired: minimum of 15 min-
utes after E; minimum of 1 minute after F).
Fig. 8 — Control Timing Sequence
for Normal Start-Up
* Auto Restart After Power Failure Timing sequence will be faster.
Fig. 9 — Confirm Stop
a19-2122
Unit Start/Stop
PRESTART CHECK CONDITION* STATE NUMBER
STARTS IN 12 HOURS 8 (not counting recycle restarts or auto restarts after power failure) Alert – 100 OIL SUMP TEMP 140° F (60° C) and OIL SUMP TEMP EVAP_SAT + 50° F (27.8° C) Alert – 101 COND PRESSURE COND PRESS OVERRIDE – 20 psi Alert – 102 #RECYCLE RESTARTS LAST 4 HOURS > 5 Alert – 103 COMP BEARING TEMPS COMP BEARING ALERT– 10° F (5.6° C) Alarm – 230 COMP MOTOR WINDING TEMP COMP MOTOR WINDING– 10° F (5.6° C) Alarm – 231 COMP DISCHARGE TEMPERATURE COMP DISCHARGE ALERT– 10° F (5.6° C) Alarm – 232 EVAP_SAT <Evap trip point** + EVAP OVERRIDE DELTA T Alarm – 233 EVAP REFRIG LIQUID TEMP <Evap trip point** + EVAP OVERRIDE DELTA T Alarm – 233 AVERAGE LINE VOLTAGE UNDERVOLTAGE THRESHOLD Alarm – 234 AVERAGE LINE VOLTAGE OVERVOLTAGE THRESHOLD Alarm – 235 CHECK FOR GUIDE VANE CALIBRATION Alarm – 236
* If Prestart Check Condition is True, then resulting State is as indicated in the State Number column.
See the Controls Operation and Troubleshooting guide for alarm and alert codes.
**Evap trip point = 33 F (0.6 C) (water) or EVAP REFRIG TRIPPOINT (brine)
The oil heater relay is energized whenever the chiller com­pressor is off and the oil sump temperature is less than 140 F (60 C) or the oil sump temperature is less than the evaporator saturated refrigerant temperature plus 53° F (29.4° C). The oil heater is turned off when either of the following conditions is true:
• Oil sump temperature is more than 152 F (66.7 C)
• Oil sump temperature is more than 144 F (62.2 C) and
more than the evaporator saturated refrigerant tempera-
ture plus 55° F (30.6° C) The oil heater is always off when the compressor is running.
The oil pump is also energized for 30 seconds after each 30 minutes of oil heat relay being energized in order to stir the oil for more evenly distributed heating.
Shutdown — The unit can be stopped locally using the
HMI by pressing the green Start/Stop icon . The Unit Start/ Stop screen is displayed. Press Confirm Stop (see Fig. 9).
Lubrication Control — As part of the prestart checks
executed by the controls, the oil sump temperature is compared to the evaporator saturated refrigerant temperature. If the oil temperature is less than 140 F (60 C) and less than evaporator saturated refrigerant temperature plus 50° F (27.8° C), the start-up will be delayed until either of these conditions is no longer true. Once this temperature is confirmed, the start-up continues.
12

BEFORE INITIAL START-UP

Fig. 10 — Typical Wet-Bulb Type
Vacuum Indicator

Job Data Required

• list of applicable design temperatures and pressures (product data submittal)
• chiller certified prints
• starting equipment details and wiring diagrams
• diagrams and instructions for special controls or options
• 19XR Installation Instructions

Equipment Required

• mechanic’s tools (refrigeration)
• digital volt-ohmmeter (DVM)
• true RMS (root mean square) digital multimeter with clamp-on current probe or true RMS digital clamp-on ammeter for at least 480 vac
• electronic leak detector
• absolute pressure manometer or wet-bulb vacuum indicator (see Fig. 10)
• insulation tester for compressor motor rated at motor design voltage
Remove Shipping Packaging — Remove any pack-
aging material from the unit and starter.
Open Oil Circuit Valves — Check to ensure the oil fil-
ter isolation valves are open by removing the valve cap and checking the valve stem.
Tighten All Gasketed Joints — Gaskets normally
relax by the time the chiller arrives at the jobsite. Tighten all gasketed joints to ensure a leak-tight chiller (does not apply to refrigerant joints covered by factory insulation). Gasketed joints (excluding O-rings) may include joints at some or all of the following:
• waterbox covers
• compressor suction elbow flanges (at compressor and at the cooler)
• compressor discharge flange
• compressor discharge line spacer (both sides) if no isolation valve
• cooler inlet line spacer (both sides) if no isolation valve
• hot gas bypass valve (both sides of valve)
• hot gas bypass flange at compressor
See Tables 3 and 4 for bolt torque requirements.
Check Chiller Tightness — Figure 11 outlines the
proper sequence and procedures for leak testing.
The 19XR chillers are shipped with the refrigerant con-
tained in the condenser shell and the oil charge in the compres­sor. The cooler is shipped with a 15 psig (103 kPa) refrigerant charge. Units may be ordered with the refrigerant shipped sepa­rately, along with a 15 psig (103 kPa) nitrogen-holding charge in each vessel.
To determine if there are any leaks, the chiller should be
charged with refrigerant. Use an electronic leak detector to check all flanges and solder joints after the chiller is pressur­ized. If any leaks are detected, follow the leak test procedure (page 16).
If the chiller is spring isolated, keep all springs blocked in
both directions to prevent possible piping stress and damage during the transfer of refrigerant from vessel to vessel during the leak test process, or any time refrigerant is being trans­ferred. Adjust the springs when the refrigerant is in operating condition and the water circuits are full.
13
Table 3 — Bolt Torque Requirements, Foot Pounds
SAE 8
HEX HEAD
SA354 GR BD
BOLT SIZE
(in.)
SAE 2, A307 GR A
HEX HEAD
NO MARKS
LOW CARBON STEEL
SOCKET HEAD OR HEX
WITH 3 RADIAL LINES, OR SA499
MEDIUM CARBON STEEL
SAE 5
WITH 6 RADIAL LINES OR
MEDIUM CARBON STEEL
MINIMUM MAXIMUM MINIMUM MAXIMUM MINIMUM MAXIMUM
1
/
4
5
/
16
3
/
8
7
/
16
1
/
2
9
/
16
5
/
8
3
/
4
7
/
8
46 69913
811 13182028 13 19 22 31 32 46 21 30 35 50 53 75 32 45 53 75 80 115 46 65 75 110 115 165 65 95 105 150 160 225
105 150 175 250 260 370 140 200 265 380 415 590
1 210 300 410 580 625 893
1
/
1
8
1
/
1
4
3
1
/
8
1
/
1
2
5
/
1
8
3
1
/
4
7
/
1
8
330 475 545 780 985 1,410 460 660 770 1,100 1,380 1,960 620 885 1,020 1,460 1,840 2,630
740 1060 1,220 1,750 2,200 3,150 1010 1450 1,670 2,390 3,020 4,310 1320 1890 2,180 3,110 3,930 5,610 1630 2340 2,930 4,190 5,280 7,550
2 1900 2720 3,150 4,500 5,670 8,100
1
/
2
4
1
/
2
2
3
/
2
4
2180 3120 4,550 6,500 8,200 11,710 3070 4380 5,000 7,140 11,350 16,210 5120 7320 8,460 12,090 15,710 22,440
3 6620 9460 11,040 15,770 19,900 28,440
Table 4 — Bolt Torque Requirements, Foot Pounds (Metric Bolts)
BOLT SIZE
(METRIC)
MINIMUM MAXIMUM MINIMUM MAXIMUM
M4 1.75 2.5 2.5 3.5 M6 69812
M8 14 20 20 30 M10 28 40 40 57 M12 48 70 70 100 M16 118 170 170 240 M20 230 330 330 470 M24 400 570 570 810 M27 580 830 820 1175
CLASS 8.8 CLASS 10.9
14
5 AND 6)
5 AND 6)
Fig. 11 — 19XR Leak Test Procedures
a19-1151tf.eps
15
Refrigerant Tracer — Carrier recommends the use of an
environmentally acceptable refrigerant tracer for leak testing with an electronic detector.
Ultrasonic leak detectors can also be used if the chiller is
under pressure.
WARNING
Do not use air or oxygen as a means of pressurizing the chiller. Mixtures of HFC-134a and air can undergo combustion, resulting in equipment damage and possible personal injury.
Leak Test Chiller — Due to regulations regarding refrig-
erant emissions and the difficulties associated with separating contaminants from the refrigerant, Carrier recommends the following leak test procedure. Refer to Tables 5 and 6 for re­frigerant pressure/temperature values.
1. If the pressure readings are normal for the chiller condition:
a. Evacuate the holding charge from the vessels, if
present.
b. Raise the chiller pressure, if necessary, by adding
refrigerant until pressure is at the equivalent satu­rated pressure for the surrounding temperature. Follow pumpout procedures in the Transfer Refrig­erant from Pumpout Storage Tank to Chiller sec­tion, Steps 1a-e, page 34.
CAUTION
Never charge liquid refrigerant into the chiller if the pres­sure in the chiller is less than 35 psig (241 kPa) for HFC­134a. Charge as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN/LOCKOUT (located in the Maintenance menu) and TERMINATE LOCKOUT mode on the PIC 5 control interface. Flashing of liquid refrigerant at low pres­sures can cause tube freeze-up and considerable damage.
c. Leak test chiller as outlined in Steps 3 to 9.
2. If the pressure readings are abnormal for the chiller con­dition:
a. Prepare to leak test chillers shipped with refriger-
ant (Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap test all joints. If the test pressure holds for 30 minutes,
prepare the test for small leaks (Steps 2g and 2h). c. Plainly mark any leaks that are found. d. Release the pressure in the system. e. Repair all leaks. f. Retest the joints that were repaired. g. After successfully completing the test for large
leaks, remove as much nitrogen, air, and moisture
as possible, given the fact that small leaks may be
present in the system. This can be accomplished by
following the dehydration procedure outlined in
the Chiller Dehydration section, page 18. h. Slowly raise the system pressure to a maximum of
160 psig (1103 kPa) but no less than 35 psig
(241 kPa) for HFC-134a by adding refrigerant.
Proceed with the test for small leaks (Steps 3 to 9).
3. Check the chiller carefully with an electronic leak detec­tor or soap bubble solution.
4. Leak Determination — If an electronic leak detector indi­cates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chiller. Leakage at rates greater than 0.1% of the total charge per year must be repaired. Note the total chiller leak rate on the start-up report.
5. If no leak is found during the initial start-up procedures, complete the transfer of refrigerant gas from the storage tank to the chiller. Retest for leaks.
6. If no leak is found after a retest: a. Transfer the refrigerant to the storage tank and per-
form a standing vacuum test as outlined in the Standing Vacuum Test section, below.
b. If the chiller fails the standi ng vacuum test, check
for large leaks (Step 2b).
c. If the chiller passes the standing vacuum test,
dehydrate the chiller. Follow the procedure in the Chiller Dehydration section, page 18. Charge the chiller with refrigerant.
7. If a leak is found after a retest, pump the refrigerant back into the storage tank or, if isolation valves are present, pump the refrigerant into the non-leaking vessel. See the Transfer Refrigerant from Pumpout Storage Tank to Chiller section on page 34.
8. Transfer the refrigerant until the chiller pressure is at 18 in. Hg (40 kPa absolute).
9. Repair the leak and repeat the procedure, beginning from Step 2h, to ensure a leak-tight repair. (If the chiller is opened to the atmosphere for an extended period, evacu­ate it before repeating the leak test.)
Standing Vacuum Test — When performing the
standing vacuum test or chiller dehydration, use a manometer or a wet bulb indicator. Dial gages cannot indicate the small amount of acceptable leakage during a short period of time.
1. Attach an absolute pressure manometer or wet bulb indi­cator to the chiller.
2. Evacuate the vessel to at least 18 in. Hg vac (41 kPa [abs]), using a vacuum pump or the pumpout unit.
3. Valve off the pump to hold the vacuum and record the manometer or indicator reading.
4. a.
5. Repair the leak, retest, and proceed with dehydration.
If the leakage rate is less than 0.05 in. Hg (0.17 kPa) in 24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (0.17 kPa)
24 hours, re-pressurize the vessel and test for leaks if refrigerant is available. If not, use nitrogen and a refrigerant tracer. Raise the vessel pressure in incre­ments until the leak is detected. If refrigerant is used, the maximum gas pressure is approximately 70 psig (483 kPa) for HFC-134a at normal ambient temperature. If nitrogen is used, limit the leak test pressure to 160 psig (1103 kPa) maximum.
in
16
Table 5 — HFC-134a Pressure —
Temperature (F)
Table 6 — HFC-134a Pressure —
Temperature (C)
TEMPERATURE
(F)
0 6.50 2 7.52 4 8.60 6 9.66 8 10.79
10 11.96 12 13.17 14 14.42 16 15.72 18 17.06
20 18.45 22 19.88 24 21.37 26 22.90 28 24.48
30 26.11 32 27.80 34 29.53 36 31.32 38 33.17
40 35.08 42 37.04 44 39.06 46 41.14 48 43.28
50 45.48 52 47.74 54 50.07 56 52.47 58 54.93
60 57.46 62 60.06 64 62.73 66 65.47 68 68.29
70 71.18 72 74.14 74 77.18 76 80.30 78 83.49
80 86.17 82 90.13 84 93.57 86 97.09 88 100.70
90 104.40 92 108.18 94 112.06 96 116.02 98 120.08
100 124.23 102 128.47 104 132.81 106 137.25 108 141.79
110 146.43 112 151.17 114 156.01 116 160.96 118 166.01
120 171.17 122 176.45 124 181.83 126 187.32 128 192.93
130 198.66 132 204.50 134 210.47 136 216.55 138 222.76 140 229.09
PRESSURE
(PSIG)
TEMPERATURE
(C)
–18.0 44.8 –16.7 51.9 –15.6 59.3 –14.4 66.6 –13.3 74.4
–12.2 82.5 –11.1 90.8 –10.0 99.4
–8.9 108.0 –7.8 118.0
–6.7 127.0 –5.6 137.0 –4.4 147.0 –3.3 158.0 –2.2 169.0
–1.1 180.0
0.0 192.0
1.1 204.0
2.2 216.0
3.3 229.0
4.4 242.0
5.0 248.0
5.6 255.0
6.1 261.0
6.7 269.0
7.2 276.0
7.8 284.0
8.3 290.0
8.9 298.0
9.4 305.0
10.0 314.0
11.1 329.0
12.2 345.0
13.3 362.0
14.4 379.0
15.6 396.0
16.7 414.0
17.8 433.0
18.9 451.0
20.0 471.0
21.1 491.0
22.2 511.0
23.3 532.0
24.4 554.0
25.6 576.0
26.7 598.0
27.8 621.0
28.9 645.0
30.0 669.0
31.1 6
32.2 7
33.3 746.0
34.4 773.0
35.6 800.0
36.7 828.0
37.8 857.0
38.9 886.0
40.0 916.0
41.1 946.0
42.2 978.0
43.3 1010.0
44.4 1042.0
45.6 1076.0
46.7 1110.0
47.8 1145.0
48.9 1180.0
50.0 1217.0
51.1 1254.0
52.2 1292.0
53.3 1330.0
54.4 1370.0
55.6 1410.0
56.7 1451.0
57.8 1493.0
58.9 1536.0
60.0 1580.0
PRESSURE
(KPA)
94.0
20.0
17
Chiller Dehydration — Dehydration is recommended if
Fig. 12 — Dehydration Cold Trap
the chiller has been open for a considerable period of time, if the chiller is known to contain moisture, or if there has been a complete loss of chiller holding charge or refrigerant pressure.
CAUTION
Do not start or megohm-test the compressor motor or oil pump motor, even for a rotation check, if the chiller is under dehydration vacuum. Insulation breakdown and severe damage may result.
WARNING
Starters must be disconnected by an isolation switch before placing the machine under a vacuum. To be safe, isolate any starter before evacuating the chiller if you are not sure if there are live leads to the hermetic motor.
Dehydration can be done at room temperatures. Using a cold trap (Fig. 12) may substantially reduce the time required to complete the dehydration. The higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum is required to boil off any moisture. If low ambient temperatures are involved, contact a qualified service representative for the dehydration techniques required.
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm [.002 m or larger is recommended) to the refrigerant charging valve (Fig. 2). Tubing from the pump to the chiller should be as short in length and as large in diameter as possible to provide least resistance to gas flow.
2. Use an absolute pressure manometer or a wet bulb vacu­um indicator to measure the vacuum. Open the shutoff valve to the vacuum indicator only when taking a read­ing. Leave the valve open for 3 minutes to allow the indi­cator vacuum to equalize with the chiller vacuum.
3. If the entire chiller is to be dehydrated, open all isolation valves (if present).
4. With the chiller ambient tem perature at 60 F (15.6 C) or higher, operate the vacuum pump until the manometer reads 185 psig (1275 kPa), or a vacuum indicator reads 35 F (1.7 C). Operate the pump an additional 2 hours.
Do not apply a greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (0.56 C) on the wet bulb vacuum indicator. At this temperature and pressure, iso­lated pockets of moisture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low tempera­tures and pressures greatly increases dehydration time.
5. Valve off the vacuum pump, stop the pump, and record the instrument reading.
6. After a 2-hour wait, take another instrument reading. If the reading has not changed, dehydration is complete. If the reading indicates vacuum loss, repeat Steps 4 and 5.
7. If the reading continues to change after several attempts, perform a leak test up to the maximum 160 psig (1103 kPa) pressure. Locate and repair the leak, and re­peat dehydration.
8. Once dehydration is complete, the evacuation process can continue. The final vacuum prior to charging the unit with refrigerant should in all cases be 29.9 in Hg (500 microns,
0.07 kPa [abs]) or less.
3
/s]
Inspect Water Piping — Refer to piping diagrams pro-
vided in the certified drawings and the piping instructions in the 19XR Installation Instructions manual. Inspect the piping to the cooler and condenser. Be sure that the flow directions are correct and that all piping specifications have been met.
Piping systems must be properly vented with no stress on waterbox nozzles and covers. Water flows through the cooler and condenser must meet job requirements. Measure the pres­sure drop across the cooler and the condenser.
CAUTION
Water must be within design limits, clean, and treated to ensure proper chiller performance and to reduce the poten­tial of tube damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage result­ing from untreated or improperly treated water.
Check Relief Valves — Be sure the relief valves have
been piped to the outdoors in compliance with the latest edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections must allow for access to the valve mechanism for periodic inspection and leak testing.
The standard 19XR relief valves are set to relieve at 185 psig (1275 kPa) chiller design pressure.

Inspect Wiring

WARNING
Do not check the voltage supply without proper equipment and precautions. Serious injury may result. Follow power company recommendations.
CAUTION
Do not apply any kind of test voltage, even for a rotation check, if the chiller is under a dehydration vacuum. Insula­tion breakdown and serious damage may result.
1. Examine the wiring for conformance to the job wiring di­agrams and all applicable electrical codes.
2. Compare the ampere rating on the starter nameplate to rating on the compressor nameplate. The overload trip amps must be 108% to 120% of the rated load amps.
3. The starter for a centrifugal compressor motor must contain the components and terminals required for PIC 5 controls platform. Check the certified drawings.
4. Check the voltage to the components and compare it to the nameplate values.
5. Ensure that fused disconnects or circuit breakers have been supplied for the control panel.
18
6. Ensure all electrical equipment and controls are properly grounded in accordance with job drawings, certified drawings, and all applicable electrical codes.
7. Ensure the customer’s contractor has verified proper op­eration of the pumps, cooling tower fans, and associated auxiliary equipment. This includes ensuring motors are properly lubricated and have proper electrical supply and proper rotation.
8. Test the chiller compressor motor and its power lead insu­lation resistance with an insulation tester such as a meg­ohmmeter. (Use a tester rated for motor voltage.)
a. Open the starter main disconnect switch and follow
lockout/tagout rules.
CAUTION
Ensure the starter (with relay 1CR closed) goes through a complete and proper start cycle.

SOLID-STATE STARTER

WARNING
This equipment is at line voltage when AC power is con­nected. Pressing the STOP button does not remove voltage.
CAUTION
An isolation switch or circuit breaker must be open ahead of any solid-state starter when the chiller is in a vacuum. If not, damage to the machine may result.
If the motor starter is a solid-state starter, the motor leads must be disconnected from the starter before an insulation test is performed. The voltage generated from the tester can damage the starter solid-state components.
b. With the tester connected to the motor leads, take
10-second and 60-second megohm readings as follows:
3-Lead Motor and test between the group and ground.
c. Divide the 60-second resistance reading by the
10-second reading. The ratio, or polarization index, must be one or higher. Both the 10 and 60-second readings must be at least 50 megohms.
If the readings on a field-installed starter are unsat­isfactory, repeat the test at the motor with the power leads disconnected. Satisfactory readings in this second test indicate the fault is in the power leads.
— Tie terminals 1, 2, and 3 together

Check Starter

WARNING
BE AWARE that certain automatic start arrangements can engage the starter. Open the disconnect ahead of the starter
in addition to shutting off the chiller or pump. Failure to follow this procedure may result in personal injury by elec­tric shock.
Use the instruction and service manual supplied by the start­er manufacturer to verify the starter has been installed correct­ly, to set up and calibrate the starter, and for complete trouble­shooting information.
WARNING
The main disconnect on the starter front panel may not deenergize all internal circuits. Open all internal and remote disconnects before servicing the starter. Failure to follow this procedure may result in personal injury by elec­tric shock.

MECHANICAL STARTER

1. Check all field wiring connections for tightness, clear­ance from moving parts, and correct connection.
2. Check the contactor(s) to ensure they move freely. Check all other electro-mechanical devices, such as relays, for free movement. If the devices do not move freely, contact the starter manufacturer for replacement components.
3. Reapply starter control power (not main chiller power) to check the electrical functions.
1. Ensure all wiring connections are properly terminated to the starter.
2. Verify the ground wire to the starter is installed properly and is sufficient size.
3. Verify the motors are properly grounded to the starter.
4. Verify the proper ac input voltage is brought into the start­er according to the certified drawings.
5. Apply power to the starter.
Oil Charge — The oil charge for the 19XR two-stage com-
pressor frame size 6 is 29 gal (110 L); for frame size 7 the oil charge is 44.5 gal (168 L).
The chiller is shipped with oil in the compressor. When the sump is full, the oil level should be no higher than the middle of the upper sight glass, and minimum level is the bottom of the lower sight glass (Fig. 2). If oil is added, it must meet Carri­er’s specification for centrifugal compressor use as described in the Oil Specification section on page 39. Charge the oil through the oil charging valve located near the bottom of the transmission housing. The oil must be pumped from the oil container through the charging valve due to higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down.
Power Up the Controls and Check the Oil Heater —
sor and the chiller is not in a vacuum before energizing the con­trols. Typically a circuit breaker in the starter energizes the oil heater and the control circuit.
The oil heater is energized by powering the control circuit. This should be done several hours before start-up to minimize oil-refrigerant migration. The oil heater is controlled by the PIC 5 and is powered through a contactor in the control panel. A separate circuit breaker powers the heater, oil pump, and the control circuit. This arrangement allows the heater to energize when the main motor circuit breaker is off for service work or extended shutdowns.
Ensure that an oil level is visible in the compres-

