Broan ECM SERIES, Nortron 21ECM10, Nortron 21ECM15, Nortron 21ECM18, Nortron 21ECM20 Installation And Operating Instructions Manual

...
ECM SERIES ELECTRIC FURNACE
TEL.: 905-670-2500
FAX: 905-795-8311
CUSTOMER SERVICE TEL.: 1-888-882-7626
MISSISSAUGA, ONTARIO L5T 1H9
30042458A
• Never tamper with the unit or its controls. User MUST contact a specialized contractor when a failure occurs. DO NOT ATTEMPT to repair.
• When using a humidifier make sure not to damage the heating element bank.
• We recommend that your unit be inspected by a specialized technician once a year.
• Poor maintenance of air filters OR an unbalanced static pressure may result in a performance decrease.
• Always use genuine parts for maintenance or service call. The use of unbranded parts will void the warranty.
• The use of this unit without an air distribution duct will void the warranty.
• It is strictly forbidden to use jumpers to simulate heat demand.
• Risk of electrical shock. Disconnect power before installation, servicing, maintenance or field wiring. Replace all panels before operating. Failure to do so can result in electrical shock causing severe injuries or death.
• When performing installation, servicing or cleaning the unit, it is recommended to wear safety glasses and gloves.
• To assure a proper performance of your furnace, we recommend that you use high quality name brand thermostats.
• When applicable local regulation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses.
• For your safety, do not store or use gasoline or other flammable liquids and vapors in the vicinity of this unit or any other appliance.
• These instructions are intended to be use by qualified personnel who have been trained in installing this type of furnace. Installation of this furnace by an unqualified person may lead to equipment damage and/or hazardous condition which may lead to bodily harm.
• This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect its electrical components from water. Outdoor installation leads to a hazardous electrical condition and to premature furnace failure, thus voiding the warranty.
• Do not block the combustion air openings in the furnace. Any blockage will result in improper overheat situation and may result in a fire hazard and/or cause bodily harm.
• The unit must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. When performing electrical connection, the ground conductor must be firmly attached to the ground lug in the furnace.
• Do not use this furnace as a construction heater. Use of this furnace as a construction heater exposes the furnace to abnormal conditions, contaminated combustion air and the lack of air filters. Failure to follow this warning can lead to premature furnace failure and/or vent failure which could result in a fire hazard and/or bodily harm.
• The owner and/or the user is responsible of the following: Always maintain the immediate surrounding of the furnace free from combustible and highly flammables materials.The furnace ambient air should not have an excessive dust concentration and humidity. Never operate this central heating appliance without an air filter.
• Before performing any service functions, unless operations specifically require the power to be on, make sure all utilities are turned “OFF” upstream of the appliance. Failure to comply with this warning will cause a fire hazard and/or bodily harm.
• All questions regarding the operation, maintenance or warranty of this unit should be addressed to the company where this product has been sold from.
WARNING
!
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
CAUTION
• Never burn garbage or paper in the heating system and never leave rags or paper around the unit.
• Return air grilles and warm air registers must not be obstructed.
IMPORTANT: All local and national code requirements governing the electrical installation heating equipment, wiring and flue connections must be followed. Some of the codes that may be applicable are: ANSI/NFPA 70 NATIONAL ELECTRICAL CODE CSA C22.1 CANADIAN ELECTRICAL CODE Only the latest issues of the above codes should be used, and are available from either:
The National Fire Protection Agency
Batterymarch Park Quincy, MA 02269
The Canadian Standards Association
178 Rexdale Blvd.
Rexdale, Ontario M9W 1R3
or
2
This furnace has been designed and manufactured to give the most reliable performance possible. Each unit has been given a running inspection before shipment to assure that every component is operating efficiently.
The safe and dependable operation of the furnace depends upon proper installation and compliance with all national and local codes and standards.
INSTALLATION AND OPERATING INSTRUCTIONS
FRONT VIEW RIGHT SIDE VIEW REAR VIEW LEFT SIDE VIEW
TOP VIEW
(38 mm)
(38 mm)
20
(508 mm)
20
(508 mm)
1
(25 mm)
39
(991 mm)
FILTER FRAME (EITHER SIDE, REAR OR BOTTOM)
x 1½ KO
(38 mm x 38 mm)
x 1½ KO
(38 mm x 38 mm)
x 1½ KO
(38 mm x 38 mm)
WIRING KO’S
A B C
WIRING KO’S
C
A = 1 (25 mm) B = 1/4 (6 mm) & 1¼ (32 mm) C = 1/2 (13 mm) & 1½ (38 mm)
WIRING KO’S VALUES
DISCHARGE
17 x 17
(432 mm x 432 mm)
18” x 18”
(457 mm x 457 mm)
RETURN
18” x 18”
(457 mm x 457 mm)
RETURN
18” x 18”
(457 mm x 457 mm)
RETURN
1. LOCATION – The furnace should be centrally located to the heating area.
2. POSITIONS – It can be installed for vertical, horizontal or downflow operation. When installed horizontally, the furnace should be positioned such as the door will not end up being on the top. The door should be on the side of the furnace, to ensure that the motor bearings are in their designed position. In vertical downflow installations, use only “L”- or “T”-shaped plenum with no openings or registers directly below furnace.
