Carnes HRAA Installation Manual

READ AND SAVE THESE INSTRUCTIONS
MODEL HRAA TECHNICAL MANUAL
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
CARNES COMPANY, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 - Phone: 608/845-6411 - Fax: 608/845-6470 carnes@carnes.com www.carnes.com
FORM 16799
ISSUED: 06-08
TYPICAL INSTALLATION
Figure A
Humidistat
Steam
Hose
Steam Distributor Pipe
Condensate Return Line
Water Shutoff Valve (By Others)
Wall Humidistat
Cold Water Line
Fused Disconnect or Circuit Breaker
(By Others)
Air Flow Switch
Air Flow
Humidifier Cabinet
Drain Line
Air Gap Drain Fitting
WARNING:
THE HUMIDIFIER CABINET CONTAINS HIGH VOLTAGE WIRING AND HOT SURFACES. THE CABINET DOOR INCLUDES A LOCK AND ACCESS MUST BE LIMITED TO TRAINED AND QUALIFIED PERSONNEL ONLY. THE DOOR MUST BE LOCKED AND KEY MUST BE KEPT IN A SECURE LOCATION AWAY FROM THE HUMIDIFIER
2
Steam Cylinder
Hinged Door with Key Lock
Steam Hose
Diagnostic Display Panel
Condensate Return Inlet
Figure B
Hole For Power Wiring
Hole for Control Wiring
Water Inlet
Fill Solenoid Valve
Door Interlock Switch
Drain Solenoid Valve
Figure C
Wiring Access
Panel
Electric Power Terminals
Current Sensing Transformer
Control Connection Terminals
Power Contactor (Relay)
Power Transformer
Figure D
WARNING:
INSTALLING AND SERVICING THIS EQUIPMENT CAN BE HAZARDOUS DUE TO ELECTRICAL COMPONENTS AND HOT SURFACES. ONLY TRAINED AND QUALIFIED PERSONNEL SHOULD INSTALL, REPAIR OR SERVICE THIS EQUIPMENT. INSTALLATION MUST BE MADE IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS.
INSTALLATION
UNPACKING AND INSPECTION
1. An envelope shipped with the cabinet contains the cabinet keys and Installation, Operation and Maintenance Instructions.
2. The following optional components are packed in a separate shipping carton for connection when installing the humidifier.
A. Steam Distributor Pipe. B. Steam Hose. C. Condensate Return Line. D. Humidistats and Air Flow Switches. E. Steam Hose Clamps. F. Condensate Return Clamps. G. Air Gap Drain Fitting.
The distributor pipe should be located to insure best distribution of steam into the airstream. A minimum clearance of 4” must be maintained between the top of the duct and the distributor pipe. The steam distributor pipe is usually located in the supply duct downstream of the fan. It is important to locate the distributor as far upstream as possible from any obstruc­tions in the ductwork so that air can absorb the steam before it impinges on a surface and condenses. There must be minimum of three feet between the distributor and any fans, coils, filters, dampers, elbows or outlets downstream to reduce the possibility of condensation. Duct air temperatures below 60°F may require a conden­sate drain pan, supplied by others, below the steam distributor pipe.
STEAM DISTRIBUTOR PIPE LOCATION
In a typical installation the humidifier is located below a duct as shown in Figure A. The distance between the humidifier cabinet and the steam distributor pipe should be the shortest possible.
In a vertical duct with either upward or downward air flow the distributor pipe should be installed horizontally.
The maximum length of steam hose that may be installed is 10 feet.
Figure E
AIR
FLOW
The distributor pipe may be located below the humidifier if the installation is made as shown in Figure F. A trap may be necessary to prevent steam from flowing back through the condensate return line.
Figure F
INSTALL STEAM DISTRIBUTOR PIPE
The steam distributor pipe must be mounted on a plumb surface so that it is inclined upward. This is required so the condensate, which forms in the distributor pipe, will drain into the return line.
Insert the distributor pipe into duct and secure with four sheet metal screws, not provided.
