Bosch IUI-UEZ-BE1000s Operating Manual

IUI-UEZ-BE1000s Intrusion Keypad
Manuel d'utilisation
IUI-UEZ-BE1000s Intrusion
FR
Gebruiksaanwijzing
IUI-UEZ-BE1000s Inbraakdetectie
NL
Operating manual
IUI-UEZ-BE1000s Intrusion
Bedienungsanleitung
IUI-UEZ-BE1000s Notruf
EN
DE
- 2 -
Introduction and safety instructions..............3
Display/control elements
Explanation of message display ........................4
Explanation of keys............................................5
Message display/processing ..........................6
Querying statuses
Querying areas and triggering statuses.............7
Querying internal program statuses...................8
Time-controlled activation
Time-controlled arming ......................................9
Time-controlled disarming................................10
Code mode
Starting and ending code mode.......................11
Starting and ending code mode with
messages present............................................12
Operation in the menu
Calling up and ending functions.......................13
Switching internal programs on and off............14
Resetting the control panel..............................15
Resetting internal messages............................15
Display test ......................................................16
Querying areas and ignoring
detector zones and faults.................................17
Isolating detector zones...................................18
Isolating a detector in a detector zone.............19
Walktest...........................................................20
Notes ..............................................................21
Table of Contents
- 3 -
Introduction to operation
The remote keypad can only be operated by trained personnel.
For safety reasons and to prevent faulty op­eration, the authorization code for operating the system should only be provided to these people.
Under certain conditions, the keypad is inac­tive, i.e. inoperable
Detection area is armed. The keypad has
been allocated to the armed detection area.
Detection area is armed. The keypad has
been programmed to "dark when armed".
Holdup alarm in the system. The keypad
has been programmed to "dark if holdup".
What will this operating manual tell you
This manual contains all information required for interpreting the message display and op­erating the keypad.
What this operating manual will not tell you
The operating manual does do not provide any information regarding general or special­ized technical/safety knowledge.
Therefore: Please ensure that you are famil­iar with all safety/technical procedures and guidelines in your area (e.g. what to do in the event of an alarm, application plans, alarm organization, etc.).
Notes regarding cleaning
When cleaning the surface of the keypad, particularly the user interface and display unit, ensure that no corrosive or abrasive cleansers are used and that no fluid pene­trates into the inside of the unit.
Introduction and safety instructions
- 4 -
Explanation of message display
Display for operation (green LED). The display lights up when the unit is ready for operation.
Cumulative display for alarms (red LED). The display lights up in the event of an ex­ternal or internal alarm, a pre-alarm, or a fault with external alarm signaling. The corresponding alarm is saved and in­dicated by the buzzer.
General display for faults (yellow LED). The display lights up for all types of faults. The corresponding fault message is saved and indicated by the buzzer. If the type of fault cannot be reset by the authorized user, 24-hour service must be informed.
Display (LCD): The display consists of 2 lines with 16 characters. All pending mes­sages as well as the notes for operation are displayed in the menu in plain text. If the key­pad is in standby mode, i.e. there are no messages and no functions have been called up from the menu, then the current time, the date, as well as access via the center vari­able function key in the menu will appear.
Display/control elements
p Number of the current message q Type of message r Detector zone number s Detector number of the detector zone
3 HO UP 0012-6 MESSAGE? DETEC.
p
q r s
n Number of messages o Type of message
03 HOLD UP
MENU
n o
15 : 13 22.11.2005
MENU
0
9 87
6 54
21 3
G H I D E F
A
B C
P Q R M N O J K L
S T U Y Z
ENTER
./:
STOP
V W X
- 5 -
Explanation of keys
Variable function keys
The variable function keys can be used to call up the functions dis­played via these keys. The text that appears above the key in the display provides information for operating the corresponding vari­able function key; for example:
- The left variable key calls up the next mes­sage.
- The center variable key displays the help text for 3 seconds.
- The right variable key calls up the next de­tector of the detector zone.
Information regarding the variable function keys for operating the functions in the menu:
Scroll forward through the functions in the menu using the right variable function key.
Scroll backwards through the functions in the menu using the left variable function key.
Function keys Enter digits:
If number entries are required (e.g. inputting the operator code), these entries can be made at the position where the cursor is lo­cated.
Confirm input:
Press the "ENTER" key:
- After inputting the digits.
