Burkert 6115 User Manual [en, de, fr]

PTB 01 ATEX 2194 X
Example/Beispiel/Exemple Type 6115
Device with II 2G EEx i-approval Geräte mit II 2G EEx i-Zulassung Appareils avec mode de protection II 2G EEx i
Operating Instructions
Bedienungsanleitung Instructions de Service
© 2006 – 2011 Bürkert Werke GmbH
Operating Instructions 1111/10_EU-ML_00804534 / Original DE
Content:
PTB 01 ATEX 2194 X
Devices with II 2G EEx i approval PTB 01 ATEX 2194 X
1. THE OPERATING INSTRUCTIONS .........................................................4
1.1. Symbols ..............................................................................................4
2. AUTHORIZED USE .........................................................................................5
2.1. Limitations ..........................................................................................5
2.2. Licences ............................................................................................. 5
2.3. Conformity .........................................................................................5
3. GENERAL SAFETY INSTRUCTIONS .....................................................6
4. GENERAL INFORMATION ...........................................................................7
4.1. Contact addresses .......................................................................... 7
4.2. Warranty .............................................................................................7
4.3. Information on the Internet ............................................................. 7
5. SYSTEM DESCRIPTION ...............................................................................7
5.1. Operating conditions of the devices ............................................ 7
6. TECHNCIAL DATA ...........................................................................................8
6.1. Electrical data....................................................................................8
7. INSTALLATION AND COMMISSIONING ........................................... 10
7.1. Safety Instructions .........................................................................10
7.2. Montage ...........................................................................................10
7.3. Commissioning ...............................................................................11
8. MAINTENANCE, FAULTS .......................................................................... 12
8.1. Faults .................................................................................................12
9. TRANSPORT, STORAGE, DISPOSAL ................................................. 12

english

3
PTB 01 ATEX 2194 X
The operating instructions
1. THE OPERATING INSTRUCTIONS
The operating manual describes the whole life cycle of the appliance. Store this manual in such a way that is easily accessible to every user and is available to every new owner of the appliance.
WARNING!
The operating manual must be read and understood.
• Read the operating manual carefully.
• Pay particular attention to the sections Intended Use and General Safety Precautions!
1.1. Symbols
DANGER!
Warns of an immediate danger!
• Failure to observe the warning may result in a fatal or serious injury.
WARNING!
Warns of a potentially dangerous situation!
• Failure to observe the warning may result in serious injuries or death.
CAUTION!
Warns of a possible danger!
• Failure to observe this warning may result in a medium or minor injury.
NOTE!
Warns of damage to property!
• Failure to observe the warning may result in damage to the device or the equipment.
Indicates important additional information, tips and recommendations.
Refers to information in these operating instructions or in other documentation.
→ designates a procedure which you must carry out.
4
english
PTB 01 ATEX 2194 X
Authorized use
2. AUTHORIZED USE
WARNING!
The device may only be used for the applications indicated in the chapter Operating conditions for the devices, and only in connection with third-party devices or components recom­mended or approved by Bürkert. Observe the instructions in this operating manual, as well as the conditions of use and permissible data specified in the chapter “5.1. Operating con­ditions of the devices”.
The proper and safe function of the system depends on proper transport, storage and installation, and on careful operation and maintenance.
• The device serves exclusively as a piezoelectric actuator for the media stated in the data sheet and for use in Explosion Group II, Category 2 G and Temperature Class T6 (see data on the
approval plate).
• The type of protection used is inherent safety EEx i. Connection is made by rectangular connectors, circular connectors or via 2 impressed wires.
• The device must be installed in a housing with a protection type of at least IP 20 to EN 60529.
• The device may be used in a potentially explosive atmosphere only in the manner approved by the Physikalisch-Technische Bundesanstalt, i.e. the values specified in the approval or the electrical wiring must be observed.
• Any other use or use exceeding the specific scope is consid­ered to be non-intended use. Bürkert will not be liable for any damage resulting therefrom. The risk will be borne by the user.
2.1. Limitations
If exporting the system/device, observe any existing restrictions.
EX approval
The EX approval is only valid if the modules and components authorized by Bürkert are used as described in these operating instructions.
Type 6106 may be used only in combination with the additional com­ponents released by Bürkert, otherwise the EX approval will be voided!
