Brooks Instrument MT3809E User Manual

Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Models MT 3809 & 3819
Brooks® Model MT 3809 and 3819 Metal Tube Variable Area Flowmeters
5
with Optional Electronics Based on Smart Meter Manager Technology
TM
Model MT 3809
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
September, 2008
Essential Instructions
Read this page before proceeding!
Brooks Instrument designs, manufactures and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you must properly install, use and maint ain them to ensure they continue to operate within their normal specifications. The following instructions must be adhered to and integrated into your safety program when installing, using and maintaining Brooks Products.
Read all instructions prior to installing, operating and servicing the product. If this instruction manual is not the correct manual, please see back cover for local sales office contact information. Save this instruction manual for future reference.
If you do not understand any of the instructions, contact your Brooks Instrument representative for clarification.
Follow all warnings, cautions and instructions marked on and supplied with the product.
Inform and educate your personnel in the proper installation, operation and maintenance of the product.
Install your equipment as specified in the installation instructions of the appropriate instruction manual and per applicable local and national codes. Connect all products to the proper electrical and pressure sources.
T o ensure proper performance, use qualified personnel to inst all, operate, update, program and maintain the product.
When replacement parts are required, ensure that qualified people use replacement parts specified by Brooks Instrument. Unauthorized parts and procedures can affect the product's performance and place the safe operation of your process at risk. Look-alike substitutions may result in fire, electrical hazards or improper operation.
Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified persons, to prevent electrical shock and personal injury .
Pressure Equipment Directive (PED)
All pressure equipment with an internal pressure greater than 0.5 bar (g) and a size larger than 25mm or 1" (inch) falls under the Pressure Equipment Directive (PED). The Directive is applicable within the European Economic Area (EU plus Norway, Iceland and Liechtenstein). Pressure equipment can be traded freely within this area once the PED has been complied with.
Section 1 of this manual contains important safety and operating instructions related to the PED directive.
Meters described in this manual are in compliance with EN directive 97/23/EC module H Conformity Assessment.
All Brooks Instrument Flowmeters fall under fluid group 1.
Meters larger than 25mm or 1" (inch) are in compliance with category I, II, III of PED.
Meters of 25mm or 1" (inch) or smaller are Sound Engineering Practice (SEP).
ESD (Electrostatic Discharge)
Handling Procedure:
1. Power to unit must be removed.
2. Personnel must be grounded, via a wrist strap or other safe, suitable means before any printed circuit card or other internal device is installed, removed or adjusted.
3. Printed circuit cards must be transported in a conductive container . Boards must not be removed from protective enclosure until immediately before installation. Removed boards must immediately be placed in protective container for transport, storage or return to factory.
Comments
This instrument is not unique in its content of ESD (electrostatic discharge) sensitive components. Most modern electronic designs contain components that utilize metal oxide technology (NMOS, SMOS, etc.). Experience has proven that even small amounts of static electricity can damage or destroy these devices. Damaged components, even though they appear to function properly, exhibit early failure.
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Dear Customer , We appreciate this opportunity to service your flow measurement and control requirements with a Brooks
Instrument device. Every day, flow customers all over the world turn to Brooks Instrument for solutions to their gas and liquid low-flow applications. Brooks provides an array of flow measurement and control products for various industries from biopharmaceuticals, oil and gas, fuel cell research and chemicals, to medical devices, analytical instrumentation, semiconductor manufacturing, and more.
The Brooks product you have just received is of the highest quality available, offering superior performance, reliability and value to the user . It is designed with the ever changing process conditions, accuracy requirements and hostile process environments in mind to provide you with a lifetime of dependable service.
We recommend that you read this manual in its entirety. Should you require any additional information concerning Brooks products and services, please contact your local Brooks Sales and Service Office listed on the back cover of this manual or visit www.BrooksInstrument.com
Y ours sincerely , Brooks Instrument
Models MT 3809 & 3819
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
THIS PAGE WAS INTENTIONALLY
LEFT BLANK
ContentsInstallation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Paragraph Page Number Number
1-1 Description .......................................................................................................................................1-1
1-2 Design Features ...............................................................................................................................1-1
1-3 Specifications - Meter.......................................................................................................................1-1
1-4 Optional Accessories ........................................................................................................................ 1-7
1-5 Optional Electronic Equipment ......................................................................................................... 1-7
1-6 Microprocessor T ransmitter With or Without Alarms and Pulse Output
Based on Brooks Smart Meter Management T echnology ................................................................1-7
1-7 Microprocessor Transmitter With Inductive Alarms ......................................................................... 1-16
1-8 Inductive Alarm Switches ................................................................................................................ 1-18
Section 2 Installation
2-1 General.............................................................................................................................................2-1
2-2 Receipt of Equipment ....................................................................................................................... 2-1
2-3 Recommended S torage Practice................................................................................................ ......2-1
2-4 Return Shipment ..............................................................................................................................2-2
2-5 Transit Precautions .......................................................................................................................... 2-2
2-6 Removal from Storage......................................................................................................................2-2
2-7 Installation of Flowmeter .................................................................................................................. 2-3
2-8 Installation of Models Model MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager
Transmitter with or without Optional Alarms and Pulse Output ........................................................ 2-4
2-9 Installation of Models Model MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager
Transmitter with Inductive Alarms (1 or 2 Switches)........................................................................2-10
2-10 Installation of Models Model MT 3809 and MT 3819 Flowmeters with Inductive Alarms
(1 or 2 Switches) ............................................................................................................................. 2-10
Section 3 Operation
3-1 Pre-Start Check................................................................................................................................ 3-1
3-2 S tart-Up and Operation of Flowmeter...............................................................................................3-1
3-3 Operation of Models Model MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager
Transmitter with or without Optional Alarms and Pulse Output for Totalization ................................ 3-2
3-4 Operation of Models Model MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager
Transmitter with Inductive Alarms (1 or 2 Switches)........................................................................3-13
3-5 Operation of Models Model MT 3809 and MT 3819 Flowmeters with
with Inductive Alarms (1 or 2 Switches)...........................................................................................3-13
Section 4 Maintenance
4-1 General Service Information.............................................................................................................4-1
4-2a Meter Float Replacement and Cleaning (MT 3809)..........................................................................4-2
4-2b Meter Float Replacement and Cleaning (MT 3819)..........................................................................4-8
4-3 Meter Indicator Reference Mark (Zero) Adjustment ......................................................................... 4-8
4-4 Smart Meter Manager Transmitter Replacement with or without Alarms and Pulse Output.............4-8
4-5 Inductive Alarm Replacement........................................................................................................... 4-8
4-6 SMM Transmitter Replacement with Inductive Alarms.................................................................... 4-10
4-7 Monitoring the Integrity of the SMM Electronics - Diagnostics Alarms ............................................ 4-10
Section A CE Certification
CE Certification of Mass Flow Equipment ........................................................................................A-1
Models MT 3809 & 3819
Warranty, Local Sales/Service Contact Information....................................................................... Back Cover
i
Contents
Models MT 3809 & 3819
Figures
Figure Page Number Number
1-1 Models MT 3809 and MT 3819 Dimensions.....................................................................................1-6
1-2 Power Supply vs. Maximum Load Resistance ................................................................................. 1-9
1-3 Transmitter Only Wiring Diagram.................................................................................................... 1-11
1-4 Transmitter Only Wiring Notes........................................................................................................ 1-12
1-5 Transmitter with Alarm and Pulse Outputs Wiring Diagram ............................................................ 1-13
1-6 Transmitter with Alarm and Pulse Outputs Wiring Notes ................................................................ 1-14
1-7 Model MT3809 Explosion-Proof Housing Wiring Diagram .............................................................. 1-15
1-8 Transmitter with Inductive Alarm Wiring Diagram ........................................................................... 1-16
1-9 Transmitter with Inductive Alarm Wiring Notes................................................................................1-17
1-10 Inductive Alarms Only Wiring Diagram............................................................................................ 1-20
1-1 1 Inductive Alarms Only Wiring Notes ................................................................................................1-21
2-1 T ypical Bypass Installation................................................................................................................ 2-3
2-2 Smart Meter Manager Electrical Configuration.................................................................................2-5
2-3 T ypical SMM Transmitter Analog Output and Power Wiring.............................................................2-5
2-4 Alternate SMM Transmitter Analog Output and Power Wiring (Where 4-20 mA is not required) ..... 2-6
2-5 Multi-drop SMM Transmitter Analog Output and Power Wiring ........................................................2-6
2-6 Typical SMM Transmitter with Alarms and Pulse Digital Output and Power Wiring.......................... 2-8
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
3-1 Models MT 3809 and MT 3819 SMM Electronics Device Description T ree (Basic Setup)............... 3-3
3-2 Models MT 3809 and MT 3819 SMM Electronics Device Description T ree (Detailed Setup)........... 3-4
3-3 HART Communicator .......................................................................................................................3-5
3-4 Typical HART Communicator Interface............................................................................................3-5
3-5 HART Communicator Action / Hot Keys ...........................................................................................3-6
3-6 HART LCD .......................................................................................................................................3-6
4-1 Meter Float Replacement & Cleaning (Model MT 3809) .................................................................. 4-6
4-2 Exploded View, Model MT 3809, Size 15 (Gas or Liquid Service)....................................................4-7
4-3 Exploded View, Model MT 3809, Size 16 (Liquid Service Only) ....................................................... 4-7
4-4 Meter Float Replacement & Cleaning (Model MT 3819) .................................................................. 4-9
Tables
Table Page Number Number
1-1A Model MT 3809 Capacities, Pressure Drop and Viscosity Immunity Ceiling .................................... 1-4
1-1B Model MT 3819 (Tefzel Lined)Capacities and Pressure Drop .......................................................... 1-4
1-2 Model MT 3809 Pressure Ratings*...................................................................................................1-5
1-3 Maximum Fluid Temperatures at 104oF (40oC) Ambient .................................................................. 1-5
ii
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
1-1 Description
The Brooks® Models MT 3809 and MT 3819 Variable Area Flowmeters are rugged, all metal flowmeters offering 2% full scale accuracy. The Model MT 3809 is constructed with stainless steel components for measuring a variety of gas, liquid and steam applications while the Model MT 3819 utilizes a ETFE (Tefzel™) lining for aggressive liquid and gas applications. Flow rate indication is provided by means of magnetic coupling where a magnet, encapsulated in the float, is coupled to a rotatable magnet located in the rear of the indicator, thus turning the dial indicator mounted on the meter. Optional accessories available include 4-20 mA output with HART microprocessor transmitter with or without configurable alarms and pulse output for totalization. The microprocessor electronics are based on the proprietary Smart Meter Manager technology utilized as the basis for an array of Brooks products. Also available are front adjustable inductive alarms, high temperature or stainless steel indicator housings, valves, sight flows, flow controllers and material certifications.
Section 1 Introduction
Models MT 3809 & 3819
1-2 Design Features
1-3 Specifications - Meter
• Broad range of flow capacities
• 2% Full scale accuracy
• Versatile construction for all gas, liquid, steam applications
• Operable under high temperatures and pressures
• Flanged or female NPT connections
• Optional 4-20mA and HART microprocessor transmitter with or without alarms and pulse output for totalization
• Electronics designed with either intrinsically safe or explosion proof construction to meet UL, (US & Canada) ATEX certifications and CE requirements
®
programmable
WARNING
Do not operate this instrument in excess of the specifications listed below. Failure to heed this warning can result in serious personal injury and/or damage to the equipment.
Capacities, Pressure Drop and V iscosity Immunity
Ceiling
Refer to Tables 1-1A and 1-1B
Accuracy
Standard Flow Accuracy: ± 2% Full Scale Optional Flow Accuracy: ± 1% Full Scale
1-1
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Repeatability
0.25% Full Scale
Pressure Ratings
Refer to Table 1-2 for Model MT 3809 maximum non-shock pressure. Model MT 3819 pressure rating is dependant on flange rating.
Pressure Equipment Directive (PED) 97/23/EC
Flow meter complies under Sound Engineering Practices (SEP) or Catagories I, II or III
Scales
Standard: Det achable aluminum plate (Single or dual scales) Graduations: Choice of direct reading units, percentage of maximum flow
Operating Fluid Temperature Limits (Meter only)
Minimum MT 3809 and MT 3819: -20°F (-29°C) Maximum:
Standard MT 3809: 420°F(215°C) Standard MT 3809 with Valve: 392°F(200°C) Standard MT 3819: 302°F (150°C)
Refer to Table 1-3 for temperature limitations for meters with electronics.