- To call up the functions in the menu.
Return / Stop:
The "STOP" key causes a return by one level or cancellation of the function started.
Switch off buzzer:
The buzzer will sound in the event of alarm or fault messages. The buzzer can be switched off using the "Buzzer off" key.
.................................
?
Display/control elements
)
Variable function keys
3 HO UP 0012-6 MESSAGE ? DETEC
Display
ENTER
STOP
A B C
1
Important
info
- 6 -
Description
Example: there are a total of 3 messages (de­tector zones) pending that are message type e.g. "INTRUSION". If multiple message types are pending, they are displayed according to their priority.
Procedure
1. Call up the next message type. Press the
right
key.
The right
key can be used to call up
additional message types (e.g. "FAULT").
2. Call up the message for the message type
selected. Press the "ENTER" key. The chronologically first message (1) will
be displayed along with the detector zone (no. 0001) and the detector (no. 02).
3. Call up additional messages. Press the left
key.
The messages (detector zones) for the message type selected can be called up with the left
key. The messages are displayed consecutively according to their chronological order e.g. detector zone (no. 0033) along with the detector (no. 07).
4. Call up additional detectors. Press the right key.
The next triggered detector (no. 14) in the detector zone (no. 0033) will be displayed in the first line.
5. Call up additional information. Press the
center
key.
The additional information (e.g. staircase) will be displayed in plain text for approxi­mately 3 seconds. For units networked us­ing SRT, the unit number is displayed for an additional 3 seconds. The display then returns to the previous display.
1 FAULT 0001-02 STAIRCASE
2 FAULT 0033-14 MESSAGE ? DETEC
03 INTRUS. EXT
MENU
2 FAULT 0033-07 MESSAGE ? DETEC
02 FAULT
MENU
1 FAULT 0001-02 MESSAGE ? DETEC
Message display/processing
- 7 -
Querying areas and triggering statuses
Description
The status of ON/OFF areas (armed/dis­armed) and their triggering of detectors can be displayed on the display. For example, in order to properly arm the system, all doors and windows must be in normal condition (closed). This function can be used, for ex­ample, to locate corresponding detectors and detector zones in the system. Example – dis­play:
Procedure
1. Start a query. Press the center "menu" key.
The query display will appear.
2. Call up areas. Press the left
key.
The first area and its status will be dis­played.
3. Call up additional areas. Press the right
key.
The right
key can be used to call up additional areas consecutively. After the last area, "AREA 01" reappears in the dis­play. If the area is not ready for arming, "NARM" (reasons for "not ready for arm­ing") appears in the display.
4. Call up an area's triggering. Press the cen­ter
key.
The reasons for "not ready for arming" will be displayed.
5. Call up an area's additional triggering. Press the right
key.
The right
key can be used to call up the area's additional triggering consecu­tively. After the last triggering, the first trig­gering reappears in the display.
6. Call up additional information. Press the center
key.
Additional information for the triggering will be displayed for approximately 3 seconds.
7. Return. Press the "STOP" key twice. The "STOP" key causes a return by one
level. The query will be ended.
15 : 13 22.11.2005 MENU
ID:0 CO:¾¾¾¾¾¾
A
REA PROG.
0005 - 13 = TRIGGE Window room 6
0005 - 17 = TRIGGE
?
0005 - 13 = TRIGGE
?
AREA 01 = OFF
NARM
ID:0 CO:¾¾¾¾¾¾ AREA PROG.
AREA 02 = OFF
NARM
Querying statuses
- 8 -
Querying internal program statuses
Description
Example – display:
Procedure
1. Start a query. Press the center "menu" key.
The query for the internal program will be started and displayed.
2. Call up internal programs. Press the right
key.
The first internal program and its status (ON/OFF) will be displayed
3. Call up additional internal programs. Press the right
key.
By pressing the right
key, additional internal programs can be called up con­secutively. The status of internal program 02 (ON/OFF) will be displayed. After the last internal program and pressing the right
key, internal program 1 reappears in
the display.
4. End the query. Press the "STOP" key This action ends the query. If you press the
"STOP" key is again, the standby picture will appear in the display.
15 : 13 22.11.2005 MENU
ID:0 CO:¾¾¾¾¾¾
A
REA PROG.
INT-PR 01 = ON
ID:0 CO:¾¾¾¾¾¾ AREA PROG.
