Burnham Apex Installation and Operation Manual

INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
APEX™
DIRECT VENT
GAS - FIRED HOT WATER BOILER
9700609
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury, or loss of life. For assistance or additional information, consult a qualied installer, service agency or the gas supplier. This boiler requires a special venting system. Read these instructions carefully before installing.
103022-04 - 8/13
Price - $5.00
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The City of New York requires a Licensed Master Plumber supervise the installation of this product.
The Massachusetts Board of Plumbers and Gas Fitters has approved the Apex™ Series boiler. See the Massachusetts Board of Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pl_products/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance.
If you smell gas vapors, NO NOT try to operate any appliance - DO NOT touch any electrical switch or use any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the gas
supplier’s instructions or if the supplier is unavailable, contact the re department.
2
Special Installation Requirements for Massachusetts
A. For all sidewall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes and where the sidewall exhaust vent termination is less than seven (7) feet above grade, the
following requirements shall be satised:
1. If there is no carbon monoxide detector with an alarm already installed in compliance with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code in the residential unit served by the sidewall horizontally vented gas fueled equipment, a battery operated carbon monoxide detector with an alarm shall be installed in compliance with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code.
2. In addition to the above requirements, if there is not one already present, a carbon monoxide detector with an alarm and a battery back-up shall be installed and located in accordance with the installation requirements supplied with the
detector on the oor level where the gas equipment is installed. The carbon monoxide detector with an alarm shall
comply with 527 CMR, ANSI/UL 2034 Standards or CSA 6.19 and the most current edition of NFPA 720. In the event that the requirements of this subdivision can not be met at the time of the completion of the installation of the equipment, the installer shall have a period of thirty (30) days to comply with this requirement; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed in compliance with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code. In the event that the sidewall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the carbon monoxide detector
may be installed on the next adjacent habitable oor level. Such detector may be a battery operated carbon monoxide
detector with an alarm and shall be installed in compliance with the most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code.
3. A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. A nal inspection by the state or local gas inspector of the sidewall horizontally vented equipment shall not be performed
until proof is provided that the state or local electrical inspector having jurisdiction has granted a permit for installation of carbon monoxide detectors and alarms as required above.
B. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved sidewall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
C. When the manufacturer of Product Approved sidewall horizontally vented gas equipment provides a venting system design
or venting system components with the equipment, the instructions for installation of the equipment and the venting system shall include:
1. A complete parts list for the venting system design or venting system; and
2. Detailed instructions for the installation of the venting system design or the venting system components.
D. When the manufacturer of a Product Approved sidewall horizontally vented gas fueled equipment does not provide the parts
for venting ue gases, but identies “special venting systems”, the following shall be satised:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
E. A copy of all installation instructions for all Product Approved sidewall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
3
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be performed only by an experienced, skilled, and knowledgeable installer or service agency
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life
to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on left side of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instruc­tions, including all those contained in component manufacturers manuals which are provided with the boiler before installing, starting up, operating, maintaining or servicing.
All cover plates, enclosures and guards must be in place at all times.
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete.
4
TABLE OF CONTENTS
I. Product Description, Specications and Dimensional Data...................... 6
II. Unpacking Boiler........................................................................................ 10
III. Pre-Installation and Boiler Mounting.......................................................... 11
IV. Venting...................................................................................................... 15
A. General Guidelines............................................................................... 15
B. CPVC/PVC Venting.............................................................................. 18
C. Polypropylene Venting......................................................................... 26
D. Stainless Steel Venting........................................................................ 30
E. Concentric Polypropylene Venting....................................................... 32
F. Removing the Existing Boiler............................................................... 38
G. Multiple Boiler Installation Venting....................................................... 40
V. Condensate Disposal................................................................................. 43
VI. Water Piping and Trim............................................................................... 45
VII. Gas Piping ............................................................................................... 59
VIII. Electrical ................................................................................................... 63
IX. System Start-Up ....................................................................................... 75
X. Operation...................................................................................................... 81
A. Overview.............................................................................................. 81
B. Supply Water Temperature Regulation................................................ 82
C. Boiler Protection Features.................................................................... 83
D. Multiple Boiler Control Sequencer........................................................ 84
E. Boiler Sequence of Operation.............................................................. 85
1. Normal Operation........................................................................... 85
2. Using the Display............................................................................ 86
F. Viewing Boiler Status.......................................................................... 87
1. Status Screens............................................................................... 87
2. Detail Screens................................................................................ 88
3. Multiple Boiler Sequencer Screens................................................ 89
G. Changing Adjustable Parameters........................................................ 90
1. Entering Adjust Mode.................................................................... 90
2. Adjusting Parameters.................................................................... 90
XI. Service and Maintenance ........................................................................ 101
XII. Troubleshooting........................................................................................ 105
XIII. Repair Parts ............................................................................................. 109
Appendix A - Figures................................................................................ 124
Appendix B - Tables.................................................................................. 127
Warranty...........................................................................................Back Page
5
I. Product Description, Specications and Dimensional Data
Apex™ Series boilers are condensing high efciency gas-red direct vent hot water boilers designed for use
in forced hot water space or space heating with indirect domestic hot water heating systems, where supply water temperature does not exceed 210°F. These boilers have special coil type stainless steel heat exchangers, constructed, tested and stamped per Section IV ‘Heating Boilers’ of
Table 1: Dimensional Data (See Figures 1A, 1B and 1C)
Dimension
APX399 APX500 APX800
A - Inch
(mm)
B - Inch
(mm)
C - Inch
(mm)
D - Inch
(mm)
E - Inch
(mm)
Gas Inlet F
(FPT)
Return G 1-1/2” (FPT) 2” (MPT)
28-7/8
(734)
6-3/16
(157)
13-1/16
(332)
23-3/4
(602)
15-13/16
(402)
3/4” 3/4” 1
ASME Boiler and Pressure Vessel Code, which provide a maximum heat transfer and simultaneous protection against
ue gas product corrosion. These boilers are not designed
for use in gravity hot water space heating systems or
systems containing signicant amount of dissolved oxygen
(swimming pool water heating, direct domestic hot water heating, etc.).
Boiler Model
44-7/8 (1140)
22-1/8
(562)
29
(737)
39-11/16
(1008) 29-3/8
(752)
54-9/16
(1384)
28-3/8
(724)
34-1/4
(876)
48-1/16
(1226)
33-13/16
(864)
Supply H 1-1/2” (FPT) 2” (MPT)
Condensate Drain J Factory Provided Socket End Compression Pipe Joining Clamp for 3/4” Schedule 40 PVC Pipe
Boiler Two-Pipe
CPVC/PVC Vent Connector
(Figures 1A, 1B and 1C) - Inch
Approx. Shipping Weight (LBS) 304 350 430
4 x 4 6 x 6
6
I. Product Description, Specications and Dimensional Data (continued)
Figure 1A: Apex™ - Model APX399
7
I. Product Description, Specications and Dimensional Data (continued)
8
Figure 1B: Apex™ - Model APX500
I. Product Description, Specications and Dimensional Data (continued)
Figure 1C: Apex™ - Model APX800
9
I. Product Description, Specications and Dimensional Data (continued)
Table 2A: Rating Data - Models APX399, APX500 and APX800 (0 to 5000 Feet Elevation Above Sea Level)
Apex Series Gas-Fired Boilers
Model
Number
APX399 80 399 375 326 94.1 94.5 3.4 41.8
APX500 100 500 475 413 95.0 95.0 4.2 50.8
APX800 160 800 760 661 95.0 93.0 5.0 65.3
Notes: * Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800) Maximum Allowable Temperature, Water - 210°F APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be eld adjusted for LP gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build. Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
Input (MBH)
Min. Max.
* Output
(MBH)
Net AHRI
Ratings Water
(MBH)
Thermal
Efciency
(%)
Combustion
Efciency (%)
Boiler Water
Volume (Gal.)
