CaptiveAire L4006A Installation Manual

FOR SURFACE MOUNTING

GENERAL

FOR VERTICAL MOUNTING AND HORIZONTAL SENSOR INSERTION
WITH REMOTE BULB
L4006,7,8; L6006,7,8
Aquastat® Controllers
PRODUCT DATA

FEATURES

• L4006,7 and 8 provide spst switching for high or low limit or circulator control.
• L4006G includes two spst switches that provide high limit and circulator control.
• L4006,7; L6006,7 models are available for insertion in vertical or horizontal immersion well, vertical or horizontal direct immersion, and surface mounting.
• L4008, L6008 include remote bulb for mounting controller at a location away from the sensing element.
• Totally enclosed Micro Switchª snap-acting switches operate on temperature rise to set point.
• Models calibrated for high limit use are also suitable for low limit control if a separate high limit controller is used.
• Visible control point scale and external adjustment screw permit easy setting.
• Remote bulb models may be used to sense air temperature in ducts and in outside air sensing applications.
Aquastat® Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
General ............................................................................. 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 8
Operation .......................................................................... 15
Adjustments ...................................................................... 16
Checkout .......................................................................... 17
Material Safety Data Sheet .............................................. 18
60- 2104- 9
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifica­tions. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

SUPER TRADELINE®/TRADELINE® MODELS

SUPER TRADELlNE controls offer features not available on TRADELlNE or standard models, and are designed to replace a wide range of Honeywell and competitive controls.
TRADELINE models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. Specifications of SUPER TRADELINE and TRADELINE controls are the same as those of standard models except as noted below.
SUPER TRADELINE Model: L6006A Aquastat Controller.
SUPER TRADELINE Features:
SUPER TRADELINE package with cross reference label and
special instructions. Factory-set stop at 240°F (116°C). Vertical or horizontal mount. Tube of heat-conductive compound. Insulation: 1-1/2 to 3 in. (38 to 76 mm).
TRADELINE Models: L4006A,B,E; L4008E; L6006C;
L6008A Aquastat Controllers.
TRADELINE Features Available:
TRADELINE package with cross reference label and special
instructions. Some Tradeline models include well. Factory-set stops at 180°F, 240°F, or 250°F (82°C, 116°C,
or 121°C). Vertical or horizontal mount. Tube of heat-conductive compound. Insulation depths of 1-1/2 or 3 in. (38 or 76 mm).
NOTE: The following specifications are standard. Variances,
Electrical Ratings (A):
Models with 2°F (1°C) fixed differential:
Full Load 2.6 1.3
Locked Rotor 15.6 7.8
Models with 5°F (3°C) fixed differential or 5°F to 30°F (3°C to 17°C) adjustable differential:
Full Load 8.0 5.1 4.2
Locked Rotor 48.0 30.6 25.2
Millivoltage 0.25 at 0.25 to 12 Vdc
a
L6008G only.
Switching:
L4006, L4007, L4008: Spst. L6006, L6007, L6008: Spdt (breaks R-B and makes R-W on
available as options, are listed in Tables 1 and 2.
120 Vac 240 Vac
110/120 Vac 200/240 Vac 277 Vac
temperature rise at setpoint).
a
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2104—9 2