Materials of Construction:
Metering Tube MT 3809 Standard: 316L st ainless steel MT 3809 Optional: Inconnel 625™, Hastelloy B™, Hastelloy C™, titanium
1-2
MT 3819 S tandard: 316L stainless steel with ETFE (Tefzel) lining
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Flanges and End Fittings
MT 3809 Standard: 316/316L st ainless steel dual certified MT 3809 Optional: Hastelloy B, Hastelloy C, titanium
MT 3819 Standard: 316L stainless steel
Connections
MT 3809 Standard: 150 lbs, 300 lbs or 600 lbs RF ANSI B 16.5 flanges or PN 40 DIN 2527/ 2635; or JIS flanges 10K or 20K; or Female NPT, Male NPT for No O-ring meter only 125/250 Ra micro inch (3.2/6.3 Ra micro meter) cerated flange finish. Consult factory for optional uncerated flange finish. Vertical inlet and outlet
MT 3819 Standard: 150 lbs RF ANSI B 16.5 flanges or PN 40 DIN 2527/2635 MT 3819 Optional: 300 lbs RF ANSI B 16.5 flanges or PN 40 DIN 2527/2635. For other ratings/flange types consult factory . 125/250 Ra micro inch (3.2/6.3 Ra micro meter) cerated flange finish. Consult factory for optional uncerated flange finish. Vertical inlet and outlet
Section 1 Introduction
Models MT 3809 & 3819
Floats
MT 3809 Standard: 316L stainless steel MT 3809 Optional: Inconnel 625, Hastelloy C or titanium
MT 3819 Standard: Hastelloy C, Sizes 7 and 8, PVDF Sizes 10, 12 and 13. MT 3819 Optional: Inconnel 625 or titanium all sizes; all Teflon Sizes 10, 12 and 13.
O-rings (NPT only)
MT 3809 Standard: V iton® fluoroelastomers MT 3809 Optional: Teflon, none with male NPT connections
MT 3819: None
Indicator Housing and Cover
Enclosure NEMA 4X construction MT 3809 and MT 3819 S t andard Housing: Die cast aluminum, polyurethane paint with glass window MT 3809 and MT 3819 Optional Housing: 316L st ainless steel with gritblast and glass window; epoxy paint for aluminum housing
Meter Dimensions
Refer to Figure 1-1
®
internals
1-3
Section 1 Introduction
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
Table 1-1A Model MT 3809 Capacities, Pressure Drop and Viscosity Immunity Ceiling
CONNECTION SIZE FLOAT MATERIAL STAINLESS STEEL 316L
METER DIN ANSI FLOAT WATER
SIZE DN mm inches CODE l/h gpm scfm nm3/h mbar inches WC (c S t) (cSt) Category
7
8
10
12
13
15
16
15 1/2" A 25 0.11 0.49 0.78 30 13 1 40 SEP
B* 65 0.28 1.2 2 30 13 1 20 SEP
C 130 0.59 2.4 3.7 30 13 1 120 SEP
D* 200 0.88 3.7 5.8 35 15 1 20 SEP
15 1/2" A 250 1.1 5.2 8.2 45 19 2 250 SEP
B 400 1.7 7.7 12 55 23 1 180 SEP C 650 2.8 11 18 60 25 2 475 SEP D 1000 4.4 21 33 130 53 1.5 250 SEP
25 1" A 1200 5.2 19 30 60 25 5 475 CAT I, II or III
B 1500 6.6 31 49 7 0 29 1.5 400 CAT I, II or III C 2400 10 41 65 85 35 7 475 CAT I, II or III D 3500 15 65 100 155 63 4 475 CAT I, II or III
40 1 1/2" A 4000 17 67 100 50 21 50 475 CAT I, II or III
B 6000 26 94 140 60 25 30 475 CAT I, II or III C 8000 35 150 230 150 61 2 475 CAT I, II or II I D 10000 46 210 330 300 121 2 475 CAT I, II or III
50 2" A 6500 28 100 160 50 21 50 475 CAT I, II or III
B 9500 41 160 250 60 25 50 475 CAT I, II or III C 12000 55 200 310 100 41 2.5 475 CAT I, II or III D 20000 88 390 620 300 121 1 475 CAT I, II or III
80 3" A 20000 88 390 620 110 45 8 475 CAT I, II or II I
B 30000 130 550 860 140 57 7 475 CAT I, II or III C 40000 170 750 1100 280 113 5 475 CA T I , I I or III
100 4" A 49000 210 NA NA 160 65 15 475 CAT I, II or III
B 70000 300 NA NA 210 85 10 475 CAT I, I I or III C 100000 440 NA NA 300 121 5 475 CAT I , I I or III
AIR
1,2
Press Drop Press Drop VIC (cSt)Max. Visc PED
September, 2008
1. Air flow s in s c fm are given at 70 ° F and 14.7 psia
2. Air flow s in nm 3/h are giv en at 0°C and 1.013 bar (a)
3. *Mini mum operating pres s ure required 7 psig / 0.48 bar
Table 1-1B Model MT 3819 (Tefzel Lined) Capacities and Pressure Drop
CONNECTION SIZE TUBE STANDARD F LOAT MATERIAL CAPACITIES (See Note 3)
METER DIN ANSI FLOAT WATER AIR
1,2,4
Press Drop Press Drop PED
SIZE DN mm inches CODE l/h gpm scfm nm3/h mbar inches WC Category
7
15 1/2" GA 110 0.48 2 3.2 25 11 SEP
GB 170 0.75 3.2 5 50 21 SEP
15 1/2" A 250 1.1 4.6 7.3 30 13 SEP
8
B 420 1.8 7.7 12 45 19 SEP C 500 2.2 9.2 14 40 17 SEP D 850 3.7 15 24 130 53 SEP
25 1" A 1400 6.2 26 41 4 5 19 CAT I, II or III
10
B 2000 8.8 37 58 106 43 CAT I, II or III C 2400 10 44 7 0 90 37 CAT I, II or III D 3000 13 55 8 7 130 53 CAT I, II or III
40 1 1/2" A 3000 13 55 87 50 21 CAT I, II or III
12
B 4000 18 74 110 75 31 CAT I, II or I II C 5000 22 92 140 85 35 CAT I, I I or III D 6000 26 110 170 120 49 CAT I, II or I II
50 2" A 6000 26 110 170 9 5 39 CAT I , II or III
13
B 8000 35 147 230 125 51 CAT I, II or III C 12000 53 220 340 200 81 C AT I, II or III D 15000 66 270 430 225 91 C AT I, II or III
1. Air flows in scfm are given at 70°F and 14.7 psia
2. Air flows in nm3/h are given at 0° C an d 1.013 bar ( a)
3. Sizes 7 & 8 floats are Hastelloy C-276 (Density = 8.94 kg/dm
3
), Sizes 10, 12 & 13 are PVDF (Density = 4.22 kg/dm3)
4. For gas applications operating pre ssure must be greater than 29 PSIA / 2 bar ( a)
1-4
Installation and Operation Manual
y
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Table 1-2 Model MT 3809 Pressure Ratings*
Flange Rating**
150 lb. 300 lb. 600 lb.
-20°F to 100°F 275 720
1440
200°F
Section 1 Introduction
Models MT 3809 & 3819
316/316L Stainless Steel (psig at indicated temperature)
500°F
170 480 955
240 620
1240
300°F
215 560
1120
400°F
195 515
1030
316L Stainless Steel (psig at indicated temperature)
600°F
140 450 905
617°F
134 448 899
Threaded NPT
7 & 8
10 12 13
-20°F to 100°F
1500 1500 1500 1300
200°F
1500 1500 1500 1300
300°F
1400 1400 1400 1200
400°F
1400 1400 1400 1200
500°F
1300 1300 1300 1100
600°F
1200 1200 1200 1000
* Model MT 3819 pressure ratings dependent on flange rating. **Flanges are dual certified 316L/316 stainless steel.
Table 1-3 Maximum Fluid Temperatures at 104°F (40°C) Ambient
3809 Indicator Only Indicator with Alarm
Size Standard High Temperature Standard High Temperature Standard High Temperature
7 & 8
10 thru 16
3819 Indicator Only Indicator with Alarm
Size Standard High Temperature Standard High Temperature Standard High Temperature
7 thru 13
-58° thru 420° F 617° F -22° thru 320° F 450° F -22° thru 195° F 300° F
-50° thru 215° C 325° C -30° thru 160° C 230° C -30° thru 90° C 150° C
-58° thru 420° F 617° F -22° thru 320° F 617° F -22° thru 195° F 400° F
-50° thru 215° C 325° C -30° thru 160° C 325° C -30° thru 90° C 200° C
-22° thru 300° F 300° F -22° thru 300° F 300° F -22° thru 195° F 300° F
-30° thru 150° C 150° C -30° thru 150° C 150° C -30° thru 90° C 150° C
1
1
Indicator with Transmitter
Indicator with Transmitter
617°F
1200 1200 1200 1000
1
1
309 &3819 Minimum and Maximum Ambient Temperature
2
Indicator Onl
-58° thru 150° F
-50° thru 65° C
1. High Temperature option not available with Explosion Proof Housing
2. Ambient Temperature below -22° F / -30° C requires Low Ambient Temperature Option
Indicator with Alarm or Transmitter
-22° thru 150° F
-30° thru 65° C
1-5
Section 1 Introduction
Models MT 3809 & 3819
Model MT 3809 with NPT-F Connections mm (inches)*
D
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
B
D
Meter Size
7 & 8
10 12 13
Connection 1/2" NPT-F
1" NPT-F
1-1/2" NPT-F
2" NPT-F
C
A
225 (8.85) 300 (11.81) 300 (11.81) 300 (11.81)
108 (4.25)
E
88 (3.46) 95 (3.78)
105 (4.13)
111 (4.37)
A ± 2
122 (4.8 0)
B
C 72 (2.83) 80 (3.15) 89 (3.50) 95 (3.74)
135 (5. 31 )
D 53 (2.09) 59 (2.32) 65 (2.56)
77 ( 3.63)
104 (4.10 )
E 59 (2.32) 96 (3.78) 96 (3.78) 96 (3.78)
Models MT 3809 and MT 3819 with Flanged Connections mm (inches)*
WEIGHT (Approx.)**
1.3 kg (3 lbs.)
2.8 kg (7 lbs.) 5 kg. (12 lbs.)
6.3 kg (14 lbs.)
Meter Size
7 & 8
10 12 13
MT 3809 Only
15 16
* Dimensions shown are for standard indicator units as well as units with the Smart Meter Manager transmitter or stand-alone inductive
alarms. Consult factory for dimensions of units with transmitters plus alarms and pulse output or transmitters with inductive alarms.
Consult Factory for no O-ring male NPT meter dimensions. ** Weights shown for aluminum indicator and PN40/50 lb flanges. Add 1.7 kg (3.8 lbs.) for steel indicator housing. ***Model MT 3809 meters with explosion proof transmitters and 300# oversized flanges or 600# regular and oversized flanges have a
300mm lay length.
Connection 1/2" Flange
1" Flange
1-1/2" Flange
2" Flange
3" Range 4" Range
A*** 250 (9.84) 250 (9.84) 250 (9.84) 250 (9.84)
250 (9.84)
350 (13.78)
B 88 (3.46) 96 (3.78)
105 (4.13) 111 (4.37)
128 (5.04) 142 (5.59)
C 72 (2.83) 80 (3.15) 89 (3.50) 95 (3.74)
112 (4.41) 126 (4.96)
D 53 (2.09) 59 (2.32) 65 (2.56) 77 (3.03)
89 (3.50)
102 (4.02)
E 71 (2.78) 71 (2.78) 71 (2.78) 71 (2.78)
71 (2.78)
121 (4.76)
WEIGHT (Approx.)**
2.5 kg (6 lbs.)
4.2 kg (10 lbs.)
6.8 kg (15 lbs.)
8.7 kg (20 lbs.)
15 kg. (33 lbs.)
29 kg (64 lbs.)
Figure 1-1 Models MT 3809 and MT 3819 Dimensions
1-6
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
1-4 Optional Accessories
Needle control valves, sight flow indicators and flow controllers (available on the MT 3809 only) For flow rate control, needle control valves or flow controllers may be externally piped into the inlet or outlet side of the instrument. Needle control valves and flow controllers can be supplied up to size 10 (1”) maximum 6.6 gpm (1,500 l/hr) water equivalent. Sight flow indicators are available for all flanged meters and up to size 13 (2”) NPT meters.
1-5 Optional Electronic Equipment
Electronic equipment available with the Models MT 3809 and MT 3819 include the Microprocessor Transmitter, Microprocessor Transmitter/Alarm/ Pulse Output for totalization, Inductive Alarms, and Transmitter with Inductive Alarms, refer to pages 6 through 12 for additional information. All models are designed to be either Intrinsically Safe (aluminum or stainless steel housing) or Explosion Proof (aluminum housing only). All electronic accessories options are available for high temperature applications. Refer to Table 3 to determine the appropriate model for your application.
Section 1 Introduction
Models MT 3809 & 3819
1-6 Microprocessor T ransmitter With or W ithout Alarms and Pulse Output
Based on Brooks Smart Meter Manager T echnology
• A 2-wire, loop-powered device for ease of wiring and installation
• 4-20 mA analog output for flowrate, with Bell-202 modulated HART communication channel
• User selectable 0% and 100% analog output ranges with optional smoothing
• Flexible (mix & match) units of measure for flowrates, totals, temperatures, densities, etc.
• Two flow tot alizers: Resettable and inventory totalization
• User configurable, scaleable pulse output for various engineering units
• Comprehensive alarms for both process flow and internal diagnostic checks
• Easily configured and compatible with other plant equipment
• Patented magnetic sensor which is resistant to external magnetic fields
B. Description
“Smart Inside” best defines the Brooks transmitter with optional alarms and pulse output for totalization. The transmitter (with or without the alarms and pulse output) is a compact microprocessor device designed to interface directly with the Models MT 3809 and MT 3819 flowmeters. The microprocessor electronics are based on the Brooks Smart Meter Manager (SMMTM) technology common to other Brooks flowmeters.