Heat Transfer
Area
(Sq. Ft.)
Table 2B: Rating Data - Models APX399, APX500 and APX800 (5001 to 10000 Feet Elevation Above Sea Level)
Apex Series Gas-Fired Boilers
Model
Number
Input (MBH)
Min. Max.
* Output
(MBH)
Net AHRI
Ratings
Water (MBH)
Thermal
Efciency
(%)
Combustion
Efciency (%)
Boiler Water
Volume
(Gal.)
Heat Transfer
Area
(Sq. Ft.)
APX399 80 399 375 328 94.1 94.5 3.4 41.8
APX500 167 500 475 413 95.0 95.0 4.2 50.8
APX800 267 800 760 661 95.0 93.0 5.0 65.3
Notes: * Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800) Maximum Allowable Temperature, Water - 210°F APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be eld adjusted for LP gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build. Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
II. Unpacking Boiler
D. Remove boiler from cardboard positioning sleeve on
CAUTION
Do not drop boiler.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container.
shipping skid.
WARNING
Installation of this boiler should be undertaken only by trained and skilled personnel from a
qualied service agency.
E. Move boiler to its permanent location.
10
III. Pre-Installation and Boiler Mounting
WARNING
If you do not follow these instructions exactly,
a re or explosion may result causing property
damage or personal injury.
NOTICE
Due to the low water content of the boiler, mis­sizing of the boiler with regard to the heating system load will result in excessive boiler cycling and accelerated component failure. Burnham Commercial DOES NOT warrant failures caused by mis-sized boiler applications. DO NOT oversize the boiler to the system. Multiple boiler installations greatly reduce the likelihood of boiler oversizing.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/ CSA B149.1 Installation Codes.
B. Boiler is certied for installation on combustible
ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local re
ordinance. Refer to Figure 2 for minimum listed clearances from combustible material. Recommended service clearance is 24 inches from left side, front, top and rear of the boiler. Recommended front clearance may be reduced to the combustible material clearance providing:
1. Access to boiler front is provided through a door or removable front access panel.
2. Access is provided to the condensate trap located underneath the heat exchanger.
D. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
E. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes, or: USA - National Fuel Gas Code, NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas and Propane Installation Code,
CAN/CSA-B149.1, Venting Systems and Air Supply for Appliances.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion.
F. The boiler should be located so as to minimize the
length of the vent system. The PVC combustion air piping, or the optional concentric vent piping, containing integral combustion air inlet piping, must terminate where outdoor air is available for combustion and away from areas that may contaminate combustion air. In particular, avoid areas near chemical products
containing chlorines, chlorouorocarbons, paint
removers, cleaning solvents and detergents. Avoid
areas containing saw dust, loose insulation bers, dry
wall dust etc.
CAUTION
Avoid operating this boiler in an environment
where sawdust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
G. General.
1. Apex boilers are intended for installations in an
area with a oor drain, or, in a suitable drain pan to
prevent any leaks or relief valve discharge to cause property damage
2. Apex boilers are not intended to support external piping and venting. All external piping and venting must be supported independently of the boiler.
3. Apex boilers must be installed level to prevent condensate from backing up inside the boiler.
4. Boiler Installation:
a. For basement installation provide a solid level
base such as concrete, where oor is not level, or, water may be encountered on the oor
around boiler. Floor must be able to support weight of boiler, water and all additional system components.
b. Boiler must be level to prevent condensate from
backing up inside the boiler.
c. Provide adequate space for condensate piping or
a condensate pump if required.
11
III. Pre-Installation and Boiler Mounting G. General (continued)
Boiler Clearances to Combustible (and Non­Combustible) Material:
APX399 and APX500 Boiler Models:
These boilers are approved for closet installation with
the following clearances – Top = 1”, Front = 1”, Left Side = 10”, Right Side = 2”, Rear = *6”
APX800 Boiler Model:
This boiler is approved for alcove installation with the
following clearances – Top = 1”, Front = Open, Left Side = 10”, Right Side = 2”, Rear = *6”
* Note:
When boiler is vented vertically, the minimum
clearance from the rear of the jacket is increased to 18” with a short radius 90° elbow provided in order to provide adequate space at boiler rear for installation of vent and air intake piping and service access
Approved Direct
Factory Standard
Two-Pipe CPVC/PVC Vent and PVC Air Intake
Available Optional
Two-Pipe Rigid Polypropylene Vent (or, Flexible Polypropylene Liner for Vertical Venting only) and Rigid
Polypropylene or PVC Combustion Air Intake
Available Optional
Two-Pipe Stainless Steel Vent and Galvanized Steel or Air Intake
Available Optional
Concentric Inner Polypropylene Vent and Outer Steel Air Intake
* Do not enclose PVC venting - use CPVC vent pipe in enclosed spaces, or to penetrate through
combustible or non-combustible walls
Vent System
Boiler Service Clearances – Applicable to all Boiler Models:
Top = 24”, Front = 24”, Left Side = 24”, Right Side =
24”, Rear = 24”
The above Clearances are recommended for Service
Access but may be reduced to the Combustible Material Clearances provided:
1. The boiler front is accessible thru a door
2. Access is provided to the condensate trap located on the left side of boiler
3. Access is provided to thermal link located at the boiler rear
Vent Pipe
Material
* CPVC/PVC
Pipe Rigid
Polypropylene
Vent (or,
Flexible
Polypropylene
Liner for
Vertical
Venting only)
Stainless
Steel
Polypropylene
Vent Pipe
Direction
Vertical or Horizontal
Enclosure
Unenclosed at
all Sides
Vent Pipe
Nominal
Diameter
4” or 6” 1”
80 mm 10 mm
(110 mm)
150 mm
(160 mm)
4” or 6” 1”
100/150 mm
(110/160 mm)
Minimum Clearance to Combustible
Material
1”
0”
12
Figure 2: Clearances To Combustible and Non-combustible Material
III. Pre-Installation and Boiler Mounting G. General (continued)
H. Boiler Stacking
1. For installations with unusually high space heating and/or domestic hot water heating loads, where employing two (2) Apex (APX) boilers will offer the
benets of greater operational efciency, oor space
savings and boiler redundancy, the Apex (APX) boilers may be installed stacked one on the top of the other. Refer to Table 3 “Apex (APX) Boiler Model Stacking Combinations” for details.
Table 3: Apex (APX) Boiler Model Stacking Combinations
Bottom
Boiler Model
APX399
APX500 APX399 or APX500 APX800 APX399, APX500 or APX800
2. To eld assemble individual Apex (APX) boilers into a stackable conguration, use the steps below:
a. Position the bottom boiler rst. Refer to Sections
II “Unpacking Boiler” and III “Pre-Installation & Boiler Mounting” of the manual for details.
Always position higher input boiler model as
bottom boiler.
b. Each Apex (APX) boiler is factory packaged
with two (2) Stacking Boiler Attachment Brackets (P/N 101679-01) and the bracket mounting hardware [six (6) self-drilling hex washer head plated #8 x ½” long screws, P/N 80860743]. Locate and remove the brackets and the hardware. The Stacking Boiler Attachments Bracket has three 7/32” diameter holes punched in a triangular pattern. See Figure 3 “Stacking Boiler Attachment Bracket Placement”.
c. Apex (APX) boiler left and right side panels
have a series of dimples at panel top and bottom. These dimples are positioning dimples for Stacking Boiler Attachment Bracket mounting screws. Side panel bottom positioning dimples are evenly spaced from boiler front and back, while side panel top positioning dimples follow
specic pattern to compensate for Apex (APX)
boiler model variable depth.
d. Position the upper boiler on the top of the bottom
boiler and align boiler front doors and sides ush
with each other.
Place rst Stacking Boiler Attachment
Bracket onto the upper boiler left side panel, at the panel lower left corner and align bracket two upper holes with corresponding side panel lower dimples.
