Bryant 580J*04A, 580J*04B, 580J*05C, 580J*06A, 580J*04C Installation Instructions Manual

...
LEGACY™ LINE 580J SINGLE PACKAGE ROOFTOP WITH GAS HEAT/ELECTRIC COOLING SIZES 04, 05, 06 & 07
Installation Instructions
580J 07 units for installation in the United States contain use of a 2-Speed Indoor Fan Motor System. This complies with the U.S. Department of Energy (DOE) efficiency standard of 2018. 580J 07 units for installation outside the United States may or may not contain use of the 2-Speed Indoor Fan Motor System as they are not required to comply with the U.S. Department of Energy (DOE) efficiency standard of 2018. For specific details on operation of the 2-Speed Indoor Fan Motor System refer to the Variable Frequency Drive (VFD) Factory-Installed Option 2-Speed Motor Control Installation, Setup, and Troubleshooting manual.

TABLE OF CONTENTS

Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 2-6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-48
Job-Site Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 1 — Plan for Unit Location. . . . . . . . . . . . . . . . . . . . . 6
Step 2 — Plan for Sequence of Unit Installation. . . . . . . . . . . . 7
Curb-mounted Installation . . . . . . . . . . . . . . . . . . . . . . . . 7
Pad-mounted Installation. . . . . . . . . . . . . . . . . . . . . . . . . 7
Frame-mounted Installation. . . . . . . . . . . . . . . . . . . . . . . 7
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 — Provide Unit Support. . . . . . . . . . . . . . . . . . . . . . 7
Roof Curb Mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Slab Mount (Horizontal Units Only) . . . . . . . . . . . . . . . . 7
Alternate Unit Support (In Lieu Of Curb or Slab
Mount) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 5 — Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . 9
Step 6 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . . . . . .9
Positioning on Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required) . . . . . . . . . . . . . . . . . . . . . 10
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . . . . . 10
Economizer And Two Position Damper Hood Package
Removal And Setup — Factory Option. . . . . . . . . . . . .10
Economizer Hood And Two-position Hood . . . . . . . . . 10
Step 9 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 10 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . .11
Factory-option Thru-base Connections (Gas
Connections). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Step 11 — Install External Condensate Trap and Line . . . 14
Step 12 — Make Electrical Connections . . . . . . . . . . . . . 14
Field Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Units With Factory-Installed Non-Fused Disconnect . 15 Units Without Factory-Installed Non-fused Disconnect. . .16
Convenience Outlets. . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Factory-Option Thru-Base Connections (Electrical
Connections) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Perfect Humidity™ Control Connections . . . . . . . . . . . .20
Economi$er
Economizer Module Wiring Details. . . . . . . . . . . . . . . 23
Interface Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
RTU Open Control System . . . . . . . . . . . . . . . . . . . . . 36
RTU Open Control System Field Connections . . . . . . 40
RTU Open Communication Wiring Protocols . . . . . . . 43
Local Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Outdoor Air Enthalpy Control . . . . . . . . . . . . . . . . . . . 45
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Step 13 — Adjust Factory-Installed Options . . . . . . . . . . 47
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Economi$er IV Occupancy Switch . . . . . . . . . . . . . . . 47
Step 14 — Install Accessories . . . . . . . . . . . . . . . . . . . . . 47
Step 15 — Check Belt Tension . . . . . . . . . . . . . . . . . . . . 47
Belt Force — Deflection Method. . . . . . . . . . . . . . . . . 47
Belt Tension Method . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1, CL-2
®
X (Factory-Installed Option) . . . . . . . . . 22
Page

