WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury, or loss of life. For assistance or additional information, consult a qualied installer, service agency or the
gas supplier. This boiler requires a special venting system. Read these instructions carefully before installing.
103022-04 - 8/13
Price - $5.00
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction
shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The City of New York requires a Licensed Master Plumber supervise the installation of this product.
The Massachusetts Board of Plumbers and Gas Fitters has approved the Apex™ Series boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pl_products/pb_pre_form.asp for the latest Approval
Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels,
or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death, serious
injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death, serious injury
or substantial property damage.
Indicates a potentially hazardous situation which,
if not avoided, may result in moderate or minor
injury or property damage.
Indicates special instructions on installation,
operation, or maintenance which are important
but not related to personal injury hazards.
CAUTION
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance.
If you smell gas vapors, NO NOT try to operate any appliance - DO NOT touch any electrical switch or use
any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the gas
supplier’s instructions or if the supplier is unavailable, contact the re department.
2
Special Installation Requirements for Massachusetts
A. For all sidewall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes and where the sidewall exhaust vent termination is less than seven (7) feet above grade, the
following requirements shall be satised:
1. If there is no carbon monoxide detector with an alarm already installed in compliance with the most current edition of
NFPA 720, NFPA 70 and the Massachusetts State Building Code in the residential unit served by the sidewall horizontally
vented gas fueled equipment, a battery operated carbon monoxide detector with an alarm shall be installed in compliance
with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code.
2. In addition to the above requirements, if there is not one already present, a carbon monoxide detector with an alarm
and a battery back-up shall be installed and located in accordance with the installation requirements supplied with the
detector on the oor level where the gas equipment is installed. The carbon monoxide detector with an alarm shall
comply with 527 CMR, ANSI/UL 2034 Standards or CSA 6.19 and the most current edition of NFPA 720. In the event
that the requirements of this subdivision can not be met at the time of the completion of the installation of the equipment,
the installer shall have a period of thirty (30) days to comply with this requirement; provided, however, that during
said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed in compliance
with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code. In the event that the
sidewall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the carbon monoxide detector
may be installed on the next adjacent habitable oor level. Such detector may be a battery operated carbon monoxide
detector with an alarm and shall be installed in compliance with the most current edition of NFPA 720, NFPA 70 and the
Massachusetts State Building Code.
3. A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. A nal inspection by the state or local gas inspector of the sidewall horizontally vented equipment shall not be performed
until proof is provided that the state or local electrical inspector having jurisdiction has granted a permit for installation of
carbon monoxide detectors and alarms as required above.
B. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA
54 as adopted by the Board; and
2. Product Approved sidewall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
C. When the manufacturer of Product Approved sidewall horizontally vented gas equipment provides a venting system design
or venting system components with the equipment, the instructions for installation of the equipment and the venting system
shall include:
1. A complete parts list for the venting system design or venting system; and
2. Detailed instructions for the installation of the venting system design or the venting system components.
D. When the manufacturer of a Product Approved sidewall horizontally vented gas fueled equipment does not provide the parts
for venting ue gases, but identies “special venting systems”, the following shall be satised:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
E. A copy of all installation instructions for all Product Approved sidewall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.
3
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Read and understand the entire manual before attempting installation, start-up
operation, or service. Installation and service must be performed only by an experienced, skilled, and
knowledgeable installer or service agency
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season
and should be inspected periodically throughout the heating season for any obstructions. A clean and
unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life
to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on left side
of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start
without service. If damage due to frozen pipes is a possibility, the heating system should not be left
unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating
system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the
temperature and pressure of the boiler. This boiler contains components which become very hot when
the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals,
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause
death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions, including all those contained in component manufacturers manuals which are provided with the
boiler before installing, starting up, operating, maintaining or servicing.
All cover plates, enclosures and guards must be in place at all times.
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility
of the installing contractor to see that all controls are correctly installed and are operating properly when the
installation is complete.
4
TABLE OF CONTENTS
I.Product Description, Specications and Dimensional Data......................6
I. Product Description, Specications and Dimensional Data
Apex™ Series boilers are condensing high efciency
gas-red direct vent hot water boilers designed for use
in forced hot water space or space heating with indirect
domestic hot water heating systems, where supply water
temperature does not exceed 210°F. These boilers have
special coil type stainless steel heat exchangers, constructed,
tested and stamped per Section IV ‘Heating Boilers’ of
Table 1: Dimensional Data (See Figures 1A, 1B and 1C)
Dimension
APX399APX500APX800
A - Inch
(mm)
B - Inch
(mm)
C - Inch
(mm)
D - Inch
(mm)
E - Inch
(mm)
Gas Inlet F
(FPT)
Return G1-1/2” (FPT)2” (MPT)
28-7/8
(734)
6-3/16
(157)
13-1/16
(332)
23-3/4
(602)
15-13/16
(402)
3/4”3/4”1
ASME Boiler and Pressure Vessel Code, which provide a
maximum heat transfer and simultaneous protection against
ue gas product corrosion. These boilers are not designed
for use in gravity hot water space heating systems or
systems containing signicant amount of dissolved oxygen
(swimming pool water heating, direct domestic hot water
heating, etc.).
Boiler Model
44-7/8
(1140)
22-1/8
(562)
29
(737)
39-11/16
(1008)
29-3/8
(752)
54-9/16
(1384)
28-3/8
(724)
34-1/4
(876)
48-1/16
(1226)
33-13/16
(864)
Supply H1-1/2” (FPT)2” (MPT)
Condensate Drain JFactory Provided Socket End Compression Pipe Joining Clamp for 3/4” Schedule 40 PVC Pipe
Boiler Two-Pipe
CPVC/PVC Vent Connector
(Figures 1A, 1B and 1C) - Inch
Approx. Shipping Weight (LBS)304350430
4 x 46 x 6
6
I. Product Description, Specications and Dimensional Data (continued)
Figure 1A: Apex™ - Model APX399
7
I. Product Description, Specications and Dimensional Data (continued)
8
Figure 1B: Apex™ - Model APX500
I. Product Description, Specications and Dimensional Data (continued)
Figure 1C: Apex™ - Model APX800
9
I. Product Description, Specications and Dimensional Data (continued)
Table 2A: Rating Data - Models APX399, APX500 and APX800 (0 to 5000 Feet Elevation Above Sea Level)
Apex Series Gas-Fired Boilers
Model
Number
APX3998039937532694.194.53.441.8
APX50010050047541395.095.04.250.8
APX80016080076066195.093.05.065.3
Notes: * Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI
Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from
Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800)
Maximum Allowable Temperature, Water - 210°F
APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be eld adjusted for LP
gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
Input (MBH)
Min.Max.
* Output
(MBH)
Net AHRI
Ratings Water
(MBH)
Thermal
Efciency
(%)
Combustion
Efciency (%)
Boiler Water
Volume (Gal.)
Heat Transfer
Area
(Sq. Ft.)
Table 2B: Rating Data - Models APX399, APX500 and APX800 (5001 to 10000 Feet Elevation Above Sea Level)
Apex Series Gas-Fired Boilers
Model
Number
Input (MBH)
Min.Max.
* Output
(MBH)
Net AHRI
Ratings
Water (MBH)
Thermal
Efciency
(%)
Combustion
Efciency (%)
Boiler Water
Volume
(Gal.)
Heat Transfer
Area
(Sq. Ft.)
