The operating instructions describe the entire life cycle of the device.
Keep these instructions in a location which is easily accessible to
every user and make these instructions available to every new owner
of the device.
The operating instructions contain important safety
information!
Failure to observe these instructions may result in hazardous
situations.
The operating instructions must be read and understood.
•
1.1. Symbols
DANGER!
Warns of an immediate danger!
• Failure to observe the warning may result in a fatal or serious
injury.
WARNING!
Warns of a potentially dangerous situation!
• Failure to observe the warning may result in serious injuries or
death.
CAUTION!
Warns of a possible danger!
• Failure to observe this warning may result in a medium or minor
injury.
NOTE!
Warns of damage to property!
• Failure to observe the warning may result in damage to the
device or the equipment.
Indicates important additional information, tips and
recommendations.
Refers to information in these operating instructions or in
other documentation.
→ designates a procedure which you must carry out.
4
english
PTB 01 ATEX 2175
Authorized use
2. AUTHORIZED USE
Unauthorized use of the device Type 6106 may be dangerous
to people, nearby equipment and the environment.
• The device is used exclusively as a solenoid valve for media permitted according to data sheet and for use in Group II Category
2 G and temperature class T4, T5 or T6 (see specifications on
the approval plate).
• The applied protection class is the intrinsic safety EX “i” for coils
with circular plug connection, rectangular plug connection with
or without protective collar as well as connection by pressed-in
single wires and device socket connection in accordance with
DIN 43650 Form C.
• The faultless and reliable operation of the system assumes correct transportation, correct storage and installation as well as
careful operation and maintenance. Any other use is regarded as
unauthorized. Bürkert is not liable for any resulting damage. The
user alone bears the risk.
• Only use the device for its intended purpose.
2.1. Restrictions
If exporting the system/device, observe any existing restrictions.
2.2. EX approval
The EX approval is only valid if the modules and components authorized by Bürkert are used as described in these operating instructions.
Type 6106 may be used only in combination with the additional components released by Bürkert, otherwise the EX approval will be voided!
If any unauthorized changes are made to the device, modules or components, the EX approval will also be voided.
english
5
3. BASIC SAFETY
INSTRUCTIONS
These safety instructions do not make allowance for any
• Contingencies and events which may arise during the installation,
operation and maintenance of the devices.
• Local safety regulations – the operator is responsible for observing
these regulations, also with reference to the installation personnel.
Danger of explosion!
• The device is a closed system and must not be modified in any
way.
A device which has already been used in a non-hazardous “i” circuit
must no longer be used in the hazardous “i” circuit, as safety cannot
be guaranteed.
• Use the device in the hazardous “i” circuit only.
• Devices which were used in a non-hazardous “i” circuit must be
identified after they have been removed, denoting that their use is
prohibited in the hazardous “i” circuit.
Danger – high pressure!
When reaching into the system, there is an acute risk of injury.
• Before dismounting pneumatic lines and valves, turn off the
pressure and vent the lines.
• During the installation, make certain the flow direction is correct.
• Observe applicable accident prevention and safety regulations
for pressurized devices.
PTB 01 ATEX 2175
Basic safety instructions
Danger of explosion caused by electrostatic charge!
If there is a sudden discharge from electrostatically charged
devices or persons, there is a danger of explosion in the EX area.
• Using suitable measures, ensure that no electrostatic charges
can occur in the EX area.
• Clean the device surface by gently wiping it with a damp or antistatic cloth only.
General Hazardous Situations.
To prevent injuries:
• Ensure that the system cannot be activated unintentionally.
• Installation and maintenance work may be carried out only by
authorized technicians with the appropriate tools.
• After an interruption in the power supply or pneumatic supply,
ensure that the process is restarted in a defined or controlled
manner.
The device may be operated only when in perfect condition and
•
in consideration of the operating instructions.
• The general rules of technology must be observed for application
planning and operation of the device.
Failure to observe this operating manual and its operating
instructions as well as unauthorized tampering with the device
release us from any liability and also invalidate the warranty
covering the devices and accessories!
6
english
PTB 01 ATEX 2175
General information
4. GENERAL INFORMATION
4.1. Contact addresses
Germany
Bürkert Fluid Control Systems
Sales Center
Christian-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: info@de.buerkert.com
International
Contact addresses can be found on the final pages of the printed
operating instructions.
