Burnham Alpine Series, ALP080, ALP105, ALP150, ALP210 Supplemental Instructions

...
Supplemental Instructions
Modular Installation
Alpine™ Series Gas Boiler
These instructions supplement information contained in Installation, Operating and Service Instructions for Alpine™ Gas-Fired Boiler (IO&S), Part No. 101602-01. Follow Supplemental Instructions and details outlined below until directed otherwise.
WARNING
Prior to attempting any service on this boiler, read, understand and follow all instructions as outlined in this supplement and also the Installation, Operating and Service Instructions which was provided with the boiler.
GENERAL INFORMATION
These instructions contain supplemental information related only to Modular Installations on the Alpine™ boiler.
This information is also found in the IO&S manual furnished with the boiler. Refer to IO&S manual for all non­modular related installation instructions. Where applicable, substitute these instructions, paragraph for paragraph, for the information outlined in the IO&S manual..
Modular Installation
A. General Guidelines
1. Read and follow all venting, combustion air, water piping, gas piping and electrical instructions contained in the Installation, Operating and Service Instructions unless otherwise instructed in this section.
2. Consult Local Building Codes or National Fuel Gas Code, NFPA 54/ANSI Z222.3 for restrictions and instructions on modular boiler installations.
B. Venting
1. Each boiler must have an individual vent pipe. Refer to Venting Section of the Installation, Operating and Service Instructions for venting guidelines and options.
WARNING
Do not manifold vent pipes together.
2. The maximum vent length for each boiler is sixty (60) equivalent feet.
3. The minimum horizontal distance between vent terminations is one (1) foot. Additional horizontal distance is desirable to avoid frost damage to the building. Vent terminations must be at least twelve (12) inches above the ground plus the expected snow accumulation.
102170-01-6/08
CAUTION
Installing multiple vent terminations close together promotes frost buildup on buildings. To minimize this possibility, extend the distance from the building to the end of the vent termination and increase the horizontal distance between terminations.
4. Multiple vertical vent pipes may be piped through a common conduit or chase so that one roof penetration may be made. Each vent termination must be one (1) foot from other terminations.
C. Air Intake Piping
1. Each boiler must have an individual air intake pipe, refer to Venting Section of the Installation, Operating and Service Instructions for Air Intake Guidelines and Options.
2. The maximum air intake length for each boiler is sixty (60) equivalent feet.
3. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet (or visa versa) if installation conditions do not allow alternate arrangement.
D. Water Piping (See Table S1)
Installing a low water cutoff in the system piping of
modular systems is strongly recommended and may be required by Local Codes.
1
Figure S1: Modular Boiler Water Piping
2
Loading...
+ 1 hidden pages