GENERAL

These installation instructions cover the 580J units with gas heat and electric cooling. Units are pre-wired and pre-charged with environmentally sound Puron
®
(R-410A) refrigerant at the factory. See Fig. 1 for model number nomenclature. See Fig. 2 for unit dimensions. See Fig. 3 for service clearances.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The quali­fied installer or agency must use factory-authorized kits or ac­cessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when install­ing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-alert symbol. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAU­TION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signi­fies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may re­sult in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in en­hanced installation, reliability, or operation.
WARNING
Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pres­sures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field­supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
WARNING
Failure to follow this warning could cause personal injury or death. Before performing service or maintenance opera­tions on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
!
WARNING
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puron (R-410A) refrigerant systems operate at higher pres­sures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
WARNING
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrig­erants and oils.
CAUTION
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
Rated Indoor Airflow (cfm) — Table 1 lists the rated in-
door airflow used for the AHRI efficiency rating for the units covered in this document.
Table 1 — AHRI Efficiency — Rated Indoor Airflow
MODEL NUMBER FULL LOAD AIRFLOW (CFM)
580J*04A/B/C 1275 580J*05A/B/C 1400 580J*06A/B/C 1800
580J*07A/C/G/J 2200
2
Position:
Example:
1234567891011 12 13 14 15 16 17
580JE0 6A072A1B0AA
Unit Type
580 - Gas Heat RTU Legacy™ Series
Model
J - Puron
®
(R-410A) Refrigerant
Voltage
E = 460-3-60 J = 208/230-1-60 P = 208/230-3-60 T = 575-3-60
Cooling Tons
04 - 3 tons 05 - 4 tons 06 - 5 tons 07 - 6 tons
Refrig. System/Gas Heat Options
A = Standard One Stage cooling models/Natural Gas Heat B = Standard One Stage cooling models/Low NO C = Standard One Stage cooling models/Stainless Steel HX Heat
Heat
x
G = One Stage cooling models/Alum Heat Exchanger with Perfect Humidity™ (07 models only) J = One Stage cooling models/Stainless Steel Exchanger with Perfect Humidity™ (07 models only)
Heat Level
Standard/Stainless Steel 072 = 72,000 115 = 115,000 125 = 125,000 150 = 150,000
Low NOx 060 = 60,000 090 = 90,000 120 = 120,000
Note: On single phase (-J voltage code) models, the following are not available as a factory installed option:
- Coated Coils or Cu Fin Coils
- Louvered Hail Guards
- Economizer or 2 Position Damper
- Powered 115 Volt Convenience Outlet
Packaging & 2-Speed Indoor Fan Motor
A = Standard Packaging, electro mech. controls that require W7212 EconoMi$er
®
IV B = LTL Packaging, electro mech. controls that require W7212 EconoMi$er IV C = Standard Packaging, electro mech. controls that require W7220 EconoMi$er X F = LTL Packaging, electro mech. controls that require W7220 EconoMi$er X
Factory Installed Options
0A = None NOTE: See the 580J 3 to 15 ton Price Pages for a complete list of factory installed options.
Outdoor Air Options
A = None B = Temperature Economizer, Barometric Relief, Standard Leak (W7212 or W7220) E = Temperature Economizer, Barometric Relief, Standard Leak w/CO
Enthalpy
H =
Economizer, Barometric Relief,
, (W7212 or W7220)
2
Standard Leak, (W7212 or W7220)
Enthalpy
L = Standard Leak w/CO Q = Motorized 2 Position Damper U = Temperature
Economizer,Barometric Relief,
, (W7212 or W7220)
2
Economizer,
Barometric
Relief, Ultra Low Leak, (W7220) W =
Enthalpy
Economizer, Barometric Relief,
Ultra Low Leak, (W7220)
Indoor Fan Options
0 = Direct Drive, Standard Staitc Option (04/05/06 models only) 1 = Belt Drive, Standard Static Option 2 = Belt Drive, Medium Static Option 3 = Belt Drive, High Static/ Option
Coil Options For Round Tube/Plate Fin Condenser Coil Models Only (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu -Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Coil Options For All Aluminum - Novation Condenser Coil Models Only (Outdoor - Indoor - Hail Guard)
G = Al/Al - Al/Cu H = Al/Al - Cu/Cu J = Al/Al - E-coat Al/Cu K = E-coat Al/Al - Al/Cu L = E-coat Al/Al - E-coat Al/Cu T = Al/Al - Al/Cu — Louvered Hail Guard U = Al/Al - Cu/Cu — Louvered Hail Guard V = Al/Al - E-coat Al/Cu — Louvered Hail Guard W = E-coat Al/Al - Al/Cu — Louvered Hail Guard X = E-coat Al/Al - E-coat Al/Cu — Louvered Hail Guard
Fig. 1 — 580J*04-07 Units Model Number Nomenclature
3
Fig. 2 — Unit Dimensional Drawing
4
Fig. 2 — Unit Dimensional Drawing (cont)
5
C
LOCATION
DIMENSION
in. (mm)
CONDITION
A
48 (1219)
18 (457) 18 (457) 12 (305)
Unit disconnect is mounted on panel. No disconnect, convenience outlet option. Recommended service clearance. Minimum clearance.
B
42 (1067)
36 (914)
Special
Surface behind servicer is grounded (e.g., metal, masonry wall). Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass). Check for sources of flue products within 10-ft of unit fresh air intake hood.
C
36 (914) 18 (457)
Side condensate drain is used. Minimum clearance.
D
48 (1219)
42 (1067)
36 (914)
Special
No flue discharge accessory installed, surface is combustible material. Surface behind servicer is grounded (e.g., metal, masonry wall, another unit). Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass). Check for adjacent units or building fresh air intakes within 10-ft (3 m) of this unit’s flue outlet.
D
B
A
Fig. 3 — Service Clearances — 580J**04-07 Units
NOTE: Unit is not designed to have overhead obstruction. Contact Application Engineering for guidance on any appli­cation planning overhead obstruction or for vertical clear­ances.