The remaining lower bracket hole must align
with a matching bottom boiler left side panel top positioning dimple.
Top Boiler Model
APX399
Once bracket holes and side panel dimple alignment is veried, attach the bracket to
top and bottom boiler left side panels with the mounting screws.
e. Repeat above procedure to install second
Stacking Boiler Attachment Bracket and secure the stacked boiler right side panels together at the front right corner.
f. Install the third Stacking Boiler Attachment
Bracket to secure top and bottom boiler left side panels at the rear left corner. Align the bracket holes with corresponding positioning dimples in the top boiler and bottom boiler left side panels, then secure bracket with the screws.
g. Repeat above procedure to install the forth
Stacking Boiler Attachment Bracket to secure stacked boiler right side panels at the rear right corner.
3. When installing stackable boiler combinations observe the following guidelines:
a. Venting - Top and bottom boilers must have their
individual vent piping and vent terminals.
WARNING
No common manifolded venting is permitted.
For side-wall venting individual model vent
terminals must terminate not closer than 12 inches horizontally and three (3) feet vertically from each other in order to prevent combustion air contamination. For vertical through the roof venting, individual vertical vent terminals, if level with each other, must be spaced no closer than 12 inches horizontally. If vertical terminals cannot end in one plane, they must be spaced no closer than three (3) feet horizontally.
Chimney chase concentric venting is permitted
for modules, when stackable, providing concentric vertical (roof) vent terminals, if level with each other, are spaced no closer then 12 inches horizontally.
If vertical vent terminals cannot end in one
plane, they must be spaced no closer then three (3) feet horizontally.
Follow instructions in Section IV “Venting”
of the manual for specics of individual boiler
vent termination. Follow instructions in Section V “Condensate Disposal” for each individual
boiler ue gas condensate line construction and
condensate disposal. Terminating individual boiler condensate lines into common pipe prior to drain disposal is permissible, providing
common pipe has sufcient ow capacity
to handle combined condensate volume of stackable combination.
13
III. Pre-Installation and Boiler Mounting G. General (continued)
b. Gas Piping - Follow instructions in Section
VII “Gas Piping” of the manual for sizing and installation of an individual boiler. When common gas piping is sized, insure it will have
adequate capacity for combined input (CFH gas ow) of the selected stackable boiler
combination.
c. Water Piping and Trim - Follow instructions
in Section VI “Water Piping and Trim” of the manual for system piping and boiler secondary
piping selection/sizing based on combined
heating capacity and/or gross output of
the selected stackable boiler combination. Follow instructions of Section VI “Water Piping and Trim” for each individual boiler trim installation.
d. Electrical - Follow instructions in Section VIII
“Electrical” of the manual to wire individual boilers.
14
Figure 3: Stacking Boiler Attachment Bracket Placement
IV. Venting
WARNING
Failure to vent this boiler in accordance with these instructions could cause products of combustion to enter the building resulting in severe property damage, personal injury or death.
Do not interchange vent systems or materials unless otherwise specied.
The use of thermal insulation covering vent pipe and ttings is prohibited.
Do not use a barometric damper, draft hood or vent damper with this boiler.
When using the CPVC/PVC vent option, the use of CPVC is required when venting in vertical or horizontal
chase ways, closets and through wall penetrations. The CPVC vent materials supplied with this boiler do not comply with B149.1.S1-07 and are not ap-
proved for use in Canadian jurisdictions that require vent systems be listed to ULC S636-2008. In
these jurisdictions, vent this boiler using either stainless steel Special Gas vent or a listed ULC S636 Class IIB venting system.
Do not locate vent termination where exposed to prevailing winds. Moisture and ice may form on surface around vent termination. To prevent deterioration, surface must be in good repair (sealed, painted, etc.).
Do not locate air intake vent termination where chlorines, chlorouorocarbons (CFC’s), petroleum
distillates, detergents, volatile vapors or other chemicals are present. Severe boiler corrosion and failure will result.
The use of cellular core PVC (ASTM F891), cellular core CPVC or Radel (polyphenolsulfone) is prohibited. Do not locate vent termination under a deck.
Do not reduce specied diameters of vent and combustion air piping.
When installing vent pipe through chimney, as a chase, no other appliance can be vented into the chimney.
Do not allow low spots in the vent where condensate may pool.
A. General Guidelines
1. Vent system installation must be in accordance with National Fuel Gas Code, NFPA 54/ANSI Z221.3 or CAN/CSA B149.1 Installation Code for Canada, or, applicable provisions of local building
codes. Contact local building or re ofcials about
restrictions and installation inspection in your area.
2. The Apex™ is designed to be installed as a Direct Vent (sealed combustion) boiler. The air for combustion is supplied directly to the burner
enclosure from outdoors and ue gases are vented
directly outdoors (through wall or roof).
3. The following combustion air/vent system options are approved for use with the Apex™ boilers (refer to Table 4):
a. Two-Pipe CPVC/PVC Vent/Combustion Air
System - separate CPVC/PVC pipe serves to expel products of combustion and separate PVC pipe delivers fresh outdoor combustion air.
Refer to Part B for specic details.
b. Two-Pipe Polypropylene Vent/Combustion Air
System - separate rigid or exible polypropylene
pipe serves to expel products of combustion and separate rigid polypropylene pipe or PVC pipe delivers fresh outdoor combustion air. Refer to
part C for specic details.
c. Two-Pipe Stainless Steel Vent/Combustion Air
System - separate stainless steel pipe serves to expel products of combustion. Separate PVC or galvanized pipe delivers fresh outdoor air. Refer
to Part D for specic details.
d. Concentric Inner Polypropylene Vent
and Outer Steel Combustion Air System
- the assembly consists of inner re resistant
polypropylene vent pipe and outer steel pipe casing. The inner pipe serves as conduit to expel products of combustion, while outdoor fresh combustion air is drawn through the space between the inner and outer pipes. Refer to Part
E for specic details.
4. Horizontal vent pipe must maintain a 1/4" per foot slope down towards the boiler.
5. Horizontal combustion air pipe must maintain a minimum ¼" per foot slope down towards terminal, when possible. If not, slope toward boiler.
6. Do not install venting system components on
the exterior of the building except as specically
required by these instructions (refer to Figure 4):
a. Vent terminals must be at least 1 foot from door,
window, or gravity inlet into the building.
b. Maintain the correct clearance and orientation
between the vent and air intake terminals.
15
IV. Venting A. General Guidelines (continued)
Table 4: Vent/Combustion Air System Options
Approved Direct
Vent System
Factory Standard
Two-Pipe,
CPVC/PVC Vent and
PVC Air Intake
Available Optional
Two-Pipe, Rigid
Polypropylene
Vent (or Flexible
Polypropylene Liner
for Vertical venting
only) and Rigid
Polypropylene or PVC
Pipe Air Intake
Available Optional
Two-Pipe,
Stainless Steel Vent
and PVC/Galvanized
Steel Air Intake
Available Optional
Concentric, Inner
Polypropylene Vent and
Outer Steel Air Intake
Vent
Material
CPVC/PVC
Rigid
Polypropylene
(or Flexible
Polypropylene
Liner for vertical
Venting only)
Stainless Steel
Polypropylene
Orientation Termination Description Figures
Standard
(thru sidewall)
Horizontal
Optional
Snorkel
(thru sidewall)
Optional
Vertical
Horizontal
Optional
Vertical
Horizontal
Vertical Vertical (thru roof)
Horizontal
Vertical
Vertical
(thru roof)
Standard
(thru sidewall)
Optional Snorkel
(thru sidewall)
Vertical
(thru roof or
chimney/chase)
Standard
(thru sidewall)
Optional Snorkel
(thru sidewall)
Horizontal
(Wall) Terminal
Vertical (Roof)
Terminal
The system includes separate CPVC
vent pipe and PVC air intake pipe
terminating thru sidewall with individual penetrations for the vent and air intake
piping and separate terminals (tees).