The transmitter is HART-programmable for numerous variables such as flow rate, totalization, calibration factors, and high-low alarm parameters. It is programmable with easy-to-use hand held configurators such as the EmersonTM HART 275 Communicator. Prior to shipment, commonly used default values are programmed by Brooks to ensure ease of operation and quick startup. However , p arameters may be reprogrammed by the user if needed. The 2-wire electronics system is easy to install and interface with other existing equipment such as process management systems or maintenance control packages.
1-7
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
In operation the microprocessor transmitter converts the measured process flow into a 4-20mA output with HAR T protocol. The signal originates when the float magnet inside the metering tube passes a magnetic sensor mounted on the transmitter. Flow rate information may be viewed locally at the meter scale or displayed remotely (along with other flow data) as a function of external support systems through analog/pulse outputs or multiple digital communications.
In addition to transmitter features, this unit can also be ordered with optional alarms and pulse output provided by open collector switches. One or two alarms may be programmed prior to shipment of the unit or at the customer site with a hand-held communicator.
C. Specifications - SMM Microprocessor Transmitter with or without Alarm and Pulse Output
EMC Directive 89/336/EEC: EN 50081, EN 50082
and EN 61326-1
Hazardous Location Classification
Enclosure: T ype 4X/ IP65 Ambient Temperature: -22°F > Tamb < 65°C)
Intrinsically Safe United States and Canada UL Listed, E73889, Vol. 1, Sect. 15 Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G; T4
Europe – KEMA 01ATEX1235 X
II 2 G EEx ia IIC T4 II 2 D T135oC
Entity Parameters (Transmitter): Ui=Vmax=30 Vdc; Ii=Imax=140 mA; Ci= 15 nF; Li= 0 mH
Entity Parameters (Integral Alarms): Ui=Vmax=30 Vdc; Ii=Imax=45 mA; Ci= 0 nF; Li= 0 mH
> Tamb < 150°F (-30°C
1-8
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Non-Incendive United S tates and Canada UL Listed, E73889, Vol. 1, Sect. 15 Class I, II, III, Division 2, Groups A, B, C,D F, and G; T4
Europe – KEMA 01ATEX1236
Section 1 Introduction
Models MT 3809 & 3819
II 3 G EEx nA II T4 II 3 D T135
o
C
Explosion- proof/ Flame-proof United S tates and Canada UL Listed, E73889, Vol. 1, Sect. 14 Class I, Division 1, Groups C, D; Dust Ignition-proof, Class II, Division 1, Groups E, F, G; Class III; T4
Europe – KEMA 01ATEX2207 X
II 2 G EEx d IIB T4 II 2 D T135o C
Power Supply and Maximum Load Resistance
21.0 to 33.5 Vdc Power Supply , refer to Figure 1-2 below.
Input Power: Derived from Analog Output (2-wire current loop transmitter)
Note: Load resistance should also include I.S. barrier resistance. When using Model 275 HART Communicator the minimum load resistance is 250 ohms.
Figure 1-2 Power Supply vs. Maximum Load Resistance
Output Signals
Transmitter: 4-20 mA analog output with HART
Update Rate: 4 times per sec. Range: 3.8 to 22.0 mA
1-9
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Two Alarm Outputs (open collector) Optically isolated outputs assignable to alarms, reverse flow indicator , or manual valve.
Maximum off-state voltage: 30 Vdc Maximum off-state current: 0.05 mA Maximum on-state voltage: 1.2 Vdc Maximum on-state current: 20 mA
One Pulse Output (open collector) Optically isolated. Scaleable to a variety of engineering unit systems (pulses per liter, gallons, etc.)
Range: 1 Hz to 1 kHz Maximum off-state voltage: 30 Vdc Maximum off-state current: 0.05 mA Maximum on-state voltage: 1.2 Vdc Maximum on-state current: 20 mA
Linearity
Less than 1% at maximum current
T emperature Influence
Less than 0.04% per °C
V oltage Influence
Less than 0.002%/Vdc
Load Resistance Influence
±0.1% full scale
Transmitter, Alarm and Pulse Wiring Diagrams
Refer to Figures 1-3, 1-4, 1-5 and 1-6 For Division 1 explosion proof installations, the optional explosion proof
enclosure must be used. This enclosure does not use the auxiliary terminal box, as shown on some of the installation diagrams. All connections are made directly within the housing. Cable entry device shall be certified as Flame-proof type, suitable per the conditions of use and correctly installed. If used with conduit, refer to Figure 1-7, a sealing device shall be provided in accordance with Figure 1-7.
For Division 2 non-incendive installations, either the standard enclosure or the explosion proof enclosure may be used. For both Division 1 explosion proof and Division 2 non-incendive installations, the barriers shown in the installation drawings are unnecessary . However , NEC Class 2 circuits are required.
1-10
The circuits shall be wired separately or using a Multicore Cable Type B, in accordance with EN 60079-14. Also wiring must be done in accordance with the applicable electrical codes, ie., NEC Chapter 5, CEC Section 18 and any local codes.
TRANSMITTER ACCESSORIES
General purpose and intrinsically safe HART compatible power supplies are available in 1 10V and 220V.
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Models MT 3809 & 3819
Figure 1-3 Transmitter Only Wiring Diagram
Ref. No.981Y006 - Rev . F Sheet 1 of 2
1-11
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Figure 1-4 Transmitter Only Wiring Notes
1-12
Ref. No.981Y006 - Rev . F Sheet 2 of 2
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Models MT 3809 & 3819
Figure 1-5 Transmitter with Alarm and Pulse Outputs Wiring Diagram
Ref. No.981Y005 - Rev . F Sheet 1 of 2
1-13
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Figure 1-6 Transmitter with Alarm and Pulse Outputs Wiring Diagram
1-14
Ref. No.981Y005 - Rev . F Sheet 2 of 2
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Models MT 3809 & 3819
Figure 1-7 Model MT3809 Explosion-Proof Housing Wiring Diagram
Ref. No.981Y008 - Rev. D Sheet 1 of 1
1-15
Section 1 Introduction
Models MT 3809 & 3819
1-7 Microprocessor Transmitter with Inductive Alarms
This combined system provides both the sophistication of the microprocessor along with the simplicity of one or two switch inductive alarms. Specifications for the transmitter are as st ated previously and specifications for the front adjustable inductive alarms are as follows. For Wiring Diagrams, Refer to Figures 1-8 and 1-9.
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Figure 1-8 Transmitter with Inductive Alarm Wiring Diagram
1-16
Ref. No.981Y007 - Rev . F Sheet 1 of 2
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Models MT 3809 & 3819
Figure 1-9 Transmitter with Inductive Alarm Wiring Notes
Ref. No.981Y007 - Rev . F Sheet 2 of 2
1-17
Section 1 Introduction
Models MT 3809 & 3819
1-8 Inductive Alarm Switches
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
A. Design
• 1 or 2 normally open inductive limit switches
• Optional intrinsically safe power supply/amplifier/relay unit
• For low or high limit signaling/switching
• Front adjustable
B. Description
One or 2 electronic limit switches can be installed in the indicator housing to allow initiation of signaling or switching functions on a preset flow value. The limit switch operates as a slot initiator that is inductively actuated by a disc mounted on the pointer shaft. Any flow value can be used for setting the limit value by sliding the initiator along the indicator scale. Minimum setting distance between two limit switches is approximately 40% full scale. The position of the initiator also serves to visually indicate the set value. Settings can be adjusted by removing the indicator cover, loosening, moving and retightening of the alarm indication needle, and replacement of the indicator cover.
C. SPECIFICA TIONS EMC Directive 89/336/EEC: EN 50081, EN 50082 and EN 61326-1
Hazardous Location Classification
Enclosure: T ype 4X/ IP65 Ambient Temperature: -22°F
Intrinsically Safe United S tates and Canada UL Listed, E73889, Vol. 1, Sect. 15 Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G; T4
Europe – KEMA 01ATEX1235 X
II 2 G EEx ia IIC T4 II 2 D T135oC
Entity Parameters: Ui=Vmax=30 Vdc; Ii=Imax=140 mA; Ci= 0.015 uF; Li= 0 mH
Non-Incendive United S tates and Canada UL Listed, E73889, Vol. 1, Sect. 15 Class I, II, III, Division 2, Groups A, B, C,D F, and G; T4
> T amb < 150°F (-30°C > Tamb < 65°C)
1-18
Europe – KEMA 01ATEX1236
II 3 G EEx nA II T4 II 3 D T135oC
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Explosion- proof/ Flame-proof United S tates and Canada UL Listed, E73889, Vol. 1, Sect. 14 Class I, Division 1, Groups C, D; Dust Ignition-proof, Class II, Division 1, Groups E, F, G; Class III; T4
Europe – KEMA 01ATEX2207 X
Section 1 Introduction
Models MT 3809 & 3819
II 2 G EEx d IIB T4 II 2 D T135
Power Supply 5-25 Vdc; 25 mA max.
Impedance
Approximately 1 kohm with cam absent Approximately 8 kohm with cam present
Maximum Operating T emperature
Refer to Table 1-3
Alarm Wiring Diagrams
Explosion-proof/ Flame-proof: Refer to Figure 1-7 Intrinsically Safe or Non Incendive: Refer to Figures 1-8 and 1-9 For Division 1 explosion proof installations, the optional explosion proof
enclosure must be used. This enclosure does not use the auxiliary terminal box, as shown on some of the installation diagrams. All connections are made directly within the housing. Cable entry device shall be certified as Flame-proof type, suitable per the conditions of use and correctly installed. If used with conduit, refer to Figure 1-7, a sealing device shall be provided in accordance with Figure 1-7.
o
C
For Division 2 non-incendive installations, either the standard enclosure or the explosion proof enclosure may be used. For both Division 1 explosion proof and Division 2 non-incendive installations, the barriers shown in the installation drawings are unnecessary . However , NEC Class 2 circuits are required.
The circuits shall be wired separately or using a Multicore Cable Type B, in accordance with EN 60079-14. Also wiring must be done in accordance with the applicable electrical codes, ie., NEC Chapter 5, CEC Section 18 and any local codes.
Alarm Accessories
Amplifier Power Supply (approved isolated barrier) 1 or 2 channel approved for intrinsically safe application, remotely mounted, 1 15 or 230 V ac power. Single pole with double throw (SPDT) relay standard. For other configurations, consult factory .
1-19
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Figure 1-10 Inductive Alarms Only Wiring Diagram
1-20
Ref. No.981Y001 - Rev . F Sheet 1 of 2
Installation and Operation Manual
X-VA-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 1 Introduction
Models MT 3809 & 3819
Figure 1-11 Inductive Alarms Only Wiring Notes
Ref. No.981Y001 - Rev. D Sheet 2 of 2
1-21
Section 1 Introduction
Models MT 3809 & 3819
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
THIS PAGE WAS INTENTIONALLY
LEFT BLANK
1-22
X-V A-MT3809-3819 Part Number: 541B049AHG September , 2008
2-1 General
2-2 Receipt of Equipment
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
This section contains the procedures for the receipt and installation of the instrument. See Section 1 for dimensional and connection requirements. Do not attempt to start the system until the instrument has been permanently installed. It is important that the start-up procedures be followed in the exact sequence presented.
When the instrument is received, the outside packing case should be checked for damage incurred during shipment. If the packing case is damaged, the local carrier should be notified at once regarding his liability . A report should be submitted to your nearest Product Service Department.
Brooks Instrument
407 W. V ine Street P.O. Box 903 Hatfield, PA 19440 USA Toll Free (888) 554-FLOW (3569) Tel (215) 362-3700 Fax (215) 362-3745 E-m ail: BrooksAm @BrooksInstrument.com www.BrooksInstrument.com
2-3 Recommended Storage Practice
Brooks Instrument Brooks Instrument
Neonstraat 3 1-4-4 Kitasuna Koto-Ku 6718 WX Ede, Netherlands Tokyo, 136-0073 Japan P.O. Box 428 Tel 011-81-3-5633-7100 6710 BK Ede, Netherlands Fax 011-81-3-5633-7101 Tel 31-318-549-300 Email: BrooksAs@BrooksInstrument.com Fax 31-318-549-309 E-mail: BrooksEu@BrooksInstrument.com
Remove the envelope containing the packing list. Outside of your clean area, carefully remove the equipment from the packing case. Make sure spare parts are not discarded with the packing material. Inspect for damaged or missing parts.
If intermediate or long-term storage of equipment is required, it is recommended that the equipment be stored in accordance with the
following: a. Within the original shipping container. b. In a sheltered area preferably a warm, dry heated warehouse. c. Ambient temperature 21°C (70°F) nominal, 40°C (104°F) maximum
and 7°C (45°F) minimum.
d. Relative humidity 45% nominal, 60% maximum and 25% minimum.