INSTALLATION

Job-Site Survey —
installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may in­terfere with unit lifting or rigging.
Step 1 — Plan for Unit Location — Select a location
for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units. Be sure that unit is installed such that snow will not block the com­bustion intake or flue outlet.
Complete the following checks before
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air in­lets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Com­bustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1­B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adja­cent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assem­bly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
6
ROOF MOUNT — Check building codes for weight dis-
A
B
C
A TO B
in. (mm)
B TO C
in. (mm)
A TO C
in. (mm)
0.5 (13) 1.0 (25) 1.0 (25)
tribution requirements. Unit operating weight is shown in Table 2.
Step 2 — Plan for Sequence of Unit Installation —
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

CURB-MOUNTED INSTALLATION

1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation in­structions for details)
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 11 for de­tails)
5. Rig and place unit
6. Install outdoor air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories

PAD-MOUNTED INSTALLATION

1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connec­tion plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories
FRAME-MOUNTED INSTALLATION — Frame­mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit — Inspect unit for transportation
damage. File any claim with transportation agency. Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.

Step 4 — Provide Unit Support

ROOF CURB MOUNT — Curb should be level. This is necessary for unit drain to function properly. Unit leveling tol­erances are show in Fig. 4. Refer to Accessory Roof Curb In­stallation Instructions for additional information as required.
Fig. 4 — Unit Leveling Tolerances
Accessory roof curb details and dimensions are shown in Fig. 5. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 5. Improperly applied gasket can also result in air leaks and poor unit performance.
Install insulation, cant strips, roofing felt, and counter flash­ing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired, use factory-supplied bly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.
SLAB MOUNT (HORIZONTAL UNITS ONLY) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob­structing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT) — A non-combustible sleeper rail can
be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of three equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.
1
/2-in. pipe coupling and gas plate assem-
Table 2 — Operating Weights
580J
Base Unit 438 (199) 494 (224) 524 (238) 607 (275) Economizer 35 (16) 35 (16) 35 (16) 35 (16) Perfect Humidity™ System 15 (7) 15 (7) 15 (7) 24 (7) Cu Fins 25 (11) 43 (20) 56 (25) 73 (33) Powered Outlet 32 (15) 32 (15) 32 (15) 32 (15) Curb
14-in. (356 mm) 110 (50) 110 (50) 110 (50) 110 (50) 16-in. (610 mm) 145 (66) 145 (66) 145 (66) 145 (66)
04 05 06 07
UNITS — lb (kg)
7
E
E
7/16"
[11]
4 9/16"
[115.5]
1/4"
[7.0]
5' 7-3/8"
[1711.3]
1' 4-13/16"
[427] INSIDE
1-3/4"
[44.4]
2-3/8"
[61]
1-3/4"
[44.5]
1.00"
[25.4]
"A"
1-3/4"
[44.4]
21.74" [552.2]
5.42" [137.7]
11.96" [303.8]
4.96" [126.0]
70.87" [1800.2]
40.69" [1033.5]
21.84" [554.7]
16.03" [407.2]
1.75" [44.5]
20.41" [518.3]
3.00"
[76.2]
13.78" [350.0]
14.00" [355.6]
3.00"
[76.2]
15.19" [385.8]
32.19" [817.6]
3'-1 3/16"
[944.6]
"A"
1-3/4"
[44.5]
CRBTMPWR001A01 3/4" [19] NPT
3/4" [19] NPT
1/2" [12.7] NPTCRRFCURB002A01
CONNECTOR PKG. ACC.
GAS CONNECTION TYPE
GAS FITTING
POWER WIRING
FITTING
CONTROL WIRING
FITTING
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
THRU THE CURB
1/2" [12.7] NPT 1/2" [12.7] NPT
CRBTMPWR003A01
THRU THE BOTTOM
ROOF CURB
ACCESSORY #
A
CRRFCURB001A01
14"
[356]
24"
[610]
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898CMM--04/22/13
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
A
DRAWING RELEASE LEVEL:
PRODUCTION
THIRD ANGLE
PROJECTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCES ON:
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1 DEC 2 DEC 3 DEC ANG
MATERIAL
----
---
AUTHORIZATION NUMBER TITLE
1041738
CURB ASY, ROOF
ENGINEERING
(004-007)
ENGINEERING REQUIREMENTS
-
-
-
-
SIZE DRAWING NUMBER REV
T-005, Y-002
DRAFTER CHECKER
D
48TC400427
B
WEIGHT:
-
MMC 06/17/11 - -
SHEET 5 OF 5
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
-PURCH - N/A MMC
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
TYPICAL (4) SIDES
SUPPLY AIR RETURN AIR
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
UNIT
GASKET
(SUPPLIED WITH CURB)
RIGID INSULATION
(FIELD SUPPLIED)
DUCT
(FIELD SUPPLIED)
NAIL (FIELD SUPPLIED)
CERTIFIED DRAWING
VIEW "B"
CORNER DETAIL
SEE VIEW "B"
RETURN AIR
SUPPLY AIR
SUPPLY AIR
OPENING
RETURN AIR
OPENING
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SEE NOTE #2
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1/3/4"[44.5]
SCALE 0.250
E-E
SECTION
8
Fig. 5 — Roof Curb Details
Step 5 — Field Fabricate Ductwork — Cabinet
DETAIL "A"
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL "A"
"A"
(914-1371)
36"- 54"
"C"
"B"
SPREADER
BARS
REQUIRED
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in () are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
4. Max weight includes the base unit plus shipping pallet plus all available FIOPs which could be on that size unit.
UNIT
MAX WEIGHT
DIMENSIONS
A B C
LB KG LB KG LB KG LB KG 580J-04A 772 350 74.5 1890 39.0 990 33.5 850 580J-05A 826 375 74.5 1890 39.0 990 33.5 850 580J-06A 896 406 74.5 1890 39.0 990 33.5 850 580J-07A 1075 489 74.5 1890 39.0 990 41.5 1055
return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer. For vertical ducted applica­tions, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insu­lated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
CAUTION
Failure to follow this caution may result in damage to roof­ing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit — Keep unit upright and
do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Level by using unit frame as a refer­ence. See Table 1 and Fig. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.
Rigging materials under unit (cardboard or wood to prevent base pan damage) must be removed PRIOR to placing the unit on the roof curb. When using the standard side drain connec­tion, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a
1
/2-in. square socket drive extension.
For further details see Step 11 — Install External Condensate Trap and Line on page 14.
Before setting the unit onto the curb, recheck gasketing on
curb.
CAUTION
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
POSITIONING ON CURB — Position unit on roof curb so that the following clearances are maintained: clearance between the roof curb and the base rail inside the front and back, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately (6.4 mm).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft (1220 mm) from electric and gas meters, gas regu­lators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechani­cal draft system flue assembly at least 48 in. (1220 mm) from an adjacent building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will reduce the minimum clearance to combustible material to 18 in. (460 mm).
After unit is in position, remove rigging skids and shipping materials.
1
/4 in. (6.4 mm)
1
/4 in.
Fig. 6 — Rigging Details
9
Step 7 — Convert to Horizontal and Connect
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
FILTER ACCESS PANEL
Hood Parts
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
Ductwork (when required) —
tical duct configuration. Unit without factory-installed econo­mizer or return air smoke detector option may be field-convert­ed to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 7.
Unit is shipped in the ver-
Fig. 8 — Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the base-
pan and remove. Locate and cut the (2) plastic tie-wraps securing the assembly to the damper. (See Fig. 9.) Be careful to not damage any wiring or cut tie-wraps secur­ing any wiring.
Fig. 7 — Horizontal Conversion Panels
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. In­sulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accor­dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.