APX3998039937532894.194.53.441.8
APX50016750047541395.095.04.250.8
APX80026780076066195.093.05.065.3
Notes: * Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI
Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from
Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800)
Maximum Allowable Temperature, Water - 210°F
APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be eld adjusted for LP
gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
II. Unpacking Boiler
D. Remove boiler from cardboard positioning sleeve on
CAUTION
Do not drop boiler.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container.
shipping skid.
WARNING
Installation of this boiler should be undertaken
only by trained and skilled personnel from a
qualied service agency.
E. Move boiler to its permanent location.
10
III. Pre-Installation and Boiler Mounting
WARNING
If you do not follow these instructions exactly,
a re or explosion may result causing property
damage or personal injury.
NOTICE
Due to the low water content of the boiler, missizing of the boiler with regard to the heating
system load will result in excessive boiler cycling
and accelerated component failure. Burnham
Commercial DOES NOT warrant failures caused
by mis-sized boiler applications. DO NOT
oversize the boiler to the system. Multiple boiler
installations greatly reduce the likelihood of
boiler oversizing.
A.Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such
requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/
CSA B149.1 Installation Codes.
B. Boiler is certied for installation on combustible
ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local re
ordinance. Refer to Figure 2 for minimum listed
clearances from combustible material. Recommended
service clearance is 24 inches from left side, front, top
and rear of the boiler. Recommended front clearance
may be reduced to the combustible material clearance
providing:
1. Access to boiler front is provided through a door or
removable front access panel.
2. Access is provided to the condensate trap located
underneath the heat exchanger.
D. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap,
control replacement, etc.).
E. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes,
or: USA - National Fuel Gas Code, NFPA 54/ANSI
Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas and Propane Installation Code,
CAN/CSA-B149.1, Venting Systems and Air Supply for
Appliances.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion.
F. The boiler should be located so as to minimize the
length of the vent system. The PVC combustion
air piping, or the optional concentric vent piping,
containing integral combustion air inlet piping, must
terminate where outdoor air is available for combustion
and away from areas that may contaminate combustion
air. In particular, avoid areas near chemical products
containing chlorines, chlorouorocarbons, paint
removers, cleaning solvents and detergents. Avoid
areas containing saw dust, loose insulation bers, dry
wall dust etc.
CAUTION
Avoid operating this boiler in an environment
where sawdust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under
these conditions, the burner interior and ports
must be cleaned and inspected daily to insure
proper operation.
G. General.
1. Apex boilers are intended for installations in an
area with a oor drain, or, in a suitable drain pan to
prevent any leaks or relief valve discharge to cause
property damage
2. Apex boilers are not intended to support external
piping and venting. All external piping and venting
must be supported independently of the boiler.
3. Apex boilers must be installed level to prevent
condensate from backing up inside the boiler.
4. Boiler Installation:
a. For basement installation provide a solid level
base such as concrete, where oor is not level,
or, water may be encountered on the oor
around boiler. Floor must be able to support
weight of boiler, water and all additional system
components.
b. Boiler must be level to prevent condensate from
backing up inside the boiler.
c. Provide adequate space for condensate piping or
a condensate pump if required.
11
III. Pre-Installation and Boiler Mounting G. General (continued)
Boiler Clearances to Combustible (and NonCombustible) Material:
APX399 and APX500 Boiler Models:
These boilers are approved for closet installation with
the following clearances – Top = 1”, Front = 1”, Left
Side = 10”, Right Side = 2”, Rear = *6”
APX800 Boiler Model:
This boiler is approved for alcove installation with the
following clearances – Top = 1”, Front = Open, Left
Side = 10”, Right Side = 2”, Rear = *6”
* Note:
When boiler is vented vertically, the minimum
clearance from the rear of the jacket is increased
to 18” with a short radius 90° elbow provided in
order to provide adequate space at boiler rear for
installation of vent and air intake piping and service
access
Approved Direct
Factory Standard
Two-Pipe CPVC/PVC Vent and PVC
Air Intake
Available Optional
Two-Pipe Rigid Polypropylene Vent
(or, Flexible Polypropylene Liner
for Vertical Venting only) and Rigid
Polypropylene or PVC Combustion
Air Intake
Available Optional
Two-Pipe Stainless Steel Vent and
Galvanized Steel or Air Intake
Available Optional
Concentric Inner Polypropylene Vent
and Outer Steel Air Intake
* Do not enclose PVC venting - use CPVC vent pipe in enclosed spaces, or to penetrate through
combustible or non-combustible walls
Vent System
Boiler Service Clearances – Applicable to all Boiler
Models:
Top = 24”, Front = 24”, Left Side = 24”, Right Side =
24”, Rear = 24”
The above Clearances are recommended for Service
Access but may be reduced to the Combustible Material
Clearances provided:
1. The boiler front is accessible thru a door
2. Access is provided to the condensate trap located on
the left side of boiler
3. Access is provided to thermal link located at the
boiler rear
Vent Pipe
Material
* CPVC/PVC
Pipe Rigid
Polypropylene
Vent (or,
Flexible
Polypropylene
Liner for
Vertical
Venting only)
Stainless
Steel
Polypropylene
Vent
Pipe
Direction
Vertical or
Horizontal
Enclosure
Unenclosed at
all Sides
Vent Pipe
Nominal
Diameter
4” or 6”1”
80 mm
10 mm
(110 mm)
150 mm
(160 mm)
4” or 6”1”
100/150 mm
(110/160 mm)
Minimum
Clearance to
Combustible
Material
1”
0”
12
Figure 2: Clearances To Combustible and Non-combustible Material
III. Pre-Installation and Boiler Mounting G. General (continued)
H. Boiler Stacking
1. For installations with unusually high space heating
and/or domestic hot water heating loads, where
employing two (2) Apex (APX) boilers will offer the
benets of greater operational efciency, oor space
savings and boiler redundancy, the Apex (APX)
boilers may be installed stacked one on the top of
the other. Refer to Table 3 “Apex (APX) Boiler
Model Stacking Combinations” for details.
Table 3: Apex (APX) Boiler Model Stacking
Combinations
Bottom
Boiler Model
APX399
APX500APX399 or APX500
APX800APX399, APX500 or APX800
2. To eld assemble individual Apex (APX) boilers
into a stackable conguration, use the steps below:
a. Position the bottom boiler rst. Refer to Sections
II “Unpacking Boiler” and III “Pre-Installation
& Boiler Mounting” of the manual for details.
Always position higher input boiler model as
bottom boiler.
b. Each Apex (APX) boiler is factory packaged
with two (2) Stacking Boiler Attachment
Brackets (P/N 101679-01) and the bracket
mounting hardware [six (6) self-drilling hex
washer head plated #8 x ½” long screws, P/N
80860743]. Locate and remove the brackets and
the hardware. The Stacking Boiler Attachments
Bracket has three 7/32” diameter holes punched
in a triangular pattern. See Figure 3 “Stacking
Boiler Attachment Bracket Placement”.
c. Apex (APX) boiler left and right side panels
have a series of dimples at panel top and bottom.
These dimples are positioning dimples for
Stacking Boiler Attachment Bracket mounting
screws. Side panel bottom positioning dimples
are evenly spaced from boiler front and back,
while side panel top positioning dimples follow
specic pattern to compensate for Apex (APX)
boiler model variable depth.
d. Position the upper boiler on the top of the bottom
boiler and align boiler front doors and sides ush
with each other.
• Place rst Stacking Boiler Attachment
Bracket onto the upper boiler left side panel,
at the panel lower left corner and align
bracket two upper holes with corresponding
side panel lower dimples.
