12. DISPOSAL OF THE PRODUCT ........................................................... 31
Type 8045
Warns against material damage.
Failure to observe this warning may result in damage to the device
About the Quickstart
1. ABOUT THE QUICKSTART
The quickstart describes the life cycle of the device. Please keep this
manual in a safe place, accessible to all users and any new owners.
Important safety information.
Respect the safety instructions. Study in particular the chapters
entitled Intended Use and Basic Safety Instructions.
• The quickstart must be read and understood.
The quickstart explains how to install, set, and start-up the device.
A detailed description of the device can be found in the related
operating instructions on the elivered CD.
1.1. Symbols used
danger
Warns against an imminent danger.
• Failure to observe this warning can result in death or in serious
injury.
Warning
Warns against a potentially dangerous situation.
• Failure to observe this warning can result in serious injury or even
death.
attention
Warns against a possible risk.
• Failure to observe this warning can result in substantial or minor
injuries.
note
•
or system.
Indicates additional information, advice or important
recommendations.
Refers to information contained in this manual or in other
documents.
→ Indicates a procedure to be carried out.
1.2. Definition of the word "device"
The word "device" used within this manual refers to the flowmeter
type 8045.
English
3
Type 8045
Intended use
2. INTENDED USE
Use of the device that does not comply with the instructions
could present risks to people, nearby installations and the
environment.
• The 8045 flowmeter is intended exclusively to measure flow rate
in liquids.
• This device must be protected against electromagnetic interference, ultraviolet rays and, when installed outdoors, the effects of
climatic conditions.
• This device must be used in compliance with the characteristics
and commissioning and use conditions specified in the contractual documents and in the operating instructions.
• Requirements for the safe and proper operation of the device
are proper transport, storage and installation, as well as careful
operation and maintenance.
• Only use the device as intended.
→ Observe any existing restraints when the device is exported.
3. BASIC SAFETY INFORMATION
This safety information does not take into account:
• any contingencies or occurences that may arise during installation,
use and maintenance of the devices.
• the local safety regulations for which the operating company
is responsible including the staff in charge of installation and
maintenance.
Danger due to high pressure in the installation.
• Stop the circulation of fluid, cut off the pressure and drain the
pipe before loosening the process connections.
Danger due to electrical voltage.
• Shut down the electrical power source of all the conductors and
isolate it before carrying out work on the system.
• Observe all applicable accident protection and safety regulations for electrical equipment.
Danger due to high temperatures of the fluid.
• Use safety gloves to handle the device.
• Stop the circulation of fluid and drain the pipe before loosening
the process connections.
Danger due to the nature of the fluid.
• Respect the prevailing regulations on accident prevention and
safety relating to the use of aggressive fluids.
4
English
Type 8045
Basic safety information
Various dangerous situations
To avoid injury take care:
• not to use the device for the measurement of gas flow rates.
• not to use the device in explosive atmospheres.
• not to use the device in an environment incompatible with the
materials it is made of.
• not to subject the device to mechanical loads (e.g. by placing
objects on top of it or by using it as a step).
• not to make any external or internal modifications to the device.
• to prevent any unintentional power supply switch-on.
• to ensure that installation and maintenance work are
carried out by qualified, authorised personnel in possession of
the appropriate tools.
• to guarantee a defined or controlled restarting of the process,
after a power supply interruption.
• to use the device only if in perfect working order and in compliance with the instructions provided in the operating instructions.
• to observe the general technical rules when installing and using
the device.
note
The device may be damaged by the fluid in contact with.
• Systematically check the chemical compatibility of the component materials of the device and the fluids likely to come into
contact with it (for example: alcohols, strong or concentrated
acids, aldehydes, alkaline compounds, esters, aliphatic compounds, ketones, halogenated aromatics or hydrocarbons,
oxidants and chlorinated agents).
note
Elements / Components sensitive to electrostatic discharges
• This device contains electronic components sensitive to electrostatic discharges. They may be damaged if they are touched by
an electrostatically charged person or object. In the worst case
scenario, these components are instantly destroyed or go out of
order as soon as they are activated.
• To minimise or even avoid all damage due to an electrostatic
discharge, take all the precautions described in the EN 613405-1 and 5-2 norms.
• Also ensure that you do not touch any of the live electrical
components.
