Fire Alarm Systems | FMM‑462 Series POPIT Addressable Manual Stations
FMM‑462 Series POPIT Addressable
Manual Stations
www.boschsecurity.com
u Single‑gang mounting
u Latching alarm lever and key‑locked reset
u Rugged die‑cast housing with 14 gauge (1.9 mm)
plated steel back and corrosion‑resistant
construction
u Optional scored acrylic breakrod
The FMM‑462 Series Addressable Manual Stations
allow people evacuating a building to initiate an alarm
and alert others still inside. This UL-listed initiating
device is compatible with the Bosch Security Systems,
Inc. G Series Control Panels and the D9124 Fire Alarm
Control Panel (FACP).
The POPIT module is addressed using on-board slide
switches. It is then connected to a D9124 data
expansion loop. The POPIT is polled by the control
panel and sends reports on any opens, shorts, or
ground faults on the manual station's wiring. The
addressable feature allows the agencies responding to
alarm or trouble conditions to go to the point that
initiated the alarm or trouble report.
These low-profile manual stations are die cast with
rounded edges to fit most design applications. All
metallic components are painted or plated to inhibit
corrosion. The FMM‑462 Series Manual Stations
conform with the Americans with Disabilities Act
(ADA) standards.
Functions
Addressable Operation
The POPIT connects to a two‑wire data expansion
circuit from the control panel. Device address is set
through slide switches on the POPIT Module, allowing
programmable device identification by the control
panel.
Certifications and Approvals
ADA Complies with Americans with
Disabilities Act ADA 4.28.3
NFPA Complies with National Fire
Protection Association NFPA 72
Region Certification
USA UL UNIU: Boxes, Non-Coded (UL38)
CSFM 7150-1615:0122
2 | FMM‑462 Series POPIT Addressable Manual Stations
Installation/Configuration Notes
Compatibility Information
The FMM‑462 Series Addressable Manual Stations are
compatible with the following products:
Category Product ID Product Description
Control D7212G Control panel
Panels: D7412G Control panel
D9412G Control panel
D9124 Addressable FACP
Modules D9127U POPIT module
Mounting Considerations
The FMM‑462 manual stations are for indoor use only.
The FMM‑462 or FMM‑462‑D and the wiring from the
control panel data expansion loop fit into a single-gang
back box for flush mounting. Use the larger
FMM‑100BB‑R Back Box for surface mounting and to
provide additional room for system wiring and the
module.
Parts Included
Quant. Component
1 Manual station
1 D9127U POPIT module
1 FMM‑100GR scored acrylic breakrod
1 D102 Key (1358)
1 Literature pack
Ordering Information
FMM‑462 Single‑Action Manual Station
A UL-listed initiating device compatible with the Bosch
Security Systems, Inc. G Series Control Panels and the
D9124 Fire Alarm Control Panel (FACP)
Order number FMM-462
FMM‑462‑D Double‑Action Manual Station
A UL-listed initiating device compatible with the Bosch
Security Systems, Inc. G Series Control Panels and the
D9124 Fire Alarm Control Panel (FACP)
Order number FMM-462-D
Accessories
D102 Replacement Key
Replacement key (#1358) for the D101 lock.
Order number D102
FMM‑100BB‑R Surface‑mount Back Box (red)
Red cast‑metal back box
Order number FMM-100BB-R
FMM‑100GR Scored Acrylic Break Rods
Scored acrylic rods (12 per package)
Order number FMM-100GR
Technical Specifications
Environmental Considerations
Temperature (operating): +14°F to +120°F (-10°C to +49°C)
Mechanical Properties
Activation Force: 5 lb (2.3 kg)
Alarm Response Time: 1 sec (approximately)
Dimensions (HxWxD): 4.75 in. x 3.2 in. x 0.875 in.
Material: Painted die‑cast metal, plated steel back
(12.1 cm x 8.1 cm x 2.2 cm)
and painted steel front
Power Requirements
Current (alarm): 0.8 mA
Current (normal): 0.5 mA
Voltage (operating): 7 VDC to 15 VDC supplied by the control
panel