3
DRAIN LINE CONNECTION
1. Remove the large nut and plastic gasket located on the fitting on the bottom of the cabinet. The nut and gasket may be used with standard type drain fitting if an air gap fitting is not required by local codes.
2. Connect the air gap drain fitting to the cabinet drain connection. It may be necessary to cut off some of the air gap fitting depending on available space.
3. Connect the drain or air gap fitting to S or P trap or run piping to a floor drain. Use plumbing material capable of handling hot water, such as copper or CPVC.
CONNECT THE STEAM HOSE & CONDENSATE RETURN LINE
COPPER TUBE IS THE ONLY ACCEPTABLE SUBSTI­TUTE FOR STEAM HOSE OR CONDENSATE RETURN LINE.
1. The steam hose should be installed so there is a continuous rise from the humidifier to the distributor pipe. The rise should be 2” in 12” to allow proper condensate drainage.
Support the steam hose at intermediate points to prevent dips or pockets. It is very important that both the steam hose and condensate return line be installed so that sags are prevented. The steam is at very low pressure and it cannot overcome resistance caused by water standing in the steam hose. Water accumulating in sags in the return line will restrict the flow and may cause water to enter the duct from the distributor pipe.
If it is difficult to install the steam hose to prevent sags, it is recommended that copper tube be used as a substi­tute. Size 3/4” copper tube can be used. Any 90° elbows are approximately equivalent to three feet of steam hose.
If copper tube is used, a minimum of one inch of insulation must be applied to prevent excessive condensation and contact with the hot pipe. A short
length of steam hose must be used to connect the cylinder in the humidifier to the copper tube. Another short length should be used to connect the copper tube to the distributor pipe. Any turns in the hose should have a minimum radius of 8” to prevent kinking.
2. Fasten the steam hose to the distributor pipe with one of the hose clamps provided.
3. Push the steam hose through the opening on the top of the humidifier cabinet and slip over the outlet stub
on the top of the cylinder. Fasten with the hose clamp
provided.
4. Fasten the condensate return line to the distributor pipe with the hose clamp provided. Connect the return line to the condensate return inlet with the hose clamp provided.
If it is impossible to maintain a drop to the top of the cabinet, it will be necessary to run the condensate return line directly to the air gap drain fitting or some other drain. A trap (usually 8” is sufficient) may be necessary to pre­vent loss of steam through the return line. Do not install a trap if condensate is returned to the top of the cabinet.
MOUNTING THE HUMIDIFIER
Locate the humidifier cabinet level and plumb on a surface as close to the steam distributor as possible at a convenient height for servicing. Allow 1” or more on the sides for ventilation and 16” from the bottom to the floor to allow for drain connections. Allow at least 16” in front of cabinet for door opening. Consult local and national codes prior to installation and comply with any provisions they require.
The humidifier must never be located outside or where it may be exposed to freezing temperatures unless a heated, ventilated, weatherproof enclosure by others is provided. Do not mount humidifiers on a hot or vibrating surface.
Maximum operating weight is 70 pounds. Fasten the mounting bracket to wood studs or solid wood. Recommended fasteners: Four 1/4” x 1” long lag screws. Fasteners are not provided.
Place the mounting flange on the humidifier cabinet over the mounting bracket. A sheet metal screw should be installed through the back of the humidifier cabinet to secure the humidifier to the mounting bracket.
WATER SUPPLY CONNECTION
DO NOT
use hot water, deionized water, or water that has been treated by a water softener without consulting the factory.
Use ordinary tap water (20 to 120 psi). A 1/4” FPT fitting is provided at the top of the humidifier. A shutoff valve, not provided, must be installed ahead of this fitting.
MOUNTING FLANGE
MOUNTING BRACKET
AIR GAP DRAIN FITTING
Figure G
4
5
Line Recommended Digital
Maximum Amp Disconnect Steam Display
Model Lb./Hr. kW Voltage Phase Rating Size (Amps) Cylinder Code
HRAAA U 005 5 1.7 120 1 14.4 20 HXCBAX220 0005 HRAAD U 005 5 1.7 230 1 7.5 15 HXCBAX380 3005 HRAAD U 010 10 3.4 230 1 15.0 20 HXCBAX380 3010
U = UL C = cUL
ELECTRICAL DATA
Check unit electrical characteristics on label outside of cabinet. They must agree with power provided to the unit.