English
5
Type 8045
1
25
34
General information
4. GENERAL INFORMATION
4.1. Manufacturer's address and
international contacts
To contact the manufacturer of the device, use following address:
Bürkert SAS
Rue du Giessen
BP 21
F-67220 TRIEMBACH-AU-VAL
You may also contact your local Bürkert sales office.
The addresses of our international sales offices are available on the
internet at: www.burkert.com
4.2. Warranty conditions
The condition governing the legal warranty is the conforming use of
the 8045 in observance of the operating conditions specified in this
manual.
4.3. Information on the Internet
You can find the user manuals and technical data sheets regarding
the type 8045 at: www.burkert.com
5. DESCRIPTION OF THE NAME
PLATE
FLOW 8045 SST LONG SUPPLY: 18-36V 300 mA
DO1: 5-36V= 100mA DO2/3:250V 3A Max
DI1: 18-36V= 10mA IP65 Fluid: PN16:-15/110°C
S/N 11 162
Made in France
00449673 W43M
13
10
67891112
FLOW
14
6
English
Type 8045
Technical data
1. Measured value and type of the device
2. Specification of the flow sensor
3. Specification of the DO1 digital output
4. Specifications of the relay outputs DO2 and DO3
5. Electrical power supply and current consumption
6. Manufacturing code
7. Conformity logo
8. Warning: Before using the device, take into account the tech-
nical specifications described in these operating instructions.
9. Fluid temperature range and fluid nominal pressure
10. Protection class of the device
11. Specification of the DI1 digital input
12. Serial number
13. Order code
14. Shows the flow direction
Fig. 1: Name plate of the 8045 flowmeter
6. TECHNICAL DATA
6.1. Conditions of use
Ambient temperature-10 to +60 °C
Air humidity< 85%, non condensated
Height above see levelmax. 2000 m
Protection class acc.
to EN 60529
6.2. Conformity to standards and
directives
The device conforms to the EC directives through the following
standards:
• EMC: EN 61000-6-2, EN 61000-6-3
• LVD: EN 61 010-1
• Vibration: EN 60068-2-6
• Shock: EN 60068-2-27
Pressure: article 3§3 of the Pressure Directive 97/23/CE. Acc. to
the Pressure Directive 97/23/CE: the device can only be used in the
following cases (depending on the max. pressure, the DN of the pipe
and the fluid)
Type of fluidConditions
Fluid group 1, par. 1.3.aForbidden
IP65, device wired and cable glands
tightened and cover lid screwed tight.
English
7
Type 8045
Technical data
Type of fluidConditions
Fluid group 2 par. 1.3.a
Fluid group 1 par. 1.3.bPNxDN ≤ 2000
Fluid group 2 par. 1.3.b
DN ≤ 32
or DN > 32 and PNxDN ≤ 1000
DN ≤ 200
or PN ≤ 10
or PNxDN ≤ 5000
6.3. Mechanical data
Part
Housing / sealPC / NBRBlack PPA / NBR
Cover with lid /
seal
Front foilPolyester
M20x1,5 cable
glands / seal
ScrewsStainless steel
NutPCPPA
Flow sensor
(exposed to the
fluid)
Material (8045 with
flow sensor in PVDF)
PC / siliconePSU / silicone
PA / neoprene
PVDF Stainless steel 316L
Material (8045
with flow sensor in
stainless steel)
(DIN 1.4404)
Part
SealFKM8045 with a G2" nut:
Earth ring of the
flow sensor
Electrodes holder -PEEK
ElectrodesStainless steel 316L (DIN 1.4404) or Alloy
Material (8045 with
flow sensor in PVDF)
Stainless steel 316L
(DIN 1.4404) or Alloy
C22
Material (8045
with flow sensor in
stainless steel)
FKM
-
C22
6.4. General data
Min. fluid conductivity20 µS/cm
Fluid temperature
• 8045 with flow sensor
in PVDF
• 8045 with flow sensor in
stainless steel
The fluid temperature may be
restricted by the fluid pressure, the
material the flow sensor is made of
and the material the S020 fitting used
is made of.
• 0 to +80 °C
• -15 to +110 °C
8
English
Type 8045
A
A
Technical data
Fluid pressure
The fluid pressure may be restricted
by the fluid temperature, the material
the flow sensor is made of, the
material the S020 fitting used is made
of and the DN of the fitting used.
