MODEL
PM44
®
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY
TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer, if
you have questions, contact the manufacturer at the address or
telephone number iisted in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel
and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel
3. Installation work and electrical wiring must be done by a qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to pre-
vent backdrafting. Follow the heating equipment manufacturer's
guideline and safety standards such as those published by the
National Fire Protection Association (NFPA), and the American
Society of Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the Iocal code authorities.
5. When cutting or drilling into walI or ceiling, do not damage electri-
cal wiring and other hidden utiIities.
6. To reduce the risk of fire or electric shock, do not use this range
hood with an additional speed control device.
7. Ducted fans must always be vented to the outdoors.
8. To reduce the risk of fire, use only metal ductwork.
9. This unit must be grounded.
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
1. Never leave surface units unattended at high settings. Boilovers
cause smoking and greasy spiilovers that may ignite. Heat oils
slowly on low or medium settings.
2. Always turn hood ON when cooking at high heat orwhen cooking
flaming foods.
3. Clean ventilating fans frequently. Grease should not be allowed to
accumulate on fan or fiIter.
4. Use proper pan size. Always use cookware appropriate for the
size of the surface element.
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT
OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING: _
1. SMOTHER FLAMES with aclose-fitting lid, cookie sheet, or metal
tray,then turn off the burner. BE CAREFUL TO PREVENT BURNS.
if the flames do not go out immediately, EVACUATE AND CALL
THE FiRE DEPARTMENT.
2. NEVER PiCK UPA FLAMING PAN -- You may be burned.
3. DO NOT USE WATE R, including wet dishcloths or towels -violent
steam explosion will resuit.
4. Use an extinguisher ONLY if:
A. You know you have a Class ABC extinguisher and you al-
ready know how to operate it.
B. The fire is smail and contained in the area where it started.
C. The fire department is being called.
D. You can fight the fire with your back to an exit.
* Based on "Kitchen Fire Safety Tips" published by NFPA.
1. For generaI ventilating use only. Do not use to exhaust hazard-
ous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced
impe!Iers, keep drywaiI spray, construction dust, etc. off power
unit.
3. For best capture of cooking impurities, your range hood shouid
be mounted so that the top of the hood is 24-30" above the cook-
ing surface.
4. Please read specification label on product for further informa-
tion and requirements.
Installer: Leave this manual with the homeowner.
Homeowner: Operating and Cleaning information on page 3.
VENTiLATiNG AND WiRiNG
1. Mark locations on cabinet for ventilating duct and electrical wir-
ing from the dimensions given (FIGURE 1).
2. Cut holes at the marked locations to accommodate the venti-
lating duct and electrical wiring. AiIow 3/4" extra on the ventilat-
ing opening toward the front of the cabinet. Be sure to minimize
openings, these will have to be sealed later (FIGURE 2).
3. Run house wiring through 1-1/2" diameter hoIe in cabinet or
waII. Be sure alI wiring is in accordance with the NationaI Ebc-
tricaI Code and IocaI ordinances.
FIGURE 1
1
1. Remove bIower housing and fiiters for easier installation. See
exhaust unit assembly illustration used for "Replacement Parts
List."
2. Lift the exhaust unit into position and mark the hole locations
on the cabinet for each of the four keyhole mounting slots.
NOTE: REMOVE FASTENERS FROM PLASTIC BAG.
3= Remove the unit. Start all four screws (#10 x 5/8 shotted) in
center of the narrow neck of the keyhole slots previously marked
on the cabinet bottom (FIGURE 3).
RGURE 3 KEYHOLESLOTINCANOPY
SCREW
(iN iNSTALLATiON PARTS BAG}
4. There are predriIIed holes on each side of the 3-1/2 x 10 hole in
exhaust unit for damper attachment. Use the smaII sheet metal
screws included (#8 x 1/4).
5. Remove junction box cover and appropriate knockout in ex-
haust unit for access to wiring.
6. install proper ductwork (FIGURE 4).
FmGURE 2
RGURE4
CABINET CUTOUTS
7. Lift the exhaust unit into position simultaneously feeding house
wiring through exhaust unit knockout.
8. Tighten the four mounting screws to secure the exhaust unit to
the cabinet. Be sure the screw heads are in the narrow neck of
the keyhole slots (FIGURE 3).
9. Complete electrical wiring in junction box according to the Na-
tional EIectrical Code and IocaI ordinances.
10. Replace junction box cover.
11. Seal holes around ventilating pipe and wiring passing through
ceiIing or walIs with cauIking or insulation to prevent heat loss.
12. Replace blower housing and filters.
BLOWER ORiENTATiON
REPLACEMENT PARTS LIST
IMPORTANT: Be sure the blower is correctly orientated. Note ar-
row on the side of the blower housing indicating the correct air flow
direction (FIGURE 5).
FmGURE 5 = VERTICAL DISCHARGE
VERTICAL
DISCHARGE
VENT
(TOP OF HOOD)
BLOWER
fr DISCHARGE=
LOCATEAT
DISCHARGE
VENTIN TOP
OFROOD
THinS
Part No. Description
R561107 3-Pos. Rotary Light Switch
R567073 Motor, Speed Control
R730079 Blower Assembly
R610038 FiIter
R566066 Lampholder
R520098 Motor
R531041 Blower Wheel CW
R531042 Blower Wheel CCW
MOTOR LIGHT SWITCH
CONTROL
JUNCTION
BOX
CLEANING INFORMATION
F_LTER
For greatest efficiency, the aIuminum filters shouId be removed and
cleaned periodicaIIy.
To clean, the filter should be soaked in hot water and detergent
then thoroughly rinsed. The aluminum filter can be cleaned in a
dishwasher.
EXTERIOR SURFACE
Topreserve its Iasting beauty, clean with a mild detergent. DO NOT
use abrasive cleaners.
MOTOR SPEED
TROUBLESHOOTING
If you have a motor speed problem, please check the following list
for possible troubles.
1. Knockouts not removed from hood.
2. BIower assembly instalIed wrong - intended for vertical dis-
charge but instaIled for horizontaI discharge and vice versa
(FIGURE 5).
3. Damper blade not opening.
4. Duct undersized - reduced airflow because duct too smaII or
too long.
5. Restriction in duct from foreign materials or debris.
6. Undersized or restrictive wall or roof cap.
7. Damper blade in wall or roof cap not opening.
8. Wait for 20 - 30 seconds between speed changes for RPM to
adjust.
By removing or correcting these adverse factors, the motor speed
control will be able to decrease from maximum RPM.
I
l
FILTER