5
INSTALL STEAM DISTRIBUTOR PIPE
EACH CYLINDER REQUIRES SEPARATE STEAM HOSE, CONDENSATE RETURN LINE, AND STEAM DISTRIBUTOR PIPE.
1. Steam distributor pipe must be mounted on a plumb surface.
When on a plumb surface the standard distributor pipe is
inclined upward. This is required so the condensate which
forms in the distributor pipe will drain to the return line and
back to the unit, or to common drain.
2. Insert distributor pipe into duct and secure with four sheet
metal screws, not provided by Carnes.
3. Special distributor pipes are shipped with specific instructions
on how to mount them.
4. If the optional fan distribution unit is to be used, follow the
instructions included with the unit.
CONNECT THE STEAM HOSE
COPPER OR BRASS TUBE IS THE ONLY ACCEPTABLE
SUBSTITUTE FOR CARNES STEAM HOSE OR CONDENSATE
HOSE.
1. The steam hose should be installed so there is a continuous
rise from the humidifier to the distributor pipe. Support the
steam hose at intermediate points to prevent dips, pockets,
sags or horizontal runs. See Figure H.
2. Any turns should have a minimum radius of 8” to prevent the
hose from kinking. Fasten the steam hose to the distributor
pipe with one of the hose clamps provided.
3. Push the steam hose through the opening on the top of the
humidifier cabinet and slip over the outlet stub on the top of
the cylinder. Fasten the hose clamp provided.
4. If long lengths of steam hose, (or hard tubing) are used, the
use of periodic “T’s” to drain condensate should be used.
See Figure C.
CONDENSATE RETURN LINE
1. Fasten the condensate return line to the distributor pipe with
the hose clamp provided.
2. Follow the steam hose to the humidifier cabinet and secure
the return line to the steam hose.
3. Connect the return line to the condensate return inlet with
hose clamp provided.
4. If it is impossible to maintain a drop to the top of the cabinet,
it is necessary to run the condensate return line directly to the
air gap drain fitting or some other drain.
5. A trap (of sufficient size) may be necessary to prevent loss of
steam through the return line and reduce the temperature of
condensate water to the common drain. Do not install a trap
if condensate is returned to the top of cabinet.
STEAM DISPERSION CRITERIA
1. Distributor pipe location must be at a minimum of 6 feet
upstream from any elbows, splits, coils, turning vanes, grilles,
diffusers, etc.
2. If temperature in duct is 55° to 60°F or less, recommended 10
feet of distance be used.
3. Under normal and average conditions, most absorption distances will probably fall into the 4 to 5 feet length. This is true,
whether the unit is a 30 lb./hr. or less capacity or 30 lb./hr. or
more capacity.
4. If distance recommended can not be possible, then a drain
pan with drain capability may be required.
5. If the air in the duct can not hold the volume of steam, the only
recourse may be to lower the maximum output of the unit.
6. If shorter absorption distances are required, 3 ft. or less,
multiple distributor pipes could be used. 2 pipes split off one
steam house or 2 pipes from a dual cylinder unit.
7. If even shorter absorption distances are required, 2 ft. or less,
then multi tube short absorption manifolds may be required.
NOTES: Identifying and explaining the following electrical
data and unit detail sheet
“Model” and “Optional Circuit Breaker” columns designate
presence, quantity and amp rating of optional circuit breakers. All
models have overload protection provided by the electronic circuit
board. In addition, as an option, internally mounted, switchable
on-off, circuit breakers are available in models preceded by “HB
”.
“Maximum Lb./Hr.” designates maximum capacity of humidifier.
Units are shipped from the factory preset at the maximum rate.
The output rate may be easily reset after installation anywhere
between 100% and 25% of maximum capacity.
“Voltage” and “Phase” designate available phase and nominal
voltages. Single phase units may be operated from two legs of a
three phase supply but the load will be unbalanced.
“kW” ratings shown is at maximum output rate. If a unit is reset
for less than maximum output, the kW is reduced proportionally.
“Line Amp” and “Disc. Size” are amp ratings shown for use in
selecting electrical service requirements.
“Steam Cylinder” column shows the quantity and the model of
steam generating cylinders mounted in the humidifier. Each
cylinder requires its own steam distribution pipe, steam hose and
condensate return line.
“Digital Display Code” column shows the code that will appear
on the digital display when in the “Calibration” function. The
calibration function of the circuit board can be checked for
accuracy with the model shown on the rating label.
“J4 (Set) & J5 (GND) Vdc” - test lead rating of circuit board when
in calibration mode. Consult factory for procedures.
“Cylinder Wire Current” - as a process of troubleshooting, it may
be necessary to confirm current flow through individual cylinder
wires during operation. Match humidifier with electrical data.
“Minimum Output Settings” - the minimum setting that a
maximum output can be adjusted to and still maintain normal
effective and efficient operation.
STEAM DISPERSION CRITERIA
(Continued)
You must keep in mind that there are a lot of variables involved in
proper steam distribution and absorption distances (duct length
downstream from the dispersion method, required absorption distance determined by design, capacity of humidification, velocity of
air flow, temperature of air flow, location of humidifier/s, distance
between humidifier/s to distribution point and so on). Since this is
important to successful humidification, proper planning must be a
pre-requisite to good performance - PRIOR PREPARATION
PREVENTS POOR PERFORMANCE.
ELECTRICAL CONNECTIONS
POWER MUST BE OFF BEFORE MAKING ANY ELECTRICAL
CONNECTIONS
Check unit electrical characteristics on label outside of cabinet. It
must agree with power provided to the unit. If it does not, contact
your Carnes Representative.
A fused disconnect or circuit breaker not provided by Carnes,
MUST be installed per local and national codes. See Table 4 for
recommended circuit ratings. The optional circuit breaker switch,
offered as an accessory, installed in the humidifier, is NOT for use
as a replacement for the required external disconnect switch, but
as a maintenance convenience addition.
1. Remove screws securing hinged panel for access to wiring.
2. An opening is provided on the bottom of the electrical
section. Bring electrical power lines through this opening and
connect to electric power terminals.
3. Connect cabinet ground terminals to an independent ground.
DO NOT use the neutral of a four-wire power supply.
4. Replace electrical cover panel.