Software Configuration

WARNING
Do not operate the chiller before the control configurations have been checked and a Control Test has been satisfacto­rily completed. Protection by safety controls cannot be assumed until all control configurations have been confirmed.
See the 19XR with PIC 5 Controls Operation and Trouble­shooting manual for instructions on using the PIC 5 interface to configure the 19XR unit. As the unit is configured, all configu­ration settings should be written down. A log, such as the one
19
shown on pages CL-1 to CL-8, provides a list for configuration
Fig. 13 — Main Menu Icon
Fig. 14 — Main Menu — Setpoint Table Icon
a19-2121
SETPOINT - Setpoint Table
Fig. 15 — Setpoint Table Screen
values.
Input the Design Set Points — To access the set
point screen, press the Main Menu icon on the home screen. See Fig. 13.
The Main Menu screen is displayed. Press the Setpoint Ta-
ble icon (Fig. 14).
Main Menu
The Setpoint screen is displayed (see Fig. 15). Set the base demand limit set point, and either the LCW set point or the ECW set point. To set a value, press the appropriate set point, enter the value, and press OK. For more information, see the the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
Input the Local Occupied Schedule — Access
the schedule screen and set up the occupied time schedule ac­cording to the customer’s requirements. If no schedule is avail­able, the default is factory set for 24 hours occupied, 7 days per week including holidays. The Schedule Menu as well as the Holiday Menu can be reached through the Configuration Menu (see Appendix A on page 88 for an overview of the available menus). When the control mode is LOCAL SCHEDULE, the chiller will be automatically started if the configured local schedule is occupied; it will be shut down by the unoccupied schedule, EMSTOP software point, STOP button on HMI screen, or remote emergency stop contact.
The Network Schedule should be configured if a CCN sys­tem is being installed. When control mode is NETWORK, the chiller can be started and stopped by the CHIL_S_S software point as written by other equipment through the network com­mand and network schedule. The chiller can be shut down by EMSTOP software point and remote emergency stop contact.
For more information about setting time schedules, see the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
Input Service Configurations — For specific values
for the following configurations, refer to the chiller perfor­mance data or job-specific data sheet:
• password
• log in/logout
• input time and date
• service parameters
• equipment configuration
• automated control test PASS W OR D — The PIC 5 control system provides different
levels of access: Basic access, User access, Advanced User/ Service access and Factory access. User access provides basic access to the chiller controls. Advanced User access has access to all Service tables, and Factory user has access to factory ta­bles. The PIC 5 default password configurations are as follows:
• Basic: No password required
• User: 1111
• Advanced User / Service Access: 2222
• Factory: 4444
When accessing the SERVICE tables, a password must be entered. The password can be changed from the Configuration Menu. USER CONFIGURATION allows change of the User access password. SERVICE PARAMETERS allows change of the Advanced User/Service password, and FACTORY PA­RAMETERS allows change of the Factory password. Pass­words must be from 1 to 5 digits (range from 1 to 65535).
IMPORTANT: Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless accessed by a Carrier representative.
LOGIN/LOGOUT — Press the lock icon on the home screen to enter the password. See Fig. 16.
20
Fig. 16 — Lock Icon
User Login Screen
Fig. 17 — User Login Screen
The User Login Screen is displayed. Enter the password on this screen. See Fig 17. The language and system of measure­ment can also be changed on this screen. For details, see the 19XR with PIC 5 Controls Operation and Troubleshooting guide.
INPUT TIME AND DATE — Set day and time and if appli­cable Holidays through MAIN MENU CONFIGURATION MENU  DATE/TIME CONFIGURATION. See the Con­trols Operation and Troubleshooting guide for details. Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and date have been set.
NOTE: The date format is MM-DD-YY for English units and
MODIFY CONTROLLER IDENTIFICATION IF NECES­SARY — The module address can be changed from the Con­figuration Menu. Change this address under CONTROL IDENTIFICATION for each chiller if there is more than one chiller at the jobsite. Write the new address on the HMI module for future reference.
CONFIGURE SERVICE TABLES — Access the SER­VICE tables through MAIN MENU  CONFIGURATION MENU to modify or view the job site parameters shown in Ta­ble 7. For details, see the 19XR with PIC 5 Controls Operation and Troubleshooting guide.
DD-MM-YY for SI units.
Table 7 — Job Site Parameters
PARAMETER TABLE
Starter Type Motor Rated Line Voltage CONF_ISM — Motor rated voltage from chiller information nameplate. Volt Transformer Ratio Motor Rated Load Amps CONF_ISM — Per chiller nameplate data. RL AMPS on compressor nameplate.
Motor Locked Rotor Trip CONF_ISM — Per chiller iden tification nameplate. Starter LRA Rating
Motor Current CT Ratio Current % Imbalance CONF_ISM — Current imbalance trip threshold. Enter up to 100% for starter type 3 (VFD).
Ground Fault Current Transformers CONF_ISM — Ent er 0 if no ground fault CTs are wired to terminal J5 of ISM. Enter 1 if gr ound fault CTs are used. Ground Fault CT Ratio CONF_ISM — Enter ratio (reduced to a ratio to 1) of ground fault CT. Single Cycle Dropout CONF_ISM — ENABLE if motor protection required from drop in line voltage within one cycle. Line Frequency CONF_ISM — Enter YES for 60 Hz or NO for 50 Hz. Line Frequency Faulting CONF_ISM — ENABLE if motor protection required for drop in line frequency.
Hot Gas Bypass Option Minimum Load Points (Tsmin, IGVmin) CFGSURGE — Per job data — See modify load points section. Refer to table located in the control panel. Full (Maximum) Load Points (Tsmax, IGVmax) Surge Line Shape Factor (shapefac) CFGSURGE — Per Chiller Requisition (shapefac). Refer to table located in the control panel.
Chilled Medium FACTORY — Enter water or brine. Evaporator Refrigerant Trippoint CFGLIMIT — Usually 3° F (1.7° C) below design refrigerant temperature. Evaporator Flow Delta P Cutout CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).* Condenser Flow Delta P Cutout CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).* High Condenser Water Delta P CFGLIMIT — Enter the maximum allowable value for condenser water pressure drop.
Motor Rated Kilowatts
*With variable flow systems this point may be configured to the lower end of the range.
NOTE: Other parameters: Screens are normally left at the default settings; they may be changed as required. The time and persistence settings on the CONF_ISM table can be adjusted to increase or decrease the sensitivity to a fault condition. Increasing time or persistence decreases sensitivity. Decreas­ing time or persistence increases sensitivity to the fault condition.
CONF_ISM — Select 0 for full voltage, 1 for reduced voltage, 2 for solid state, or 3 for freestanding variable frequency drive.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of power transformer wired to ter minal J3 of ISM. If no transf ormer is used enter 1.
CONF_ISM — Enter value from nameplate in starter cabinet MAXIMUM FUSE. This value shall always be “9999” for Benshaw RediStart MX3 wye-delta and solid-state starters.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of current transf ormers wired to terminal J4 of ISM. This value shall always be “100” for Benshaw RediStart MX3 and solid-state starters.
CONF_OPT — 1 = HGBP for Surge Correction; 2 = HGBP for Low Load Operation; 3 = Combination HGBP; 0 = no HGBP or HGBP is Disabled.
CFGSURGE — Chiller Requisition (TSmin, IGV min) or per job data — See modify load points section. Refer to table located in the control panel.
FACTORY — Enter value from chiller requisition form (product data submittal) if DEMAND LIMIT SOURCE is set to kW.
21

Field Set Up and Verification

SAFETY CODE CERTIFICATION
COMPRESSOR MOTOR DATA
R-
REFRIGERATION MACHINE
CARRIER CHARLOTTE 9701 OLD STATESVILLE ROAD CHARLOTTE, NORTH CAROLINA 28269 MADE IN USA PRODUCTION YEAR: 20XX
19XR05009801
A United Technologies Company
T
M
THIS UNIT IS DESIGNED,CONSTRUCTED, AND TESTED IN CONFORMANCE WITH ANSI/ASHRAE 15 (LATEST REVISION),
SPECIFICATION Z-415.
IN ACCORDANCE WITH CARRIER
AND OVERLOAD PROTECTION MUST BE
THE COMPRESSOR MOTOR CONTROLLER
REFRIGERATION.
SAFETY CODE FOR MECHANICAL
TEST PRESSURE
DESIGN PRESSURE CLR.WATER PRESSURE COND.WATER PRESSURE
PSI PSI PSI PSI
KPA KPA KPA KPA
CAZTREH/ESAHP/STLOV RL AMPS OLT AMPS
LR AMPS Y-
LR AMPS D­MAX FUSE/CIRCUIT BKR MIN. CIRCUIT AMPACITY
LBS. CHARGED
KGS.REFRIGERANT
MODEL NUMBER
SERIAL NO. MACHINE COMP'R COOLER CONDENSER ECON STOR TANK
RATED iKW
RATED TONS
Fig. 18 — Machine Identification Nameplate
CHILLER ID NAMEPLATE — CONSTANT SPEED CHILLER
a19-1881
IMPORTANT: Some parameters are specific to the chiller configuration and will need to be verified prior to operation. All command functions must be initiated from the HMI.
Use the HMI touch screen to confirm that the ISM values match the chiller paramter labels and Chiller Builder design data sheet. The ISM values can be located from MAIN MENU CONFIGURATION MENU ISM CONFIGURATION.
LABEL LOCATIONS — Verify the following labels have been installed properly and match the chiller requisition:
• Surge Parameters — Located inside the chiller control panel.
• Chiller identification nameplate — Located on the right side of the control panel. (See Fig. 18.)
STARTER/DRIVE PROTECTION AND OTHER INCOM­ING WIRING
1. Verify that the branch disconnects or other local discon­nects are open and properly tagged out.
2. Verify that the branch circuit protection and AC input wiring to the starter are in accordance with NEC/CEC (National Electrical Code/California Energy Commis­sion) and all other local codes.
3. Verify that the fuses are per the field wiring diagram.
4. Verify that the incoming source does not exceed the SCCR (short circuit current rating) of the equipment marking.
5. Verify the power lugs in the starter/VFD and branch pro­tection are properly secured. Inspect the ground cable and ensure it is properly connected at the branch and to the
6. Verify the conduit for the power wiring in securely con-
ground lug in the starter.
nected to the starter flanged cover and runs continuously to the branch protection.
7. Ensure the control and signal wires connected to the chiller controller or the starter/VFD are in separate con­duits.
FINE TUNING VPF (VARIABLE PRIMARY FLOW) SURGE PRE VENTION — Figures 19-22 show how the pa­rameters defined below will affect the configured surge line. The menu can be found under MAIN MENU CONFIGU- RATION MENU SURGE CORRECTION CONFIG.
NOTE: Before tuning surge prevention, check for VFD (vari­able frequency drive) speed limitation or capacity overrides. If the source of low capacity is found in one of these places, do not proceed with an attempt to tune the Surge Prevention con­figurations.
If capacity is not reached and
1. ACTUAL GUIDE VANE POSITION < GUIDE VANE TRAVEL RANGE
and
2. SURGE PREVENTION ACTIVE = YES (can be identi­fied in MAIN MENU  MAINTENANCE MENU SURGE CORRECTION)
and
3. PERCENT LINE CURRENT < 100%
then the surge line is probably too conservative. Note the following parameters from HMI when maximum
ACTUAL LINE CURRENT achieved:
• EVAPORATOR REFRIGERANT TEMP
• EVAPORATOR PRESSURE
• CONDENSER REFRIG TEMP
• CONDENSER PRESSURE
• ACTUAL GUIDE VANE POSITION
• ACTUAL LINE CURRENT The ACTIVE DELTA Tsat and the CALC REF DELTA
TSAT can be monitored on the MAINTENANCE MENU SURGE CORRECTION screen. When DELTA TSAT exceeds CALC REF DELTA TSAT + ENVELOPE LINE OFFSET surge prevention will occur.
If ACTUAL GUIDE VANE POSITION is less than 30%,
then increase SURGE DELTA TSMIN in steps of 2º F (1.2º C) until one of the three conditions listed above no longer applies. Do not change SURGE DELTA TSMAX.
If ACTUAL GUIDE VANE POSITION is greater than
60%, then increase SURGE DELTA TSMAX in steps of 2º F (1.2º C) until cooling capacity is reached or one of conditions listed above no longer applies. Do not change SURGE/HGBP DELTA TSMIN.
If ACTUAL GUIDE VANE POSITION is more than 30%
AND less than 60%, then:
1. Increase SURGE DELTA TSMIN in steps of 2º F (1.2º C).
2. Increase SURGE DELTA TSMAX in steps of 2º F (1.2º C).
3. Repeat Steps 1 and 2 until one of the conditions listed above no longer applies.
NOTE: DELTA TSMIN should seldom need to be increased more than 10 degrees above the selection program value. Like­wise, DELTA TSMAX rarely requires more than a 2º F (1.2º C) increase.
If surge is encountered then the surge line is probably too optimistic or high. Note following parameters from HMI at surge:
• EVAPORATOR REFRIGERANT TEMP
• EVAPORATOR PRESSURE
• CONDENSER REFRIG TEMP
• CONDENSER PRESSURE
• ACTUAL GUIDE VANE POSITION
• AVERAGE LINE CURRENT
22
40
Fig. 19 — Effect of SURGE DELTA TSMIN on
Surge Prevention
a19-1959
0
5
10
15
20
25
30
35
40
45
0 102030405060708090100110
Tsmax= 60
Tsmax= 70
Tsmax= 80
GV_POS
Delta Tsat
Fig. 20 — Effect of SURGE DELTA TSMAX on
Surge Prevention
a19-1960
Fig. 21 — Effect of SURGE LINE SHAPE FACTOR
on Surge Prevention
a19-1961
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
0 102030405060708090100110
Speed Factor =1.60
Speed Factor =1.85
Speed Factor =2.00
GV_POS
Delta Tsat
Fig. 22 — Effect of SURGE LINE SPEED FACTOR
on Surge Prevention
a19-1962
35
30
25
20
Delta Tsat
15
10
5
0
0 102030405060708090100110
60.00
55.00
50.00
45.00
40.00
35.00
30.00
Delta Tsat
25.00
20.00
15.00
10.00
5.00
0.00 0 10 20 30 40 50 60 70 80 90 100 110
GV_POS
GV_POS
Tsmin= 30
Tsmin= 40
Tsmin= 50
Shape factor = -0.020
Shape factor = -0.040
Shape factor = -0.050
If ACTUAL GUIDE VANE POSITION is less than 30%, go to Step 1. If ACTUAL GUIDE VANE POSITION is greater than 60%, then go to Step 3.
1. Do not change SURGE LINE SHAPE FACTOR from the value selected by Chiller Builder (ECAT). Decrease SURGE DELTA TSMIN in 1° F steps up to 5 times. Monitor chiller for surge.
2. If ACTUAL GUIDE VANE POSITION is still less than 30 and Step 1 failed, then increase the value of SURGE LINE SHAPE FACTOR in steps of 0.01 up to 2 times. For example, if surge is encountered when shape factor is –0.06, increase the SURGE LINE SHAPE FACTOR to –0.05. If this does not solve the problem, go to Step 5, even if ACTUAL GUIDE VANE POSITION is less than 30%.
3. Do not change SURGE LINE SHAPE FACTOR from the value selected by Chiller Builder (ECAT). Decrease SURGE DELTA TSMAX by 1° F steps up to 5 times. Monitor chiller for surge.
4. If ACTUAL GUIDE VANE POSITION is greater than 60% and Step 3 failed to eliminate surge, then set SURGE DELTA TSMAX to 5° F below the value speci­fied by Chiller Builder (ECAT). Increase the value of the SURGE LINE SHAPE FACTOR in steps of 0.01 up to 2 times. For example, if surge is encountered when the SURGE LINE SHAPE FACTOR is –0.06, increase the SURGE LINE SHAPE FACTOR to –0.05. If this does not solve the problem, go to Step 5, even if ACTUAL GUIDE VANE POSITION is greater than 60%.
5. If ACTUAL GUIDE VANE POSITION is greater than 30% but less than 60% or if Step 2 failed (with ACTUAL GUIDE VANE POSITION less than 30) or if Step 4 failed (with ACTUAL GUIDE VANE POSITION great­er than 60), then perform this step. Do not change SURGE LINE SHAPE FACTOR from the value speci­fied by Chiller Builder (ECAT). Reset SURGE DELTA TSMIN and SURGE DELTA TSMAX to the value spec­ified by Chiller Builder (ECAT). Decrease SURGE DEL­TA TSMIN and SURGE DELTA TSMAX in steps of 1° F up to 5 times. Monitor chiller for surge.
If the chiller is equipped with a VFD and the drive does not slow down adequately at part load, then the machine is likely operating at a point above the configured “software” surge line and the machine is in surge prevention mode. Check for a surge protection message on the HMI. If the unit is not in a surge pro­tection state, then the ENVELOPE SPEED FACTOR may
23
need to be increased (more aggressive surge line protection) in combination with a decrease in the SURGE LINE SHAPE FACTOR.
MODIFY EQUIPMENT CONFIGURATION IF NECES­SARY — The EQUIPMENT SERVICE table has screens to select, view, or modify parameters. Carrier’s certified drawings have the configuration values required for the jobsite. Modify these values only if requested. Modifications can include:
• Chilled water reset
• Entering chilled water control (Enable/Disable)
• 4 to 20 mA demand limit
• Auto restart option (Enable/Disable)
• Remote contact option (Enable/Disable) See the 19XR with PIC 5 Controls Operation and Trouble-
shooting guide for more details about these functions.
Perform a Controls Test (Quick Test) — Check
the safety controls status by performing an automated controls test. The path to the QUICK TEST is MAIN MENU QUICK TEST TABLE. (The QUICK TEST screen can only be accessed when the chiller is in STOP mode.) On the
QUICK TEST table screen, select a test to be performed (see Table 8).
The Quick Test checks all outputs and inputs for function. In order to successfully proceed with the controls test, the com­pressor should be off, no alarms showing, and voltage should be within ±10% of rating plate value. Each test asks the opera­tor to confirm the operation is occurring and whether or not to continue. If an error occurs, the operator can try to address the problem as the test is being done or note the problem and pro­ceed to the next test.
NOTE: If during the controls test the guide vanes do not open, verify the low pressure alarm is not active. (An active low pressure alarm causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if cooler pressure is below –5 psig (–35 kPa).
When the controls test is finished the test stops and the QUICK TEST menu displays. If a specific automated test pro­cedure is not completed, access the particular control test to test the function when ready. For information about calibration, see the sections Checking Pressure Transducers, page 46, and High Altitude Locations, page 46.
Table 8 — Quick Test Table
CCN TABLE NAME: QCK_TEST PIC 5 PATH: Main Menu Quick Test
LINE PIC 5 DESCRIPTION CCN NAME RANGE
1 Quick Test Enable QCK_TEST DSABLE/ENABLE DSABLE RW 2 GV 1 Calibration Enable GV1_CAL DSABLE/ENABLE DSABLE RW 3 GV1 Calibration Status
0=No Calibration or Failure
1=In Progress, 2=Completed 4 Guide Vane 1 Actual Ohms GV1_OHM 0.00 to 12000.00 RO 5 Guide Vane 1 Actual mA GV1_MAF 0.0 to 20.8 mA RO 6 Guide Vane 1 Forced Position Q_GV1POS 0.0 to 100.0 0.0 % RW 7 Quick Test GV1 Open Q_GV1OP OFF/ON OFF RW 8 Quick Test GV1 Close Q_GV1CL OFF/ON OFF RW 9 Quick Test Oil Pump Q_OILP OFF/ON OFF RW
10 Oil Pres Test Passed OP_PASS NO/YES RO 11 Oil Pump Delta Pressure OIL_PDQ –6.7 t o 420.0 psig RO 12 Quick Test Oil Heater Q_OILH OFF/ON OFF RW 13 Quick Test HGBP Open Q_HGBPOP OFF/ON OFF RW 14 Quick Test HGBP Close Q_HGBPCL OFF/ON OFF RW 15 Quick Test Damper Open Q_DMPOP OFF/ON OFF RW 16 Quick Test Damper Close Q_DMPCL OFF/ON OFF RW 17 Quick Test Cond Pump Q_CDWP OFF/ON OFF RW 18 Condenser Water Flow CDW_FLOW NO/YES RO 19 Quick Test Chilled Pump Q_CHWP OFF/ON OFF RW 20 Chileld Water Flow CHW_FLOW NO/YES RO 21 Condenser Water Flow CDW_FLOW NO/YES RO 22 Chilled Water Flow CHW_FLOW NO/YES RO 23 Quick Test Head Val Pos Q_HDP 0.0 to 100.0 0.0 % RW 24 Quick Test Diffuser Pos Q_SRD 0.0 to 100.0 0.0 % RW 25 Quick Test Chiller Status Q_CHST 4.0 to 20.0 4.0 mA RW 26 Quick Test Oil EXV Q_EXV 4.0 to 20.0 4.0 mA RW 27 Condenser Water Delta T CDW_DT –40.0 to 245.0 °F RO 28 Chilled Water Delta T CHW_DT –40.0 to 245.0 °F RO 29 Cond Water Deviation CDWT_DV OFF/ON RO 30 Chilled Water Deviation CHWT_DV OFF/ON RO 31 Quick Test Alarm Output Q_ALM OFF/ON OFF RW 32 Quick Test Alert Output Q_ALE OFF/ON OFF RW 33 Guide Vane 1 Ohms 100% GV1_MAXO 0.00 to 12000.00 RO 34 Guide Vane 1 Ohms 0% GV1_MINO 0.00 to 12000.00 RO 35 Guide Vane 1 mA 100% GV1_MAXA 0.0 to 20.8 mA RO 36 Guide Vane 1 mA 0% GV1_MINA 0.0 to 20.8 mA RO
LEGEND
GV Guide Vane HGBP — Hot Gas Bypass RO Read Onl y RW Read Write
*Default value is shown only if configurable in this table.
GV1_STAT 0 to 2 RO
NOTES:
1. Quick Test ENABLE defaults back to DISABLE after 1 hour.
2. During any of the tests, an out-of-range reading will have an asterisk (*) next to the reading and a message will be displayed if the diffuser control is enabled.
DEFAULT
VALUE*
UNIT READ/WRITE
24

Charge Refrigerant into Chiller

CAUTION
The transfer, addition, or removal of refrigerant in spring isolated chillers may place severe stress on and damage external piping if springs have not been blocked in both up and down directions.
CAUTION
Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups.
1. Access the terminate lockout function on the PUMP­DOWN/LOCKOUT screen (located in the Maintenance Menu).
2. IMPORTANT: Turn on the chilled water and condenser water pumps to prevent freezing.
3. Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 23 and 24. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process takes approximately 15 minutes.
4. Once the pressures have equalized, the discharge isola­tion valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves 1a and 1b, and all pumpout unit valves.
The standard 19XR chiller is shipped with the refrigerant already charged in the vessels. However, the 19XR chiller may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the nitrogen from the entire chiller, and charge the chiller from refrigerant cylinders.

CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT

CAUTION
When equalizing refrigerant pressure on the 19XR chiller after service work or during the initial chiller start-up, do not use the discharge isolation valve to equalize. A charging hose (connected between the charging valves on top of the cooler and condenser) should be used as the equalization valve. Failure to follow this procedure may damage equipment.
To equalize the pressure differential on a refrigerant isolated 19XR chiller, use the terminate lockout function of PUMP­DOWN/LOCKOUT (located in the Maintenance Menu). This helps to turn on pumps and advises the operator on proper pro­cedures.
The following steps describe how to equalize refrigerant pressure in an isolated 19XR chiller without a pumpout unit.
1. Access terminate lockout function on the Maintenance Menu. (Alternatively, the Quick Test provides a means for cooler and condenser pump control.)
2. IMPORTANT: Turn on the chilled water and condenser water pumps to prevent freezing.
3. Slowly open the refrigerant charging valves. The chiller cooler and condenser pressures will gradually equalize. This process takes approximately 15 minutes.
4. Once the pressures have equalized, the cooler isolation valve, the condenser isolation valve, and the hot gas isola­tion valve may now be opened. Refer to Fig. 23 and 24 for the location of the valves.
WARNING
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation. Failure to follow this procedure may damage equipment and result in bodily injury.
CHILLER EQUALIZATION WITH FREE-STANDING PUMPOUT UNIT — The following steps describe how to equalize refrigerant pressure on an isolated 19XR chiller using the pumpout unit.
WARNING
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation. Failure to follow this procedure may damage equipment and result in bodily injury.
The full refrigerant charge on the 19XR chiller will vary with chiller components and design conditions, as indicated on the job data specifications. An approximate charge may be de­termined by adding the condenser charge to the cooler charge as listed in the Heat Exchanger Data tables in the Physical Data section that begins on page 48.
CAUTION
Always operate the condenser and chilled water pumps whenever charging, transferring, or removing refrigerant from the chiller. Always confirm that water flow is estab­lished. Failure to follow this procedure may result in equip­ment damage.
Use the PUMPDOWN/LOCKOUT terminate lockout func­tion to monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge refrigerant is added through the pumpout charging connection (Fig. 23 and 24, valve 1b). First evacuate the nitrogen holding charge from the chiller vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig (241 kPa) for HFC­134a. After the chiller is beyond this pressure the refrigerant should be charged as a liquid until all the recommended refrig­erant charge has been added. The charging valve (Fig. 23 and 24, valve 7) can be used to charge liquid to the cooler if the cooler isolation valve (11) is present and is closed. Do not charge liquid through the linear float to the condenser.
TRIMMING REFRIGERANT CHARGE — The 19XR chiller is shipped with the correct charge for the design duty of the chiller. Trimming the charge can best be accomplished when the design load is available. To trim the charge, check the temperature difference between the leaving chilled water tem­perature and cooler refrigerant temperature at full load design conditions. If necessary, add or remove refrigerant to bring the temperature difference to design conditions or minimum differential. See the 19XR Installation Instructions manual for required chiller refrigerant charge.
The 19XR chiller refrigerant charges are shown in Tables 9 and 10. Total refrigerant charge is the sum of the cooler, con­denser, and economizer charge.
, the
25
STORAGE
TANK LIQUID
VALVE
OIL SEPARATOR
PUMPOUT CONDENSER WATER SUPPLY AND RETURN
PUMPOUT CONDENSER
STORAGE TANK VAPOR VALVE
2
3
4
5
PRESSURE RELIEF SAFETY VALVE
PUMPOUT COMPRESSOR
TEE FOR CHARGING
REFRIGERANT CHARGING VALVE
COOLER REFRIGERANT ISOLATION VALVE
LIQUID LINE SERVICE VALVE
CHILLER CONDENSER VESSEL
CHILLER COOLER VESSEL
10
6
7
11
1a
1b
SERVICE VALVE ON PUMPOUT UNIT
=
SERVICE VALVE ON CHILLER (FIELD SUPPLIED)
=
=
MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND STORAGE TANK FOR SERVICE AND OPERATION WORK.
REFRIGERANT CHARGING VALVE
Fig. 23 — Typical Optional Pumpout System Piping Schematic with Storage Tank
a19-1721
OIL SEPARATOR
PUMPOUT CONDENSER WATER SUPPLY AND RETURN
PUMPOUT CONDENSER
2
3
4
5
PRESSURE RELIEF SAFETY VALVE
PUMPOUT COMPRESSOR
COOLER REFRIGERANT ISOLATION VALVE
REFRIGERANT CHARGING VALVE
CHILLER CONDENSER VESSEL
CHILLER COOLER VESSEL
7
11
1a
1b
SERVICE VALVE ON PUMPOUT UNIT
=
SERVICE VALVE ON CHILLER
=
LIQUID LINE SERVICE VALVE
REFRIGERANT CHARGING VALVE
Fig. 24 — Typical Freestanding Pumpout System Piping Schematic without Storage Tan k
a19-1722
26
Table 9 — 19XR Two-Stage Compressor Frame Size 6 Heat Exchanger Refrigerant Charge
ENGLISH SI
CODE*
COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY
A40 1647 927 360 747 420 163 A41 1773 927 360 804 420 163 A42 1887 927 360 856 420 163 A45 1599 927 360 725 420 163 A46 1714 927 360 777 420 163 A47 1837 927 360 833 420 163
A60 1878 1074 360 852 48 7 163 A61 2022 1074 360 917 48 7 163 A62 2152 1074 360 976 48 7 163 A65 1823 1074 360 827 48 7 163 A66 1954 1074 360 886 48 7 163 A67 2095 1074 360 950 48 7 163
A4A 1681 861 360 762 391 163 A4B 1792 861 360 813 391 163 A4C 1897 861 360 860 391 163 A4F 1626 861 360 738 391 163 A4G 1736 861 360 787 391 163 A4H 1890 861 360 857 391 163
A6A 1917 998 360 870 453 163 A6B 2044 998 360 927 453 163 A6C 2164 998 360 982 453 163 A6F 1854 998 360 841 453 163 A6G 1979 998 360 898 453 163 A6H 2156 998 360 978 453 163
MACHINE CHARGE MACHINE CHARGE
REFRIGERANT WEIGHT (lb) REFRIGERANT WEIGHT (kg)
B40 1233 360 559 163 B41 1233 360 559 163 B42 1233 360 559 163 B45 1233 360 559 163 B46 1233 360 559 163 B47 1233 360 559 163
B60 1423 360 645 163 B61 1423 360 645 163 B62 1423 360 645 163 B65 1423 360 645 163 B66 1423 360 645 163 B67 1423 360 645 163
B4A 1148 360 521 163 B4B 1148 360 521 163 B4C 1148 360 521 163 B4F 1148 360 521 163 B4G 1148 360 521 163 B4H 1148 360 521 163
B6A 1326 360 601 163 B6B 1326 360 601 163 B6C 1326 360 601 163 B6F 1326 360 601 163 B6G
H 1326 360 60
B6
*See Model Number Nomenclature on page 5.
1326 360 601 163
1 163
27
Table 10 — 19XR Two-Stage Compressor Frame Size 7 Heat Exchanger Refrigerant Charge
ENGLISH SI
CODE*
COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY COOLER ONLY CONDENSER ONLY ECONOMIZER ONLY
B60 2273 646 1031 293 B61 2355 646 1068 293 B62 2460 646 1116 293 B65 2185 646 991 293 B66 2275 646 1032 293 B67 2379 646 1079 293
B6A 2081 646 944 293 B6B 2162 646 981 293 B6C 2256 646 1023 293
B6F 1951 646 885 293 B6G 2019 646 916 293 B6H 2120 646 962 293
C60 2647 1610 646 1201 730 293
C61 2751 1610 646 1248 730 293
C62 2875 1610 646 1304 730 293
C65 2562 1610 646 1162 730 293
C66 2666 1610 646 1209 730 293
C67 2793 1610 646 1267 730 293
C6A 2443 1497 646 1108 679 293 C6B 2534 1497 646 1149 679 293 C6C 2627 1497 646 1192 679 293
C6F 2334 1497 646 1059 679 293 C6G 2415 1497 646 1095 679 293 C6H 2500 1497 646 1134 679 293
MACHINE CHARGE MACHINE CHARGE
REFRIGERANT WEIGHT (lb) REFRIGERANT WEIGHT (kg)
D60 2097 646 951 293
D61 2097 646 951 293
D62 2097 646 951 293
D65 2097 646 951 293
D66 2097 646 951 293
D67 2097 646 951 293
D6A 1947 646 883 293 D6B 1947 646 883 293 D6C 1947 646 883 293
D6F 1947 646 883 293 D6G 1947 646 883 293 D6H 1947 646 883 293
*See Model Number Nomenclature on page 5.
28