2-1
Section 2 Installation Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
2-4 Return Shipment
Prior to returning any instrument to the factory , contact your nearest Brooks
location for a Return Materials Authorization Number (RMA#). This can be
obtained from one of the following locations:
Brooks Instrument
407 W. V ine Street
P.O. Box 903
Hatfield, PA 19440 USA
Toll Free (888) 554-FLOW (3569)
Tel (215) 362-3700
Fax (215) 362-3745
E-m ail: BrooksAm @BrooksInstrument.com
www.BrooksInstrument.com
Brooks Instrument Brooks Instrument
Neonstraat 3 1-4-4 Kitasuna Koto-Ku
6718 WX Ede, Netherlands Tokyo, 136-0073 Japan
P.O. Box 428 Tel 011-81-3-5633-7100
6710 BK Ede, Netherlands Fax 011-81-3-5633-7101
Tel 31-318-549-300 Email: BrooksAs@BrooksInstrument.com
Fax 31-318-549-309
E-mail: BrooksEu@BrooksInstrument.com
September, 2008
2-5 Transit Precautions
2-6 Removal from Storage
Instrument must have been purged in accordance with the following:
Completion of form RPR003-1, Brooks Instrument Decontamination
Statement. A copy of this form can be downloaded from the Brooks website
www.brooksinstrument.com or is available from any Brooks Instrument
location listed above. This is required before any Brooks Personnel can
begin processing. Copies of the form can be obtained from any Brooks
Instrument location listed above. Provide a Material Safety Data Sheet
(MSDS) for the fluid(s) used in the instrument.
To safeguard against damage during transit, transport the instrument to the
installation site in the same container used for transportation from the
factory if circumstances permit.
Upon removal from storage, a visual inspection should be conducted to
verify the condition of the equipment is “as received.” If the equipment has
been in storage in conditions in excess of those recommended (See
Section 2-3), the device should be subjected to a pneumatic pressure test
in accordance with applicable vessel codes.
2-2
X-V A-MT3809-3819 Part Number: 541B049AHG September , 2008
2-7 Installation of Flowmeter
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
WARNING
If the inlet and outlet valves adjacent to the indicator are to be closed for any reason, the indicator must be completely drained. Failure to do so may result in thermal expansion of the liquid which can rupture the meter and cause possible personal injury.
Recommended installation for Models MT 3809 and MT 3819 is as follows:
a. Carefully remove the covers from each end of the flowmeter. b. Install the flowmeter with the inlet at the bottom and the outlet at the
top.
c. When installing the flowmeter in the process line, follow accepted
plumbing practices for flanged or NPT fittings.
d. Install the flowmeter within 5° of true vertical. Use of a level is
recommended to determine the proper alignment.
e. Installation of a bypass piping arrangement is recommended,
Figure 2-1. Bypass piping permits the meter to be isolated from the flow line for servicing and cleaning.
Figure 2-1 Typical Bypass Installation
2-3
Section 2 Installation Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
2-8 Installation of Models MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager Transmitter
with or without Optional Alarms and Pulse Output
a. Install the meter as described in Section 2-4.
b. Transmitter setup is done solely through proper system wiring and
parameter configuration. Common transmitter parameters are set by Brooks prior to shipment. These parameters, such as flow rate, are set based on order information, meter configuration or defaults inherent to the transmitter . If requested when ordering the electronics, all parameters will be set prior to receiving the unit and no further configuration will be needed at installation. However , more detailed configurations as well as on-line monitoring can be done through standard HART communication protocol, or can be set using an EmersonTM Model 275 Hand-held communicator. See Operations Section 3 for manual programming details.
With a HART protocol compatible transmitter, the digital communication signals are superimposed on top of the 4-20 mA signal. Communication of more than just the process variables is possible. Plants utilizing HART compatible transmitters can increase productivity by reducing trips to the field, gather data needed to reduce process downtime, proactively perform maintenance rather than reactively , and transport data to the field and back to the shop. Also, with the Emerson Process Management Asset Management SolutionsTM software (AMS), information may be moved from the Model 275 Communicator to your personal computer.
September, 2008
The 2-wire, 4-20 mA analog output provides real-time information on process flow rate. The 1200 baud, HART communication data is overlaid and transmitted on the 4-20 mA signal. Refer to Figure 2-2 for SMM electrical configuration. The float is constructed with an integral magnet that activates a magnetic sensor that is part of the transmitter . This same float magnet also drives the mechanical pointer . The flow rate is scalable by setting independent high and low range parameters. The Analog Output (AO) transmitter parameters, AO Hi­Range and AO Lo-Range span the 4-20 mA signal. For example, if flow rate is normally between 100 and 500 gpm, the AO Hi-Range parameter is set at 500 and the AO Lo-Range is set at 100. Like other common parameters, the AO Hi-Range and AO Lo-Range can be set by Brooks prior to shipment.
c. Microprocessor T ransmitter Wiring Connections
Refer to Figures 1-3, 1-4, 1-5 and 1-6 for detailed UL approved wiring hookup. Figures 2-3 through 2-6 are schematic drawings showing typical electronic hookups.
CAUTION
Since this is a magnetically activated device, strong magnetic fields and materials with magnetic properties may cause faulty operation when in close proximity to the flowmeter. This includes steel pipes, steel conduit, motors, and transformers.
2-4
X-V A-MT3809-3819
TM
Smart Meter Manager
®
inside
TM
Smart Meter Manager
®
inside
Part Number: 541B049AHG September , 2008
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
Figure 2-2 Smart Meter Manager Electrical Configuration
Figure 2-3 Typical SMM Transmitter Analog Output and Power Wiring
2-5
Section 2 Installation Installation and Operation Manual
TM
Smart Meter Manager
®
inside
TM
Smart Meter Manager
®
inside
TM
Smart Meter Manager
®
inside
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
September, 2008
Figure 2-4 Alternate SMM Transmitter Analog Output and Power Wiring (Where 4-20 mA signal is not required)
Figure 2-5 Multi-drop SMM Transmitter Analog Output and Power Wiring
2-6
X-V A-MT3809-3819 Part Number: 541B049AHG September , 2008
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
Typically applications require only the use of the 2 wire loop analog signal.
In some applications where transmitters and actuators are widely
separated (e.g. tank farms), devices are wired in a multi-drop configuration
to save wiring costs. Each unit is given an individual HART address in the
range of 1-15 to distinguish each unit during communications over a
common wire pair . In this configuration, the 4-20 mA output signal cannot
be used.
To install the typical transmitter analog output configuration:
1. For intrinsically safe installation, intrinsic safety barrier selection, cable parameters, and power supply limits must be in accordance with the entity parameters shown in Figure 1-3. Alternatively, the optional intrinsically safe power supply available from Brooks may be used. Cable parameters for inductance and capacit ance still apply.
2. If the area classification is Division 2, a barrier is not required and cable parameters are not applicable. The electrical code will require the use of conduit for wire protection. Refer to Figure 1-3.
3. If the installation is to be protected by Division 1 explosion proof methods, the optional explosion proof enclosure is required and explosion proof installation methods must be followed. Refer to Fig.1-5.
4. and should be taped up and not connected at the receiver end. Insulation of the shield at the receiving end is especially important for intrinsically safe installations.
5. The maximum resistance of the loop resistor, the associated cable and the barrier is determined by the power supply voltage and is shown graphically in Figure 1-2.
6. After installation and powering of the loop, the transmitter must be zeroed, both electrically and mechanically . This operation will compensate for any stray magnetic effects in the vicinity of the transmitter. Flow must be verified to be zero when the zero function is momentarily activated.
With the float at the zero flow position, set zero flow by either shorting the two pins together at the terminal block. If desired, a zero switch can be remotely mounted and wired to these terminals. The hazardous area classification will determine the wiring methods used for this switch.
The pointer must also be adjusted to the reference line on the scale using the adjustment screw on the face of the pointer, next to the hub. The zero function may be activated as part of a periodical maintenance check.
2-7
Section 2 Installation Installation and Operation Manual
TM
Smart Meter Manager
®
inside
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
September, 2008
7. Under actual flow conditions, verify that the transmitter output matches the mechanical pointer position. If a discrepancy is noted, the HART communications channel can be used to verify or adjust the transmitter settings. The Emerson Model 275 hand held communicator provides a simple means to accomplish this check anywhere in the loop. Refer to Figure 3-2 for connection instructions. Note: The Brooks SMM transmitter device description (DD) will not be programmed into the Emerson Model 275 hand-held communicators until after Summer 1997. Until the Brooks device description becomes standard to the Emerson Model 275 units, please contact Brooks Customer Service, Hatfield, PA, to provide programming for a nominal fee. After Summer 1997, we request that the customers update their Model 275 units through Emerson Service Centers located throughout the world.
d. Microprocessor Transmitter with Alarm and Pulse Output Wiring
Connections.
CAUTION
Since this is a magnetically activated device, strong magnetic fields and materials with magnetic properties may cause faulty operation when in close proximity to the flowmeter. This includes steel pipes, steel conduit, motors, and transformers.
CAUTION
Flowmeters with a transmitter must be mounted at least 18 inches apart to prevent the interaction of adjacent float magnets and transmitter.
WARNING
To prevent ignition of hazardous atmospheres and serious personal injury, proper installation methods must be used as defined in Article 505 of the National Electrical Code and the Canadian Electrical Code and ISA Stnadard 12.6.
Figure 2-6 Typical SMM Transmitter with Alarms and Pulse Digital Output and Power Wiring
2-8
X-V A-MT3809-3819 Part Number: 541B049AHG September , 2008
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
All internal parameters can be accessed over the HART communications channel, including the configuration of the output signals used for alarms and pulse output. An external termination box is att ached for easy hookup of these signals. The alarms are configurable as normally open or normally closed.
The alarm contact and pulse output digital signals are electrically identical, independent, optically coupled transistor outputs. Wiring will be as required by the external driven system— Prover, DCS/PLC, terminal-automation system, batch controller etc. These can be wired as an open collector or open emitter signal on the high or low side of voltage-rail within the receiving equipment, depending upon the signal needs. When interfacing to external electronics, be careful to work within the voltage/current polarity and limits as specified in Section 1.
To install the typical transmitter alarms and/or pulse digital outputs configuration:
1. Intrinsically safe installations require the use of barriers, power supply limits and cable parameters as shown in the installation diagram. All connections are made in the terminal box attached to the back of the transmitter housing. Refer to Figures 1-4 and 1-8.
2. If the area classification is Division 2, a barriers are not required and cable parameters are not applicable. However , the electrical code will require the use of conduit for wire protection. Refer to Figures 1-4 and 1-8.
3. If the installation is to be protected by Division 1 explosion proof methods, the optional explosion proof enclosure is required and explosion proof installation methods must be followed. Refer to Figures 1-5 and 1-8.
4. It is highly recommended that shielded cable be used for hook up. The shield should be connected to chassis ground at the transmitter end and should be taped up and not connected at the receiver end. Insulation of the shield at the receiving end is especially important for intrinsically safe installations.
5. The maximum resistance of the loop resistor, the associated cable and the barrier is determined by the power supply voltage and is shown graphically in Figure 1-2.
6. The pulse and alarm outputs function as isolated switch closures (optically isolated open collector-emitter) and must be supplied with a power source, as shown in wiring diagram, Figure 1-4. Observe polarity and do not exceed 30 V olts for the supply and limit load current to 20 mA for each output.
7. The zero function is activated by momentarily shorting the zero terminals on the wiring block. This may be accomplished with any conductive jumper or a switch which can be remotely mounted. The hazardous area classification will determine the wiring methods used for this switch.
2-9
Section 2 Installation Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
8. After installation and powering of the loop, the transmitter must be zeroed, both electrically and mechanically . This operation will compensate for any stray magnetic effects in the vicinity of the transmitter. Flow must be zero and when the zero function is momentarily activated. The pointer must also be adjusted to the reference line on the scale using the adjustment screw on the face of the pointer, next to the hub. The zero function may be activated as part of a periodical maintenance check.
9. Under actual flow conditions, verify that the transmitter output matches the mechanical pointer position and that the alarms and pulse outputs are working properly . If a discrep ancy is noted, the HAR T communications channel can be used to verify or adjust the transmitter settings. The Emerson Model 275 hand held communicator provides a simple means to accomplish this check anywhere in the loop. Refer to Figure 3-2 for connection instructions.
2-9 Installation of Models MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager Transmitter
with Inductive Alarms (1 or 2 Switches)
September, 2008
a. Install the meter as described in Section 2-7. b. Install the transmitter as described in Section 2-8. c. Install the inductive alarms as indicated below Section 2-10.
2-10 Installation of Models MT 3809 and MT 3819 Flowmeters with Inductive Alarms (1 or 2 Switches)
CAUTION
Since this is a magnetically activated device, strong magnetic fields and materials with magnetic properties may cause faulty operation when in close proximity to the flowmeter. This includes steel pipes, steel conduit, motors, and transformers.
CAUTION
Flowmeters with a transmitter must be mounted at least 18 inches apart to prevent the interaction of adjacent float magnets and transmitter.
WARNING
To prevent ignition of hazardous atmospheres and serious personal injury, proper installation methods must be used as defined in Article 505 of the National Electrical Code and the Canadian Electrical Code and ISA Stnadard 12.6.