• The remaining lower bracket hole must align
with a matching bottom boiler left side panel
top positioning dimple.
Top Boiler Model
APX399
• Once bracket holes and side panel dimple
alignment is veried, attach the bracket to
top and bottom boiler left side panels with
the mounting screws.
e. Repeat above procedure to install second
Stacking Boiler Attachment Bracket and secure
the stacked boiler right side panels together at
the front right corner.
f. Install the third Stacking Boiler Attachment
Bracket to secure top and bottom boiler left side
panels at the rear left corner. Align the bracket
holes with corresponding positioning dimples in
the top boiler and bottom boiler left side panels,
then secure bracket with the screws.
g. Repeat above procedure to install the forth
Stacking Boiler Attachment Bracket to secure
stacked boiler right side panels at the rear right
corner.
3. When installing stackable boiler combinations
observe the following guidelines:
a. Venting - Top and bottom boilers must have their
individual vent piping and vent terminals.
WARNING
No common manifolded venting is permitted.
For side-wall venting individual model vent
terminals must terminate not closer than 12
inches horizontally and three (3) feet vertically
from each other in order to prevent combustion
air contamination. For vertical through the roof
venting, individual vertical vent terminals, if
level with each other, must be spaced no closer
than 12 inches horizontally. If vertical terminals
cannot end in one plane, they must be spaced no
closer than three (3) feet horizontally.
Chimney chase concentric venting is permitted
for modules, when stackable, providing
concentric vertical (roof) vent terminals, if level
with each other, are spaced no closer then 12
inches horizontally.
If vertical vent terminals cannot end in one
plane, they must be spaced no closer then three
(3) feet horizontally.
Follow instructions in Section IV “Venting”
of the manual for specics of individual boiler
vent termination. Follow instructions in Section
V “Condensate Disposal” for each individual
boiler ue gas condensate line construction and
condensate disposal. Terminating individual
boiler condensate lines into common pipe prior
to drain disposal is permissible, providing
common pipe has sufcient ow capacity
to handle combined condensate volume of
stackable combination.
13
III. Pre-Installation and Boiler Mounting G. General (continued)
b. Gas Piping - Follow instructions in Section
VII “Gas Piping” of the manual for sizing
and installation of an individual boiler. When
common gas piping is sized, insure it will have
adequate capacity for combined input (CFH
gas ow) of the selected stackable boiler
combination.
c. Water Piping and Trim - Follow instructions
in Section VI “Water Piping and Trim” of the
manual for system piping and boiler secondary
piping selection/sizing based on combined
heating capacity and/or gross output of
the selected stackable boiler combination.
Follow instructions of Section VI “Water
Piping and Trim” for each individual boiler trim
installation.
d. Electrical - Follow instructions in Section VIII
“Electrical” of the manual to wire individual
boilers.
Failure to vent this boiler in accordance with these instructions could cause products of combustion to
enter the building resulting in severe property damage, personal injury or death.
Do not interchange vent systems or materials unless otherwise specied.
The use of thermal insulation covering vent pipe and ttings is prohibited.
Do not use a barometric damper, draft hood or vent damper with this boiler.
When using the CPVC/PVC vent option, the use of CPVC is required when venting in vertical or horizontal
chase ways, closets and through wall penetrations.
The CPVC vent materials supplied with this boiler do not comply with B149.1.S1-07 and are not ap-
proved for use in Canadian jurisdictions that require vent systems be listed to ULC S636-2008. In
these jurisdictions, vent this boiler using either stainless steel Special Gas vent or a listed ULC S636
Class IIB venting system.
Do not locate vent termination where exposed to prevailing winds. Moisture and ice may form on
surface around vent termination. To prevent deterioration, surface must be in good repair (sealed,
painted, etc.).
Do not locate air intake vent termination where chlorines, chlorouorocarbons (CFC’s), petroleum
distillates, detergents, volatile vapors or other chemicals are present. Severe boiler corrosion and
failure will result.
The use of cellular core PVC (ASTM F891), cellular core CPVC or Radel (polyphenolsulfone) is prohibited.
Do not locate vent termination under a deck.
Do not reduce specied diameters of vent and combustion air piping.
When installing vent pipe through chimney, as a chase, no other appliance can be vented into the
chimney.
Do not allow low spots in the vent where condensate may pool.
A. General Guidelines
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI
Z221.3 or CAN/CSA B149.1 Installation Code for Canada, or, applicable provisions of local building
codes. Contact local building or re ofcials about
restrictions and installation inspection in your area.
2. The Apex™ is designed to be installed as a
Direct Vent (sealed combustion) boiler. The air
for combustion is supplied directly to the burner
enclosure from outdoors and ue gases are vented
directly outdoors (through wall or roof).
3. The following combustion air/vent system options
are approved for use with the Apex™ boilers (refer
to Table 4):
a. Two-PipeCPVC/PVC Vent/Combustion Air
System - separate CPVC/PVC pipe serves to
expel products of combustion and separate PVC
pipe delivers fresh outdoor combustion air.
Refer to Part B for specic details.
b. Two-Pipe Polypropylene Vent/Combustion Air
System - separate rigid or exible polypropylene
pipe serves to expel products of combustion and
separate rigid polypropylene pipe or PVC pipe
delivers fresh outdoor combustion air. Refer to
part C for specic details.
c. Two-Pipe Stainless Steel Vent/Combustion Air
System - separate stainless steel pipe serves to
expel products of combustion. Separate PVC or
galvanized pipe delivers fresh outdoor air. Refer
to Part D for specic details.
d. Concentric Inner Polypropylene Vent
and Outer Steel Combustion Air System
- the assembly consists of inner re resistant
polypropylene vent pipe and outer steel pipe
casing. The inner pipe serves as conduit to
expel products of combustion, while outdoor
fresh combustion air is drawn through the space
between the inner and outer pipes. Refer to Part
E for specic details.
4. Horizontal vent pipe must maintain a 1/4" per foot
slope down towards the boiler.
5. Horizontal combustion air pipe must maintain a
minimum ¼" per foot slope down towards terminal,
when possible. If not, slope toward boiler.
6. Do not install venting system components on
the exterior of the building except as specically
required by these instructions (refer to Figure 4):
a. Vent terminals must be at least 1 foot from door,
window, or gravity inlet into the building.
b. Maintain the correct clearance and orientation
between the vent and air intake terminals.
15
IV. Venting A. General Guidelines (continued)
Table 4: Vent/Combustion Air System Options
Approved Direct
Vent System
Factory Standard
Two-Pipe,
CPVC/PVC Vent and
PVC Air Intake
Available Optional
Two-Pipe, Rigid
Polypropylene
Vent (or Flexible
Polypropylene Liner
for Vertical venting
only) and Rigid
Polypropylene or PVC
Pipe Air Intake
Available Optional
Two-Pipe,
Stainless Steel Vent
and PVC/Galvanized
Steel Air Intake
Available Optional
Concentric, Inner
Polypropylene Vent and
Outer Steel Air Intake
Vent
Material
CPVC/PVC
Rigid
Polypropylene
(or Flexible
Polypropylene
Liner for vertical
Venting only)
Stainless Steel
Polypropylene
OrientationTerminationDescriptionFigures
Standard
(thru sidewall)
Horizontal
Optional
Snorkel
(thru sidewall)
Optional
Vertical
Horizontal
Optional
Vertical
Horizontal
VerticalVertical (thru roof)
Horizontal
Vertical
Vertical
(thru roof)
Standard
(thru sidewall)
Optional Snorkel
(thru sidewall)
Vertical
(thru roof or
chimney/chase)
Standard
(thru sidewall)
Optional Snorkel
(thru sidewall)
Horizontal
(Wall) Terminal
Vertical (Roof)
Terminal
The system includes separate CPVC
vent pipe and PVC air intake pipe
terminating thru sidewall with individual
penetrations for the vent and air intake
piping and separate terminals (tees).
