Bosch FAA-440-B4-ISO, FPE-1000-SLC, FPE-1000-NW, FPE-1000-NF, FPE-1000-NE Quick Selection Guide

...
Quick Selection Guide
FPA-1000-V2 Network Fire Panel
Analog Fire Detector 440 Series
instant access to important system functions,
device, streamlining installation and reducing
Processing (ISP), which uses a sophisticated,
not detected, a trouble message is generated
Analog Addressable Fire Systems
Intelligent detection. Superior protection.A focused direction in fire protection
With features that enable easier programming, installation and system management, the new FPA-1000-V2 offers a wealth of benefits for both installers and end users.
Plug-and-play installation
Networking module mounts to the panel slot, requiring less wiring and no need for separate power and supervision.
Remote programming & diagnostics
A set of interactive Web pages provide
such as status, programming, diagnostic tools and test data. This unique feature enables programming and diagnostic cababilities using any browser-enabled
time required for servicing the system.
IP-based reporting
Built-in Bosch Conettix IP technology communicates over local or wide area networks for faster alarm reporting and reduced costs.
Integrated gas detection
The first combination panel listed for both fire and carbon monoxide (CO) alarm. Complies with new CO regulation requiring this hazardous gas be monitored and reported.
Enhanced safety and efficiency
Extra-large buttons allow operation of the keypad control while wearing protective gloves.
More points, more protection
Networking capbilities support more than 2000 addressable points in one system for campuses or other large commercial environments. All connected panels can easily be programmed and controlled via any panel.
Suited to a wide range of applications
The FPA-1000-V2 Panel now offers networking capabilities to support a wide variety of medium to large applications:
Retail - single-building applications Schools and Universities Apartment Buildings Manufacturing plants Warehouses Office Complexes Military Bases Government Installations Healthcare Facilities
The Automatic Fire Detector 440 Series is an innovative addition to Bosch’s expanding fire systems portfolio. These advanced analog addressable detectors feature Dual Ray Technology and Intelligent Signal Processing — setting the standard for reliable fire detection and false alarm prevention.
Multicriteria and multisensor fire detection
Multicriteria detectors better distinguish between fire and non-fire conditions to reduce false alarms in areas with challenging environmental conditions. The analog addressable 440 Series gives you a choice of heat, optical smoke, or a combination of optical smoke and heat.
And, our most advanced model represents a step forward for the fire detection industry — a multicriteria detector that identifies the presence of smoke, heat and carbon monoxide (CO) for maximum reliability.
Intelligent Signal Processing
Each detector features Intelligent Signal
high speed microprocessor to analyze signals from each sensor. A complex algorithm ensures the sensor pattern matches that of a real fire scenario to provide immunity against possible false alarm triggers.
This advanced technology significantly reduces false alarm rates and provides more accurate fire detection, while also achieving faster recognition of different types of fires.
Reliable, affordable performance
The 440 series features a unique self­monitoring feature. If sensor functionality is
and reported back to the panel. This helps ensure each area of your facility is always being monitored. In addition, a triple-color LED indicates status, including normal, trouble or alarm.
Detect even the smallest particles
The new dual-optical variants in the 440 Series use Bosch's Dual Ray Technology for even greater precision. Dual Ray Technology determines smoke density and particle size by comparing the intensity of scattered light from the differing wavelengths of two LED sources, one infrared and one blue.
Bosch's powerful fire-detection algorithm provides exceptional differentiation between smoke particles and other particles — like dust and steam — that can cause a false alarm in other detectors. As a result, the Dual Ray detectors provide earlier, more reliable fire detection and produce fewer false alarms.