INITIAL START-UP

Fig. 25 — Correct Motor Rotation
Preparation —
1. Power is on to the main starter, oil pump relay, tower fan starter, oil heater relay, and the chiller control panel.
2. Cooling tower water is at proper level and at-or-below design entering temperature.
3. Chiller is charged with refrigerant and all refrigerant and oil valves are in their proper operating positions.
4. Oil is at the proper level in the reservoir sight glasses.
5. Oil reservoir temperature is above 140 F (60 C) or above CALC EVAP SAT TEMP plus 50 F (28 C).
6. Valves in the evaporator and condenser water circuits are open.
NOTE: If the pumps are not automatic, ensure water is circulating properly.
Before starting the chiller, verify:
CAUTION
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief valves and result in the loss of refrigerant charge.
7. Access the PUMPDOWN/LOCKOUT feature from the Maintenance Menu. Press the End Lockout button on the touch screen and accept the “press OK to Terminate Lockout?” prompt. The unit is reset to operating mode. The chiller is locked out at the factory in order to prevent accidental start-up.

Check Motor Rotation

1. Disengage the main starter disconnect and engage the control panel power circuit breaker.
NOTE: The circuit breaker may be located in the starter if the disconnect and step down transformer option was or­dered with the starter. If located in the starter, close the door securely after this step.
2. Close the starter enclosure door.
3. The ISM (integrated starter module) mounted in the start­er enclosure checks for proper phase rotation as soon as power is applied to the starter and the PIC 5 controls power up.
4. An alarm message will appear on the HMI screen if the phase rotation is incorrect. If this occurs reverse any 2 of the 3 incoming power leads to the starter and reapply power. The motor is now ready for a rotation check.
5. Start the chiller by Local On (assumes LOCAL operation mode) by pressing the Start/Stop button on the HMI and following the prompts. The PIC 5 control performs start­up checks.
6. When the starter is energized and the motor begins to turn, check for clockwise motor rotation (Fig. 25).
IMPORTANT: Do not check motor rotation during coast­down. Rotation may have reversed during equalization of vessel pressures.

Check Oil Pressure and Compressor Stop

1. When the motor is at full speed, note the differential oil pressure reading on the HMI default screen. It should be between 18 and 40 psid (124 and 206 kPad). The oil pump will geenrate design oil pressure only with the cor­rect electrical phasing of ABC.
2. Press the Stop button and listen for any unusual sounds from the compressor as it coasts to a stop.
To Prevent Accidental Start-Up — A chiller STOP
override setting may be entered to prevent accidental start-up during service or whenever necessary. From the Main Menu, access the General Parameters Menu and use the down arrow to reach Stop Override on the GENUNIT table. Change Stop Override to Yes; then execute the command by touching the lightning button. The message “ALM-276 Protective Limit ­Stop Override” will appear in the Home Screen message area. To restart the chiller, access the same screen change the Stop Override option to No.
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and oil and refrigerant levels indicate the system is functioning properly.
Instruct the Customer Operator — Ensure the op-
erator(s) understand all operating and maintenance procedures. Point out the various chiller parts and explain their function as part of the complete system.
COOL ER-CON DENSE R — High side float chamber, relief valves, refrigerant charging valve, temperature sensor loca­tions, pressure transducer locations, Schrader fittings, water­boxes and tubes, and vents and drains.
OPTIONAL PUMPOUT STORAGE TANK AND PUMP­OUT SYSTEM — Transfer valves and pumpout system, re­frigerant charging and pumpdown procedure, and relief devices.
MOTOR COMPRESSOR ASSEMBLY — Guide vane ac­tuator, transmission, motor cooling system, oil cooling system, temperature and pressure sensors, oil sight glasses, integral oil pump, isolatable oil filter, extra oil and motor temperature sen­sors, synthetic oil, and compressor serviceability.
MOTOR COMPRESSOR LUBRICATION SYSTEM — Oil pump, cooler filter, oil heater, oil charge and specification, operating and shutdown oil level, temperature and pressure, and oil charging connections.
ECONOMIZER — Float valve, drain valve, Schrader fitting, damper valve.
CONTROL SYSTEM — CCN and LOCAL start, reset, menu, softkey functions, HMI operation, occupancy schedule, set points, safety controls, and auxiliary and optional controls.
AUXILIARY EQUIPMENT — Starters and disconnects, separate electrical sources, pumps, and cooling tower.
DESCRIBE CHILLER CYCLES — Refrigerant, motor cooling, lubrication, and oil reclaim.
29
REVIEW MAINTENANCE — Scheduled, routine, and ex­tended shutdowns, importance of a log sheet, importance of water treatment and tube cleaning, and importance of maintain­ing a leak-free chiller.
SAFETY DEVICES AND PROCEDURES — Electrical disconnects, relief device inspection, and handling refriger­ant.
CHECK OPERATOR KNOWLEDGE — Start, stop, and shutdown procedures, safety and operating controls, refrigerant and oil charging, and job safety.
REVIEW THE START-UP, OPERATION, AND MAINTE­NANCE MANUAL.

OPERATING INSTRUCTIONS

Operator Duties

1. Become familiar with the chiller and related equipment before operating the chiller.
2. Prepare the system for start-up, start and stop the chiller, and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any abnormal readings.
4. Inspect the equipment, make routine adjustments, and perform a Control Test. Maintain the proper oil and re­frigerant levels.
5. Protect the system from damage during shutdown periods.
6. Maintain the set point, time schedules, and other PIC functions.
Prepare the Chiller for Start-Up — Follow the steps
described in the Initial Start-Up section, page 29.

To Start the Chiller

1. Start the water pumps, if they are not automatic.
2. Press the Start/Stop icon on the HMI home screen to start the system. If the chiller is in the OCCUPIED mode and the start timers have expired, the start sequence will start. Follow the procedure described in the Start-Up/Shut­down/Recycle Sequence section, page 11.
Check the Running System — After the compres-
sor starts, the operator should monitor the display and observe the parameters for normal operating conditions:
1. The oil reservoir temperature should be above 120 F (49 C) during shutdown.
2. The bearing oil temperature accessed from the Tempera­tures menu should be 120 to 165 F (49 to 74 C) for com­pressors with rolling element bearings. If the bearing tem­perature reads more than 180 F (83 C) with the oil pump running, stop the chiller and determine the cause of the high temperature. Do not restart the chiller until correct­ed.
3. The oil level should be visible anywhere in one of the two sight glasses. Foaming oil is acceptable as long as the oil pressure and temperature are within limits.
4. The oil pressure should be between 18 and 40 psid (124 and 207 kPad) differential, as seen on the HMI Transmis­sion Status screen. Typically the reading will be 18 to 35 psid (124 to 241 kPad) at initial start-up.
5. The moisture indicator sight glass on the ref rigerant mo­tor cooling line should indicate refrigerant flow and a dry condition.
6. The condenser pressure and temperature varies with the chiller design conditions. Typically the pressure will range between 60 and 135 psig (390 and 950 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering water temperature should be controlled below the specified design entering water
temperature to save on compressor kilowatt requirements.
7. Cooler pressure and temperature also will vary with the design conditions. Typical pressure range will be between
29.5 and 40.1 psig (203.4 and 276.4 kPa), with tempera­ture ranging between 34 and 45 F (1.1 and 7.2 C).
8. The compressor may operate at full capacity for a short time after the pulldown ramping has ended, even though the building load is small. The active electrical demand setting can be overridden to limit the compressor kW, or the pulldown rate can be decreased to avoid a high demand charge for the short period of high demand oper­ation. Pulldown rate can be based on load rate or tempera­ture rate and is accessed on the MAINTENANCE MENU CAPACITY CONTROLS  RAMP_DEM (Ramping Demand Limit Value).
9. The economizer (if installed) has two sight glasses that look into the float chamber. When the chiller is operating, the top sight glass is empty and the bottom sight glass is full.

To Stop the Chiller

The occupancy schedule starts and stops the chiller automati­cally once the time schedule is configured.
The unit can be stopped manually using the HMI by press­ing the green Start/Stop icon . The Unit Start/Stop screen is displayed. Press Confirm Stop. The compressor will then fol­low the normal shutdown sequence as described in the Start­Up/Shutdown/Recycle Sequence section on page 11. The chiller is now in the OFF control mode.
IMPORTANT: Do not attempt to stop the chiller by opening an isolating knife switch. High intensity arcing may occur.
If the chiller is stopped by an alarm condition, do not restart the chiller until the problem is diagnosed and corrected.
After Limited Shutdown — No special preparations
should be necessary. Follow the regular preliminary checks and starting procedures.
Preparation for Extended Shutdown — The refrig-
erant should be transferred into the pumpout storage tank (if supplied; see Pumpout and Refrigerant Transfer Procedures on page 31) to reduce chiller pressure and the possibility of leaks. Maintain a holding charge of 5 to 10 lb (2.27 to 4.5 kg) of re­frigerant or nitrogen to prevent air from leaking into the chiller.
If freezing temperatures are likely to occur in the chiller ar­ea, drain the chilled water, condenser water, and the pumpout condenser water circuits to avoid freeze-up. Keep the waterbox drains open. It is recommended not to store the refrigerant in the unit if below freezing temperatures are anticipated. A nitro­gen holding charge is recommended in this case.
Leave the oil charge in the chiller with the oil heater and controls energized to maintain the minimum oil reservoir temperature.
After Extended Shutdown — Ensure the water sys-
tem drains are closed. It may be advisable to flush the water circuits to remove any soft rust that may have formed. This is a good time to brush the tubes and inspect the Schrader fittings on the waterside flow devices for fouling, if necessary.
Check the cooler pressure on the HMI panel and compare it to the original holding charge that was left in the chiller. If (af­ter adjusting for ambient temperature changes) any loss in pres­sure is indicated, check for refrigerant leaks. See Check Chiller Tightness section, page 13.
Recharge the chiller by transferring refrigerant from the pumpout storage tank (if supplied). Follow the Pumpout and Refrigerant Transfer Procedures section on page 31. Observe freeze-up precautions.
30
Carefully make all regular preliminary and running system checks. If the compressor oil level appears abnormally high, the oil may have absorbed refrigerant. Ensure that the oil tem­perature is above 40 F (4.4 C) or above the EVAP SAT TEMP plus 50F (27 C).
Cold Weather Operation — When the entering con-
denser water temperature drops very low, the operator should automatically cycle the cooling tower fans off to keep the tem­perature up. Piping may also be arranged to bypass the cooling tower.
IMPORTANT: A field-supplied water temperature con­trol system for condenser water should be installed. The system should maintain the leaving condenser water temperature at a temperature that is at least 20 F (11C) above the leaving chilled water temperature.
Manual Guide Vane Operation — It is possible to
manually operate the guide vanes in order to check control operation or to control the guide vanes in an emergency. Manu­al operation is possible by overriding the target guide vane position.
NOTE: Manual control overrides the configured pulldown rate during start-up and permits the guide vanes to open at a faster rate. Motor current above the electrical demand setting, capac­ity overrides, and chilled water temperature below the control point override the manual target and close the guide vanes. For descriptions of capacity overrides and set points, see the 19XR with PIC 5 Controls Operation and Troubleshooting guide.
Refrigeration Log — A refrigeration log (as shown in
Fig. 26), is a convenient checklist for routine inspection and maintenance and provides a continuous record of chiller per­formance. It is also an aid when scheduling routine mainte­nance and diagnosing chiller problems.
Keep a record of the chiller pressures, temperatures, and liq­uid levels on a sheet similar to the one in Fig. 26. Automatic re­cording of data is possible by using CCN devices such as the
Data Collection module and a Building Supervisor. Contact a Carrier representative for more information.
PUMPOUT AND REFRIGERANT
TRANSFER PROCEDURES
Preparation —
with an optional pumpout storage tank, pumpout system, or pumpout compressor. The refrigerant can be pumped for ser­vice work to either the chiller compressor vessel or chiller con­denser vessel by using the optional pumpout system. If a pumpout storage tank is supplied, the refrigerant can be iso­lated in the storage tank. The following procedures describe how to transfer refrigerant from vessel to vessel and perform chiller evacuation.
The 19XR chiller may come equipped
CAUTION
The power to the pumpout compressor oil heater must be on whenever any valve connecting the pumpout compres­sor to the chiller or storage tank is open. Leaving the heater off will result in oil dilution by refrigerant and can lead to compressor failure.
If the compressor is found with the heater off and a valve open, the heater must be on for at least 4 hours to drive the refrigerant from the oil. When heating the oil the compressor suction must be open to a vessel to give the re­frigerant a means to leave the compressor.
CAUTION
Always run the chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when the chiller pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up.
31
REFRIGERATION LOG CARRIER 19XR SEMI-HERMETIC CENTRIFUGAL REFRIGERATION MACHINE
PLANT___________________________ MACHINE MODEL NO. ________________________ MACHINE SERIAL NO. _____________________________
32
DATE
TIME
__
REFRIGERANT FLOW TEMP. REFRIGERANT FLOW TEMP. REFRIG. BEARING TEMPS. OIL MOTOR
PRESS. TEMP. GPM IN OUT PRESS. TEMP. GPM IN OUT PRESS.
COOLER CONDENSER ECON.
#1 LSME#2 LSCE#3 HSME#4 HSCEPRESS.
COMPRESSOR
DIFF.
SUMP TEMP
LEVEL
FLA/AMPS POSITION)
(OR VANE
OPER-
ATOR
INITIALS
REMARKS
REMARKS: Indicate shutdowns on safety controls, repairs made and oil or refrigerant added or removed. Include amounts.
Fig. 26 — Refrigeration Log
DANGER
COMPRESSOR
OIL
SEPARATOR
CONDENSER
LEAVING
WATER
ENTERING
WATER
VALVE
5
VALVE
4
VALVE
2
CONTROL
PANEL
FRAME
ASSEMBLY
OIL
HEATER
VALVE
3
OIL FILL FITTING
Fig. 27 — Pumpout Unit
a23-1546
2 OL
2 OL 2 OL
MTR-1
L1 L2
PUMP OUT
COMPRESSOR
CRANKCASE HEATER
240-600v
27-40 WA TT
GND
H1 H4
X1 X2
X2
HIGH PRESSURE
SAFETY
NC OPEN > 185psig
CONTROL POWER
TRANSFORMER
XFMR-1
69 VA
C C C
8 7
HTR-1
FU1
0.25A
FU2
0.25A
FU3
0.5A
1 2
2
2
3
4
SS-1 OFF
AUTO ON
LOW PRESSURE CONTROL NC OPEN < 7 psia (-15.7 in. HG) CLOSE > 9 psia (-11.6 in. HG)
5
C
X2
6
FIELD POWER SUPPLY
L1
L2 L3
Fig. 28 — Pumpout Unit Wiring Schematic
a23-1615
LEGEND
C—Contactor FU Fuse GND — Ground HTR — Heater MTR — Motor NC Normally Closed OL Overload SS Selector Switch
During transfer of refrigerant into and out of the optional storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank or the release of refrigerant which will result in personal injury or death.
CAUTION
Do not mix refrigerants from chillers that use different compressor oils. Compressor damage can result.
Operating the Optional Pumpout Unit (Fig. 27) —
pressor sight glass under all operating conditions and during shutdown. If oil is low, add oil as described under Optional Pumpout System Maintenance section, page 41. The pumpout unit control wiring schematic is detailed in Fig. 28.
TO READ REFRIGERANT PRESSURES (during pumpout or leak testing):
1. The display on the chiller control panel is suitable for de­termining refrigerant-side pressures and low (soft) vacu­um. To assure the desired range and accuracy when mea­suring evacuation and dehydration, use a quality vacuum indicator or manometer. This can be placed on the Schrader connections on each vessel by removing the pressure transducer (Fig. 2).
2. To determine pumpout storage tank pressure, a 30 in. Hg vacuum -0-400 psi (-101-0-2769 kPa) gage is attached to the storage tank.
3. Refer to Fig. 23 and 24 for valve locations and numbers.
Oil should be visible in the pumpout unit com-
POSITIVE PRESSURE CHILLERS WITH STORAGE TANKS — In the Valve/Condition tables that accompany these instructions, the letter “C” indicates a closed valve. Figures 23 and 24 show the locations of the valves.
CAUTION
Always run chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when chiller vessel pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up.
CAUTION
Transfer, addition, or removal of refrigerant in spring­isolated chillers may place severe stress on and damage external piping if springs have not been blocked in both up and down directions.
33
Transfer Refrigerant from Pumpout Storage Tank to Chiller
WARNING
During transfer of refrigerant into and out of the 19XR storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank and personal injury.
1. Equalize refrigerant pressure. a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2 , 4, 5, and
10, and close refrigerant charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present.
c. Open pumpout and storage tank valves 3 and 6;
open chiller valves 1a and 1b.
VALVE 1A1B2345671011
CONDITION C C C C C
d. Gradually crack open valve 5 to increase chiller
pressure to 35 psig (241 kPa). Slowly feed refriger­ant to prevent freeze-up.
e. Open valve 5 fully after the chiller pressure rises
above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charging valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller.
VALVE 1A1B2345671011
CONDITION C C
2. Transfer remaining refrigerant. a. Close valve 5 and open valve 4. Turn off the
pumpout condenser water, and turn on the pumpout compressor in manual mode to push liquid refrigerant out of the storage tank. Monitor
the storage tank level until the tank is empty. b. Close refrigerant charging valves 7 and 10. c. Turn off the pumpout compressor. d. Turn off the chiller water pumps. e. Close valves 3 and 4. f. Open valves 2 and 5.
VALVE 1A1B2345671011
CONDITION C C C C
g. Turn on pumpout condenser water. h. Run the pumpout compressor in manual mode until
the storage tank pressure reaches 5 psig (34 kPa),
18 in. Hg vacuum (41 kPa absolute). i. Turn off the pumpout compressor. j. Close valves 1a, 1b, 2, 5, and 6.
VALVE 1A1B2345671011
CONDITIONCCCCCCCCC
k. Turn off pumpout condenser water.
Transfer the Refrigerant from Chiller to Pumpout Storage Tank
1. Equalize refrigerant pressure. a. Valve positions:
VALVE 1A1B2345671011
CONDITION C C C C C
b. Slowly open valve 5 and refrigerant charging
valves 7 and 10 to allow liquid refrigerant to drain by gravity into the storage tank.
VALVE 1A1B2345671011
CONDITION C C
2. Transfer the remaining liquid. a. Turn off pumpout condenser water. Place valves in
the following positions:
VALVE 1A1B2345671011
CONDITION C C
b. Run the pumpout compressor in automatic mode
until vacuum switch is satisfied and compressor stops. Close valves 7 and 10.
VALVE 1A1B2345671011
CONDITION C C C C
c. Turn off the pumpout compressor.
3. Remove any remaining refrigerant. a. Turn on chiller water pumps. b. Turn on pumpout condenser water. c. Place valves in the following positions:
VALVE 1A1B2345671011
CONDITION C C C C
d. Run the pumpout compressor until the chiller pres-
sure reaches 35 psig (241 kPa); then, shut off the pumpout compressor. Warm chiller condenser water will boil off any entrapped liquid refrigerant and chiller pressure will rise.
e. When chiller pressure rises to 40 psig (276 kPa),
turn on the pumpout compressor until the pressure again reaches 35 psig (241 kPa), then, turn off the pumpout compressor. Repeat this process until the chiller pressure no longer rises; then, turn on the pumpout compressor and pump out until the chiller pressure reaches 18 in. Hg vacuum (41 kPa abso­lute). This can be done in On or Automatic mode.
f. Close valves 1a, 1b, 3, 4, and 6.
VALVE 1A1B2345671011
CONDITIONCCCCCCCCC
g. Turn off the pumpout condenser water.
4. Establish vacuum for service. To conserve refrigerant, operate the pumpout compressor as described in Step 3e until the chiller pressure is reduced to 18 in. Hg vacuum (41 kPa absolute).
This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automati­cally at approximately 15 in. Hg vacuum (51 kPa absolute).
CHILLERS WITH ISOLATION VALVES — The va l v es re­ferred to in the following instructions are shown in Fig. 23 and
24. Valve 7 remains closed. Transfer All Refrigerant to Chiller Condenser Vessel
1. Push refrigerant into chiller condenser vessel. a. Turn on the chiller water pumps and monitor the
chiller pressure.
b. Valve positions:
VALVE 1A1B234511
CONDITION C C
34
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout con-
denser water supply.
e. Turn on pumpout compressor to push liqu id out of
the chiller cooler vessel.
f. When all liquid has been pushed into the chiller
condenser vessel, close the cooler refrigerant isola-
tion valve (11). g. Turn on the chiller water pumps. h. Turn off the pumpout compressor.
2. Evacuate gas from chiller cooler vessel. a. Close liquid line service valves 2 and 5; open
valves 3 and 4.
VALVE 1A1B234511
CONDITION C C C
b. Turn on pumpout condenser water. c. Run pumpout compressor until the chiller cooler
vessel pressure reaches 18 in. Hg vacuum (41 kPa absolute). Monitor pressures on the chiller control panel and on refrigerant gages.
This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automatically at approximately 15 in. Hg vacuum (51 kPa absolute).
d. Close valve 1a. e. Turn off pumpout compressor. f. Close valves 1b, 3, and 4.
VALVE 1A1B234511
CONDITION CCCCCCC
g. Turn off pumpout condenser water. h. Turn off chiller water pumps and lock out chiller
compressor.
Transfer All Refrigerant to Chiller Cooler Vessel
1. Push refrigerant into the chiller cooler vessel. a. Turn on the chiller water pumps and monitor the
chiller pressure.
b. Valve positions:
VALVE 1A1B234511
CONDITION C C
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout con-
denser water.
e. Turn on pumpout compressor to push refrigerant
out of the chiller condenser.
f. When all liquid is out of the chiller condenser,
close valve 11 and any other liquid isolation valves on the chiller.
g. Turn off the pumpout compressor.
2. Evacuate gas from chiller condenser vessel. a. Turn on chiller water pumps. b. Make sure that liquid line servi ce valves 3 and 4
are closed and valves 2 and 5 are open.
VALVE 1A1B234511
CONDITION C C C
c. Turn on pumpout condenser water.
d. Run the pumpout compressor until t he chiller con-
denser reaches 18 in. Hg vacuum (41 kPa absolute) in Manual or Automatic mode. Monitor pressure at
the chiller control panel and refrigerant gages. e. Close valve 1b. f. Turn off pumpout compressor. g. Close valves 1a, 2, and 5.
VALVE 1A1B234511
CONDITION CCCCCCC
h. Turn off pumpout condenser water. i. Turn o ff chiller water pumps and lock out chiller
compressor.
Return Refrigerant to Normal Operating Conditions
1. Be sure that the chiller vessel that was opened has been evacuated.
2. Turn on chiller water pumps.
3. Open valves 1a, 1b, and 3.
VALVE 1A1B234511
CONDITION C C C C
4. Crack open valve 5, gradually increasing pressure in the evacuated chiller vessel to 35 psig (241 kPa). Feed refrig­erant slowly to prevent tube freeze-up.
5. Leak test to ensure chiller vessel integrity.
6. Open valve 5 fully.
VALVE 1A1B234511
CONDITION C C C
7. Close valves 1a, 1b, 3, and 5.
8. Open chiller isolation valve 11 and any other isolation valves, if present.
VALVE 1A1B234511
CONDITION CCCCCC
9. Turn off chiller water pumps.