Same as above but separate snorkel
type terminals.
The system includes separate CPVC
vent pipe and PVC air intake pipe
terminating thru roof with individual penetrations for the vent and air intake
piping and separate vertical terminals.
The system includes separate Rigid Polypropylene vent pipe and Rigid
Polypropylene or PVC air intake pipe
terminating thru sidewall with individual penetrations for the vent and air intake
piping and separate terminals (tees).
Same as above but separate snorkel
type terminals.
The system includes separate Flexible Polypropylene vent liner and Rigid Polypropylene vent pipe combination for venting and Rigid Polypropylene or PVC air intake pipe terminating thru roof with individual penetrations for the vent
and air intake and individual vent /air terminals.
The system includes separate stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating thru sidewall with individual penetrations for the
vent and air intake piping and separate terminals
Same as above but separate snorkel
type terminals.
The system includes separate stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating thru roof with individual penetrations for the vent and
air intake piping and separate terminals.
Concentric vent/air pipe terminates thru
sidewall.
Concentric vent/air pipe terminates thru
roof.
Component
Table
4 thru 9A,
9B, 10
4 thru 7,
10, 11
4 thru 6, 10,
12, 13
4 thru 9A,
9B, 10
4 thru 7,
10, 11
12 thru 16 9, 10
9A, 9B,
16, 17
11, 16, 17
12, 13, 17
18 thru 25
18 thru 21,
26 thru 31
9, 10
9, 10
11A, 11B D.
12, 13 E.
5A
5B
5C
Part
B.
C.
16
i. The centerlines between the vent and air
intake terminals must be spaced a minimum of 12” apart. More than 12” spacing is recommended.
ii. If possible, locate air intake and vent
terminations on the same wall to prevent nuisance shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or vice versa where installation conditions do not allow for alternate arrangement.
iii. The vent and air intake terminations may
be at varying heights when installed on the same wall, but the height of the vent termination should always be higher than the air intake termination and within the
specied limit as shown in Figure 9B.
c. The bottom of the vent and air intake terminal
must be at least 12" (18" in Canada) above the normal snow line. In no case should they be less than 12" above grade level.
d. The bottom of the vent terminal must be at least
7 feet above a public walkway.
e. Do not install the vent terminal directly over
windows or doors.
f. The bottom of the vent terminal must be at least
3 feet above any forced air inlet located within 10 feet.
g. A clearance of at least 4 feet horizontally must
be maintained between the vent terminal and gas meters, electric meters, regulators, and relief equipment. Do not install vent terminal over this equipment.
IV. Venting A. General Guidelines (continued)
Figure 4: Location of Vent Terminal Relative to Windows, Doors, Grades,
Overhangs, Meters and Forced Air Inlets
(Concentric Terminal Shown - Two-Pipe System Vent Terminal to be installed in same location -
Two-Pipe System Air Intake Terminal Not Shown)
h. Do not locate the vent terminal under decks or
similar structures.
i. Minimum twelve (12) inches vertically from any
roof overhang twelve (12) inches or less wide.
If a roof overhang width exceeds twelve (12)
inches the terminal vertical clearance must be
increased to avoid ue vapor condensation.
j. Top of vent terminal must be at least 5 feet
below eaves, softs, or overhangs. Maximum
depth of overhang is 3 ft.
k. If window and/or air inlet is within four (4) feet
of an inside corner, then terminal must be at least six (6) feet from adjoining wall of inside corner.
l. Concentric - Minimum twelve (12) inches
horizontally from a building corner.
m. Under certain conditions, water in the ue gas
may condense, and possibly freeze, on objects around the terminal including on the structure itself. If these objects are subject to damage by
ue gas condensate, they should be moved or
protected.
n. If possible, install the vent and air intake
terminals on a wall away from the prevailing
Installing multiple individual module (boiler) vent terminations too close together may result in cross contamination and combustion product water vapor condensation on building surfaces, where
vent termination are placed, and subsequent
frost damage. To avoid/minimize frost damage, extend the distance from building surfaces to vent termination end and increase the horizontal distance between adjacent vent terminations.
wind. Reliable operation of this boiler cannot be guaranteed if the terminal is subjected to winds in excess of 40 mph.
o. Air intake terminal must not terminate in areas
that might contain combustion air contaminates, such as near swimming pools.
p. For sidewall venting the minimum horizontal
distance between any adjacent individual module (boiler) vent terminations is twelve (12) inches.
Increasing this distance is recommended to avoid
frost damage to building surfaces where vent terminations are placed.
CAUTION
17
IV. Venting A. General Guidelines (continued)
q. The minimum horizontal distance between any
adjacent individual module (boiler) roof vent terminations is one (1) foot.
7. Use noncombustible ¾" pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system. Maximum support spacing four (4) feet. Avoid low spots where condensate may pool. Do not penetrate any part of the vent system with fasteners.
8. Maintain minimum clearance to combustible materials. See Figure 2 for details.
9. Enclose vent passing through occupied or unoccupied spaces above boiler with the material
having a re resistance rating of at least equal to the rating of adjoining oor or ceiling.
Note: For one or two family dwellings, re
resistance rating requirement may not need to be met, but is recommended.
10. Multiple individual module vertical vent pipes may be piped through a common conduit or chase so that one roof penetration may be made.
B. CPVC/PVC Venting
WARNING
All CPVC vent components (supplied with boiler) must be used for near-boiler vent piping before transitioning to Schedule 40 PVC pipe (ASTM
2665) components for remainder of vent system.
WARNING
CPVC vent components must be used within any interior space where air cannot circulate freely, such as air inside a stud wall, and in any boiler closet or chase way.
When using the CPVC/PVC vent options, the
use of CPVC is required when venting in vertical
or horizontal chase ways. All condensate that forms in the vent must
be able to drain back to the boiler.
1. Components and Length Restrictions
a. See Table 5A for CPVC/PVC Vent & Air Intake
Components included with boiler, Table 5B for CPVC/PVC Vent and Air Intake Components (Installer Provided) required for Optional
Table 5A: CPVC/PVC Vent & Air Intake Components Included With Boiler
Quantity
Vent & Air Intake Components
4” Schedule 40 PVC Tee (Vent or Air Intake Terminals) 102190-02 2 N/A
6” Schedule 40 PVC 90° Elbow (Vent or Air Intake
Terminal)
4” Stainless Steel Rodent Screen 102191-02 2 N/A
6” Stainless Steel Rodent Screen 102191-03 N/A 2
4” x 30” Schedule 40 CPVC Pipe 102193-02 1 N/A
6” x 30” Schedule 40 CPVC Pipe 103267-01 N/A 1
4” Schedule 80 CPVC 90° Elbow 102192-02 1 N/A
6” Schedule 80 CPVC 90° Elbow 103268-01 N/A 1
4 oz. Bottle of Transition Cement 102195-01 1
4 oz. Bottle of Primer 102194-01 1
4" Vent/4" Combustion Air CPVC/PVC Connector 102183-03 1 N/A
6" Vent/6" Combustion Air CPVC/PVC Connector 103270-01 N/A 1
4" Vent/4" Combustion Air CPVC/PVC Connector
Gasket
6" Vent/6" Combustion Air CPVC/PVC Connector
Gasket
Part
Number
103313-01 N/A 2
102185-02 1 N/A
103248-01 N/A 1
APX399 and APX500
Standard Termination
Vent Kit
(P/N 102189-03)
includes
APX800
Standard Termination
Vent Kit
(P/N 103253-01)
includes
18
IV. Venting B. CPVC/PVC Venting (continued)
Table 5B: CPVC/PVC Vent & Air Intake Components (Installer Provided) required for Optional Horizontal
(Snorkel) Termination
Quantity
Vent Components
4" Schedule 40 PVC Pipe x up to 7 ft. max. vertical run
6" Schedule 40 PVC Pipe x up to 7 ft. max. vertical run N/A 2
4" Schedule 40 PVC 90° Elbow 4 N/A
6" Schedule 40 PVC 90° Elbow N/A 4
4" Schedule 40 PVC Pipe x ½ ft. min. horizontal run 2 N/A
6" Schedule 40 PVC Pipe x ¾ ft. min. horizontal run N/A 2
Part
Number
N/A
Supplied by Others
Table 5C: CPVC/PVC Vent & Air Intake Components (Installer Provided) required for Optional Vertical
(Roof) Termination
Vent Components
4" Schedule 40 PVC Coupler
6" Schedule 40 PVC Coupler N/A 1
4" Schedule 40 PVC 90° Elbow 2 N/A
6" Schedule 40 PVC 90° Elbow N/A 2
4" Schedule 40 CPVC Pipe x ½ ft. min. horizontal run 1 N/A
6" Schedule 40 CPVC Pipe x ¾ ft. min. horizontal run N/A 1
Supplied by Others
Part
Number
N/A
APX399 and APX500
Horizontal (Snorkel)
Termination
2 N/A
APX399 and APX500
Vertical (Roof)
Termination
1 N/A
APX800
Horizontal (Snorkel)
Termination
Quantity
APX800
Vertical (Roof)
Termination
Horizontal (Snorkel) Termination and Table 5C for CPVC/PVC Vent and Air Intake Components (Installer Provided) required for Optional Vertical (Roof) Termination.