Step 8 — Install Outside Air Hood

ECONOMIZER AND TWO POSITION DAMPER HOOD PACKAGE REMOVAL AND SETUP — FACTORY OPTION

NOTE: Economizer and two position damper are not avail­able as factory installed options for single phase (-J voltage code) models.
1. The hood is shipped in knock-down form and must be field assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are packaged together, attached to a metal support tray using plastic stretch wrap, and shipped in the return air compartment behind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie­wraps.
2. To gain access to the hood, remove the filter access panel. See Fig. 8.
Fig. 9 — Economizer and Two-Position Damper Hood
Parts Location
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps out­lined in Economizer Hood and Two–Position Hood, be­low.

ECONOMIZER HOOD AND TWO-POSITION HOOD

NOTE: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
10
1. The indoor coil access panel will be used as the top of
B
TOP PANEL
INDOOR COIL ACCESS PANEL
19 1/16
SCREW
HOOD DIVIDER
LEFT HOOD
SIDE
33 3/8”
(848mm)
(483mm)
DIVIDER
BAROMETRIC RELIEF
CLEANABLE ALUMINUM FILTER
FILTER
HOOD
FILTER CLIP
OUTSIDE AIR
BLOWER ACCESS PANEL
the hood. Remove the screws along the sides and bot­tom of the indoor coil access panel. See Fig. 10.
TOP PANEL
TOP PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 10 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws pro­vided to attach the hood sides to the unit. See Fig. 11.
Fig. 12 — Economizer Filter Installation

Step 9 — Install Flue Hood

Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping loca­tion and using screws provided, install flue hood and screen in location shown in Fig. 13.
Fig. 11 — Economizer Hood Construction
3. Remove the shipping tape holding the economizer baro­metric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 11 and 12. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bot­tom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 12.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
Fig. 13 — Flue Hood Details