DISTILLING THE REFRIGERANT

1. Transfer the refrigerant from the chiller to the pumpout storage tank as described in the Transfer the Refrigerant from Chiller to Pumpout Storage Tank section on page 34.
2. Equalize the refrigerant pressure. a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, and
10, and close chiller charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present.
c. Open pumpout and storage tank valves 3 and 6;
open chiller valves 1a and 1b.
VALVE 1A1B2345671011
CONDITION C C C C C
d. Gradually crack open valve 5 to increase chiller
pressure to 35 psig (241 kPa). Slowly feed refriger­ant to prevent freeze-up.
e. Open valve 5 fully after the chiller pressure rises
above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize.
35
3. Transfer remaining refrigerant. a. Close valve 3. b. Open valve 2.
VALVE 1A1B2345671011
CONDITION C C C C
c. Turn on pumpout condenser water. d. Run the pumpout compressor until the storage tank
pressure reaches 5 psig (34 kPa), 18 in. Hg vacuum
(41 kPa absolute) in Manual or Automatic mode. e. Turn off the pumpout compressor. f. Close valves 1a, 1b, 2, 5, and 6. g. Turn off pumpout condenser water.
VALVE 1A1B2345671011
CONDITIONCCCCCCCCC
4. Drain the contaminants from the bottom of the storage tank into a container. Dispose of contaminants safely.

GENERAL MAINTENANCE

Refrigerant Properties —
the 19XR chiller is HFC-134a. At normal atmospheric pres­sure, HFC-134a will boil at –14 F (–25 C) and must, therefore, be kept in pressurized containers or storage tanks. The refriger­ant is practically odorless when mixed with air and is noncom­bustible at atmospheric pressure. Read the Material Safety Data Sheet and the latest ASHRAE Safety Guide for Mechani­cal Refrigeration to learn more about safe handling of this refrigerant.
The standard refrigerant for
DANGER
HFC-134a will dissolve oil and some nonmetallic materi­als, dry the skin, and, in heavy concentrations, may dis­place enough oxygen to cause asphyxiation. When handling this refrigerant, protect the hands and eyes and avoid breathing fumes.
Adding Refrigerant — Follow the procedures de-
scribed in Trim Refrigerant Charge section, page 38.
CAUTION
Always use the compressor pumpdown function in the PUMPDOWN/LOCKOUT feature to turn on the cooler pump and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and cause possible freeze-up when the chiller pressure is below 30 psig (207 kPa) for HFC-134a.
Adjusting the Refrigerant Charge — If the addi-
tion or removal of refrigerant is required to improve chiller per­formance, follow the procedures given under the Trim Refrig­erant Charge section, page 38.
Refrigerant Leak Testing — Because HFC-134a is
above atmospheric pressure at room temperature, leak testing can be performed with refrigerant in the chiller. Use an elec­tronic halogen leak detector, soap bubble solution, or ultrasonic leak detector. Ensure that the room is well ventilated and free from concentration of refrigerant to keep false readings to a minimum. Before making any necessary repairs to a leak, transfer all refrigerant from the leaking vessel.
Leak Rate — It is recommended by ASHRAE that chillers
be taken off line immediately and repaired if the refrigerant
leak rate for the entire chiller is more than 10% of the operating refrigerant charge per year.
In addition, Carrier recommends that leaks totalling less than the above rate but more than a rate of 0.1% of the total charge per year should be repaired during annual maintenance or whenever the refrigerant is transferred for other service work.
Test After Service, Repair, or Major Leak —
If all the refrigerant has been lost or if the chiller has been opened for service, the chiller or the affected vessels must be pressure tested and leak tested. Refer to the Leak Test Chiller section on page 16 to perform a leak test.
WARNING
HFC-134a should not be mixed with air or oxygen and pressurized for leak testing. In general, this refrigerant should not be present with high concentrations of air or oxygen above atmospheric pressures, because the mixture can undergo combustion.
TESTING WITH REFRIGERANT TRACER — Use an en­vironmentally acceptable refrigerant as a tracer for leak test procedures. Use dry nitrogen to raise the machine pressure to leak testing levels.
TESTING WITHOUT REFRIGERANT TRACER — An­other method of leak testing is to pressurize with nitrogen only and to use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present.
TO PRESSURIZE WITH DRY NITROGEN NOTE: Pressurizing with dry nitrogen for leak testing should
not be done if the full refrigerant charge is in the vessel because purging the nitrogen is very difficult.
1. Connect a copper tube from the pressure regulator on the cylinder to the refrigerant charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence.
2. Open the charging valve fully.
3. Slowly open the cylinder regulating valve.
4. Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do not exceed 140 psig (965 kPa).
5. Close the charging valve on the chiller. Remove the cop­per tube if it is no longer required.
Repair the Leak, Retest, and Apply Standing Vacuum Test —
leaks with an electronic halide leak detector, soap bubble solu­tion, or an ultrasonic leak detector. Bring the chiller back to at­mospheric pressure, repair any leaks found, and retest.
After retesting and finding no leaks, apply a standing vacu­um test. Then dehydrate the chiller. Refer to the Standing Vacu­um Test and Chiller Dehydration sections (pages 16 and 18) in the Before Initial Start-Up section.
After pressurizing the chiller, test for
Checking Guide Vanes — During normal shutdown,
when the chiller is off, the guide vanes are closed. Check that the coupling is tight on the shaft and make sure that the guide vane shaft is closed. Complete the following steps to adjust po­sition (see Fig. 29-31):
1. Remove the set screw in the guide vane coupling.
2. Loosen the holddown bolts on the guide vane actuator.
3. Pull the guide vane actuator away from the suction housing.
36
GUIDE VANE ACTUATOR
Fig. 29 — Guide Vane Actuator, Frame Size 6
a19-2123
GUIDE VANE ACTU ATOR
Fig. 30 — Guide Vane Actuator, Frame Size 7
37
GUIDE VANE
Fig. 31 — Guide Vane Actuator Detail
a19-2128
NOTE: Rotate coupling clockwise to close guide vanes. Rotate coupling counterclockwise to open guide vanes.
ACTUATOR
SET SCREW
ACTUATOR BRACKET
GUIDE VANE COUPLING
HOLDDOWN BOLTS (4)
4. If required, rotate the guide vane sprocket fully clockwise and spot-drill the guide vane actuator shaft. Spot-drilling is necessary when the guide vane actuator sprocket set screws on the guide vane actuator shaft need to be re-seated. (Remember: Spot-drill and tighten the first set screw before spot-drilling for the second set screw.)
Trim Refrigerant Charge — If to obtain optimal
chiller performance it becomes necessary to adjust the refriger­ant charge, operate the chiller at design load and then add or re­move refrigerant slowly until the difference between the leav­ing chilled water temperature and the cooler refrigerant tem­perature reaches design conditions or becomes a minimum. Do
not overcharge.
Refrigerant may be added either through the storage tank or directly into the chiller as described in the Charge Refrigerant into Chiller section.
To remove any excess refrigerant, follow the procedure in Transfer Refrigerant from Chiller to Pumpout Storage Tank section, Steps 1a and b, page 34.

WEEKLY MAINTENANCE

Check the Lubrication System —
el on the reservoir sight glass, and observe the level each week while the chiller is shut down.
If the level goes below the lower sight glass, check the oil reclaim system for proper operation. If additional oil is re­quired, add it through the oil drain charging valve (Fig. 2). A pump is required when adding oil against refrigerant pressure. The oil charge for the 19XR two-stage compressor frame size 6 is 29 gal. (110 L); for frame size 7 the oil charge is 44.5 gal (168 L).
The added oil must meet Carrier specifications for the 19XR chiller. Refer to Changing Oil Filter and Oil Changes sections on page 39. Any additional oil that is added should be logged by noting the amount and date. Any oil that is added due to oil loss that is not related to service will eventually return to the sump. It must be removed when the level is high.
An oil heater is controlled by the PIC 5 control system to maintain oil temperature (see the 19XR with PIC 5 Controls Operation and Troubleshooting manual) when the compressor
Mark the oil lev-
is off. If the PIC 5 control system shows that the heater is ener­gized and if the sump is still not heating up, the power to the oil heater may be off or the oil level may be too low. Check the oil level, the oil heater contactor voltage, and oil heater resistance.
The PIC 5 control system does not permit compressor start­up if the oil temperature is too low. The PIC 5 control system continues with start-up only after the temperature is within al­lowable limits.

SCHEDULED MAINTENANCE

Establish a regular maintenance schedule based on your ac­tual chiller requirements such as chiller load, run hours, and water quality. The time intervals listed in this section are of-
fered as guides to service only.
Service Ontime — The HMI will display a SERVICE
ONTIME value on the MAIN MENU RUN TIMES screen. This value should be reset to zero by the service person or the operator each time major service work is completed so that the time between service events can be viewed and tracked.
Inspect the Control Panel — Maintenance consists of
general cleaning and tightening of connections. Vacuum the cabinet to eliminate dust build-up. If the chiller control mal­functions, refer to the Troubleshooting Guide section on page 42 for control checks and adjustments.
WARNING
Ensure power to the starter is isolated when cleaning and tightening connections inside the starter enclosure. Failure to disconnect power could result in electrocution. The oil filter housing is at a high pressure. Relieve this pressure slowly. Failure to do so could result in serious personal injury.
38
Changing Oil Filter — Change the oil filter on a
yearly basis or when the chiller is opened for repairs. The 19XR chiller has an isolatable oil filter so that the filter may be changed with the refrigerant remaining in the chiller. Use the following procedure:
1. Ensure the compressor is off and the disconnect for the compressor is open.
2. Disconnect the power to the oil pump.
3. Close the oil filter isolation valves.
4. Close the isolation valves located on both ends of the oil filter. Have rags and a catch basin available to collect oil spillage.
5. Equalize the filter’s higher internal pressure to ambient by connecting an oil charging hose to the Schrader valve on the oil filter housing. Collect the oil-refrigerant mix­ture which is discharged.
6. Remove the oil filter assembly by loosening the hex nuts on both ends of the filter assembly.
7. Insert the replacement filter assembly with the arrow on the housing pointing away from the oil pump.
8. Rotate the assembly so that the Schrader drain valve is oriented at the bottom, and tighten the connection nut on each end to a torque of approximately 30 ft-lb (41 N-m).
WARNING
The oil filter housing is at a high pressure. Relieve this pressure slowly. Failure to do so could result in serious per­sonal injury.
9. Evacuate the filter housing by placing a vacuum pump on the charging valve. Follow the normal evacuation proce­dures. Shut the charging valve when done and reconnect the valve so that new oil can be pumped into the filter housing. Fill with the same amount that was removed; then close the charging valve.
10. Remove the hose from the charging valve, open the isola­tion valves to the filter housing, and turn on the power to the pump and the motor.
Oil Specification — If oil is added, it must meet the fol-
lowing Carrier specifications:
Oil Type for units using R-134a . . . . . . . . . . . . . . . . . .Inhibited
polyolester-based synthetic
compressor oil formatted for
use with HFC, gear-driven,
hermetic compressors.
ISO Viscosity Grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
The polyolester-based oil (P/N: PP23BZ103) may be
ordered from your local Carrier representative.
Oil Changes — Carrier recommends that a yearly oil
analysis be performed to determine when to change oil and when to perform a compressor inspection. However, if yearly analysis is not performed or available, the time between oil changes should be no longer than 5 years. Additionally Carrier recommends vibration measurement done at regular intervals to obtain a signature of the moving compressor parts as part of a total productive maintenance (TPM) program.
TO CHANGE THE OIL
1. Transfer the refrigerant into the chiller condenser vessel (for isolatable vessels) or to a pumpout storage tank.
2. Mark the existing oil level.
3. Open the control and oil heater circuit breaker.
4. When the chiller pressure is 5 psig (34 kPa) or less, drain the oil reservoir by opening the oil charging valve (Fig. 2). Slowly open the valve against refrigerant pressure.
5. Change the oil filter at this time. See Changing Oil Filter section.
6. Change the refrigerant filter at this time, see the next sec­tion, Refrigerant Filter.
7. Charge the chiller with oil. Charge until the oil level is equal to the oil level marked in Step 2. Turn on the power to the oil heater and let the PIC 5 warm it up to at least 140 F (60 C). Operate the oil pump manually, using the Control Test function, for 2 minutes. For shutdown condi­tions, the oil level should be full in the lower sight glass. If the oil level is above move the excess oil. The oil level should now be equal to the amount shown in Step 2.
1
/2 full in the upper sight glass, re-
Refrigerant Filter — A refrigerant filter/drier, located on
the refrigerant cooling line to the motor, should be changed once a year or more often if filter condition indicates a need for more frequent replacement. Change the filter by closing the fil­ter isolation valves (Fig. 2) and slowly opening the flare fittings with a wrench and back-up wrench to relieve the pressure. A moisture indicator sight glass is located beyond this filter to in­dicate the volume and moisture in the refrigerant. If the mois­ture indicator indicates moisture, locate the source of water im­mediately by performing a thorough leak check.
Oil Reclaim Filter — The oil reclaim system has a
strainer on the eductor suction line, a strainer on the discharge pressure line, and a filter on the cooler scavenging line. Re­place the filter once every 5 years or when the machine is opened for service. This filter does not contain desiccant for moisture removal, so changing the filter will not change the moisture indicator status. Change the filter by closing the filter isolation valves and slowly opening the flare fitting with a wrench and back-up wrench to relieve the pressure. Change the strainers once every 5 years or whenever refrigerant is evacuat­ed from the cooler.
Inspect Refrigerant Float System — Perform this
inspection only if the following symptoms are seen.
• There is a simultaneous drop in cooler pressure and increase in condenser pressure. This will be accompa­nied by an increase in kW/Ton.
• The liquid line downstream of the float valve feels warm. This indicates condenser gas flowing past the float. An increase in kW/Ton will also occur.
1. Transfer the refrigerant into the cooler vessel or into a pumpout storage tank.
2. Remove the float access cover.
3. Clean the chamber and valve assembly thoroughly. Be sure the valve moves freely. Ensure that all openings are free of obstructions.
4. Examine the cover gasket and replace if necessary. In­spect the orientation of the float slide pin. It must be pointed toward the bubbler tube for proper operation.
ECONOMIZER FLOAT SYSTEM — For two-stage com­pressors, the economizer has a low side ball type float system. The float refrigerant level can be observed through the two sight glasses located on the float cover under the condenser. See Fig. 32 for float detail. Inspect the float every five years. Clean the chamber and the float valve assembly. Be sure that the float moves freely and the ball bearings that the float moves on are clean.
ECONOMIZER DAMPER VALVE — The damper valve should be inspected every 5 years or when the condenser is opened for service. Check the economizer damper actuator’s movement and wiring.
39
Inspect Relief Valves and Piping — The relief valves
TOP VIEW
1
2
3
Fig. 32 — Economizer Float System (Two-Stage Compressor Chiller)
LEGEND
1—Float Ball 2—Refrigerant Exit 3—Bearings
a19-2124
on this chiller protect the system against the potentially danger­ous effects of overpressure. To ensure against damage to the equipment and possible injury to personnel, these devices must be kept in peak operating condition.
As a minimum, the following maintenance is required.
1. At least once a year, disconnect the vent piping at the valve outlet and carefully inspect the valve body and mechanism for any evidence of internal corrosion or rust, dirt, scale, leakage, etc.
2. If corrosion or foreign material is found, do not attempt to repair or recondition. Replace the valve.
3. If the chiller is installed in a corrosive atmosphere or the relief valves are vented into a corrosive atmosphere, in­spect the relief valves at more frequent intervals.
Compressor Bearing and Gear Maintenance —
The key to good bearing and gear maintenance is proper lubri­cation. Use the proper grade of oil, maintained at recom­mended level, temperature, and pressure. Inspect the lubrication system regularly and thoroughly. Annual oil analy­sis and vibration measurements are recommended.
Excessive bearing wear can sometimes be detected through increased vibration or increased bearing temperature. Gears, babbitted journal bearings, and thrust bearings should be exam­ined for signs of wear based on the results of the annual oil analysis and vibration levels. To inspect the bearings, a com­plete compressor teardown is required. Only a trained service technician should remove and examine the bearings. The fre­quency of examination is determined by the hours of chiller op­eration, load conditions during operation, and the condition of the oil and the lubrication system. High speed shaft rolling ele­ment bearings cannot be field inspected; excessive vibration is the primary sign of wear or damage. If either symptom ap­pears, contact an experienced and responsible service organiza­tion for assistance.

Inspect the Heat Exchanger Tubes and Flow Devices

COOLER AND OPTIONAL FLOW DEVICES — Inspect and clean the cooler tubes at the end of the first operating sea­son. Because these tubes have internal ridges, a rotary-type tube cleaning system is needed to fully clean the tubes. Inspect the tubes’ condition to determine the scheduled frequency for future cleaning and to determine whether water treatment in the chilled water/brine circuit is adequate. Inspect the entering and leaving chilled water temperature sensors and flow devices for signs of corrosion or scale. Replace a sensor or Schrader fitting if corroded or remove any scale if found.
CONDENSER AND OPTIONAL FLOW DEVICES — Since this water circuit is usually an open-type system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least once per year and more often if the water is contaminated. Inspect the entering and leaving condenser water sensors and flow devices for signs of corrosion or scale. Replace the sensor or Schrader fitting if corroded or remove any scale if found.
Higher than normal condenser pressures, together with the inability to reach full refrigeration load, usually indicate dirty tubes or air in the chiller. If the refrigeration log indicates a rise above normal condenser pressures, check the condenser refrig­erant temperature against the leaving condenser water tempera­ture. If this reading is more than what the design difference is supposed to be, the condenser tubes may be dirty or water flow may be incorrect. Because HFC-134a is a high-pressure refrig­erant, air usually does not enter the chiller.
During the tube cleaning process, use brushes specially de­signed to avoid scraping and scratching the tube wall. Contact your Carrier representative to obtain these brushes. Do not use wire brushes.
40
Hard scale may require chemical treatment for its preven-
CONTACTOR
TERMINAL
STRIP
FUSES
TRANSFORMER
SWITCH
Fig. 33 — Pumpout Control Box (Interior)
a19-1569
tion or removal. Consult a water treatment specialist for proper treatment.
Water Leaks — The refrigerant moisture indicator on the
refrigerant motor cooling line (Fig. 2) indicates whether there is water leakage during chiller operation. Water leaks should be repaired immediately.
CAUTION
The chiller must be dehydrated after repair of water leaks or damage may result. See Chiller Dehydration section, page 18.
Water Treatment — Untreated or improperly treated
water may result in corrosion, scaling, erosion, or algae. The services of a qualified water treatment specialist should be ob­tained to develop and monitor a treatment program.
CAUTION
Water must be within design flow limits, clean, and treated to ensure proper chiller performance and reduce the poten­tial of tube damage due to corrosion, scaling, erosion, and algae. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated water.
Inspect the Starting Equipment — Before work-
ing on any starter, shut off the chiller, open and tag all discon­nects supplying power to the starter.
CAUTION
The motor leads must be disconnected from the starter before an insulation test is performed. The voltage gener­ated from the tester can damage the starter components.
Optional Pumpout System Maintenance — For
pumpout unit compressor maintenance details, refer to the 19XR Positive Pressure Storage System Installation, Start-Up, and Service Instructions.
OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE — Use oil conforming to Carrier specifications for reciprocating compressor usage. Oil requirements are as follows:
ISO Viscosity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 or 220
Carrier Part Number . . . . . . . . . . . PP23BZ103 or PP23BZ104
The total oil charge is 13 oz. (0.5 L).
Oil should be visible in the pumpout compressor sight glass both during operation and at shutdown. Always check the oil level before operating the pumpout compressor. Before adding changing oil, relieve the refrigerant pressure through the access valves.
Relieve refrigerant pressure and add oil to the pumpout unit as follows:
1. Close service valves 2 and 4.
2. Run the pumpout compressor in Automatic mode for one minute or until the vacuum switch is satisfied and com­pressor shuts off.
3. Move the pumpout selector switch to OFF. Pumpout compressor shell should now be under vacuum.
4. Oil can be added to the shell with a hand oil pump through the access valve in the compressor base.
NOTE: The compressor access valve has a self-sealing fitting which will require a hose connection with a depressor to open.
OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS (Fig. 33) — The optional pumpout system high-pressure switch opens at 185 psig (1276 kPa) and closes at 140 psig (965 kPa). Check the switch setting by operating the pumpout compressor and slowly throttling the pumpout condenser water.
WARNING
The disconnect on the starter front panel does not always de-energize all internal circuits. Open all internal and remote disconnects before servicing the starter. Failure to follow this procedure may result in personal injury by elec­tric shock.
Periodically vacuum accumulated debris on the internal
parts. Use electrical cleaner for electrical parts as required.
Power connections on newly installed starters may relax and loosen after a month of operation. Turn power off and re­tighten. Recheck annually thereafter.
CAUTION
Loose power connections can cause voltage spikes, over­heating, malfunctioning, or failures.
Recalibrate Pressure Transducers — Once a
year, the pressure transducers should be checked against a pres­sure gage reading. Check all eight transducers: the 2 oil differ­ential pressure transducers, the condenser pressure transducer, the cooler pressure transducer, and the optional waterside pres­sure transducer pairs (consisting of 4 flow devices: 2 cooler, 2 condenser). For details, see page 46.
Ordering Replacement Chiller Parts —
When ordering Carrier specified parts, the following infor-
mation must accompany an order:
• chiller model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment.
41