INT-PR 02 = ON
Querying statuses
- 9 -
Time-controlled arming
Description
The exit delay time must be entered by the safety company in charge. Not in compliance with VdS.
There are ______ seconds available for exit­ing the premises before the system is armed.
Procedure
1. Call up the input field for time-controlled arming. Press the center
key.
The input field for the time-controlled arm­ing code will be displayed.
2. Start time-controlled arming. Enter ID (1 to 3 digits) for ID 7, e.g. enter
007. Enter code (0 to 6 digits), e.g. 123123; time-controlled arming starts automatically after entry of the digits. Only press the "ENTER" key if the code is < 6 digits.
3. Time-controlled arming is activated. The delay time has started. The buzzer will
sound during the exit delay time. The room must be exited within the programmed time of ... seconds.
The left
key can be used to cancel the
arming procedure if needed.
4. Time-controlled arming is active. After the door is closed, the system is
armed, which is indicated by a buzzer sound of 3 seconds. The following mes­sage will appear on the display.
15 : 13 22.11.2005 MENU
AREA
A
RMED
ID: 007 CO:_ _ _ _ _ _ AREA PROG.
ID:0 CO:¾¾¾¾¾¾ AREA PROG.
ARMED IN . . . . . s
CANCEL
Time-controlled activation
- 10 -
Time-controlled disarming
Description
The entry delay time must be entered by the safety company in charge. Not in compliance with VdS.
There are ______ seconds available to enter the premises and disarm the system.
Procedure
1. The buzzer sounds when the door group is triggered.
2. Call up the input field for time-controlled disarming. Press the
"menu" key.
The input field for the time-controlled dis­arming code will be displayed.
3. Enter the time-controlled disarming code. Enter ID (1 to 3 digits) for ID 7, e.g. en-
ter 007. Enter code (0 to 6 digits), e.g. 123123; time-controlled disarming starts automatically after entry of the six digits. Only press the "ENTER" key if the code is
< 6 digits. There are .... seconds available.
4. Time-controlled disarming has been exe­cuted.
After successfully disarming, the message "AREA DISARMED" will appear in the dis­play.
ID:0 CO:¾¾¾¾¾¾
ID: 007 CO:_ _ _ _ _ _
15 : 13 22.11.2005 MENU
AREA
DISARMED
Time-controlled activation
- 11 -
Starting and ending code mode
Description
Inputting the user code grants control au­thorization level 1 for basic operation or con­trol authorization level 2 for all operations.
The user code is divided up into the following areas:
- ID (1 – 3 digits)
- Password (0 – 6 digits) The password can be changed on the control
panel's operating panel.
Procedure
1. The standby status of the system will be displayed.
2. Starting code input. Press the center key.
The code input display will appear.
3. Enter the user code. Enter ID (1 to 3 digits) for ID 2, e.g. en-
ter 002. Enter password (0 to 6 digits), e.g. 123123
4. Start code mode. If the user code has been entered correctly
and confirmed with the "ENTER" key with a code of < 6 digits, the first function will be displayed in the menu.
If no key is pressed for one minute, the standby picture for the menu or the current message with the highest priority is dis­played. If no input is made for 15 minutes, code mode ends automatically.
5. End code mode. Call up the "STOP CODEOPERATION"
function in the menu, and confirm with the "ENTER" key (also see chapter "Calling up and ending functions"). The code mode will be exited once again.
15 : 13 22.11.2005 MENU
15 : 13 22.11.2005 MENU
01: INTERN. PROG.
ID: 002 CO:_ _ _ _ _ _ AREA PROG.
ID:0 CO:¾¾¾¾¾¾ AREA PROG.
Code mode
- 12 -
Starting and ending code mode with messages present
Description
Inputting the user code grants control au­thorization level 1 for basic operation or con­trol authorization level 2 for all operations.
The user code is divided up into the following areas:
- ID (1 – 3 digits)
- Password (0 – 6 digits) The password can be changed on the control
panel's operating panel.
Procedure
1. For example, 3 intrusion messages are displayed.
2. Start code input. Press the center "menu" key.
The code input display will appear.
3. Enter the user code. Enter ID (1 to 3 digits) for ID 2, e.g. en-
ter 002. Enter password (0 to 6 digits), e.g. 123123.