A fused disconnect or circuit breaker, not provided, must be installed per local and national codes.
1. Remove screws securing hinged panel for access to wiring.
2. An opening is provided on the top of the electrical section. Bring electrical power lines through this opening and connect to the electric power terminals as shown on wiring diagram.
3. Replace electrical cover panel.
CONTROLS
CONTROL HUMIDISTAT
Either a wall-mounted humidistat or duct-mounted humidistat in the return air may be used. The wall-mount­ed humidistat is the most common as it allows the setting to be easily adjusted to accommodate changing require­ments or to lower the level of relative humidity in the space to prevent condensation on windows during extremely cold weather. Room humidity is usually set in range of 30-40% RH. Other settings may be necessary for certain conditions.
If an on-off humidistat is used the humidifier will generate steam at the preset output rate and cycle on or off as necessary to satisfy the conditioned area requirements.
If a proportional humidistat is used the humidifier will automatically vary the steam output rate in the range of 25-100% of the humidifiers maximum rating in response to the humidistat. Proportional control provides less on-off cycling of the humidifier.
ELECTRICAL CONNECTIONS
WARNING:
BEFORE MAKING ANY
ELECTRICAL CONNECTIONS SWITCH POWER OFF AT SERVICE PANEL, FUSED DISCONNECT OR CIRCUIT BREAKER AND LOCK THE DISCONNECTING MEANS TO PREVENT POWER FROM BEING SWITCHED ON ACCIDENTALLY.
AIR FLOW DETECTION
The humidifier control circuit should include some method to confirm air flow. If the steam distributor pipe were “located in a duct where there is no air flow and the control humidistat is calling for humidity, steam would be discharged into the duct where it would immediately condense.
Air flow may be detected by using a pressure differential switch that detects air flow by sensing static pressure in the duct.
CONDENSATION PROTECTION
An additional device may be used to provide condensa­tion protection in the duct system. A high limit humidistat may be installed 10 feet downstream from the steam distributor pipe. This humidistat is normally set to 90-95% RH and opens the circuit if the humidity level in the duct exceeds the set-point. Once the humidity level returns below the set-point, humidifier operation will resume following a delay of several minutes after reclosure of the circuit. Use of this device is recommended particularly when the humidifier is used in applications where cooling air is being humidified.
Either an on-off or proportional high limit humidistat may be used. If a proportional humidistat is used the output of the humidifier will automatically be decreased to reduce the possibility of condensation. Two proportional humidis­tats may be used. One may be located in the area to be humidified or its return duct and another as a high limit in the supply duct. The humidifier will automatically select the lowest signal to control the humidifier output.
EXTERNAL MONITORING
Terminals 11 and 12, shown in Figure H are provided for remote monitoring of the status of the humidifier if desired. When the unit is on terminals 11 and 12 are closed. When the output of the humidifier is less than 50% of set-point terminals 13 and 14 are closed indicat­ing a need for service. Each set of terminals is capable of switching 1/2 amp at 24 volt maximum.
WARNING:
BEFORE MAKING ANY
ELECTRICAL CONNECTIONS SWITCH POWER OFF AT SERVICE PANEL, FUSED DISCONNECT OR CIRCUIT BREAKER AND LOCK THE DISCONNECTING MEANS TO PREVENT POWER FROM BEING SWITCHED ON ACCIDENTALLY.
CONTROL CONNECTIONS
1. A 7/8” opening is provided on top of the cabinet. The control wiring should pass through the opening to the
terminal strip.
NOTE: A built-in transformer provides power for the control circuit. No outside power supply is required for the control circuit.
2. If an air flow switch or high limit humidistat is not used jumpers must be installed before the humidifier will operate.
Controls should be connected to the terminals on the electronic circuit board as shown Figure H using #18 AWG wire. Avoid running control wiring near high voltage wires.
Figure H
6
Loading...
+ 11 hidden pages