b. Vent length restrictions are based on equivalent
length of vent/combustion air pipe (total length of straight pipe plus equivalent length of
ttings). Maximum vent/combustion air lengths
are listed in Table 8. Do not exceed maximum vent/combustion air lengths. Table 6 lists
equivalent lengths for ttings. Do not include
vent/combustion air terminals in equivalent feet calculations. See “Combustion Air/Vent, Equivalent Length Work Sheet”.
c. The vent termination location is restricted as per
'General Guidelines', Paragraph A, 6.
(Refer to Figure 4).
2. System Assembly
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at vent connector at boiler and work towards vent termination.
b. Do not exceed maximum Vent/Combustion Air
length. Refer to Table 8.
c. Design the Vent System to allow 3/8" of thermal
expansion per 10 feet of CPVC/PVC pipe. Runs of 20 feet or longer that are restrained at both ends must use an offset or expansion loop. Refer to Figure 5 and Table 7.
d. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining and using the primer and the cement.
3. Field Installation of CPVC/PVC Two-Pipe
Vent System Connector
Refer to Figure 6 and Steps below:
a. Position the CPVC/PVC vent connector and
gasket onto boiler rear/bottom panel and insert vent connector inner stainless steel vent pipe into heat exchanger vent outlet.
b. Align vent connector plate and gasket clearance
holes with rear/bottom panel engagement holes; than, secure the connector and gasket to the panel with six mounting screws.
c. Apply supplied dielectric grease (grease pouch
attached to two-pipe vent connector) to gasket inside vent section of two-pipe vent connector, The grease will prevent gasket rupture when inserting vent pipe and gasket deterioration due to condensate exposure.
19
IV. Venting B. CPVC/PVC Venting (continued)
Table 6: Vent System and Combustion Air System Components Equivalent Length
vs. Component Nominal Diameter
Vent or Combustion Air System
Component Description
Equivalent Length (Ft.) for Vent or Combustion Air System Component
vs. Component Nominal Diameter (In.)
Component Nominal Diameter, In. 4” 6”
90° Elbow (Sch. 80 or Sch.40) 13 22
45° Elbow (Sch. 80 or Sch. 40) 4.5 7.5
Sch. 40 CPVC Pipe x 30 In. Long 2.5
Sch. 40 PVC Pipe x 1 Ft. Long 1
Sch. 40 PVC Pipe x 2 Ft. Long 2
Sch. 40 PVC Pipe x 3 Ft. Long 3
Sch. 40 PVC Pipe x 4 Ft. Long 4
Sch. 40 PVC Pipe x 5 Ft. Long 5
L
LOOP LENGTH
4
(L)
CHANGE OF DIRECTION
(VERTICAL OR HORIZONTAL)
LONG RUN OF PIPE
L
OFFSET
L 2
KEY
RESTRAINT (RESTRICTS MOVEMENT)
HANGER (ALLOWS MOVEMENT)
Table 7: Expansion Loop Lengths
Nominal
Pipe
Dia. (In.)
4
6
Length of
Straight Run
(Ft.)
20 60
30 74
40 85
50 95
60 104
20 73
30 90
40 103
50 116
60 127
Loop Length
“L” (In.)
LOOP
(HORIZONTAL ONLY)
(TOP VIEW)
L
6"
MIN
L 5
6"
MIN
Figure 5: Expansion Loop and Offset
L 4
2 L
5
WARNING
Apply supplied dielectric grease to gasket inside vent section of two-pipe vent connector. Failure to apply the grease could result in gasket rupture during vent pipe installation and gasket deterioration due to condensate exposure.
20
IV. Venting B. CPVC/PVC Venting (continued)
Figure 6: Field Installation of CPVC/PVC Two-Pipe Vent System Connector
4. Near-Boiler Vent/Combustion Air Piping
Refer to Figure 7 and the following Steps:
APX399 and APX500 Boiler Models:
a. 4” x 4” Two-Pipe CPVC/PVC Vent System
Connector (P/N 102183-03), used on APX399 and APX500 boiler models, has factory installed internal sealing gaskets at both vent and air intake sections.
b. Install provided 4” Schedule 40 x 30” long
CPVC pipe into the connector vent section with a slight twisting motion and secure by tightening the metal strap.
c. All CPVC vent components supplied with
boiler inside vent carton (4” Schedule 40 x 30”
long CPVC pipe and 4” Schedule 80 CPVC 90° Elbow) must be used for near-boiler piping before transitioning to Schedule 40 PVC (ASTM
2665) pipe components for reminder of vent system. The CPVC 30” long straight pipe may be
cut to accommodate desired vent conguration
provided both pieces are used in conjunction with CPVC 90° Elbow before any PVC components are used. Ensure that the CPVC 90°
Elbow is the rst elbow used in the vent system
as it exits the boiler.
d. Insert 4” Schedule 40 PVC combustion air pipe
(installer provided) into the connector air intake section with a slight twisting motion and secure by tightening the metal strap.
Figure 7: Near-Boiler Vent/Combustion Air Piping
21
IV. Venting B. CPVC/PVC Venting (continued)
Table 8: Vent/Combustion Air Pipe Length – Two-Pipe Direct Vent System Options CPVC/PVC Polypropylene (PP) or Polypropylene (PP)/PVC Stainless Steel/PVC or Galvanized Steel)
Boiler
Model
APX399 30 In. 100 Ft. 30 In. 100 Ft.
APX500 30 In. 100 Ft. 30 In. 100 Ft.
APX800 30 In. 200 Ft. 30 In. 200 Ft.
4” Combustion Air Pipe
(Equivalent Length)
Min. Max. Min. Max. Min. Max. Min. Max.
6” Combustion Air Pipe
(Equivalent Length)
4” Vent Pipe
(Equivalent Length)
6” Vent Pipe
(Equivalent Length)
Vent/Combustion Air Equivalent Length Calculation Work Sheet
Combustion Air Vent
90° Elbow(s) PVC (Installer Supplied) 90° Elbow(s) CPVC (Supplied with Boiler)
Nominal
Diameter,
In.
4 13 4 1 13 13 6 22 6 1 22 22
Nominal
Diameter,
In.
4 4.5 4 13 6 7.5 6 22
Nominal
Diameter,
In.