4. Start code mode. If the user code has been entered correctly
and confirmed with the "ENTER" key for a code of < 6 digits, any activated sirens will be switched off and the first function will be displayed in the menu.
5. Call up the message display in code mode once again.
After the "STOP" key has been pressed, the message is displayed without ending code mode.
6. End code mode. Call up the "STOP CODEOPERATION"
function in the menu and confirm with the "ENTER" key. (Also see chapter "Calling up and ending functions".) The code mode will be exited once again.
ID: 002 CO:_ _ _ _ _ _ AREA PROG.
03 INTRUS. EXT.
Menu
03 INTRUS. EXT.
Menu
03 INTRUS. EXT
Menu
01: INTERN. PROG.
ID:0 CO:¾¾¾¾¾¾ AREA PROG.
Code mode
- 13 -
Calling up and ending functions
Description
All functions used to execute the different tasks are described on the following pages of these operating instructions.
Procedure
1. Start code mode (see chapter "Code mode").
If the user code has been entered properly, the first "Intern. prog." function of the menu will be displayed.
2. The right
key can be used to jump to
the individual functions consecutively.
If no key is pressed for 1 minute, the standby picture for the menu is displayed.
3. Call up a function for processing. A function, e.g. "TOTAL RESET", is called
up by pressing the "ENTER" key.
4. End code mode. Select the "STOP CODEOPERATION"
function and confirm with the "ENTER" key. The code mode will be exited once again.
15 : 13 22.11.2005 MENU
01: INTERN.PROG.
TOTAL RESET ?
RESET
01: INTERN. PROG.
02: TOTAL RESET
03: INTERN. RESET
04: DISPLAY TEST
05: AREAS
06: ISOLATE ZONES
07: WALKTEST
00:STOP CODEOPER
Operation in the menu
- 14 -
Switching internal programs on and off
Procedure
1. Call up "Intern. prog." function from the menu. See chapter "Calling up and ending functions".
2. Call up "Internal programs". By pressing the "ENTER", the first internal
program and its status (ON/OFF) are dis­played.
3. Call up additional "Internal programs". By pressing the right
key, additional internal programs can be called up con­secutively. After the last internal program and pressing the right
key, internal
program 1 reappears in the display.
4. Switch "Internal programs" on and off. The internal program can be switched on
or off using the center
key.
5. Return The "STOP" key causes a return by one
level. The menu will be displayed.
INT-PR 02 = OFF
ON
INT-PR 01 = OFF
ON
01: INTERN. PROG.
INT-PR 02 = OFF
ON
01: INTERN. PROG.
Operation in the menu
- 15 -
Resetting the control panel
Description
To switch the system back into standby mode after messages have come in, the messages must be reset. Then the system can be re­armed. To perform a reset, the areas must be switched to disarmed.
Procedure
1. To call up the "TOTAL RESET" function from the menu see chapter "Calling up and ending functions".
2. Call up "TOTAL RESET". By pressing the "ENTER" key, the "TOTAL
RESET" display appears.
3. Execute "TOTAL RESET". After pressing the center
key, all trig­gering for the control panel are reset. The messages disappear from the display as soon as all detectors are in normal con­dition. If the message type cannot be reset by the authorized user, 24-hour service must be informed.
Resetting internal messages
Description
All triggered internal messages are reset.
Procedure
1. To call up the "INTERN. RESET" function from the menu, see chapter "Calling up and ending functions".
2. Call up "INTERN. RESET". By pressing the "ENTER" key, the "Internal
reset" display appears.
3. Execute "INTERN RESET". By pressing the center
key, all trig­gered internal messages are reset. The corresponding message type is de­leted in the display as soon as all reset de­tectors are restored to normal condition.
INTERN. RESET ?
RESET
03: INTERN. RESET
03: INTERN. RESET
TOTAL RESET ?
RESET
02: TOTAL RESET
02: TOTAL RESET
Operation in the menu
- 16 -
Display test
Description
The LEDs, the display, and the buzzer for the keypad are checked that they function cor­rectly (including any external buzzers that are activated).
Procedure
1. To call up the "DISPLAY TEST" function from the menu, see chapter "Calling up and ending functions".
2. Execute "DISPLAY TEST". By pressing the "ENTER" key, the LED`s,
the display, and the buzzer of the keypad are checked that they function correctly. The display test ends automatically after 3 seconds.