Step 10 — Install Gas Piping

Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NF­GC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances. This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at el­evations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions re­garding these accessories.
NOTE: Furnace gas input rate on rating plate is for installa­tion up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be der­ated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for alti­tudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating, see Table 3. For liquefied petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13.0 in. wg (3240 Pa) at the unit connection, see Table 4.
11
Table 3 — Natural Gas Supply Line Pressure Ranges
LEGEND
* Field-Supplied.
STEEL PIPE NOMINAL
DIAMETER (in.)
SPACING OF SUPPORTS X
DIMENSIONS (FT)
1
/
2
6
3
/
4
or 1 8
1
1
/
4
or larger 10
NFGC — National Fuel Gas Code
LOW VOLTAGE CONDUIT CONNECTOR
HIGH VOLTAGE CONDUIT CONNECTOR
BRASS FITTING FOR 3 TO 6 TON UNITS.
UNIT MODEL UNIT SIZE MIN. MAX.
580J* 04, 05, 06, 07
4.0 in. wg (996 Pa)
13.0 in. wg (3240 Pa)
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MODEL UNIT SIZE MIN. MAX.
580J* 04, 05, 06, 07
11.0 in. wg (2740 Pa)
13.0 in. wg (3240 Pa)
The gas supply pipe enters the unit at the burner access pan­el on the front side of the unit, through the long slot at the bot­tom of the access panel. The gas connection to the unit is made
1
/2-in. FPT gas inlet port on the unit gas valve.
to the
Manifold pressure is factory-adjusted for NG fuel use. Ad­just as required to obtain best flame characteristics. See Table 5 for ranges.
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODEL UNIT SIZE
580J* 04, 05, 06, 07
HIGH FIRE.
3.5 in. wg (872 Pa)
LOW FIRE
1.7 in. wg (423 Pa)
Manifold pressure for LP fuel use must be adjusted to spec­ified range, see Table 6. Follow instructions in the accessory kit to make initial readjustment.
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE
580J* 04, 05, 06, 07
HIGH FIRE.
10.0 in. wg (2490 Pa)
LOW FIRE
5.0 in. wg
(1245 Pa)
CAUTION
Failure to follow this caution may result in damage to equipment.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
X
9” MINIMUM CLEARANCE
BASE UNIT
BASE RAIL
FROM GAS METER
FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
48” MINIMUM
ROOF CURB
DRIP LEG PER NFGC
GAS REGULATOR
*
*
FIELD-FABRICATED SUPPORT
*
*
Fig. 14 — Gas Piping Guide (with Accessory Thru-the-
Curb Service Connections)
FACTORY-OPTION THRU-BASE CONNECTIONS (GAS CONNECTIONS) — This service connection kit
consists of a electrical bulkhead connector and a
1
/2-in. NPT gas adapter fitting (brass), a 1/2-in.
3
/4-in. electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. See Fig. 15.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe size smaller than gas supply line to allow for a maximum pressure drop of 0.5­in.wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru-curb/ under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult ac­cessory kit installation instructions for details on these installa­tion methods. Observe clearance to gas line components per Fig. 14.
1
/2-in. Size the
Fig. 15 — Thru-Base Connection Fittings
The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
Install a Attach a
1
/2-in. NPT street elbow on the thru-base gas fitting.
1
/2-in. pipe nipple with minimum length of 16-in. (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 16.
12
EMBOSSMENT
9 (229mm) min
Union
Shut Off
Valve
Drip Leg
Thru-Curb Adapter
Unit Base Rail
Drip Leg
Shut Off
Valve
Union
Thru-Curb Adapter
Burner Access Panel
9 (229mm) min
