Bosch HUMBSBP-12H6--A, HUMBLBP-17H6--A Installation And Maintenance Manual

Installation and Maintenance Manual
FLOW-THROUGH BYPASS HUMIDIFIER
FOR INSTALLATION ON A VERTICAL PLENUM SURFACE
IAQ Series
OF ANY AIR HANDLER
HUMBSBP-12H6--A HUMBLBP-17H6--A
6 720 220 343 Revised 07-12
2 IAQ Series Table of Contents
TABLE OF CONTENTS
Installation ....................................................................................... 3
Additional Materials That May Be Necessary ................................ 3
Humidity Control Humidistat HUMB-TST-A-A .................................... 5
Safety .............................................................................................. 5
Application ....................................................................................... 5
Operation ........................................................................................ 5
Installation Instructions—Precautions .............................................. 5
Wall Mount Instructions—Humidistat/Dehumidistat Versions ........... 5
Duct Mounting on the Return Air—Wall Base ..................................... 6
Duct Mounting on the Return Air—Duct Base .................................... 6
HUM-TST-H-A Calibration Instructions ............................................. 7
Wiring .............................................................................................. 7
Checkout ......................................................................................... 7
Settings ........................................................................................... 7
Care and Maintenance ..................................................................... 7
How the Humidier Works ............................................................... 8
Humidier Packaged Component Accessories ................................. 8
Contact your local Bosch Dealer or Installing Contractor
for product support ...................................................................... 8
Heat Pump Wiring Diagram .............................................................. 9
Alternate Electrical & Control Connections .................................... 10
Parts List for Humidier ................................................................. 11
Bosch Humidier Specications .................................................... 11
Humidier Dimensional Drawings .................................................. 12
Troubleshooting ............................................................................. 13
Product Limited Warranty .............................................................. 14
6 720 220 343
Subject to change without prior notice Revised 07-12
Installation IAQ Series 3
The installer should be an experienced service technician. Disconnect electrical power before beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures exceed 150 degrees F. When wiring into a multi-speed blower circuit see Step 6.
INSTALLATION
The humidier may be mounted with the 6” outlet to the right or left side. The humidier may be mounted
on the warm or return air plenum with equal
efciency. See Typical Installations.
Step 2: The BOSCH humidier may be installed on
either the supply or return plenum of a forced air
handling system. Select a location for the humidier that allows for service and maintenance. Cut out a rectangle. Extend horizontal center line of cut out to the adjacent plenum. Cut a 6” hole 10” to 15” from side of humidier, on cabinet center line, using connecting collar as guide. The bypass is reversible
and can be mounted on the right or left side of the
humidier. Use provided template provided in the humidier package. See Figure 1.
Additional Materials That May Be Necessary
1. 1/4” diameter plastic supply tubing or 1/4”
copper supply tubing for hot water applications
2. 6” diameter galvanized by-pass pipe
3. Electrical wire and wire nuts
4. Current sensing relay
5. #8 self piercing sheet metal screws
6. Accurate Humidity measuring device.
STEP 1: Carefully unpack the Bosch Humidier and verify that all contents are present and undamaged. Remove the cover using the the release tabs on the top and bottom, exposing the humidier evaporator pad. Remove the evaporator pad, drain pan, and
distributor trough ( all of this should come out as one piece).
Figure #1
Step 3: Humidier is self retaining. Slide top side in
rst, then slide chassis down. Level chassis and
install center screws. If by-pass duct installs to opposite side of chassis, bend clip on chassis,
remove side discharge, and reinstall discharge to
opposite side of chassis. Install remaining four
corner screws. See Figure 2.
Figure #2
Step 4: Connect by-pass duct to collar and
humidier cabinet. Using holes at top and bottom of
side panel discharge, pierce 2 self tapping screws
through by-pass pipe. See Figure 3.
Revised 07-12 Subject to change without prior notice
6 720 220 343
1
2
4 IAQ Series Installation
Figure #3
Step 5: Mount the self tapping saddle valve or code
valve on either a cold or a hot water pipe. A side or top mount is best to avoid clogging from pipe sediment. Connect 1/4” O.D. tubing to the saddle valve. Copper tubing requires a brass compression nut and brass sleeve. Plastic tubing requires a brass insert inside the tubing, a plastic sleeve on the outside with a brass compression nut. See Figure 4.