********************************** ********************************** **********************************
04: DISPLAY TEST
Operation in the menu
- 17 -
Querying areas and ignoring detector zones and faults
Description
If it is not possible to arm the system, the de­tector that was triggered can be removed from monitoring (Ignore). Not in compliance with VdS.
Notify 24-hour service after the sys-
tem is disarmed.
Procedure
1. To call up the "AREAS" function from the menu, see chapter "Calling up and ending functions".
2. Call up "AREAS". By pressing the "ENTER" key, the first de-
tection area is displayed. If the area is not ready for arming, "NARM" appears in the display for the center
key to call up NARM reasons (reasons for "Not ready for arming").
3. Call up additional "AREAS". By pressing the right
key, additional areas can be called up consecutively. After the last area, "AREA 1" reappears in the display.
4. Calling up NARM reasons. The center key is used to display the NARM reasons (reasons for "Not ready for arming").
5. Execute one of the 3 operational steps: Ignore detectors zones and faults.
If it is not possible to arm the system, a maximum of one "triggered detector zone", "Network fault", or "NVU fault" can be removed from monitoring (Ignore) by pressing the left
key. Notify 24-hour
service after the system is disarmed.
Call up additional information.
By pressing the center
key, addi­tional information for the displayed trig­gering will be shown for approximately 3 seconds.
Call up additional triggering.
By pressing the right
key, additional reasons for failure to arm the area will be displayed. After the last triggering, the first triggering reappears in the display.
6. The "STOP" key causes a return by one level.
7. The "STOP" key causes a return by one level. The menu will be displayed.
AREA 02 = ON
NARM
05: AREAS
0010 - 05 = TRIGGE IGNORE ?
0005 - 13 = TRIGGE IGNORE ?
AREA 01 = OFF
NARM
05: AREAS
AREA 02 = OFF
NARM
Operation in the menu
- 18 -
Isolating detector zones
Description
This function makes it possible to isolate one detector zone or multiple detector zones be­fore the system is armed. Areas of disarmed detector zones can be entered if the system is armed, without an alarm being triggered. Not in compliance with VdS.
Procedure
1. To call up "ISOLATE ZONES" from the menu, see chapter "Calling up and ending functions".
2. Call up detector zone. By pressing the "ENTER" key, the first de-
tector zone that can be isolated and its status (ON/OFF) will be displayed.
3. Call up additional detector zones. By scrolling with the
keys or by direct entry of the address using the number pad, additional detectors zones that can be iso­lated are displayed.
4. Initiate isolation procedure. Once the detector zone to be isolated has
been called up, the isolation procedure is initiated by pressing the center
key.
5. Isolate detector zone. To isolated detector zone 2, press the right
key. After isolation has been com­pleted, the new status of the detector zone (= OFF) will be displayed.
6. Reset. The "STOP" key causes a return by one
level. The menu will be displayed.
06: ISOLATE ZONES
ZO 0002 = OFF
v
ZO 0001 = ON
v
06: ISOLATE ZONES
ZO 0002 = ON
v
ZO 0002 = ON ON v OFF
Operation in the menu
- 19 -
Isolating a detector in a detector zone
Description
This function can be used to isolate individual detectors before the system is armed. Areas with isolated detector zones can be entered if the system is armed, without an alarm being triggered. Not in compliance with VdS.
Procedure
1. To call up "ISOLATE ZONES" from the menu, see chapter "Calling up and ending functions".
2. Call up detector zone. By pressing the "ENTER" key, the first de-
tector zone that can be isolated and its status (ON/OFF) will be displayed.
3. Call up additional detector zones. By scrolling with the
keys or by direct entry of the address using the number pad, additional detectors zones that can be iso­lated are displayed.
4. Search for "Detector". Press center
key 2 x to enable the
display of individual detectors.
5. Call up detector. By pressing the right
key, the first de­tector from the selected detector zone will be displayed.
6. Call up additional detectors. By scrolling with the right
key, a par­ticular detector from this detector zone can be selected and displayed.
7. Initiate isolation procedure. Once the detector zone to be switched off
has been called up, the isolation procedure is initiated by pressing the center
key.
8. Isolate detector. Press the right
key to isolate the de­tector. After isolation has been completed, the new status of the detector (=OFF) will be displayed.
9. Reset. Press "STOP" key 2 x. The "STOP" key
causes a return by one level. The menu will be displayed.
