Bosch LM024, LM048, LM036, LM060, LM070 Installation, Operation And Maintenance Manual

LM AH Series Heat Pump
LM024 | LM036 | LM048 | LMO60 | LM070
Installation, Operation and Maintenance Manual
8 733 920 847 (2014/01)
2 | LM Series Heat Pump AH
CONTENTS
Key to Symbols.................................................................. 3
Safety Warnings ................................................................ 3
LM AH Standard Package ................................................... 4
INITIAL INSPECTION .......................................................... 4
GENERAL DESCRIPTION .................................................... 4
MOVING AND STORAGE ..................................................... 4
SAFETY CONSIDERATIONS................................................. 4
LOCATION......................................................................... 5
Air Handler ................................................................. 5
Condensing Section ..................................................... 5
INSTALLATION .................................................................. 5
Air Handler ................................................................. 5
CONDENSATE DRAIN ......................................................... 6
DUCT SYSTEM ................................................................... 6
ELECTRICAL ...................................................................... 7
Electronic Thermostat Installation .................................. 7
Thermostat Connections............................................... 8
OPTIONS......................................................................... 11
Electric Heat ............................................................. 11
Installation Of pressure .............................................. 11
Regulating Valves....................................................... 11
SEQUENCE OF OPERATION .............................................. 11
Cooling Mode............................................................ 11
Heating Mode ........................................................... 12
WELL WATER SYSTEMS ................................................... 13
COOLING TOWER/BOILER SYSTEMS ................................ 13
EARTH COUPLED SYSTEMS ............................................. 16
SYSTEM CHECKOUT ........................................................ 17
UNIT START-UP ............................................................... 17
MAINTENANCE................................................................ 17
TROUBLESHOOTING ........................................................ 18
Unit Lockouts............................................................ 19
WIRING DIAGRAMS ......................................................... 24
DIMENSIONAL DRAWINGS ............................................... 26
Notes.............................................................................. 28
LM Series Heat Pump AH8 733 920 847 (2014/01) Subject to change without prior notice
LM AH MODEL NOMENCLATURE
LM 024 - 1 AV X - X L T A
SERIES
FAN MOTOR OPTIONS
LM A - Constant Airflow ECM
SIZE DISCHARGE AIR CONFIGURATION
024 T - Top (AV only) 036 048 E - End (AH only) 060 070
RETURN AIR CONFIGURATION
L - Left
VOLTAGE DESIGNATIONS
R - Right
1
- 208/1/60 & 230/1/60
X - None
CABINET CONFIGURATION Not used on Air Handlers
AH - Air Handler Horizontal AV - Air Handler Vertical
Revision Level A
CS/AH Pairing | 3LM Series Heat Pump
S - Straight (AH only)
CS/AH PAIRING
UNIT MODEL
Unit 1 Unit 2
LM024-1CSC LM036-1CSC LM048-1CSC LM060-1CSC LM070-1CSC
LM024-1AVX LM036-1AVX LM048-1AVX LM060-1AVX LM070-1AVX
KEY TO SYMBOLS
Warnings
Warnings in this document are identified by
Paired Air Handler
LM024-1AHX LM036-1AHX LM048-1AHX LM060-1AHX LM070-1AHX
SAFETY WARNINGS
Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could
cause personal injury or death.
Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.
a warning triangle printed against a grey background. Keywords at the start of the warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in
damage to property or equipment.
CAUTION indicates a situation that could
result in minor to medium injury.
WARNING indicates a situation that could
result in sever injury or death.
DANGER indicates a situation that will result in
severe injury or death.
Important Information
This symbol indicates important information where there is no risk to property or people.
refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area.
8 733 920 847 (2014/01)Revised 01-14
4 | LM AH Standard Package LM Series Heat Pump AH
1
2
To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. Doing so may affect the unit’s warranty. The mechanical components and filters will quickly become clogged with construction dirt and debris, which may cause system damage.
