Bosch FMR-7036 User Manual 2

Fire Alarm Systems | FMR‑7036 Fire Annunciator Keypad
FMR‑7036 Fire Annunciator Keypad
www.boschsecurity.com
u Compatible with FPD‑7024 Fire Alarm Control Panel
u Two‑line, 16‑character LCD display
u On‑board LEDs indicate Silenced, Trouble, Alarm,
u Silence and Reset buttons
u Built‑in keyswitch
The FMR‑7036 is a four‑wire LCD annunciator keypad used with the FPD‑7024 Fire Alarm Control Panel (FACP) to establish the location of a fire alarm. The two‑line, 16‑character display is capable of showing all messages normally displayed on the control panel. All alarm and status messages are included. Four on‑board LEDs provide easy reading of the annunciator's status from a distance. There are Silence and Reset buttons for controlling annunciator and control panel operation. A built‑in keyswitch offers extra security by locking the annunciator to prevent unwanted sounder silencing or control panel resetting.
Certifications and Approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
FM
CSFM 7165-1615:0227
FDNY­CoA
(ANSI/UL 864)
#6024
Installation/Configuration Notes
Compatible Products
Category Product ID Product Description
Control Panels FPD‑7024 Four‑zone FACP
Mounting
The FMR‑7036 can be surface mounted on a standard three‑gang box, or with the mounting backplate provided.
Wiring Guidelines
For the FPD‑7024 FACP, the maximum allowed DC current draw from the option bus is 500 mA for keypads. The maximum length of wire (all branches added together) that can be connected to the option bus terminals is 4000 ft (1220 m). The maximum length between any one device and the control panel terminals depends on the current draw on the branch that the device is on. The current draw on a particular branch can be found by adding together the individual current draws of each device connected to the branch.
2 | FMR‑7036 Fire Annunciator Keypad
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 al.securitysystems@bosch.com www.boschsecurity.com
© Bosch Security Systems 2012 | Data subject to change without notice 2696443659 | en, V2, 11. Sep 2012
Notice
Refer to the FPD‑7024 Installation Guide (P/N: F01U008458) for complete wire length calculations.
Number of Keypads
Up to four keypads can be used per system. Up to three keypads can be used on any single 1000 ft (305 m) run of 18 AWG (1.2 mm) wire.
Parts Included
Quant. Component
1 LCD annunciator keypad
1 Literature pack
Technical Specifications
Environmental Considerations
Environment: Indoor, dry
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating):
+32°F to 120°F (0°C to +49°C)
Mechanical Properties
Base Dimensions (HxW):
Cover Dimensions (HxW):
4.6 in. x 8.2 in. (11.7 cm x 20.8 cm)
4.3 in. x 8.1 in. (10.9 cm x 20.6 cm)
Power Requirements
Current (Alarm):
Current (Standby):
100 mA
80 mA nominal
Voltage (Operating): 12 VDC nominal
Ordering Information
FMR‑7036 Fire Annunciator Keypad
Four‑wire LCD annunciator keypad used with the FPD‑7024 Fire Alarm Control Panel to establish the location of a fire alarm
Order number FMR-7036
Accessories
KEY‑ANN Replacement Key
This is a spare or replacement key for the FMR-7036 lock.
Order number KEY-ANN