Photoelectric Heat MultiSensor MultiCriteria Dual-Photoelectric MultiSensor MultiCriteria Base Type Standard Isolator
Single Single Single Dual Dual Dual Indictor LED § No Multicolor
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
6-inch
Adjustable
135° F
135° F
135° F
135° F
Programmable
SLC Loop SLC Loop SLC Loop SLC Loop SLC Loop SLC Loop SLC Loop
1 to 254 1 to 254 1 to 254 1 to 254 1 to 254 1 to 254 1 to 254
Rotary Switch Rotary Switch Rotary Switch Rotary Switch Rotary Switch Rotary Switch Rotary Switch
6 mA 6 mA 6 mA 6 mA 6 mA 6 mA 6 mA
0.17 mA 0.17 mA 0.17 mA 0.17 mA 0.17 mA 0.17 mA 0.17 mA
24 - 41 VDC 24 - 41 VDC 24 - 41 VDC 24 - 41 VDC 24 - 41 VDC 24 - 41 VDC 24 - 41 VDC
50 Ω 50 Ω 50 Ω 50 Ω 50 Ω 50 Ω 50 Ω
18 AWG 4000 ft (1200 m) 4000 ft (1200 m) 4000 ft (1200 m) 4000 ft (1200 m) 4000 ft (1200 m) 4000 ft (1200 m) 4000 ft (1200 m)
18 AWG 6225 ft (1900 m) 6225 ft (1900 m) 6225 ft (1900 m) 6225 ft (1900 m) 6225 ft (1900 m) 6225 ft (1900 m) 6225 ft (1900 m)
14 AWG 7200 ft (2200 m) 7200 ft (2200 m) 7200 ft (2200 m) 7200 ft (2200 m) 7200 ft (2200 m) 7200 ft (2200 m) 7200 ft (2200 m)
12 AWG
4000 ft (1200 m)
4000 ft (1200 m)
4000 ft (1200 m)
4000 ft (1200 m)
4000 ft (1200 m)
4000 ft (1200 m)
4000 ft (1200 m)
Remote
< 10 ft (3m) from
< 10 ft (3m) from
< 10 ft (3m) from
< 10 ft (3m) from
< 10 ft (3m) from
< 10 ft (3m) from
< 10 ft (3m) from
IP 42 IP 42 IP 42 IP 42 IP 42 IP 42 IP 42
< 95% < 95% < 95% < 95% < 95% < 95% < 95%
32° to 100° F **
32° to 100° F **
32° to 100° F **
32° to 100° F **
32° to 100° F **
32° to 100° F **
32° to 100° F **
CYCOLOY / ABS CYCOLOY / ABS CYCOLOY / ABS CYCOLOY / ABS CYCOLOY / ABS CYCOLOY / ABS CYCOLOY / ABS
4000 ft/min
4000 ft/min
4000 ft/min
4000 ft/min
4000 ft/min
4000 ft/min
4000 ft/min
Multicolor Multicolor Multicolor Multicolor Multicolor Multicolor Multicolor
4.4 x 2.0 in.
4.4 x 2.0 in.
4.4 x 2.0 in.
4.4 x 2.0 in.
4.4 x 2.0 in.
4.4 x 2.0 in.
4.4 x 2.0 in.
Thermal sensor
Method
Range
Rate-of-Rise
Smoke Sensitvity
Quick Selection Guide
Detector Type
Addressing
6.6 x 0.94 in.
5.3 x 0.94 in.
5.3 x 0.94 in.
4-inch
Max. Line resistance
Current Draw -
Environmental
Mechanical
Protection category
Housing
Operating
Analog Addressable Fire Systems
Series 440
Sensor
Electrical
Optical Sensor
Chemical (CO gas)
Heat Sensitivity
Communication
Current Draw - Alarm
Operating voltage
Wiring
Indicator
Relative Humidity
Temperature
FAP-440 FAH-440 FAP-440-T FAP-440-TC FAP-440-D FAP-440-DT FAP-440-DTC
1.25 to 3.5 %/ft
base
(0° to 38° C)
135° to 194° F (57° to 90° C)
base
(0° to 38° C)
1.25 to 3.5 %/ft
(57° C)
base
(0° to 38° C)
1.25 to 3.5 %/ft
(57° C)
base
(0° to 38° C)
1.25 to 3.5 %/ft
base
(0° to 38° C)
1.25 to 3.5 %/ft
(57° C)
base
(0° to 38° C)
1.25 to 3.5 %/ft
(57° C)
base
(0° to 38° C)
(base only)
(base only)
FAA-440-B4 FAA-440-B6
(13.5 x 2.4 cm)
(16.8 x 2.4 cm)
FAA-440-B4 ISO FAA-440-B6 ISO
(13.5 x 2.4 cm)
Max. Airflow
Indictor LED
Dimensions
(20 m/s)
(11.2 x 5.1 cm)
** FAH-440: If the sensitivity temperature is programmed within a range of +175°F to +249°F (+79.4°C to +120.6°C), the maximum installation temperature is +150°F (+66°C)
(20 m/s)
(11.2 x 5.1 cm)
(20 m/s)
(11.2 x 5.1 cm)
(20 m/s)
(11.2 x 5.1 cm)
(20 m/s)
(11.2 x 5.1 cm)
(20 m/s)
(11.2 x 5.1 cm)
(20 m/s)
(11.2 x 5.1 cm)