Same as above but separate snorkel
type terminals.
The system includes separate CPVC
vent pipe and PVC air intake pipe
terminating thru roof with individual
penetrations for the vent and air intake
piping and separate vertical terminals.
The system includes separate Rigid
Polypropylene vent pipe and Rigid
Polypropylene or PVC air intake pipe
terminating thru sidewall with individual
penetrations for the vent and air intake
piping and separate terminals (tees).
Same as above but separate snorkel
type terminals.
The system includes separate Flexible
Polypropylene vent liner and Rigid
Polypropylene vent pipe combination
for venting and Rigid Polypropylene or
PVC air intake pipe terminating thru roof
with individual penetrations for the vent
and air intake and individual vent /air
terminals.
The system includes separate stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating thru sidewall
with individual penetrations for the
vent and air intake piping and separate
terminals
Same as above but separate snorkel
type terminals.
The system includes separate stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating thru roof with
individual penetrations for the vent and
air intake piping and separate terminals.
Concentric vent/air pipe terminates thru
sidewall.
Concentric vent/air pipe terminates thru
roof.
Component
Table
4 thru 9A,
9B, 10
4 thru 7,
10, 11
4 thru 6, 10,
12, 13
4 thru 9A,
9B, 10
4 thru 7,
10, 11
12 thru 169, 10
9A, 9B,
16, 17
11, 16, 17
12, 13, 17
18 thru 25
18 thru 21,
26 thru 31
9, 10
9, 10
11A, 11BD.
12, 13E.
5A
5B
5C
Part
B.
C.
16
i. The centerlines between the vent and air
intake terminals must be spaced a minimum
of 12” apart. More than 12” spacing is
recommended.
ii. If possible, locate air intake and vent
terminations on the same wall to prevent
nuisance shutdowns. However, boiler
may be installed with vertical venting and
sidewall combustion air inlet or vice versa
where installation conditions do not allow
for alternate arrangement.
iii. The vent and air intake terminations may
be at varying heights when installed on
the same wall, but the height of the vent
termination should always be higher than
the air intake termination and within the
specied limit as shown in Figure 9B.
c. The bottom of the vent and air intake terminal
must be at least 12" (18" in Canada) above the
normal snow line. In no case should they be less
than 12" above grade level.
d. The bottom of the vent terminal must be at least
7 feet above a public walkway.
e. Do not install the vent terminal directly over
windows or doors.
f. The bottom of the vent terminal must be at least
3 feet above any forced air inlet located within
10 feet.
g. A clearance of at least 4 feet horizontally must
be maintained between the vent terminal and
gas meters, electric meters, regulators, and relief
equipment. Do not install vent terminal over this
equipment.
IV. Venting A. General Guidelines (continued)
Figure 4: Location of Vent Terminal Relative to Windows, Doors, Grades,
Overhangs, Meters and Forced Air Inlets
(Concentric Terminal Shown - Two-Pipe System Vent Terminal to be installed in same location -
Two-Pipe System Air Intake Terminal Not Shown)
h. Do not locate the vent terminal under decks or
similar structures.
i. Minimum twelve (12) inches vertically from any
roof overhang twelve (12) inches or less wide.
If a roof overhang width exceeds twelve (12)
inches the terminal vertical clearance must be
increased to avoid ue vapor condensation.
j. Top of vent terminal must be at least 5 feet
below eaves, softs, or overhangs. Maximum
depth of overhang is 3 ft.
k. If window and/or air inlet is within four (4) feet
of an inside corner, then terminal must be at least
six (6) feet from adjoining wall of inside corner.
l. Concentric - Minimum twelve (12) inches
horizontally from a building corner.
m. Under certain conditions, water in the ue gas
may condense, and possibly freeze, on objects
around the terminal including on the structure
itself. If these objects are subject to damage by
ue gas condensate, they should be moved or
protected.
n. If possible, install the vent and air intake
terminals on a wall away from the prevailing
Installing multiple individual module (boiler) vent
terminations too close together may result in cross
contamination and combustion product water
vapor condensation on building surfaces, where
vent termination are placed, and subsequent
frost damage. To avoid/minimize frost damage,
extend the distance from building surfaces to
vent termination end and increase the horizontal
distance between adjacent vent terminations.
wind. Reliable operation of this boiler cannot be
guaranteed if the terminal is subjected to winds
in excess of 40 mph.
o. Air intake terminal must not terminate in areas
that might contain combustion air contaminates,
such as near swimming pools.
p. For sidewall venting the minimum horizontal
distance between any adjacent individual module
(boiler) vent terminations is twelve (12) inches.
Increasing this distance is recommended to avoid
frost damage to building surfaces where vent
terminations are placed.
CAUTION
17
IV. Venting A. General Guidelines (continued)
q. The minimum horizontal distance between any
adjacent individual module (boiler) roof vent
terminations is one (1) foot.
7. Use noncombustible ¾" pipe strap to support
horizontal runs and maintain vent location and
slope while preventing sags in pipe. Do not restrict
thermal expansion or movement of vent system.
Maximum support spacing four (4) feet. Avoid low
spots where condensate may pool. Do not penetrate
any part of the vent system with fasteners.
8. Maintain minimum clearance to combustible
materials. See Figure 2 for details.
9. Enclose vent passing through occupied or
unoccupied spaces above boiler with the material
having a re resistance rating of at least equal to the
rating of adjoining oor or ceiling.
Note: For one or two family dwellings, re
resistance rating requirement may not need to be
met, but is recommended.
10. Multiple individual module vertical vent pipes may
be piped through a common conduit or chase so that
one roof penetration may be made.
B. CPVC/PVC Venting
WARNING
All CPVC vent components (supplied with boiler)
must be used for near-boiler vent piping before
transitioning to Schedule 40 PVC pipe (ASTM
2665) components for remainder of vent system.
WARNING
CPVC vent components must be used within
any interior space where air cannot circulate
freely, such as air inside a stud wall, and in
any boiler closet or chase way.
When using the CPVC/PVC vent options, the
use of CPVC is required when venting in vertical
or horizontal chase ways.
All condensate that forms in the vent must
be able to drain back to the boiler.