LM AH STANDARD PACKAGE
Figure # 1
[1] LM Series Water-to-Air Heat Pump: Air Handler [2] Installation and Operation Manual
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember that the purchaser is responsible for filing the necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
In the cooling mode, the air coil in the air handler section serves as an evaporator and the water-to­refrigerant heat exchanger serves as a condenser. In the heating mode, their roles are reversed. The refrigerant lines connecting the two sections consist of one line carrying liquid refrigerant and another carrying refrigerant vapor. The liquid carrying line will be referred to as the liquid line while the vapor carrying line will be referred to as the suction line.
The LM Split AH Water-to-Air Heat Pump units are performance certified to American Heating and Refrigeration Institute (AHRI) ISO Standard 13256-
1. All LM Water-to-Air Heat Pumps conform to UL1995 standard and are certified to CAN/CSA C22.1 No 236 by Intertek-ETL.
NOTE: This product should not be used for temporarily heating/cooling during construction. Doing so may effect the units warranty.
Several factory installed options are available: Electric Heat, Air proving sensor and MERV 8&13
filters.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area. Units must only be sto r ed or m o v ed in t h e normal upright position as indicated by the "UP" arrows on each carton at all times.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment. Untrained personnel can perform basic functions of maintenance such as cleaning coils and replacing filters.
GENERAL DESCRIPTION
The LM Split System Water-to-Air Heat Pumps provide the best combination of performance and efficiency available. Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained.
Split system heat pumps consist of two independently installed sections allowing for centralized air distribution while remotely locating the section containing the compressor and water­to-refrigerant heat exchanger.
WARNING: Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.
When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area.
LM Series Heat Pump AH8 733 920 847 (2014/01) Subject to change without prior notice
LOCATION | 5LM Series Heat Pump
AH
CS
LOCATION
To maximize system performance, efficiency and reliability, and to minimize installation costs, it is always best to keep the refrigerant lines as short as possible. Every effort should be made to locate the air handler and the condensing section as close as possible to each other.
Figure # 2
Air Handler
Locate the air handler unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make electrical and duct connections. If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter the space. On horizontal units, allow adequate room below the unit for a condensate drain trap.
The air handler units are not approved for
outdoor installation; therefore, they must be installed inside the structure being conditioned. Do not locate in areas that are subject to freezing.
INSTALLATION
Remove all shipping blocks from the inside and/or putside of the air handler section prior to final installation.
NOTE: The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In lieu of local codes, the equipment should be installed in accordance with the recommendations made by the National electric code, and in accordance with the recommendations made by the National Board of Fire Underwriters.
Air Handler
The air handler section may be installed on any level surface strong enough to support its weight. When installed in a closet or on a base stand, it should be mounted on a vibration absorbing pad slightly larger than the base to minimize vibration transmission to the building structure.
When installed in an attic or above a drop ceiling, the installation must conform to all local codes. When installed in the horizontal position (supply air at the end or side of the unit), the unit should be supported on all four corners with threaded rods attached to the building ceiling rafters and utilizing the hanger kits (Figure #3). Refer to the hanging bracket assembly and installation instructions for details.
Condensing Section
Locate the condensing section in an area that provides sufficient room to make water and electrical connections, and allows easy removal of the access panels, for service personnel to perform maintenance or repair.
Reference the Condensing Section section of this manual for detailed installation and operation.
Figure # 3
Some applications require an attic floor installation of the air handling unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling.
8 733 920 847 (2014/01)Revised 01-14
6 | CONDENSATE DRAIN LM Series Heat Pump AH
Vibration Pad is recommended
The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4" drain connected to this secondary pan should be run to an eave at a location that will be noticeable.(See Figure #4)
If the air handler is located in a crawl space, the bottom of the unit must be at least 4" above grade to prevent flooding of the electrical parts due to heavy rains.
Figure # 4
CONDENSATE DRAIN
The air handler should be pitched approximately 1/ 4" towards the drain in both directions, to facilitate condensate removal. A drain line must be connected to the air handler and pitched away from the unit a minimum of 1/8" per foot to allow the condensate to flow away from the unit. This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to insure free condensate flow. A vertical air vent is sometimes required to avoid air pockets. (See Figure #5).