4 1 4 4.5 6 1 6 7.5
* Total Equivalent Length, Ft. (A+B+C) = 30” (2.5 Ft.) Straight Pipe, CPVC (Supplied with Boiler)
* Note: Total Equivalent Length Calculated Value Cannot Exceed Max. Equivalent Length Values shown in Table 8. Vent and Combustion Air Terminals Do Not Count Towards Total Equivalent Length.
Quantity
(Pc)
45° Elbow(s) PVC (Installer Supplied) 90° Elbow(s) PVC (Installer Supplied)
Quantity
(Pc)
Straight Pipe, PVC (Installer Supplied) 45° Elbow(s) PVC (Installer Supplied)
Quantity
(Length,
Ft.)
Equivalent
Length, Ft/Pc
Equivalent
Length, Ft/Pc
Equivalent
Length,
Ft/Ft
Subtotal,
Equivalent
Ft. (A)
Subtotal,
Equivalent
Ft. (B)
Subtotal,
Equivalent
Ft. (C)
Nominal
Diameter,
In.
Nominal
Diameter,
In.
Nominal
Diameter, In.
Nominal
Diameter,
In.
4 2.5 1 2.5 6 2.5 1 2.5
Nominal
Diameter,
In
4 1 6 1
* Total Equivalent Length, Ft. (A+B+C+D+E) =
Quantity
(Pc)
Quantity
(Pc)
Quantity
(Length, Ft.)
Quantity
(Length, Ft.)
Straight Pipe, PVC (Installer Supplied)
Quantity
(Length, Ft.)
Equivalent Length,
Ft/Pc
Equivalent Length,
Ft/Pc
Equivalent Length,
Ft/Ft
Equivalent Length,
Ft/Ft
Equivalent Length,
Ft/Ft
Subtotal,
Equivalent Ft.
(D)
Subtotal,
Equivalent Ft.
(A)
Subtotal,
Equivalent Ft.
(B)
Subtotal,
Equivalent Ft.
(E)
Subtotal,
Equivalent Ft.
(C)
22
IV. Venting B. CPVC/PVC Venting (continued)
e. Clean all vent and combustion air pipe joints
with primer and secure with transition cement (4-oz. bottles of primer and cement are supplied with boiler inside vent carton). Follow application instructions provided on primer and cement bottles.
APX800 Boiler Model:
f. 6” x 6” Two-Pipe CPVC/PVC Vent System
Connector (P/N 102183-03), used on APX800 boiler model, does not have factory installed internal sealing gaskets at both vent and air intake sections and requires use of supplied red RTV silicon sealant to seal vent and combustion air pipes to the connector.
g. Apply a coating of the sealant, at least 1” wide,
onto provided 6” Schedule 40 x 30” long CPVC pipe.
h. Insert the coated end of the CPVC pipe with a
slight twisting motion into the connector vent section and secure by tightening the metal strap.
i. All CPVC vent components supplied with
boiler inside vent carton (6” Schedule 40 x 30” long CPVC pipe and 6” Schedule 80 CPVC 90° Elbow) must be used for near-boiler piping before transitioning to Schedule 40 PVC (ASTM
2665) pipe components for remainder of vent system. The CPVC 30” long straight pipe may be
cut to accommodate desired vent conguration
provided both pieces are used in conjunction with CPVC 90° Elbow before any PVC components are used. Ensure that the CPVC 90°
Elbow is the rst elbow used in the vent system
as it exits the boiler.
Figure 8: Wall Penetration Clearances for PVC Vent Pipe
• PVC vent pipe must be installed in such
way as to permit adequate air circulation around the outside of the pipe to prevent internal wall temperature rising above
ANSI Z21.13 standard specied limit.
• Do not enclose PVC venting – use higher
temperature rated CPVC pipe in enclosed spaces, or, to penetrate combustible or non-combustible walls.
• PVC vent pipe may not be used
to penetrate combustible or non­combustible walls unless all following three conditions are met simultaneously (see Figure 8 “ Wall Penetration Clearances for PVC Vent Pipe”):
- The wall penetration is at least 66 inches from the boiler as measured along the vent
j. Apply a coating of the sealant, at least 1” wide,
onto 6” Schedule 40 PVC combustion air pipe (installer provided).
k. Insert the coated end of the PVC pipe with a
slight twisting motion into the connector air intake section and secure by tightening the metal strap.
l. Clean all vent and combustion air pipe joints
with primer and secure with transition cement (4-oz. bottles of primer and cement are supplied with boiler inside vent carton). Follow application instructions provided on primer and cement bottles.
5. Horizontal Vent Termination
a. Standard Two-Pipe Termination
See Figures 8 through 11.
i. Vent Piping
Running PVC vent pipe inside Enclosures
and thru Walls:
Figure 9A: Direct Vent - Sidewall Terminations
23
IV. Venting B. CPVC/PVC Venting (continued)
Figure 9B: Direct Vent - Sidewall Terminations (Optional)
- The wall is 12” thick or less
- An air space of at least of that shown in Figure 8 is maintained around outside of the vent pipe to provide air circulation
• If above three conditions cannot be
met simultaneously when penetrating a combustible wall, use a single wall thimble [Burnham Commercial part numbers 102181-01 (4”) and 103419-01 (6”)].
• Thimble use is optional for non-
combustible wall.
• Insert thimble into cut opening from outside. Secure thimble outside ange to
wall with nails or screws and seal ID and OD with sealant material.
• When thimble is not used for non-
combustible wall, size and cut wall opening such that a minimal clearance is obtained and to allow easy insertion of vent pipe.
• Apply sealant between vent pipe and
thimble or wall opening to provide weather­tight seal. Sealant should not restrain the expansion of the vent pipe.
• Install Rodent Screen and Vent Terminal
(supplied with boiler). See Figure 10 for
appropriate conguration details.
24
WARNING
All CPVC pipe supplied with boiler vent carton must be used as part of vent system prior to connecting supplied PVC vent terminal.
Methods of securing and sealing terminals to the outside wall must not restrain the thermal expansion of the vent pipe.
ii. Combustion Air Piping
• Do not exceed maximum combustion air
pipe length. Refer to Table 8.
• Size combustion air pipe wall penetration
opening to allow easy insertion of the pipe.
• Install Rodent Screen and Combustion Air
Terminal (supplied with boiler). See Figure
10 for appropriate conguration details.
• Apply sealant between combustion air pipe
and wall opening to provide weather-tight seal.
b. Optional Two-Pipe Snorkel Termination
See Figures 10 and 11.
This installation will allow a maximum of seven (7)
feet vertical exterior run of the vent/combustion air piping to be installed on the CPVC/PVC horizontal venting application.
Figure 10: Rodent Screen Installation
Figure 11: Direct Vent - Optional Sidewall
Snorkel Terminations
IV. Venting B. CPVC/PVC Venting (continued)
NOTICE
Exterior run to be included in equivalent vent/
combustion air lengths.
i. Vent Piping
• After penetrating wall, install a Schedule
40 PVC 90° elbow so that the elbow leg is in the up direction.
• Install maximum vertical run of seven (7)
feet of Schedule 40 PVC vent pipe. See Figure 11.
• At top of vent pipe length install another
PVC 90° elbow so that elbow leg is opposite the building’s exterior surface.
• Install Rodent Screen and Vent Terminal
(supplied with boiler), see Figure 10 for
appropriate conguration.
• Brace exterior piping if required.
ii. Combustion Air Piping
• After penetrating wall, install a Schedule
40 PVC 90 the up direction.
• Install maximum vertical run of seven (7)
feet of Schedule 40 PVC vent pipe. See Figure 11.
• At top of air pipe length install another PVC
90° elbow so that elbow leg is opposite the building’s exterior surface.
• Install Rodent Screen and Combustion Air
Terminal (supplied with boiler), see Figure
10 for appropriate conguration.
• Brace exterior piping if required.