• 8045 with flow sensor
• PN10
in PVDF
• 8045 with flow sensor in
• PN16
stainless steel
P (bar)
10
9
8
7
PVC + PP
6
5
4
3
2
1
0
PVC (PN10)
0+20+40+60+80
PVDF (PN10) /
PP (PN10)
T (°C)
Metal
A: range of use
Fig. 2: Fluid pressure /temperature dependency for a 8045 with
PVDF flow sensor and a fitting S020 in metal, PVC, PVDF
or PP
P (bar)
16
15
14
13
12
11
PVDF
Metal
(PN16)
1)
DN100 for measuring
devices with a clamp con-
nection (PN10)
10
9
8
7
PVC + PP
PVDF (PN10)
6
5
4
3
2
1
0
-200+20 +40 +60 +80 +100 +120
PVC (PN10)
PP (PN10)
T (°C)
1)
Except DN100 for measuring devices with a clamp connection
A: range of use
Fig. 3: Fluid pressure /temperature dependency for a 8045 with
stainless steel flow sensor and a fitting S020 in metal,
PVC, PVDF or PP
English
9
Type 8045
Technical data
6.5. Electrical data
Power supply• 18-36 V DC, filtered and
regulated
• oscillation rate: ±5 %
Current consumption300 mA max. (at 18 V DC)
Transistor output DO1
• type
• function
• frequency
• Electrical data
• duty cycle if f > 2 Hz
• min. pulse duration if
f < 2 Hz
• protections
• NPN / PNP (wiring dependent),
open collector
• pulse output (by default), user
configurable
• 0-250 Hz
• 5-36 V DC, 100 mA max.
• 1/2
• 250 ms
• galvanically isolated, and
protected against overvoltages, polarity reversals and
short-circuits
Relay outputs (DO2 and
DO3)
• operating
• electrical data of the load
• max. breaking capacity
• life span
Current output AO1
• specification
• max. loop impedance
Digital input (DI1)
• supply voltage
• input impedance
• min. pulse duration
• protections
• hysteresis (by default), configurable, normally open
• 250 V AC / 3 A or 30 V DC /
3 A (resistive load)
• 750 VA (resistive load)
• min. 100000 cycles
• 4-20 mA, sink or source (wiring
dependent), 22 mA to indicate
a fault
• 1300 W at 36 V DC, 1000 W at
30 V DC, 700 W at 24 V DC,
450 W at 18 V DC
• 18-36 V DC
• 15 kW
• 200 ms
• galvanically isolated, and protected against polarity reversals
and voltage spikes
10
English
Type 8045
Installation and wiring
6.6. Electrical connection
Type of connectionThrough two M20x1,5 cable
glands
Cable specifications
• cable type
• Cross section
• Diameter of each cable:
- if only one cable is used
per cable gland
- if two cables are used per
cable gland
• shielded
• 0,5 to 1,5 mm
- 6...12 mm
- 4 mm, with the supplied
multi-way seal
2
7. INSTALLATION AND WIRING
7.1. Safety instructions
danger
Risk of injury due to high pressure in the installation.
Risk of injury due to electrical voltage.
Risk of injury due to high fluid temperatures.
Risk of injury due to the nature of the fluid.
Warning
Risk of injury due to non-conforming installation.
• The electrical and fluid installation can only be carried out by
qualified and skilled staff with the appropriate tools.
• Install appropriate safety systems (correctly rated fuse and/or
circuit-breaker);
• Respect standard NF C 15-100 / IEC 60364.
• Respect the assembly instructions for the fitting used.
Risk of injury due to unintentional switch on of power supply
or uncontrolled restarting of the installation.
• Take appropriate measures to avoid unintentional activation of
the installation.
• Guarantee a set or controlled restarting of the process subsequent to any intervention on the device.
English
11
Protect this device against electromagnetic interference,
ultraviolet rays and, when installed outdoors, the effects of
the climatic conditions.
7.2. Recommandations for installing
the 8045 on the pipe
→ Choose an S020 fitting appropriate to the velocity of the fluid
inside the pipe.
→ Install the device on the pipe in such a way that the upstream
and downstream distances are respected according to the
design of the pipes, refer to standard EN ISO 5167-1 and Fig.