Pressure Rating:
7
5 (
9)
S E C
N
T
T
3
Capillary Bulb (Direct Immersion): 200 psi (1379 kPa). Immersion Well: 255 psi (1758 kPa).
Sensing Bulb Material: Copper.
Sensing Bulb Fill: Liquid—toluene or silicone oil.
Sensing Bulb Dimensions: 2-7/8 in. (73 mm) long,
3/8 in. (10 mm) diameter.
Wiring: Screw terminals.
Maximum Ambient Temperature: 150°F (66°C).
Approvals:
Underwriters Laboratories Inc: Remote bulb devices and well-mounted devices shipped
without well are component recognized: File No. MP466, Guide No. MBPR2.
L4006A shipped with well, L4006G, L4007A,B; L6006C for
surface mounting, L6006B for direct immersion mounting,
and L6007A are listed: File No. MP466, Guide No. MBPR. L6008G is listed: File No. E4436, Guide No. XAPX. Canadian Standards Association: File No. LR1620,
Guide No. 400-E-O.
ANSI Miswiring: Models with 1/4 in. tab terminal meet ANSI
Appliance Miswiring Standard.
Mounting:
Horizontal and vertical models mount directly to an immersion
well installed in a boiler fitting. L4006H and L6006C contain
bracket and clamp for surface mounting on pipe or
tank. Remote bulb models have three mounting holes
in rear of case for screw mounting to a vertical surface.
The L6006B direct immersion model also mounts directly
to a boiler fitting.
Finish: Gray.
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
1 (25)
5/16
(8)
2 (51)
-5/8
136)
1-7/8
(48)
KNOCKOUT FOR 3/4 (19) CONDUIT ON VERTICAL INSERTION MODELS ONLY
ELEMENT FOR HORIZONTAL IMMERSION
KNOCKOUT FOR 3/4 (19 ) CONDUIT ON ALL MODELS. SIMILAR KNOCKOUT ON BOTTOM FOR HORIZONTAL INSERTION AND REMOTE BULB MODELS.
3/4
(19)
3/16
(5)
RESET BUTTON (L4006E,
L4008E
ONLY)
ELEMENT FOR VERTICAL IMMERSION
2-1/8 (54)
11/16
(18)
Fig. 1. Approximate case installation dimensions
in in. (mm) for direct insertion models.
ALTERNATE POSITION OF SENSING ELEMEN CAPILLARY
M895
3/4 (1
Dimensions:
Installation: See Fig. 1, 2, and 3. Immersion Well: See Fig. 4. Boiler Fitting and Bulb: See Fig. 5.
Accessories and Parts:
137536A Scale Lock Assembly: Includes one 137536-767
Scale Lock and one 80844C-767 Screw, No. 3-48 x 3/16.
Q615A1004 Weatherproof Enclosure (for remote bulb devices
only). 107408 Heat-Conductive Compound (4-oz. can). 104488 Spring Clip (stainless steel). 124904 Well Adapter.
4-3/16
(106)
13/64 (5) (3)
MOUNTING HOLE FOR 3/16 IN. (5 MM) SCREW (3)
Immersion Well Assemblies and Compression Fittings:
3/8 (10)
ENSING LEMENT APILLARY
15/16
(24)
1-1/4
(32)
ALTERNATE POSITIO OF SENSING ELEMEN CAPILLARY
M882
See form 68-0040, Wells and Fittings for Temperature
Controllers, for list and ordering information.
Fig. 2. Approximate installation dimensions
in in. (mm) for remote bulb models. Other
dimensions are the same as Fig. 1.
3 60-2104—9
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
/8
)
9
9
2 (51)
2-3/4 (70)
7/8 IN. (22 MM) STANDARD KNOCKOUT (2)
C
L
2 (51)
1
(25)
5-5 (136
M8958
1/2 — 14 IN. NPT
7/16 (11)
1-1/2 (38)
3 (76)
M878
Fig. 4. Approximate immersion well dimensions in in.
(mm) for all models except L4006C and L6006B.
1/2 OR 3/4 — 14 IN. NPT
3/8
(10)
1-5/16 (33)
3 (76)
M879
Fig. 5. Approximate boiler fitting and bulb dimensions
in in. (mm) for L4006C and L6006B.
Fig. 3. Approximate installation dimensions
in in. (mm) for surface mount models.
60-2104—9 4
Standard Models:
L
Table 1. L4006, L4007, L4008 Controller (Spst Switching) Specifications.
Range
Model Application
L4006A High or low
limit
°F (°C)