The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
The air handler should be pitched approximately 1/ 4" towards the drain in both directions, to facilitate condensate removal. (See Figure #6)
Figure # 6
DUCT SYSTEM
A supply air outlet collar and return air duct flange are provided on all units to facilitate duct connections.
A flexible connector is recommended for supply and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of one inch duct insulation to avoid heat loss or gain and prevent condensate forming during the cooling operation. Application of the unit to uninsulated duct work is not recommended as the unit’s performance will be adversely affected.
The factory provided air filter must be removed when using a filter back return air grill.The factory filter should be left in place on a free return system.
If the unit will be installed in a new installation which includes new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit is to be connected to existing ductwork, a check should be made to assure that the duct system has the capacity to handle the air required for the unit application. If the duct system is too small, larger ductwork should be installed. Check for existing leaks and repair.
CAUTION: Do not connect discharge ducts directly to the blower outlet.
Figure # 5
Units are not internally trapped.
The duct system and all diffusers should be sized to handle the designed air flow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. The re s h o u l d b e n o d i r e c t straight air path thru the return air grille into the heat pump.
LM Series Heat Pump AH8 733 920 847 (2014/01) Subject to change without prior notice
ELECTRICAL | 7LM Series Heat Pump
THERMOSTAT
PACKAGED HEAT PUMP
Y1
G
C
O
R
Y1
G
B
R
W2
C
O
E
B
W1
W2
Y2
Y2
The return air inlet to the heat pump must have at least one 90 degree turn away from the space return air grille. If air noise or excessive air flow are a problem, the blower speed can be changed to a lower speed to reduce air flow. (Refer to ECM motor interface board section in this manual and Figure #8)
ELECTRICAL
Field wiring must comply with local and national electric codes. Power to the unit must be within the operating voltage range indicated on the unit nameplate or on the performance data sheet. .
CAUTION: Operation of unit on improper line voltage or with excessive phase imbalance will be hazardous to the unit, constitutes abuse and may void the warranty.
Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See unit nameplate for maximum fuse or breaker size.
ECM Interface Board
Figure # 8
Electronic Thermostat Installation
Position the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the wall. Thermostat wire must be 8-conductor, 18-AWG wire. Strip the wires back 1/4-inch (longer strip lengths may cause shorts) and insert the thermostat wires into the connector as shown. Tighten the screws to ensure secure connections. The thermostat has the same type connectors, requiring the same wiring. See instructions in the thermostat for detailed installation and operation information.
Figure # 7 Electrical Component Box Layout
The unit is provided with a concentric knock-out in the front left corner post for attaching common trade sizes of conduit, route power supply wiring through this opening. Always connect the ground lead to the grounding lug provided in the control box and power leads to the power supply terminal block as indicated on the wiring diagram and Figure #7.
When using a 2-cool, 3-heat thermostat both the W1 & W2 on the Heat Pump and W2 & EM on the thermostat must be connected together via a jumper. (See Figure#9)
Figure # 9
8 733 920 847 (2014/01)Revised 01-14
8 | LM Series Heat Pump AH
Packaged heat pumps are equipped with detachable Thermostat connectors. These connectors are located in different locations based on the blower motor that is installed in the unit.
For the EON motor, the three detachable thermostat connectors are located on the ECM Interface board. See Wiring Harness Drawing on Pg#24.
Harness wiring can be loose, based on the options installed for the unit. See the Wiring Harness Drawing notes for further details.
Figure 10: Low Voltage Connection Points
Function
24 VAC Common C CC C 24 VAC Power R R R R Fan Operation G G- - Reversing Valve (3) O O O O Compressor 1st Stage Y1 Y1 Y1 Y1 Compressor 2nd Stage Y2 Y2 Y2 Y2 Condensate Sensor (1) - -CS CS Alarm Output (From UPM) L /ALR Splice ALR (UPM) Auxiliary Electric Heat (4) W/W1/W2 W1 - - Emergency Heat (4) W2/E W2 - -
From
Thermostat
Table Notes:
1)If the condensate overflow sensor option is
utilized connect ‘CS’ at the condensing section to
To Air
Handler
From Air
Handler
To Condensing Section
The thermostat connections and their functions are as follows:
Y2 Second Stage Compressor Operation
‘CS’ at the air handler. Be sure to ground power supply.