Unit Base Rail
BRASS FITTING FOR 3-6 TON UNITS
SUPPORT BRACKET
Fig. 16 — Gas Line Piping (3 to 6 Ton Units Only)
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6-ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9-in. (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4-ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual shut­off valve be located upstream of the sediment trap. See Fig. 17 and 18 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 19 for typical piping arrangement when thru-base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
Fig. 18 — Gas Piping with Thru-Curb Accessory
(Alternate Layout)
Fig. 17 — Gas Piping with Thru-Curb Accessory
Fig. 19 — Gas Piping Thru-Base Connections
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4-in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/2-in., follow rec-
ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied pe­troleum gases as specified by local and/or national codes. If using PTFE (Teflon*) tape, ensure the material is Dou­ble Density type and is labeled for use on gas lines. Apply tape per manufacturer’s instructions.
4. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting pip­ing to unit.
* Teflon is a registered trademark of DuPont.
13
NOTE: Pressure test the gas supply system after the gas
BURNER
ORIFICE
DRAIN (FACTORY-INSTALLED)
PLUG
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
ALTERNATE BOTTOM DRAIN
MINIMUM PITCH 1 (25mm) PER 10 (3m) OF LINE
BASE RAIL
OPEN VENT
TO ROOF DRAIN
DRAIN PLUG
ROOF CURB
SEE NOTE
2 in.
(51) MIN
supply piping is connected to the gas valve. The supply pip­ing must be disconnected from the gas valve during the test­ing of the piping systems when test pressure is in excess of
0.5 psig (3450 Pa). Pressure test the gas supply piping sys­tem at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas pip­ing system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
Check for gas leaks at the field-installed and factory-in­stalled gas lines after all piping connections have been com­pleted. Use soap-and-water solution (or method specified by local codes and/or regulations).
WARNING
Failure to follow this warning could result in personal
injury, death and/or property damage.
• Connect gas pipe to unit using a backup wrench to avoid damaging gas controls.
• Never purge a gas line into a combustion chamber.
• Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions.
• Use proper length of pipe to avoid stress on gas con­trol manifold.
NOTE: If orifice hole appears damaged or it is suspected to have been re-drilled, check orifice hole with a numbered drill bit of correct size. Never re-drill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. See Fig. 20.
Fig. 21 — Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be
completed after the unit is in place. See Fig. 22. NOTE: If the alternate bottom drain is not used check the
drain plug for tightness prior to setting the unit on the roof curb.
Fig. 20 — Orifice Hole
Step 11 — Install External Condensate Trap and Line —
on the end of the condensate pan and an alternate connection on the bottom. See Fig. 21. Unit airflow configuration does not determine which drain connection to use. Either drain connec­tion can be used with vertical or horizontal applications.
red drain plug from the bottom connection (use a square socket drive extension) and install it in the side drain connection.
The unit has one 3/4-in. condensate drain connection
To use the alternate bottom drain connection, remove the
1
/2-in.
Fig. 22 — Condensate Drain Piping Details
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (
3
/4-in.).