4 :
Type 8045
Installation and wiring
flow direction
50 x DN 5 x DN
With control valvePipe with 2 elbows at 90° in 3
40 x DN 5 x DN
dimensions
25 x DN 5 x DN20 x DN 5 x DN
Pipe with 2 elbows at 90°Pipe with 1 elbow at 90° or 1
T-piece
12
18 x DN 5 x DN15 x DN 5 x DN
With pipe expansionWith pipe reduction
Fig. 4: Upstream and downstream distances depending on the
design of the pipes.
English
Type 8045
Installation and wiring
→ Respect the following additional mounting conditions to ensure
that the measuring device operates correctly:
- Preferably install the device at a 45° angle to the horizontal centre of
the pipe to avoid having deposits on the electrodes and false measurements due to air bubbles (see Fig. 5);
45°
45°
Fig. 5: Mounting angle on the pipe
- Ensure that the pipe is always filled in the section around the
device (see Fig. 6).
- When mounting vertically ensure that the flow direction is in an
upward direction (see Fig. 6).
Horizontal mounting
CorrectIncorrect
Vertical mounting
flow direction
CorrectIncorrect
Fig. 6: Filling of the pipe
- Prevent the formation of air bubbles in the pipe in the section
around the device (see Fig. 7).
- Always mount the device upstream a possible injection point
in the pipe of a high-conductivity fluid (for example: acid, base,
saline,...).
English
13
Correct
CorrectIncorrect
Fig. 7: Air bubbles within the pipe
Incorrect
flow direction
→ If necessary, use a flow conditioner to improve measurement
precision.
Type 8045
Installation and wiring
7.3. Installation into the pipe of a
8045 with a G2'' nut
In order to ensure a high accuracy of the measurements and
good stability of the „flow zero“ point, install the device into
the processed medium at least 24 H before calibration.
→ Install the S020 fitting into the pipe taking into account the rec-
ommendations in chap. 7.2.
→ Check that there is a seal on the fitting and that it is not damaged.
Replace the seal if necessary.
→ Check that there is a seal (see mark 6, Fig. 8) on the flow sensor.→ Insert the nut (see mark 3, Fig. 8) on the fitting.→ Insert the snap ring (mark 2 Fig. 8) into the groove (mark 5 Fig.
8).
→ Position the arrow on the side of the device in the direction of the
flow: the totalizers will increment.
→ Insert the device (mark 1 Fig. 8) into the fitting.→ Tighten the nut (mark 3, Fig. 8) by hand on the device.
14
English
Type 8045
Installation and wiring
1
FLOW
→ Make sure that the polarizing pin (mark 4 Fig. 9) is on the fitting.→ Insert the device (mark 1 Fig. 9) into the fitting. Position the
arrow on the side of the device in the direction of the flow: the
totalizers will increment.
→ Tighten by hand the clamp collar (mark 2 Fig. 9).→ Charge the pipe to make sure the installation is tight.
6
Electrodes
2
3
5
4
flow direction
Fig. 8: Installation into the pipe of a 8045 with a G2'' nut
7.4. Installation into the pipe of a
8045 with a clamp connection
In order to ensure a high accuracy of the measurements and
good stability of the „flow zero“ point, install the device into
the processed medium at least 24 H before calibration.
→ Install the S020 fitting into the pipe taking into account the rec-
ommendations in chap. 7.2.
→ Install the seal (mark 3 Fig. 9) on the S020 fitting.
1
2
4
flow direction
3
Fig. 9: Installation into the pipe of a 8045 with a clamp
connection
English
15
Type 8045
Installation and wiring
7.5. Wiring
danger
Risk of injury due to electrical voltage.
• Shut down the electrical power source of all the conductors and
isolate it before carrying out work on the system.
• Observe all applicable accident protection and safety regulations for electrical equipment.
• Use a high quality electrical power supply (filtered and
regulated).
• Make sure the installation is equipotential. See chap.
7.5.1.
• Use shielded cables with a temperature limit of 80 °C
minimum.
• Do not install the cables near high voltage or high frequency cables; If this cannot be avoided, observe a min.
distance of 30 cm.
• Protect the power supply by means of a 300 mA fuse and
a switch.
• Protect the relays by means of a max. 3 A fuse and a
circuit breaker (depending on the process).