°
elbow so that elbow leg is in
CAUTION
Vertical venting and combustion air roof
penetrations (where applicable) require the use of roof ashing and storm collar, which are not
supplied with boiler, to prevent moisture from entering the structure.
- Install storm collar on vent pipe
immediately above ashing. Apply
Dow Corning Silastic 732 RTV Sealant between vent pipe and storm collar to provide weather-tight seal.
• Install Rodent Screen and Vent Terminal
(supplied with boiler), see Figure 10 for
appropriate conguration.
• Brace exterior piping if required.
WARNING
All CPVC pipe and elbow supplied with boiler vent carton must be used as part of vent system prior to connecting supplied PVC vent terminal.
Do not operate boiler without the rain cap over vent pipe in place.
ii. Combustion Air Piping
• Locate combustion air termination on the
same roof location as the vent termination to prevent nuisance boiler shutdowns. Combustion air terminal can be installed closer to roof than vent.
6. Vertical Vent Termination
a. Standard Two-Pipe Termination Refer to Figures 10, 12 and 13.
i. Vent Piping
• Install re stops where vent passes through oors, ceilings or framed walls. The re
stop must close the opening between the vent pipe and the structure.
• Whenever possible, install vent straight
through the roof. Refer to Figures 12 and
13.
- Size roof opening to maintain minimum
clearance of 1" from combustible materials.
- Extend vent pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Additional vertical distance for expected snow accumulation. Provide brace as required.
Figure 12: Direct Vent - Vertical Terminations
25
IV. Venting B. CPVC/PVC Venting (continued)
Figure 13: Direct Vent - Vertical Terminations
with Sloped Roof
Extend vent/combustion air piping to maintain minimum vertical (‘X’) and minimum horizontal (‘Y’) distance of twelve (12) inches (18 inches Canada) from roof surface. Allow additional vertical (‘X’) distance for expected snow accumulation.
• Size roof opening to allow easy insertion
of combustion air piping and allow proper
installation of ashing and storm collar
to prevent moisture from entering the structure.
- Use appropriately designed vent ashing
when passing through roofs. Follow
ashing manufacturers’ instructions for
installation procedures.
- Extend combustion air pipe to maintain minimum vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required.
- Install storm collar on combustion
air pipe immediately above ashing.
Apply Dow Corning Silastic 732 RTV Sealant between combustion air pipe and storm collar to provide weather-tight seal.
• Install Rodent Screen and Combustion
Air Terminal (supplied with boiler), see
Figure 10 for appropriate conguration.
• Brace exterior piping if required.
C. Polypropylene Venting
Apex boilers have been approved for use with
polypropylene vent system.
It is an installing contractor responsibility to
procure listed below polypropylene vent system pipe
and related components.
Polypropylene vent system manufactures are listed
below:
Approved Polypropylene Vent System Manufacturers
Make Model
PolyPro Single Wall Rigid Vent
M&G/DuraVent
Centrotherm
Eco Systems
PolyPro Flex Flexible Vent (APX399 and
APX500)
InnoFlue SW Rigid Vent Flex Flexible Vent (APX399 and APX500)
NOTE: Do not mix vent components from approved manufacturers.
M&G/DuraVent PolyPro Single Wall Rigid Vent
and PolyPro Flex Flexible Vent comply with the requirements of ULC-S636-08 ‘Standard for Type BH Gas Venting Systems’.
Centrotherm Eco Systems InnoFlue SW Rigid Vent
and Flex Flexible Vent comply with the requirements of UL 1738 ‘Standard for Safety for Venting Systems’ and ULC-S636-08 ‘Standard for Type BH Gas Venting Systems’.
For polypropylene vent system installation details refer
to an approved manufacturer either Rigid Single Wall Polypropylene Vent Installation Instructions, or Flexible Polypropylene Vent Installation Instructions provided
with a manufacturer specic kits. See Tables 9 and 10.
Refer to Table 8 ‘Vent/Combustion Air Pipe Length –
Two-Pipe Direct Vent System Options’ for minimum and maximum listed equivalent length values.
All terminations must comply with listed options for
two-pipe venting system. See Figures 8 thru 12 for details.
26
IV. Venting C. Polypropylene Venting (continued)
Table 9: Approved Polypropylene Pipe, Fittings and Terminations - M&G/DuraVent
Boiler Model
APX399
APX500 APX800 6PPS-06PVCM-6PPF 150 mm N/A 6PPS-LBC 6PPS-E90B N/A
Male Boiler Adapter,
PVC to PP
4PPS-04PVCM-4PPF 100 mm 100 mm 43PPS-LB 43PPS-TB 4PPS-FK
Rigid Pipe Flex Pipe
Table 10: Approved Polypropylene Pipe, Fittings and Terminations - Centrotherm Eco
Boiler Model
APX399
APX500
APX800
Male Boiler Adapter,
PVC to PP
ISAA0404
ISSAL0404
ISAA0606
ISSAL0606
Rigid Pipe Flex Pipe
110 mm 110 mm IANS04 ISTT0420
160 mm N/A IANS06 ISTT0620 N/A
M&G / DuraVent Part Numbers/Sizes
Pipe Joint
Locking Band
Centrotherm Eco Part Numbers/Sizes
Pipe Joint
Locking Band
Side Wall
Termination Tee
Side Wall
Termination Tee
Chimney Kit for
Venting Only
Chimney Kit for
Venting Only
IFCK0425
and
IFCK0435
When using exible polypropylene vent pipe (liner):
• Flexible pipe must be treated carefully and stored at
temperatures higher than 41°F (5°C).
• Do not bend or attempt to install exible pipe if
it has been stored at lower ambient temperature without allowing the pipe to warm up to a higher
temperature rst.
CAUTION
Bending or attempting to install exible pipe if it
has been stored at ambient temperature below 41°F (5°C) will cause material to become brittle and lead to cracks.
When exible polypropylene pipe (liner) is
used for combustion product venting, it must not be installed at an angle greater than 45 degrees from vertical plane. This will insure
proper condensate ow back towards the boiler.
CAUTION
Do not install exible polypropylene pipe at an
angle greater than 45 degrees from vertical plane when used for combustion product venting. Failure to do so will result in improper condensate drainage towards the boiler and possible
subsequent vent pipe blockage.
• When exible polypropylene pipe (liner) is used
for combustion air supply to a boiler, the pipe (liner) can be installed in vertical or horizontal position.
Follow flexible polypropylene pipe (liner) manufacturer specic installation instructions
regarding application/listing, permits, minimum clearances to combustibles; installation details
(proper joint assembly, pipe support and routing,
gasket and tting installation, optional tooling
availability/usage, routing thru masonry chimney for combustion product venting or, combination of combustion product venting and combustion air supply).
When there is a conflict between flexible polypropylene pipe (liner) manufacturer installation instructions and Apex boiler Installation, Operating and Service Instructions, the more restrictive instructions shall govern.
Apex Boiler Two-Pipe Vent System Connector Field
Modication Procedure To Accept Polypropylene
Vent Piping:
Apex boilers are factory supplied with a model-specic
boiler two-pipe CPVC/PVC vent system connector
shipped within a model-specic boiler CPVC gasketed
vent kit carton.
Locate and remove a model-specic boiler two-pipe
CPVC/PVC vent system connector.
When using M&G/DuraVent polypropylene pipe for
combustion product venting and/or air supply, male PVC to PP boiler adapter (4PPS-04PVCM-4PPF or 6PPS-06PVCM-6PPF as applicable) is installed into the two-pipe vent system connector vent or combustion air supply port as follows (see Figure 14):
1) APX399 and APX500 models - Apply provided dielectric grease (grease pouch taped to the vent system connector) all around to the vent or air connection inner red silicon gasket.
2) APX399 and APX500 models - Push and twist PVC to PP boiler adapter (4PPS-04PVCM-4PPF) into two-pipe vent system connector vent connection or air supply port until bottomed out.