Step 12 — Make Electrical Connections

WARNING
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/ NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limita­tions of minimum 63°F (33°C) rise.
14
FIELD POWER SUPPLY — If equipped with optional
Disconnect
per
NEC
Disconnect
per
NEC
208/230-1-60
11
13
11
13 13
L1
L2 L3
TB
C
CIFC
or
(1-ph IFM)
208/230-3-60
460-3-60 375-3-60 575-3-60
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory con­nected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your ar­ea.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit­mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.
Refer to Fig. 23 for power transformer connections and the
discussion on connecting the convenience outlet on page 18.
Field power wires are connected to the unit at line-side pres­sure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component ar­rangement) or at factory-installed option non-fused disconnect switch. Max wire size is #2 AWG (copper only). (See Fig. 23.)
NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only.
Assemble the shaft and handle to the switch at this point. Dis­card the factory test leads (see Fig. 24).
Connect field power supply conductors to LINE side termi­nals when the switch enclosure cover is removed to attach the handle.
Fig. 24 — Location of Non-Fused Disconnect Enclosure
To field install the NFD shaft and handle
1. Remove the unit front pane (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure - (2) on the face of the cover and (1) on the left side cover (see Fig. 25).
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF position (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in the horizontal position.
6. Measure from the tip of the shaft to the top surface of the black pointer; the measurement should be 3.75 to 3.88 in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow point­ing at OFF.
9. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) hex screws on the NFD enclosure.
12. Re-install the unit front panel.
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch
Fig. 23 — Power Wiring Connections
WARNING
and 580J unit. Use only copper wire. (See Fig. 24)
UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT — The factory-installed option non-fused
disconnect (NFD) switch is located in a weatherproof enclo­sure located under the main control box. The manual switch handle and shaft are shipped in the disconnect enclosure.
Fig. 25 — Handle and Shaft Assembly for NFD
15
UNITS WITHOUT FACTORY-INSTALLED NON-
ABC
MOTOR
FUSED DISCONNECT — When installing units, provide a disconnect switch per NEC (National Electrical Code) of ade­quate size. Disconnect sizing data is provided on the unit infor­mative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative late if mounting the disconnect on the unit cabinet.
All Units
— Field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 23 and the unit label dia­gram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #4 ga AWG per pole.
Provide a ground-fault and short-circuit over-current protec­tion device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maxi­mum Over-current Protection) device size.
Table 7 — Unit Wire/Fuse or HACR Breaker Sizing Data — 2-Speed Indoor Fan Motor
NO C.O. OR UNPWR C.O. WITH PWRD C.O.
WITH P.E. (POWERED
MCA
UNIT
580J*A07
NOM. V-PH-HZIFM
208/230-3-60
460-3-60
575-3-60
TYPE
STD 34/33 50/50 32/32 167 35/35 50/50 35/34 169 38/38 50/50 38/38 172 40/40 50/50 40/40 174
MED 35/34 50/50 34/33 193 37/36 50/50 36/35 195 40/39 50/50 40/39 198 42/41 60/60 42/41 200
HIGH 37/36 50/50 37/36 217 39/38 50/50 39/38 219 42/41 60/60 42/41 222 44/43 60/60 44/43 224
STD15 20 148216 20 1583 17 20 17 84 18 25 1885
MED15 20 159516 20 1696 18 25 17 97 19 25 1898
HIGH 16 20 16 107 17 25 17 108 19 25 19 109 20 25 20 110
STD13 15 127015 20 1472 15 20 14 72 16 20 1674
MED14 15 137916 20 1681 16 20 15 81 17 20 1883
HIGH 14 15 13 79 16 20 16 81 16 20 15 81 17 20 18 83
MCA
NO P.E.
FUSE
DISC. SIZE
OR
HACR
FLA LRA FLA LRA FLA LRA FLA LRA
BRKR
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the male spade connector from the 230-v connection and moving it to the 200-v
1
/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional informa­tion.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Tables 7 and 8. On 3-phase units, voltages between phases must be bal­anced within 2% and the current within 10%. Use the formula shown in the legend for Tables 7 and 8 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invali­date any applicable Bryant warranty.
NOTE: Check all factory and field electrical connections for tightness.
FROM UNIT)
FUSE
DISC. SIZE
OR HACR BRKR
MCA
NO P.E.
FUSE
OR HACR BRKR
DISC. SIZE
WITH P.E. (POWERED
FROM UNIT)
FUSE
OR
MCA
HACR BRKR
1
/4-in. fe-
DISC. SIZE
LEGEND AND NOTES FOR TABLES 7 AND 8
LEGEND
BRKR — Circuit breaker C.O. — Convenience outlet DD — Direct drive DISC — Disconnect FLA — Full load amps IFM — Indoor fan motor LRA — Locked rotor amps MCA — Minimum circuit amps MOCP — MAX FUSE or HACR circuit breaker P.E. — Power exhaust PWRD C.O. — Powered convenience outlet UNPWR C.O. — Unpowered convenience outlet
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage:
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance:
% Voltage Imbalance = 100 x
Example: Supply voltage is 230-3-60
AB = 224 v BC = 231 v AC = 226 v
Average Voltage = 100 x
Determine maximum deviation from average voltage.
max voltage deviation from average voltage
average voltage
(224 + 231 + 226)
33
681
=
=227
(AB) 227-224 = 3 v (BC) 231-227 = 4 v (AC) 227-226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allow­able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
227
4
=1.76%
16
Loading...
+ 36 hidden pages