2)If service LED is utilized connect ‘ALR’ terminal
Y1 First Stage Compressor Operation
GFan
on the UPM board to ‘L’ on the thermostat sub base. The wiring may be spliced in the air handling unit. The ‘ALR’ output is hot (R) so check thermostat instruction manual to ensure compatibility.
3)‘O’ – reversing valve is energized in the cooling mode. Fail safe is to heating.
4)Utilized when electric strip heater package
O Reversing Valve (energized in cooling)
W1
EM/W2 Emergency Heat (electric heat only)
NC
Auxiliary Electric Heat (runs in conjunction with compressor)
Transformer 24 VAC Common (extra connection)
present.
Thermostat Connections
C1
Transformer 24 VAC Common (primary connection)
Thermostat wiring is connected to the 10 pin screw type terminal block on the lower center portion of the ECM Interface Board. In addition to
R Transformer 24 VAC Hot
HUM Dehumidification Mode
providing a connecting point for thermostat wiring, the interface board also translates thermostat inputs into control commands for the variable speed programmable ECM DC fan motor and displays an LED indication of operating status.
LM Series Heat Pump AH8 733 920 847 (2014/01) Subject to change without prior notice
| 9LM Series Heat Pump
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit alarm output.
If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made.
If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board.
On the above series units the thermostat wiring connections are made at the air handling section.
This will allow the capability to utilize both the condensate overflow switch and the alarm output options if ordered.
FHP recommends the use of 18 gauge 7 wire solid copper thermostat conductive cable to wire from the condensing section terminal strip to the air handler terminal strip. Typical wiring diagrams are shown for both the air handler and the condensing sections.
Just above the connector block is a single red LED labeled CFM that will blink intermittently when the unit is running and may flicker when the unit is off. This LED indicates the air delivery of the blower at any given time. Each blink of the LED represent 100 CFM of air delivery so if the LED blinks 12 times, pauses, blinks 12 times, etc. the blower is delivering 1200 CFM. Refer to Figure #11 for factory programmed air delivery settings for the LM Series.
To the right of the thermostat connection block is a green LED labeled dehumidify. This feature is not utilized on the LM Series.
Connection point logic is as follows: To the left of the thermostat connection block are
a row of 2 red and 4 green LED’s. These LED’s indicate the operating status of the unit. They are labeled as follows:
EM
W1
RED
RED
O GREEN
Y2
Y1
G
GREEN
GREEN
GREEN
Emergency Heat On
Auxiliary Heat On
Reversing Valve Energized, unit is in cooling mode
Second Stage Compressor On
First Stage Compressor On
Fan On
8 733 920 847 (2014/01)Revised 01-14
10 | LM Series Heat Pump AH
Figure 11: Motor Profile Air-Flow Table CFM
MODEL
LM024
LM036
LM048
LM060
LM070
FAN
ONLY
450
700
900 925 1500 1500 1500 1700 1275 B
1200 1500 2000 2000 2000 2300 1700 A
1600
Y1
COOL/
HEAT
500 800 800 800 900 700 A
1050 1225 1225 1225 1400 1050 A
1600 2200 2200 2200 2300 1900 A
Y2
COOL/
HEAT
AUX
HEAT
Just above and to the right of the thermostat connection block are DIP Switches labeled ADJ, DELAY, HEAT and COOL. The ADJ set of pins are labeled NORM, (+), (-) and TEST. LM units will all be set on the NORM position from the factory, however, airflow can be increased (+) or decreased (-) by 15% from the pre-programmed setting by relocating the jumper in this section.
The TEST position is used to verify proper motor operation. If a motor problem is suspected, move the ADJ jumper to the TEST position and energize G on the thermostat connection block.
