III. Field Test Operation ...................... 24
IV. Indoor Airflow and Airflow
Adjustments ............................ 24
V. Gas Valve Adjustment ....................25
VI. Main Burners ........................... 28
VII. Power Exhaust Operation .................. 28
VIII. Head Pressure Control ................... 28
IX. Low Ambient Kit .........................28
CARE AND MAINTENANCE .....................28
SERVICE .....................................29-32
I. Cleaning ...............................29
II. Lubrication ............................. 29
III. Evaporator Fan Service and
Replacement ............................31
IV. Evaporator-Fan Motor Replacement ........31
V. Power Failure ...........................31
VI. Refrigerant Charge .......................31
VII. Filter Drier ..............................32
VIII. Thermostatic Expansion Valve (TXV) ........ 32
IX. Protective Devices ....................... 32
X. Relief Devices ........................... 32
XI. Control Circuits ......................... 32
XII. Compressor Lockout Logic ...............32
XIII. Replacement Parts ....................... 32
TROUBLESHOOTING ...........................33-41
I. Diagnostic LEDs .........................33
II. Error Code Summary .....................34
III. Input/Output Channel Designations .........34
START-UP CHECKLIST ....................CL-1, CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters.Allother
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
WARNING:
nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.
WARNING:
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s
Information Manual provided with this unit for more
details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in
your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
WARNING:
pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is
subjected to pressure greater than 0.5 psig, it must be
replaced before use. When pressure testing fieldsupplied gas piping at pressures of 0.5 psig or less, a
unit connected to such piping must be isolated by closing the manual gas valve(s).
Before performing service or mainte-
Disconnect gas piping from unit when
INSTALLATION
I. PROVIDE UNIT SUPPORT
CAUTION:
All panels must be in place when rig-
ging. Unit is not designed for handling by fork truck.
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with the curb. Accessory roof curb and
information required to field fabricate a roof curb or horizontal adapter are shown in Fig. 1. Install insulation, cant strips,
roofing, and counter flashing as shown. Ductwork can be
secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a leak-proof seal. Install gasket supplied with the
roof curb as shown in Fig. 1. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain
to function properly. Unit leveling tolerance is shown in
Fig 1. Refer to Accessory Roof Curb Installation Instructions
for additional information as required. When accessory roof
curb is used, unit may be installed on class A, B, or C roof
covering material.
NOTES:
1. Unless otherwise specified, all dimensions are to outside of part.
2. Roof curb accessory is shipped disassembled.
3. All roof curb parts are to be 16 ga galvanized steel.
4. Dimensions are in inches.
NOTE: On retrofit jobs, ductwork may be attached to old unit
instead of roof curb. Be careful not to damage ductwork when
removing old unit.
B. Alternate Unit Support
When the preferred curb or adapter cannot be used, support
unit with sleepers using unit curb or adapter support area. If
sleepers cannot be used, support long sides of unit (refer to
Fig. 2 and 3) with 3 equally spaced 4-in. x 4-in. pads on each
side. Unit may sag if supported by corners only.
II. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright, and do not drop.
Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by
using unit frame as a reference; leveling tolerance is shown
in. Fig. 1. See Fig. 4 for additional information. Unit weight
is shown in Table 1.
Four lifting lugs are provided on the unit base rails as shown
in Fig. 4. Refer to rigging instructions on unit.
(Copy continued on page 7.)
NOTE: To prevent standing water in the drain pan of the
indoor section and the heat exchangers, UNIT CAN ONLY BE
PITCHED AS SHOWN.
UNIT LEVELING TOLERANCES
Deg.in.Deg.in.
*From edge of unit to horizontal.
DIMENSIONS*
(Degrees and Inches)
AB
1.02.9.50.75
Fig. 1 — Roof Curb (Sizes 240-360)
—2—
NOTES:
1. Weights include economizer (STD).
2.Center of gravity.