• Do not apply both a dangerous voltage and a safety extralow voltage to the relays.
Insert the supplied stopper gasket into the unused cable
gland to ensure the tightness of the device.
If two cables are used in the same cable gland, first insert
the supplied multi-way seal.
To wire the device:
→ Loosen the screw from the lid.→ Flip the lid.→ Loosen the 4 screws from the cover of the housing.→ Remove the cover.→ Loosen the nuts of the cable glands.→ Insert the cable through the nut then through the cable gland.→ Make sure the earth cable coming from the housing and, on a
version with stainless steel sensor, the cable coming from the
flow sensor, are connected as shown in Fig. 15, chap. 7.5.2.
→ Wire acc. to chap. 7.5.1 to 7.5.3.
7.5.1. Equipotentiality of the installation
To ensure the equipotentiality of the installation (power supply device - fluid):
→ Connect together the various earth spots in the installation to
eliminate the potential differences that may occur between different earthes.
→ Observe faultless earthing of the shield of the power supply
cable, at both ends.
16
English
Type 8045
Installation and wiring
→ Connect the negative power supply terminal to the earth to sup-
press the effects of common mode currents. If this connection
cannot be made directly, a 100 nF/50 V capacitor can be fitted
between the negative power supply terminal and the earth.
→ Special attention has to be paid if the device is installed on
plastic pipes because there is no direct earthing possible.
Proper earthing is performed by earthing together the metallic
instruments such as pumps or valves, that are as close as possible to the device. If no such instrument is near the device,
insert metallic earth rings inside the plastic pipes upstream and
downstream the device and connect these parts to the same
earth. The earth rings must be in contact with the fluid.
Power cable shield
Power supply
18-36VDC
+
-
1)
Pipes in plastic
Valve, pump,... (or earthing rings,
not provided, inserted into the
pipe)
1)
If a direct earth connection is not possible, fit a 100 nF / 50 V
capacitor between the negative power supply terminal and the earth.
Fig. 10: Equipotentiality skeleton diagram with pipes in plastic
English
17
Type 8045
Installation and wiring
Power cable shield
Power supply
18-36VDC
+
-
1)
Metal pipe
1)
If a direct earth connection is not possible, fit a 100 nF / 50 V
capacitor between the negative power supply terminal and the
earth.
Fig. 11: Equipotentiality skeleton diagram with pipes in metal
7.5.2. Terminal assignment and use of the
selectors
1
A
2
4 pin ribbon ca-
ble coming from
the flow sensor
Selector
Selector
B
4
5
A
: see Fig. 13
B
: see Fig. 14
CURRENT
OFF ON
DO3
SOURCESINK
DO2
AO1
L+ L-PEP+P-Iout
Supply
18...36 Vdc
PE
-
+
DI1
PULSE
DO1
PE
3
18
English
Type 8045
Installation and wiring
Terminal block 1
Iout: 4-20 mA output (AO1)
L+: V+ (positive voltage)
L-: 0V (power supply ground)
PE: functional earth, wired in the factory (see Fig. 15)
P+: positive transistor output (DO1)
P-: negative transistor output (DO1)
Terminal block 2
PE: shieldings of both the power supply cable and the AO1
and DO1 output cables
Terminal block 3
PE: functional earth of the DI1 digital input
-: negative signal of the DI1 input
+: positive signal of the DI1 input
Terminal block 4: wiring the DO2 relay output
Terminal block 5: wiring the DO3 relay output
Fig. 12: Terminal assignment
A
Use switch
to configure the wiring of the 4-20 mA cur-
rent output in sinking or sourcing mode.
A
CURRENT
SOURCESINK
Wire the current output
in sourcing mode.
Fig. 13: Sink/source switch
B
Use the switch
unauthorized access to the configuration of the device.
to lock/unlock the
CURRENT
SOURCESINK
Wire the current output in
sinking mode.
ENTER
key to prevent
B
OFF ON
ENTER
The
Fig. 14: Switch to lock/unlock the ENTER key
key is unlocked (de-
fault position).
OFF ON
ENTER
The
locked.
key is
English
19
123456
Type 8045
Installation and wiring
7.5.4. Wiring the AO1 current output
For safety reasons, secure the cables using a non-conducting cable clamp.
The 4-20 mA output can be wired in either sourcing or sinking
mode.