3. INSTALLATION CLEARANCES – As shipped from the factory, each unit is approved for “zero inch” clearance. If additional clearance is required, it will be indicated on the data label attached to the furnace.
4. TEMPERATURE RISE – Furnaces are shipped to operate at
0.20” W.C. (50 Pa) external static pressure. They are certified for operation up to 0.50” W.C. (125 Pa). Check the following page for temperature rise table on specification chart and, if necessary, adjust the unit to match.
5. SERVICE CLEARANCE – Units are serviced from the FRONT. Leave at least 24” (610 mm) clearance in front of the door.
GENERAL REQUIREMENTS AND SPECIFICATIONS
CAUTION
This unit must be installed in a dry place, in a non-corrosive, well-ventilated environment, without excessive dust. The ambient temperature must be over 10°C and under 27°C. If the ambient temperature is 10°C or less, the plenum must be insulated on 10 ft linear minimum length.
UNIT CERTIFICATION
This furnace is CSA certified.
®
GENERAL REQUIREMENTS AND SPECIFICATIONS (CONT’D)
OPERATING OPTIONS
The furnace is shipped from the factory in a “Standard Heating Mode” (both switches in the Down position). When the thermostat calls for heat, the automatic controls will be activated and the furnace turns “ON”.
The blower will run at low speed or higher speed (as selected by SPEED SELECTOR switch).
As the furnace heats up, it automatically switches to a medium speed when additional elements are activated by the electronic control, if it was initially set to run at low speed. The timing of this blower speed change will depend on whether C
OLD or MILD is
selected on the SEASON SELECT switch. You may, however, change from the Standard Heating Mode by
using the controls built into your furnace.
SPEED SELECTOR SEASON SELECT
HIGH
MILD
COLD
The SPEED SELECTOR switch is used to control the fan speed (ventilation). Even if there is no call for heat, the ventilation can be controlled by the thermostat; the fan speed is determined by this switch.
L
OW – The blower motor will operate at low speed.
H
IGH – The blower motor will operate at a higher speed.
During spring or fall, you may require less rapid response when the thermostat calls for heat.
When M
ILD is selected, it takes more time to bring all the elements
online. When C
OLD is selected, the heating elements come online faster.
3
L
OW
*FACTORY SETTINGS. SUBJECT TO CHANGE WITHOUT NOTICE.
**This speed can only be run with heater off, for cooling/ventilation purposes only.
WARNING:
240 VOLTS – SINGLE PHASE TEMP. RISE @ 0.20 in. W.C.
MODEL NO. kW BTUH AMPS INCL. MOTOR HP BLOWER °C °F *SPEED RPM
21ECM10 10 34120 43 1/3
10” x 8”
(254 mm x 203 mm)
19 34 MEDIUM 903 21ECM15 15 51180 64 1/3 22 40 MEDIUM 903 21ECM18 18 61420 76 1/3 26 47 MEDIUM 903 21ECM20 20 68240 84 1/3 29 52 MEDIUM 903 21ECM23 22.5 76770 94 1/3 36 65 MEDIUM 903
10” x 8” (254 mm x 203 mm) BLOWER
SPEED FLOW RATE
STATIC PRESSURE
(INCHES OF WATER COLUMN)
0.2 0.3 0.4 0.5 0.6
LOW**
CFM
L/s
684 323
582 275
535 252
481 227
429 202
MEDIUM
CFM
L/s
1149
542
1104
521
1064
502
1016
479
977 461
HIGH
CFM
L/s
1238
584
1203
568
1174
554
1139
538
1106
522
MILD SEASON (First Stage)
Slow Response Sequence
COLD SEASON (Second Stage)
Rapid Response Sequence
Element 1 - Heat on instantly Element 1 - Heat on instantly
Blower on after 3 seconds delay Blower on after a 3 seconds delay
Elements 3 and 5 after 1 minute delay Elements 3 and 5 after 10 seconds delay
Element 2 after 2 minutes delay Element 2 after 20 seconds delay
Element 4 after 3-minute delay Element 4 after 30 seconds delay
NOTE: Elements 4 and 5 only where applicable.