ZO 0002 = ON
v
ZO 0001 = ON
v
0002 – 13 = OFF
v
0002 – 13 = ON ON v OFF
0002 – 13 = ON
v
ZO 0002 = ON ? v DETEC
06: ISOLATE ZONES
0002 – 01 = ON
v
06: ISOLATE ZONES
Operation in the menu
- 20 -
Walktest
Description
This function can be used to check the sys­tem's detectors via a walktest. Any stored messages from detector cover can be reset using this function. The walktest is done with the detection areas in a disarmed status. Triggering of the detector is indicated by the detector's red LED during a walktest.
Procedure
1. To call up the "WALKTEST" function from the menu, see chapter "Calling up and end­ing functions".
2. Call up "WALKTEST". By pressing the "ENTER" key, the first de-
tection area as well as its status with re­spect to the walktest will be displayed.
3. Call up additional detection areas for a "WALKTEST".
By pressing the right
key, additional detection areas can be called up consecu­tively. After the last detection area, detec­tion area 1 reappears in the display.
4. Switch on "WALKTEST". The "WALKTEST" of the detection area is
switched on by pressing the center key.
5. Conduct "WALKTEST". Trigger movement alarm. A triggering of
the detector is indicated by the detector's red LED.
6. Switch off "WALKTEST". The "WALKTEST" for the detection area is
switched off by pressing the center key.
7. Return. The "STOP" key causes a return by one
level. The menu will be displayed.
ZO 02 = OFF
ON
ZO 02 = OFF
ON
ZO 01 = OFF
ON
AREA 02 = MNSTB
OFF
07: WALKTEST
07: WALKTEST
Operation in the menu
- 21 -
Notes
- 22 -
Notes
- 23 -
Notes
- 24 -
Einführung und Sicherheitshinweise...........25
Anzeige-/Bedienelemente
Erklärung der Meldungsanzeige......................26
Erklärung der Tasten .......................................27
Meldungsanzeige-/bearbeitung ....................28
Abfragen von Zuständen
Abfragen von Bereichen und
Auslösungszuständen......................................29
Abfragen von Internprogrammzuständen ........30
Zeitscharfschaltung (ZSS)
Zeitscharfschalten............................................31
Zeitunscharfschalten........................................32
Codebetrieb
Codebetrieb starten und beenden ...................33
Codebetrieb starten und beenden bei
vorliegenden Meldungen..................................34
Bedienung im Menü
Funktionen aufrufen und beenden...................35
Internprogramme ein-/ausschalten ..................36
Rücksetzen der Zentrale..................................37
Rücksetzten von Internmeldungen ..................37
Anzeigentest....................................................38
Abfragen von Bereichen und übergehen
von Meldergruppen und Störungen .................39
Meldergruppen abschalten ..............................40
Melder einer Meldergruppe abschalten ...........41
Begehtest.........................................................42
Notizen............................................................43
Inhaltsverzeichnis
- 25 -
Einführung zur Bedienung
Die abgesetzte Bedieneinheit darf nur von eingewiesenen Personen bedient werden!
Aus Sicherheitsgründen und um Fehlbedie­nungen zu vermeiden, sollte der Berechti­gungscode zur Bedienung der Anlage nur diesen Personen mitgeteilt werden.
Unter bestimmten Voraussetzungen ist die Bedieneinheit nicht aktiv, d.h. nicht bedien­bar:
Meldebereich ist scharf geschaltet. Die Be-
dieneinheit ist dem scharf geschaltetem Meldebereich zugeordnet.
Meldebereich ist scharf geschaltet. Be-
dieneinheit ist auf „bei scharf dunkel“ pa­rametriert.
Überfallalarm im System. Bedieneinheit ist
auf „bei Überfall dunkel“ parametriert.
Worüber informiert Sie diese Bedienungs­anleitung
In dieser Anleitung finden Sie alle Informatio­nen, die Sie für die Interpretation der Mel­dungsanzeige und der Bedienung der Be­dieneinheit benötigen.
Worüber informiert Sie diese Bedienungs­anleitung nicht
Die Bedienungsanleitung vermittelt keine In­formationen über allgemeines oder spezielles sicherheitstechnisches Wissen.
