Bryant 580J***D series Installation Instructions Manual

580J***D SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNIT WITH NOVATIONt COIL SIZES 17, 20, 24, 28 WITH PURONR(R--410A) REFRIGERANT
Installation Instructions
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
INSTALLATION 6...............................
Step 1 -- Plan for Unit Location 6..................
Step 2 -- Plan for Sequence of Unit Installation 7......
Step 3 -- Inspect Unit 7...........................
Step 4 -- Provide Unit Support 7...................
Step 5 -- Field Fabricate Ductwork 11...............
Step 6 -- Rig and Place Unit 11....................
Step 7 -- Duct Connection 12.....................
Step 8 -- Install Outside Air Hood 12...............
Step 9 -- Install Flue Hood and Combustion Air Hood 13
Step 10 -- Install Gas Piping 13....................
Step 11 -- Install External Condensate Trap and Line 16
Step 12 -- Make Electrical Connections 16...........
Step 13 -- Adjust Factory--Installed Options 32........
Step 14 -- Install Accessories 32...................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connecte d to such piping must be isolated by closing the manual gas valve.
!
WARNING
ELECTRICAL SHOCK HAZARD
580J***D
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protec tive clothing, safety glasses and gl oves when handling parts and servicing air conditioning units.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
2
580J***D
Fig. 1 -- Unit Dimensional Drawing – 17 and 20 Size Units
C09128
3
580J***D
C09129
Fig. 1 -- Unit Dimensional Drawing – 17 and 20 Size Units (cont.)
4
580J***D
Fig. 2 -- Unit Dimensional Drawing – 24 and 28 Size Units
C09130
5
580J***D
C09131
Fig. 2 -- Unit Dimensional Drawing – 24 and 28 Size Units (cont.)
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project pl ans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units.
Be sure that the unit is installed such that snow will not block the combustion intake or flute outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is used.
36” (914)
42” (1067)
42” (1067)
18” (457)
C09051
Fig. 3 -- Service Clearance Dimensional Drawing
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, ade quate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA-- --54----84 ----1. In Canada, installation must be in accordance with the CAN1----B149 installation codes for gas burning appliances.
6
Although unit is weatherproof, a void locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refe r to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
Roof mount —
Check building codes for weight distribution requirements. Unit operati ng weight is shown in Table 1.
Pad--mounted installation —
Prepare pad and unit supports Rig and place unit Remove duct covers and top skid Install field--fabricated ductwork at unit duct openings Install combustion air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim with transportation agency.
580J***D
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb Install field--fabricated ductwork inside curb Install thru--base service connection fittings (affects
curb and unit) Rig and place unit Remove top skid Install combustion air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 5 (size 17 and 20 units) a nd Fig. 6 (size 24 and 28 units). Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 5 and Fig. 6. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 7. Refer to Accessory Roof Curb Installation Instructions for additional informati on as required.
580J***D UNITS LB (KG)
Component 17D 20D 24D 28D
Base Unit 1824 (828) 1839 (835) 1989 (903) 2118 (961)
Economizer 245 (111) 245 (111) 245 (111) 245 (111) Powered Outlet 32 (15) 32 (15) 32 (15) 32 (15)
Curb
14--- in/356 mm 243 (111) 243 (111) 273 (124) 273 (124)
24--- in/610 mm 315 (143) 315 (143) 350 (159) 350 (159)
Table 1 – Operating Weights
7
Install insulation, cant strips, roofing felt, and counter
A
flashing as shown. Ductwork must be attached to curb and not to the unit. Thru--t he--base power connection must be installed before the unit is set on the roof curb. If
field--installed thru--the--roof curb ga s connections are desired remove knockout in basepan located in the gas section, see Fig. 4 for location. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan remove knockouts in basepan located in control box area, see Fig. 4 for location. Attach the service connections to the basepans.
Control Box
ccess Panel
580J***D
Filter and
Indoor Coil
Access Panel
Indoor Blower Access Panel
Gas
Access
Panel
Compressor
(each side)
Fig. 4 -- Typica l Access Panel and Comp ressor Locatio n s
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 4--in. x 4-- in. (102 mm x 102 mm) pads on each side. Locate pads so that they support the rails. Make sure to avoid the fork openings.
C09078
8
580J***D
Fig. 5 -- Roof Curb Details – 17 and 20 Size Units
C09052
9
580J***D
Fig. 6 -- Roof Curb Details – 24 and 28 Size Units
C09100
10
Loading...
+ 22 hidden pages