273 Branchport Avenue
Long Branch, NJ 07740 Thank you for using our products.
(800) 631-2148 (USA)
(800) 397-5777 (CANADA) INSTALLATION INSTRUCTIONS
www.wheelockinc.com MULTITONE STROBE WEATHERPROOF APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
The Multitone Strobe Weatherproof Appliances are UL Listed under Standard 1638 (Visual Signaling Appliances) for indoor/outdoor use, Fire Protective Service and
UL Standard 464 for Audible Signal Appliances. The MTWP Appliance is ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling and under Standard
CAN/ULC-S525-99 for Audible Signal Devices for Fire Alarm Systems. An outdoor backbox is required for outdoor installation. The Multitone Strobe Appliances use
a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling.
Multitone Strobe Appliances can be field set to produce any one of eight commonly used alarm tones. Sound output can be field set to provide either HIGH (HI) dBA
or STANDARD (STD) dBA sound output level.
All Multitone Strobe models are designed for use with either filtered DC or unfiltered full-wave-rectified (FWR) input voltage. The Multitone Strobe Appliances have
separate input terminals for alarm tone activation and strobe activation. Shunt wires are provided to operate both the alarm tone and the strobe simultaneously on a
single input circuit (See Wiring Diagram). All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a fire alarm control
panel (FACP).
NOTE: All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems, CAN/ULC-S524-01 and the
Canadian Electrical Code, Part 1. Final acceptance is subject to authorities having jurisdiction (AHJ).
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
1. Strobes will produce 1 flash per second over the "Regulated Voltage" range.
2. All models are UL and ULC Listed for indoor and outdoor use with a temperature range of UL -31°F to +150°F (-35°C to +66°C) ULC -40°F
to +150°F (-40°C to +66°C) and maximum humidity of 93% ±2% RH.
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS AND 8.0-
17.5 VOLTS FOR 12V MODELS USING FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE
OUTSIDE OF THIS RANGE.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE
VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM
WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as
“Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
Use Tables 2, 2A, and 2B to determine the highest value of “Rated Current” for an individual Multitone Strobe (across the expected operating voltage range of the
Multitone Strobe). Add strobe current from Table 2B audible appliance current from Table 2 and 2A to obtain total current for each unit, if the strobe and audible are
wired to operate in unison on a single circuit. Be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source
and include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
WARNING: MAKE SURE THAT THE TOTAL RATED CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE
SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER
SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS
TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS
Copyright 2005 Wheelock, Inc. All rights reserved. P84150 H
Sheet 1 of 6
Page 2
OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Table 2: UL Current Ratings for Multitone only (AMPS)
Tone Tone
Description 16-33VDC 16-33VRMS
HI
Horn Broadband Horn (Continuous) 0.084 0.038 0.087 0.045
Bell 1560 Hz Modulated (0.07 Sec. ON/Repeat) 0.053 0.024 0.051 0.028
March Time Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat) 0.062 0.027 0.087 0.045
Code 3 Horn Horn (ANSI S3.41 Temporal Pattern) 0.051 0.027 0.087 0.045
Code 3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 0.052 0.025 0.056 0.029
Slow Whoop 500-1200Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat) 0.098 0.035 0.092 0.042
Siren 600-1200Hz Sweep (1.0 Sec. ON/Repeat) 0.088 0.036 0.092 0.040
HI/LO 1000/800 Hz (0.25 Sec. ON/Alternate) 0.057 0.025 0.058 0.032
Table 2A: ULC Current Ratings for 24VDC Multitone only (AMPS)
Tone
Horn
Bell
March Time
Code 3 Horn
Code 3 Tone
Slow Whoop
Siren
HI/LO
AUDIBILITY RATINGS:
Tone
Horn
Bell
March Time
Code 3 Horn
Code 3 Tone
Slow Whoop
Siren
HI/LO
ULC Directional Characteristics:
At a voltage range of 20.0-31.0VDC. -3 dBA: 48 degrees left, 41 degrees right -6 dBA: 50 degrees left, 58 degrees right.