Deshalb: Vergewissern Sie sich bitte, dass Sie mit allen sicherheitstechnischen Abläufen und Vorschriften in Ihrem Bereich (z.B. auch Verhalten bei Alarm, Einsatzplänen, Alarmor­ganisation etc.) vertraut sind.
Hinweise zur Reinigung
Beim Reinigen der Oberfläche der Bedien­einheit, speziell bei der Bedien- und Anzeige­einheit ist darauf zu achten, dass keine ät­zenden und scheuernden Reinigungsmittel verwendet werden, und keine Flüssigkeit ins Innere des Gerätes eindringt.
Einführung und Sicherheitshinweise
- 26 -
Erklärung der Meldungsanzeige
Anzeige für Betrieb (LED grün). Anzeige leuchtet bei Betriebsbereitschaft der Anla­ge.
Summenanzeige für Alarme (LED rot). Anzeige leuchtet beim Auftreten eines Ex­tern- oder Internalarms, eines Voralarms oder einer Störung mit Externalarmierung. Der entsprechende Alarm wird gespeichert und durch den Summer signalisiert.
Summenanzeige für Störungen (LED gelb). Anzeige leuchtet bei allen Stö­rungsarten. Die entsprechende Störmel­dung wird gespeichert und durch den Summer signalisiert. Ist die Störungsart durch den Bedienberechtigten nicht rück­setzbar, ist der Störungsdienst zu benach­richtigen.
Display (LCD): Das Display besteht aus 2 Zeilen mit 16 Zeichen. Im Klartext-Display werden alle anstehenden Meldungen sowie die Hinweise für die Bedienung im Menü an­gezeigt. Befindet sich die Bedieneinheit im Ruhezustand, d.h. es sind keine Meldungen eingetroffen und es sind keine Funktionen aus dem Menü aufgerufen, erscheint die ak­tuelle Uhrzeit, das Datum sowie der Einstieg über die mittlere variable Funktionstaste in das Menü.
Anzeige-/Bedienelemente
p Nummer der laufenden Meldung q Meldungsart r Meldergruppen-Nummer s Melder-Nummer der Meldergruppe
3 ÜBERFALL 0012-6 Meldun
g
? Melder
p
q r s
n Anzahl der Meldungen o Meldungsart
03 ÜBERFALL
Menue
n
o
15 : 13 22.11.2005
Menue
0
9 87
6 54
21 3
G H I D E F
A
B C
P Q R M N O J K L
S T U Y Z
ENTER
./:
STOP
V W X
- 27 -
Erklärung der Tasten
Variable Funktionstasten
Mit den variablen Funktionstasten können die über diesen Tasten im Display angezeigten Funktionen aufgerufen werden. Der jeweils über der Taste liegende Text im Display gibt einen Hinweis für die Bedienung der entsprechenden variablen Funktionstaste; d.h.
- mit der linken variablen Taste wird die nächste Meldung aufgerufen.
- mit der mittleren variablen Taste wird der Hilfetext für 3 Sekunden angezeigt.
- mit der rechten variablen Taste wird der nächste Melder der Meldegruppe aufgeru­fen.
Hinweis zu den variablen Funktionstasten zur Bedienung der Funktionen im Menü:
Vorwärtsblättern der Funktionen im Menü mit der rechten variablen Funktionstas­te.
Rückwärtsblättern der Funktionen im Menü mit der linken variablen Funktionstaste.
Funktionstasten Ziffern eingeben:
Soweit Zahleneingaben erforderlich sind (z.B. Eingabe des Betreibercodes), können diese an der Stelle erfolgen, an der die Cur­sormarke positioniert worden ist.
Eingabe bestätigen:
Die Taste „ENTER“ wird gedrückt:
- nach der Eingabe von Ziffer.
- zum Aufruf der Funktionen im Menü.
Zurückschalten:
Mit der Taste „STOP“ wird um eine Ebene zu­rückgeschaltet oder eine gestartete Funktion abgebrochen.
Summer ausschalten:
Der Summer ertönt beim Auftreten von Alarm- und Störungsmeldungen. Mit der Tas­te „Summe aus“ wird der Summer ausge­schaltet.
.................................
?
Anzeige-/Bedienelemente
ENTER
STOP
A B C
1
Wichtige
Info
)
Variable Funktionstasten
3 ÜBERFALL 0012-6 Meldung ? Melder
Display
Loading...
+ 61 hidden pages