BRANT RADIANT DX3 User Manual

DX3 Series
!
Insert Manual
For complete installation instructions, see the Tube Heater General Manual that accompanies this insert manual.
The DX3 Series Infrared Tube Heater is a positive pressure, single-stage radiant heater system. This insert manual is a supplement to the Tube Heater General Manual and provides specific information related to the DX3 Series model. All persons involved with the installation, operation and maintenance of the heater system must read and understand the information in this insert manual and the accompanying Tube Heater General Manual.
For Your Safety
If you smell gas:
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operation and maintenance instructions thoroughly before installing or servicing this equipment.
This heater must be installed and serviced by trained gas installation and service personnel only. Failure to comply could result in personal injury, asphyxiation, death, fire or property damage.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats, in a conspicuous location.
Not for residential use! Do not use this heater in the home, sleeping quarters, attached garages, etc. Installation of a commercial tube heater system in residential indoor spaces may result in property damage, serious injury, asphyxiation or death.
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
• Do not touch any electrical switch. • Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the fire department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
Model#: ___________________ Serial #: _________________________
(located on rating label)
Print: Rev.13012_5M-11/13_r1-5/14(CDS)
Replaces: LIODX3-1M-8/12(CDS)
LIODX3 - Rev.27512
DX3 Series
Contents
1.0 Safety...................................................................3
Safety Labels and Locations ............................................3
Clearance to Combustibles .............................................4
2.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Requirements ...................................................6
Electrical Requirements................................................6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Specifications ......................................................10
Tube Installation Sequence ............................................11
3.0 Operation ..............................................................12
Sequence of Operation ...............................................12
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operational Indicator Lights............................................13
4.0 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.0 Parts ..................................................................18
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Parts List ..........................................................18
Kit Contents Check List ...............................................20
Approvals..........................................................20
Limited Warranty ....................................................20
NOTE: See page 10 for a list of available models and specifications.
2
DX3 Series
- 120V HEATER INPUT -
Air Metering Orifice
DO NOT REMOVE
TP-114
TP-3014
3”
SAMPLE
1.0 Safety • Safety Labels and Locations
1.0 Safety
Read and understand all safety information and warnings in this insert manual and the Tube Heater General Manual before installation, operation and maintenance of the radiant tube heater system.
Safety Labels and Their Locations
Product safety signs or labels should be replaced by the product user when they no longer are legible. Contact either your local distributor or the product manufacturer for obtaining replacement signs or labels.
HOT
F/ N : LLV3EP1
F/ N : LLV3EP5
(Models with
24VAO Option)
120V
NEUTRAL
EARTH
HOT
NEUTRAL
120V
EARTH
- 120V HEATER INPUT -
F/N: LLAC Air Metering Orifice
Back Panel
F/ N : LLV3EP 6
Top Panel
2. Remove top cover (2 thumbscrews).
3. Remove tsix (6) 1/4” screws.
4. Lift and remove panel.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
F/N: LLTB018 (Natural Gas) F/N: LLTB019 ( LP Gas)
FAN COMPARTMENT
1. Disconnect gas & electricity.
SERVICE ACCESS PANEL
SERVICE ACCESS PANEL
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
4. Swing hinged panel downward.
3. Remove top cover.
2. Remove four (4) thumbscrews.
1. Disconnect gas & electricity.
CONTROLS & GAS VALVE COMPARTMENT
F/N: LLTCL001L/C/R
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
CAUTION: HOT SURFACE.
SERVICE ACCESS PANEL
cover upward and outward.
2. Remove cover by lifting top
1. Disconnect gas & electricity.
IGNITER & FLAME SENSE COMPARTMENT
Clearance to Combustibles Labels
F/N: LLLOGO1 Logo Label
3
1.0 Safety • Safety Labels and Locations • Clearance to Combustibles
!
AVOID EQUIPMENT FAILURE
THIS 10 FT. TUBE IS THE
COMBUSTION CHAMBER.
THIS TUBE MUST BE THE FIRST TUBE
FOLLOWING THE BURNER CONTROL BOX.
!
INSTALLER
The combustion chamber utilizes either 409 stainless, titanium alloy or aluminized steel -
depending on the model number of your heater.
Rotate the tube’s welded seam to bottom.
Consult the manual(s) for further details.
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
SERVICE ACCESS PANEL
F/N: LLTB026 F/N: LLTB024L
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Disconnect gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
RE-VERBER-RAY INFRA-RED RADIANT TUBE HEATER
®
FOR INDOOR (Non-Residential) INSTALLATION ONLY. Class IIIA Permanent Label
MODEL NO.