TROUBLESHOOTING GUIDE

Overview —
to help the operator and technician troubleshoot a 19XR chiller.
• The HMI shows the chiller’s actual operating conditions and can be viewed while the unit is running.
• The HMI default screen indicates when an alarm occurs. Once all alarms have been cleared (by correcting the problems), the HMI default screen indicates normal operation. For information about displaying and resetting alarms and a list of alert codes, see the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
• The Configuration menu screens display information that helps to diagnose problems with chilled water tempera­ture control, chilled water temperature control overrides, hot gas bypass, surge algorithm status, and time schedule operation.
• The quick test feature facilitates the proper operation and test of temperature sensors, pressure transducers, the guide vane actuator, diffuser actuator (if equipped), oil pump, water pumps, tower control, and other on/off out ­puts while the compressor is stopped. It also has the abil­ity to lock off the compressor and turn on water pum ps for pumpout operation. The HMI shows the temperatures and pressures required during these operations.
• If an operating fault is detected, an alarm indicator is is displayed on the HMI default screen. A more detailed message — along with a diagnostic message — is also stored in the Current Alarms table.
• Review the Alarms History table to view other less criti­cal events which may have occurred. Compare timing of relevant events and alarms.
For detailed information about alarms, see the 19XR with
PIC 5 Controls Operation and Troubleshooting manual. Press the bell icon in the top right corner of the home screen to access current alarms and alarm history, and to reset alarms.
The PIC 5 control system has many features
Checking Display Messages — The first area to
check when troubleshooting the 19XR is the HMI display. Sta­tus messages are displayed at the bottom of the screen, and the alarm icon indicates a fault. For a complete list of alarms, see the 19XR with PIC 5 Controls Operation and Troubleshooting manual.
Checking Temperature Sensors — All tempera-
ture sensors are thermistor-type sensors. This means that the re­sistance of the sensor varies with temperature. All sensors have the same resistance characteristics. If the controls are on, deter­mine sensor temperature by measuring voltage drop; if the con­trols are powered off, determine sensor temperature by measur­ing resistance. Compare the readings to the values listed in Tables 11 and 12.
RESISTANCE CHECK — Turn off the control power and, from the module, disconnect the terminal plug of the sensor in question. With a digital ohmmeter, measure sensor resistance between receptacles as designated by the wiring diagram. The resistance and corresponding temperature are listed in Tables 11 and 12. Check the resistance of both wires to ground. This resistance should be infinite.
VOLT A G E DR O P — The voltage drop across any energized sensor can be measured with a digital voltmeter while the con­trol is energized. Table 11 or 12 lists the relationship between temperature and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when measuring voltage to prevent damage to the sensor leads, connector plugs, and mod­ules. Sensors should also be checked at the sensor plugs.
CAUTION
Relieve all refrigerant pressure or drain the water before removing any thermowell threaded into the refrigerant pressure boundary. Failure to do so could result in personal injury and equipment damage.
42
Table 11 — Thermistor Temperature (F) vs. Resistance/Voltage Drop
TEMPERATURE
(F)
PIC
VOLTAGE
DROP (V)
RESISTANCE
(OHMS)
–25 4.700 97,706 –24 4.690 94,549 –23 4.680 91,474 –22 4.670 88,480 –21 4.659 85,568 –20 4.648 82,737 –19 4.637 79,988 –18 4.625 77,320 –17 4.613 74,734 –16 4.601 72,229 –15 4.588 69,806 –14 4.576 67,465 –13 4.562 65,205 –12 4.549 63,027 –11 4.535 60,930 –10 4.521 58,915
–9 4.507 56,981 –8 4.492 55,129 –7 4.477 53,358 –6 4.461 51,669 –5 4.446 50,062 –4 4.429 48,536 –3 4.413 47,007 –2 4.396 45,528 –1 4.379 44,098
0 4.361 42,715 1 4.344 41,380 2 4.325 40,089 3 4.307 38,843 4 4.288 37,639 5 4.269 36,476 6 4.249 35,354 7 4.229 34,270 8 4.209 33,224
9 4.188 32,214 10 4.167 31,239 11 4.145 30,298 12 4.123 29,389 13 4.101 28,511 14 4.079 27,663 15 4.056 26,844 16 4.033 26,052 17 4.009 25,285 18 3.985 24,544 19 3.960 23,826 20 3.936 23,130 21 3.911 22,455 22 3.
88
6 21,800
23 3.861 21,163 24 3.835 20,556 25 3.808 19,967 26 3.782 19,396 27 3.755 18,843 28 3.727 18,307 29 3.700 17,787 30 3.672 17,284 31 3.644 16,797 32 3.617 16,325 33 3.588 15,868 34 3.559 15,426 35 3.530 14,997 36 3.501 14,582 37 3.471 14,181 38 3.442 13,791 39 3.412 13,415 40 3.382 13,050 41 3.353 12,696 42 3.322 12,353 43 3.291 12,021 44 3.260 11,699 45 3.229 11,386 46 3.198 11,082 47 3.167 10,787 48 3.135 10,500 49 3.104 10,221 50 3.074 9,949 51 3.042 9,689 52 3.010 9,436 53 2.978 9,190 54 2.946 8,951 55 2.914 8,719 56 2.882 8,494 57 2.850 8,275 58 2.819 8,062 59 2.788 7,855 60 2.756 7,655 61 2.724 7,460 62 2.692 7,271 63 2.660 7,088 64 2.628 6,909 65 2.596 6,736
TEMPERATURE
(F)
PIC
VOLTAGE
DROP (V)
RESISTANCE
(OHMS)
66 2.565 6,568 67 2.533 6,405 68 2.503 6,246 69 2.472 6,092 70 2.440 5,942 71 2.409 5,796 72 2.378 5,655 73 2.347 5,517 74 2.317 5,382 75 2.287 5,252 76 2.256 5,124 77 2.227 5,000 78 2.197 4,880 79 2.167 4,764 80 2.137 4,650 81 2.108 4,539 82 2.079 4,432 83 2.050 4,327 84 2.021 4,225 85 1.993 4,125 86 1.965 4,028 87 1.937 3,934 88 1.909 3,843 89 1.881 3,753 90 1.854 3,667 91 1.827 3,582 92 1.800 3,500 93 1.773 3,420 94 1.747 3,342 95 1.721 3,266 96 1.695 3,192 97 1.670 3,120 98 1.644 3,049
99 1.619 2,981 100 1.595 2,914 101 1.570 2,849 102 1.546 2,786 103 1.523 2,724 104 1.499 2,663 105 1.476 2,605 106 1.453 2,547 107 1.430 2,492 108 1.408 2,437 109 1.386 2,384 110 1.364 2,332 111 1.343 2,282 112 1.321 2,232 113 1.
300
2,184
114 1.279 2,137 115 1.259 2,092 116 1.239 2,047 117 1.219 2,003 118 1.200 1,961 119 1.180 1,920 120 1.161 1,879 121 1.143 1,840 122 1.124 1,801 123 1.106 1,764 124 1.088 1,727 125 1.070 1,691 126 1.053 1,656 127 1.036 1,622 128 1.019 1,589 129 1.002 1,556 130 0.986 1,524 131 0.969 1,493 132 0.953 1,463 133 0.938 1,433 134 0.922 1,404 135 0.907 1,376 136 0.893 1,348 137 0.878 1,321 138 0.864 1,295 139 0.849 1,269 140 0.835 1,244 141 0.821 1,219 142 0.808 1,195 143 0.795 1,172 144 0.782 1,149 145 0.769 1,126 146 0.756 1,104 147 0.744 1,083 148 0.731 1,062 149 0.719 1,041 150 0.707 1,021 151 0.696 1,002 152 0.684 983 153 0.673 964 154 0.662 945 155 0.651 928 156 0.640 910
TEMPERATURE
(F)
PIC
VOLTAGE
DROP (V)
RESISTANCE
(OHMS)
157 0.630 893 158 0.619 876 159 0.609 859 160 0.599 843 161 0.589 827 162 0.579 812 163 0.570 797 164 0.561 782 165 0.551 768 166 0.542 753 167 0.533 740 168 0.524 726 169 0.516 713 170 0.508 700 171 0.499 687 172 0.491 675 173 0.484 663 174 0.476 651 175 0.468 639 176 0.460 628 177 0.453 616 178 0.445 605 179 0.438 595 180 0.431 584 181 0.424 574 182 0.418 564 183 0.411 554 184 0.404 544 185 0.398 535 186 0.392 526 187 0.385 516 188 0.379 508 189 0.373 499 190 0.367 490 191 0.361 482 192 0.356 474 193 0.350 466 194 0.344 458 195 0.339 450 196 0.333 442 197 0.328 435 198 0.323 428 199 0.318 421 200 0.313 414 201 0.308 407 202 0.304 400 203 0.299 393 204 0
.
294 387
205 0.290 381 206 0.285 374 207 0.281 368 208 0.277 362 209 0.272 356 210 0.268 351 211 0.264 345 212 0.260 339 213 0.256 334 214 0.252 329 215 0.248 323 216 0.245 318 217 0.241 313 218 0.237 308 219 0.234 303 220 0.230 299 221 0.227 294 222 0.224 289 223 0.220 285 224 0.217 280 225 0.214 276 226 0.211 272 227 0.208 267 228 0.205 263 229 0.203 259 230 0.198 255 231 0.195 251 232 0.192 248 233 0.190 244 234 0.187 240 235 0.184 236 236 0.182 233 237 0.179 229 238 0.176 226 239 0.174 223 240 0.172 219 241 0.169 216 242 0.167 213 243 0.164 210 244 0.162 207 245 0.160 204 246 0.158 201 247 0.155 198 248 0.153 195
43
Table 12 — Thermistor Temperature (C) vs. Resistan ce/Voltage Drop
TEMPERATURE
(C)
–33 4.722 105 616 –32 4.706 99 640 –31 4.688 93 928 –30 4.670 88 480 –29 4.650 83 297 –28 4.630 78 377 –27 4.608 73 722 –26 4.586 69 332 –25 4.562 65 205 –24 4.538 61 343 –23 4.512 57 745 –22 4.486 54 411 –21 4.458 51 341 –20 4.429 48 536 –19 4.399 45 819 –18 4.368 43 263 –17 4.336 40 858 –16 4.303 38 598 –15 4.269 36 476 –14 4.233 34 484 –13 4.196 32 613 –12 4.158 30 858 –11 4.119 29 211 –10 4.079 27 663
–9 4.037 26 208 –8 3.994 24 838 –7 3.951 23 545 –6 3.906 22 323 –5 3.861 21 163 –4 3.814 20 083 –3 3.765 19 062 –2 3.716 18 097 –1 3.667 17 185
0 3.617 16 325 1 3.565 15 513 2 3.512 14 747 3 3.459 14 023 4 3.406 13 341 5 3.353 12 696 6 3.298 12 087 7 3.242 11 510 8 3.185 10 963
9 3.129 10 444 10 3.074 9 949 11 3.016 9 486 12 2.959 9 046 13 2.901 8 628 14 2.844 15 2.788 7 855 16 2.730 7 499 17 2.672 7 160 18 2.615 6 839 19 2.559 6 535 20 2.503 6 246 21 2.447 5 972 22 2.391 5 711 23 2.335 5 463 24 2.280 5 226 25 2.227 5 000 26 2.173 4 787 27 2.120 4 583 28 2.067 4 389 29 2.015 4 204 30 1.965 4 028 31 1.914 3 861 32 1.865 3 701 33 1.816 3 549 34 1.768 3 404 35 1.721 3 266 36 1.675 3 134 37 1.629 3 008 38 1.585 2 888 39 1.542 2 773 40 1.499 2 663 41 1.457 2 559 42 1.417 2 459 43 1.377 2 363
PIC
VOLTAGE
DROP (V)
RESISTANCE
(OHMS)
2
8 23
TEMPERATURE
(C)
44 1.338 2 272 45 1.300 2 184 46 1.263 2 101 47 1.227 2 021 48 1.192 1 944 49 1.158 1 871 50 1.124 1 801 51 1.091 1 734 52 1.060 1 670 53 1.029 1 609 54 0.999 1 550 55 0.969 1 493 56 0.941 1 439 57 0.913 1 387 58 0.887 1 337 59 0.861 1 290 60 0.835 1 244 61 0.811 1 200 62 0.787 1 158 63 0.764 1 117 64 0.741 1 079 65 0.719 1 041 66 0.698 1 006 67 0.677 971 68 0.657 938 69 0.638 906 70 0.619 876 71 0.601 846 72 0.583 818 73 0.566 791 74 0.549 765 75 0.533 740 76 0.518 715 77 0.503 692 78 0.488 670 79 0.474 648 80 0.460 628 81 0.447 608 82 0.434 588 83 0.422 570 84 0.410 552 85 0.398 535 86 0.387 518 87 0.376 502 88 0.365 487 89 0.355 472 90 0.344 458 91 0.335 92 0.325 431 93 0.316 418 94 0.308 405 95 0.299 393 96 0.291 382 97 0.283 371 98 0.275 360
99 0.267 349 100 0.260 339 101 0.253 330 102 0.246 320 103 0.239 311 104 0.233 302 105 0.227 294 106 0.221 286 107 0.215 278 108 0.210 270 109 0.205 262 110 0.198 255 111 0.193 248 112 0.188 242 113 0.183 235 114 0.178 229 115 0.174 223 116 0.170 217 117 0.165 211 118 0.161 205 119 0.157 200 120 0.153 195
PIC
VOLTAGE
DROP (V)
RESISTANCE
(OHMS)
444
44
CHECK SENSOR ACCURACY — Place the sensor in a
a19-2216
Fig. 34 — Bearing 1 Sensor Wiring from Back of Terminal Block
TERMINAL BLOCKS LOCATED BETWEEN HEATER AND OIL PUMP
Fig. 35 — Bearings 2-4 Sensor Wiring from Back of Terminal Block
a19-2125
medium of known temperature and compare that temperature to the measured reading. The thermometer used to determine the temperature of the medium should be of laboratory quality with 0.5 F (0.25 C) graduations. The sensor in question should be accurate to within 2 F (1.2 C).
Note that the PIC 5 control module, MAINTENANCE menu, offers a temperature sensor calibration feature where the sensor temperature can be offset. To use this feature, place the sensor at 32 F (0 C) or other known temperature. Read the raw temperature and calculate offset based on the reading seen in the TEMP_CAL menu. Enter and execute the offset, which cannot exceed ± 2 F (1.2 C).
See Fig. 2 for sensor locations. The sensors are immersed directly in the refrigerant or water circuits. When installing a
BEARING #1
new sensor, apply a pipe sealant or thread sealant to the sensor threads.
An additional thermistor, factory installed in the bottom of the cooler barrel, is displayed as Evap Refrig Liquid Temp on the TEMPERATURES display screen. This thermistor pro­vides additional protection against a loss of water flow.
DUAL TEMPERATURE SENSORS — For servicing con­venience, there are 2 redundant sensors each on the bearing and motor temperature sensors. If one of the sensors is damaged, the other can be used by simply moving a wire. The number 2 terminal in the sensor terminal box is the common line. To use the second sensor, move the wire from the number 1 position to the number 3 position. See Fig. 34 or Fig. 35.
TERMINAL BLOCK LOCATED ON END OF MOTOR COVER
45
Checking Pressure Transducers — There are 4
factory-installed pressure transducers measuring refrigerant and oil pressure, and a fifth pressure transducer measuring economizer pressure.
These transducers can be calibrated if necessary. It is necessary to calibrate at initial start-up, particularly at high altitude locations, to ensure the proper refrigerant temperature/ pressure relationship. Each transducer is supplied with 5 vdc power. If the power supply fails, a transducer voltage reference alarm occurs. If the transducer reading is suspected of being faulty, check the TRANSDUCER VOLTAGE REF supply voltage. It should be 5 vdc ± 0.5 v as displayed in MAINTE­NANCE MENU MAINTENANCE OTHERS, where all the transducer voltages are shown. If the TRANSDUCER VOLTAGE REF supply voltage is correct, the transducer should be recalibrated or replaced.
Also check that inputs have not been grounded and are not receiving anything other than a 4 to 20 mA signal.
TRANSDUCER REPLACEMENT — Since the transducers are mounted on Schrader-type fittings, there is no need to re­move refrigerant from the vessel when replacing the transduc­ers. Disconnect the transducer wiring. Do not pull on the trans- ducer wires. Unscrew the transducer from the Schrader fitting. When installing a new transducer, do not use pipe sealer (which can plug the sensor). Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks.
WARNING
Be sure to use a back-up wrench on the Schrader fitting whenever removing a transducer, since the Schrader fitting may back out with the transducer, causing a large leak and possible injury to personnel.
COOLER AND CONDENSER PRESSURE TRANS­DUCE R CALI BRATIO N — Calibration can be checked by comparing the pressure readings from the transducer to an accurate refrigeration gage reading. These readings can be viewed or calibrated from the HMI screen. The transducer can be checked and calibrated at 2 pressure points. These calibra­tion points are 0 psig (0 kPa) and between 25 and 250 psig (173 and 1724 kPa). Wiring is shown in Fig. 36. To calibrate these transducers:
1. Shut down the compressor, cooler, and condenser pumps. NOTE: There should be no flow through the heat
exchangers.
2. Disconnect the transducer in question from its Schrader fitting for cooler or condenser transducer calibration. For oil pressure or flow device calibration, leave the transduc­er in place.
NOTE: If the cooler or condenser vessels are at 0 psig (0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for zero without remov­ing the transducer from the vessel.
3. Access the PRESSURE or HYDRAULIC STATUS screen and view the particular transducer reading. To cal­ibrate oil pressure or waterside flow device, view the par­ticular reading. It should read 0 psig (0 kPa). If the reading is not 0 psig (0 kPa), but within ± 5 psig (35 kPa), the value may be set to zero from the Maintenance Menu while the appropriate transducer parameter is highlighted. The value will now go to zero.
If the transducer value is not within the calibration range, the transducer returns to the original reading. If the pres­sure is within the allowed range (noted above), check the voltage ratio of the transducer. To obtain the voltage ratio, divide the voltage (dc) input from the transducer by the supply voltage signal or measure across the positive
(+ red) and negative (– black) leads of the transducer. The input to reference voltage ratio must be between 0.80 and
0.11 for the software to allow calibration. Rotate the wa­terside flow pressure device from the inlet nozzle to the outlet nozzle and repeat this step. If rotating the waterside flow device does not allow calibration, then pressurize the transducer until the ratio is within range. Then attempt calibration again.
4. Pressures can be calibrated between 100 and 250 psig (689.5 and 1723.7 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen cylinder). For calibration, access the Pressure Sensor Calibration Menu from the Maintenance Menu and calibrate the ap­propriate sensor.
The PIC 5 control system does not allow calibration if the transducer is too far out of calibration. In this case, a new trans­ducer must be installed and re-calibrated. If calibration prob­lems are encountered on the OIL PRESSURE DELTA P chan­nel, sometimes swapping the compressor oil discharge pressure transducer and the oil sump pressure transducer will offset an adverse transducer to to proceed.
OPTIONAL THERMAL DISPERSION FLOW SWITCH CALI BRA TIO N — Set the flow through the water circuit to the minimum safe flow that will be encountered. Thermal dis­persion switch inputs are shown in Fig. 37. The Water Pressure Option must be enabled.
Reduce the sensitivity of the switch by turning the adjust­ment counter-clockwise until the yellow LED turns off. This indicates that the switch is now open.
Increase the sensitivity of the flow switch by turning the ad­justment potentiometer clockwise until the yellow LED is lit.
In case of nuisance trips at low flow increase the sensitivity of the switch by turning the potentiometer clockwise.
HYDRAULIC STATUS — The HYDRAULIC STATUS screen (access from the Main Menu) provides a convenient way to detect if any of the cooler/condenser pressure switches (if installed) are in need of calibration. With no flow and no added resistors the water delta should read zero psig (0 kPa). If it does not, the value may be set to zero using PRESSURE SENSOR CALIB located in the Maintenance Menu.
lerance stack
up and allow the calibration
High Altitude Locations — Because the chiller is ini-
tially calibrated at sea level, it is necessary to recalibrate the pressure transducers if the chiller has been moved to a high altitude location. See the calibration procedure in the 19XR with PIC 5 Controls Operation and Troubleshooting guide. Note that Atmospheric Pressure can be adjusted in the Service Parameters Menu (located in the Configuration Menu).
46
a19-2292
Fig. 36 — Inputs for Optional Waterside Delta P Transducers for IOB4
47
4.3 kOhm
Fig. 37 — Inputs for Optional Thermal Dispersion Switches for IOB4
(Evaporator Flow Switch, Condenser Flow Switch)
4.3 kOhm
4.3 kOhm
4.3 kOhm
TB (FIELD SUPPLIED)
EVAP FS
COND FS
(+) (G)
(-)
(+) (G)
(-)
CONTROL BOARD.
Quick Test — The Quick Test feature is located in the
Main Menu. Through this feature one can perform guide vane calibration, test chiller status, test the status of various actua­tors, view water temperature deltas, test oil pump and oil heater relays, as well as control inlet guide vane, hot gass bypass, economizer damper, alarms, condenser and chilled water pumps. The tests can help to determine whether a switch is de­fective or a pump relay is not operating, as well as other useful troubleshooting issues. During pumpdown operations, the pumps are energized to prevent freeze-up and the vessel pres­sures and temperatures are displayed.
CHILLED WA TER PUMP
CONDENSER WA TER PUMP
TOWER FAN HIGH
TOWER FAN LOW
a19-2284
Pumpdown/Lockout — The Pumpdown/Lockout fea-
ture, available from the Maintenance Menu, prevents compres­sor start-up when there is no refrigerant in the chiller or if the vessels are isolated. The Terminate Lockout feature ends the Pumpdown/Lockout after the pumpdown procedure is reversed and refrigerant is added.
Physical Data — Tables 13-32 and Fig. 38-50 provide
additional information on component weights, compressor fits and clearances, physical and electrical data, and wiring sche­matics for the operator’s convenience during troubleshooting.
48
Table 13 — 19XR Two-Stage Compressor Frame Size 6
Heat Exchanger Weights (English)
CODE†
A40 16,877 18,542 1647 927 4328 4553 A41 17,270 19,062 1773 927 4557 4890 A42 17,690 19,565 1887 927 4816 5213 A45 16,968 18,493 1599 927 4453 4582 A46 17,371 19,063 1714 927 4701 4949 A47 17,761 19,578 1837 927 4941 5281
A60 18,354 20,139 1878 1074 4721 5029 A61 18,807 20,745 2022 1074 4984 5415 A62 19,295 21,330 2152 1074 5280 5786 A65 18,469 20,095 1823 1074 4859 5060 A66 18,936 20,758 1954 1074 5144 5482 A67 19,389 21,357 2095 1074 5419 5862
A4A 15,540 17,089 1681 861 4183 4524 A4B 15,794 17,472 1792 861 4392 4859 A4C 16,063 17,812 1897 861 4615 5137 A4F 15,592 17,076 1626 861 4322 4588
A4G 15,845 17,405 1736 861 4531 4867
A4H 16,249 17,821 1890 861 4865 5219
A6A 16,465 18,359 1917 998 4555 4996 A6B 16,758 18,806 2044 998 4794 5368 A6C 17,070 19,202 2164 998 5050 5698 A6F 16,535 18,356 1854 998 4709 5068
A6G 16,829 18,739 1979 998 4948 5387
A6H 17,296 19,225 2156 998 5331 6156
DRY RIGGING WEIGHT (lb)* REFRIGERANT WEIGHT (lb) WATER WEIGHT (lb)
COOLER
ONLY
CONDENSER
ONLY
COOLER
ONLY
CONDENSER
ONLY
COOLER
ONLY
CONDENSER
ONLY
B40 21,217 1233 5850 B41 21,965 1233 6333 B42 22,581 1233 6729 B45 21,173 1233 5904 B46 21,909 1233 6379 B47 22,653 1233 6859
B60 23,061 1423 6464 B61 23,932 1423 7018 B62 24,649 1423 7473 B65 23,022 1423 6521 B66 23,879 1423 7066 B67 24,745 1423 7617
B4A 19,217 1148 5756 B4B 19,793 1148 6243 B4C 20,254 1148 6633 B4F 19,217 1148 5852
B4G 19,721 1148 6279
B4H 20,318 1148 6785
B6A B6B 21,465 1326 6915 B6C 22,002 1326 7362 B6F 20,806 1326 6462
B6G 21,393 1326 6951
B6H 22,088 1326 8379
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and do not include refrigerant weight. †See Model Number Nomenclature on page 5.
20,794 1326 6
NOTES:
1. Cooler weight includes the suction elbow and the distribution piping to the economizer and two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis­charge pipe, and mizer to the float chamber and two-pass Victaulic dished heads.
the distribution piping weight from the econo-
357
49
Table 14 — 19XR Two-Stage Compressor Frame Size 6
Heat Exchanger Weights (SI)
CODE†
A40 7655 8 410 747 420 1963 2065 A41 7833 8 646 804 420 2067 2218 A42 8024 8 875 856 420 2184 2365 A45 7697 8 388 725 420 2020 2078 A46 7879 8 647 777 420 2132 2245 A47 8056 8 880 833 420 2241 2395
A60 8325 9 135 852 487 2141 2281 A61 8531 9 410 917 487 2261 2456 A62 8752 9 675 976 487 2395 2624 A65 8377 9 115 827 487 2204 2295 A66 8589 9 416 886 487 2333 2487 A67 8795 9 687 950 487 2458 2659
A4A 7049 7 751 762 391 1897 2052 A4B 7164 7 925 813 391 1992 2204 A4C 7286 8 079 860 391 2093 2330
A4F 7072 7 746 738 391 1960 2081 A4G 7187 7 895 787 391 2055 2208 A4H 7370 8 083 857 391 2207 2367
A6A 7468 8 328 870 453 2066 2266 A6B 7601 8 530 927 453 2175 2435 A6C 7743 8 710 982 453 2291 2585
A6F 7500 8 326 841 453 2136 2299 A6G 7633 8 500 898 453 2244 2444 A6H 7845 8 730 978 453 2418 2792
DRY RIGGING WEIGHT (kg)* REFRIGERANT WEIGHT (kg) WATER WEIGHT (kg)
COOLER
ONLY
CONDENSER
ONLY
COOLER
ONLY
CONDENSER
ONLY
COOLER
ONLY
CONDENSER
ONLY
B40 9 624 559 2653
B41 9 963 559 2873
B42 10 243 559 3052
B45 9 604 559 2678
B46 9 938 559 2893
B47 10 275 559 3111
B60 10 460 645 2932
B61 10 855 645 3183
B62 11 181 645 3390
B65 10 442 645 2958
B66 10 831 645 3205
B67 11 224 645 3455
B4A 8 717 521 2611 B4B 8 978 521 2832 B4C 9 187 521 3009
B4F 8 717 521 2654 B4G 8 945 521 2848 B4H 9 216 521 3078
B6A B6B 9 736 601 3137 B6C 9 980 601 3339
B6F 9 487 601 2931 B6G 9 704 601 3153 B6H 10 019 601 3801
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and do not include refrigerant weight. †See Model Number Nomenclature on page 5.
9 432 601 2
NOTES:
1. Cooler weight includes the suction elbow and the distribution piping to the economizer and two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis­charge pipe, and mizer to the float chamber and two-pass Victaulic dished heads.
the distribution piping weight from the econo-
883
50
Table 15 — 19XR Two-Stage Compressor Frame Size 7
Heat Exchanger Weights (English)
CODE†
B60 24,704 2273 6340 B61 25,337 2355 6737 B62 25,964 2460 7116 B65 25,014 2185 6485 B66 25,631 2275 6873 B67 26,264 2379 7255
B6A 22,819 2081 6159 B6B 23,299 2162 6568 B6C 23,829 2256 6993 B6F 23,139 1951 6344
B6G 23,648 2019 6774
B6H 24,171 2120 7194
C60 30,825 29,857 2647 1610 8475 8,630 C61 31,536 30,881 2751 1610 8924 9,275 C62 32,467 31,871 2875 1610 9474 9,916 C65 31,135 29,982 2562 1610 8645 8,684 C66 31,851 31,064 2666 1610 9097 9,362 C67 32,777 32,186 2793 1610 9644 10,078
C6A 28,641 27,676 2443 1497 6898 8,675 C6B 29,167 28,315 2534 1497 7352 9,216 C6C 29,750 28,918 2627 1497 7823 9,752 C6F 28,929 27,774 2334 1497 7724 8,710
C6G 29,478 28,457 2415 1497 8194 9,283
C6H 30,083 29,223 2500 1497 8681 9,935
DRY RIGGING WEIGHT (lb)* REFRIGERANT WEIGHT (lb) WATER WEIGHT (lb)
COOLER ONLY CONDENSER ONLY COOLER ONLY
CONDENSER
ONLY
COOLER ONLY CONDENSER ONLY
D60 38,296 2097 11,473 D61 39,624 2097 12,309 D62 41,031 2097 13,210 D65 37,624 2097 11,617 D66 38,837 2097 12,387 D67 40,460 2097 13,410
D6A 35,286 1947 11,401 D6B 36,328 1947 12,255 D6C 37,288 1947 13,078 D6F 34,447 1947 11,448
D6G 35,637 1947 12,408
D6H 36,663 1947 13,278
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and do not include refrigerant weight. †See Model Number Nomenclature on page 5.
NOTES:
1. Cooler weight includes the suction elbow and the distribution piping to the economizer and two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis­charge pipe, and mizer to the float chamber and two-pass Victaulic dished heads.
the distribution piping weight from the econo-
51
Table 16 — 19XR Two-Stage Compressor Frame Size 7
Heat Exchanger Weights (SI)
CODE†
B60 11 206 1031 2876 B61 11 493 1068 3056 B62 11 777 1116 3228 B65 11 346 991 2941 B66 11 626 1032 3118 B67 11 913 1079 3291
B6A 10 351 944 2794 B6B 10 568 981 2979 B6C 10 809 1023 3172 B6F 10 496 885 2878
B6G 10 727 916 3073
B6H 10 964 962 3263
C60 13 982 13 543 1201 730 3841 3914 C61 14 304 14 007 1248 730 4048 4207 C62 14 727 14 456 1304 730 4297 4498 C65 14 123 13 600 1162 730 3921 3939 C66 14 447 14 090 1209 730 4126 4247 C67 14 867 14 599 1267 730 4374 4571
C6A 12 991 12 554 1108 679 3129 3935 C6B 13 230 12 843 1149 679 3325 4180 C6C 13 494 13 117 1192 679 3553 4423 C6F 13 122 12 508 1059 679 3504 3951
C6G 13 371 12 908 1095 679 3717 4211
C6H 13 645 13 255 1134 679 3938 4506
DRY RIGGING WEIGHT (kg)* REFRIGERANT WEIGHT (kg) WATER WEIGHT (kg)
COOLER ONLY CONDENSER ONLY COOLER ONLY
CONDENSER
ONLY
COOLER ONLY CONDENSER ONLY
D60 17 371 951 5204 D61 17 973 951 5583 D62 18 611 951 5992 D65 17 066 951 5269 D66 17 616 951 5619 D67 18 352 951 6083
D6A 16 005 883 5171
D6B 16 478 883 5559 D6C 16 914 883 5932
D6F 15 625 883 5193
D6G 16 165 883 5628 D6H 16 630 883 6023
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and do not include refrigerant weight. †See Model Number Nomenclature on page 5.
NOTES:
1. Cooler weight includes the suction elbow and the distribution piping to the economizer and two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis­charge pipe, and mizer to the float chamber and two-pass Victaulic dished heads.
the distribution piping weight from the econo-
52
Table 17 — 19XR Two-Stage Compressor Frame Sizes 6 and 7