3. Do not locate adjacent units with flue discharge
facing economizer inlet. Min. clearances to be:
Adjacent Units: 158-09
Top of Units: No Overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Heat Side: 48-09
FilterAccess Side: 108-09 (For Removalof Evaporator Coil)
4. For smaller service andoperational clearances, contact Carrier Application Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is
recommended the ducts be supported by braces
as done on accessory roof curb.
3. Do not locate adjacent units with flue discharge facing
economizer inlet. Min. clearances to be:
Adjacent Units: 158-09
Top of Units: No Overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Application Engineering department.
5. Dimensions are in inches.
6. For side supply/return applications a single return and
supply ductwork connection is recommended for covering both return and both supply openings.
MUST BE IN PLACE WHEN RIGGING.
NOTE: Rig with four cables and spread with two 92 in.
(2337 mm) spreader bars. Maintain a distance of 74 in.
(1880 mm) from top of unit to eyehook.
NOTE:
Add 32 lb (14.5 kg) for domestic crating.
Add 312 lb (142 kg) for export crating.
Add 220 lb (100 kg) for copper condenser coil.
Add 250 lb (113 kg) for power exhaust.
Quantity11 1 1
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)33.333.333.333.3
CONDENSER FANPropeller Type
Nominal Cfm13,42013,42013,42013,420
Quantity...Diameter (in.)2...302...302...302...30
Motor Hp (1075 Rpm)11 1 1
EVAPORATOR COILCross-Hatched
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)31.731.731.731.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20x152...20x152...20x152...20x15
Type DriveBeltBeltBeltBelt
Nominal Cfm8,00010,00011,00012,000
Motor Hp510**157.510**151015**201015**20
Motor Frame Size
High EfficiencyS184TS215TS254TS213TS215TS254TS215TS254TS256TS215TS254TS256T
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1200120012001200
Motor Pulley Pitch Diameter4.84.45.75.46.15.54.44.95.94.45.75.9
Nominal Motor Shaft Diameter (in.)1
Fan Pulley Pitch Diameter (in.)12.48.69.112.411.18.79.48.18.79.09.18.7
Nominal Fan Shaft Diameter (in.)115⁄
Belt, Quantity...Type
Belt, Length (in.)
Pulley Center Line Distance (in.)16.0-18.7 15.6-18.4 15.0-17.915.6-18.415.0-17.9 15.6-18.415.0-17.915.6-18.415.0-17.9
Factory Speed Setting (rpm)717924109677396211068481059118788410961187
Provide clearance around and above unit for airflow, safety,
and service access (Fig. 2 and 3).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas Code,
ANSI Z223.1 (American National Standards Institute).
Although unit isweatherproof,guardagainst water from higher
level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
FAN
SHEAVE
FAN
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
(QUANTITY)
OUTSIDE
BELT
LENGTH
BELT
TENSION
(lb at
.24 in.)
B. 580H Units
Remove shipping covers from supply and return air openings.Attachfield-suppliedductworkto unit. Use a single duct
over both return openings and a single duct over both supply openings. See Fig. 3 for duct opening dimensions. Secure
all ducts to the building structure. See Fig. 6. Use flexible
duct connectors between unit and ducts as required.
Install accessory barometric relief or power exhaust in
the field-fabricated return ductwork. Refer to Power
Exhaust/Barometric Relief Damper Hood section for more
information.
III. FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct connectors betweenunitandducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with
counter flashing andmasticinaccordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
To attach ductwork to roof curb, insert ductwork approximately 10 to 11 in. up into the curb. Connect ductwork to
14-gage roof curb material using sheet metal screws driven
from inside the duct.
WARNING:
For vertical supply and return units, tools
or parts could drop into ductwork and cause an injury.
Install 90 degree elbow turns in the supply and return
ductwork between the unit and the conditioned space.
If a 90 degree elbow cannot be installed, then grilles of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.
IV. UNIT DUCT CONNECTIONS
A. 580G Units
Unit is shipped for through-the-bottom duct connections. Ductwork openings are shown in Fig. 2. Attach all ductwork toroof curb. Air distribution is shown in Fig. 5. Refer to
installation instructions shipped with accessory roof curb for
more information.