2-10
Install the meter as described in Section 2-7. To install the inductive alarms (1 or 2 switches):
X-V A-MT3809-3819 Part Number: 541B049AHG September , 2008
Section 2 InstallationInstallation and Operation Manual
Models MT 3809 & 3819
1. The inductive alarms can be supplied as a stand alone option or
combined with the transmitter. When st and alone, connections to the alarms are made inside the indicator housing. When supplied in combination with the transmitter, connections are made inside the auxiliary terminal box attached to the indicator housing. Refer to Fig. 1-7 for stand alone inductive alarm installation and to Figures 1-6 and 1-8 for installation with the transmitter combined with the inductive alarms.
2. Intrinsically safe installations require the use of relay isolators for the alarms and a barrier for the transmitter, if equipped. Power supply limits and cable parameters must be as shown in the installation diagram.
3. If the area classification is Division 2, the transmitter barrier and cable parameters are not applicable. However for proper operation of the inductive alarms, the relay isolators must be used. The electrical code will require the use of conduit for wire protection.
4. If the installation is according to Division 1 explosion proof methods, the optional explosion proof enclosure is required and explosion proof installation methods must be followed. For proper operation of the inductive switches, the relay isolators must be used.
5. It is highly recommended that shielded cable be used for hook up. The shields should be connected to chassis ground at the transmitter/alarm end and should be taped up and not connected at the receiver end. The taping and insulation of the shields at the receiving end is especially important for intrinsically safe installations.
6. For the transmitter output, if supplied, the maximum resistance of the loop resistor , the associated cable and the barrier is determined by the power supply voltage and is shown graphically in Figure 1-2.
7. The relay isolator has built in power handling contacts. Refer to the specifications for these ratings.
8. If desired, the transmitter zero function can be remotely mounted using a momentary contact switch. Follow the same wiring practices as used for the other outputs.
9. After installation and powering of the loop, the transmitter must be zeroed, both electrically and mechanically . This operation will compensate for any stray magnetic effects in the vicinity of the transmitter. Flow must be zero when the zero function is activated, using the remote switch or shorting the zero terminals. The pointer must also be adjusted to the reference line on the scale using the adjustment screw on the face of the pointer, next to the hub. The zero function may be activated as part of a periodical maintenance check.
10.Under actual flow conditions, verify that the transmitter output matches the mechanical pointer position. If a discrepancy is noted with the transmitter, the HAR T communications channel can be used to verify or adjust the transmitter settings. The Emerson Model 275 hand-held communicator provides a simple means to accomplish this check anywhere in the loop. Refer to Figure 3-2 for connection instructions.
1 1.Proper operation of the inductive alarms can be determined by manually
rotating the mechanical pointer and observing the status lights on the relay isolator . The small alarm pointers indicate the alarm trip points. Changes to the set points can be made by loosening the pointer screws and repositioning the pointers.
2-11
Section 2 Installation Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 & 3819
September, 2008
THIS PAGE WAS INTENTIONALLY
LEFT BLANK
2-12
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
3-1 Pre-Start Check
After the flowmeter has been properly installed in the process, it is ready for operation. When initiating flow , slowly open the valve to avoid a flow surge.Bypass is a help in bringing the flow on smoothly. A void starting a pump to supply the flowmeter without the use of a valve upstream of the flowmeter
Section 3 Operation
Models MT 3809 and 3819
Do not operate this instrument in excess of the specifications listed in Section 1-3. Failure to heed this warning can result in serious personal injury and/or damage to the equipment.
At no flow condition the indicator pointer should align with the “0” mark on the scale. If necessary , adjust the pointer as per directions in the Maintenance Section 4-3.
3-2 Start-Up and Operation of Flowmeter
a. Slowly initiate flow into the system. Open process valves slowly to avoid b. Check for leaks around the meter inlet and outlet connections. If no
WARNING
flow surges. leaks are present, bring the system up to operating pressure.
3-1
Section 3 Operation
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 and 3819
September, 2008
3-3 Operation of the Models MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager T ransmitter
with or without Optional Alarms and Pulse Output for tot alization
a. Start-up the meter as described in Section 3-2. b. Programming performed prior to shipment (parameters)
The SMM transmitter with or without alarms and pulse output is preprogrammed prior to shipment for the following parameters based on the order information, meter configuration and application. If parameters are not specified in the customer purchase order, the defaults inherent to the electronics will be as shown in (parenthesis).
Transmitter Only (uP) Transmitter (uP) Plus... Pre-Programmed Parameters Alarms and Pulse Output
Preprogrammed Parameters
Model Number Alarm LoLimit (0% FS flow)
Serial Number Alarm HiLimit (100% FS flow) Tag Name (blank) Pulse output units (1 ppg) Flow Rate units of measure (gpm) Resettable totalizer units of measure (gal.) Low Flow cutoff (10% FS flow) Inventory totalizer units of measurement Calibration factor (% scales only) (gal.) Analog Output LoRange
(4 mA @ 0% flow)
Analog Output HiRange
(20 mA @ 100% flow)
c. Manual Programming or Reprogramming of the SMM electronics
If electronic parameters were not preprogrammed prior to shipment or new settings are required, programming of the SMM transmitter with or without alarms and pulse output may also be done locally via an Emerson Model 275 hand held Communicator . Refer to Figures 3-1 and 3-2 for Device Description Basic Setup and Detailed Device Description Setup Trees.generate an electrical signal directly proportional to the gas mass flow rate.
3-2
Installation and Operation Manual
A
A
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 3 Operation
Models MT 3809 and 3819
Device De scription
Process V ariables
PV (FlowRat e) AO Percent SV (ResettableTotalizer) TV (Invento ryTotalizer) QV (unused?)
Diagnostics & Service
Alarm Statu s Diagnostic Code Sequence Number Current Float Position Internal Temperature Tes t Device
Analog/L oop Test
Set 4mA Set 20mA End Tes t
Contact Out1 Test
Set ON Set OFF End Test
Contact Out2 Test
Set ON Set OFF End Test
Pulse Output Test
Output n P ulses End Test
Basic Se t up
Tagname Model Number Serial Number FlowMeter Configuration
Meter Zero LowFlow Cutoff Cal ibration Facto r
Analog Output
AO Percent AO Milliamps
O HiRange AO LoR ange AO Filter AO Failur e Behavio r
Pulse Output
PulseOut Scaler Pulse O ut Width PulseOut UOM
FlowRate Alarm
larm HiLimit Alarm LoLimit
Detailed Setup
Measurements
Flow
...
Temperature
...
Density
...
Pressure
...
Viscosity
...
Computations
Totalizers
Resettable
Inventory
Outputs
Review
List of All Parameters...
...
...
...
Alarms
...
Device Information
...
Figure 3-1 Models MT 3809 and MT 3819 SMM Electronics Device Description Tree (Basic Setup)
3-3
Section 3 Operation
f
y
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Detailed Setup
Measurements
Flow
FlowRate UOM Met er Configura ti on
Meter Zero LowFlow Cutof Calibration Factor
Meter Calibration
CalibFlowRate UOM Calibr ati on Points
Calibration Info
Temperature
Float Position#1 FlowRate#1 : Float Position#10 FlowRate#10
Process Fluid Calibration Tool Calibrator Name Calibration Date Calib Temperature UOM Calibration Temperature Gas Piston/Pr ove r Temp ? Calib Pressure UOM Calibration Pressure Gas Piston/Prover Pressure ? Calib Density UOM Calibration Density Calib Viscosity UOM Calibration Viscosit
ccuracy Class
Computations
Totalizers
Resettable
Resettable Tota lize r Resettab le Tota lizer UOM ResTot Digits&Decimals Sequence Number Reset
Inventory
Inventory Totaliz er Inventory Totali zer UOM InvTot Digits&Decimals
Outputs
nalog Output
O Percent O Milliamps O HiRange O LoRange O Filter O Failure Behav io r
Contact Out1
ContactOut Function ContactOut Polarity Co nta ct O ut State
Contact Out2
ContactOut Function ContactOut Polarity Co nta ct O ut State
Pulse Output
PulseOut UOM PulseOut Scaler PulseOut Width
HART Output
HART ShortFrame Address Number of Preambles
Alarms
larm Status
Diagnostic Code
larm Configuration
FlowRate
PulseOut Overrun Diagnostics DataBase Initialization Power Internal T emperature
larm HiLimit larm LoLimit larm Time Period larm Enable larm Destination larm Type
Device Information
Tagname Description Message Date Manufacturer Code DeviceType Code (?) Serial Number (? ) Final Ass'y# (?) Config.Changed Revi si on N umbers
Universal Rev Field Device Rev Hardware Rev Software Rev
FlowMeter
MeterFlow HiLimit MeterFlow LoLimit MeterTemp HiLimit MeterTemp LoLimit MeterPressure HiLimit MeterPressure LoLimit MaxPressure Drop Meter Type Meter Material Flange Typ e Flange Material Float Type Float Material O-Rin g Mate rial
ccessories
ExternalTerminationBox
Temperature UOM Observed Temperature
Density
Density UOM Observed Density
Pressure
Pressure UOM Observed Pressure
Viscosity
Viscosity UOM Observed V iscos ity
Figure 3-2 Models MT 3809 and MT 3819 SMM Electronics Device Description Tree (Detailed Setup)
3-4
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
The HART Communicator is the hand-held interface that provides a common communication link to all HART compatible, microprocessor­based devices. A keypad, liquid crystal display (LCD) and software menu structure make up the HART communicator user interface. The Emerson Model 275 is easy to use. Just press a few buttons to become familiar with the Action Keys and menu structure.
Action Keys
Action Keys
Shift Keys
Shift Keys
LCD
LCD
Section 3 Operation
Models MT 3809 and 3819
3
0
5
1
C
:D
P
T
O
-
0
n
1
lin
0
1
e
1
D
e
v
ic
e
s
2
P
e
t
u
V
p
3
A
O
4
0
L
.8
6
R
in
V
H
5
U
F1
HART Communicator
A B C
D E F
7
8
J K L
M N O
4
5
S T U
V W X
1
2
# % &
< >
0
.
* : +
_
2
O
4
R
.2
V
7
5
m
0
A
.0
0
in
H
S
2
5
O
A
0
V
.0
E
0
in
H
2
O
F2
F3
F4
G H I
9
P Q R
6
Y Z /
Alpha-Numeric Keypad
Alpha-Numeric Keypad
3
Function Keys
Function Keys
Figure 3-3 HART Communicator
T ypical Connection Emerson Model 275 Communicator Interface
The HART Communicator interfaces with any HART instrument from any wiring termination point in a 4-20 mA loop, provided a minimum load resistance of 250 ohms is present between the HART Communicator and power supply. A minimum load resistance of 250 ohms must be present between the HART Communicator and power supply in order for the HAR T Communicator to communicate with any HART compatible instrument. (An optional rugged 250 ohm resistor that attaches to the lead set is available from Emerson. The resistor must be installed in series,
HART-Compatible Device
not in parallel.)
Power
+
Supply
_
_
+
DVC:FCV101B Fisher Dig Vlv Ctrl
1 Main
2 Analog In 12.13 mA 3 Travel 50.36 % 4 Drive Sgl 31.54 % 5 Instrument Status
F1 F2 F3 F4
HART Communicator
A B C D E F G H I
7
89
J K L M N O P Q R
456
V W X Y Z
S T U
32
<
>
# % &
0.
/
1
* : +
-
Receiver
+
(DCS/PLCl etc.)
_
250 Ohm
Resistance Minimal
Figure 3-4 Typical HART Communicator Interface
3-5
Section 3 Operation
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Emerson Model 275 Communicator Functions Action Keys and Hot Key
Six Action Keys promote easy navigation through the menu structure. You may customize the Hot Key to quickly access a menu of your most frequently performed on-line tasks. The Hot Key Menu is a user-definable menu containing one permanent option, Range V alues. Range Values provides quick access to rearrange capability. Up to 19 frequently performed tasks can also be added to this menu. These t asks are stored even when the communicator is off, and are always readily available by simply pressing the Hot Key .
On/Off Up Hot Key
Figure 3-5 HART Communicator Action / Hot Keys
LCD
The LCD is an eight-line by twenty-one character display that provides a window to all the functions of a HART compatible device. When connected to a HART compatible device, the top line of each menu displays the model name of the device and its tag. The bottom line of each menu is reserved for a dynamic label for each function key , F1 through F4.
Brooks MT 3809 On-line
1 Device setup
2 PV 0.86 gpm 3 AO 4.275 mA 4 LRV 0.00 gpm 5 URV 50.00 gpm SAVE
F1 F2 F3 F4
3-6
Figure 3-6 HART LCD
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Function Keys
Use the four function keys, marked F1 through F4 located below the LCD to perform software functions as indicated by the dynamic labels. Different labels appear over the four function keys as you move among the various menus.
On-line Menu
When connected to a HART compatible device, simply press the ON Key to display the On-line Menu. This menu contains the most critical information about the connected device and your measurement including:
Section 3 Operation
Models MT 3809 and 3819
Model Number
User-defined Tag Number
Flow Rate Units of Measure
Analog Output LoRange
Analog Output HiRange
a. Simulation Mode
The HART Communicator provides a mode that allows you to simulate
an on-line connection to a specific HART compatible device. The simulation mode is a training tool that enables you to become familiar with a device before configuring it in a critical environment. Access to the simulation mode is through the utility menu.
