Bryant 583B User Manual

installation, start-up,
583B
and operating instructions
3-PHASE SINGLE PACKAGE GAS HEATING/AIR CONDITIONERS WITH PURON® (R-410A) REFRIGERANT
Low NOx Models Available
NOTE: Read the entire instruction manual before starting the installation.
Index Page
SAFETY CONSIDERATIONS .....................................................1
RULES FOR SAFE INSTALLATION AND OPERATION....1-2
RECEIVING AND INSTALLATION ..........................................2
CHECK EQUIPMENT ..................................................................2
Roof Curb..................................................................................2
Slab Mount................................................................................2
Ground Mount...........................................................................2
FIELD FABRICATE DUCTWORK..........................................2-3
PROVIDE CLEARANCES ........................................................4-7
RIG AND PLACE UNIT ...........................................................7-8
CONNECT CONDENSATE DRAIN ...........................................8
INSTALL FLUE HOOD ...............................................................8
INSTALL GAS PIPING............................................................... 9
INSTALL DUCT CONNECTIONS ..................................... 10-11
INSTALL ELECTRICAL CONNECTIONS.........................12-14
High-Voltage Connections......................................................12
Special Procedures for 208-V Operation ...............................12
Control Voltage Connections .................................................13
Standard Connection...............................................................13
Heat Anticipator Setting....................................................13-14
Transformer Protection ...........................................................14
PRE-START-UP ......................................................................... 14
START-UP ............................................................................ 14-23
MAINTENANCE....................................................................23-27
REFRIGERANT SYSTEM..........................................................27
QUICK REFERENCE GUIDE....................................................28
TROUBLESHOOTING......................................................... 29-31
START-UP CHECKLIST............................................................32
NOTE TO INSTALLER — Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation. the furnace is NOT to be used for temporary heating of buildings or structures under construc­tion.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Sizes
030-060
Cancels: New II 583B-30-1
2-06
Fig. 1—Unit 583B
RULES FOR SAFE INSTALLATION AND OPERATION
WARNING: Improper installation, adjustment, alter-
ation, service, maintenance, or use can cause carbon monoxide poisoning, fire, or an explosion which can result in serious injury or unit damage. Consult a quali­fied installer, service agency, or gas supplier for infor­mation or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product.
Understand the signal words —DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe serious injury or death. WARNING indicates a condition that could result in serious injury or death. CAUTION is used to identify unsafe practices which would result in minor or moderate injury or product and property damage.
The power supply (volts, phase, and hertz) must correspond to that specified on unit rating plate.
The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
This installation must conform with local building codes and with NEC (National Electrical Code) and NFPA 70, NFPA 54/ANSI Z223.1 latest revision, and NFGC (National Fuel Gas Code). Refer to provincial and local plumbing or waste water codes and other applicable local codes.
C99087
—1—
WARNING: Before performing service or maintenance
operations on unit, turn off gas supply then unit main
power switch. Electrical shock or explosion could cause
serious injury or death.
CAUTION: Puron (R-410A) systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron (R-410A)
equipment. Ensure service equipment is rated for Puron
(R-410A).
A
B
Fig. 2—Unit Leveling Tolerances
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
C99065
A. General
The 583B units (see Fig. 1) are fully self-contained, combination Category I gas heating/electric cooling units designed for outdoor installation. See Fig. 6 and 7 for unit dimensions. All unit sizes have discharge openings for both horizontal and downflow con­figurations, and are factory shipped with all downflow duct openings covered . Units may be installed either on a rooftop, cement slab, or directly on the ground (if permitted by local codes). See Figs. 4 and 5 for roof curb dimensions.
Models with an N in the thirteenth position of the model number are dedicated Low NO
units designed for California installation.
x
These models meet the California maximum oxides of nitrogen
) emissions requirements of 40 nanograms/joule or less as
(NO
x
shipped from the factory and must be installed in California Air Quality Management Districts where a Low NO
rule exists.
x
RECEIVING AND INSTALLATION
I. CHECK EQUIPMENT
IDENTIFY UNIT — The unit model number and serial number are stamped on unit identification plate. Check this information against shipping papers and job data.
INSPECT SHIPMENT — Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Bryant Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original packages until installation.
II. PROVIDE UNIT SUPPORT
ROOF CURB — Install accessory roof curb in accordance with instructions shipped with curb. See Figs. 4 and 5 and Table 1 for roof curb dimensions. Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing can also result in air leaks and poor unit performance. Curb should be level to within 1 /4 inch. This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required (see Fig. 2).
2"
(50.8mm)
OPTIONAL
RETURN
AIR
OPENING
EVAP.
COIL
COND.
