Fire Alarm Systems | FMR‑1000‑RA Remote Annunciator
FMR‑1000‑RA Remote Annunciator
www.boschsecurity.com
u LED status indicators
u 80‑character LCD display
u Piezo sounder
The FMR‑1000‑RA Remote Annunciator is a
four‑conductor LCD annunciator without system
control capability. It shows the equivalent LEDs and
LCD display. It includes a piezo sounder, navigation
buttons, and acknowledge key. The navigation
functions and the acknowledge key are accessible
without restriction.
The Remote Annunciator features tabs with different
language versions for LED and key text. The housing
includes a built-in level and allows for surface and
semi‑flush mounting.
Functions
Display
The Remote Annunciator uses an 80‑character (4 lines
X 20 characters) wide viewing-angle LCD display. The
display includes a long‑life LED backlight. The
backlight is controlled by the panel, or locally turned
on upon any key press and turned off after a 30 sec
timeout without key press. Even when AC power is
lost, the LED backlight is still turned on if a user is
operating the keypad.
System Normal: When no alarms or troubles exist in
the system, the Power LED lights steadily, and no
other LEDs are lit. The LCD display shows two banner
lines, the system status line, and the date and time.
u Navigation buttons
u Acknowledge key
System Off‑normal: If any off‑normal condition exists,
the panel displays the number of off‑normal conditions
classified in groups. Groups include fire alarm, gas
alarm, supervisory, and trouble. The panel holds up to
255 events for each group at a time. Any restored
event is deleted from the list.
Piezo Sounder
The Remote Annunciator has a piezo sounder that
provides audible indication of the system status. In
case of multiple activation, the system status with
highest priority is indicated.
Certifications and approvals
Region Certification
USA UL FSYE: Emergency Alarm System Acces-
sories (ANSI/UL 2017), UOXX: Control
Unit Accessories, System (ANSI/UL 864,
9th edition)
CSFM see our website
FDNY-
#6101
CoA
2 | FMR‑1000‑RA Remote Annunciator
Installation/configuration notes
Mounting Considerations
The Remote Annunciator can be surface mounted in
the supplied back box or flush mounted using a 3‑gang
electrical box.
Notice
The annunciator should be mounted no higher
than shoulder height of the shortest person
operating the system.
Wiring Considerations
Use four conductor, 18 AWG (ISO 0.75 mm2) or larger
wire to connect the Remote Annunciator to the Option
Bus of the FACP. The total length of wire connected to
the Option Bus terminals must not exceed 4000 ft
(1219 m), regardless of the wire gauge used. For
detailed wire length calculations, see the FPA‑1000
Installation and Operation Guide.
Parts included
Quant. Component
1 Remote annunciator in back box with cover frame
Tabs with different language versions for LED and key text
1 Hardware pack
1 Literature – Installation and Operation Guide
Technical specifications
Electrical
Voltage (operating): 12 VDC or 24 VDC nominal
Current consumption at 12 VDC
Alarm: 150 mA maximum (with annunciator lit and
piezo sounder on)
Stand-by: 25 mA maximum (only Power LED on)
Mechanical
Operating and Display Elements
LCD: 4‑line x 20‑character display, backlit
LEDs: Six: Fire Alarm (red); Gas Alarm (blue);
Power (green); Supervisory, Silenced,
and Trouble (3 x yellow)
Keys: Acknowledge key, 4 navigation keys
Sounder: Built-in piezo sounder
Housing
Material: ABS-FR
Color: Red
Dimensions (W x H x D)
• Back box: 7.40 in x 4.41 in x 1.89 in. (188 mm x
112 mm x 48 mm)
Cover frame: 7.40 in x 4.41 in x 2.40 in. (188 mm x
112 mm x 61 mm)
Weight: 15.2 oz (430 g)
Wiring
Cable Entries: 3 knockouts for ½ in. diameter conduit
connectors on back, bottom and top side
Connections: 4 terminals
Wre Gauge: 12 AWG to 18 AWG (ISO 0.75 mm2 to
4 mm2)
Wire Type: Non-shielded, four conductor wire
Ordering information
FMR‑1000‑RA Remote Annunciator
LCD annunciator without system control capability for
use with the FPA‑1000 Analog Addressable Fire Panels
Order number FMR-1000-RA
Current consumption at 24 VDC
Alarm: 120 mA maximum (with annunciator lit and
Stand-by: 30 mA maximum (only Power LED on)
piezo sounder on)
Environmental
Environment: Indoor, dry
Environment Friendly: RoHS compliant
Protection Class: IP 30 (per IEC 605029)
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Temperature (storage): -4°F to +140°F (-20°C to +60°C)