Carnes HBDA Installation Manual

READ AND SAVE THESE INSTRUCTIONS
ELECTRONICALLY CONTROLLED STEAM HUMIDIFIER
DESIGN SERIES HB
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
CARNES COMPANY, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: 608/845-6411 Fax:608/845-6470 carnes@carnes.com http://www.carnes.com
External Disconnect or Circuit Breaker
(Not Provided by Carnes)
Water Shutoff Valve
(Not Provided by Carnes)
FORM 16632-B
Steam Hose
Water Strainer
Fill Solenoid Valve
Door Interlock
“On” Lamp
Steam Output Rate Meter
“Abnormal” Lamp
“On-Off-Drain” Switch
Magnetic Overload Switch
Low V oltage Fuse
Steam Output Control
Hose Clamp
Cylinder Retaining Band
Steam Cylinder
Drain Solenoid Valve
Brass Cylinder Fitting
Photo A
MODEL HBDA SHOWN
INSTALLATION
UNPACKING AND INSPECTION
1.
2.
3.
4.
5.
A manila envelope attached to the outside of the cab­inet contains the following items: A. Installation instr uctions B. One cabinet key
Open the cabinet and check for concealed shipping damage. Report any damage immediately to the car­rier who delivered shipment.
The following components are packed in a shipping carton for connection when installing humidifiers: A. Distributor pipe B. Steam hose C. Condensate return line
Optional accessories may be packed with the cabinet or in the same shipping carton. Large accessories ship in separate cartons.
Inside the cabinet are the following items: A. Steam hose clamps B. Condensate return line clamps C. Air gap drain fitting
1.
2.
3.
Remove the large nut and plastic gasket located on the fitting on the bottom of the cabinet (Photo B). The nut and gasket may be used with standard type drain fitting if an air gap drain fitting is not required by local codes.
Connect the air gap drain fitting to the cabinet drain connection. Drop plastic insert into the top of the air gap drain fitting before connecting. It may be neces­sary to cut off some of the air gap fitting depending on available space.
Connect the drain or air gap fitting to S or P Trap. Note: If the drain water pump accessory package is used, follow instructions included with the drain water pump package.
MOUNTING THE HUMIDIFIER
Mount the humidifier cabinet securely on a level and plumb surface near the ductwork. Allow 6” or more on each side for proper ventilation and a minimum of 16”from the bottom of th cabinet to the floor to allow space for the drain connection. The humidifier must never be mounted outside or where it may be exposed to freezing tempera­tures. Maximum operating weights for the humidifier are shown below.
TABLE 1
MAXIMUM OPERATING WEIGHT
MODEL WEIGHT (Pounds)
HBDA 85 HBEA 130
HBFA 175 HBGA 105 HBHA 185
HBJA 260
WATER SUPPLY CONNECTION Use ordinary tap water (20 to 120 psi) — DO NOT use hot
or deionized water. A 3/8” FPT fitting is provided at the
top of the humidifier for connection to tap water supply. A shut-off valve, not provided by Car nes, must be installed just ahead of this fitting.
DRAIN LINE CONNECTION
Drain Line Connection
Photo B
MODEL HBDA SHOWN
TYPE OF WALL
6 FASTENERS REQUIRED (Models HBDA, HBEA & HBFA) 8 FASTENERS REQUIRED (Models HBGA, HBHA, & HBJA)
Wood Studs or Solid Wood 1/4” Lag Screws Hollow Plaster 1/4” Molly Bolts or Toggle Bolts Sheet Metal 1/4” Thread Forming Screws Cement or Masonery 1/4” Lead Type Anchor and Bolts
FASTENER RECOMMENDATION
1.2.Steam distributor pipe must be mounted on a plumb
surface. When mounted on a plumb surface the stan­dard distributor pipe for Models HBDA, HBEA and HBFA pitches downward and is inclined upward for Models HBGA, HBHA and HBJA. This is required so the condensate which forms in the distributor pipe will drain to the return line and back to the unit.
Steam distributor pipe should be mounted in the duct to insure even distribution of steam across the center portion of the duct (Figure A). The condensate return line must always be kept on the bottom. A minimum clearance of 4” must be maintained between the duct and distributor pipe. The steam distributor pipes are designed with a steam outlet hole pattern which gives even distribution, y et k eeps steam a w a y from the sides of the duct.
The standard humidifier steam distributor pipe must never be installed v ertically. If air flows are vertical, the steam distributor pipe should be installed horizontally (Figure B).
The steam distributor pipes should be installed in the supply air stream, downstream of the fan (Figure C). When installed in packaged units (central station air handlers, multizone units, make-up air units, etc.) the distributor pipe should be mounted just downstream of the fan discharge in the primary air stream.
INSTALL STEAM DISTRIBUTOR PIPE
3.
4.
5.
6.
In multizone applications it is preferable to have a sep­arate humidifier serving each zone. However, steam can be introduced into the hot deck upstream of the zone dampers. In this case, good distribution of steam across the entire hot deck is very important.
It is preferable to locate the steam distributor pipes downstream from any obstructions in the ductwork so that air can absorb moisture before it impinges on a surface and accumulates. There must be a minimum of three feet between the steam distributor pipes and any fans, coils , filters , z one dampers, elbo ws or outlets which may be installed downstream of the distributor pipe. Howe v er, in all cases, the steam distributor pipes should be located as far upstream from any such obstruction as possible.
An adhesive backed template is provided for each dis­tributor pipe. This provides the hole pattern for mount­ing each steam distributor pipe. Using the template(s), cut necessary holes in ductwork at desired location of distributor pipe.
Inset any distributor pipe into duct and secure tightly with four sheet metal screws, not provided by Car nes.
Special distributor pipes are shipped with specific instructions on how to mount them.
If the accessory fan distribution unit is to be used, fol­low the instructions included with the unit.
INSTALLATION
Figure A
Figure B Figure C
Loading...
+ 5 hidden pages