COIL
OPTIONAL
SUPPLY
AIR
OPENING
C99014
Fig. 3—Slab Mounting Details
SLAB MOUNT — Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. The slab should be flush on the compressor end of the unit (to allow condensate drain installation) and should extend 2 in. on the three remaining sides of the unit. See Fig. 3. Do not secure the unit to the slab except when required by local codes.
GROUND MOUNT — The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit on level ground prepared with gravel for condensate dis­charge.
III. FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed -.25 in. wg.
—2—
6
C
46 3/16
44 5/16
B
17 3/8 TYP.
D
1 TYP.
3
SUPPORT B
B
SUPPORT A (2)
SIDE (2)
A
7/8
13/16
2
END VIEW
END (2)
DECK PAN (INSULATED)
Fig. 4—Roof Curb Dimensions
A99320
Top View
SIDE PANEL
0.75"
SUPPORT RIB(S)
SEAL STRIP (FACTORY SUPPLIED)
3.0"
BASE PAN
BOTTOM SUPPLY
4.0"
COUNTER FLASHING (FIELD SUPPLIED)
ROOFING FELT (FIELD SUPPLIED)
CANT STRIP (FIELD SUPPLIED)
NAILER
ROOFING MATERIAL (FIELD SUPPLIED)
Fig. 5—Roof Curb Dimensions
Side View
—3—
INSULATION (FIELD SUPPLIED)
A99340
TABLE 1—ROOF CURB DIMENSIONS
UNIT SIZE ODS ORDER NUMBER
ROOF CURB
Notes:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16 gauge steel.
5. Table lists only the dimensions per part number that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb. density.
8. Dimensions are in inches.
583B030-036
583B042-060
CPRFCURB006A00 8 (203) 11 27/32 (301) 30 5/8 (778) 28 3/4 (730) CPRFCURB007A00 14 (356) 11 27/32 (301) 30 5/8 (778) 28 3/4 (730) CPRFCURB008A00 8 (203) 15 27/32 (402) 42 1/8 (1070) 40 1/4 (1022) CPRFCURB009A00 14 (356) 15 27/32 (402) 42 1/8 (1070) 40 1/4 (1022)
A
IN. (MM)
B
IN. (MM)
C
IN. (MM)
D
IN. (MM)
IV. PROVIDE CLEARANCES
The required minimum operating and service clearances are shown in Fig. 6 and 7. Adequate combustion, ventilation, and condenser air must be provided, in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American National Standards Institute) Z223.1 (in Canada, sec­tions 7.2, 7.3 or 7.4 or Can/CGA (Canadian Gas Association) B149 Installation Codes), or applicable provisions of local build­ing code.
CAUTION: Do not restrict condenser airflow. An air
restriction at either the outdoor-air inlet or the fan
discharge can be detrimental to compressor life.
The condenser pulls air through the condenser coil and discharges it through the top cover. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48-in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting, tile, or other combustible materials. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.
V. RIG AND PLACE UNIT
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers and labels attached to the equipment, and any other safety precautions that might apply.
Training for operations of the lifting equipment should include, but NOT be limited to the following:
1. Application of the lifter to the load and adjustment of the lifts, if any, that adapts it to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load itself, required for operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
WARNING:
Never exceed 200 lbs. per bracket lifting force. Accessory lifting kit is only to be used with Small Packaged units which have a composite base pan with molded hand holds. Never stand beneath rigged units or lift over people. Lifting point should be directly over the center of gravity for the unit. A dropped unit could cause serious injury or death.
INSPECTION — Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded.
INSTALLATION:
1. Position the lifting bracket assembly around the base of the unit. Leave the top shipping skid on the unit to act as a spreader bar. Be sure the strap does not twist.
2. Place each of the four (4) metal lifting brackets into the handholds in the composite pan.
3. Tighten the ratchet strap until tight. Lifting brackets should be secure in the handholds.
4. Attach the clevis or hook of sufficient strength to hole in the lifting bracket as shown in Fig. 8.
5. Attach safety straps directly to the field supplied rigging straps or clevis clip. Do not attach the safety straps to the lifting brackets.
6. Use the top of the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood top is not available, use a spreader bar of sufficient length to not damage the unit.
VI. CONNECT CONDENSATE DRAIN
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
The 583B units dispose of condensate water through a 3/4 in. NPT fitting which exits through the compressor access panel. See Fig. 6 and 7 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground­level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain pan condensate connection to prevent the pan from overflowing. See Fig. 9. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
—4—
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side ..................36(914)
Power entry side (except for NEC requirements) .........36(914)
Unittop ..........................48(1219)
Side opposite ducts .....................36(914)
Duct panel ........................12
Flue Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 (914.4)
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall
system, then the system performance may be compromised.