HI/LO
Volume
HI 89 92 94 97 99 100
STD 84 87 90 91 93 94
HI 83 86 88 90 92 93
STD 76 80 83 85 87 88
HI 86 89 91 97 99 100
STD 80 84 87 91 93 94
HI 85 88 90 97 99 100
STD 79 83 86 91 93 94
HI 81 85 86 93 95 96
STD 76 80 82 88 90 91
HI 87 90 92 97 99 100
STD 81 85 87 92 94 95
HI 86 89 92 96 98 99
STD 81 84 87 91 93 94
HI 83 86 89 91 93 94
STD 77 81 84 86 88 89
HI/LO
Volume
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.013 0.014 0.018
STD 0.011 0.012 0.015
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.025 0.028 0.035
STD 0.015 0.017 0.021
HI 0.043 0.048 0.060
STD 0.023 0.026 0.033
HI 0.032 0.036 0.045
STD 0.021 0.023 0.029
HI 0.018 0.020 0.025
STD 0.013 0.014 0.018
Table 2B: Current Ratings for Strobe only (AMPS)
Voltage 75cd
DC 16-33VDC 0.138
FWR 16-33VRMS 0.222
UL 24VDC dBA Reverberant Ratings
Per UL 464 at 10 Feet
16V 24V 33V 20V 24V 31V
20VDC 24VDC 31VDC
Maximum RMS Current
Table 3: dBA Ratings
DC
Maximum RMS Current
(AMPS)
dBA
ULC 24VDC dBA Anechoic Ratings
Per CAN/ULC S525-99 at 10 Feet
STD
dBA
HI
dBA
STD
dBA
P84150 H
Sheet 2 of 6
Page 3
WARNING: THE MULTITONE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM
TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR POSITION
SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY
DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CAUTION: If Multitone Strobe appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that exceeds the maximum 120 dBA permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person's hearing.
LIGHT DISTRIBUTION:
A7
Table 4: Candela at Various Angles Per UL 1638
Model Rated Candela
UL ULC A1 A2 A3 A4 A5 A6/A7
A4
A2
A1
A6
A5
A3
MTWP-2475W 75.0cd 180.0cd 180 16 16 15 15 8
MTWP-2475C 75.0cd 180.0cd 180 16 16 15 15 8
MULTITONE SETTINGS:
The Switch (SW1) of the Multitone Appliance, shown in Figure 1, is used to set the dBA sound output level and alarm tone. The factory settings are shown below.
Read these instructions carefully before changing any of these factory settings.
Figure 1:
PC Board Layout Showing Location
Switch (SW1)
SLIDE HERE FOR (0)
SLIDE HERE FOR (1)
ON
234
1
STB
-
+
+
SW1
-
AUD
The factory settings for 24VDC models are:
ON
432
1
SW1
HIGH dBA SW1 POS 1 set on 1
HORN TONE SW1 POS 2, 3, 4 set on 1, 1, 1
STEP 1:
Set desired dBA sound output level as follows (Refer to Figure 2):
Multitone Strobe Appliances cannot be field set for input voltage. Multitone Strobe Appliances are field set for dBA sound output level by adjusting a four position
Switch (SW1) as shown in Table 5 and Figure 2. Use SW1 Position 1 to select the dBA sound output level.
Table 5: dBA Sound Output Level Settings
Input Voltage and Decibel Level SW1 Settings
24 VDC/HIGH dBA: Set SW1 POS 1 on 1 (Factory Setting)
24 VDC/STD dBA: Set SW1 POS 1 on 0
Figure 2: Switch Settings
SLIDE HERE FOR (1)
SLIDE HERE FOR (0)
POS 1
POS 2
POS 3
POS 4
USE A SMALL SCREWDRIVER TO
CHANGE THE SWITCH POSITION.
WARNING: DOUBLE CHECK THE SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT. IMPROPER SETTINGS CAN
DAMAGE THE UNIT OR RESULT IN NO SOUND OUTPUT OR A dBA SOUND OUTPUT LEVEL THAT IS BELOW THE 75dB MINIMUM CODE
REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION. THIS COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
STEP 2:
Set desired alarm tone as follows (refer to Figure 2 and Table 6).
P84150 H
Sheet 3 of 6
Page 4
Multitone Strobe Appliances are field set for any one of eight alarm tones by setting a four-position switch (SW1) as shown in Figure 2 and Table 6. Use SW1 POS 2,
3, 4 to select the desired alarm tone.
Table 6: Switch Settings
Tone POS 2 POS 3 POS 4
Horn 1 1 1
Bell 1 0 1
March Time Horn 0 0 1
Code 3 Horn 1 1 0
Code 3 Tone 0 1 1
Slow Whoop 0 1 0
Siren 1 0 0
HI/LO 0 0 0
NOTE: The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation
signaling. They should be used only for fire evacuation signaling and not for any other purpose.
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently. All other
tones are recommended for use only on continuous (non-coded)
CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WIRING DIAGRAMS:
Figure 3:
1. Multitone Strobe models have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at
each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in Figure 3. The
polarity shown in the wiring diagrams is for operation of the appliances. The polarity is reversed by the FACP during
supervision.
Figure 4:
Audible appliance and strobe operate independently.
FROM PRECEDING
AUDIBLE OR FIRE ALARM
CONTROL PANEL (FACP)
FROM PRECEDING
APPLIANCE OR FIRE ALARM
CONTROL PANEL (FACP)
+
-
+
-
-+
+
STROBE
AUDIBLE
-
+
-
+
-
TO NEXT
AUDIBLE OR
END OF LINE RESISTOR
(EOLR)
TO NEXT
STROBE OR
EOLR
Figure 5:
Audible appliance and strobe operate in unison.