INPUT BTU/H
DET-40-125N(-3)
125,000 / 95,000
HL3 DX3
Volts AC:
Manifold Pressure:
120VAC - 60Hz
3.5 in.
AMPS - Starting:
Maximum Inlet Pressure:
1.7 14 in.
AMPS - Running:
Minimum Inlet Pressure:
1.1
5.0 in.
Combustion Chamber:
4” Black Coated Aluminized
DESIGN COMPLIES WITH:
ANSI Z83.20b-2004-GAS FIRED LOW INTENSITY INFRA-RED HTR.
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI (586) 756-0950 - www.drp-co.com
Inches W.C.P.
Inches W.C.P.
Inches W.C.P.
FOR USE WITH
Natural Gas
Heater Type
C1
Minimum Mounting Angle:
045DEGREES
Maximum Mounting Angle:
DEGREES
Serial No.: 1208XXXXXXXXXX 0001
Controls Compartment
SERVICE ACCESS PANEL
DX3 Series
HL-40-125N(-3)
DX
HL3-125
DX3
Production Code:
7.08
Version:
Data on this label is for the model shown on this label. If your heater has been converted, this information is not accurate. Please contact the factory for assistance.
BURNER COMPONENTS:
Gas Valve: Circuit Board: Wire Harness: N.O. Switch: N.O. VL Orifice: N.C. Switch: N.C. VL Orifice: Diff Switch: Diff VL Orifice: Igniter: Burner: 16” Tube: Ind. Lights:
HEATER
TYPE:
C1
For parts replacement information, contact factory at 586-756-0950 or visit www.drp-co.com/parts.
(Specify TP-#’s)
36G54-224-N 35-66 3 PCS Harness None None None None IS22010051F5166 Grey (+ / -) Norton
SAMPLE
Mid 4” Gen. Yellow - 24V
Orifice Type: Gas:
TP-204#
Air:
1 5/16”
TP-44#191 7/16”
840A 851B 3252 N/A
N/A
264E
50 201B 380 828
C1 C2 C3
19
Serial No.: 0804XXXXXXXXXX 0001
None
Stock:
Add-On:
N/A
On Circuit Board
Diag. Light:
None
Term. Block:
40 VA
Transformer:
Fasco Lg.
Fan:
50Hz - 120V
Alt. Fan:
When Specified
Alt. Fan Usage:
Picker x2
Relay:
None
Filter:
3 T-plug
24 Volt In:
6’ Blk. Cord
120 Volt In:
7/8” FC
Gas In:
None
Extra VL Orifice:
Internal Use Only:
Electric:
19
LLWT038
Tag:
1 5/16”
None
Special 1: Special 2:
N/A 826 55A 55B
1325 N/A 832 333 83
17 1 7/16”
Burner Control Box Component Label (located inside the center compartment lid)
RE-VERBER-RAY INFRA-RED RADIANT TUBE HEATER
®
FOR OUTDOOR USE AND INDOOR (Non-Residential) INSTALLATION ONLY. Class IIIA Permanent Label
MODEL NO.
HL-40-125N(-3)
DX
Volts AC:
120V - 60Hz
AMPS - Starting:
4.8
AMPS - Running:
1.1
Combustion Chamber:
4” Black Coated Aluminized
DESIGN COMPLIES WITH:
ANSI Z83.20b-2004-GAS FIRED LOW INTENSITY INFRA-RED HTR.
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI (586) 756-0950 - www.drp-co.com
INPUT BTU/H
125,000 / 95,000
Manifold Pressure:
3.5 in.
W.C.P.
Maximum Inlet Pressure:
14 in.
W.C.P.
Minimum Inlet Pressure:
5.0 in.
W.C.P.
SAMPLE
For stainless steel upgrades: The combustion tube is 409 Series stainless steel.
FOR USE WITH
Natural Gas
Heater Type
C1
Minimum Mounting Angle:
045DEGREES
Maximum Mounting Angle:
DEGREES
Serial No.: 0807XXXXXXXXXX 0001
Rating Plate
F/N: LLTB025R
Fan Compartment
F/N: LL01 - Clearance Safety Tag (Affix adjacent to heater’s thermostat)
Clearance to Combustibles
16” Burner Tube Combustion Chamber
F/N: LLTB004 (orange)
(150,000 - 200,000 Btu/h models only)
WARNING
Radiant Tube (s)
Clearance to combustibles is defined as the minimum distance that must exist between the tube surface, or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that must be maintained from moving objects around the tube heater. When installing the tube heater system, clearances to combustibles for the model tube heater and configuration must be maintained. Refer to Chart 1.1 to determine the required distances for your model.