LEGEND CG - Center of Gravity COND - Condenser EVAP - Evaporator NEC - National Electrical Code REQ'D - Required Note: Dimensions are in in. (mm)
(304.8)*
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Topofunit.........................14(355.6)
Duct side of unit .......................2(50.8)
Side opposite ducts .....................14(355.6)
Bottomofunit.......................0.50(12.7)
NEC REQ’D CLEARANCES. in. (mm)
Between units, power entry side ..............42(1066.8)
Unit and ungrounded surfaces, power entry side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................42(1066.8)
C99017
CENTER OF GRAVITY
IN. (MM)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
lb. kg. X Y Z
UNIT HEIGHT
IN. (MM)
"A"
583B030040/060 208/230-3-60 313.0 142.0 39.02 (991.1) 22.0 (558.8) 15.3 (387.4) 17.6 (447.0)
583B036060/090
208/230-3-60,
460-3-60
321.0 145.6 35.02 (889.5) 22.0 (558.8) 15.3 (387.4) 16.5 (419.1)
Fig. 6—583B030, 036 Unit Dimensions
—5—
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE..............................................................36.00 [914.0]
POWER ENTRY SIDE......................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.........................................................................................36.00 [914.0]
SIDE OPPOSITE DUCTS ................................................................36.00 [914.0]
DUCT PANEL ...................................................................................12.00 [304.8] *
FLUE HEAT PANEL *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
.................................................................36.00 [914.4]
in. [mm]
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
FLUE HOOD
in. [mm]
in. [mm.]
UNIT
583B042060/090
583B048090/115/130
583B060090/115/130
ELECTRICAL
CHARACTERISTICS
208/230-3-60
460-3-60
208/230-3-60
460-3-60
208/230-3-60,
460-3-60
UNIT WEIGHT
lb. kg. X Y Z
UNIT HEIGHT
IN. (MM)
"A"
CENTER OF GRAVITY
IN. (MM)
382 173.3 38.98 (990.2) 23.0 (584.2) 16.3 (412.8) 16.6 (421.6)
421 191.0 38.98 (990.2) 21.5 (546.1) 16.6 (422.1) 18.0 (457.2)
468 212.3 42.98 (1091.7) 23.5 (596.9) 16.3 (412.8) 17.6 (447.0)
Fig. 7—583B042-060 Unit Dimensions
—6—
C99074
DETAIL A
UNIT 583B
SIZE
030 335 152 22.0 558.5 15.3 388.6 036 343 156 22.0 558.5 15.3 388.6 042 404 183 23.0 584.2 16.3 414.0 048 443 201 21.5 546.1 16.3 414.0 060 490 222 23.5 596.9 16.3 414.3
MAXIMUM WEIGHT A B
lb kg in. mm in. mm
Fig. 8—Suggested Rigging
A05179
If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage. See Fig. 9. Make sure that the outlet of the trap is at least 1 in. lower than the drain pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
1” (25mm) MIN.
TRAP OUTLET
2” (50mm) MIN.
C99013
Fig. 9—Condensate Trap
VII. INSTALL FLUE HOOD
The flue hood assembly is shipped screwed to the coil panel in the indoor blower compartment. Remove the service access panel to locate the assembly.
CAUTION: The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicated in this section of the unit installation instruc­tions.
NOTE: Dedicated low NOxmodels MUST be installed in Cali- fornia Air Quality Management Districts where a Low NO
rule
x
exists.
IN
OUT
3˝ MIN
TEE
NIPPLE
CAP
C99020
Fig. 10—Sediment Trap
These models meet the California maximum oxides of nitrogen (NO
) emissions requirements of 40 nanograms/joule or less as
x
shipped from the factory.
NOTE: Low NO
requirements apply only to natural gas instal-
x
lations.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or NFPA (National Fire Protection Association) latest revi­sion. Refer to Provincial and local plumbing or waste water codes and other applicable local codes.
2. Remove flue hood from shipping location (inside the blower compartment). Place vent cap assembly over flue panel. Orient screw holes in vent cap with holes in the flue panel.
—7—
3. Secure flue hood to flue panel by inserting a single screw on the right side and the left side of the hood.
VIII. INSTALL GAS PIPING
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2-in. FPT gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 4 and the NFGC for gas pipe sizing. Do not use cast-iron pipe. It is recommended that a black iron pipe is used. check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wg maximum pressure drop. Never
use pipe smaller than the 1/2-in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 7.0 in. wg or greater than 13 in. wg at the unit connection.
A 1/8-in. NPT plugged tapping accessible for test gauge connec­tion must be installed immediately upstream of the gas supply connection to the gas valve.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI Z223.1, NFPA 54 latest edition (in Canada, CAN/CGA B149.1, B149.2 latest edition). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. in every 15 ft. to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than 1/2 in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. Never use Teflon tape.