Fig. 5 — Air Distribution — Thru-the-Bottom
Fig. 6 — Air Distribution — Thru-the-Side
—7—
V. FLUE HOOD
Flue hood is shipped inside gas section of unit. To install, secure flue hood to access panel. See Fig. 7.
NOTE: When properly installed, flue hood will line up with
combustion fan housing. See Fig. 8.
Fig. 7 — Flue Hood Location
Fig. 9 — Condensate Drain Connections
(Typical Roof Curb or
Slab Mount Shown)
Condensate pans are sloped sothatwaterwillcompletelydrain
from the condensate pan to comply with indoor air quality
guidelines.
VII. GAS PIPING
Unit is equipped for use with natural gas. Installation must
conform with local building codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1.
1
Install manual gas shutoff valve with a
⁄8-in. NPT pressure
tap for test gage connection at unit. Field gas piping must
include sediment trap and union. See Fig. 10.
WARNING:
Do not pressure test gas supply while
connected to unit. Always disconnect union before
servicing.
Fig. 8 — Combustion Fan Housing Location
VI. TRAP CONDENSATE DRAIN
See Fig. 2, 3, and 9 for drain location. Condensate drain is
open to the atmosphere and must be trapped. Install a trapped
drain at the drain location. One 1-in. NPT coupling is provided inside unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. Trap must
be installed to prevent freeze-up.
Natural gas pressure at unit gas connection must not be less
than 5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
Fig. 10 — Field Gas Piping
—8—
VIII. ELECTRICAL CONNECTIONS
A. Controls Options
The standard constant volume (CV) units, as shipped, are
operable as stand-alone units, using a standard (mechanical
or electronic) 2-stage heat, 2-stage cool thermostat.
Withastandard thermostat (programmable is optional), heating and cooling operation is set by space temperature. The
standard DDC (direct digital controls) are installed in the control box. The DDC control board diagram is shown in Fig. 11.
Features with Thermostat Control of Unit
• two-stage heating
• two-stage cooling
• control of unit using Y1, Y2, W1, W2, and G thermostat
inputs
• control of the indoor fan
• outdoor-air temperature/supply-air temperature
monitoring
• control of modulating economizer damper to provide free
cooling when outdoor conditions are suitable, using supplyair temperature as a control point
• control of the economizer damper and indoor fan to obtain
unoccupied free cooling
• provide power exhaust output to an external power
exhaust controller
• support a field test for field checkout
• control of 2 stages of CV power exhaust
• compressor time delay for power up and minimum off and
on times
An electronic expansion board may be field-installed to provide the following features:
• control of modulating economizer damper to maintain
indoor air quality (IAQ) when outdoor conditions are
suitable
NOTE: The IAQ sensor must be set for current output (4 to
20 mA). This requires removing the sensor cover and removing a jumper on the sensor. See Fig. 12.
• provide discrete inputs for fan status, filter status, fieldapplied status, and demand limit
• provide an output for the external alarm light indicator
• provide power exhaust fire outputs for directcontrolofpower
exhaust stages during fire or smoke control modes
• control of smoke control modes including evacuation, smoke
purge, pressurization, and fire shutdown (non-modulating
or modulating power exhaust required)
B. Power Wiring
Units are factory wiredforthevoltageshownon the unit nameplate. The main terminal block is suitable for use with aluminum or copper wires.
When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (MOCP [maximum overcurrent protection]ofunitis on the informative plate).
All field wiring must comply with NEC and all local codes.
Size wire based on MCA (minimum circuit amps) on the unit
informative plate. See Fig. 13 for power wiring connections
to the unit power terminal block and equipment ground.
The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 13. Units have circuit breakers for compressors, fan motors, and control circuit. If required
by local codes, provide an additional disconnect, per NEC and
local codes requirements, of adequate size (Table 3). Whenever external electrical sources are used, unit must be electrically grounded in accordance with local codes, or in absence
of local codes, with NEC, ANSI C1-latest year.