If any unauthorized changes are made to the device, modules or com­ponents, the EX approval will also be voided.
2.2. Licences
The EC type-examination certificate PTB 01 ATEX 2194 X was issued by the
PTB (Physikalisch Technische Bundesanstalt) Bundesallee 100
38116 Braunschweig which also audits production (CE 102). The EC type-examination certificate can be found on the Internet at:
www.burkert.com
2.3. Conformity
The device conforms to the EC directives according to the EC Declaration of Conformity.
english
5
PTB 01 ATEX 2194 X
General safety instructions
3. GENERAL SAFETY INSTRUCTIONS
DANGER!
Risk of explosion if the device is opened!
• The device is a sealed system. It must not be opened.
Hazard due to high pressure!
Interference with the system will result in an acute risk of injury.
• Switch off the pressure before loosening pipes and modules!
Hazard due to electrical voltage!
Interference with the system will result in an acute risk of injury.
• Before starting work, be sure to switch off the supply voltage and secure it to prevent restarting!
• Observe all applicable accident prevention and safety regula­tions for electrical equipment!
Danger of explosion caused by electrostatic charge!
If there is a sudden discharge from electrostatically charged devices or persons, there is a danger of explosion in the EX area.
• Using suitable measures, ensure that no electrostatic charges can occur in the EX area.
• Clean the device surface by gently wiping it with a damp or anti­static cloth only.
WARNING!
General Hazardous Situations.
• Do not supply the medium connectors of the system with aggressive or flammable mediums.
• Do not supply the medium connectors with any liquids.
• Do not put any loads on the housing (e.g. by placing objects on it or standing on it).
• Do not make any external modifications to the device housings. Do not paint the housing parts or screws.
To prevent injuries:
• Ensure that the system cannot be activated unintentionally.
• Installation and maintenance work may be carried out only by authorized technicians with the appropriate tools.
• After an interruption in the power supply or pneumatic supply, ensure that the process is restarted in a defined or controlled manner.
• The device may be operated only when in perfect condition and in consideration of the operating instructions.
• The general rules of technology must be observed for application planning and operation of the device.
Failure to observe this operating manual and its operating instructions as well as unauthorized tampering with the device release us from any liability and also invalidate the warranty covering the devices and accessories!
6
english
PTB 01 ATEX 2194 X
General information
4. GENERAL INFORMATION
4.1. Contact addresses
Germany
Bürkert Fluid Control Systems Sales Center Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0) 7940 - 10 91 111 Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com
International
Contact addresses can be found on the final pages of the printed operating instructions.
And also on the Internet at: www.buerkert.com
4.2. Warranty
The warranty is only valid if the device is used as intended in accordance with the specified application conditions.
4.3. Information on the Internet
The operating instructions and data sheets for Type 6106 can be found on the Internet at:
www.buerkert.com
5. SYSTEM DESCRIPTION
5.1. Operating conditions of the devices
1. Individual assembly / Block assembly The piezoelectric actuator Type 6115 is suitable for individual and
block assembly (see „Electrical data“).
2. Ambient temperature range The devices are suitable for an ambient temperature range of
-25 °C ... +65 °C (temperature class T6).
The piezoelectric actuator must be installed in a housing with a pro­tection class of at least IP 20 according to EN 60529.
The ambient temperature range of the piezoelectric actuator must not drop below -25 °C or exceed +65 °C both for individual and block assembly.
The piezoelectric actuator may be used for switching non-combus­tible media only.
The piezoelectric actuator shall only be operated in a built-in state, or if otherwise can be guaranteed that explosive atmosphere will penetrate into the interior valve only infrequently or for a short period.
The piezoelectric actuator may be connected to certified intrinsically safe circuits only.
The supply must not exceed the specified limit values.
english
7
PTB 01 ATEX 2194 X
Techncial data
6. TECHNCIAL DATA
DANGER!
RISK OF EXPLOSION!
• Exceeding the technical data indicated on the rating plate increases the explosion risk!
• Never exceed the technical data indicated on the rating plate!
