Bosch FMR-1000-RA Specsheet

Fire Alarm Systems | FMR‑1000‑RA Remote Annunciator
FMR‑1000‑RA Remote Annunciator
www.boschsecurity.com
u LED status indicators
u 80‑character LCD display
u Piezo sounder
The FMR‑1000‑RA Remote Annunciator is a four‑conductor LCD annunciator without system control capability. It shows the equivalent LEDs and LCD display. It includes a piezo sounder, navigation buttons, and acknowledge key. The navigation functions and the acknowledge key are accessible without restriction. The Remote Annunciator features tabs with different language versions for LED and key text. The housing includes a built-in level and allows for surface and semi‑flush mounting.
Functions
Display
The Remote Annunciator uses an 80‑character (4 lines X 20 characters) wide viewing-angle LCD display. The display includes a long‑life LED backlight. The backlight is controlled by the panel, or locally turned on upon any key press and turned off after a 30 sec timeout without key press. Even when AC power is lost, the LED backlight is still turned on if a user is operating the keypad. System Normal: When no alarms or troubles exist in the system, the Power LED lights steadily, and no other LEDs are lit. The LCD display shows two banner lines, the system status line, and the date and time.
u Acknowledge key
System Off‑normal: If any off‑normal condition exists, the panel displays the number of off‑normal conditions classified in groups. Groups include fire alarm, gas alarm, supervisory, and trouble. The panel holds up to 255 events for each group at a time. Any restored event is deleted from the list.
Piezo Sounder
The Remote Annunciator has a piezo sounder that provides audible indication of the system status. In case of multiple activation, the system status with highest priority is indicated.
Certifications and approvals
Region Certification
USA UL FSYE: Emergency Alarm System Acces-
sories (ANSI/UL 2017), UOXX: Control Unit Accessories, System (ANSI/UL 864, 9th edition)
CSFM see our website
FDNY-
#6101
CoA
2 | FMR‑1000‑RA Remote Annunciator
Installation/configuration notes
Mounting Considerations
The Remote Annunciator can be surface mounted in the supplied back box or flush mounted using a 3‑gang electrical box.
Notice
The annunciator should be mounted no higher than shoulder height of the shortest person operating the system.
Wiring Considerations
Use four conductor, 18 AWG (ISO 0.75 mm2) or larger wire to connect the Remote Annunciator to the Option Bus of the FACP. The total length of wire connected to the Option Bus terminals must not exceed 4000 ft (1219 m), regardless of the wire gauge used. For detailed wire length calculations, see the FPA‑1000
Installation and Operation Guide.
Parts included
Quant. Component
1 Remote annunciator in back box with cover frame
Tabs with different language versions for LED and key text
1 Hardware pack
1 Literature – Installation and Operation Guide
Technical specifications
Electrical
Voltage (operating): 12 VDC or 24 VDC nominal
Current consumption at 12 VDC
Alarm: 150 mA maximum (with annunciator lit and
piezo sounder on)
Stand-by: 25 mA maximum (only Power LED on)
Mechanical
Operating and Display Elements
LCD: 4‑line x 20‑character display, backlit
LEDs: Six: Fire Alarm (red); Gas Alarm (blue);
Power (green); Supervisory, Silenced, and Trouble (3 x yellow)
Keys: Acknowledge key, 4 navigation keys
Sounder: Built-in piezo sounder
Housing
Material: ABS-FR
Color: Red
Dimensions (W x H x D)
• Back box: 7.40 in x 4.41 in x 1.89 in. (188 mm x 112 mm x 48 mm)
Cover frame: 7.40 in x 4.41 in x 2.40 in. (188 mm x
112 mm x 61 mm)
Weight: 15.2 oz (430 g)
Wiring
Cable Entries: 3 knockouts for ½ in. diameter conduit
connectors on back, bottom and top side
Connections: 4 terminals
Wre Gauge: 12 AWG to 18 AWG (ISO 0.75 mm2 to
4 mm2)
Wire Type: Non-shielded, four conductor wire
Ordering information
FMR‑1000‑RA Remote Annunciator
LCD annunciator without system control capability for use with the FPA‑1000 Analog Addressable Fire Panels
Order number FMR-1000-RA
Current consumption at 24 VDC
Alarm: 120 mA maximum (with annunciator lit and
Stand-by: 30 mA maximum (only Power LED on)
piezo sounder on)
Environmental
Environment: Indoor, dry
Environment Friendly: RoHS compliant
Protection Class: IP 30 (per IEC 605029)
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Temperature (storage): -4°F to +140°F (-20°C to +60°C)