1. Components and Length Restrictions
a. See Table 5A for CPVC/PVC Vent & Air Intake
Components included with boiler, Table 5B for
CPVC/PVC Vent and Air Intake Components
(Installer Provided) required for Optional
Table 5A: CPVC/PVC Vent & Air Intake Components Included With Boiler
Quantity
Vent & Air Intake Components
4” Schedule 40 PVC Tee (Vent or Air Intake Terminals)102190-022N/A
6” Schedule 40 PVC 90° Elbow (Vent or Air Intake
Terminal)
4” Stainless Steel Rodent Screen102191-022N/A
6” Stainless Steel Rodent Screen102191-03N/A2
4” x 30” Schedule 40 CPVC Pipe102193-021N/A
6” x 30” Schedule 40 CPVC Pipe103267-01N/A1
4” Schedule 80 CPVC 90° Elbow 102192-021N/A
6” Schedule 80 CPVC 90° Elbow103268-01N/A1
4 oz. Bottle of Transition Cement102195-011
4 oz. Bottle of Primer102194-011
4" Vent/4" Combustion Air CPVC/PVC Connector102183-031N/A
6" Vent/6" Combustion Air CPVC/PVC Connector103270-01N/A1
4" Vent/4" Combustion Air CPVC/PVC Connector
Gasket
6" Vent/6" Combustion Air CPVC/PVC Connector
Gasket
Part
Number
103313-01N/A2
102185-021N/A
103248-01N/A1
APX399 and APX500
Standard Termination
Vent Kit
(P/N 102189-03)
includes
APX800
Standard Termination
Vent Kit
(P/N 103253-01)
includes
18
IV. Venting B. CPVC/PVC Venting (continued)
Table 5B: CPVC/PVC Vent & Air Intake Components (Installer Provided) required for Optional Horizontal
(Snorkel) Termination
Quantity
Vent Components
4" Schedule 40 PVC Pipe x up to 7 ft. max. vertical run
6" Schedule 40 PVC Pipe x up to 7 ft. max. vertical runN/A2
4" Schedule 40 PVC 90° Elbow4N/A
6" Schedule 40 PVC 90° ElbowN/A4
4" Schedule 40 PVC Pipe x ½ ft. min. horizontal run2N/A
6" Schedule 40 PVC Pipe x ¾ ft. min. horizontal runN/A2
Part
Number
N/A
Supplied by Others
Table 5C: CPVC/PVC Vent & Air Intake Components (Installer Provided) required for Optional Vertical
(Roof) Termination
Vent Components
4" Schedule 40 PVC Coupler
6" Schedule 40 PVC CouplerN/A1
4" Schedule 40 PVC 90° Elbow2N/A
6" Schedule 40 PVC 90° ElbowN/A2
4" Schedule 40 CPVC Pipe x ½ ft. min. horizontal run1N/A
6" Schedule 40 CPVC Pipe x ¾ ft. min. horizontal runN/A1
Supplied by Others
Part
Number
N/A
APX399 and APX500
Horizontal (Snorkel)
Termination
2N/A
APX399 and APX500
Vertical (Roof)
Termination
1N/A
APX800
Horizontal (Snorkel)
Termination
Quantity
APX800
Vertical (Roof)
Termination
Horizontal (Snorkel) Termination and Table 5C
for CPVC/PVC Vent and Air Intake Components
(Installer Provided) required for Optional
Vertical (Roof) Termination.
b. Vent length restrictions are based on equivalent
length of vent/combustion air pipe (total length
of straight pipe plus equivalent length of
ttings). Maximum vent/combustion air lengths
are listed in Table 8. Do not exceed maximum
vent/combustion air lengths. Table 6 lists
equivalent lengths for ttings. Do not include
vent/combustion air terminals in equivalent
feet calculations. See “Combustion Air/Vent,
Equivalent Length Work Sheet”.
c. The vent termination location is restricted as per
'General Guidelines', Paragraph A, 6.
(Refer to Figure 4).
2. System Assembly
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at
vent connector at boiler and work towards vent
termination.
b. Do not exceed maximum Vent/Combustion Air
length. Refer to Table 8.
c. Design the Vent System to allow 3/8" of thermal
expansion per 10 feet of CPVC/PVC pipe. Runs
of 20 feet or longer that are restrained at both
ends must use an offset or expansion loop. Refer
to Figure 5 and Table 7.
d. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining
and using the primer and the cement.
3. Field Installation of CPVC/PVC Two-Pipe
Vent System Connector
Refer to Figure 6 and Steps below:
a. Position the CPVC/PVC vent connector and
gasket onto boiler rear/bottom panel and insert
vent connector inner stainless steel vent pipe into
heat exchanger vent outlet.
b. Align vent connector plate and gasket clearance
holes with rear/bottom panel engagement holes;
than, secure the connector and gasket to the
panel with six mounting screws.
c. Apply supplied dielectric grease (grease pouch
attached to two-pipe vent connector) to gasket
inside vent section of two-pipe vent connector,
The grease will prevent gasket rupture when
inserting vent pipe and gasket deterioration due
to condensate exposure.
19
IV. Venting B. CPVC/PVC Venting (continued)
Table 6: Vent System and Combustion Air System Components Equivalent Length
vs. Component Nominal Diameter
Vent or Combustion Air System
Component Description
Equivalent Length (Ft.) for Vent or Combustion Air System Component
vs. Component Nominal Diameter (In.)
Component Nominal Diameter, In.4”6”
90° Elbow (Sch. 80 or Sch.40)1322
45° Elbow (Sch. 80 or Sch. 40)4.57.5
Sch. 40 CPVC Pipe x 30 In. Long2.5
Sch. 40 PVC Pipe x 1 Ft. Long1
Sch. 40 PVC Pipe x 2 Ft. Long2
Sch. 40 PVC Pipe x 3 Ft. Long3
Sch. 40 PVC Pipe x 4 Ft. Long4
Sch. 40 PVC Pipe x 5 Ft. Long5
L
LOOP LENGTH
4
(L)
CHANGE OF DIRECTION
(VERTICAL OR HORIZONTAL)
LONG RUN OF PIPE
L
OFFSET
L
2
KEY
RESTRAINT (RESTRICTS MOVEMENT)
HANGER (ALLOWS MOVEMENT)
Table 7: Expansion Loop Lengths
Nominal
Pipe
Dia. (In.)
4
6
Length of
Straight Run
(Ft.)
2060
3074
4085
5095
60104
2073
3090
40103
50116
60127
Loop Length
“L” (In.)
LOOP
(HORIZONTAL ONLY)
(TOP VIEW)
L
6"
MIN
L
5
6"
MIN
Figure 5: Expansion Loop and Offset
L
4
2 L
5
WARNING
Apply supplied dielectric grease to gasket inside vent section of two-pipe vent connector. Failure to apply the
grease could result in gasket rupture during vent pipe installation and gasket deterioration due to condensate
exposure.
20
IV. Venting B. CPVC/PVC Venting (continued)
Figure 6: Field Installation of CPVC/PVC Two-Pipe Vent System Connector
4. Near-Boiler Vent/Combustion Air Piping
Refer to Figure 7 and the following Steps:
APX399 and APX500 Boiler Models:
a. 4” x 4” Two-Pipe CPVC/PVC Vent System
Connector (P/N 102183-03), used on APX399
and APX500 boiler models, has factory installed
internal sealing gaskets at both vent and air
intake sections.
b. Install provided 4” Schedule 40 x 30” long
CPVC pipe into the connector vent section with
a slight twisting motion and secure by tightening
the metal strap.
c. All CPVC vent components supplied with
boiler inside vent carton (4” Schedule 40 x 30”
long CPVC pipe and 4” Schedule 80 CPVC
90° Elbow) must be used for near-boiler piping
before transitioning to Schedule 40 PVC (ASTM
2665) pipe components for reminder of vent
system. The CPVC 30” long straight pipe may be
cut to accommodate desired vent conguration
provided both pieces are used in conjunction
with CPVC 90° Elbow before any PVC
components are used. Ensure that the CPVC 90°
Elbow is the rst elbow used in the vent system
as it exits the boiler.
d. Insert 4” Schedule 40 PVC combustion air pipe
(installer provided) into the connector air intake
section with a slight twisting motion and secure
by tightening the metal strap.