For more details and instructions on use of the Emerson Model 275
Communicator please contact Brooks Service Department Representative or your local Emerson office.
b. Recalibration of Analog T ransmitter Output (spanning high and
low)
At any time after factory calibration, shipment, installation, or service, the
SMM transmitter can be recalibrated by overwriting any of the previous calibration point-pairs, assuming that the user can provide a series of accurate rates of flow through the meter. If preferred, the meter with transmitter may be returned for recalibration at the Brooks Service Department for a fee.
c. Basic T ransmitter Setup Parameters
Refer to Figures 3-1 and 3-2. These are meter identification parameters
set prior to shipment of the meter.
Flowmeter Identification: Model Number , Serial Number, T ag Name Flowmeter Configuration: Low Flow Cutoff, Calibration Factor , Flow Rate
Units of Measure
3-7
Section 3 Operation
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Transmitter Analog Output: Analog Output HiRange, Analog Output LoRange
d. Optional Programmable Alarm and Pulse Output Parameters and
Features
Alarm Contact Output: HiLimit, LoLimit One or two digital outputs are available for a alarm signals. Contact output polarity is configurable as Normally Open (N.O.) or Normally Closed (N.C.). The alarms may be set at the minimum and maximum flow rate or at any other preferred high and low limits. The units of measure of the alarm limits is the same units of measure as the process variable itself.
Computations: Totalization Totalizers are available in both Resettable and Inventory options. Resettable totalization is used for batching while inventory totalization measures the total volume over time. Units of measure are set independently for each of these options.
Pulse Output: Pulse Out Scaler , Pulse Out Width The SMM has a pulse output channel that indicates flow rate as a variable frequency and therefore can pass information to many types of external equipment such as batch controllers, automation systems or provers. The output pulse width default is 1 millisec but may be user-configured since certain external receiving equipment cannot keep up with high incoming frequency.
Low Flow Cutoff Warning for Pulse Output and Totalization The low flow cutoff parameter can be programmed to signal when the flow level is below which the process is intended. Below this level, the totalizer will assume that the flow rate is actually zero and that no data should be accumulated by the totalizers.
Pulse Output Overrun Alarm If a larger than acceptable output pulse width is configured, totalizer pulses may be delayed or queued. No loss of pulses will occur. The tot alizer output pulses will to be sent until the queue is empty . Under these circumstances, an alarm message will be sent to the control station. However, the alarm can be disabled if not required.
Optional Alarm Configurations— Enable, Destination, Alarm Type (Latching) Three additional parameters may be programmed for process and diagnostic alarms to control functionality — enable, destination, and alarm type (latching). ‘Enable’ allows alarms to be enabled and disabled depending on use of the alarm. For example, if output pulses are being used it may be normal practice to delay (e.g. queue up) output pulses because of a slow receiving end-device that requires a wide pulse-width. The ‘enable’ parameter allows the user to disable the pulse output overrun alarm and not send an alarm when in fact pulse outputs are delayed by choice. Some critical diagnostic alarms, such as database initialization, can
3-8
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
not be disabled or turned off. When an alarm occurs, it can be posted through the defined ‘destination’ digital contact closure outputs #1, #2 both or neither. Therefore the alarms may be managed according to local operating practices and the need to notify upstream control/safety systems.
An alarm may be posted at a designated destination only when the alarm situation is occurring or posted until the alarm is acknowledged by the operator. The decision to ‘latch or unlatch’ the alarm is controlled by setting the ‘alarm type’ parameter. By utilizing this optional parameter, the operator can see that there is an alarm as it is occurring (unlatched) or even after the fact, in the case when the operator did not directly observe the unit alarm (latched).
The following are two examples of typical programming via an Emerson Model 275 hand-held communicator.
Example 1: Programming Flow Rate Units.
Section 3 Operation
Models MT 3809 and 3819
Brooks MT 38xxVA On-line
1 Device Setup
2 PV 3 AO 4 URV 5 LRV
SAVE
F1 F4F3F2
Brooks MT 38xxVA Device Setup 1 Process Variables 2 Diags & Services 3 Basic Setup
4 Detailed Setup
SAVE
F1 F4F3F2
setup
25 gpm
12.0 mA
0.00 gpm
50.00 gpm
From the Online Menu, select Device Setup.
From the Device Setup Menu, select Detailed Setup.
3-9
Section 3 Operation
Models MT 3809 and 3819
Brooks MT 38xxVA Detailed Setup
1 Measurements
2 Computations 3 Outputs 4 Alarms 5 Device Info
SAVE
F1 F4F3F2
Brooks MT 38xxVA Measurements
1 Flow
2 Temperature 3 Density 4 Pressure 5 Viscosity
SAVE
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
From the Detailed Setup Menu, select Measurements.
From the Measurements Menu, select Flow.
F1 F4F3F2
3-10
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Brooks MT 38xxVA Flow
1 FlowRate Units
2 Configuration 3 Meter Calibration
SAVE
F1 F4F3F2
Brooks MT 38xxVA FlowRate Units
gal/min
L/min
I mpgal/min
F1 F4F3F2
ESC
ENTER
Section 3 Operation
Models MT 3809 and 3819
From the Flow Menu, select
FlowRate Units of Measure
(FlowRate UOM).
In Flow, scroll through list optional units. Highlight the FlowRate UOM desired. Press
ENTER (F4) to enter the new
information, and press SEND (F2) to send this information to the transmitter.
Note: Two Warning messages will appear.
Warning Pressing OK will change device output. Put loop in manual.
Warning Return control loop to automatic control. These warnings confirm changes to the programming and alert the user to
make changes in other related fields.
Example 2: Programming Low Flow Cutoff.
Brooks MT 38xxVA On-line
1 Device setup
2 PV 3 AO 4 URV 5 LRV
SAVE
F1 F4F3F2
setup
25 gpm
12.0 mA
0.00 gpm
50.00 gpm
From the Online Menu, select Device Setup.
3-11
Section 3 Operation
Models MT 3809 and 3819
Brooks MT 38xxVA Device Setup 1 Process Variables 2 Diags & Services
3 Basic Setup
4 Detailed Setup
SAVE
F1 F4F3F2
Brooks MT 38xxVA Basic Setup 1 Tag 2 Model 3 Ser No
4 Configuration
5 Analog Output
SAVE
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
From the Device Setup Menu, select Basic Setup.
From the Basic Setup Menu, select Configuration.
F1 F4F3F2
Brooks MT 38xxVA Configuration
1 Cutoff
2 CalFact
SAVE
F1 F4F3F2
From the Configuration Menu, select Cutoff.
3-12
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 3 Operation
Models MT 3809 and 3819
Brooks MT 38xxVA Cutoff
00.00 L/min
Enter the Cutoff value in the same units specified in the FlowRate UOM. Press ENTER
HELP
F1 F4F3F2
DEL
ESC
ENTER
(F4) to enter the new information and press SEND (F2) to send this information to the transmitter.
3-4 Operation of the Models MT 3809 and MT 3819 Flowmeters with a Smart Meter Manager T ransmitter
with Inductive Alarms ( 1 or 2 Switches)
a. St art-up the meter as described in Section 3-2. b. S tart-up the transmitter as described in Section 3-3. c. Start-up the inductive alarms as described in Section 3-5.
3-5 Operation of the Models MT 3809 and MT 3819 Flowmeters
with Inductive Alarms ( 1 or 2 Switches)
a. St art-up the meter as described in Section 3-2. b. To modify the alarm set points, remove the front cover with gasket of
the indicator housing by removing the four screws.
c. Set the alarm position by loosening the two pointer screws, moving
the pointer to the desired alarm setting and tightening the screws.
d. Replace the indicator housing cover with gasket and secure with the
four screws.
3-13
Section 3 Operation
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
THIS PAGE WAS INTENTIONALLY
LEFT BLANK
3-14
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
4-1 General Service Information
Section 4 Maintenance
Models MT 3809 and 3819
4-1
Section 4 Maintenance
Models MT 3809 and 3819
If this equipment is not properly serviced, serious personal injury and/or damage to the equipment can result from potentially high operating pressures. Process line pressure should be removed prior to servicing.
There is no routine maintenance required for the Models MT 3809 and MT 3819 flowmeters. However should it become necessary to replace, adjust or remove components of the flowmeter , specific recommendations must be followed.
4-2a Meter Float Replacement and Cleaning (MT 3809)
Float replacement procedures are dependent on the meter size, connection type and fluid (gas vs. liquid) application. Please refer to the appropriate section below for instructions along with Figures 4-1, 4-2 and 4-3 for referenced part numbers (#) appearing in parenthesis.
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
WARNING
WARNING
Pressure test the meter before returning it to service. Hydrostatic pressure testing should be performed only by qualified personnel or serious personal injury and/or damage to the equipment can result.
1. Flanged Connection
a. Size 7 (1/2") Flanged Liquid or Gas Service
1. Remove the meter from the process line and lay the meter horizontal
on a table.
2. With a small screwdriver , remove the spiral retaining ring (#1) from the
meter inlet.
3. Push the entire float assembly slowly downward and out of the meter
inlet by pushing from the top with a round bar stock (3/4" or 19 mm diameter).
4. Remove the float snap-ring to clean individual float assembly parts .
5. Reassemble the meter by reassembling the float assembly and
inserting it into the bottom of the meter . Replace the spiral retaining ring (#1) in the meter inlet.
b. Size 8 (1/2") Flanged Liquid Service
1. Remove the meter from the process line and lay the meter horizontal
on a table.
2. With small screwdriver remove the spiral retaining ring (#1) from the
4-2
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
3. Loosen the float assembly with two screwdrivers one on each end of
4. Remove the guide vane (#3) at the bottom of the meter and gently push
5. Reassemble by inserting the float assembly into the top of the meter.
c. Size 8 (1/2") Flanged Gas Service
1. Remove the meter from the process line and lay the meter horizontal on
2. With the help of a small screwdriver remove the spiral retaining ring
3. Secure the damper from turning by inserting a 1/8” pin through the top
4. Push the float assembly out through the inlet/bottom.
5. To clean the gas damper, unscrew the cylinder head (#6). Then remove
6. Reassemble the meter by assembling the damper with float assembly.
Section 4 Maintenance
Models MT 3809 and 3819
meter inlet.
the meter and turn to loosen the inlet and outlet screws (#2). Remove inlet screw (#2) at the bottom of the meter .
the float assembly up and out the top/outlet side.
Replace the guide vane (#3) and secure the float assembly by tightening the inlet and outlet screws (#2). Replace the spiral retaining ring (#1) in the meter inlet.
a table.
(#1) from the meter inlet.
guide cartridge. While holding the damper in place, remove the top/ outlet screw (#5).
the bolt (#7) and carefully take out the small piston so as to not damage the critical surfaces.
Insert the float assembly with damper into the inlet/bottom of the meter. Secure the inlet/bottom screw. While holding the damper in place with a pin (1/8” diameter), insert and secure the top/outlet screw (#5). Replace the spiral retaining ring (#1).
d. Sizes 10 (1"), 12 (1 1/2"), 13 (2") Flanged Liquid Service
1. Remove the meter from the process line and lay the meter horizontal on a table.
2. Loosen the float assembly with two screwdrivers one on each end of the meter and turn to loosen the inlet and outlet screws (#2).
3. Remove inlet screw (#2) at the bottom of the meter.
4. Remove the guide vane (#3) at the bottom of the meter and gently push the float assembly up and out the top/outlet side.
5. Reassemble by inserting the float assembly into the top of the meter. Replace the guide vane (#3) and secure the float assembly by tightening the inlet and outlet screws (#2).
e. Sizes 10 (1"), 12 (1 1/2"), 13 (2") Flanged Gas Service
1. With the help of a small screwdriver remove the spiral retaining ring (# 1) from the meter inlet.
2. Secure the damper from turning by inserting a 1/8” pin through the top guide cartridge. While holding the damper in place, remove the top/
4-3
Section 4 Maintenance
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
outlet screw (#5).
3. Push the float assembly out through the inlet/bottom.
4. To clean the gas damper, unscrew the cylinder head (#6). Then remove the bolt (#7) and carefully take out the small piston so as to not damage the critical surfaces.
5. Reassemble the meter by assembling the damper with float assembly. Insert the float assembly with damper into the inlet/bottom of the meter . Secure the inlet/bottom screw. While holding the damper in place with a pin (1/8” diameter), insert and secure the top/outlet screw (#5). Replace the spiral retaining ring (#1).
Sizes 15 and 16 (3" and 4") Flanged Liquid or Gas Service (Size 15 only)
f.
1. Remove the meter from the process line and lay the meter horizontal on a table.
2. Loosen the float assembly by fixating two pliers one on each end of the float assembly inlet guide cartridge (#8). T urn to loosen with the help of a pin wrench.
3. Carefully remove the complete float assembly (#2) and conical taper (#7) as well as the spacer bushing (#10, Size 16 only) out the inlet/ bottom of the meter .
4. Reassemble by inserting the float assembly inside the conical taper (as well as the spacer bushing, Size 16 only). Then insert the complete float assembly into the bottom of the meter. Replace the float assembly inlet guide cartridge and tighten the float assembly into place.
2. NPT Connection
a.
Size 7 (1/2") NPT Liquid or Gas Service
1. Remove the meter from the process line and lay the meter horizontal on a table.
2. Unscrew the inlet fitting (#4) at the bottom of the meter.
3. Push the entire float assembly slowly downward and out of the meter inlet by pushing from the top with a round bar stock (3/4” or 19 mm diameter).