And also on the Internet at: www.burkert.com
4.2. Warranty
The warranty is only valid if the device is used as intended in accordance
with the specified application conditions.
4.3. Information on the Internet
The operating instructions and data sheets for Type 6106 can be found
on the Internet at: www.burkert.com
5. APPLICATION CONDITIONS OF
THE DEVICES
5.1. Individual assembly, block
assembly
The solenoid coils type AC21 are suitable for individual assembly and
for block assembly.
5.2. Operating temperature range
For each type observe the operating temperature range specified in
the Electrical Data.
english
7
PTB 01 ATEX 2175
Technical data
6. TECHNICAL DATA
6.1. Conformity
The device conforms to the EC directives according to the EC
Declaration of Conformity.
6.2. Standards
The conformity with EC guidelines is guaranteed in accordance with
standards:
EN 60079-0, EN 60079-11
•
6.3. Licences
The EC type-examination certificate PTB 01 ATEX 2175 was issued
by the
Not specified Appliance socket connection in accordance with
Width
(mm)
Height
(mm)
protective collar
DIN 43650 form C
english
Mass
(g)
Electrical
connection
ohne Angaben
9
PTB 01 ATEX 2175
Technical data
6.5.2. Use in temperature class T6
Ignition protection type Ex ia, Gas group II C
Temperature
class
T6
The maximum permitted power depends on the max.
ambient temperature, the temperature class and the
installation.
Max. per-
mitted
ambient tem-
perature [°C]
-40 ... +60
-40 ... +550.5
-40 ... +500.7
-40 ... +450.9
-40 ... +401.1
-40 ... +60
-40 ... +550.9
-40 ... +501.1
AssemblyMax. per-
mitted power
consumption
Block
assembly
Individual
[W]
0.4
0.7
6.5.3. Use in temperature class T5
Ignition protection type Ex ia, Gas group II C
Temperature
class
T5
Max. per-
mitted
ambient tem-
perature [°C]
-40 ... +75
-40 ... +700.5
-40 ... +650.7
-40 ... +600.9
-40 ... +551.1
-40 ... +75
-40 ... +700.9
-40 ... +651.1
AssemblyMax. per-
mitted power
consumption
Block
assembly
Individual
6.5.4. Use in temperature class T4
Ignition protection type Ex ia, Gas group II C
Temperature
class
T4
Max. per-
mitted
ambient tem-
perature [°C]
-40 ... +100Block
AssemblyMax. per-
assembly
mitted power
consumption
[W]
0.4
0.7
[W]
0.7
10
english
PTB 01 ATEX 2175
Technical data
6.5.5. Safety data
Group: II C
Ignition protection type: Ex ia
Temperature class: T4, T5 or T6
Max. permitted input voltage (Ui): 35 V
Max. permitted input current (Ii): 0.9 A
Inductance (Li): ~ 0
Capacity (Ci): ~ 0
The maximum permitted voltages and the associated shortcircuit currents can be found in Table A1 in the standard EN
60079-11 for the corresponding gas group.
Ignition protection type Ex ia II C: Coil Type AC21 (example):
1518202225283035
U
i
0.90.440.309 0.224 0.1580.120.101 0.073
I
i
The coils of type AC21 are available in two versions:
• Version for use with 300 Ω supply module (300 Ω barrier),
• High-resistance version for use with other authorized supply
modules (e.g. 8 x remote I/O from Stahl).
VersionResis-
tance
R20 [Ω]
Minimum
clamping
voltage
Minimum
current
[mA]
[V]
Version which
3209.329EX I / 21
uses 300 Ω
supply module
High-resistance
47510.923EX I / 22
version
Version for Type
1256.149EX I / 23
8650
The maximum voltage and current values are specified by
the permitted electrical equipment.
6.5.6. Permitted ambient temperature
The maximum permitted ambient temperature depends on
the power fed in, the temperature class and the installation.
For the appropriate values see chapters “6.5.2” “6.5.3” and
“6.5.4”.
Type
english
11
PTB 01 ATEX 2175
Installation
6.5.7. Protection class
Electrical connection
Appliance socket connection in
accordance with DIN 43650 form C