All field wiring must comply with NEC and local code
requirements.
C. Field Power Supply
Unit is factory wired for voltage shown on nameplate. See
Table 3 for electrical data.
Field wiring can be brought into the unit from bottom (through
basepan and roof curb) or through side of unit (corner post
next to control box).
1
⁄2-in. NPT knockout for field power wiring and a3⁄4-in.
A3
NPT knockout for 24-v control wiring are provided in base-
1
pan. In the side post, there are two 2
⁄2-in. knockouts for the
field power wiring. See Fig. 2 and 3. If control wiring is to be
7
brought in through the side of unit, a
⁄8-in. diameter hole is
provided in the condenser side post next to the control box.
If disconnect box is mounted to corner post, be careful not to
drill any screws into the condenser coil.
Routing Through Bottom of Unit
If wiring is brought in through bottom of unit, use fieldsupplied watertight conduit to run power wiring from base-
1
pan out through bottom 3
⁄2-in. hole to the disconnect box and
back into unit to the main control box.
1
Use strain relief going into control box through 2
⁄2-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section
on this page).
Low-voltage wiring must be run in watertight conduit from
the basepan to control box and through 1-in. diameter hole
provided in bottom of unit control box. Field-supplied strain
relief must be used going into the box. After wiring is in control box, make connections to proper terminals on terminal
blocks (see Field Control Wiring section on page 11).
Install conduit connector in unit basepan or side panel openings provided. Route power and ground lines through connector to connections in unit control box as shown on unit
wiring diagram and Fig. 13.
Routing Through Side of Unit
Route power wiring in field-supplied watertight conduit into
1
unit through 2
⁄2-in. hole. Strain relief (field supplied) must
be used in hole.
Use field-supplied strain relief going into control box through
1
⁄2-in. diameter hole provided. After wires are in unit con-
2
trol box, connect to power terminal block (see Power Wiring
section on this page).
Bring low-voltage control wiring through factory-drilled
7
⁄8-in. diameter hole in condenser side post. Use strain relief
going into
7
⁄8-in. diameter hole in bottom of unit control box.
After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring section
on page 11).
WARNING:
The unit must be electrically grounded
in accordance with local codes and NEC ANSI/NFPA70
(National Fire Protection Association).
—9—
—10—
Fig. 11 — Control Board Diagram
LEGEND
COM — CommonR—Relay
D—DiodeSIO — Serial Input/Output
LED — Light-Emitting DiodeSW — Switch
N.C. — Normally ClosedT—Terminal
N.O. — Normally Open
*Where X is the unit control software version number (1 or 2).
JUMPER CONNECTION
FOR VOLTAGE OUTPUT
JUMPER CONNECTION
FOR CURRENT OUTPUT
Fig. 12 — Indoor Air Quality Sensor Configuration
3. Cap orange wire.
4. Splice red wire and black unit power wire. Cap wires.
IMPORTANT: Becertain unused wires are capped. Failure to
do so may damage the transformers.
D. Field Control Wiring
Install an approved accessory thermostat. Control box diagram is shown in Fig. 14.
Thermostat Wiring
Install an approved accessory thermostat assembly (per cur-
rent price pages) according to the installation instructions included with the accessory, or these instructions. Locate thermostat assembly on a solid wall in the conditioned space to
sense average temperature.
Route thermostat cable or equivalent single leads of
no. 18AWG (American Wire Gage) colored wire from subbase
terminals to low-voltage connections as shown on unit label
wiring diagram and in Fig. 15.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG
insulated wire (35 C minimum). For over 75 ft, use no. 14
AWG insulated wire (35 C minimum). All wire larger than
no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
Set heat anticipators settings to .1 for all voltages. Settings
may be changed slightly to provide a greater degree of comfort for a particular installation.
Operating voltage to compressor must be within voltage range
indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the current
must be balanced within 10%.