MOUNTING OPTIONS:
FROM PRECEDING
APPLIANCE OR
FIRE ALARM CONTROL
PANEL (FACP)
Red and black shunt-wires are supplied.
+
-
(+)
STROBE
(-)
RED
BLACK
GND.
(+)
(-)
AUDIBLE
TO NEXT
+
APPLIANCE OR
END OF LINE
-
RESISTOR (EOLR)
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these
limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown
and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.
P84150 H
Sheet 4 of 6
Page 5
Figure A
FLUSH (4" BOX)
4" SQ. X 2-1/8"
DEEP BACKBOX
#8-32 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8488
Figure B
FLUSH (2-GANG BOX)
2-GANG x 3-1/2"
DEEP BACKBOX
#6-32 SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8888
SCREW COVERS
Figure C
SURFACE MOUNTING
INDOOR/OUTDOOR
BACKBOX (IOB)
WOOD
SCREWS
#8-18 SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8888
SCREW COVERS
Figure D
CONCEALED CONDUIT MOUNTING
INDOOR/OUTDOOR
BACKBOX (IOB)
#8-18 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8888
MOUNTING PROCEDURES:
EXISTING
BOX
Figure E
RETROFIT PLATE MOUNTING
EXISTING FSB
BOX
#8-32 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8888
RETROFIT
PLATE
Figure F
SURFACE OR SEMI-FLUSH (4" X 2-1/8" BOX)
DBB OR 4" SQ. X 2-1/8"
ISP EXTENDER
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #1 6 AWG #14 AWG #12
DEEP BACKBOX
#8-32 SCREWS
SCREW COVERS
8888
Figure G
SURFACE OR SEMI-FLUSH (4" X 1-1/2" BOX)
DBB OR 4" SQ. X 1-1/2"
ISP EXTENDER
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
DEEP BACKBOX
#8-32 SCREWS
SCREW COVERS
8488
1. The MT can be flush mounted to a 100mm backbox (Fig. A) or double-gang backbox (Fig. B). It can also be surface mounted to a indoor/outdoor backbox (Figs.
C & D). It can also be used with a retrofit plate (Fig. E) or with an ISP extender (Figs. F & G). Mounting hardware for each mounting option is supplied.
2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. Do not pass additional wires (used for other
than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance.
3. The knock-out opening on the outdoor backbox is sized for a ½” conduit and matching connector. Be sure that a proper watertight conduit fitting is used to
connect the backbox for outdoor/severe environment applications.
4. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the appliance.
5. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
6. Connect field wires to the MT terminal block (polarity must be observed). Bend the field wires up 90° at the connection to the terminal block.
7. Carefully push the field wires into the backbox by hand. Press the MT to the backbox, verifying that it is seated and aligned correctly.
8. Fasten the MT to the backbox using the screws supplied.
WARNING: THIS UNIT MUST BE MOUNTED ON A FLAT SURFACE, SO THAT THE SURFACE COVERS THE ENTIRE BACK SURFACE OF
THE BACKBOX. WHEN USED IN AN OUTDOOR APPLICATION OR A NEMA 3R APPLICATION, USE WEATHER PROOF RATED CONDUIT
FITTING ON ALL KNOCKOUTS OF THE BACKBOX.
WARNING: THE MTWP STROBE APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT”.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING
OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE
AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER
CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK
STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE
INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS,
STANDARDS, REGULATIONS, CODES AND GUIDELINES.
NOTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area.
These appliances can produce a distinctive three pulse Temporal Pattern Fire Alarm Evacuation Signal for total evacuation in accordance with NFPA 72.
P84150 H
Sheet 5 of 6
Page 6
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or
locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require
special precautions to assure immunity from electrical noise (e.g. audio crosstalk).
The Multitone Strobe products and these instructions are copyrighted by Wheelock and the Multitone Strobe products contain proprietary, confidential and trade secrets
of Wheelock. No part of the Multitone Strobe products and these instructions may be photocopied, printed or reproduced in any form or modified, adapted, changed or
enhanced, or converted to another programming language, or used to create updated, related or derivative works, without the prior written consent of Wheelock. No
part of the Multitone Strobe products shall be decompiled, disassembled or reverse engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE
PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE
PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL
NOT HAVE ANY LIABILITY FOR SUCH USE.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the
receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help.
IMPORTANT: READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE PLACEMENT, LIMITATIONS,
INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES.
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally
tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes,
regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in
accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National
Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire
standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having
jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted
against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or
replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY
SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE
FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A
PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS
TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL
ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER
SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE
OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF
PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK
SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE
USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR
OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON
EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED
IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE
WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL
CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE
RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE,
REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART
THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE
INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY
CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING
IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES
DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT
APPLY TO ALL PURCHASERS.
11/05
Limited Warranty
Limitation of Liability
P84150 H
Sheet 6 of 6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.