Example
PTB-certification No. Coil type - port size for fluid part
- coil size Mode of protection/temperature code
Voltage (±10 %) - power rating Ambient temperature
Serial no. of the coil /CE designation Ident. no / date of production Space for barcode
6.1. Electrical data
Devices suitable for individual and block assembly
Device dimensions:
Length (mm) Width (mm) Height (mm) Mass (g)
18 10 49 14
Approval code: PE40 PTB 01 ATEX 2194 X II 2G EEx ia IIC T6 Piezoelectric actuator Type 6115
The device may be attached with or without protective circuit, as specified.
Electrical connection: JC18 2 impressed FEP wires, blue and brown JF79 circular connector M8, 3-pole JF80 Rectangular connector, 2-pole
Data on safety engineering:
Piezoelectric actuator in ignition protection type intrinsically safe EEx ia IIC, for connection only to certified intrinsically safe circuits with
8
english
PTB 01 ATEX 2194 X
Techncial data
the following max. values: Explosion group: IIC Category: ia Temperature class: T6 Max. permissible input voltage (Ui): 35 V Max. permissible input current (Ii): 0.9 A Max. permissible input power (Pi): 225 mW
The maximum permissible voltages and the associated maximum permissible short-circuit currents for the corresponding gas group may be taken from Table A1 in the standard DIN EN 50020.
As an example, some pairs of values for the ignition protection type EEx are given for the gas group IIC.
Piezoelectric actuator Type 6115 in ignition protection type intrinsi­cally safe
Voltage
EEx ia IIC.
15 18 20 22 25 28 30 35 value (V) = Ui
Current
0.9 0.44 0.309 0.224 0.158 0.12 0.101 0.073
value (A) = li
The maximum voltage and current values are determined by the permissible electrical equipment.
Assembly:
The piezoelectric actuator type 6115 is suitable for individual and block assembly.
Permissible ambient temperature range:
The devices are suitable for an ambient temperature range of
-25 °C ... +65 °C.
Type of protection:
The IP protection type can be taken from the following table in dependence on the electrical connection type.
El. connection type
Circular connector
Without associated connector
Protection type
With associated connector
IP 20 IP 65
M8, 3-pole 2 impressed single
wires 0.2 mm
3
IP 65
-
(AWG 24) Rectangular con-
IP 20 IP 20
nector 2-pole
english
9
PTB 01 ATEX 2194 X
Installation and commissioning
7. INSTALLATION AND COMMISSIONING
7.1. Safety Instructions
DANGER!
Danger of explosion!
• The device is a sealed system. The unit must not be dismantled! The following safety regulations must be observed::
• The surface of the device may develop an electrostatic charge. In areas with an explosion hazard, the surface of the units may only be cleaned with a damp cloth!
• Only permanently laid cables and wiring may be inserted.
• The operator must provide suitable stress relief.
High voltage!
Acute risk of injury from hazardous structure-borne voltage! Risk of damage to the device due to short circuit!
• Work on the electrical system may only be carried out by quali­fied electricians!
• Before starting work, switch off the power supply and secure to prevent it being switched on again!
• The connecting cables to the electromagnets must be secure, and be laid so that they are adequately protected from mechani­cal damage.
• Observe the applicable accident prevention and safety regula­tions for electrical devices!
WARNING!
Pressurised system!
Interventions in the pneumatic system represent an acute risk of injury.
• Work on the pneumatic system may only be carried out by quali­fied and instructed personnel using appropriate tools.
• First switch off pressure before disconnecting lines and valves!
• Observe the flow direction during installation!
• Observe the applicable accident prevention and safety regula­tions for pneumatic systems!
7.2. Montage
NOTES:
Installation in any position. Preferably with solenoid system mounted at the top.
Activity Notes
→ Clean the pipe runs - → Installation in any position Preferred direction with drive
mounted at the top
→ Connect a dirt-trap
(strainer) upstream
Note the direction of flow!
→ Seal PTFE
10
english
PTB 01 ATEX 2194 X
Installation and commissioning
Activity Notes
→ Screwing on the pipe run Note the direction of flow! → Installation / Dismounting
→ Make electrical
connections
Types of connection
Rectangular plug
connector
2 individual wires Circular plug
Note
Always connect the earth
conductor!
Note for units with connecting cable
The connecting cable and the coil are moduled together. They must not be dismantled!
-
7.3. Commissioning
Before commissioning, ensure that
• The device has been correctly installed,
• The connections have been correctly made,
• The device is not damaged,
• All bolts are securely tightened.
connector
english
11