Earth cable coming from the housing.
On a version with stainless steel flow sensor, a second cable
is coming from the sensor.
Fig. 15: Connection of the earth wire coming from the housing
(made in the factory)
7.5.3. Wiring the DO2 and DO3 relay
outputs
m
230 VAC
230 VAC
Fig. 16: Wiring of the DO2 and DO3 relay outputs
20
3 A
3 A
English
DO2
DO3
Position the A switch to the right.
PULSE
DO1
(*)
Power supply
18-36 V DC
+
-
PE
4-20mA input at external
device
A
CURRENT
SOURCESINK
+
300 mA
-
I
L+ L-PEP+P-Iout
Supply
AO1
18...36 Vdc
Fig. 17: Wiring of the 4-20 mA output (AO1) in sourcing mode
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth
Type 8045
18-36 V DC
Installation and wiring
Position the A switch to the left.
I
AO1
L+ L-PEP+P-Iout
Supply
18...36 Vdc
300 mA
PULSE
DO1
(*)
+
-
Power supply
PE
4-20mA input at external
device
A
CURRENT
SOURCESINK
+
-
Fig. 18: Wiring of the 4-20 mA output (AO1) in sinking mode
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth
7.5.5. Wiring the DO1 transistor output
18-36 V DC
Power supply
+
-
(*)
300 mA
L+ L-PEP+P-Iout
Supply
AO1
18...36 Vdc
PULSE
DO1
Fig. 19: NPN wiring of the DO1 transistor output
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth
+
5-36 VDC
-
+
-
PE
PLC
English
21
Type 8045
Installation and wiring
18-36 V DC
Power supply
300 mA
+
-
(*)
+
5-36 VDC
-
+
-
PLC
L+ L-PEP+P-Iout
Supply
AO1
18...36 Vdc
PULSE
DO1
PE
Fig. 20: PNP wiring of the DO1 transistor output
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth
7.5.6. Wiring the DI1 digital input
(*)
CURRENT
SOURCESINK
DO3
DO2
AO1
L+ L-PEP+P-Iout
Supply
18...36 Vdc
DI1
PE
-
+
PULSE
DO1
PE
18-36 V DC
+
-
Power supply
Switch
22
English
Type 8045
Adjustment, commissioning
CURRENT
SOURCESINK
DO2
AO1
L+ L-PEP+P-Iout
Supply
18...36 Vdc
PE
-
+
DI1
PULSE
DO1
PE
Power supply
18-36 V DC
+
-
(*)
Switch
8. ADJUSTMENT, COMMISSIONING
8.1. Safety instructions
Warning
Risk of injury due to non-conforming operating.
Non-conforming operating could lead to injuries and damage the
device and its surroundings.
• The operators in charge of operating must have read and understood the contents of these operating instructions.
• In particular, observe the safety recommendations and intended use.
• The device/installation must only be operated by suitably trained
staff.
Warning
DO3
Fig. 21: Possible wirings of the DI1 digital input
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth
Danger due to non-conforming commissioning.
Nonconforming commissioning could lead to injuries and damage
the device and its surroundings.
• Before commissioning, make sure that the staff in charge
have read and fully understood the contents of the operating
instructions.
• In particular, observe the safety recommendations and intended use.
• The device / the installation must only be commissioned by suitably trained staff.
• Before commissioning the device, enter the K factor of the fitting used. See chap. 8.6.
English
23
8.2. Operating levels of the device
The device has two operating levels: the Process level and the Configuration level.
Table 1: Default settings of the device
FunctionDefault valueFunctionDefault value
LANGUAGEEnglishOUTPUT
2+= 0.000K-SENSORKw= 1.000
Not invertedFLOW-W.W-= 0.000
time delay = 0
DO3
Hysteresis
time delay = 0
vated for 30s
W+= 0.000
Type 8045
Adjustment, commissioning
24
English
Type 8045
Adjustment, commissioning
Process level
12.6 L/s
16.45 mA
0......9
Parameters menuTest Menu
ENTER
LANGUAGE
> 5 s
87654 L
UNit
K-FACtOR
OUtPUt
231 L.
0......9
iNPUt
FiLtER
+
0......9
> 2 s
To reset the daily totalizer (identified by
a dot after the volume units).
tOtAL
FREqUENC.