Use the formula in Table 3 to determine the percentage of
voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
On 208/230-v units, transformer no. 1 is wired for 230-v. If
208/230-v unit is to be run with 208-v power supply ,the transformer must be rewired as follows:
1. Remove cap from red (208-v) wire.
2. Remove cap from spliced orange (230-v) wire. Disconnect orange wire from black unit power wire.
LEGEND
C—Compressor/Contactor
CB— Circuit Breaker
DIP— Dual In-Line Package
FU— Fuse
HR— Heater Relay
IF— Indoor Fan
OF— Outdoor Fan
PEC— Power Exhaust Controller
TB— Terminal Block
TRAN — Transformer
Fig. 14 — Control Box Diagram
—11—
Table 3— Electrical Data — 580G,H240-360
UNIT
SIZE
580G,H
240
300
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where aphaseimbalance in supply voltage is
greater than 2%.
voltage imbalance.
% Voltage Imbalance
= 100 x
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
208/230187 254 39.1 228 25.6 160215.3
460414 508 19.9 114 11.580212.7
575518 632 16.0919.664212.4
208/230187 254 39.1 228 39.1 228215.3
460414 508 19.9 114 19.9 114212.7
575518 632 16.091 16.091212.4
max voltage deviation from average voltage
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
LEGEND
or
Use the following formula to determine the percent
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
POWER
EXHAUST
16.7/
——0.96101.8/100.3 125/125
15.2
23.6 41.60.96125.4/123.9 150/150
30.8/
——0.96115.9/113.1 150/150
28.0
23.6 41.60.96139.5/136.7 175/175
46.2/
——0.96131.3/127.1 150/150
42.0
23.6 41.60.96154.9/150.7 175/175
——0.5049.460
12.6 23.60.5062.080
——0.5055.870
12.6 23.60.5068.480
——0.5062.880
12.6 23.60.5075.490
——0.5040.550
12.6 23.60.5053.160
——0.5045.460
12.6 23.60.5058.070
——0.5051.460
12.6 23.60.5064.080
24.2/
——0.96122.8/120.6 150/150
22.0
23.6 41.60.96146.4/144.2 175/175
30.8/
——0.96129.4/126.6 150/150
28.0
23.6 41.60.96153.0/150.2 175/175
46.2/
——0.96144.8/140.6 175/175
42.0
23.6 41.60.96168.4/164.0 200/200
——0.5061.280
12.6 23.60.5073.890
——0.5064.280
12.6 23.60.5076.890
——0.5071.290
12.6 23.60.5083.8100
——0.5049.860
12.6 23.60.5062.470
——0.5051.860
12.6 23.60.5064.480
——0.5057.870
12.6 23.60.5070.480
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
COMBUSTION
FAN MOTOR
= 1.53%
452 + 464 + 455
1371
=
3
= 457
7
457
POWER SUPPLY
3
—12—
Table 3— Electrical Data — 580G,H240-360 (cont)
UNIT
SIZE
580G,H
324
360
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where aphaseimbalance in supply voltage is
greater than 2%.
voltage imbalance.