Figure 7: Near-Boiler Vent/Combustion Air Piping
21
IV. Venting B. CPVC/PVC Venting (continued)
Table 8: Vent/Combustion Air Pipe Length – Two-Pipe Direct Vent System Options
CPVC/PVC
Polypropylene (PP) or Polypropylene (PP)/PVC
Stainless Steel/PVC or Galvanized Steel)
Boiler
Model
APX39930 In.100 Ft.30 In.100 Ft.
APX50030 In.100 Ft.30 In.100 Ft.
APX80030 In.200 Ft.30 In.200 Ft.
4” Combustion Air Pipe
(Equivalent Length)
Min.Max.Min.Max.Min.Max.Min.Max.
6” Combustion Air Pipe
(Equivalent Length)
4” Vent Pipe
(Equivalent Length)
6” Vent Pipe
(Equivalent Length)
Vent/Combustion Air Equivalent Length Calculation Work Sheet
Combustion AirVent
90° Elbow(s) PVC (Installer Supplied)90° Elbow(s) CPVC (Supplied with Boiler)
Nominal
Diameter,
In.
413411313
622612222
Nominal
Diameter,
In.
44.5413
67.5622
Nominal
Diameter,
In.
4144.5
6167.5
* Total Equivalent Length, Ft. (A+B+C) =30” (2.5 Ft.) Straight Pipe, CPVC (Supplied with Boiler)
* Note: Total Equivalent Length Calculated Value Cannot Exceed Max. Equivalent Length Values shown in Table 8.
Vent and Combustion Air Terminals Do Not Count Towards Total Equivalent Length.
with primer and secure with transition cement
(4-oz. bottles of primer and cement are
supplied with boiler inside vent carton). Follow
application instructions provided on primer and
cement bottles.
APX800 Boiler Model:
f. 6” x 6” Two-Pipe CPVC/PVC Vent System
Connector (P/N 102183-03), used on APX800
boiler model, does not have factory installed
internal sealing gaskets at both vent and air
intake sections and requires use of supplied red
RTV silicon sealant to seal vent and combustion
air pipes to the connector.
g. Apply a coating of the sealant, at least 1” wide,
onto provided 6” Schedule 40 x 30” long CPVC
pipe.
h. Insert the coated end of the CPVC pipe with a
slight twisting motion into the connector vent
section and secure by tightening the metal strap.
i. All CPVC vent components supplied with
boiler inside vent carton (6” Schedule 40 x 30”
long CPVC pipe and 6” Schedule 80 CPVC
90° Elbow) must be used for near-boiler piping
before transitioning to Schedule 40 PVC (ASTM
2665) pipe components for remainder of vent
system. The CPVC 30” long straight pipe may be
cut to accommodate desired vent conguration
provided both pieces are used in conjunction
with CPVC 90° Elbow before any PVC
components are used. Ensure that the CPVC 90°
Elbow is the rst elbow used in the vent system
as it exits the boiler.
Figure 8: Wall Penetration Clearances for PVC Vent Pipe
• PVC vent pipe must be installed in such
way as to permit adequate air circulation
around the outside of the pipe to prevent
internal wall temperature rising above
ANSI Z21.13 standard specied limit.
• Do not enclose PVC venting – use higher
temperature rated CPVC pipe in enclosed
spaces, or, to penetrate combustible or
non-combustible walls.
• PVC vent pipe may not be used
to penetrate combustible or noncombustible walls unless all following
three conditions are met simultaneously
(see Figure 8 “ Wall Penetration
Clearances for PVC Vent Pipe”):
- The wall penetration is at least 66
inches from the boiler as measured
along the vent
j. Apply a coating of the sealant, at least 1” wide,
onto 6” Schedule 40 PVC combustion air pipe
(installer provided).
k. Insert the coated end of the PVC pipe with a
slight twisting motion into the connector air
intake section and secure by tightening the metal
strap.
l. Clean all vent and combustion air pipe joints
with primer and secure with transition cement
(4-oz. bottles of primer and cement are
supplied with boiler inside vent carton). Follow
application instructions provided on primer and
cement bottles.
5. Horizontal Vent Termination
a. Standard Two-Pipe Termination
See Figures 8 through 11.
i. Vent Piping
Running PVC vent pipe inside Enclosures
and thru Walls:
Figure 9A: Direct Vent - Sidewall Terminations
23
IV. Venting B. CPVC/PVC Venting (continued)
Figure 9B: Direct Vent - Sidewall Terminations (Optional)
- The wall is 12” thick or less
- An air space of at least of that shown
in Figure 8 is maintained around
outside of the vent pipe to provide air
circulation
• If above three conditions cannot be
met simultaneously when penetrating
a combustible wall, use a single wall
thimble [Burnham Commercial part
numbers 102181-01 (4”) and 103419-01
(6”)].
• Thimble use is optional for non-
combustible wall.
• Insert thimble into cut opening from
outside. Secure thimble outside ange to
wall with nails or screws and seal ID and
OD with sealant material.
• When thimble is not used for non-
combustible wall, size and cut wall opening
such that a minimal clearance is obtained
and to allow easy insertion of vent pipe.
• Apply sealant between vent pipe and
thimble or wall opening to provide weathertight seal. Sealant should not restrain the
expansion of the vent pipe.
• Install Rodent Screen and Vent Terminal
(supplied with boiler). See Figure 10 for
appropriate conguration details.
24
WARNING
All CPVC pipe supplied with boiler vent carton
must be used as part of vent system prior to
connecting supplied PVC vent terminal.
Methods of securing and sealing terminals to
the outside wall must not restrain the thermal
expansion of the vent pipe.
ii. Combustion Air Piping
• Do not exceed maximum combustion air
pipe length. Refer to Table 8.
• Size combustion air pipe wall penetration
opening to allow easy insertion of the pipe.
• Install Rodent Screen and Combustion Air
Terminal (supplied with boiler). See Figure
10 for appropriate conguration details.
• Apply sealant between combustion air pipe
and wall opening to provide weather-tight
seal.
b. Optional Two-Pipe Snorkel Termination
See Figures 10 and 11.
This installation will allow a maximum of seven (7)
feet vertical exterior run of the vent/combustion air
piping to be installed on the CPVC/PVC horizontal
venting application.
Figure 10: Rodent Screen Installation
Figure 11: Direct Vent - Optional Sidewall
Snorkel Terminations
IV. Venting B. CPVC/PVC Venting (continued)
NOTICE
Exterior run to be included in equivalent vent/
combustion air lengths.
i. Vent Piping
• After penetrating wall, install a Schedule
40 PVC 90° elbow so that the elbow leg is
in the up direction.
• Install maximum vertical run of seven (7)
feet of Schedule 40 PVC vent pipe. See
Figure 11.
• At top of vent pipe length install another
PVC 90° elbow so that elbow leg is opposite
the building’s exterior surface.
• Install Rodent Screen and Vent Terminal
(supplied with boiler), see Figure 10 for
appropriate conguration.
• Brace exterior piping if required.
ii. Combustion Air Piping
• After penetrating wall, install a Schedule
40 PVC 90
the up direction.
• Install maximum vertical run of seven (7)
feet of Schedule 40 PVC vent pipe. See
Figure 11.
• At top of air pipe length install another PVC
90° elbow so that elbow leg is opposite the
building’s exterior surface.
• Install Rodent Screen and Combustion Air
Terminal (supplied with boiler), see Figure
10 for appropriate conguration.
• Brace exterior piping if required.