40° to 180° (4° to 82°) or 100° to 240° (38° to 116°)
L4006B Circulator 100° to 240°F
(38° to 116°C)L
L4006C High or low
limit
b
L4006E
High limit 130° to 290°F
L4006G High limit and
circulator
65° to 200°F (18° to 93°C)
(54° to 141°C)
100° to 200°F (38° to 93°C)
control
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Midscale
Differential
°F (°C) Insertion
2° or 5° fixed
Horizontal Breaks — TRADELINE models
a
(1° or 3°) or 5° to 30° adjustable (3° to 17°)
5°F (3°C) fixed
Horizontal Makes — TRADELINE model or 5° to 30°F (3° to 17°C) adjustable
3-1/2°F (2°C) fixed
Horizontal
direct
immersion
Manual reset Horizontal or
vertical
10°F (6°C)
Horizontal Two switches fixed
Switching On
Temperature
Rise Available Options
available.
— NPT brass spud 1/2 or
3/4 in.
— Special capillary
assembly.
— Insertion 3-3/8 or 5 in.
(86 or 127 mm) — Celsius scale markings. — Factory-set stops at
160°, 180°, 185°, 200°,
220°, or 230°F (71°,
82°, 85°, 93°, 104°, or
110 °C). — Insulation depths of
1-1/2, 3 or 4 in. (38, 76,
or 102 mm). — Screw and mounting
brackets. — Plastic tubing over well. — Modified dial with stop. — Special cover and
knobs. — With ground screw.
available. — Insulation depth 1-1/2
or 3 in. (38 or 76 mm). — NPT brass spud 3/4 in. — Screw in front of case
on dial suitable for
Powerpile® control. — Factory-set stop at
240°F (116°C).
Breaks — TRADELINE model
available. — Less cover. — Capillary 10 in. (254
mm). — NPT brass spud 3/4 in.
Breaks — TRADELINE model
availiable. — Insulation depth 1-1/2
or 3 in. (38 or 76 mm). — NPT brass spud 1/2 in. — Factory-set stop at
250°F (121°C). — Capillary 8 in. (203
mm).
— External adjustment
break simultaneously
knob. — Insulation depth 4 in.
(102 mm). — Factory-set stop at
160°F (71°C). — Celsius scale markings. — Without well.
5 60-2104—9
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Table 1. L4006, L4007, L4008 Controller (Spst Switching) Specifications.
Switching On
Temperature
a
Rise Available Options
Breaks — Insulation depth 1-1/2
or 3 in. (38 or 76 mm).
Model Application
L4007A High or low
limit
Range °F (°C)
100° to 240°F (38° to 116°C)
Midscale
Differential
°F (°C) Insertion
2° or 5°F (1° or 3°C) fixed, 5° to
Horizontal or
vertical 30°F (3° to 17°C) adjustable
L4007B Circulator 100° to 240°F
(38° to 116°C)
5°F (3°C) fixed or 5° to 30°F
Vertical Makes — Celsius scale markings.
(3° to 17°C) adjustable
L4008A High or low
limit
100° to 240°F (38° to 116°C) or 130° to 270°F (54° to 132°C)
5°F (3°C) fixed, 5° to 30°F (3° to 17°C) adjustable
Remote bulb
direct
immersion
Breaks — Remote capillary 5-1/2
ft (1.7 m), 8-1/2 ft (2.6 m) or 10 ft (3.0 m).
— Factory-set scale stops
at 120°, 170°, or 200°F
(49°, 77°, or 93°C) — Celsius scale markings. — Front cover screw.
L4008B Circulator 100° to 240°F
(38° to 116°C)
5°F (3°C) fixed or 5° to 30°F (3° to 17°C)
Remote bulb direct immersion
Makes — Capillary 5-12 ft. (1.7
m).
adjustable
L4008E
High limit 40° to 80°F
(4° to 27°C) or 130° to 270°F (54° to 132°C)
Manual reset Remote bulb Breaks — Factory-set scale stops
at 140°, 200°, or 250°F
(60°, 93°, or 121°C). — Capillary 5-1/2 ft. or 20
b
ft. (1.7m or 6.1 m).
a
Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. NPT and insulation depth.
b
Manual reset (trip-free) switch breaks circuit and locks out when controlled medium reaches setpoint. Controlled temperature
must drop 20°F (11°C) below setpoint before contacts can be manually reset.
60-2104—9 6