4. Remove the float snap-ring and clean individual float assembly parts .
5. Reassemble the meter by reassembling the float assembly and inserting it into the bottom of the meter . Reinstall and secure the inlet fitting (#4).
b. Sizes 8 (1/2"), 10 (1"), 12 (1 1/2"), 13 (2") NPT Liquid Service
1. Remove the meter from the process line and lay the meter horizontal on a table.
2. Unscrew the inlet fitting (#4) at the bottom of the meter.
3. Loosen the float assembly with two screwdrivers one on each end of the meter and turn to loosen the inlet and outlet screws (#2). Remove inlet screw (#2) at the bottom of the meter .
4. Remove the guide vane (#3) at the bottom of the meter and gently push
4-4
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
5. Reassemble by inserting the float assembly into the top of the meter.
c. Size 8 (1/2”) NPT Gas Service
1. Remove the meter from the process line and lay the meter horizonta l
2. Unscrew the outlet fitting (#4) at the top/outlet of the meter and remove
3. Unscrew the inlet/bottom fitting (#4) and slowly remove the float
4. To reassemble the meter, insert the float assembly into the inlet/bottom
Section 4 Maintenance
Models MT 3809 and 3819
the float assembly up and out the top/outlet side.
Replace the guide vane (#3) and secure the float assembly by tightening the inlet and outlet screws (#2). Reinstall and secure the inlet fitting (#4).
on a table.
the gas damper.
assembly .
of the meter. Secure the inlet/bottom fitting (#4). Replace the gas damper and secure the outlet/top fitting (#4).
d. Sizes 10 (1"), 12 (1 1/2"), 13 (2") NPT Gas Service
1. Remove the meter from the process line and lay the meter horizonta l
on a table.
2. Remove the top/outlet screw (#5).
3. Loosen the float assembly by holding the damper in place with a pin
(1/8” diameter) in the top while loosening the inlet/bottom fitting. Gently push the float assembly out through the inlet/bottom.
4. To clean the gas damper, unscrew the cylinder head (#6). Then remove
the bolt (#7) and take out the small piston carefully so as to not damage the critical surfaces.
5. Reassemble the meter by inserting the float assembly with damper into
the inlet/bottom of the meter. Secure the inlet/bottom screw by holding
4-5
Section 4 Maintenance
Models MT 3809 and 3819
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
Liquid Service
Gas Service
Figure 4-1 Meter Float Replacement & Cleaning (MT 3809)
4-6
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 4 Maintenance
Models MT 3809 and 3819
Figure 4-2 Exploded View, Model MT 3809, Size 15 ( Gas or Liquid Service Only)
Figure 4-3 Exploded View, Model MT 3809, Size 16 ( Liquid Service Only)
4-7
Section 4 Maintenance
Models MT 3809 and 3819
4-2b Meter Float Replacement and Cleaning (MT 3819)
Flanged Connections, All Sizes, Liquid or Gas
1. Remove the meter from the process line and lay the meter horizontal on a table.
2. With a screwdriver, carefully loosen the inlet and outlet inserts (#3, #5).
3. Continue to pull until the inlet and outlet inserts are removed from the meter .
4. Remove the float (#4) and tapered insert (#2) from the meter.
5. Reassemble by reinserting the float (#4) and tapered insert (#2). And then gently push the inlet and outlet inserts (#3, #5) into the flanges. Sizes 10 (1"), 12 (1-1/2") and 13 (2") meters, be careful to line up the top of the float assembly shaft with the outlet insert to ensure proper fit.
4-3 Meter Indicator Reference Mark (Zero) Adjustment
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
This adjustment is performed with no process flow with the float resting on the guide vane or the inlet end fitting.
a. Completely stop fluid flow through the indicator. b. Remove the four screws securing the indicator housing window and
remove the gasket and cover .
c. Turn the slotted screw on the bottom of the point until the pointer is
in line with the reference (zero) mark on the scale.
d. Replace the indicator housing cover with gasket and secure with the
four screws.
4-4 Smart Meter Manager Transmitter Replacement with or without Alarms and Pulse Output
The transmitter is a self contained unit matched specifically to the associated flowmeter. If there is a need to replace, please contact your nearest authorized Brooks Service Representative.
4-5 Inductive Alarm Replacement
a. Remove the front cover of the indicator housing by removing the
four screws securing it.
b. The wires from the alarm switch(es) are plugged into the alarm
terminal circuit board and must be unplugged for replacement.
c. Loosen the two screws securing the scale, with the alarm switches
attached, and remove the scale.
d. Turn the scale over and locate the screw centered in the green
alarm switch. Remove the screw being careful not to lose the nut on the outside of the alarm set bracket. Remove the alarm switch from
4-8
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September, 2008
Section 4 Maintenance
Models MT 3809 and 3819
support.
e. Place the switch on the bracket with the open end facing towards the
center of the scale plate and the wires facing away from the scale plate.
f. Place the switch screw through the opening in the switch, and the
support bracket. Use the nut to secure the screw and tighten.
g. Plug in the switches. h. Replace the scale and tighten two clamping screws. Make sure that
the alarm switch wires do not interfere with the alarm cam. Insure that the pointer is aligned with the ‘R’ or zero mark. If not refer to Section 4-3, Indicator Reference Mark (Zero) Adjustment.
Sizes 7 & 8 Sizes 10, 12 & 13
Figure 4-4 Meter Float Replacement & Cleaning (MT 3819)
4-9
Section 4 Maintenance
Installation and Operation Manual
Models MT 3809 and 3819
i. Set the alarm position, by loosening the two pointer screws, moving
the point of the desired alarm setting, and tightening the screws.
j. Connect the field wiring. k. Replace the indicator housing cover and secure with four screws.
4-6 SMM T ransmitter Replacement with Inductive Alarms
The transmitter is a self contained unit matched specifically to the associated flowmeter. If there is a need to replace it, please contact your nearest authorized Brooks Service Representative. However , the inductive alarms may be replaced according to the procedure in Section 4-5.
4-7 Monitoring the Integrity of the SMM Electronics - Diagnostic Alarms
As part of its normal operations, the SMM continuously monitors its own internal health. Automatic diagnostics can trigger alarms indicating poor communications, memory integrity , or sensor problems. The user can define whether these malfunctions are serious and instruct that a 4-20 mA analog-signal be sent automatically to a receiving devices such as a DCS or PLC system.
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008
a. Power Failure Alarm The power failure alarm will occur when the current-loop is broken and then restored. In this case, the transmitter will raise the power-fail alarm to notify the user that there was a gap in data collection. The 4-20 mA loop provides all internal power for the SMM electronics. However, if power is lost, the setup parameters are internally stored in nonvolatile memory (lithium battery) and maintained in the event that external power is disconnected.
b. Database-Initialization Alarm will occur when the transmitter powers up and finds that the internal parameter database was not saved properly and must return parameters to the inherent defaults.
c. High Internal Temperature Alarm Should the electronics unit exceed functional limits (70°C), this information will be indicated.
TRADEMARKS
AMS ................. Emerson Process Management Grp. of Companies
Brooks ........................................................... Brooks Instrument, LLC
Emerson ........................................................... Emerson Electric Co.
Emerson Access Management ........................ Emerson Electric Co.
HART ......................................... HART Communications Foundation
Smart Meter Manager ....................................... Brooks Instrument, LLC
SMM ............................................................. Brooks Instrument, LLC
Teflon ................................................ E.I. DuPont de Nemours & Co.
Viton ............................................... DuPont Performance Elastomers
4-10
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September , 2008
Dansk
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Emne : Tillæg til instruktions manual. Reference : CE mærkning af Masse Flow udstyr Dato : Januar-1996.
Brooks Instrument har gennemført CE mærkning af elektronisk udstyr med succes, i henhold til regulativet om elektrisk støj (EMC direktivet 89/336/EEC).
Der skal dog gøres opmærksom på benyttelsen af signalkabler i forbindelse med CE mærkede udstyr.
Kvaliteten af signal kabler og stik:
Brooks lever kabler af høj kvalitet, der imødekommer specifikationerne til CE mærkning. Hvis der anvendes andre kabel typer skal der benyttes et skærmet kabel med hel skærm med 100% dækning. Forbindelses stikket type “D” eller “cirkulære”, skal være skærmet med metalhus og eventuelle PG-forskruninger
skal enten være af metal eller metal skærmet. Skærmen skal forbindes, i begge ender , til stikket s metalhus eller PG-forskruningen og have forbindelse over 360
grader. Skærmen bør være forbundet til jord. “Card Edge” stik er standard ikke af metal, der skal derfor ligeledes benyttes et skærmet kabel med hel skærm
med 100% dækning. Skærmen bør være forbundet til jord. Forbindelse af stikket; venligst referer til vedlagte instruktions manual. Med venlig hilsen,
Appendix A CE Certification
Models MT 3809 and 3819
Deutsch
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Subject : Nachtrag zur Bedienungsanleitung. Referenz : CE Zertifizierung für Massedurchflußgeräte Datum : Januar-1996.
Nach erfolgreichen Tests enstprechend den Vorschiften der Elektromagnetischen Verträglichkeit (EMC Richtlinie 89/336/EEC) erhalten die Brooks-Geräte (elektrische/elektronische Komponenten) das CE-Zeichen.
Bei der Auswahl der V erbindungskabel für CE-zertifizierte Geräte sind spezielle Anforderungen zu beachten.
Qualität der Verbindungskabel, Anschlußstecker und der Kabeldurchführungen
Die hochwertigen Qualitätskabel von Brooks entsprechen der S pezifikation der CE-Zertifizierung. Bei Verwendung eigener Verbindungskabel sollten Sie darauf achten, daß eine 100 %igenSchirmababdeckung des Kabels gewährleistet ist.
“D” oder “Rund” -Verbindungsstecker sollten eine Abschirmung aus Metall besitzen.
Wenn möglich, sollten Kabeldurchführungen mit Anschlußmöglichkeiten für die Kabelabschrimung verwendet werden.
Die Abschirmung des Kabels ist auf beiden Seiten des Steckers oder der Kabeldurchführungen über den vollen Umfang von 360 ° anzuschließen.
Die Abschirmung ist mit dem Erd potential zu verbinden. Platinen-Steckverbindunger sind st andardmäßige keine metallgeschirmten V erbindungen. Um die Anforderungen
der CE-Zertifizierung zu erfüllen, sind Kabel mit einer 100 %igen Schirmababdeckung zu verwenden. Die Abschirmung ist mit dem Erd potential zu verbinden. Die Belegung der Anschlußpins können Sie dem beigelegten Bedienungshandbuch entnehmen.
A-1
Appendix A CE Certification
Models MT 3809 and 3819
English
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Subject : Addendum to the Instruction Manual. Reference : CE certification of Mass Flow Equipment Date : January-1996.
The Brooks (electric/electronic) equipment bearing the CE mark has been successfully tested to the regulations of the Electro Magnetic Compatibility (EMC directive 89/336/EEC).
Special attention however is required when selecting the signal cable to be used with CE marked equipment.
Quality of the signal cable, cable glands and connectors:
Brooks supplies high quality cable(s) which meets the specifications for CE certification. If you provide your own signal cable you should use a cable which is overall completely screened with a 100%
shield. “D” or “Circular” type connectors used should be shielded with a metal shield. If applicable, metal cable glands
must be used providing cable screen clamping. The cable screen should be connected to the metal shell or gland and shielded at both ends over 360 Degrees. The shield should be terminated to a earth ground. Card Edge Connectors are standard non-metallic. The cables used must be screened with 100% shield to comply
with CE certification. The shield should be terminated to a earth ground. For pin configuration : Please refer to the enclosed Instruction Manual.
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September , 2008
Español
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Asunto : Addendum al Manual de Instrucciones. Referencia : Certificación CE de los Equipos de Caudal Másico Fecha : Enero-1996.
Los equipos de Brooks (eléctricos/electrónicos) en relación con la marca CE han pasado satisfactoriamente las pruebas referentes a las regulaciones de Compatibilidad Electro magnética (EMC directiva 89/336/EEC).
Sin embargo se requiere una atención especial en el momento de seleccionar el cable de señal cuando se va a utilizar un equipo con marca CE
Calidad del cable de señal, prensaestopas y conectores:
Brooks suministra cable(s) de alta calidad, que cumple las especificaciones de la certificación CE . Si usted adquiere su propio cable de señal, debería usar un cable que esté completamente protegido en su
conjunto con un apantallamiento del 100%. Cuando utilice conectores del tipo “D” ó “Circular” deberían estar protegidos con una pantalla metálica. Cuando
sea posible, se deberán utilizar prensaestopas metálicos provistos de abrazadera para la p ant alla del cable. La pantalla del cable deberá ser conectada al casquillo metálico ó prensa y protegida en ambos extremos
completamente en los 360 Grados. La pantalla deberá conectarse a tierra. Los conectores estandar de tipo tarjeta (Card Edge) no son metálicos, los cables utilizados deberán ser
protegidos con un apantallamiento del 100% para cumplir con la certificación CE. La pantalla deberá conectarse a tierra. Para ver la configuración de los pines: Por favor , consultar Manual de Instrucciones adjunto.