°
elbow so that elbow leg is in
CAUTION
Vertical venting and combustion air roof
penetrations (where applicable) require the use
of roof ashing and storm collar, which are not
supplied with boiler, to prevent moisture from
entering the structure.
- Install storm collar on vent pipe
immediately above ashing. Apply
Dow Corning Silastic 732 RTV Sealant
between vent pipe and storm collar to
provide weather-tight seal.
• Install Rodent Screen and Vent Terminal
(supplied with boiler), see Figure 10 for
appropriate conguration.
• Brace exterior piping if required.
WARNING
All CPVC pipe and elbow supplied with boiler
vent carton must be used as part of vent
system prior to connecting supplied PVC vent
terminal.
Do not operate boiler without the rain cap
over vent pipe in place.
ii. Combustion Air Piping
• Locate combustion air termination on the
same roof location as the vent termination
to prevent nuisance boiler shutdowns.
Combustion air terminal can be installed
closer to roof than vent.
6. Vertical Vent Termination
a. Standard Two-Pipe Termination
Refer to Figures 10, 12 and 13.
i. Vent Piping
• Install re stops where vent passes through
oors, ceilings or framed walls. The re
stop must close the opening between the
vent pipe and the structure.
• Whenever possible, install vent straight
through the roof. Refer to Figures 12 and
13.
- Size roof opening to maintain minimum
clearance of 1" from combustible
materials.
- Extend vent pipe to maintain minimum
vertical and horizontal distance of
twelve (12) inches from roof surface.
Additional vertical distance for expected
snow accumulation. Provide brace as
required.
Figure 12: Direct Vent - Vertical Terminations
25
IV. Venting B. CPVC/PVC Venting (continued)
Figure 13: Direct Vent - Vertical Terminations
with Sloped Roof
Extend vent/combustion air piping to maintain minimum vertical (‘X’) and minimum horizontal (‘Y’) distance of
twelve (12) inches (18 inches Canada) from roof surface. Allow additional vertical (‘X’) distance for expected
snow accumulation.
• Size roof opening to allow easy insertion
of combustion air piping and allow proper
installation of ashing and storm collar
to prevent moisture from entering the
structure.
- Use appropriately designed vent ashing
when passing through roofs. Follow
ashing manufacturers’ instructions for
installation procedures.
- Extend combustion air pipe to maintain
minimum vertical and horizontal distance
of twelve (12) inches from roof surface.
Allow additional vertical distance for
expected snow accumulation. Provide
brace as required.
- Install storm collar on combustion
air pipe immediately above ashing.
Apply Dow Corning Silastic 732
RTV Sealant between combustion
air pipe and storm collar to provide
weather-tight seal.
• Install Rodent Screen and Combustion
Air Terminal (supplied with boiler), see
Figure 10 for appropriate conguration.
• Brace exterior piping if required.
C. Polypropylene Venting
Apex boilers have been approved for use with
polypropylene vent system.
It is an installing contractor responsibility to
procure listed below polypropylene vent system pipe
and related components.
Polypropylene vent system manufactures are listed
below:
Approved Polypropylene Vent System Manufacturers
MakeModel
PolyPro Single Wall Rigid Vent
M&G/DuraVent
Centrotherm
Eco Systems
PolyPro Flex Flexible Vent (APX399 and
APX500)
InnoFlue SW Rigid Vent
Flex Flexible Vent (APX399 and APX500)
NOTE: Do not mix vent components from approved
manufacturers.
M&G/DuraVent PolyPro Single Wall Rigid Vent
and PolyPro Flex Flexible Vent comply with the
requirements of ULC-S636-08 ‘Standard for Type BH
Gas Venting Systems’.
Centrotherm Eco Systems InnoFlue SW Rigid Vent
and Flex Flexible Vent comply with the requirements
of UL 1738 ‘Standard for Safety for Venting Systems’
and ULC-S636-08 ‘Standard for Type BH Gas Venting
Systems’.
For polypropylene vent system installation details refer
to an approved manufacturer either Rigid Single Wall
Polypropylene Vent Installation Instructions, or Flexible
Polypropylene Vent Installation Instructions provided
with a manufacturer specic kits. See Tables 9 and 10.
Refer to Table 8 ‘Vent/Combustion Air Pipe Length –
Two-Pipe Direct Vent System Options’ for minimum
and maximum listed equivalent length values.
All terminations must comply with listed options for
two-pipe venting system. See Figures 8 thru 12 for
details.
26
IV. Venting C. Polypropylene Venting (continued)
Table 9: Approved Polypropylene Pipe, Fittings and Terminations - M&G/DuraVent
When using exible polypropylene vent pipe (liner):
• Flexible pipe must be treated carefully and stored at
temperatures higher than 41°F (5°C).
• Do not bend or attempt to install exible pipe if
it has been stored at lower ambient temperature
without allowing the pipe to warm up to a higher
temperature rst.
CAUTION
Bending or attempting to install exible pipe if it
has been stored at ambient temperature below
41°F (5°C) will cause material to become brittle
and lead to cracks.
When exible polypropylene pipe (liner) is
used for combustion product venting, it must
not be installed at an angle greater than 45
degrees from vertical plane. This will insure
proper condensate ow back towards the boiler.
CAUTION
Do not install exible polypropylene pipe at an
angle greater than 45 degrees from vertical plane
when used for combustion product venting.
Failure to do so will result in improper condensate
drainage towards the boiler and possible
subsequent vent pipe blockage.
• When exible polypropylene pipe (liner) is used
for combustion air supply to a boiler, the pipe
(liner) can be installed in vertical or horizontal
position.
regarding application/listing, permits, minimum
clearances to combustibles; installation details
(proper joint assembly, pipe support and routing,
gasket and tting installation, optional tooling
availability/usage, routing thru masonry chimney
for combustion product venting or, combination
of combustion product venting and combustion
air supply).
• When there is a conflict between flexible
polypropylene pipe (liner) manufacturer installation
instructions and Apex boiler Installation, Operating
and Service Instructions, the more restrictive
instructions shall govern.
Apex Boiler Two-Pipe Vent System Connector Field
Modication Procedure To Accept Polypropylene
Vent Piping:
Apex boilers are factory supplied with a model-specic
boiler two-pipe CPVC/PVC vent system connector
shipped within a model-specic boiler CPVC gasketed
vent kit carton.
Locate and remove a model-specic boiler two-pipe
CPVC/PVC vent system connector.
When using M&G/DuraVent polypropylene pipe for
combustion product venting and/or air supply, male
PVC to PP boiler adapter (4PPS-04PVCM-4PPF or
6PPS-06PVCM-6PPF as applicable) is installed into the
two-pipe vent system connector vent or combustion air
supply port as follows (see Figure 14):
1) APX399 and APX500 models - Apply provided
dielectric grease (grease pouch taped to the vent
system connector) all around to the vent or air
connection inner red silicon gasket.
2) APX399 and APX500 models - Push and twist
PVC to PP boiler adapter (4PPS-04PVCM-4PPF)
into two-pipe vent system connector vent connection
or air supply port until bottomed out.
27
IV. Venting C. Polypropylene Venting (continued)
Figure 14: Vent System Field Modication to Install PVC to PP Adapter (M&G/DuraVent Shown)
3) Tighten the worm band clamp screw to secure PVC
to PP boiler adapter.
4) Do not install PVC to PP boiler adapter at the
lower combustion air supply port of the two-pipe
vent system connector when using PVC pipe for
combustion air supply to boiler.