Economizer Weight

FRAME SIZE
XR6 1589 360 1949 721 163 884 XR7 2749 646 3395 1247 293 1540
*Includes economizer weight and all the connecting piping to the compressor.
DRY WEIGHT
(lb)*
REFRIGERANT
WEIGHT (lb)
OPERATION WEIGHT (lb)
DRY WEIGHT
(kg)*
REFRIGERANT
WEIGHT (kg)
OPERATION WEIGHT
Table 18 — Additional Weights for 19XR 150 psig (1034 kPa) Marine Waterboxes*
Two-Stage Compressors, Frame Size 6†
FRAME
*Add to cooler and condenser weights for total weights. Condenser weights may be found in Tables 13 and 14. The first digit of the heat exchanger code (first column) is the heat exchanger frame size. †Values are for Victaulic nozzles, two-pass dished head design.
NUMBER
OF
PASSES
A 2 1618 2603 1396 2253 734 1181 633 1022 B 2 1414 3222 641 1461
COOLER CONDENSER COOLER CONDENSER
RIGGING
WGT
ENGLISH (lb) SI (kg)
WATER
WGT
RIGGING
WGT
WATER
WGT
RIGGING
WGT
WATER
WGT
RIGGING
WGT
Table 19 — Additional Weights for 19XR 300 psig (2068 kPa) ASME Marine Waterboxes*
Two-Stage Compressors, Frame Size 6 — English (lb)
NUMBER
FRAME
A 2 5174 5554 1738 4383 4763 1605 B 2 6171 6671 2064
*Add to cooler and condenser weights for total weights. Condenser weights may be found in Tables 13 and 14. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
OF
PASSES
Rigging Wgt
Victaulic Flange Victaulic Flange
COOLER CONDENSER
Water Wgt
Rigging Wgt
(kg)
WATER
WGT
Water Wgt
Table 20 — Additional Weights for 19XR 300 psig (2068 kPa) ASME Marine Waterboxes*
Two-Stage Compressors, Frame Size 6 — SI (kg)
NUMBER
FRAME
A 2 2347 2519 788 1988 2160 728 B 2 2799 3026 936
*Add to cooler and condenser weights for total weights. Condenser weights may be found in Tables 13 and 14. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
OF
PASSES
Rigging Wgt
Victaulic Flange Victaulic Flange
COOLER CONDENSER
Water Wgt
Rigging Wgt
Water Wgt
53
Table 21 — Additional Weights for 19XR 150 psig (1034 kPa)
Two-Stage Compressors, Frame Size 7†
Marine Waterboxes*
FRAME
*Add to cooler and condenser weights for total weights. Cooler and condenser weights may be found in Tables 15 and 16. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
NUMBER
OF
PASSES
B 2 2253 3758 1022 1705 C 2 2748 4818 2907 4439 1246 2185 1319 2013 D 2 3692 5679 1675 2576
COOLER CONDENSER COOLER CONDENSER
RIGGING
WGT
ENGLISH (lb) SI (kg)
WATER
WGT
RIGGING
WGT
WATER
WGT
†Values are for Victaulic nozzles, two-pass dished head design.
RIGGING
WGT
WATER
WGT
RIGGING
WGT
Table 22 — Additional Weights for 19XR 300 psig (2068 kPa) ASME Marine Waterboxes*
Two-Stage Compressors, Frame Size 7 — English (lb)
NUMBER
FRAME
B 2 6651 7151 1938 C 2 9330 9830 2128 7,935 8,565 2642 D 2 11,262 11,892 3080
*Add to cooler and condenser weights for total weights. Cooler and condenser weights may be found in Tables 15 and 16. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
OF
PASSES
Rigging Wgt
Victaulic Flange Victaulic Flange
COOLER CONDENSER
Water Wgt
Rigging Wgt
Table 23 — Additional Weights for 19XR 300 psig (2068 kPa) ASME Marine Waterboxes*
Two-Stage Compressors, Frame Size 7 — SI (kg)
WATER
WGT
Water Wgt
NUMBER
FRAME
B 2 3017 3244 879 C 2 4232 4459 965 3599 4021 1198 D 2 5108 5394 1397
*Add to cooler and condenser weights for total weights. Cooler and condenser weights may be found in Tables 15 and 16. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
OF
PASSES
Rigging Wgt
Victaulic Flange Victaulic Flange
COOLER CONDENSER
Water Wgt
Rigging Wgt
Water Wgt
54
Table 24 — 19XR Compressor and Motor Weights* — High-Efficiency Motors
Compressor Frame Size 6, 50 Hz
ENGLISH SI
MOTOR
CODE
Voltage: 3000-3-50
N 10,622 5918 1212 1021 4818 2684 550 463 P 10,622 6006 1230 1021 4818 2724 558 463
Q 10,622 6094 1248 1021 4818 2764 566 463
R 10,622 6184 1264 1021 4818 2805 573 463 S 10,622 6274 1280 1021 4818 2846 581 463 T 10,622 6296 1280 1021 4818 2856 581 463
Voltage: 3300-3-50
N 10,622 5913 1212 1021 4818 2682 550 463 P 10,622 6007 1230 1021 4818 2725 558 463
Q 10,622 6101 1248 1021 4818 2767 566 463
R 10,622 6192 1264 1021 4818 2809 573 463 S 10,622 6283 1280 1021 4818 2850 581 463 T 10,622 6266 1280 1021 4818 2842 581 463
Voltage: 6300-3-50
N 10,622 6277 1280 1021 4818 2847 581 463 P 10,622 6333 1298 1021 4818 2873 589 463
Q 10,622 6389 1316 1021 4818 2898 600 463
R 10,622 6473 1316 1021 4818 2936 600 463 S 10,622 6556 1316 1021 4818 2974 600 463 T 10,622 6609 1351 1021 4818 2998 613 463
Voltage: 10000-3-50
N 10,622 6281 1280 1021 4818 2849 581 463 P 10,622 6281 1281 1021 4818 2849 581 463
Q 10,622 6281 1281 1021 4818 2849 581 463
R 10,622 6441 1316 1021 4818 2922 600 463 S 10,622 6600 1351 1021 4818 2994 613 463 T 10,622 6156 1351 1021 4818 2792 613 463
Voltage: 11000-3-50
N 10,622 6600 1351 1021 4818 2994 613 463 P 10,622 6600 1351 1021 4818 2994 613 463
Q 10,622 6600 1351 1021 4818 2994 613 463
R 10,622 6765 1385 1021 4818 3069 628 463 S 10,622 T 10,622 6930 1419 1021 4818 3143 644 463
*Total compressor weight is the sum of the compressor aerody­namic components (compressor weight column), stator, rotor, and end bell cover weights. †Compressor aerodynamic component weight only, motor weight not included. Applicable to standard compressors only.
COMPRESSOR
WEIGHT
(lb)
STATOR AND
HOUSING
WEIGHT
(lb)
6930
ROTOR AND
SHAFT
WEIGHT
(lb)
1419 1021 4818 3143 644 463
END BELL
COVER
WEIGHT
(lb)
COMPRESSOR
WEIGHT
(kg)
STATOR AND
HOUSING
WEIGHT
(kg)
ROTOR AND
SHAFT
WEIGHT
(kg)
END BELL
COVER
WEIGHT
(kg)
55
Table 25 — 19XR Compressor and Motor Weights* — High-Efficiency Motors
Two-Stage Compressor Frame Size 6, 60 Hz
ENGLISH SI
MOTOR
CODE
Voltage: 2400-3-60
N 10,622 5929 1212 1021 4818 2689 550 463 P 10,622 6021 1230 1021 4818 2731 558 463 Q 10,622 6112 1248 1021 4818 2772 566 463 R 10,622 6190 1264 1021 4818 2808 573 463 S 10,622 6268 1280 1021 4818 2843 581 463 T 10,622 6259 1280 1021 4818 2839 581 463
Voltage: 3300-3-60
N 10,622 5927 1212 1021 4818 2688 550 463 P 10,622 6019 1230 1021 4818 2730 558 463 Q 10,622 6110 1248 1021 4818 2771 566 463 R 10,622 6187 1264 1021 4818 2806 573 463 S 10,622 6263 1280 1021 4818 2841 581 463 T 10,622 6277 1280 1021 4818 2847 581 463
Voltage: 4160-3-60
N 10,622 6103 1247 1021 4818 2768 566 463 P 10,622 6103 1248 1021 4818 2768 566 463 Q 10,622 6103 1248 1021 4818 2768 566 463 R 10,622 6185 1264 1021 4818 2805 573 463 S 10,622 6268 1280 1021 4818 2843 581 463 T 10,622 6268 1280 1021 4818 2843 581 463
Voltage: 6900-3-60
N 10,622 6558 1316 1021 4818 2975 600 463 P 10,622 6559 1316 1021 4818 2975 600 463 Q 10,622 6559 1316 1021 4818 2975 600 463 R 10,622 6566 1316 1021 4818 2978 600 463 S 10,622 6574 1316 1021 4818 2982 600 463 T 10,622 6604 1351 1021 4818 2996 613 463
Voltage: 11000-3-60
N 10,622 6587 1351 1021 4818 2988 613 463 P 10,622 6587 1351 1021 4818 2988 613 463 Q 10,622 6587 1351 1021 4818 2988 613 463 R 10,622 6716 1385 1021 4818 3036 628 463 S 10 T 10,622 6844 1419 1021 4818 3104 644 463
Voltage: 13800-3-60
N 10,622 6554 1351 1021 4818 2973 613 463 P 10,622 6554 1351 1021 4818 2973 613 463 Q 10,622 6554 1351 1021 4818 2973 613 463 R 10,622 6709 1385 1021 4818 3043 628 463 S 10,622 6864 1419 1021 4818 3113 644 463 T 10,622 6864 1419 1021 4818 3113 644 463
*Total compressor weight is the sum of the compressor aerody­namic components (compressor weight column), stator, rotor, and end bell cover weights. †Compressor aerodynamic component weight only, motor weight not included. Applicable to standard compressors only.
COMPRESSOR
WEIGHT
(lb)
,622 68
STATOR AND
HOUSING
WEIGHT
(lb)
ROTOR AND
SHAFT
WEIGHT
(lb)
44 1419 1021 4818 3104 644 463
END BELL
COVER
WEIGHT
(lb)
COMPRESSOR
WEIGHT
(kg)
STATOR AND
HOUSING
WEIGHT
(kg)
ROTOR AND
SHAFT
WEIGHT
(kg)
END BELL
COVER
WEIGHT
(kg)
56
Table 26 — 19XR Compressor and Motor Weights* — High-Efficiency Motors
Two-Stage Compressor Frame Size 7, 50 Hz
ENGLISH SI
MOTOR
CODE
Voltage: 3000-3-50
U 14,309 6725 1443 983 6490 3050 654 446 V 14,309 6716 1443 983 6490 3046 654 446
W 14,309 6706 1443 983 6490 3042 654 446
X 14,309 6802 1460 983 6490 3085 662 446 Y 14,309 6899 1476 983 6490 3129 670 446 Z 14,309 7066 1509 983 6490 3205 684 446
Voltage: 3300-3-50
U 14,309 6743 1443 983 6490 3059 654 446 V 14,309 6739 1443 983 6490 3057 654 446
W 14,309 6734 1443 983 6490 3054 654 446
X 14,309 6826 1460 983 6490 3096 662 446 Y 14,309 6917 1476 983 6490 3137 670 446 Z 14,309 7075 1509 983 6490 3209 684 446
Voltage: 6300-3-50
U 14,309 6743 1443 983 6490 3059 654 446 V 14,309 6900 1476 983 6490 3130 670 446
W 14,309 7058 1509 983 6490 3201 684 446
X 14,309 7130 1526 983 6490 3234 692 446 Y 14,309 7203 1542 983 6490 3267 699 446 Z 14,309 7203 1542 983 6490 3267 699 446
Voltage: 10000-3-50
U 14,309 6904 1476 983 6490 3132 670 446 V 14,309 6907 1476 983 6490 3133 670 446
W 14,309 6910 1476 983 6490 3134 670 446
X 14,309 7074 1509 983 6490 3209 684 446 Y 14,309 7238 1542 983 6490 3283 699 446 Z 14,309 7401 1575 983 6490 3357 714 446
Voltage: 11000-3-50
U 14,309 7139 1509 983 6490 3238 684 446 V 14,309 7186 1526 983 6490 3260 692 446
W 14,309 7234 1542 983 6490 3281 699 446
X 14,309 7234 1542 983 6490 3281 699 446 Y 14,309 Z 14,309 7383 1575 983 6490 3349 714 446
*Total compressor weight is the sum of the compressor aerody­namic components (compressor weight column), stator, rotor, and end bell cover weights. †Compressor aerodynamic component weight only, motor weight not included. Applicable to standard compressors only.
COMPRESSOR
WEIGHT
(lb)
STATOR AND
HOUSING
WEIGHT
(lb)
7234
ROTOR AND
SHAFT
WEIGHT
(lb)
1542 983 6490 3281 699 446
END BELL
COVER
WEIGHT
(lb)
COMPRESSOR
WEIGHT
(kg)
STATOR AND
HOUSING
WEIGHT
(kg)
ROTOR AND
SHAFT
WEIGHT
(kg)
END BELL
COVER
WEIGHT
(kg)
57
Table 27 — 19XR Compressor and Motor Weights* — High-Efficiency Motors
Two-Stage Compressor Frame Size 7, 60 Hz
ENGLISH SI
MOTOR
CODE
Voltage: 2400-3-60
U 14,309 6719 1443 983 6490 3048 654 446 V 14,309 6718 1443 983 6490 3047 654 446
W 14,309 6717 1443 983 6490 3047 654 446
X 14,309 6811 1460 983 6490 3089 662 446 Y 14,309 6906 1476 983 6490 3132 670 446 Z 14,309 7073 1509 983 6490 3208 684 446
Voltage: 3300-3-60
U 14,309 6723 1443 983 6490 3049 654 446 V 14,309 6730 1443 983 6490 3053 654 446
W 14,309 6736 1443 983 6490 3055 654 446
X 14,309 6816 1460 983 6490 3092 662 446 Y 14,309 6895 1476 983 6490 3128 670 446 Z 14,309 7055 1509 983 6490 3200 684 446
Voltage: 4160-3-60
U 14,309 6739 1443 983 6490 3057 654 446 V 14,309 6721 1443 983 6490 3049 654 446
W 14,309 6703 1443 983 6490 3040 654 446
X 14,309 6778 1460 983 6490 3074 662 446 Y 14,309 6853 1476 983 6490 3108 670 446 Z 14,309 7069 1509 983 6490 3206 684 446
Voltage: 6900-3-60
U 14,309 6730 1443 983 6490 3053 654 446 V 14,309 6909 1476 983 6490 3134 670 446
W 14,309 7088 1509 983 6490 3215 684 446
X 14,309 7076 1509 983 6490 3210 684 446 Y 14,309 7064 1509 983 6490 3204 684 446 Z 14,309 7141 1542 983 6490 3239 699 446
Voltage: 11000-3-60
U 14,309 7042 1509 983 6490 3194 684 446 V 14,309 7085 1526 983 6490 3214 692 446
W 14,309 7128 1542 983 6490 3233 699 446
X 14,309 Y 14,309 7135 1542 983 6490 3236 699 446 Z 14,309 7313 1575 983 6490 3317 714 446
Voltage: 13800-3-60
U 14,309 7073 1509 983 6490 3208 684 446 V 14,309 7109 1526 983 6490 3225 692 446
W 14,309 7146 1542 983 6490 3241 699 446
X 14,309 7146 1542 983 6490 3241 699 446 Y 14,309 7146 1542 983 6490 3241 699 446 Z 14,309 7295 1575 983 6490 3309 714 446
*Total compressor weight is the sum of the compressor aerody­namic components (compressor weight column), stator, rotor, and end bell cover weights.
COMPRESSOR
WEIGHT
(lb)
STATOR AND
HOUSING
WEIGHT
(lb)
7131
ROTOR AND
SHAFT
WEIGHT
(lb)
1542 983 6490 3235 699 446
END BELL
COVER
WEIGHT
(lb)
COMPRESSOR
WEIGHT
(kg)
†Compressor aerodynamic component weight only, motor weight not included. Applicable to standard compressors only.
STATOR AND
HOUSING
WEIGHT
(kg)
ROTOR AND
SHAFT
WEIGHT
(kg)
END BELL
COVER
WEIGHT
(kg)
58
Table 28 — 19XR Waterbox Cover Weights, Two-Stage Compressor Frame 6 — English (lb)
Two-Stage Compressor Frame 6; Cooler Frame A
WATERBOX DESCRIPTION PASSES
STANDARD NOZZLES FLANGED
Dished Head, 150 psig MWB End Cover, 150 psig MWB End Cover (ASME), 300 psig
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
Two-Stage Compressor Frame 6; Condenser Frame A and B
WATERBOX DESCRIPTION PASSES
Dished Head, 150 psig MWB End Cover, 150 psig MWB End Cover (ASME), 300 psig
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 150 psig are included in the heat exchanger weights shown in Tables 13 and 14.
STANDARD
NOZZLES
2 2 2
1084 1280 1193 1453 1084 1280 1193 1453 2117 2117 2675 2675
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 150 psig are included in the heat exchanger weights shown in Tables 13 and 14.
COOLER
FRAME A
1132 1440 1132 1440 2460 2460
CONDENSER
FRAME A FRAME B
FLANGED
STANDARD
NOZZLES
FLANGED
Table 29 — 19XR Waterbox Cover Weights, Two-Stage Compressor Frame 6 — SI (kg)
Two-Stage Compressor Frame 6; Cooler Frame A
WATERBOX DESCRIPTION PASSES
Dished Head, 1034 kPa MWB End Cover, 1034 kPa MWB End Cover (ASME), 2068 kPa
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
Two-Stage Compressor Frame 6; Condenser Frame A and B
WATERBOX DESCRIPTION PASSES
Dished Head, 1034 kPa MWB End Cover, 1034 kPa MWB End Cover (ASME), 2068 kPa
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 1034 kPa are included in the heat exchanger weights shown in Tables 13 and 14.
STANDARD
NOZZLES
2 2 2
492 581 541 659 492 581 541 659 960 960 1213 1213
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 1034 kPa are included in the heat exchanger weights shown in Tables 13 and 14.
COOLER FRAME A
STANDARD NOZZLES FLANGED
513 653 513 653
1116 1116
CONDENSER
FRAME A FRAME B
FLANGED
STANDARD
NOZZLES
FLANGED
59
Table 30 — 19XR Waterbox Cover Weights, Two-Stage Compressor Fr ame 7 — English (lb)
Two-Stage Compressor Frame 7; Cooler Frames B, C
WATERBOX DESCRIPTION PASSES
STANDARD NOZZLES FLANGED STANDARD NOZZLES FLANGED
Dished Head, 150 psig MWB End Cover, 150 psig MWB End Cover (ASME), 300 psig
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
Two-Stage Compressor Frame 7; Condenser Frames C, D
WATERBOX DESCRIPTION PASSES
STANDARD NOZZLES FLANGED STANDARD NOZZLES FLANGED
Dished Head, 150 psig MWB End Cover, 150 psig MWB End Cover (ASME), 300 psig
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
FRAME B FRAME C
1588 1848 2075 2335 1588 1848 2075 2335 3365 3365 4747 4747
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 150 psig are included in the heat exchanger weights shown in Tables 15 and 16.
FRAME C FRAME D
1614 1944 2072 2402 1614 1944 2072 2402 3639 3639 5188 5188
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 150 psig are included in the heat exchanger weights shown in Tables 15 and 16.
COOLER
CONDENSER
Table 31 — 19XR Waterbox Cover Weights, Two-Stage Compressor Frame 7 — SI (kg)
Two-Stage Compressor Frame 7; Cooler Frames B, C
WATERBOX DESCRIPTION PASSES
STANDARD NOZZLES FLANGED STANDARD NOZZLES FLANGED
Dished Head, 1034 kPa MWB End Cover, 1034 kPa MWB End Cover (ASME), 2068 kPa
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
Two-Stage Compressor Frame 7; Condenser Frames C, D
WATERBOX DESCRIPTION PASSES
STANDARD NOZZLES FLANGED STANDARD NOZZLES FLANGED
Dished Head, 1034 kPa MWB End Cover, 1034 kPa MWB End Cover (ASME), 2068 kPa
LEGEND NOTES:
ASME— American Society of Mechanical Engineers MWB — Marine Waterbox
2 2 2
FRAME B FRAME C
720 838 941 1059 720 838 941 1059
1526 1526 2153 2153
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 1034 kPa are included in the heat exchanger weights shown in Tables 15 and 16.
FRAME C FRAME D
732 882 940 1090 732 882 940 1090
1651 1651 2353 2353
1. Consult factory for 1 and 3 pass data.
2. Weights for dished head cover and MWB end cover 1034 kPa are included in the heat exchanger weights shown in Tables 15 and 16.
COOLER
CONDENSER
60
Table 32 — Compressor Component Weights
COMPONENT
TRANSMISSION ASSEMBLY (INCLUDING BULL GEAR AND HIGH SPEED SHAFT) 1,940 880 3,147 1427 BULL GEAR 121 55 220 100 HIGH SPEED SHAFT ASSEMBLY 523 237 700 318 SUCTION ASSEMBLY (INCLUDING BLADE RING) 1,520 689 2,078 943 BLADE RING ASSEMBLY 109 49 384 174 COMPRESSOR BASE 4,919 2231 6,972 3162 MOTOR END COVER 1,021 463 983 446 INTAKE WALL 220 100 719 326 DISCHARGE WALL 172 78 296 134 DIAPHRAGM 289 131 473 215 OIL PUMP 124 56 124 56 TOTAL WEIGHT (EXCLUDING MOTOR) 10,622 4818 14,309 6490
XR6 WEIGHTS XR7 WEIGHTS
lb kg lb kg
61
19XR TWO-STAGE COMPRESSOR FRAMES 6 AND 7 FITS AND CLEARANCES
LOW SPEED BEARING
MOTOR END
SEE DETAIL D
LOW SPEED BEARING
COMPRESSOR END
SEE DETAIL B
AERO
SEE DETAIL A
LOW SPEED BEARING
MOTOR END
SEE DETAIL C
a19-2217
Fig. 38 — Compressor Fits and Clearances — Two-Stage Compressor, Frame Sizes 6 and 7
ITEM
A Low Speed Journal — Compressor End 0.006/0.007 0.15/0.18 0.006/0.008 0.15/0.19 B Low Speed Journal —Motor End 0.004/0.005 0.10/0.11 0.004/0.006 0.10/0.15 C Low Speed Labyrinth — Compressor End 0.009/0.013 0.23/0.32 0.009/0.013 0.23/0.33 D Low Speed Shaft Thrust Float 0.008/0.020 0.20/0.50 0.008/0.020 0.20/0.50 E Impeller Bore to Shaft — 1st Impeller –0.002/0.000 –0.05/0.01 –0.002/0.000 –0.05/–0.01
F Impeller Bore to Shaft — 2nd Impeller –0.002/0.000 –0.06/0.01 –0.002/0.000 –0.05/–0.01 G Low Speed Bearing Labyrinth to Shaft — Motor End 0.009/0.013 0.23/0.33 0.010/0.012 0.25/0.30 H Low Speed Bearing to Cover Assembly 0.002/0.004 0.04/0.10 0.001/0.003 0.03/0.08
I Bull Gear to Low Speed Shaft –0.001/0.000 –0.03/0.00 –0.0013/0.0000 –0.033/0.000
J High Speed Shaft Labyrinth to High Speed Labyrinth Sleeve 0.006/0.009 0.15/0.23 0.006/0.009 0.15/0.23 K Balance Piston Labyrinth to 2nd Stage Impeller 0.008/0.012 0.20/0.30 0.008/0.012 0.20/0.30
L 2nd Stage Eye Labyrinth to Impeller 0.008/0.012 0.20/0.30 0.012/0.016 0.30/0.40 M Interstage Labyrinth Spacer to High Speed Shaft 0.001/0.002 0.02/0.05 0.001/0.003 0.04/0.07 N Interstage Labyrinth Seal 0.011/0.017 0.29/0.42 0.009/0.012 0.23/0.30 O 1st Stage Eye Labyrinth to Impeller 0.016/0.020 0.41/0.50 0.024/0/028 0.62/0.72
NOTES:
1. All clearances for cylindrical surfaces are diametrical.
2. Dimensions shown are with rotors in the thrust position.
3. High speed shaft and bearing assembly cannot be pulled from impeller end. The transmission assembly must be removed from the compressor casting (after the impeller is removed) and the
COMPRESSOR
DESCRIPTION
FRAME 6 (in.) FRAME 6 (mm) FRAME 7 (in.) FRAME 7 (mm)
bearing temperature sensor must be removed from the high speed shaft and bearing assembly before the high speed shaft and bearing assembly can be separated from the transmission.
4. If any components within a rolling element high speed shaft and bearing assembly are damaged it is recommended that the entire high speed shaft and bearing assembly be replaced.
62
B
B
SEE DETAIL E
ITEM M
ITEM O
ITEM N
ITEM K
ITEM L
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
DETAIL A
AERO
ITEM F
ITEM E
SECTION B-B
a19-2277
C
C
ITEM D
ITEM A
ITEM C
SECTION C-C
ITEM I
DETAIL B
LOW SPEED BEARING
COMPRESSOR END
a19-2278
Fig. 38 — Compressor Fits and Clearances — Two-Stage Compressor, Frames Size 6 and 7 (cont)
LEGEND
1—1st Stage Eye Labyrinth 10 — High Speed Shelf Labyrinth Sleeve 2—1st Stage Impeller Shim 11 — 2nd Stage Impeller 3—Intake Wall 12 — 2nd Stage Impeller Key 4—2nd Stage Eye Labyrinth 13 — Interstage Labyrinth Spacer 5—Diaphragm 14 — 1st Stage Impeller 6—Discharge Wall 15 — 1st Stage Impeller Key 7—Balance Piston Labyrinth 16 — Impeller Locknut 8—High Speed Shelf Labyrinth 17 — Nose Piece 9—High Speed Shelf Labyrinth Shaft
63
DETAIL D
LOW SPEED BEARING
MOTOR END
ITEM H
ITEM G
ITEM B
a19-2279
DETAIL E
HIGH SPEED BEARING
COMPRESSOR END
ITEM J
a19-2280
Fig. 38 — Compressor Fits and Clearances — Two-Stage Compressor, Frame Sizes 6 and 7 (cont)
a19-2220
DETAIL C
HIGH SPEED BEARING
MOTOR END
64
CAUTION
USE COPPER CONDUCTORS ONLY UTILISEZ DES CONDUCTEURS EN CUIVRE SEULMENT
ALWAYS USE 2 WRENCHES TO TIGHTEN
• TERM INSULATOR TO MOTOR – 15-35 ft. lb.
• BRASS NUT TO TERM INSULATOR – 3 ft. lb. max
• ADAPTOR TO TERM STUD – 20-35 ft. lb.
• LUG BOLTS (1/2")– 32-45 ft. lb. Insulate entire connection with electrical insulation
including 1 inch of cable insulation and 1 inch of the term insulator.
!
TERMINAL STUD
INSULATION
ADAPTER
BRASS NUT
TERMINAL INSULATOR
1
2
3
13
MOTOR LEAD INSTALLATION LABEL
19XR TWO-STAGE COMPRESSOR ASSEMBLY TORQUES
Fig. 39 — Compressor Assembly Torques — 19XR Two-Stage Compressors Frame Sizes 6 and 7
COMPRESSOR FRAME 6 FRAME 7
Oil Heater Retaining Nut — ft-lb (N·m) 40-60 (54-81) 40-60 (54-81) Bull Gear Retaining Bolt — ft-lb (N·m) 72-88 (98-119) 72-88 (98-119) Demister Bolts — ft-lb (N·m) 15-19 (20-26) 15-19 (20-26) Impeller Nut (Inner Locknut) — ft-lb (N·m) 243-257 (329-348) 243-257 (329-348) Impeller Nut (Outer) — ft-lb (N·m) 95-105 (129-142) 95-105 (129-142) Guide Vane Shaft Seal Nut/Bolts — ft-lb (N·m) 23-27 (31-37) 48-70 (64-94)
a19-1642
a19-1643
Fig. 40 — HMI Panel
7TB IN HMI PANEL FOR CUSTOMER COMMUNICATION CONNECTION A (+)
a19-2251
C (G) B (-)
65
a19-2252
Fig. 41 — Control Panel, IOB Layer
1TB
2TB
a19-2374
1TB — CUSTOMER 3-PHASE POWER CONNECTION FOR CONTROL PANEL 2TB — FIELD WIRING CONNECTION FROM STARTER
Fig. 42 — Control Panel, Bottom Layer
66
LEGEND FOR FIG. 43
19XR with Free-Standing Starter (Medium Voltage)
REFERENCE
NUMBER
3 Phase Under/Over Voltage Phase Loss/Imbalance/Reversal Motor Overload Protection Frequency Shift kW Transducer/kW Hours/Demand kW Single Cycle Dropout Motor/Starter Overcurrent Control Power Transformer (3KVA) (Integral)
1
2 Compressor Motor Starter Branch Disconnect A Evaporator Liquid Pump Starter Disconnect B Evaporator Liquid Pump Motor Starter C Condenser Liquid Pump Starter Disconnect D Condenser Liquid Pump Motor Starter E Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)
F Cooling Tower Fan Motor Starter (Low Fan/#1) G Cooling Tower Fan Motor Starter Disconnect (High/#2) H Cooling Tower Fan Motor Starter (High Fan/#2)
L Remote Alarm See Note 3.3
M Remote Annunciator See Note 3.3
N Lug Adapters See Note 2.1
See Notes on page 70.
Controls and Oil Heater Circuit Breaker (integral) Oil Pump Circuit Breaker Oil Pump Circuit Breaker with Transformer 3 Phase Analog Volts/Amps Meter Package Power Factor Correction Package Lightning/Surge Arrestor Package Auxiliary Run Status Contacts N.O./N.C. Run Indicating Light Emergency Stop Switch Phase to Ground Fault Detection
EXPLANATION
67
COMPRESSOR MOTOR STARTER
a19-2254