Do not use plastic tubing on hot water or in contact with any hot plenum surface or duct. Installation of this saddle valve must meet or exceed local codes and ordinances.
COPPER TUBING
PLASTIC TUBING
Figure #4
Step 6: Connect 1/4” water supply tube to brass
lter at inlet of solenoid. See Figure 5.
Do not use plastic tubing on hot water or in contact with any hot plenum surface or duct. If using plastic tubing, use tube support and plastic compression sleeve.
Figure #5
STEP 7: Replace the evaporator pad with the drain
pan and distributor trough attached. Ensure that the drain pan is on the bottom and that the spout aligns
with the outlet in the cabinet. The evaporator pad
assembly can only be installed in one direction. Ensure that the notch at the top in the distributor
trough goes in rst. Do not force the evaporator pad
assembly. If it does not go in easily, it might be backwards.
STEP 8: Replace the humidier cover, ensuring that
both tabs snap into place.
Step 9: Turn damper knob to the “winter” (open)
position. Turn on water supply and check operation
of humidier. Set humidistat to a demand setting.
(See Humidistat section for installation and
settings) With the air handler off, the solenoid valve
should be closed. Start the air handler, the solenoid
valve should open when the blower motor is energized. Check ow of water through distributor trough and evaporator pad. The standard yellow orice will supply approximately 3.5 GPH of water at a line water pressure of 60 psi. For low water pressures (20-40 psi) a larger orange orice (P/N
7738002989) is available to provide the same ow. Leave humidistat set at the recommended setting.
Connect drain hose to 1/2” spout on humidier cabinet using hose clamp. Run 1/2” hose to suitable drain such as oor drain, sewer or laundry sink. Be
sure hose has continuous slope and is not kinked at any point.
6 720 220 343
Subject to change without prior notice Revised 07-12
Humidity Control Humidistat HUMB-TST-A-A IAQ Series 5
HUMIDITY CONTROL HUMIDISTAT HUMB-TST—A—A
INSTALLER: Leave owner’s manual with home owner.
SAFETY
Improper electrical wiring can result in re or
loss
of humidity control. Disconnect electrical power before installing and servicing. Failure to disconnect electrical power may result in injury or death. All local building and electrical codes must be followed. The humidistat must be installed by
a qualied Technician. Failure to properly install
the humidistat may result in property damage or personal injury.
Homeowners must read instructions and understand the operation of the humidistat and the
humidier(s) it controls.
Improper operation can result in over or under humidication. Over humidication can result in
condensation, structural damage and mold. Condensation within a building’s structure can cause loss of structural strength. Condensation can also enable mold and mildew growth resulting in personal injury and damage to building structure and contents.
mounting on the return air duct. Use contacts C and NO for humidistat operation. Use contacts C and NC for dehumidistat operation.
RANGE: 10% to 85% RH ELECTRICAL RATING: 30
VAC / 60 VA
OPERATION
Set the control knob to the desired humidity setting. The recommended setting for optimum
whole-house humidication is 30% to 50%. The vertical position on the knob is approximately 42%
RH.
Setting the humidistat above or below the recommended settings may not provide
satisfactory results for your home. Refer to the Care and Maintenance section of this manual for recommended settings.
INSTALLATION INSTRUCTIONS— PRECAUTIONS
The installer must be a qualied technician.
Disconnect electrical power before beginning installation. Do not install the humidistat on the warm air duct. Conduct a thorough checkout
before leaving the installation.
WALL MOUNT INSTRUCTIONS— HUMIDISTAT/DEHUMIDISTAT VERSIONS
1. Choose a location for the HUMB-TST—H—A
about ve feet above the oor on an inside wall with average room temperature and relative
humidity conditions.
2. Drill a small hole in the wall and run low voltage wiring to the location chosen. Pull about 6” of
wire through the hole. Use the entire mounting gasket (both inside and outside portions) to seal the wall opening or use foam tape to
prevent drafts from affecting the humidistat operation. See Figure 6.
APPLICATION
The humidistat provides low voltage control of humidiers installed in central heating systems.
The humidistat control has a DPST switch and is
designed for wall mounting in the living area, or
Revised 07-12 Subject to change without prior notice
3. Squeeze the top and bottom of the base to
release the face of the humidistat.
4. Mount the base horizontally over the wires.
Attach directly to the wall, using the two screws
provided in the slotted holes.
6 720 220 343
Loading...
+ 11 hidden pages