Placement of explosive objects, flammable objects, liquids and vapors close to the heater may result in explosion, fire, property damage, serious injury or death. Do not store or use explosive objects, liquids or vapor in the vicinity of the heater.
4
DX3 Series
1.0 Safety • Clearance to Combustibles
Chart 1.1 • Clearance to Combustibles in Inches (see Figure 1.1 for Mounting Angles)
Mounting
Model Number
DX3 (20, 30, 40) - 50, 60 [N, P]
with 1 side shield with 2 side shields 9 9 6 47 20 ft. from burner 7 7 6 30
DX3 (20, 30, 40) - 75 [N, P]
with 1 side shield 29 8 6 60 with 2 side shields 9 9 6 60 20 ft. from burner
DX3 (30, 40, 50) - 100 [N, P]
with 1 side shield 29 8 6 66 with 2 side shields 16 16 6 66 20 ft. from burner 7 7 6 30
DX3 (30, 40, 50, 60) - 125 [N, P]
with 1 side shield 42 8 6 76 with 2 side shields 20 20 6 76 20 ft. from burner 7 7 6 30
DX3 (40, 50, 60) - 150 [N, P]
with 1 side shield 42 8 6 81 with 2 side shields 23 23 6 81 20 ft. from burner 11 11 6 44
DX3 (40, 50, 60, 70) - 175 [N, P]
with 1 side shield 50 8 6 92 with 2 side shields 30 30 6 92 20 ft. from burner 11 11 6 44
DX3 (50, 60, 70, 80) - 200 [N, P]
with 1 side shield 54 8 6 94 with 2 side shields 30 30 6 94 20 ft. from burner 11 11 6 44
Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
*
Angle*
9 9 6 47
45° 39 8 10 47
29 8 6 47
9 9 6 60
45° 39 8 10 60
7 7 6 30 0° 14 14 6 66
45° 39 8 10 66
20 20 6 76
45° 58 8 10 76
24 24 6 81
45° 58 8 10 81
34 34 6 92
45° 63 8 10 92
41 41 6 94
45° 63 8 10 94
The stated clearance to combustibles represents a surface temperature of 90
Side
Top BelowFront Behind
°
F (32°C) above room temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
Figure 1.1 Mounting Angles
0° Mounting Angle
Top
45° Mounting Angle
Top
0° Mounting Angle
with 1 Side Shield
(P/N: SSE)
Top
0° Mounting Angle
with 2 Side Shields
(P/N: SSE)
Top
Side
Below
Side
Front
Below
Behind
Front Behind
Below
5
Side Side
Below
2.0 Installation • Gas Requirements • Electrical Requirements
!
2.0 Installation
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury or death. Read and understand, the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. Only trained, qualified gas installation and service personnel may install or service this equipment.
Not for residential use! Do not use this heater in the home, sleeping quarters, attached garages, etc. Installation of a commercial tube heater system in residential indoor
spaces may result in property damage, serious injury or death.
Instructions for the following are detailed in the Tube Heater General Manual:
• Design considerations
• Hanger suspension and placement
• Tube layout and assembly
• Burner control box suspension
• Reflectors (and accessories)
• Venting and combustion air intake
• Gas requirements
• Baffle assembly
DX3 Series
Note: Electronic versions of all manuals are available at www.detroitradiant.com
Gas Requirements
Type of Gas
Natural 3.5 Inches W.C. 5.0 Inches W.C. 14.0 Inches W.C.
Liquefied Petroleum 10.0 Inches W.C. 11. 0 Inches W.C. 14.0 Inches W.C.
IMPORTANT: Consult the Tube Heater General Manual for gas connection requirements.
Required Manifold
Pressure
Minimum Inlet
Pressure
Maximum Inlet
Pressure
Electrical Requirements
• 120VAC - 60 Hz GRD, 3-wire.
• 120VAC thermostat connection.
• Starting current 4.8 amps
• Running current 1.1 amps
NOTICE
The DX3 Series comes standard requiring a 120VAC thermostat connection. An optional 24VAC internal relay (24VAO) may be factory installed if the heater is to be controlled via a 24VAC thermostat. A 40VA transformer is necessary when using the 24VAO option.
NOTE: A relay transformer may be used in lieu of the factory installed 24VAO option.
6