Fig. 43 — 19XR Typical Field Wiring with Free-Standing Starter (Medium Voltage)
NOTE: See Legend on page 67.
68
2TB
Fig. 43 — 19XR Typical Field Wiring with Free- Standing Starter (Medium Voltage) (cont)
CONTROL PANEL
1TB
L3
L2
L1
HMI CONTROL PANEL
7TB
GROUNDING
FOR HMI
G
+
69
NOTES FOR FIG. 43
19XR with Free-Standing Starter (Medium Voltage)
I. GENERAL
1.0 Starters shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-415.
1.1 All field-supplied conductors, devices, and the field installation wiring, termination of conductors and devices, must be in compliance with all applicable codes and job specifications.
CAUTION
To prevent damage to machine, do NOT punch holes or drill into the top surface of the starter enclosure for field wiring. Knock­outs are provided on the side of the starter enclosure for field wiring connections.
1.2 The routing of field-installed conduit and conductors and the location of field-installed devices must not interfere with equipment access or the reading, adjusting, or servicing of any component.
1.3 Equipment installation and all starting and control devices, must comply with details in equipment submittal drawings and literature.
1.4 Contacts and switches are shown in the position they would assume with the circuit de-energized and chiller shutdown.
1.5 WARNING — Do not use aluminum conductors.
1.6 Installer is responsible for any damage caused by improper wiring between starter and machine.
1.7 All field-installed wiring is field-supplied.
POWER WIRING TO STARTER
II.
2.0 Provide a means of disconnecting power to starter.
2.1 Lug adapters may be required if installation conditions dic­tate that conductors be sized beyond the minimum ampac­ity required. Contact starter supplier for lug information.
2.2 Compressor motor and controls must be grounded by using equipment grounding lug provided inside starter enclosure.
CONTROL WIRING
III.
3.0 Field supplied control conductors to be at least 18 AWG or larger.
3.1 Ice build start/terminate device contacts, remote start/stop device contacts and spare safety device contacts (devices not supplied by Carrier), must have 24 VAC rating. MAX current is 60 mA, nominal current is 10 mA. Switches with gold plated bifurcated contacts are recommended.
3.2 Remove jumper wire between J2-1 and J2-2 before con­necting auxiliary safeties between these terminals.
3.3 Each integrated contact output can control loads (VA) for evaporator pump, condenser pump, tower fan low, tower fan high, and alarm annunciator devices rated 5 amps at 115 VAC and up to 3 amps at 277 VAC.
3.8 Spare 4-20 mA output signal is designed for controllers with a non-grounded 4-20 mA input signal and a maximum input impedance of 500 ohms.
POWER WIRING BETWEEN FREE-STANDING STARTER
IV.
AND COMPRESSOR MOTOR
4.0 Medium voltage (over 600 volts) compressor motors have (3) terminals. Connections are compression lug with a single 9/16-in. diameter hole can be connected directly to the stud or 3 adapters are supplied for connecting a NEMA lug. Use suitable connectors and insu­lation for high voltage alternating current cable terminations (these items are not supplied by Carrier). Compressor motor starter must have nameplate stamped as to conform­ing with Carrier Engineering requirement “Z-415.”
4.1 Power conductor rating must meet minimum unit nameplate voltage and compressor motor RLA. Refer to the label located on the side of the chiller control panel, equipment subm itta l docu ment ation or equipment product data catalog for conductor sizing data. (Conductor as defined below may be a single lead or multiple smaller ampacity leads in paral­lel for the purpose of carrying the equivalent or higher cur­rent of a single larger lead.)
When (3) conductors are used: Minimum ampacity per conductor = 1.25 x compressor RLA
4.2 When more than one conduit is used to run conductors from starter to compressor motor terminal box, an equal number of leads from each phase (conductor) must be in each conduit to prevent excessive heating. (For example, conductors to motor terminals 1, 2, and 3 in one conduit, and those to 4, 5, and 6 in another).
4.4 Compressor motor power conductors may enter terminal box through top, left side or bottom left using holes cut by contractor to suit conduit. Flexible conduit should be used for the last few feet to the terminal box for unit vibration iso­lation. Use of stress cones may require an oversize (spe­cial) motor terminal box (not supplied by Carrier).
4.3 Compressor motor frame to be grounded in accordance with the National Electrical Code (NFPA-70) and applicable codes. Means for grounding compressor motor is a #4 AWG to 500 MCM pressure connector, supplied and located in the lower left side corner of the compressor motor terminal box.
4.5 Do not allow motor terminals to support weight of wire cables. Use cable supports and strain reliefs as required.
4.6 Use backup wrench when tightening lead connectors to motor terminal studs. Torque to 30-35 ft-lb max.
9
/16-in. threaded stud. A
CAUTION
Control wiring for Carrier to start pumps and tower fan motors and establish flows must be provided to assure machine protec­tion. If primary pump, tower fan, and flow control is by other means, also provide parallel means for control by Carrier. Fail­ure to do so could result in machine freeze-up or overpressure.
Do not use control transformers in the control center as the power source for external or field-supplied contactor coils, actuator motors or any other loads.
3.4 Do not route control wiring carrying 30 v or less within a conduit which has wires carrying 50 v or higher or along side wires carrying 50 v or higher.
3.5 Control wiring between starter and control panel must be separate shielded cables with minimum rating 600 v, 80 C. Ground shield at starter.
3.6 If optional circuit breaker is not supplied within the starter enclosure, it must be located within sight of machine w ith wir­ing routed to suit.
3.7 When providing conductors for oil pump motor and oil heater power, refer to sizing data on label located on the chiller control panel, equipment submittal documentation or equipment product data catalog.
70
LEGEND FOR FIG. 44
AC Alternating Current ACB Analog Control Board AWG American Wire Gage CBx Circuit Breaker CPTx Control Power Transformer CTx Current Transformer DI Drive Input Contactor DI-IV Drive Input Contactor Intellivac Module DIC Drive Input Control Relay DICR1 Drive Input Contactor Pilot Relay DIIS Drive Input Isolating Switch DILR Drive Input Line Reactor DIOL Drive Input Overload DIOLx Drive Input Overload Auxiliary Relay DITB Drive Input Contactor Terminal Blocks DSx Disconnect Switch EMC Electro-Magnetic Choke ES Ethernet Switch FLT Fault Relay Fx Fuse GFCT Ground Fault Current Transformer GND Ground GRD Ground HECSU Hall Effect Current Sensor (U Phase) HECSW — Hall Effect Current Sensor (W Phase) HPR High Pressure Relay IFM Interface Module ISM Integrated Starter Module LFC Line Filter Capacitors LFRNx Line Reactor Fan x LV Low Voltage LVx External Low Voltage Supply MFC Motor Filter Capacitors MFN1C Main Fan Contactor MFN1MP — Main fan Motor Protector MOV Metal Oxide Varistor MSR Monitoring Safety Relay MSRXx Monitoring Safety Relay Auxiliary Relay x MV Medium Voltage NR Neutral Resistor PE Earth Ground PFN1 Powerflex Interface Board PP Carrier Power Panel PS1A AC/DC Converter PS2 DC/DC Converter PS4 AC/DC Converter RUN Run Relay SS Surge Suppressor ST Shunt Trip VFD Variable Frequency Drive VSBx Voltage Sensing Board WRN
Warning Relay
XIO
x External Inputs/Outputs 1M Start Relay 66 Carrier ISM to be programmed by Carrier before
start-up. Relay contacts shown without
signal
power applied.
71 Calibrate for 4-20 mA; 0-5 vdc (Default 0-10 vdc). 100 WARNING: Ground must be connected to prevent
high voltages from being applied to drive control boards.
104 Located in drive low voltage control section. 105 Device is mounted on the low voltage door of the
drive.
WIRING Factory Wiring Field Wiring
Mechanically Connected Conductor, Crossing of Paths or Conductors Not
Connected Conductor, Junction of Connected Paths, Con-
ductors or Wires Conductor, Separable or Jacks Engaged Terminal
Terminal (Rockwell Automation use only) Terminal Blocks
— Barrier Wired To/From Destination
SWITCHES AND INPUT DEVICES Contact Normally Open (Make)
Contact Normally Closed (Break) OUTPUT DEVICES
Fan (3 Phase Induction Motor)
Induction Machine RESISTORS, CAPS, WINDINGS AND
GROUND Capacitor
Winding Transformer, Current
PROTECTION Circuit Breaker, Control/Power
Fuse, Control/Power Surge Suppressor
POWER ELECTRONIC DEVICES Symmetrical Gate-Commutated Thyristor and
Gate Driver Board MISCELLANEOUS Note Number Indicator
Contact Location Description
Relay Location Description
Key Interlock on Isolation Switch Key Interlock on MV Door Multiple Barrel Key Interlock on Isolation Switch Multiple Barrel Key Interlock on MV Door Transfer Block
71
DRIVE INPUT ISOLATING SWITCH
POTENTIAL TRANSFORMER
CONTROL POWER TRANSFORMER
DRIVE INPUT CONTACTOR
DRIVE INPUT OVERLOAD
CARRIER ISM MODULE
DRIVE INPUT LINE REACTOR
LINE FILTER CAPACITORS
COMMON MODE CHOKE
MOTOR FILTER CAPACITORS
CHILLER MOTOR
MAIN COOLING FAN
MAIN FAN CONTACTOR
MAIN FAN MOTOR PROTECTOR
DISCONNECT SWITCH 1
CONTROL POWER TRANSFORMER
ISOLATED GATE DRIVE POWER SUPPLY
LINE VOLTAGE
FIELD SUPPLIED
FOR VFD USE ONLY, CHILLER CONTROL POWER MUST BE FIELD SUPPLIED SEPARATELY
1200A
12R
400A
SEE TABLE FOR CABLE MINIMUM INSULATION REQUIREMENTS*
4000:1
4000:1
SEE TABLE FOR CABLE MINIMUM INSULATION REQUIREMENTS*
T1, T2, T3
16A
4A
3 Ø LV and 1 Ø 115 POWER SUPPLY IS REQUIRED AND MUST BE FIELD SUPPLIED WITH BRANCH CIRCUIT PROTECTION (8 kVA MINIMUM REQUIRED)
a19-2382
67
Fig. 44 — 19XR Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD) (Medium Voltage)
*See page 80.
72
LV
MV
MAIN COOLING FAN
COMMON MODE CHOKE
SECTION
MV
INVERTER
RECTIFIER
SECTION
MV
CAP
DRIVE INPUT LINE REACTOR
3-PHASE POWER FIELD-SUPPLIED
WITH BRANCH CIRCUIT PROTECTION
(8 kVa REQUIRED)
FIELD-SUPPLIED
GROUND
FIELD-SUPPLIED
GROUND
FIELD-SUPPLIED
GROUND
LINE VOLTAGE
FIELD-SUPPLIED
CONTROL PANEL
2TB
L1
L2
L3
1TB
3-PHASE FIELD-SUPPLIED
CONTROL POWER
TO ISM J7-A,B,C
a19-2383
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD) (Medium Voltage) (cont)
73
ISM INPUTS AND
OUTPUTS FOR
FIELD USE
CUSTOMER USE
DRIVE TERMINAL BLOCK 1
VFD UNIT SECTION 3A
DRIVE TERMINAL BLOCK 1
(CONT)
TO DRIVE INPUT
CONTACTOR TERMINAL
BLOCK
TO DRIVE INPUT
CONTACTOR TERMINAL
BLOCK
TO DRIVE INPUT
CONTACTOR TERMINAL
BLOCK
TO CARRIER
CHILLER
CONTROL PANEL
DRIVE INPUT CONTACTOR
TERMINAL BLOCK
VFD UNIT SECTION 1A
FIELD USE
WIRE TO DRIVE
TERMINAL BLOCK 1
#12 AWG
WIRE TO DRIVE
TERMINAL BLOCK 1
#12 AWG
WIRE TO DRIVE
TERMINAL BLOCK 1
#12 AWG
TO CARRIER CHILLER
POWER PANEL
WIRE TO DRIVE
INPUT CONTACTOR
TERMINAL BLOCK
DRIVE TERMINAL BLOCK
VFD UNIT SECTION 5A
DRIVE TERMINAL BLOCK 2
VFD UNIT SECTION 3A
TO DRIVE UNIT
SECTION 5A
a19-2384
Note: see fig 27 for limitations
and IOB wiring
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD) (Medium Voltage) (cont)
74
THE CONTROL POWER TRANSFORMER IS FOR VFD CONTROL POWER ONLY.
CHILLER CONTROL POWER MUST BE PROVIDED AS A SEPARATE SOURCE,
FIELD-SUPPLIED.
VFD UNIT SECTION 1A MODULE WIRING
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD) (Medium Voltage) (cont)
a19-2062
75
CHILLER
MOTOR
Fig. 44 — Typical Field Wiring with Free-Standing Variable Freq uency Drive (Medium Voltage) (VFD) (cont)
a19-2063
76
MAIN COOLING
FAN
FIELD-SUPPLIED GROUND
NOTE: ISM CAN BE CONFIGURED FOR EITHER
0 TO 5 VDC OR 0 TO 10 VDC
VFD SPEED FREQUENCY INPUT.
a19-2386
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD) (Medium Voltage) (cont)
77
CONTINUED ON NEXT PAGE
a19-2064
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD)
(Medium Voltage) (cont)
78
CONTINUED
Fig. 44 — Typical Field Wiring with Free-Standing Variable Frequency Drive (VFD)
(Medium-Voltage) (cont)
a19-2066
FROM PREVIOUS PAGE
79
NOTES FOR FIG. 44
19XR with Free-Standing Medium Voltage VFD
I. GENERAL
1.0 Variable Frequency Drive (VFD) shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-416.
1.1 All field-supplied conductors, devices, and the field installa­tion wiring, termination of conductors and devices, must be in compliance with all applicable codes and job specifica­tions.
CAUTION
To prevent damage to machine, do NOT punch holes or drill into the top surface of the VFD enclosure for field wiring. Field wiring knockouts are provided on the top and side of the VFD enclo­sure for field wiring connections.
1.2 The routing of field-installed conduit and conductors and the location of field-installed devices must not interfere with equipment access or the reading, adjusting, or servicing of any component.
1.3 Equipment installation and all starting and control devices, must comply with details in equipment submittal drawings and literature.
1.4 Contacts and switches are shown in the position they would assume with the circuit de-energized and chiller shutdown.
1.5 WARNING - Do not use aluminum conductors.
1.6 Installer is responsible for any damage caused by improper wiring between VFD and machine.
1.7 All field-installed wiring is field-supplied.
POWER WIRING TO VFD
II.
2.0 Provide a means of disconnecting power to VFD.
2.1 Lug adapters may be required if installation conditions dic­tate that conductors be sized beyond the minimum ampac­ity required. Contact VFD supplier for lug information.
2.2 Compressor motor and controls must be grounded by using equipment grounding lug provided inside VFD enclosure.
CONTROL WIRING
III.
3.0 Field supplied control conductors to be at least 18 AWG or larger.
3.1 Optional Ice build start/terminate device contacts, optional remote start/stop device contacts and optional spare safety device contacts (devices not supplied by Carrier), must have 24 VAC rating. MAX current is 60 mA, nominal current is 10 mA. Switches with gold plated bifurcated contacts are recommended.
3.2 Remove jumper wire between ISM J2-1 and ISM J2-2 before connecting auxiliary safeties between these terminals.
3.3 Each integrated contact output can control loads (VA) fo r evaporator pump, condenser pump, tower fan low, tower fan high, and alarm annunciator devices rated 5 amps at 115 VAC and up to 3 amps at 277 VAC.
CAUTION
Control wiring for Carrier to start pumps and tower fan motors and establish flows must be provided to assure machine protec­tion. If primary pump, tower fan, and flow control is by other means, also provide parallel means for control by Carrier. Fail­ure to do so could result in machine freeze-up or overpressure.
Do not use control transformers in the control center as the power source for external or field-supplied contactor coils, actuator motors or any other loads.
3.4 Do not route control wiring carrying 30 v or less within a conduit which has wires carrying 50 v or higher or along side wires carrying 50 v or higher.
3.5 Control wiring between VFD and power panel must be sep­arate shielded cables with minimum rating 600 v, 80 C. Ground shield at VFD.
3.6 If optional pumpout/oil pump circuit breaker is not supplied within the starter enclosure, it must be located within sight of machine with wiring routed to suit.
3.7 When providing conductors for oil pump motor and oil heater power, refer to sizing data on label located on the chiller power panel, equipment submittal documentation or equipment product data catalog.
3.8 Spare 4-20 mA output signal is designed for controllers with a non-grounded 4-20 mA input signal and a maximum input impedance of 500 ohms.
IV.
POWER WIRING BETWEEN FREE-STANDING VFD AND COMPRESSOR MOTOR
4.0 Medium voltage (over 600 volts) compressor motors have (3) terminals. Connections are 9/16-in. threaded stud. A compression lug with a single connected directly to the stud or 3 adapters are supplied for connecting a NEMA lug. Use suitable connectors and insu­lation for high voltage alternating current cable terminations (these items are not supplied by Carrier). Compressor motor starter must have nameplate stamped as to conform­ing with Carrier Engineering requirement "Z-416."
4.1 Power conductor rating must meet minimum unit nameplate voltage and compressor motor RLA. Refer to the label located on the side of the chiller control panel, equipment submittal documentation or equipment product data catalog for conductor sizing data. (Conductor as defined below may be a single lead or multiple smaller ampacity leads in paral­lel for the purpose of carrying the equivalent or higher cur­rent of a single larger lead.)
When (3) conductors are used: Minimum ampacity per conductor = 1.25 x compressor RLA When 96) conductors are used: Minimum ampacity per conductor = 1.25 x compressor
RLA/2
4.2 When more than one conduit is used to run conductors from VFD to compressor motor terminal box, an equal num­ber of leads from each phase (conductor) must be in each conduit to prevent excessive heating (for example, conduc­tors to motor terminals 1, 2, and 3 in one conduit, and to 1, 2, and 3 in another conduit).
4.4 Compressor motor power conductors may enter terminal box through top, left side or bottom left using holes cut by contractor to suit conduit. Flexible conduit should be used for the last few feet to the terminal box for unit vibration iso­lation. Use of stress cones may require an oversize (spe­cial) motor terminal box (not supplied by Carrier).
4.3 Compressor motor frame to be grounded in accordance with the National Electrical Code (NFPA-70) and applicable codes. Means for grounding compressor motor is a #4 AWG to 500 MCM pressure connector, supplied and located in the lower left side corner of the compressor motor terminal box.
4.5 Do not allow motor terminals to support weight of wire cables. Use cable supports and strain reliefs as required.
4.6 Use backup wrench when tightening lead connectors to motor terminal studs. Torque to 30-35 ft-lb max.
4.7 Do not exceed 100 ft. maximum power cable length between the VFD and motor terminals without consulting Carrier for special requirements.
9
/16-in. diameter hole can be
CABLE INSULATION REQUIREMENTS
SYSTEM
VOLTAGE
2400 > 2.20 > 2.20 3000 > 2.75 > 2.75 3300 > 3.00 > 3.00 4160 > 3.80 > 3.80 6000 > 5.50 > 5.50 6300 > 5.80 > 5.80 6600 > 6.00 > 6.00
CABLE INSULATION RATING (kV)
(MAX. PEAK LINE-TO-GROUND)
LINE SIDE MACHINE SIDE
80
LEGEND FOR FIG. 45-50
Control Abbreviations — Fig. 45-50 Wiring Codes — Fig. 45-50
CDWP Condenser Water Pump CDWP-V Condenser Water Pump (Variable) CHWP Chilled Water Pump CHWP_V Chilled Water Pump (Variable) COND_EWP Entering Condenser Water Pressure COND_FL Condenser Water Flow Measurement COND_FS Condenser Water Flow Switch COND_LWP Leaving Condenser Water Pressure COND_P Condenser Pressure DGT Compressor Discharge Temperature DMP_CL Economizer Damper Valve Close DMP_FC Damper Valve Feedback Fully Close DMP_FO Damper Valve Feedback Fully Open DMP_OP Economizer Damper Valve Open ECDW Entering Condenser Water Temperature ECON_P Economizer Pressure ECW Entering Chilled Water Temperature EVAP_EWP Entering Evaporator Water Pressure EVAP_FL Evaporator Water F low Measurement EVAP_LWP Leaving Evaporator Water Pressure EVAP_P Evaporator Pressure EVAP_T Evaporator Refrigerant Temperature FS_LOCK Fire Alarm Interlock GV1-ACT IGV1 Position Input HDPV_OUT Head Pressure Output HGBP_CL Hot Gas Bypass (HGBP) Valve Close HGBP_FC Hot Gas Bypass Valve Feedback Fully Close HGBP_FO Hot Gas Bypass Valve Feedback Fully Open HGBP_OP Hot Gas Bypass Valve Open HP_SW High Pressure Switch ICE_CON Ice Build Contact LCDW Leaving Condenser Water Temperature LCW Leaving Chilled Water Temperature MTRB1 Low Speed Motor End Bearing Temperature
MTRB2 Low Speed Compressor End Bearing MTRB3 High Speed Motor End Bearing Temperature MTRB4 High Speed Compressor End Bearing MTRW1 Motor Winding Temperature 1
MTRW2 Motor Winding Temperature 2 MTRW3 Motor Winding Temperature 3 OIL_HEAT Oil Heater On/Off OIL_PUMP Oil Pump On/Off OILP_DIS Oil Pump Discharge Pressure OILP_SMP Oil Sump Pressure OILT_SMP Oil Sump Temperature REM_CON Remote Connect Input REM_LOCK Chiller Lockout Input REM_STP Remote Stop Lock SAFETY Spare Safety SHFT_DIS TFR_HIGH Tower Fan High TFR_LOW Tower Fan Low TOW_FAN Tower Fan (Variable)
(Thermistor/PT100) Temperature (Thermistor/PT100) (Thermistor/PT100) Temperature (Thermistor/PT100)
Bearing Shaft D
isplacement Switch
1C Oil Heater Contactor 2C Oil Pump Contactor 1CB Micro Circuit Breaker, Control Box 2CB Micro Circuit Breaker, HMI 3FU1,2 — Transformer 1 Primary Fuse 3FU3,4 — Transformer 1 Secondary Fuse 1R Alarm Relay 1T Transformer 1 2T Transformer 2 3T Transformer 3 1TB Terminal Block for Customer Power Connection 2TB Terminal Block for Field Connection 3TB Terminal Block for Customer Optional Connection 4TB HMI Terminal Block Field CCN Connection 5TB Terminal Block for Control Panel Internal Connection 6TB Terminal Block for Guide Vane, HGBP amd Damper
7TB Terminal Block for Guide Vane Actuator (220 v) A01 IGV/Stage 1 IGV A03 Discharge Gas Temperature Thermistor A04 High Pressure Switch A06 Bearing Displacement Switch C11 HGBP Valve Actuator E01 Evaporator Pressure Transducer E03 Leaving Chilled Water Temperature Thermistor E05 Evaporator Refrigerant Liquid Temperature Thermistor EC01 Economizer Pressure Transducer EC06 Damper Valve Actuator HMI Human Interface Panel ISM Integrated Starter Module M01 Motor Winding Temperature 1 (Thermistor/PT100) M02 Motor Winding Temperature 2 (Thermistor/PT100) M03 Motor Winding Temperature 3 (Thermistor/PT100) MSP Motor Starter Protection SAIA SAIA Touch Screen and Main Board T01 Low Speed Motor End Bearing Temperature
T02 Low Speed Compressor End Bearing Temperature T03 High Speed Motor End Bearing Temperature T04 High Speed Compressor End Bearing Temperature T05 Oil Sump Temperature Thermistor
T07 Oil Sump Pressure Transducer T08 Oil Pump Discharge Pressure Transducer T10 Oil H T11
Valve
(Thermistor/PT100) (Thermistor/PT100) (Thermistor/PT100) (Thermistor/PT100)
eater
Oil Pump
81
LEGEND — FIG. 45-50
Fig. 45 — Controls Diagram
a19-287
82
CHILLER RUN STATUS (mA)
Fig. 46 — IOB 1
REMOTE LOCKOUT
FIRE SECURITY INTERLOCK
(+) (G)
(-)
(+) (G)
(-)
REMOTE CONTACT
REMOTE STOP
ALARM RELAY
ALERT RELAY
a19-2245
83
a19-2288
Fig. 47 — IOB 2
84
a19-2289
Fig. 48 — IOB 3
85
a19-2285
Fig. 49 — IOB 4
86
87
Fig. 50 — Starter Wiring
a19-2290