CUt-OFF
BACKLit
1)
Accessible when the device status LED is orange or red.
2)
If the ENTER key is unlocked.
0......9
> 5 s
Configuration level
ENTER
END
0......9
> 2 s
CAL AO1
CALiB 0
FLOw
K-sENsOR
FLOw-w.
sAVE N/Y
END
Information menu
mEAs. OVF
CAL. FAiL
NEG. FLOw
0......9
END
ENTER
or
2)
Process level
1)
English
25
Type 8045
Adjustment, commissioning
8.3. Description of the navigation keys and the state LEDs
26
• Scrolling up the
parameters
• Incrementing the figure
selected
Device state LED: see following table.
English
• Selecting the displayed parameter
• Confirming the settings
Status LED of relay DO3 (LED ON =
contact closed)
Status LED of relay DO2 (LED ON =
contact closed)
• Reading the messages
• Scrolling through the parameters
• Selecting the figure on the left
Type 8045
Adjustment, commissioning
8.4. Using the navigation keys
You want to...Press...
move between parameters within a level or a menu.
access the Parameters menu.
access the Test menu.
access the Information menu.
•
•
ENTER
0......9
0......9
to go to the next parameter.
to go to the previous parameter.
+ simultaneously for 5 s, in the Process level
ENTER
+ +
simultaneously for 5 s, in the Process level
for 2 s, in the Process level, when the device status LED is orange or red.
reset the daily totalizer.
select the displayed parameter.
confirm the displayed value.
modify a numerical value.
0......9
+ simultaneously for 2 s, when the daily totalizer is displayed in the
Process level
ENTER
ENTER
to increase the blinking digit.
•
0......9
to select the digit at the left of the blinking digit.
•
0......9
+ to move the decimal point.
•
English
27
Type 8045
Adjustment, commissioning
8.5. Choosing the display language
When the device is energized for the first time, the display language
is English.
LANGUAGEENGLish
0......9
DEUtsCh
FRANçAis
→ Confirm the displayed
language: The selected
language is immediately active.
itALiANO
EsPANOL
UNit
Fig. 22: Diagram of the "LANGUAGE" parameter of the Parameters
menu
→ If you do not want to adjust another parameter, go to the "END"
parameter of the Parameters menu and press
settings or not and go back to the Process level.
ENTER
to save the
8.6. Entering the K factor of the fitting
used:
The device determines the flow rate in the pipe using the fitting K
factor.
The K factor of the fitting used can be entered here.
The device will use the new K factor as soon as "SAVE
YES" is confirmed when leaving the Parameters menu.
28
English
Type 8045
Adjustment, commissioning
K-FACtORK=10.000
The display shows the K factor of the
fitting, may it have been entered or
determined by a teach-in procedure;
this K factor is currently used by the
device
K=2.8500
→ Enter the K factor (value between 0,0001 and
9999,9) of the fitting used.
→ Confirm the displayed value.
→ Edit the parameter.
OUtPUtVALiD N/Y
REtURN
Is only displayed if the K factor has been changed.
→ Confirm the entered K factor or not.
Fig. 23: Entering the K factor of the fitting used
→ If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
not and go back to the Process level.
ENTER
to save the settings or
English
29
Type 8045
Maintenance and troubleshooting
9. MAINTENANCE AND
TROUBLESHOOTING
9.1. Safety instructions
danger
Risk of injury due to high pressure in the installation.
Risk of injury due to electrical voltage.
Risk of injury due to high fluid temperatures.
Risk of injury due to the nature of the fluid.
Warning
Risk of injury due to non-conforming maintenance.
• Maintenance must only be carried out by qualified and skilled
staff with the appropriate tools.
• Ensure that the restart of the installation is controlled after any
interventions.
→ If a problem occurs, refer to the complete operating instructions
available on the CD delivered with the device.
10. PACKAGING, TRANSPORT
note
Damage due to transport
Transport may damage an insufficiently protected device.
• Transport the device in shock-resistant packaging and away
from humidity and dirt.
• Do not expose the device to temperatures that may exceed the
admissible storage temperature range.
• Protect the electrical interfaces using protective plugs.
11. STORAGE
note
Poor storage can damage the device.
• Store the device in a dry place away from dust.
• Storage temperature of the device: -20 to +60 °C.
30
English
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.