If the motor ramps up to 100% power, then the motor itself is functioning normally. Always remember to replace the jumper to NORM, (+) or (­) after testing and reset the unit thermostat to restore normal operation.
NOTE: Do not set the ADJ jumper to the (-) setting when electric heaters are installed. Doing so may cause the heaters to cycle on their thermal overload switches, potentially shortening the life of the switches.
EMERG
HEAT
PLUS
ADJ
MINUS
ADJ
TAP COOL/
HEAT/DELAY
The other three sets of jumper pins are used to select the proper program in the ECM motor for the unit. Refer to Figure #11 for the proper jumper placement.
NOTE: Always disconnect power before changing jumper positions on the interface board and reset the unit afterward.
To the left of the red and green status LED’s is a row of 1/4” male quick connects. These are used to pass thermostat inputs on to the rest of the control circuit. Remember to always turn off unit power at the circuit breaker before attaching or disconnecting any wiring from these connections to avoid accidental short circuits that can damage unit control components.
LM Series Heat Pump AH8 733 920 847 (2014/01) Subject to change without prior notice
OPTIONS
OPTIONS | 11LM Series Heat Pump
Electric Heat
Internally mounted supplemental electric heat is available on select models of the LM series. Electric heating elements can operate along with
In cases where Electric Heat is not available in a desired configuration but is needed, contact your distributor for available Duct Mounted Electric Heat Package.
reverse cycle heating as auxiliary heat or in lieu of mechanical heating (refrigeration heating) as emergency backup heat.
Units with internal electric heat must have 2 field power supplies.
Availability matrix, including available nominal kW capacities is shown in Figure #12:
Internal mounted Electric Heat is only available on top blow vertical cabinets, end blow horizontal cabinet or on down blow counterflow cabinets.
Figure 12: Heater Kit Compatibility Table
KW Btu/h Product Series Compatibility
Heater Model
208V 230V 208V 230V LM024 LM036 LM048 LM060 LM070
HK/HP050-1201 3.6 4.8 12300 16300 x xxxx
HK/HP100-1201 7.2 9.6 24600 32700 x xxxx
HK/HP150-1201 10.8 14.4 36900 49100 xxxx
HK/HP200-1201 14.4 19.2 49200 63400 x xx
Note: x = available
INSTALLATION OF PRESSURE
REGULATING VALVES
Pressure regulating valves are used to increase or decrease water flow through the heat pump in response to refrigerant pressure. In some cases more water may be required in heating than in cooling, or vice versa. With the Envirosaver heat pumps these valves are not required. However, if installed, a pair of valves are required for proper operation, one valve for cooling (direct acting) and another valve for heating (indirect acting). A refrigerant tap is provided in the refrigerant line located between the reversing valve and the water­to-refrigerant heat exchanger for proper monitoring of the refrigerant pressures.
The discharge water from the heat pump is not contaminated in any manner and can be disposed of in various ways depending on local building codes (i.e. discharge well, dry well, storm sewer, drain field, stream or pond, etc.) Most local codes forbid the use of a sanitary sewer for disposal. Consult your local building and zoning department
SEQUENCE OF OPERATION
(Figure #13 Wire Schematic)
Cooling Mode
Energizing the “O” terminal energizes the unit reversing valve in the cooling mode. The fan motor starts when the “G” terminal is energized. Note that the fan motor will take 30 seconds to ramp up to operating speed and will run at fan only air flow as long as there is no call for compressor or heater operation.
When “Y1” in the unit (“Y” on the thermostat) is energized the compressor starts and the unit is now cooling. Solenoid valves or loop pumps are brought on in conjunction with the compressor.
When the thermostat is satisfied, the compressor shuts down and the fan ramps down. If the “G” terminal is still energized (fan operation is on “continuous” at the thermostat) the fan will ramp down to fan only air flow in 30 seconds. If the “G” terminal is de-energized with “Y1” then the fan ramps down to off in 30 seconds.
to insure compliance in your area.
8 733 920 847 (2014/01)Revised 01-14
Loading...
+ 23 hidden pages