% Voltage Imbalance
= 100 x
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
208/230187 254 57.1 266 39.1 228215.3
460414 508 25.6 120 19.9114212.7
575518 632 20.596 16.091212.4
208/230187 254 57.1 266 57.1 266215.3
460414 508 25.6 120 25.6120212.7
575518 632 20.596 20.596212.4
max voltage deviation from average voltage
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
LEGEND
or
Use the following formula to determine the percent
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
POWER
EXHAUST
30.8/
——0.96151.9/149.1 200/200
28.0
23.6 41.60.96175.5/172.7 225/225
46.2/
——0.96167.3/163.1 200/200
42.0
23.6 41.60.96190.9/186.7 225/225
59.4/
——0.96180.5/175.1 225/225
54.0
23.6 41.60.96204.1/198.7 250/250
——0.5071.390
12.6 23.60.5083.9100
——0.5078.3100
12.6 23.60.5090.9110
——0.5084.3100
12.6 23.60.5096.9110
——0.5057.470
12.6 23.60.5070.090
——0.5063.480
12.6 23.60.5076.090
——0.5068.480
12.6 23.60.5081.0100
30.8/
——0.96169.9/167.1 225/200
28.0
23.6 41.60.96193.5/190.7 250/225
46.2/
——0.96185.3/181.1 225/225
42.0
23.6 41.60.96208.9/204.7 250/250
59.4/
——0.96198.5/193.1 250/250
54.0
23.6 41.60.96222.1/216.7 275/250
——0.5077.0100
12.6 23.60.5089.6110
——0.5084.0100
12.6 23.60.5096.6110
——0.5090.0110
12.6 23.60.50102.6125
——0.5061.980
12.6 23.60.5074.590
——0.5067.980
12.6 23.60.5080.5100
——0.5072.990
12.6 23.60.5085.5100
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
COMBUSTION
FAN MOTOR
= 1.53%
452 + 464 + 455
1371
=
3
= 457
7
457
POWER SUPPLY
3
—13—
TOP
FLANGE
Fig. 15 — Field Control Thermostat Wiring
IX. OUTDOOR-AIR INLET ASSEMBLY
A. Economizer
NOTE: If accessory power exhaust or barometric relief pack-
ages are being added to the unit, install power exhaust or
barometric relief before installing economizer hoods.
BLACK
SEAL
STRIP
HOOD SIDE
Fig. 16 — Adding Seal Strip to Top of Hood Sides
Economizer Hood Assembly
The economizer hood is shipped in a package secured to the
outside of the unit and must be field assembled. There are
2 hoods on every unit. The 580H units are side supply and
side return. The return duct limits access to economizer
filters from below. Filter tracks (mounting angle without tabs)
must be installed correctly to allow access to economizer
filters from each side.
NOTE: Before assembly of the economizer hood, check along
the outer edges of the economizer assembly for any seal strip
protruding past the flanges. Trim the excess seal strip so that
it is flush with the economizer assembly flanges.
Perform the following procedure to assemble the economizer
hood:
a. Apply black seal strip (provided in package) to out-
1.
side top edge of hood sides. Wrap seal strip over to
cover top flange (4 hood sides). Make certain seal strip
1
covers screw holes.Allowstrip to overhang
⁄8in. past
end opposite mounting flange. See Fig. 16.
b. Assemble hood sides, top, and cross member with gas-
keted screws provided. See Fig. 17.
c. Attach 10 green speed clips (provided) to hood top.
d. Apply black seal strip to mountingflanges(coverholes)
of hood sides. See Fig. 18.
NOTE: Each hood assembly has a slotted side that should be
adjacent to the other hood when mounted to the unit.
e. Apply black seal strip to hood top mounting flange.
Seal strip of hood top mounting flange must press
against seal strip of hood side mounting flanges. See
Fig. 19.
f. Add gray foam strip (provided) to cross members at
bottom tray. See Fig. 20.
NOTE: Left side economizer hood has mounting angle withouttabs and
filter track assembled end on opposite side.
Fig. 17 — Economizer Hood Assembly
(Right-Side Economizer Hood Shown)
Exhaust Mounting Details
g. Place gray foam strip on inside of slotted hood side
between filter and cross member opposite mounting
end. See Fig. 21.
h. Attach gray foam strip to blockoff baffle on outer face
area of flange. See Fig. 22.
2. Remove the screws on each end and along top of damper
assembly of unit. Remove top 2 screws on each side of
filter panel under damper assembly. Set hood assembly
in place and attach to unit using these screws.
3. Attach accessory enthalpy bracket on hood side furthest from control box end. Locate bracket on inside
upper righthandcornerusing hood mounting holes. Mount
outdoor-air thermistor to enthalpy bracket (if purchased).Attachandwireenthalpy assembly. Place quick
connects on enthalpy wires.
—14—
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.