27
IV. Venting C. Polypropylene Venting (continued)
Figure 14: Vent System Field Modication to Install PVC to PP Adapter (M&G/DuraVent Shown)
3) Tighten the worm band clamp screw to secure PVC to PP boiler adapter.
4) Do not install PVC to PP boiler adapter at the lower combustion air supply port of the two-pipe vent system connector when using PVC pipe for combustion air supply to boiler.
5) APX800 model - Apply a coating of supplied red RTV silicon sealant, at least 1” wide, to PVC to PP boiler adapter (6PPS-06PVCM-6PPF) male end,
when used for combustion product venting.
If polypropylene pipe is also used for combustion air
supply, application of the silicon sealant to PVC to PP boiler adapter (6PPS-06PVCM-6PPF) male end is not required.
6) APX800 model - Push and twist PVC to PP boiler adapter (6PPS-06PVCM-6PPF) into two-pipe vent system connector vent port or air supply port until bottomed out.
7) Tighten the worm band clamp screw to secure PVC to PP boiler adapter.
8) Do not install PVC to PP boiler adapter at the lower combustion air supply port of the two-pipe vent system connector when using PVC pipe for combustion air supply to boiler.
When using Centrotherm Eco polypropylene pipe
for combustion product venting and/or air supply PVC to PP boiler adapter (ISAA0404 or ISAAL0404 and ISAA0606 or ISAAL0606 as applicable) is installed into the two-pipe vent system connector vent or combustion air supply port as follows (see Figure 14):
9) APX399 and APX500 models - Apply provided dielectric grease (grease pouch taped to the vent system connector) all around to the vent or air connection inner red silicon gasket.
28
10) APX399 and APX500 models - Push and twist PVC to PP boiler adapter (ISAA0404 or ISAAL0404) into two-pipe vent system connector vent connection or air supply port until bottomed out.
11) Tighten the worm band clamp screw to secure PVC to PP boiler adapter.
12) Do not install PVC to PP boiler adapter at the lower combustion air supply port of the two-pipe vent system connector when using PVC pipe for combustion air supply to boiler.
13) APX800 model - Apply a coating of supplied red RTV silicon sealant, at least 1” wide, to PVC to PP boiler adapter (ISAA0606 or ISAAL0606) male end, when used for combustion product venting.
If polypropylene pipe is also used for combustion air
supply, application of the silicon sealant to PVC to PP boiler adapter (ISAA0606 or ISAAL0606) male end is not required.
14) APX800 model - Push and twist PVC to PP boiler adapter (ISAA0606 or ISAAL0606) into two-pipe vent system connector vent port or air supply port until bottomed out.
15) Tighten the worm band clamp screw to secure PVC to PP boiler adapter.
16) Do not install PVC to PP boiler adapter at the lower combustion air supply port of the two-pipe vent system connector when using PVC pipe for combustion air supply to boiler.
Optional Two-pipe Vertical Venting Installation –
Running Flexible Polypropylene Vent (Liner)
Thru Unused Chimney Chase (see Figure 15).
Apex APX399 and APX500 boilers are approved for
vertical venting by installing Flexible Vent in an UNUSED masonry chimney/chase and supplying combustion air thru a separate wall or roof air intake terminal.
IV. Venting C. Polypropylene Venting (continued)
Venting of Other Appliances (or Fireplace) into Chase or Adjacent Flues Prohibited!
Figure 15: Flexible Vent in Masonry
Chimney with Separate Air Intake
WARNING
Follow installation instructions included by the original polypropylene venting component manufacturers, M&G/DuraVent or Centrotherm, whichever applicable.
Flexible Polypropylene Vent must be installed in an UNUSED chimney. A chimney, either single or
multiple ue type, is considered UNUSED when none of the ues is being used for any appliance
venting.
Where one of the multiple ues is being used for an appliance venting, the exible vent installation is not permitted thru any of adjacent ues.
Observe all precautions outlined in either M&G/DuraVent or Centrotherm instructions in addition to those outlined in these instructions.
Examine all components for possible shipping damage prior to installation. Proper joint assembly is essential for safe installation. The venting system must be free to expand and contract and supported in accordance with installation
instructions included by the original polypropylene venting component manufacturers, M&G/DuraVent or Centrotherm, whichever applicable.
Do not mix vent components or joining methods for different vent systems.
Where a conict arises between M&G/DuraVent or Centrotherm instructions and these instructions, the
more restrictive instructions shall govern.
Do not apply thermal insulation to vent pipe and ttings.
Do not obtain combustion air from within the building.
29
IV. Venting D. Stainless Steel Venting (continued)
D. Stainless Steel Venting
CAUTION
Vent systems made by Heat Fab, Protech and Z-Flex rely on gaskets or proper sealing. When these vent systems are used, take the following precautions:
• Make sure that gasket is in position and un-
damaged in the female end of the pipe.
• Make sure that both the male and female
pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent
manufacturer in accordance with their in­ structions. When pipe is cut, cut end must
be square and carefully de-burred prior to
assembly.
WARNING
All condensate that forms in the vent must be able to drain back to the boiler.
1.
Vent Length Restrictions
a. Vent length restrictions are based on equivalent
length of vent/combustion air pipe (total length of straight pipe plus equivalent length of
ttings). Maximum vent/combustion air lengths
are listed in Table 8. Do not exceed maximum vent/combustion air lengths. Do not include vent/combustion air terminals in equivalent feet calculations. See “Combustion Air/Vent, Equivalent Length Work Sheet”.
b. The vent termination location is restricted as
per ‘General Guidelines’, Section A.5. (Refer to Figure 4)
c. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or equivalent for the vent collar. Air inlet piping sections are sealed with any general-purpose silicone sealant such as GE RTV102. PVC air inlet piping sections are connected with PVC cement.
d. Longitudinal welded seams should not be placed
at the bottom of horizontal sections of exhaust pipe.
e. Do not drill holes in vent pipe.
f. Do not attempt to mix vent components of
different vent system manufacturers.
2. Near Boiler Connection
To install the stainless steel vent adapter
[P/N 102220-01 (4”)]:
a. Push the stainless steel vent adapter onto the
CPVC/PVC connector with a slight twisting motion. Make sure that the stainless steel vent adapter is inserted at least 1” (refer to Figure 16).
b. Secure the adapter to the CPVC/PVC connector
by tightening the metal strap.
To install the stainless steel vent adapter [P/N 103285-01 (6”)]:
c. Apply a coating of supplied red RTV silicone
sealant, at least 1” wide, all around male end of the stainless steel vent adapter.
d. Afterwards, insert the male end of the adapter
with a slight twisting motion into vent section of installed two-pipe CPVC/PVC vent connector.
e. Secure the adapter to the two-pipe CPVC/PVC
vent connector by tightening the metal strap.
System Assembly
3.
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at vent connector at boiler and work towards vent termination.
b. Refer to Tables 11A and 11B for approved
AL29C Vent Systems.
c. Do not exceed maximum Vent/Combustion air
length. Refer to Table 8.
d. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining and using the primer and the cement.
e. Assemble the air intake system using either
galvanized or PVC pipe.
i. If PVC piping is used, use PVC cement
to assemble the PVC intake system components. See Part B for air intake installation instructions.
ii. If galvanized piping is used, use at least two
sheet metal screws per joint. Seal the outside of all joints.
4.
Horizontal Vent Termination
a. Standard Two-Pipe Termination Refer to Figure 9A.
i. Vent Termination
• Use Burnham Commercial stainless
exhaust terminal [P/N 100184-01 (4”)]. The outer edge of this terminal must be between 6” and 12” from the surface of the wall. The joint between the
terminal and the last piece of pipe must be outside of the building.
• Male end of terminal will t into the
female end of any of the approved stainless vent systems.
30
Loading...
+ 102 hidden pages