5) APX800 model - Apply a coating of supplied red
RTV silicon sealant, at least 1” wide, to PVC to PP
boiler adapter (6PPS-06PVCM-6PPF) male end,
when used for combustion product venting.
If polypropylene pipe is also used for combustion air
supply, application of the silicon sealant to PVC to
PP boiler adapter (6PPS-06PVCM-6PPF) male end
is not required.
6) APX800 model - Push and twist PVC to PP boiler
adapter (6PPS-06PVCM-6PPF) into two-pipe vent
system connector vent port or air supply port until
bottomed out.
7) Tighten the worm band clamp screw to secure PVC
to PP boiler adapter.
8) Do not install PVC to PP boiler adapter at the
lower combustion air supply port of the two-pipe
vent system connector when using PVC pipe for
combustion air supply to boiler.
When using Centrotherm Eco polypropylene pipe
for combustion product venting and/or air supply PVC
to PP boiler adapter (ISAA0404 or ISAAL0404 and
ISAA0606 or ISAAL0606 as applicable) is installed
into the two-pipe vent system connector vent or
combustion air supply port as follows (see Figure 14):
9) APX399 and APX500 models - Apply provided
dielectric grease (grease pouch taped to the vent
system connector) all around to the vent or air
connection inner red silicon gasket.
28
10) APX399 and APX500 models - Push and
twist PVC to PP boiler adapter (ISAA0404 or
ISAAL0404) into two-pipe vent system connector
vent connection or air supply port until bottomed
out.
11) Tighten the worm band clamp screw to secure PVC
to PP boiler adapter.
12) Do not install PVC to PP boiler adapter at the
lower combustion air supply port of the two-pipe
vent system connector when using PVC pipe for
combustion air supply to boiler.
13) APX800 model - Apply a coating of supplied red
RTV silicon sealant, at least 1” wide, to PVC to PP
boiler adapter (ISAA0606 or ISAAL0606) male
end, when used for combustion product venting.
If polypropylene pipe is also used for combustion air
supply, application of the silicon sealant to PVC to
PP boiler adapter (ISAA0606 or ISAAL0606) male
end is not required.
14) APX800 model - Push and twist PVC to PP boiler
adapter (ISAA0606 or ISAAL0606) into two-pipe
vent system connector vent port or air supply port
until bottomed out.
15) Tighten the worm band clamp screw to secure PVC
to PP boiler adapter.
16) Do not install PVC to PP boiler adapter at the
lower combustion air supply port of the two-pipe
vent system connector when using PVC pipe for
combustion air supply to boiler.
Optional Two-pipe Vertical Venting Installation –
Running Flexible Polypropylene Vent (Liner)
Thru Unused Chimney Chase (see Figure 15).
Apex APX399 and APX500 boilers are approved for
vertical venting by installing Flexible Vent in an UNUSED
masonry chimney/chase and supplying combustion air
thru a separate wall or roof air intake terminal.
IV. Venting C. Polypropylene Venting (continued)
Venting of Other Appliances (or Fireplace)
into Chase or Adjacent Flues Prohibited!
Figure 15: Flexible Vent in Masonry
Chimney with Separate Air Intake
WARNING
Follow installation instructions included by the original polypropylene venting component manufacturers,
M&G/DuraVent or Centrotherm, whichever applicable.
Flexible Polypropylene Vent must be installed in an UNUSED chimney. A chimney, either single or
multiple ue type, is considered UNUSED when none of the ues is being used for any appliance
venting.
Where one of the multiple ues is being used for an appliance venting, the exible vent installation is
not permitted thru any of adjacent ues.
Observe all precautions outlined in either M&G/DuraVent or Centrotherm instructions in addition to
those outlined in these instructions.
Examine all components for possible shipping damage prior to installation.
Proper joint assembly is essential for safe installation.
The venting system must be free to expand and contract and supported in accordance with installation
instructions included by the original polypropylene venting component manufacturers, M&G/DuraVent
or Centrotherm, whichever applicable.
Do not mix vent components or joining methods for different vent systems.
Where a conict arises between M&G/DuraVent or Centrotherm instructions and these instructions, the
more restrictive instructions shall govern.
Do not apply thermal insulation to vent pipe and ttings.
Do not obtain combustion air from within the building.
29
IV. Venting D. Stainless Steel Venting (continued)
D. Stainless Steel Venting
CAUTION
Vent systems made by Heat Fab, Protech and
Z-Flex rely on gaskets or proper sealing. When
these vent systems are used, take the following
precautions:
• Make sure that gasket is in position and un-
damaged in the female end of the pipe.
• Make sure that both the male and female
pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent
manufacturer in accordance with their in structions. When pipe is cut, cut end must
be square and carefully de-burred prior to
assembly.
WARNING
All condensate that forms in the vent must be
able to drain back to the boiler.
1.
Vent Length Restrictions
a. Vent length restrictions are based on equivalent
length of vent/combustion air pipe (total length
of straight pipe plus equivalent length of
ttings). Maximum vent/combustion air lengths
are listed in Table 8. Do not exceed maximum
vent/combustion air lengths. Do not include
vent/combustion air terminals in equivalent
feet calculations. See “Combustion Air/Vent,
Equivalent Length Work Sheet”.
b. The vent termination location is restricted as
per ‘General Guidelines’, Section A.5. (Refer to
Figure 4)
c. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or
equivalent for the vent collar. Air inlet piping
sections are sealed with any general-purpose
silicone sealant such as GE RTV102. PVC air
inlet piping sections are connected with PVC
cement.
d. Longitudinal welded seams should not be placed
at the bottom of horizontal sections of exhaust
pipe.
e. Do not drill holes in vent pipe.
f. Do not attempt to mix vent components of
different vent system manufacturers.
2. Near Boiler Connection
To install the stainless steel vent adapter
[P/N 102220-01 (4”)]:
a. Push the stainless steel vent adapter onto the
CPVC/PVC connector with a slight twisting
motion. Make sure that the stainless steel vent
adapter is inserted at least 1” (refer to Figure 16).
b. Secure the adapter to the CPVC/PVC connector
by tightening the metal strap.
To install the stainless steel vent adapter
[P/N 103285-01 (6”)]:
c. Apply a coating of supplied red RTV silicone
sealant, at least 1” wide, all around male end of
the stainless steel vent adapter.
d. Afterwards, insert the male end of the adapter
with a slight twisting motion into vent section of
installed two-pipe CPVC/PVC vent connector.
e. Secure the adapter to the two-pipe CPVC/PVC
vent connector by tightening the metal strap.
System Assembly
3.
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at
vent connector at boiler and work towards vent
termination.
b. Refer to Tables 11A and 11B for approved
AL29C Vent Systems.
c. Do not exceed maximum Vent/Combustion air
length. Refer to Table 8.
d. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining
and using the primer and the cement.
e. Assemble the air intake system using either
galvanized or PVC pipe.
i. If PVC piping is used, use PVC cement
to assemble the PVC intake system
components. See Part B for air intake
installation instructions.
ii. If galvanized piping is used, use at least two
sheet metal screws per joint. Seal the outside
of all joints.
4.
Horizontal Vent Termination
a. Standard Two-Pipe Termination
Refer to Figure 9A.
i. Vent Termination
• Use Burnham Commercial stainless
exhaust terminal [P/N 100184-01 (4”)].
The outer edge of this terminal must be
between 6” and 12” from the surface
of the wall. The joint between the
terminal and the last piece of pipe
must be outside of the building.
• Male end of terminal will t into the
female end of any of the approved
stainless vent systems.
30
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.