A-2
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September , 2008
Français
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Sujet : Annexe au Manuel d’Instructions. Référence : Certification CE des Débitmètres Massiques à Effet Thermique. Date : Janvier 1996.
Messieurs, Les équipements Brooks (électriques/électroniques) portant le label CE ont été testés avec succès selon les
règles de la Compatibilité Electromagnétique (directive CEM 89/336/EEC). Cependant, la plus grande attention doit être apportée en ce qui concerne la sélection du câble utilisé pour
véhiculer le signal d’un appareil portant le label CE.
Qualité du câble, des presse-étoupes et des connecteurs:
Brooks fournit des câbles de haute qualité répondant aux spécifications de la certification CE. Si vous approvisionnez vous-même ce câble, vous devez utiliser un câble blindé à 100 %. Les connecteurs « D » ou de type « circulaire » doivent être reliés à la terre. Si des presse-étoupes sont nécessaires, ceux ci doivent être métalliques avec mise à la terre. Le blindage doit être raccordé aux connecteurs métalliques ou aux presse-étoupes sur le pourtour complet du
câble, et à chacune de ses extrémités. Tous les blindages doivent être reliés à la terre. Les connecteurs de type « card edge » sont non métalliques. Les câbles utilisés doivent être blindés à 100% pour
satisfaire à la réglementation CE. Tous les blindages doivent être reliés à la terre. Se référer au manuel d’instruction pour le raccordement des contacts.
Appendix A CE Certification
Models MT 3809 and 3819
Greek
A-3
Appendix A CE Certification
Models MT 3809 and 3819
Italiano
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Oggetto : Addendum al manuale di istruzioni. Riferimento : Certificazione CE dei misuratori termici di portat a in massa Data : Gennaio 1996.
Questa strumentazione (elettrica ed elettronica) prodotta da Brooks Instrument, soggett a a marcatura CE, ha superato con successo le prove richieste dalla direttiva per la Compatibilità Elettomagnetica (Direttiva EMC 89/ 336/EEC).
E’ richiesta comunque una speciale attenzione nella scelt a dei cavi di segnale da usarsi con la strumentazione soggetta a marchio CE.
Qualità dei cavi di segnale e dei relativi connettori:
Brooks fornisce cavi di elevata qualità che soddisfano le specifiche richieste dalla certificazione CE. Se l’utente intende usare propri cavi, questi devono possedere una schermatura del 100%.
I connettori sia di tipo “D” che circolari devono possedere un guscio metallico. Se esiste un passacavo esso deve essere metallico e fornito di fissaggio per lo schermo del cavo.
Lo schermo del cavo deve essere collegato al guscio metallico in modo da schermarlo a 360° e questo vale per entrambe le estemità.
Lo schermo deve essere collegato ad un terminale di terra. I connettori “Card Edge” sono normalmente non metallici. Il cavo impiegato deve comunque avere una
schermatura del 100% per soddisfare la certificazione CE. Lo schermo deve essere collegato ad un terminale di terra. Per il corretto cablaggio dei terminali occorre fare riferimento agli schemi del manuale di istruzioni dello strumento.
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September , 2008
Nederlands
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Onderwerp : Addendum voor Instructie Handboek Referentie : CE certificering voor Mass Flow Meters & Controllers Datum : Januari 1996
Dames en heren, Alle CE gemarkeerde elektrische en elektronische produkten van Brooks Instrument zijn met succes getest en
voldoen aan de wetgeving voor Electro Magnetische Compatibiliteit (EMC wetgeving volgens 89/336/EEC). Speciale aandacht is echter vereist wanneer de signaalkabel gekozen wordt voor gebruik met CE gemarkeerde
produkten.
Kwaliteit van de signaalkabel en kabelaansluitingen:
Brooks levert standaard kabels met een hoge kwaliteit, welke voldoen aan de specificaties voor CE certificering.
Indien men voorziet in een eigen signaalkabel, moet er gebruik gemaakt worden van een kabel die volledig is afgeschermd met een bedekkingsgraad van 100%.
“D” of “ronde” kabelconnectoren moeten afgeschermd zijn met een metalen connector kap. Indien kabelwartels worden toegepast, moeten metalen kabelwartels worden gebruikt die het mogelijk maken het kabelscherm in te klemmen
Het kabelscherm moet aan beide zijden over 360° met de metalen connectorkap, of wartel verbonden worden. Het scherm moet worden verbonden met aarde.
“Card-edge” connectors zijn standaard niet-metallisch. De gebruikte kabels moeten volledig afgeschermd zijn met een bedekkingsgraad van 100% om te voldoen aan de CE certificering.
Het scherm moet worden verbonden met aarde. V oor pin-configuraties a.u.b. verwijzen wij naar het bijgesloten instruktie handboek. Hoogachtend,
A-4
Installation and Operation Manual
Appendix A CE Certification
X-V A-MT3809-3819-eng Part Number: 541B049AHG September , 2008
Norsk
Models MT 3809 and 3819
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Vedrørende : Vedlegg til håndbok Referanse : CE sertifisering av ut styr for massestrømsmåling og regulering Dato : Januar 1996
Til den det angår
Brooks Instrument elektrisk og elektronisk utstyr påført CE-merket har gjennomgått og bestått prøver som beskrevet i EMC forskrift om elektromagnetisk immunitet, direktiv 89/336/EEC.
For å opprettholde denne klassifisering er det av stor viktighet at riktig kabel velges for tilkobling av det måletekniske utstyret.
UTFØRELSE A V SIGNALKABEL OG TILHØRENDE PLUGGER:
Brooks Instrument tilbyr levert med utstyret egnet kabel som møter de krav som stilles til CE-sertifisering.
Dersom kunden selv velger kabel, må kabel med fullstendig, 100% skjerming av lederene benyttes.
“D” type og runde plugger og forbindelser må være utført med kappe i metall og kabelnipler må være utført i metall for jordet innfesting av skjermen. Skjermen i kabelen må tilknyttes metallet i pluggen eller nippelen i begge ender over 360°, tilkoblet elektrisk jord.
Kort-kantkontakter er normalt utført i kunst stoff. De tilhørende flatkabler må være utført med fullstendig, 100%
skjerming som kobles til elektrisk jord på riktig pinne i pluggen, for å møte CE sertifiseringskrav .
For tilkobling av medleverte plugger, vennligst se håndboken som hører til utstyret.
Vennlig hilsen
Português
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Assunto : Adenda ao Manual de Instruções Referência : Certificação CE do Equipamento de Fluxo de Massa Data : Janeiro de 1996.
O equipamento (eléctrico/electrónico) Brooks com a marca CE foi testado com êxito nos termos do regulamento da Compatibilidade Electromagnética (directiva CEM 89/336/EEC).
Todavia, ao seleccionar-se o cabo de sinal a utilizar com equipamento contendo a marca CE, será necessário ter uma atenção especial.
Qualidade do cabo de sinal, buchas de cabo e conectores:
A Brooks fornece cabo(s) de qualidade superior que cumprem os requesitos da certificação CE. Se fornecerem o vosso próprio cabo de sinal, devem utilizar um cabo que, na sua totalidade, seja isolado com uma
blindagem de 100%. Os conectores tipo “D” ou “Circulares” devem ser blindados com uma blindagem metálica. Se tal for necessário,
deve utilizar-se buchas metálicas de cabo para o isolamento do aperto do cabo. O isolamento do cabo deve ser ligado à blindagem ou bucha metálica em ambas as extremidades em 360º. A blindagem deve terminar com a ligação à massa. Os conectores “Card Edge” não são, em geral, metálicos e os cabos utilizados devem ter um isolamento com
blindagem a 100% nos termos da Certificação CE.. A blindagem deve terminar com ligação à massa. Relativamente à configuração da cavilha, queiram consultar o Manual de Instruções.
A-5
Appendix A CE Certification
Models MT 3809 and 3819
Suomi
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Asia : Lisäys Käyttöohjeisiin Viite : Massamäärämitt areiden CE sertifiointi Päivämäärä : Tammikuu 1996
Brooksin CE merkillä varustetut sähköiset laitteet ovat läpäissyt EMC testit (direktiivi 89/336/EEC). Erityistä huomiota on kuitenkin kiinnitettävä signaalikaapelin valintaan.
Signaalikaapelin, kaapelin läpiviennin ja liittimen laatu
Brooks toimittaa korkealaatuisia kaapeleita, jotka täyttävät CE sertifikaatin vaatimukset. Hankkiessaan signaalikaapelin itse, olisi hankittava 100%:sti suojattu kaapeli.
“D” tai “Circular” tyyppisen liitimen tulisi olla varustettu metallisuojalla. Mikälì mahdollista, tulisi käyttää met allisia kaapeliliittimiä kiinnitettäessä suojaa.
Kaapelin suoja tulisi olla liitetty metallisuojaan tai liittimeen molemmissa päissä 360°:n matkalta. Suojan tulisi olla maadoitettu. “Card Edge Connector”it ovat standarditoimituksina ei-metallisia. Kaapeleiden täytyy olla 100%: sesti suojattuja
jotta ne olisivat CE sertifikaatin mukaisia. Suoja on oltava maadoitettu. Nastojen liittäminen; katso liitteenä oleva manuaali. Ystävällisin terveisin,
Installation and Operation Manual
X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September , 2008
Svensk
Brooks Instrument 407 West Vine St. Hatfield, P A 19440 U.S.A.
Subject : Addendum to the Instruction Manual Reference : CE certification of Mass Flow Equipment Date : January 1996
Brooks (elektriska / elektronik) utrustning, som är CE-märkt, har testats och godkänts enligt gällande regler för elektromagnetisk kompabilitet (EMC direktiv 89/336/EEC).
Speciell hänsyn måste emellertid tas vid val av signalkabel som ska användas tillsammans med CE-märkt utrustning.
Kvalitet på signalkabel och anslutningskontakter:
Brooks levererar som standard, kablar av hög kvalitet som motsvarar de krav som ställs för CE-godkännande. Om man använder en annan signalkabel ska kabeln i sin helhet vara skärmad till 100%.
“D” eller “runda” typer av anslutningskontakter ska vara skärmade. Kabelgenomföringar ska vara av metall alternativt med metalliserad skärmning.
Kabelns skärm ska, i bada ändar, vara ansluten till kont akternas met allkåpor eller genomföringar med 360 graders skärmning.
Skärmen ska avslutas med en jordförbindelse. Kortkontakter är som standard ej metalliserade, kablar som används måste vara 100% skarmade för att
överensstämma med CE-certifieringen. Skärmen ska avslutas med en jordförbindelse. För elektrisk anslutning till kontaktstiften hänvisas till medföljande instruktionsmanual.
A-6
Installation and Operation Manual
X-V A-MT3809-3819-eng Part Number: 541B049AHG September , 2008
Models MT 3809 and 3819
THIS PAGE WAS INTENTIONALLY
LEFT BLANK
Installation and Operation Manual
X-V A-MT3809-3819-eng
Part Number: 541B049AHG
Models MT 3809 and 3819
LIMITED WARRANTY
Seller warrants that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal use and service and that the Software will execute the programming instructions provided by Seller until the expiration of the earlier of twelve (12) months from the date of initial installation or eighteen (18) months from the date of shipment by Seller. Products purchased by Seller from a third party for resale to Buyer (“Resale Products”) shall carry only the warranty extended by the original manufacturer. All replacements or repairs necessitated by inadequate preventive maintenance, or by normal wear and usage, or by fault of Buyer, or by unsuitable power sources or by attack or deterioration under unsuitable environmental conditions, or by abuse, accident, alteration, misuse, improper installation, modification, repair, storage or handling, or any other cause not the fault of Seller are not covered by this limited warranty, and shall be at Buyer’s expense. Goods repaired and parts replaced during the warranty period shall be in warranty for the remainder of the original warranty period or ninety (90) days, whichever is longer. This limited warranty is the only warranty made by Seller and can be amended only in a writing signed by an authorized representative of Seller.
BROOKS SERVICE AND SUPPORT
Brooks is committed to assuring all of our customers receive the ideal flow solution for their application, along with outstanding service and support to back it up. We operate first class repair facilities located around the world to provide rapid response and support. Each location utilizes primary standard calibration equipment to ensure accuracy and reliability for repairs and recalibration. The primary standard calibration equipment to calibrate our flow products is certified by our local Weights and Measures Authorities and traceable to the relevant International Standards.
Visit www.BrooksInstrument.com to locate the service location nearest to you.
September, 2008
ST ART-UP SERVICE AND IN-SITU CALIBRATION
Brooks Instrument can provide start-up service prior to operation when required. For some process applications, where ISO-9001 Quality Certification is important, it is mandatory to verify and/or (re)calibrate the products periodically. In many cases this service can be provided under in-situ conditions, and the results will be traceable to the relevant international quality standards.
CUSTOMER SEMINARS AND TRAINING
Brooks Instrument can provide customer seminars and dedicated training to engineers, end users and maintenance persons. Please contact your nearest sales representative for more details.
HELP DESK
In case you need technical assistance:
Americas Europe +(31) 318 549 290 Within Netherlands 0318 549 290
Asia
Due to Brooks Instrument's commitment to continuous improvement of our products, all specifications are subject to change without notice.
1-888-554-FLOW
+011-81-3-5633-7100
Loading...