Bosch FAD-325-DH Specsheet

Fire Alarm Systems | FAD-325-DH Analog Duct Smoke Detector Replacement Head
FAD-325-DH Analog Duct Smoke Detector Replacement Head
www.boschsecurity.com
u Smoke density range of 0.88 %/ft to 2.75 %/ft
(2.9%/m to 9%/m)
The FAD‑325 ‑DH Analog Duct Smoke Detector Replacement is a replacement detector for the FAD‑325 Duct Smoke Detector Housing. It detects smoke particles which typically result from wood, paper, and fabric combustion. Use it in heating, ventilation, and air conditioning (HVAC) systems. It uses a LED and photodiode to measure particulate levels in its detection chamber. These measurements are transmitted via the DCP protocol to the fire panel.
Functions
Fire Panel Connections
The detector is controlled by a microprocessor and communicates with the fire panel (both power and data) over a two‑wire polling circuit.
Sensitivity levels
The system allows for adjusting sensitivity levels by the detector over a range of 0.88 %/ft to 2.75 %/ft (2.9%/m to 9%/m) obscuration. The unique detection chamber design prevents external light from affecting the photodiode.
panel)
u Provides automatic compensation values in case of
detector contamination
u Replacement detector for FAD‑325 Analog Duct
Smoke Detector Housing
u Easy detector removal for cleaning and servicing
Status Display
The detector has two LEDs that flash every time the device is polled and can be switched on steady when the module goes into active condition.
Certifications and approvals
Region Certification
USA UL UROX: Smoke-automatic Fire Detectors
CSFM see our website
(ANSI/UL 268)
Installation/configuration notes
Compatible Products
The following products are compatible with the FAD‑325‑DH Photoelectric Smoke Detector Replacement:
Category Product ID Product Description
Fire Panels FPA‑1000
Family
Analog Addressable Fire Panels
2 | FAD-325-DH Analog Duct Smoke Detector Replacement Head
Detector Bases FAD‑325 Analog Duct Smoke Detector
Programming Products
D5070 Analog Device Programmer
Housing
Mounting
The FAD‑325‑DH installs quickly and easily into the FAD‑325 Analog Duct Housing to replace the detector. The FAD‑325‑DH attaches to the FAD‑325 Analog Duct Smoke Detector Housing by inserting the detector into a groove on the base and turning the detector clockwise.
Parts included
Quant. Component
1 FAD‑325‑DH Analog Duct Smoke Detector Replacement
1 Dust cover
1 Literature pack
Technical specifications
Electrical
Operating Voltage 17 VDC to 41 VDC range
Current Consumption Depends on housing
Mechanics
Dimensions (Ø x D) 4 in. x 1.5 in. (10.2 cm x 3.8 cm))
Weight 3.2 oz ()
Duct Air Velocity: 300 ft/min to 4000 ft/min
Color Ivory
Material ABS Blend
(1.5 m/s to 20.4 m/s)
Environmental Conditions
Relative Humidity Up to 85 %, non‑condensing
Operating Temperature +32°F to +120°F (0°C to +49°C)
Sensitivity Range 0.88 %/ft to 2.75 %/ft (2.9%/m to
9%/m) obscuration (nine threshold levels are selectable)
Ordering information
FAD-325-DH Analog Duct Smoke Detector Replacement Head
Two‑wire replacement detector for the FAD‑325 and FAD‑325‑R duct housings has adjustable threshold smoke level and automatic compensation values. It has EEPROM addressing with the D5070, two polling and detector status LEDs for 360º view, and easy removal for cleaning and servicing.
Order number FAD-325-DH