4. Install sediment trap in riser leading to heating section per Fig. 10. This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft. of heating section.
6. Install ground-joint union close to heating section between unit manual shutoff and external manual main shutoff valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connection of piping to unit.
NOTE: The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (13.8 WC). If the test pressure is equal to or less than 0.5 psig, the unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
CAUTION: Unstable operation may occur when the gas valve and manifold assembly are forced out of position while connecting improperly routed rigid gas piping to the gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, the gas control piping.
CAUTION: If a flexible conductor is required or al­lowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and shall extend a minimum of 2 in. outside the unit casing.
WARNING: Never use a match or other open flame when checking for gas leaks. Never purge gas line into combustion chamber. Failure to follow this warning could result in an explosion causing serious injury or death
8. Check for gas leaks at the field-installed and factory­installed gas lines after all piping connections have been completed. Use soap and water solution (or method speci­fied by local codes and/or regulations).
IX. INSTALL DUCT CONNECTIONS
The unit has duct flanges on the supply- and return-air openings on the side and bottom of the unit. For downshot applications the ductwork can be connected to the roof curb. See Fig. 6 and 7 for connection sizes and locations.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DIS­CHARGE
WARNING: Before performing service or maintenance operations on the system, turn off main power to unit. Electrical shock could cause serious injury or death.
1. Open all electrical disconnects before starting any service work.
2. Remove return duct cover located on duct panel by breaking connecting tabs with screwdriver and a hammer (Fig. 11).
3. To remove supply duct cover, break front and right side connecting tabs with a screwdriver and a hammer. Push louver down to break rear and left side tabs (Fig. 12).
4. If unit ductwork is to be attached to vertical opening flanges on the unit basepan (jackstand applications only), do so at this time. Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
5. It is recommended that the basepan insulation around the perimeter of the vertical return-air opening be secured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass.
6. Cover both horizontal duct openings with the duct covers from the accessory duct cover kit. Ensure opening is air-and watertight.
7. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and residence-type, NFPA 90B; and/or local codes and ordinances.
—8—
TABLE 2—PHYSICAL DATA — UNIT 583B — 030040-042090
UNIT SIZE 583B 030040 030060 036060 036090 042060 042090
NOMINAL CAPACITY (ton) 21/2 21/2 3 3 31/2 31/2
OPERATING WEIGHT (lb) 313 313 321 321 382 382
COMPRESSORS
Quantity
REFRIGERANT (R-410A) Qty (lb) 5.5 5.5 6.9 6.9 9.0 9.0
REFRIGERANT METERING DEVICE
Orifice ID (in.)Check-Flo-Rater® Piston
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal CFM Diameter (in.)
Motor Hp (RPM)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor Hp
FURNACE SECTION*
Burner Orifice No.
(Qty...Drill Size) Natural
Burner Orifice No.
(Qty...Drill Size) Propane
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (psig)
Cutout
Reset (Auto.)
RETURN-AIR FILTERS (in.)Throwaway 20 x 24x1 20 x 24x1 20 x 24x1 20 x 24x1 24 x 30x1 24 x 30x1
.057 .057 .065 .065 .070 .070
1/17
12.7
2350
22
1/8 (825)
3/15
3.7
800
10x10
1/4
2...44
2...50
1/17
12.7
2350
22
1/8 (825)
3/15
3.7
1000
10x10
1/4
2...38
2...46
1/8 (825)
10x10
2/17
9.1
2350
22
3/15
3.7
1200
1/2
2...38
2...46
Scroll
1
610 ± 15 420 ± 25
20 ± 5
45 ± 10
2/17
9.1
2350
22
1/8 (825)
3/15
3.7
1200
10x10
1/2
3...38
3...46
2/17
12.3
2350
22
1/8 (825)
3/15
4.7
1400
11x10
3/4
2...38
2...46
2/17
12.3
2350
22
1/8 (825)
3/15
4.7
1400
11x10
3/4
3...38
3...46
A. Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped for side shot installation.
2. Select and size ductwork, supply-air registers, and return-air grilles according to American Society of Heating, Refrig­eration and Air Conditioning Engineers (ASHRAE) recom­mendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather tight and airtight seal.
4. All units must have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recom­mended sizes for filters are shown in Tables 2 and 3.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
X. INSTALL ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos­sibility of serious injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI/ NFPA 70 (latest edition) (in Canada, Canadian Electrical Code CSA (Canadian Standards Association) C22.1) and local electrical codes. Do not use gas piping as an electrical ground. Failure to adhere to this warning could result in serious injury or death.
—9—
Loading...
+ 21 hidden pages