APPENDIX A — PIC 5 SCREEN AND MENU STRUCTURE

HOME
MAIN MENU LOG IN/LOG OUT CONFIRM STOP CHOOSE OPERATING MODE ALARM MENU
a19-2238
Main Menu
General Parameters
Inputs Status
Run Times
Temperatures
Outputs Status
Modes
Pressures
Hydraulic Status
Trending
Reset alarms Current Alarms History Alarms
Fig. A — Screen Structure, Basic Level (All) Access (No Password Required)
88
APPENDIX A — PIC 5 SCREEN AND MENU STRUCTURE (cont)
HOME
MAIN MENU LOG IN/LOG OUT CONFIRM STOP CHOOSE OPERATING MODE ALARM MENU
a19-2239
Main Menu
General Parameters
Temperatures Pressures
Inputs Status
Outputs Status
Hydraulic Status
Run Times
Modes Setpoint
Reset alarms Current Alarms History Alarms
Main Menu
Main MMMenunununu
Configuration Menu
Trending
Prognostics
Main Menu
a19-2281
Fig. B — Screen Structure, User Level Access (User Password Required)
89
APPENDIX A — PIC 5 SCREEN AND MENU STRUCTURE (cont)
HOME
MAIN MENU LOG IN/LOG OUT CONFIRM STOP CHOOSE OPERATING MODE ALARM MENU
Main Menu
Main Menu
General Parameters
Temperatures Pressures
Inputs Status
Outputs Status
Hydraulic Status
Run Times
Modes Setpoint
Reset alarms Current Alarms History Alarms
Configuration Menu
Quick Test
Maintenance Menu
Trending
Prognostics
a19-2282
Fig. C — Screen Structure, Service (Advanced User)/Factory Level Access Password Required)
90
APPENDIX A — PIC 5 SCREEN AND MENU STRUCTURE (cont)

Main Menu Description

ICON DISPLAYED TEXT* ACCESS ASSOCIATED TABLE†
General Parameters
Temperatures
Pressures
Inputs Status
Outputs Status
Hydraulic Status
Run Times
Modes
Setpoint User, Service (Advanced User), Factory SETPOINT
Configuration Menu User, Service (Advanced User), Factory CONFIG
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
Basic, User, Service (Advanced User), Factory
GENUINT
TEMP
PRESSURE
INPUTS
OUTPUTS
HYDRLIC
RUNTIME
MODES
Quick Test Service (Advanced User), Factory QCK_TEST
Maintenance Menu Service (Advanced User), Factory MAINTAIN
Trending
Prognostics User, Service (Advanced User), Factory HEALTH
*Displayed text depends on the selected language (default is English). †See the 19XR Controls Operation and Troubleshooting manual for table details.
Basic, User, Service (Advanced User), Factory
TRENDING
91

APPENDIX B — CCN COMMUNICATION WIRING FOR MULTIPLE CHILLERS (TYPICAL)

a19-2133
NOTE: Field-supplied terminal strip must be located in control panel.
DRAIN WIRE
BLACK (G) WHITE (–)
RED (+)
92

APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS

19XR Maintenance Interval Requirements
WEEKLY
COMPRESSOR Check Oil Level. CONTROLS Review PIC 5 Alarm/Alert History.
COOLER None. STARTER None.
CONDENSER None. OIL RECLAIM None.
MONTHLY
COMPRESSOR None. CONTROLS Perform an Automated Controls test.
COOLER None. STARTER None.
CONDENSER None. OIL RECLAIM None.
FIRST YEAR
COMPRESSOR
COOLER
CONDENSER
COMPRESSOR
COOLER
CONDENSER
STARTING
EQUIPMENT
COMPRESSOR None. CONTROLS None.
COOLER Perform eddy current test. STARTER None.
CONDENSER
COMPRESSOR
COOLER None. STARTER None.
CONDENSER None. OIL RECLAIM
COMPRESSOR None. CONTROLS Do not disconnect control power.
COOLER
CONDENSER
NOTE: Equipment failures caused by lack of adherence to the Main­tenance Interval Requirements are not covered under warranty.
Change oil filter. Send oil sample out for analysis. Change oil if required by analysis. Leak test.
Inspect and clean cooler tubes. Inspect relief valves. Leak test. Verify water pressure dif­ferential. Inspect water pumps and cooling tower.
Replace refrigerant filter/drier. Inspect and clean condenser tubes. Inspect relief valves. Leak test. Verify water pressure differential. Inspect water pumps and cooling tower.
Change oil filter. Send oil sample out for analysis. Change oil if required by analysis. Leak test.
Inspect and clean cooler tubes. Inspect relief valves. Leak test. Verify water pressure dif­ferential. Inspect water pumps and cooling tower.
Replace refrigerant filter/drier. Inspect and clean condenser tubes. Inspect relief valves. Leak test. Verify water pressure differential. Inspect water pumps and cooling tower.
Follow all lockout-tagout procedures. Inspect inside of enclosure for contaminant build-up. Vacuum any accumulated dust or debris from internal parts. Use electronic cleaner as required.
spect float valve and strainer. Perfo
In current test.
Change oil charge (if required based on oil analysis or if oil analysis has not been per­formed). Inspect compressor shafts and bearings (every 5-10 years).
Isolate and drain waterbox. Remove water­box cover from one end. Use compressed air to clear tubes.
Isolate and drain waterbox. Remove water­box cover from one end. Use compressed air to clear tubes.
rm eddy
SEASONAL SHUTDOWN
CONTROLS
STARTER
OIL RECLAIM Inspect oil sump strainer.
ANNUALLY
CONTROLS
STARTER Perform general cleaning. Tighten connections.
OIL RECLAIM None.
EVERY 3-5 YEARS
OIL RECLAIM None.
EVERY 5 YEARS
CONTROLS None.
STARTER None.
OIL RECLAIM None.
Perform general cleaning. Tighten connections. Check pressure transducers. Confirm accuracy of thermistors.
Perform general cleaning. Tighten connections. Change VFD refrigerant strainer.
Perform general cleaning. Tighten connections. Check pressure transducers. Confirm accuracy of thermistors.
Inspect oil sump strainer. Inspect oil sump heater. Replace the oil reclaim filter.
93
APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
19XR Monthly Maintenance Log
MONTH 123456789101112
DATE / / / / / / / / / / / / / / / / / / / / / / / /
OPERATOR
UNIT SECTION ACTION UNIT ENTRY
Change Oil Charge yes/no Change Oil Filter yes/no
COMPRESSOR
COOLER
94
CONDENSER
CONTROLS
STARTER General Tightening and Cleaning Connections yes/no
OIL RECLAIM
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
Send Oil Sample Out for Analysis yes/no Leak Test ppm Inspect Compressor Rotors yes/no Bearing Inspection yes/no Inspect and Clean Cooler Tubes yes/no Inspect Relief Valves yes/no Leak Test ppm Record Water Pressure Differential (PSI) PSI Inspect Water Pumps yes/no Eddy Current Test yes/no Leak Test ppm Inspect and Clean Condenser Tubes yes/no Record Water Pressure Differential (PSI) PSI Inspect Water Pumps and Cooling Tower yes/no Inspect Relief Valves yes/no Replace Refrigerant Filter Drier yes/no Inspect Float Valve and Strainer yes/no Eddy Current Test yes/no General Cleaning and Tightening Connections yes/no Check Pressure Transducers yes/no Confirm Accuracy of Thermistors yes/no Perform Automated Controls Test yes/no
Inspect Oil Sump Strainer yes/no Inspect Oil Sump Heater yes/no
APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
19XR Seasonal Shutdown Log
MONTH 123456789101112
DATE / / / / / / / / / / / / / / / / / / / / / / / /
OPERATOR
UNIT SECTION ACTION ENTRY
Isolate and Drain Waterbox
COOLER
CONDENSER
CONTROLS Do Not Disconnect Control Power
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
95
Remove Waterbox Cover from One End Use Compressed Air to Clean Tubes Isolate and Drain Waterbox Remove Waterbox Cover from One End Use Compressed Air to Clean Tubes
Abbreviations and explanations, 4 Bearing and gear maintenance, 40 Bearings, 8 Bolt torque requirements, 14 Chiller Components, 6 Dehydration, 18 Familiarization, 4 Identification, 5 Information nameplate, 4 Leak test, 16 Limited shutdown, operation after, 30 Operating condition, checking, 29 Preparing for start-up, 30 Replacement parts, ordering, 41 Starting, 30 Stopping, 30 Tightness, checking, 13 Cold weather operation, 31 Compressor Assembly torques, 65 Bearing and gear maintenance, 40 Description, 4 Fits and clearances, 62 Condenser
Description, 4
Control Panel Description, 4 Inspecting, 38 Controller identification, modifying, 21 Controls Description, 10 PIC 5 system components, 10 Powering up, 19 Cooler Description, 4 Display messages, checking, 42 Economizer Damper valve, 39 Description, 5 Float system, 39 Equipment required, 13 Extended shutdown Preparing for, 30 Operation after, 30 Field set up and verification, 22 Gasketed joints, tightening, 13 Guide vanes Checking, 36 Operation, manual, 31 Heat exchanger tubes and flow devices, maintenance, 40 Heat exchanger refrigerant charge, 27 High altitude locations, 46 Initial start-up, 29 Initial start-up checklist, CL-1 Inspecting equipment, 41 Instructing customer operator, 29 Job data required, 13 Job site parameters, 21 Leak test procedures (chart), 15 Limited shutdown, operation after, 30 Local start/stop control, 11 Login/logout, 20 Lubrication control, 12 Lubrication cycle, 8 Lubrication system, checking, 38 Maintenance General, 36 Scheduled, 38 Summary and log sheets, 93 Weekly, 38 Motor and oil cooling cycle, 8 Motor rotation, checking, 29 Oil changes, 39

INDEX

Oil charge, 19 Oil circuit valves, opening, 13 Oil filter, changing, 39 Oil heater, checking, 19 Oil pressure and compressor stop, checking, 29 Oil pump, 9 Oil reclaim filter, 39 Oil reclaim system, 8 Oil recovery, 8 Oil specification, 39 Operating instructions, 30 Operator duties, 30 Passwords, 20 Physical data, 48 PIC 5 Screen and menu reference, 88 System components, 10 Piping Inspecting before start-up, 18 Maintenance, 40 Pressure transducers Calibration, 46 Checking, 46 Recalibrating, 41 Pumpdown/lockout, 48 Pumpout and refrigerant transfer, 31 Pumpout unit Maintenance, 41 Operating, 33 Quick test Table, 24 Use in troubleshooting 48 Refrigerant
Adding, 36
Adjusting charge, 36 Charging into chiller, 25 Filter, 39 Float system, inspecting, 39 Leak rate, 36 Leak testing, 36 Properties, 36 Testing after service, repair, or major leak, 36 Tracer, 16 Trimming charge, 38 Refrigeration cycle, 7 Refrigeration log, 31 Relief valves Checking before start-up, Maintenance, 40 Replacement parts, ordering, 41 Running system, checking, 30 Safety considerations, 1 Schedule, inputting local occupied, 20 Sensor accuracy, checking, 45 Service configurations, inputting, 20 Service ontime, 38 Service tables, configuring, 21 Set points, inputting design, 20 Shipping packaging, removing, 13 Shutdown After extended, 30 After limited, 30 Local (with HMI), 12 Preparation for extended, 30 Software configuration, 19 Standing vacuum test, 16 Starter Free-standing, description, 5 Mechanical, checking, 19 Solid-state, description, 10 Solid-state, checking, 19 Starting equipment, 10
18
Start-Up Accidental, preventing, 29 Before initial, 13 Chiller dehydration, 18 Equipment required, 13 Field set up and verification, 22 Gasketed joints, tightening, 13 Initial, 29 Inspecting water piping, 18 Job data required, 13 Leak test, 16 Oil charge, 19 Oil circuit valves, opening, 13 Oil heater, checking, 19 Controls, powering up, 19 Control test (quick test), 24 Refrigerant, charging into chiller, 25 Relief valves, checking, 18 Schedule, inputting local occupied, 20 Service configurations, inputting, 20 Set points, inputting design, 20 Shipping packaging, removing, 13 Software configuration, 19 Standing vacuum test, 16 Starter, checking, 19 Timing sequence, 12 Tracer, 16 Wiring, inspecting, 18 Start-up/shutdown/recycle sequence, 11 Surge prevention, 22 System components, 4 Temperature sensors, checking, 42 Thermal dispersion switch calibration, 46 Thermistor temperature vs. resistance/ voltage drop (C) 44 Thermistor temperature vs. resistance/ voltage drop (F) 43 Time and date, inputting, 21 Troubleshooting guide, 42 VFD, free-standing, 10 Water Leaks, 41 Treatment, 41 Weights Component, 61 Compressor and motor (50 Hz), 55, 57 Compressor and motor (60 Hz), 56, 58 Economizer, 53 Heat exchanger (English), 49, 51 Heat exchanger (SI), 50, 52 Marine waterboxes, 150 psig, 53, 54 Marine waterboxes, 300 psig (English), 53, 54 Marine waterboxes, 300 psig (SI), 53, 54 Waterbox cover (English), 59, 60 Waterbox cover (SI), 59, 60 Wiring Bearing sensors, 45 CCN for multiple chillers, 92 Control panel bottom layer, 66 Control panel IOB layer, 66 Free-standing starter field wiring, 68 Free-standing VFD field wiring, 72 HMI panel, 65 IOB 1, 83 IOB 2, 84 IOB 3, 85 IOB 4, 86 Inspecting, 18 Pumpout unit schematic, 33 SAIA control board, 82 Starter, 87
96
© Carrier Corporation 2015
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190038-01 Printed in U.S.A. Form 19XR-CLT-12SS Pg 98 12-15 Replaces: 19XR-CLT-11SS
INITIAL START-UP CHECKLIST
FOR 19XR SEMI-HERMETIC TWO-STAGE CENTRIFUGAL LIQUID CHILLER
(Remove and use for job file.)
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment and follow safe practices as outlined in preceding sections of this Start-Up, Operation and Mainte­nance Instructions document.
MACHINE INFORMATION: NAME JOB NO.
ADDRESS MODEL CITY STATE ZIP S/N
DESIGN CONDITIONS:
TONS BRINE
COOLER ******
CONDENSER ******
FLOW
RATE
TEMPERATUREINTEMPERATURE
OUT
PRESSURE
DROP
PASS
SUCTION
TEMPERATURE
CONDENSER
TEMPERATURE
COMPRESSOR: Volts RLA OLTA STARTER: Mfg Type S/N OIL PUMP: Volts RLA OLTA
CONTROL PANEL SUPPLY: Voltage __________ Hertz ________ REFRIGERANT: Type:
Charge
CARRIER OBLIGATIONS: Assemble... . . . . . . . . . . . . . . . . Yes No
Leak Test . . . . . . . . . . . . . . . . . . . Yes No
Dehydrate . . . . . . . . . . . . . . . . . . Yes No
Charging . . . . . . . . . . . . . . . . . . . Yes No
Operating Instructions Hrs.
START-UP TO BE PERFORMED IN ACCORDANCE WITH APPROPRIATE MACHINE START-UP INSTRUCTIONS JOB DATA REQUIRED:
1. Machine Installation Instructions . . . . . . . . . . . . . . . . . . Yes
No
2. Machine Assembly, Wiring and Piping Diagrams. . . . . . Yes No
3. Starting Equipment Details and Wiring Diagrams. . . . . . Yes No
4. Applicable Design Data (see above). . . . . . . . . . . . . . . . Yes No
5. Diagrams and Instructions for Special Controls . . . . . . . Yes No
INITIAL MACHINE PRESSURE:
YES NO Was Machine Tight? If Not, Were Leaks Corrected? Was Machine Dehydrated After Repairs?
Manufacturer reserves the right to discontinue, or change at any time, specificatio ns or designs without not ice and without incurring obligations.
Catalog No. 04-53190038-01 Printed in U.S.A. Form 19XR-CLT-12SS Pg CL-1 12-15 Replaces: 19XR-CLT-11SS
CHECK OIL LEVEL AND RECORD: ADD OIL: Yes No
1/2 Top sight glass
1/2 Bottom sight glass
3/4
1/4
3/4 1/4
Amount:
RECORD PRESSURE DROPS: Cooler Condenser CHARGE REFRIGERANT: Initial Charge Final Charge After Trim INSPECT WIRING AND RECORD ELECTRICAL DATA:
RATINGS: Motor Voltage
Motor(s) Amps Oil Pump Voltage Starter LRA Rating
Line Voltages: Motor Oil Pump Controls/Oil Heater
RECORD THE FOLLOWING POWER ON CHECKS:
Line Voltage: Phase - Phase A-B: B-C: A-C: Line Voltage: Phase - Ground A-G: B-G: C-G:
What type and size of transformer supplies power to the unit? Delta with No Ground _____ Corner Grounded Delta _____ Wye with Center Ground _____ Wye with No Ground _____ Transformer Size _____kVa
CONTROLS: SAFETY, OPERATING, ETC. Perform Controls Test (Yes/No)
CAUTION
COMPRESSOR MOTOR AND CONTROL PANEL MUST BE PROPERLY AND INDIVIDUALLY CONNECTED BACK TO THE EARTH GROUND IN THE STARTER (IN ACCORDANCE WITH CERTIFIED DRAWINGS).
Yes
WATER/BRINE PUMP CONTROL: Can the Carrier controls independently start the pumps?
Condenser Water Pump Yes No  Chilled Water Pump Yes No 
RUN MACHINE: Do these safeties shut down machine?
Condenser Water Flow Yes No  Chilled Water Flow Yes No  Pump Interlocks Yes No 
INITIAL START: Line Up All Valves in Accordance With Instruction Manual: Start Water Pumps and Establish Water Flow Oil Level OK and Oil Temperature OK Check Oil Pump Rotation-Press ur e Check Compressor Motor Rotation (Motor End Sight Glass) and Record: Clockwise Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? Yes* No
*If yes, determine cause.
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CL-2
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...